1 D85DH EN Installation Instructions Photoelectric Duct Smoke Detector
2 D85DH Installation Instructions.0 Introduction FCC Notice The D85DH Photoelectric Duct Smoke Detector complies with Part 5 of the Federal Communication Commission (FCC) Rules. Operation is subject to the following conditions: The detector might not cause harmful interference. The detector must accept any interference received, including interference that can cause undesirable operation. Changes or modifications not expressly approved by Bosch can void the user s authority to operate the D85DH detector..0 Introduction The D85DH is a UL Listed detector designed for use with commercial fire protective signaling systems and household fire warning systems. Refer to the National Fire Alarm Code (NFPA 7). When properly installed using the D85 Series Dectectors, tamper protection is provided by the positive power line in/out wiring. This causes the control to initiate a trouble signal when a detector is removed from its base. The master control provides two-wire system supervision. An end-of-line (EOL) resistor, specified by the control manufacturer, provides four-wire supervision..0 Specifications Table : Description Operating Temperature Voltage and Current Power-up Time Compatible Control Panels Specifications Only requires a base. B is the UL compatibility identifier. Refer to the Two-Wire Smoke Detector Compatibility Technical Service Note (P/N: 3866) to determine the identifier used with the D340 Series Duct Housing. +3 F to +00 F (0 C to +38 C) 0 to 95% relative humidity (non-condensing) Refer to the D340 Duct Detector Installation Instructions (P/N: 4888) and the D34/D34 Duct Detector Installation Instructions (P/N: 4896) for voltage and current. sec maximum Two-wire: Refer to the Two-Wire Smoke Detector Compatibility Technical Service Note (P/N: 3866). Note: Bosch makes no claim written, oral, or implied the D85DH works with any two-wire control panels except those specified in the Two-Wire Smoke Detector Compatibility Technical Service Note (P/N: 3866). Four-wire: Compatible with all UL Listed four-wire control panels. Refer to the manufacturer's installation instructions for proper EOL resistor selection.
3 D85DH Installation Instructions 3.0 Mounting 3.0 Mounting. Before mounting, remove the dust cover from the detector.. Mount the duct housing according to the manufacturer s instructions. 3. Mount the detector on the base by turning it clockwise until it clicks into place (Figure ). Figure : Mounting the Base + R - Base contacts (three sets) - Start the detector contacts at these three places and rotate the base clockwise When the system is free of alarms, check each detector to ensure the red LED head indicator flashes approximately every 4 sec. This verifies the detector is receiving power and operating properly. 4. Test each detector to ensure it will cause a control panel alarm. This is the only way to ensure proper operation. Alarm the detector in on of the following methods: a. If the duct housing cover is in position, place a magnet horizontally against the recess in the cover to activate an internal reed switch. b. With duct housing cover removed, use a UL Listed aerosol smoke detector tester, such as the Home Safeguard Industries 5S to simulate an alarm. Follow the aerosol smoke detector tester manufacturer s instructions. When a detector alarms, the red LED head indicator activates and latches in the ON position. Clear the alarm before proceeding to the next detector. 5. Check the overall alarm loop loading by measuring the voltage across each EOL resistor. The voltage should equal or exceed the minimum specified by the control panel s manufacturer. The D85DH is keyed. Do not force a detector onto its base. 4.0 Testing. Check the wiring from the control panel to the last head on each run for proper polarity and continuity. Ensure each run terminates with an EOL resistor as specified by the control panel manufacturer.. Apply power to the system. Check for alarms and troubles. a. Note which detectors are in alarm (if any) and shut down the system. b. Remove these detectors from their bases and recheck the bases for proper wiring. If the problems persist, replace the affected detectors or swap them with known good units. This determines if the problem is caused by the detector or the base. c. In a system alarm with no detector alarms, remove all detectors and check the wiring at each base. Pay close attention to the wiring of each EOL resistor. 3
4 D85DH Installation Instructions 5.0 Maintenance 5.0 Maintenance Notify all concerned parties before any fire alarm system maintenance or testing and again after test completion. At least once a year clean the detector and base using a vacuum or clean/dry compressed air paying particular attention to the screens. In dusty areas or areas of heavy insect concentration, cleaning might be required more often. To clean the detectors:. Remove the duct housing cover.. Remove the detector from its base. 3. Clean both the base and cover with a clean cloth and common window cleaner. 4. Remove the detector s cover. Use a thin, flathead screwdriver to pry the chassis from the cover. Then insert the screwdriver into the cover slots and pry up (refer to Item in Figure ). 5. Gently pry the cover tab away from the chamber cover. Then pull the chamber cover up and away from the chamber (refer to Item in Figure 3). Figure 3: Removing the Detector Chamber Cover # Figure : 3 Removing the Detector s Cover # 6. Remove dust and debris from the chassis area using clean, dry compressed air or a vacuum. 7. Replace the chamber to ensure the hole for the LED is properly aligned over the LED. Align by placing the chamber parallel to the chassis and gently snapping the locking tabs into place. 8. Replace the detector s cover carefully lining up the holes for the LED and thermistor. 9. Return the detector to its base. 0. Place duct housing cover on the detector. After cleaning, test the detector for proper calibration using one of the tests described in Section 6.0 Periodic Tests on page 5. - Cover slots (3) - Detector chassis 3 - Cover Do not paint the detector. Paint or other foreign matter covering the screen can prohibit or retard smoke from entering the detector. 4
5 D85DH Installation Instructions 6.0 Periodic Testing 6.0 Periodic Testing Calibration is very important in determining the detector s continued operation. Depending on local regulations, the frequency of calibration testing might be required more than once a year. NFPA Standard 7 recommends a calibration test at installation and every other year thereafter. Perform functional testing annually. 6.3 Voltage Measurement Test. Plug a D005 Test Cable (optional) into the calibration voltage pins (Figure 4). Figure 4: Calibration Voltage Pins Notify all concerned parties before any fire alarm system maintenance or testing and again after test completion. To meet NFPA 7 requirements, check calibration using any of the tests described in Section 6. Visual Check through Section 6.3 Voltage Measurement Test. These tests confirm whether or not the detector is within its factory-marked calibration range. 6. Visual Check The D85DH includes the Chamber Check Automatic Trouble Indication, allowing it to automatically indicate if its calibration is out of the factory-listed range. Visually inspecting the D85DH and checking the LED flash rate meets the NFPA guidelines for sensitivity testing. If the calibration is out of range for more than 4 h, the D85DH alarm LED flashes once per second. The LED flashes once every 4 sec when the detector is operating normally. Visually check all detectors before resetting the power. Disconnecting the power erases this indication. If the detector was reset within the last 4 h, or you are unsure of the last reset time, perform the Magnet Test or Voltage Measurement Test to confirm sensitivity. 6. Magnet Test Place a magnet horizontally against the recess in the duct housing cover and observe the LED. If the detector is within the factory-marked calibration range, it goes into alarm and the Alarm LED latches ON. If the detector is too sensitive, the LED on the head flashes six times rapidly (once every / sec). Then the detector goes into alarm. If the detector is not sensitive enough, the LED on the head flashes four times slowly (once every sec). Then the detector goes into alarm. If the detector is not operational, it does not signal an alarm. - Calibration voltage pins. Connect a digital voltmeter to the D005 Test Cable. 3. Connect the meter s negative terminal to the D005 s black wire and connect the meter s positive terminal to the test cable s red wire. The white wire of the D005 is not used. 4. If a D344-RT or D344-RL is installed, use voltage monitor jacks. The voltage measured by the voltmeter equals / the detector s sensitivity (in %/ft obscuration). Multiply the voltage by. The result should be within the factory-marked calibration range that is printed on the label attached to the bottom of the detector. 5. If the detector is outside of the factory marked calibration range, remove it and clean it as described in Section 5.0 Maintenance on page Recheck the calibration voltage measurement. 7. If the detector remains outside the factory-marked calibration range after cleaning, return it to Bosch for re-calibration. 5
6 D85DH Installation Instructions Notes 6
7 D85DH Installation Instructions Notes 7
8 Bosch 30 Perinton Parkway Fairport, NY USA Customer Service: (800) Technical Support: (888) Bosch 4933C
D7050DH. Installation Instructions. Multiplex Photoelectric Duct Smoke Detector
D700DH EN Installation Instructions Multiplex Photoelectric Duct Smoke Detector D700DH Installation Instructions.0 Description Notices These instructions cover the installation of the D700DH Multiplex
More informationRF280THS. Installation Instructions Wireless (RF) Photoelectric Smoke Detectors
RF80THS EN Installation Instructions Wireless (RF) Photoelectric Smoke Detectors RF80THS Installation Instructions Trademarks Trademarks Chamber Check is a registered trademark of Bosch Security Systems
More informationDuct smoke housing, 2-wire D340/D340P
Duct smoke housing, 2-wire D340/D340P en Installation manual Duct smoke housing, 2-wire Notices en 3 1 Notices These instructions cover the installation of the D340 Duct smoke housing and D340P Duct smoke
More informationDuct smoke housings, 4-wire D341/D341P and D342/D342P
Duct smoke housings, 4-wire D341/D341P and D342/D342P en Installation manual Duct smoke housings, 4-wire Notices en 3 1 Notices These instructions cover the installation of the D341/D342 Duct smoke housings
More informationD250A/D253/D261AW/D280A/D290 Series
D0A/D/D6AW/D80A/D90 Series EN Installation Instructions / Smoke/Heat Detector Bases EN. D0A/D/D6AW/D80A/D90 Series Installation Instructions.0 Trademarks M Weatherban is a trademark of M. All rights reserved.
More informationD7052. Installation Instructions Multiplex Dual Input Module
D EN Installation Instructions Multiplex Dual Input Module D Installation Instructions Notices Notices Figure : D Features These instructions cover the installation of the D Multiplex Dual Input Module
More informationD7044. Installation Instructions Multiplex Single Input Module
D EN Installation Instructions Multiplex Single Input Module D Installation Instructions Notices Notices These instructions cover the installation of the D Multiplex Single Input Module in a fire system,
More informationD7053. Installation Instructions Multiplex Input/Output Module
D EN Installation Instructions Multiplex Input/Output Module D Installation Instructions Notices Notices These instructions cover the installation of the D Multiplex Input/Output Module in a fire system
More informationMicrowave/PIR Intrusion Detector with POPIT Interface ZX970
Microwave/PIR Intrusion Detector with POPIT Interface ZX970 Installation Instructions 1.0 Specifications Input Power: 9 to 15 VDC, 6 ma nominal (35 ma with LED on) Zonex Current Draw: 500 ma Standby Power:
More informationD326A/D334A/D339A. Installation Instructions. Point Contact Modules
D326A/D334A/D339A EN Installation Instructions Point Contact Modules D326A/D334A/D339A Installation Instructions 1.0 Description Notice Use these instructions to install the D326A, D334A, and D339A Point
More informationDS7465i. Installation Instructions. Input/Output Module
DS7465i EN Installation Instructions Input/Output Module DS7465i Installation Instructions.0 Introduction EN 2.0 Introduction The DS7465i Input/Output Module operates with compatible multiplex systems.
More informationD296/D297. Installation Instructions Long-Range Beam Smoke Detectors
D96/D97 EN Installation Instructions Long-Range Beam Smoke Detectors D96/D97 Installation Instructions.0 Description FCC Compliance Notice This equipment was tested and complies with the limits for a Class
More informationDS9370-BEL. Installation Instructions TriTech Ceiling Mount PIR/Microwave Intrusion Detector
DS970-BEL EN Installation Instructions TriTech Ceiling Mount PIR/Microwave Intrusion Detector DS970-BEL Installation Instructions.0 Installation Considerations.0 Installation Considerations Not suitable
More informationD343. Installation Instructions. Air Duct Smoke Housing
D E Installation Instructions Air Duct Smoke Housing D Installation Instructions.0 Overview. Trademarks ational Fire Alarm Code is a trademark of the ational Fire Protection Association, Inc. ife Safety
More informationF220-B6PS/M. Installation Guide. Addressable Detector Bases
F220-B6PS/M EN Installation Guide Addressable Detector Bases F220-B6PS/M Installation Guide 1.0 Overview 1.0 Overview These instructions cover the installation of the B6PS/M Addressable Detector Bases
More informationD350RPL INTELLIGENT PHOTOELECTRONIC DUCT SMOKE DETECTOR WITH EXTENDED AIR SPEED RANGE INSTALLATION AND MAINTENANCE INSTRUCTIONS
D350RPL INTELLIGENT PHOTOELECTRONIC DUCT SMOKE WITH EXTENDED AIR SPEED RANGE INSTALLATION AND MAINTENANCE INSTRUCTIONS Before installing detectors, please thoroughly read the NEMA Guide for Proper Use
More informationSILENT KNIGHT. IntelliKnight Smoke Detector Cleaning and Testing Instruction. Equipment Needed. Testing Equipment. Cleaning Equipment
SILENT KNIGHT IntelliKnight Smoke Detector Cleaning and Testing Instruction This document contains information necessary to properly test and clean analog photoelectric and ionization smoke detectors connected
More informationRADION smoke RFSM-A. en Installation Guide
RADION smoke RFSM-A en Installation Guide RADION smoke Table of Contents en 3 Table of contents 1 Introduction 4 1.1 About documentation 4 1.2 Bosch Security Systems, Inc. product manufacturing dates
More informationPAD100-6DB & PAD100-4DB PAD100-PD
Installation Manual Detector Bases: PAD100-6DB & PAD100-4DB PAD100-PD Photoelectric Smoke Detector (ANSI/UL 268 Listed) PAD100-PHD Photoelectric Smoke / Heat Detector Combination (ANSI/UL 268 and ANSI/UL
More informationInstallation Instructions
48/50A2,A3,A4,A5020-060, 48/50P2,P3,P4,P5030-100, 48/50N 75 to 105 Ton Return Smoke Detector Accessory Installation Instructions Part No. CRSMKDET002C00 CONTENTS GENERAL........................................
More informationSingle Doors FIREGUARD Series Use one Master Unit each door or one 2409 Support unit each door. Pairs of Doors
Hinge Edge of Door Hinge Edge of Door Wiring Instructions for the Sargent 0 Series FIREGUARD Combination Door Closer-Holder and Releasing Device with Integral Smoke Detector CAUTION: FAILURE TO INSTALL
More informationE-PDD Duct Smoke Detector Installation Sheet
E-PDD Duct Smoke Installation Sheet E-PDD operation The duct smoke detector's primary purpose is to provide early warning of an impending fire and shut down the HVAC unit in order to prevent smoke from
More informationAddressable NAC Output Module D327A
Installation Instructions Notice Addressable NAC Output Module D327A These instructions cover the installation of the D327A Addressable NAC Output Module in an analog system controlled by a Bosch D8024,
More informationFX-PDD Duct Smoke Detector Installation Sheet
FX-PDD Duct Smoke Detector Installation Sheet Table 2: LEDs LED Power LED Alarm/active LED Off when the detector is in the alarm state. Flashes intermittently when the detector is in the normal state.
More informationWiring Instructions for the 2900 Series FIREGUARD Combination Door Closer-Holder and Releasing Device with Integral Smoke Detector
Wiring Instructions for the 900 Series FIREGUARD Combination Door Closer-Holder and Releasing Device with Integral Smoke Detector CAUTION: FAILURE TO INSTALL OR ADJUST PROPERLY MAY RESULT IN INJURY OR
More information1400 Direct Wire Ionization Smoke Detector
INSTALLATION AND MAINTENANCE INSTRUCTIONS 1400 Direct Wire Ionization Smoke Detector A Division of Pittway 3825 Ohio Avenue, St. Charles, Illinois 60174 1800SENSOR2, FAX: 6303776495 Specifications Diameter:
More informationSK-Duct Air Duct Smoke Detector
INSTALLATION AND MAINTENANCE INSTRUCTIONS I56-3432-001R 12 Clintonville Road Northford, CT 06472 203.484.7161; Fax: 203.484.7118 SK-Duct Air Duct Smoke Detector http://www.silentknight.com Specifications
More informationWiring Instructions (01-09)
CAUTION Wiring Instructions 0--00-0 (0-0) Power Track Series with Single Point Hold-Open Electromechanical Releasing Device with Multi-Point Hold- Open TO PREVENT ELECTRICAL SHOCK AND EQUIPMENT DAMAGE,
More informationNotification Appliance Circuit Module
Notification Appliance Circuit Module D192G en Installation guide Notification Appliance Circuit Module Notices en 3 1 Notices These instructions cover the installation of the D192G Notification Appliance
More information0 A EIS Intrinsically-Safe Plug-in Intelligent Photoelectronic Smoke Detector INSTALLATION AND MAINTENANCE INSTRUCTIONS
INSTALLATION AND MAINTENANCE INSTRUCTIONS 2251EIS Intrinsically-Safe Plug-in Intelligent Photoelectronic Smoke Detector A Division of Pittway 3825 Ohio Avenue, St. Charles, Illinois 60174 1-800-SENSOR2,
More informationCommercial Series TriTech Motion Detector. Reference Guide
Commercial Series riech Motion Detector en Reference Guide Commercial Series riech Motion Detector able of contents en 3 able of contents 1 Safety 4 Introduction 5.1 About documentation 5. Bosch Security
More informationDH100LP Air Duct Smoke Detector with Extended Air Speed Range
INSTALLATION AND MAINTENANCE INSTRUCTIONS DH100LP Air Duct Smoke Detector with Extended Air Speed Range 3825 Ohio Avenue, St. Charles, Illinois 60174 1-800-SENSOR2, FAX: 630-377-6495 The Innovair DH100LP
More informationISC-PDL1-W18G-H. Installation Instructions Professional Series Dual Detector
ISC-PDL1-W18G-H EN Installation Instructions Professional Series Dual Detector 1.0 General Information 1.1 Unlock and remove the cover The ISC-PDL1-W18x Professional Series TriTech Detectors are exceptionally
More informationTS93 EMR WITH SMOKE DETECTOR
TS EMR WITH SMOKE GENERAL DESCRIPTION Each TS EMR series unit contains a door closer, hold open electromagnet and smoke detector. The unit can be used as a single installation or as a series of singles
More informationWiring Instructions. Single Doors 99 Checkmate Series Use one or Master Unit each door or one or Support unit each door
CAUTION Hinge Edge of Door Wiring Instructions Checkmate Series with Single Point Hold-Open Combination Door Closer-Holder and Releasing Device with or without Integral Smoke Detector INSTALLER: LEAVE
More informationFMR Installation Instructions. Addressable Fire System Controller
FMR-7033 EN Installation Instructions Addressable Fire System Controller EN 2 FMR-7033 Installation Instructions Contents Contents Contents...2 1.0 Introduction...3 2.0 Description...3 3.0 Device Mounting...3
More informationDS160/161 Request To Exit PIR sensors Installation Instructions
DS160/161 Request To Exit PIR sensors Installation Instructions 1.0 Description The DS160/161 is a passive-infrared (PIR) detector designed for request to exit (REX) interior applications. It is UL Listed
More informationD2E Duct Smoke Detector
INSTALLATION AND MAINTENANCE INSTRUCTIONS D2E Duct Smoke Detector Specifications Operating Temperature: 20 to 60 C Storage Temperature: 20 to 60 C Humidity: 0% to 93% Relative Humidity Non-condensing Air
More informationDH200PL Intelligent Air Duct Smoke Detector with Extended Air Speed Range
INSTALLATION AND MAINTENANCE INSTRUCTIONS DH200PL Intelligent Air Duct Smoke Detector with Extended Air Speed Range 3825 Ohio Avenue, St. Charles, Illinois 60174 800/736-7672, FAX: 630-377-6495 www.systemsensor.com
More informationDH400 Air Duct Smoke Detector
INSTALLATION AND MAINTENANCE INSTRUCTIONS DH400 Air Duct Smoke Detector Before Installing Please thoroughly read System Sensor s Guide for Proper Use of Smoke Detectors in Duct Applications (I56-473-XX),
More informationInstallation Manual. Detector Bases: PAD100-IB, PAD100-RB & PAD100-SB
- + - + - + 1. Description This document provides instructions for mounting and wiring the Detector Bases PAD100-, PAD100-RB and PAD100-SB. The following detectors are compatible with Detector Bases PAD100-,
More informationDH100ACDCLP Air Duct Smoke Detector with Extended Air Speed Range
INSTALLATION AND MAINTENANCE INSTRUCTIONS Air Duct Smoke Detector with Extended Air Speed Range A Division of Pittway 825 Ohio Avenue, St. Charles, Illinois 60174 1-800-SENSOR2, FAX: 60-77-6495 The Innovair
More information8600 EMR SERIES. INSPK NO Rev.06/ INS NO. GENERAL DESCRIPTION
00 EMR SERIES GENERAL DESCRIPTION Each 00 EMR series unit contains a door closer, hold open electromagnet and smoke detector. The unit can be used as a single installation or as a series of singles powered
More informationD350PL INTELLIGENT PHOTOELECTRONIC DUCT SMOKE DETECTOR WITH EXTENDED AIR SPEED RANGE INSTALLATION AND MAINTENANCE INSTRUCTIONS
D350PL INTELLIGENT PHOTOELECTRONIC DUCT SMOKE WITH EXTENDED AIR SPEED RANGE INSTALLATION AND MAINTENANCE INSTRUCTIONS I56-1975-004R Before installing detectors, please thoroughly read the NEMA Guide for
More informationDH200RPL Intelligent Air Duct Smoke Detector with Extended Air Speed Range
INSTALLATION AND MAINTENANCE INSTRUCTIONS DH200RPL Intelligent Air Duct Smoke Detector with Extended Air Speed Range 3825 Ohio Avenue, St. Charles, Illinois 60174 800/736-7672, FAX: 630-377-6495 Before
More informationINSTALLATION AND MAINTENANCE
INSTALLATION AND MAINTENANCE DH100ACDCIA & DH100ACDCPA Air Duct Smoke Detector Before Installing ULC standard CAN/ULC-S524-M91 Standard For The Installation Of Fire Alarm Systems should be referenced for
More informationDS3MX-E-I. Installation Guide. 3 Zone Mini Control Panel
DS3MX-E-I EN Installation Guide 3 Mini Control Panel DS3MX-E-I Installation Guide 1.0 General Information EN 2 1.0 General Information The DS3MX is a three zone mini control panel, which can be installed
More informationMultiplex Eight Input Remote Modules
Multiplex Eight Input Remote Modules 1.0 Introduction These instructions cover the installation of the D7042/D7042B Eight Input Remote Modules in a fire system supervised by an FPD-7024 Fire Alarm Control
More informationESL 500N Series Smoke Detector Installation Sheet
ESL 500N Series Smoke Detector Installation Sheet Additional features Depending on the model, the smoke may also provide the following features. CleanMe: Enables a CleanMe compatible control panel to receive
More informationTRN100BPT, TRN100BP, and TRN100BPC Air Duct Smoke Detector with Extended Air Speed Range
INSTALLATION AND MAINTENANCE INSTRUCTIONS TRN100BPT, TRN100BP, and TRN100BPC Air Duct Smoke Detector with Extended Air Speed Range 825 Ohio Avenue, St. Charles, Illinois 60174 1-800-SENSOR2, FAX: 60-77-6495
More informationMODEL /4" Conduit. (By others) Terminal Strips Companion unit (without electronics) not shown. Approximate Preload
2900 FIREGUARD Electromechanical Closer-Holder Device Models 12-2960, 9-2960 and 2960 Multipoint Hold Open with Rigid Arms Pull (Hinge) Side Installation Instructions CAUTION: FAILURE TO INSTALL OR ADJUST
More informationCleaning. Owner s Manual. RoboVac 11 SM-A438-V03. For FAQs and more information, please visit:
Cleaning For FAQs and more information, please visit: www.eufylife.com Owner s Manual RoboVac 11 SM-A438-V03 able of Contents 02 Important Safety Instructions 04 About Your RoboVac What's In the Box RoboVac
More informationDNR Duct Smoke Detector
INSTALLATION AND MAINTENANCE INSTRUCTIONS I56-3051-004R DNR Duct Smoke Detector Specifications Operating Temperature: 4 to 158 F ( 20 to 70 C); 32 F to 120 F (0 C to 49 C) with module installed in the
More informationInstallation Manual. Detector Base: PAD100-SPKB
1. Description This document provides instructions for mounting and wiring the detector base PAD100-SPKB. The following detectors are compatible with detector base PAD100-SPKB. PAD100-PD: Photoelectric
More informationDH500 Intelligent Air Duct Smoke Detector Housing
INSTALLATION AND MAINTENANCE INSTRUCTIONS DH500 Intelligent Air Duct Smoke Detector Housing 3825 Ohio Avenue, St. Charles, Illinois 60174 1-800-SENSOR2, FAX: 630-377-6495 www.systemsensor.com Specifications
More informationDH100ACDCI Ionization Air Duct Smoke Detector
INSTALLATION AND MAINTENANCE INSTRUCTIONS Ionization Air Duct Smoke Detector Before Installing Please thoroughly read the System Sensor Guide for Proper Use of Smoke Detectors in Duct Applications (A05-1004),
More informationDH200PL Intelligent Air Duct Smoke Detector with Extended Air Speed Range
INSTALLATION AND MAINTENANCE INSTRUCTIONS DH200PL Intelligent Air Duct Smoke Detector with Extended Air Speed Range 3825 Ohio Avenue, St. Charles, Illinois 60174 800-736/7672, FAX: 630-377-6495 Before
More informationHomeLink Wireless Control System
On EX-V6 model The HomeLink Wireless Control System built into your car can be programmed to operate remotelycontrolled devices around your home, such as garage doors, lighting, or home security systems.
More informationDH100ACDCI Ionization Air Duct Smoke Detector
INSTALLATION AND MAINTENANCE INSTRUCTIONS Ionization Air Duct Smoke Detector Before Installing Please thoroughly read the System Sensor Guide for Proper Use of Smoke Detectors in Duct Applications (A05-1004),
More informationDNR-AUS Duct Smoke Detector
INSTALLATION AND MAINTENANCE INSTRUCTIONS I56-3642-000R DNR-AUS Duct Smoke Detector Specifications Operating Temperature: 20 to 70 C ( 4 to 158 F) 0 C to 49 C (32 F to 120 F) with module installed in the
More informationCommercial Series TriTech+ Motion Detector with Anti-mask
Commercial Series riech+ Motion Detector with ISC-CDL1-WA15G, ISC-CDL1-WA15G-CHI, ISC-CDL1-WA15H, ISC-CDL1-WA15K, ISC-CDL1-WA1G, ISC-CDL1-WA1G-CHI en Reference Guide Commercial Series riech+ Motion Detector
More informationDNRECL Eclipse Duct Smoke Detector
INSTALLATION AND MAINTENANCE INSTRUCTIONS DNRECL Eclipse Duct Smoke Detector 3825 Ohio Avenue, St. Charles, Illinois 60174 1-800-SENSOR2, FAX: 630-377-6495 www.systemsensor.com SPECIFICATIONS Operating
More informationDNR Duct Smoke Detector
INSTALLATION AND MAINTENANCE INSTRUCTIONS I56-3051-007R DNR Duct Smoke Detector Specifications Operating Temperature: 4 to 158 F ( 20 to 70 C); 32 F to 120 F (0 C to 49 C) with module installed in the
More informationADEMCO 4208SNF V-Plex Universal Class A Module INSTALLATION AND SETUP GUIDE
K3179V2 2/11 Rev. A ADEMCO 4208SNF V-Plex Universal Class A Module INSTALLATION AND SETUP GUIDE FEATURES The ADEMCO 4208SNF Universal Class A Module can be used in either of two different applications.
More informationDUCTSD Duct Smoke Detector
INSTALLATION AND MAINTENANCE INSTRUCTIONS 82 Ohio Avenue, St. Charles, Illinois 07-800-SENSOR2, FAX: 0-77-9 Duct Smoke Detector www.systemsensor.com SPECIFICATIONS Operating Temperature: to 8 F ( to 70
More informationD1255RB/D1256RB/D1257RB
D1255RB/D1256RB/D1257RB EN Installation Instructions Fire Keypads and Fire Alarm Annunciator D1255RB/D1256RB/D1257RB Installation Instructions Listings and Approvals Listings and Approvals UL 365 UL 609
More informationPhotobeam 5000 ISC-FPB1-W60QS, ISC-FPB1-W120QS, ISC-FPB1-W200QS. en Installation and Operation Guide
Photobeam 5000 ISC-FPB-W60QS, ISC-FPB-W20QS, ISC-FPB-W200QS en Installation and Operation Guide Photobeam 5000 Table of Contents en 3 Table of contents Introduction 4. About documentation 4.2 Bosch Security
More informationDETECTOR TEST LOG. Detector Identification Information DHX-501 INTELLIGENT AIR DUCT SMOKE DETECTOR HOUSING INSTALLATION AND MAINTENANCE INSTRUCTIONS
TEST LOG Detector Identification Information Manufacturer and Serial Date Detector Model: Number: Installed: Description of Detector Location: Test Results and Maintenance Data Date Test Test Maintenance
More informationNetworX NX-548E Receiver Installation Instructions
NetworX NX-548E Receiver Installation Instructions Content Introduction... 1 Internal mounting... 1 External mounting... 2 Wiring... 3 DIP switch settings... 3 Power up... 3 Programming... 4 Testing and
More informationDS160/DS161 Request To Exit PIR sensors Installation Instructions
DS160/DS161 Request To Exit PIR sensors Installation Instructions 1.0 Description The DS160 is a Passive Infrared Detector (PIR) which is UL Listed as an Access Control Device under the UL 294 Standard.
More information1161/1162 Residential Wireless Detectors
INSTALLATION GUIDE 1161/1162 Residential Wireless Detectors Description The Model 1161 Smoke Detector with Sounder, and 1162 Smoke/Heat Detector with Sounder are residential wireless detectors used with
More informationD8125MUX. Operation and Installation Guide. Multiplex Bus Interface
D8125MUX EN Operation and Guide Multiplex Bus Interface EN 2 D8125MUX Operation and Guide Contents Contents Contents...2 1.0 Introduction...3 1.1 Description...3 1.2 Programming...3 1.3 Listings...3 2.0
More informationIDP-Zone-6 Six Zone Interface Module
INSTALLATION AND MAINTENANCE INSTRUCTIONS IDP-Zone-6 Six Zone Interface Module BEFORE INSTALLING If the modules will be installed in an existing operational system, inform the operator and local authority
More informationDH500ACDC Intelligent Air Duct Smoke Detector Housing
INSTALLATION AND MAINTENANCE INSTRUCTIONS DH500ACDC Intelligent Air Duct Smoke Detector Housing 3825 Ohio Avenue St. Charles, Illinois 60174 1-800-SENSOR2, FAX: 630-377-6495 Specifications Length: 14.5
More informationCONTENTS CONTROLS 3-STAGE AIR PURIFICATION. X This product is suitable for 120V only. User Manual. Odor sensor. ➌ PlasmaWave
User Manual CONTENTS 3-Stage Air Purification Controls 3 4 Where to use Installing the s 5 6 Set Up WINIX AIR CLEANER Safety Instructions Safety and Cautions 8 Operation Initial Operation Modes of Operation
More information, -9686, -9688, -9755, Duct Detector/Sensor Installation Instructions
574-776 Rev. C 4098-9685, -9686, -9688, -9755, -9756 Duct Detector/Sensor Installation Instructions Blank Page Cautions and Warnings DO NOT INSTALL ANY SIMPLEX PRODUCT THAT APPEARS DAMAGED. Upon unpacking
More informationOPTICAL SMOKE DETECTOR Model: SPD-KADET
OPTICAL SMOKE DETECTOR Model: SPD-KADET USER S MANUAL "ARTAR-PLUS" company 6 Prutska street Chernivtsi 58008 Ukraine EN 54-7 For further information please contact us: +38 0372 584373 www.artarplus.com.ua
More information7251DH Intelligent Air Duct Smoke Detector
INSTALLATION AND MAINTENANCE INSTRUCTIONS 7251DH Intelligent Air Duct Smoke Detector Specifications Length: Width: Depth: Weight: Operating Temperature Range: Operating Humidity Range: Duct Air Velocity:
More informationSC-6 Six Supervised Control Module
INSTALLATION AND MAINTENANCE INSTRUCTIONS SC-6 Six Supervised Control Module SPECIFICATIONS Normal Operating Voltage: Stand-By Current: Alarm Current: Temperature Range: Humidity: Dimensions: Accessories:
More informationPHOTOELECTRONIC SMOKE DETECTOR
PHOTOELECTRONIC SMOKE DETECTOR WITH BUILT-IN WIRELESS TRANSMITTER Installation and Operation Manual 3126052 Model # SD4-MC(US) 418 MHZ TRANSMITTER Document # 108137 General Information Before installing
More information1161/1162 Residential Wireless Detectors
INSTALLATION GUIDE 1161/1162 Residential Wireless Detectors Description The Model 1161 Smoke Detector with Sounder, and 1162 Smoke/Heat Detector with Sounder are residential, photo electric wireless detectors
More informationDNRHS Intelligent Air Duct Smoke Detector
INSTALLATION AND MAINTENANCE INSTRUCTIONS DNRHS Intelligent Air Duct Smoke Detector Specifications Length: Width: Depth: Weight: Operating Temperature Range: Operating Humidity Range: Duct Air Velocity:
More informationRCR-REX Request-to-Exit Dual Technology Motion Sensor Installation Guide
RCR-REX Request-to-Exit Dual Technology Motion Sensor Installation Guide Introduction This is the Interlogix RCR-REX Request-to-Exit Dual Technology Motion Sensor Installation Instructions for models RCR-REX-W,
More informationConventional Smoke Detectors KFAPO
Kingfisher Company, inc. Conventional Smoke Detectors KFAPO Features: Wide operating voltage, 9-33 VDC Advanced electronic technology Flashing LED Magnetic test switch Proven detection performance Designed
More informationWireless DESCRIPTION. sentrol U L
sentrol Wireless DESCRIPTION The Sentrol 4300 Series smoke detector requires a Sentrol 4000 RF gateway receiver with Rev J or higher software and a compatible control panel sold separately. To install
More information1125 PIR Motion Detector
Tamper Survey LED INSTALLATION SHEET 1125 PIR Motion Detector Description The 1125 PIR (Passive Infrared) Motion Detector is a wireless, low current sensor for use with the 1100D Wireless Receiver. Using
More informationPRODUCT DIAGRAM PACKAGE CONTENTS
PRODUCT DIAGRAM PACKAGE CONTENTS After receiving the product, please inventory the contents to ensure you have all the proper parts, as listed below. If anything is missing or damaged, please contact Monoprice
More informationIndependent Zone Control (I.Z.C.)
Operation and Installation Guide Independent Zone Control (I.Z.C.) DELAYED INSTANT ARMED 1 2 3 4 7 5 6 8 9 * * fi Radionics R D279A Operation & Installation Guide 46456B Page 2 Copyright 2000 Radionics
More informationSIGA-CC1 Single Input Signal Module Installation Sheet
SIGA-CC1 Single Input Signal Module Installation Sheet Personality codes Use the personality codes described below to configure the SIGA-CC1 module. See Table 1 for listing information Table 1: Personality
More informationDT8050A DUAL TEC Motion Sensor with Anti-Mask - Installation Instructions
DT8050A DUAL TEC Motion Sensor with Anti-Mask - Installation Instructions QUICK LINKS Mounting Location Guidelines Open the Sensor Mount the Sensor Sensor Components and Settings Wire the Sensor Wiring
More informationPhotobeam 5000 ISC-FPB1-W60QF, ISC-FPB1-W120QF, ISC-FPB1-W200QF. en Installation and Operation Guide
Photobeam 5000 ISC-FPB-W60QF, ISC-FPB-W0QF, ISC-FPB-W00QF en Installation and Operation Guide Photobeam 5000 Table of Contents en 3 Table of contents Introduction 4. About documentation 4. Bosch Security
More informationInstallation Instructions
Request-to-Exit Dual Technology Motion Sensor 1048889B November 2005 Copyright 2005, GE Security Inc. Introduction This is the GE Request-to-Exit Dual Technology Motion Sensor for models -W, -B, and -G.
More informationMMF Six Zone Interface Module
Installation and Maintenance Instructions I56-900-005 MMF-0-6 Six Zone Interface Module SPECIFICATIONS Normal Operating Voltage: 5- VDC Stand-By Current: ma Alarm Current: 40 ma (assumes all six LEDs solid
More informationInstallation Instructions Model DLC
Installation Instructions Model DLC Device Loop Card INTRODUCTION OPERATION The SIEMENS Model DLC Device Loop Card is the interface for connection of FireFinder-XLS smoke detectors, manual stations, monitor
More informationIFT-RC150 IntelliFire Touch Remote Control Installation Instructions
IFT-RC150 IntelliFire Touch Remote Control Installation Instructions Leave this manual with party responsible for use and operation. 1. Introduction The IFT-RC150 is a wall mounted device that is designed
More informationSF812 SMOKE DETECTOR. Include to or Exclude from a Z-Wave TM Network. Product Overview
SF812 SMOKE DETECTOR The photoelectric Smoke Detector is a Z-Wave TM enabled device which is fully compatible with any Z-Wave TM enabled network. Z-Wave TM enabled devices displaying the Z-Wave TM logo
More informationModel 17A00 Expansion Enclosure
HOME AUTOMATION, INC. Model 17A00 Expansion Enclosure Installation Manual Document Number 17I00-1 Rev A March, 2002 Home Automation, Inc. Model 17A00 Expansion Enclosure Installation Manual Document Number
More information1 Description. 2 Specifications. HP600ULM Access Control Power Supply/Charger with Power Distribution Controller PN 52393:A 1/05/06 ECN
Honeywell 12 Clintonville Road Northford, CT 06472 http://www.honeywellpower.com HP600ULM Access Control Power Supply/Charger with Power Distribution Controller PN 52393:A 1/05/06 ECN 04-350 Product Installation
More informationMO144. Operators Guide. Universal Timer Module
EN Operators Guide Universal Timer Module Operators Guide Notices EN Copyright Notice Unless otherwise indicated, this publication is the copyright of Bosch Security Systems, Inc. ( Bosch ). All rights
More informationMODEL 5800A CARBON MONOXIDE (CO) MONITOR AND ALARM SAMPLE-DRAWING TYPE
MODEL 5800A CARBON MONOXIDE (CO) MONITOR AND ALARM SAMPLE-DRAWING TYPE 11//07 A153-021500-1 INSTRUCTION MANUAL - MODEL 5800A CO ALARM I INTRODUCTION This MST Model 5800A Carbon Monoxide (CO) Alarm is a
More information