INSTALLATION INSTRUCTION
|
|
- Britney Sherman
- 5 years ago
- Views:
Transcription
1 INSTALLATION INSTRUCTION I - Ship ping and Pack ing List Pack age 1 of 1 con tains: INSTALLATION INSTRUCTIONS FOR ECONOMIZER USED WITH (B4,B5)SM 090/120 SERIES AIR HANDLER OUTDOOR FRESH AIR FORM # 572D Economizer As sem bly 1 - Con trols and Wir ing Har ness As sem bly 3 - Wire Nuts 14 - #10 x ½ Check contents for shipping damage. Contact the last carrier immediately if any shipping damage is found. II - Ap pli ca tion Economizers are used with Nordyne (B4,B5)SM Series Air Handlers for automatic sensor-controlled introduction of outdoor air into the system through an electro-mechanically controlled damper. Outdoor air is mixed with the buildings return air to economically improve indoor air quality and aide in reducing energy costs. Economizers can be utilized in either Horizontal or Vertical air handler applications and are easily mounted over the air handler return air and filter frame assembly, The C-7150 Mixed Air Sensor is shipped inside the economizer and must be relocated downstream of the air handler refrigerant coil in accordance with these instructions. Economizer Sup ply / Re turn Duct Con nec tions: INDOOR RETURN AIR INLET ENTHALPY SENSOR 39.75" Wide x 15.63" High (Outside Flange Dimensions) Warning: This kit is to be installed by a qualified service technician in accordance with these instructions and all codes having jurisdiction. Failure to follow these instructions could result in serious injury, property damage, or death. These instructions are primarily intended to assist qualified individuals experienced in the proper installation of this appliance. Some local codes require licensed installation/service personnel for this type of equipment. III - In stal la tion 1. DISCONNECT ALL POWER TO THE UNIT. 2. Install and secure the economizer as shown with the air handler in the Horizontal position (Figure 1) or in the Vertical position (Figure 2) using screws (12) provided in the kit. NOTE: Economizers must be properly supported when installed with this air handler. Support for the economizer is field supplied and the responsibility of the installer to use methods approved by State or Local mechanical building codes having jurisdiction. For Vertical installations, Nordyne Adjustable Support Leg Kit, SKU # may be used. 3. Connect ductwork to the economizer using flanges provided. DRIVE MOTOR W7212 LOGIC MODULE ELECTRICAL KNOCKOUTS Fig ure 1 - (B4,B5)SM Horizontal Application 1
2 INSTALLATION INSTRUCTION 4 Remove the economizer control access panel, the air handler motor access panel, and the air handler control panel cover. 5 Remove the electrical knockout on the economizer next to the damper motor and the plastic plug on the air handler panel above the control panel, This will allow routing of the economizer control wiring through a length of 1" conduit, or other equivalent means of wire protection based on State or Local codes which covers 24V Class 2 wiring. 6 Cut and discard wire tie securing control wiring bundle inside the economizer. Remove the two red wires from the C-7150 Mixed Air Sensor and mount the sensor to the divider plate located left of the blower motor assembly as shown in Figure 3 using two screws provided. Important - DO NOT cut other wires. Inspect bundle for damaged connections or loose wires. 7. Route the nine economizer control wires from the economizer quick connect plug through the conduit and into the air handler compartment. Route all wires except for the two red Mixed Air Sensor wires into the control panel through the Low Voltage bushing. 8. Connect the two red wires to the Mixed Air Sensor and secure wires away from the blower and motor components. 9. Nordyne air handlers are designed to work with either A/C or Heat Pump outdoor units. Select the proper wiring diagram for this application on Page 5 and 6 to connect the remaining seven economizer control wires to the air handler. Replace air handler control panel cover and motor access panel. IV - Op er a tion Note: These instructions are written for the economizer to operate with a standard single stage Heat/Cool or Heat Pump thermostat. If 2nd stage mechanical (compressor) cooling is desired a 2 Stage Cool / 1 Stage Heat thermostat is required. A. Cooling Mode, Sequence of Operation (Standard) 1. On a call for cooling, with ambient temperature and humidity above enthalpy control setpoint, the refrigerant system will operate normally, and damper will open to minimum vent position. See Section VI for proper set up and adjustments. 2. On a call for cooling, with outdoor ambient temperature and humidity suitable for cooling, enthalpy control will shift stage one cooling control to outside air. The economizer damper will modulate, mixing outside air with return air, to control supply air temperature to approximately 55 F (13 C). If additional cooling is required, the compressor can be energized through second stage of an optional two stage Cooling thermostat. Refer to wiring diagrams for proper connections. INSTALLATION INSTRUCTIONS FOR ECONOMIZER USED WITH (B4,B5)SM 090/120 SERIES AIR HANDLER ELECTRICAL KNOCKOUTS MOTOR ACCESS PANEL Fig ure 2 - (B4,B5)SM Vertical Application* CONTROL PANEL MIXED AIR SENSOR Fig ure 3 - Mixed Air Sensor Location * Air handler shipped from factory for horizontal application. See air handler installation instructions for conversion from horizontal to vertical application. 2
3 INSTALLATION INSTRUCTION INSTALLATION INSTRUCTIONS FOR ECONOMIZER USED WITH (B4,B5)SM 090/120 SERIES AIR HANDLER Figure 4 B. Cool ing Mode, Sin gle Enthalpy Con trol (Factory Standard) The C7400A enthalpy control senses both temperature and humidity or the heat content of the outside air. It controls the amount of outdoor air brought into the system. When the heat content of the outside air is below control setpoint, the control modulates outdoor dampers to meet cooling needs of the building. When the heat content rises above control setpoint, the control closes outdoor dampers to minimum position. The recommended setpoint is A. If Economizer is allowing air which is too warm or too humid to enter the system, control may be changed to a lower setpoint (B, C, or D). Refer to Figure 4 and Figure 5. C. Heat ing Mode (Heat Pump Ap pli ca tion ONLY) 1. On a call for heat the fresh air damper will open to the minimum vent position. V - Economizer Set Up Pro ce dures Notice to Installer: Proper operation of this economizer when used with an outdoor HEAT PUMP system is dependent on the type thermostat installed with the unit. Identify which type thermostat is connected to unit before making any wiring changes if needed. Fig ure 5 (B4,B5)SM air handler economizers come equipped with Honeywell W7212 logic modules which offer additional connections for Demand Control Ventilation (DCV) and Power Exhaust. Contact your local Honeywell or Tradeline representative for additional information on these controls and their specific applications 3
4 INSTALLATION INSTRUCTION INSTALLATION INSTRUCTIONS FOR ECONOMIZER USED WITH (B4,B5)SM 090/120 SERIES AIR HANDLER Heat Pump Ther mo stat Sin gle "O/B" ter mi nal for se lec tion of Re vers ing Valve Con trol. (B4,B5)SM Series economizers are pre-wired to work in conjunction with single stage Heat Pump thermostats that utilize the "O" terminal to energize the reversing valve when the thermostat "System Switch" is set in the "Cool" mode. Refer to these installation instructions and wiring diagrams for proper connection and operation of the economizer. When the system switch is in the OFF, HEAT, or EMERGENCY HEAT mode setting the economizer is automatically locked out during heating operation. It holds the outdoor fresh air damper at the minimum position setting only when the air handler is operating. Refer to Section VI Minimum Damper Position for proper set up and operation. VI - SYS TEM CHECK AND START UP PROCEDURES Minimum Damper Position Adjustment. Damper min i mum po si tion keeps the out door air damper from clos ing com pletely dur ing sys tem op er a tion for ven ti la tion of build ing con tam i nants and peo ple oc cu pancy. Con sult your State or lo cal codes as required. 1. Disconnect main power to outdoor unit and air handler. 2. Set thermostat "SYSTEM" switch to "OFF" position and "FAN" switch to "AUTO". 3. Install jumper wire across air handler low voltage terminal board "R" and "G" terminal. 4. Disconnect mixed air sensor from the W7212 terminals T and T1 and short terminals T and T1. See Figure Ensure the factory installed jumper is in place across terminals P and P1. 6. Calculate the appropriate mixed air temperature per the following equation: * (Return Air Temp. x % of Return Air) + (Outside Air Temp. x % of Outside Air) = Mixed Air Temperature Example: Assume local code requires 10% outdoor air during occupied conditions, (200 CFM of total unit CFM = 2,000) outdoor air is 60 o F, and return air is 75 o F. Under these conditions, what is the mixed air temperature? (0.1 x 60 o F) + (0.9 x 75 o F) = 6.0 o F o F = 73.5 o F 7. Restore power to the outdoor section and air handler. 8. Carefully adjust the MIN POS potentiometer on the W7212 control module with a small screwdriver until the mixed air temperature reaches the calculated value. 9. Once minimum position adjustments are completed, turn off power to the outdoor unit and air handler. Damper will move to fully close. 10. Remove jumper wire across "R" and "G" on the low voltage terminal board and T and T1 on the W7212 control module. 11. Reconnect the mixed air sensor. 12. Restore power to outdoor unit and air handler. VII - MAIN TE NANCE 1. Damper motor is prelubricated and does not require further lubrication. 2. Make visual inspection of dampers and linkage assemblies during routine maintenance. 3. Filters should be checked periodically and cleaned when necessary. 4. The washable filters supplied with the economizer can be cleaned with water and a mild detergent. 5. Take note of Air Flow Direction marking on filter frame when reinstalling. 6. If filter must be replaced, filter of like kind and size must be used. DO NOT replace permanent filters with throwaway type filters. 4
5 HARNESS DETAIL COMPONENT CODE WIRE COLOR CODE Revision Change Date E# = WIRE END DESIGNATION E2 STUD #6 18 Ga. Wire E3 Female ¼ Quick Disc. E4 Male ¼ Quick Disc. Insul E6 Wire Nut Size 73B Economizer C7400A Fresh Air Enthalpy Sensor C7150 Mixed Air Sensor MS7510A Damper Actuator 24v W7212A Logic Module TB-11 Terminal Block BLK Black BLU Blue BRN Brown GRN Green GRY Gray ORN Orange RED Red VIO Violet YEL Yellow WHT White 1. C & W2 to be connected to optional electric heat. 2. Remove BLACK wire from air handler low voltage terminal board Y terminal and connect to YELLOW wire from economizer. 3. Second Stage refrigerant cooling with optional economizer installed. A 2 stage thermostat is required for simultaneous operation of the economizer and refrigerant system. Connect Y2 from 2 stage thermostat to BLUE wire from economizer. 4. Heat Pump Economizer Relay. For heat pump applications only. Required for proper operation of an economizer (optional) in the heat pump Heating mode. CONNECT TO "R" FOR AC ONLY APPLICATIONS. Modulating Economizer (B4,B5)SM 090/120 Series Air Handler Date: February 4, 2011 Supersedes: Drawn by: Unit #: Diagram#: w Approved by:
6 HARNESS DETAIL COMPONENT CODE WIRE COLOR CODE Revision Change Date E# = WIRE END DESIGNATION E2 STUD #6 18 Ga. Wire E3 Female ¼ Quick Disc. E4 Male ¼ Quick Disc. Insul E6 Wire Nut Size 73B Economizer C7400A Fresh Air Enthalpy Sensor C7150 Mixed Air Sensor MS7510A Damper Actuator 24v W7212A Logic Module TB-11 Terminal Block BLK Black BLU Blue BRN Brown GRN Green ORN Orange RED Red VIO Violet YEL Yellow WHT White 1. Jumper be tween W2 and E is re quired. 2. C & W2 to be con nected to elec tric heat. 3. Re move BLACK wire from air han dler low volt age ter mi nal board Y ter mi nal and con nect to YEL LOW wire from economizer. 4. Sec ond Stage re frig er ant cool ing with op tional economizer in stalled. A 2 stage ther mo stat is re quired for si mul ta neous op er a tion of the economizer and re frig er ant sys tem. Con nect Y2 from 2 stage ther mo stat to BLUE wire from economizer. 5. Heat Pump Economizer Re lay. Re quired for proper op er a tion of an economizer (optional) in the heat pump Heating mode. Refer to economizer installation instruction for proper connection to thermostat. Modulating Economizer (B4,B5)SM 090/120 Series Air Handler Date: February 4, 2011 Supersedes: Drawn by: Unit #: Diagram#: w Approved by:
7 7
8 FEBRUARY 4, 2011 NEIMB01 8
Installation Instructions
2-5 Ton Pack age Unit Low Leak Mod u lat ing Economizer w/ W7220A JADE Con trol Installation Instructions This product is certified to meet California Title 24, Part 6 Low Leak and FDD requirements Horizontal
More information6-10 Ton Pack age Unit Low Leak Mod u lat ing Economizer w/ W7220A JADE Con trol In stal la tion In struc tions
6-10 Ton Pack age Unit Low Leak Mod u lat ing Economizer w/ W7220A JADE Con trol In stal la tion In struc tions This product is certified to meet California Title 24, Part 6 Low Leak and FDD requirements
More informationInstallation Instructions
2-5 Ton Pack age Unit Low Leak Mod u lat ing Economizer w/ W7220A JADE Con trol Installation Instructions This product is certified to meet California Title 24, Part 6 Low Leak and FDD requirements Downflow
More informationCOMMERICAL SPLIT SYSTEM KITS AND ACCESSORIES /2012 Supersedes
COMMERICAL SPLIT SYSTEM KITS AND ACCESSORIES 506956 01 2/2012 Supersedes 506167 01 Litho U.S.A. TAA ECONOMIZERS INSTALLATION INSTRUCTIONS FOR ECONOMIZERS (44W94, 44W95 AND 44W96) USED WITH TAA SERIES UNITS
More informationINSTALLATION INSTRUCTIONS MODELS (-)XRD-01RGHAM3 HORIZONTAL AIRFLOW ECONOMIZERS
INSTALLATION INSTRUCTIONS MODELS (-)XRD-01RGHAM3 HORIZONTAL AIRFLOW ECONOMIZERS WARNING THIS ACCESSORY IS TO BE INSTALLED BY A QUALIFIED, LICENSED SERVICE PERSON. TO AVOID UNSATISFACTORY OPERATION OR DAMAGE
More informationIN STAL LA TION IN STRUC TION
IN STAL LA TION IN STRUC TION SINGLE PACKAGE HEAT PUMPS Su per sedes: 511.06- N5W (1298) (900) MODELS B*CB036 AND 048 (STYLE B) AND MOD ELS B*CB060 (STYLE A ) (10 SEER w/belt-drive Option) (* = C or E)
More informationCompak Unit Coolers. LCA - Air Defrost LCE - Electric Defrost LCH - Hot Gas Defrost. Bulletin LC-03A August 2004 (Replaces LC-03 3/03)
Bulletin LC-03A August 2004 (Replaces LC-03 3/03) Compak Unit Coolers LCA - Air Defrost LCE - Electric Defrost LCH - Hot Gas Defrost 3,500 to 27,000 BTU/H Front access to refrigeration components. Now
More informationINSTALLATION INSTRUCTIONS
The 2SD04700524 Smoke Detector Kit contains the parts and hardware to mount the smoke detector in the following applications: A. B. C. D. WARNING: BEFORE INSTALLING READ ALL OF THE MANUFACTURERS INSTALLATION
More informationINSTALLATION INSTRUCTIONS MODELS RXRD-01MDDAM3 VERTICAL AIRFLOW ECONOMIZERS
! INSTALLATION INSTRUCTIONS MODELS RXRD-01MDDAM3 VERTICAL AIRFLOW ECONOMIZERS THIS ACCESSORY IS TO BE INSTALLED BY A QUALIFIED, LICENSED SERVICE PERSON. TO AVOID UNSATISFACTORY OPERATION OR DAMAGE TO THE
More informationIN STAL LA TION IN STRUC TION
IN STAL LA TION IN STRUC TION SIN GLE PACKAGE CON VERTI BLE SE RIES HEAT PUMPS WITH OR WITHOUT SUP PLE MEN TAL ELEC TRIC HEAT Su per sedes: (693) 511.06- N3W (195) MODELS BACB180 & 40 (8.5-8.8 EER) 035-1545
More informationUnitized Energy Recovery Ventilators for use with Carrier Air Conditioning
Engineering Data Unitized Energy Recovery Ventilators for use with Carrier Air Conditioning Energy recovery COMPONENT certified to the AHRI Air-to-Air Energy Recovery Ventilation Equipment Certification
More informationWiring Diagrams DIAGRAM INDEX
50TFF004-014 Single Package Rooftop Electric Cooling Units Wiring Diagrams DIAGRAM INDEX UNIT LABEL DIAGRAM Unit 50TFF Voltage-Phase-Hertz Type Label Diagram Figure No. 208/230-1-60 Schematic/Component
More informationINSTALLATION INSTRUCTIONS MODELS (-)XRD-01RECAM3, (-)XRD-01RECBM3, (-)XRD-01RCCAM3, & (-)XRD-01RCCBM3 CONVERTIBLE AIRFLOW ECONOMIZERS
WARNING INSTALLATION INSTRUCTIONS MODELS (-)XRD-01RECAM3, (-)XRD-01RECBM3, (-)XRD-01RCCAM3, & (-)XRD-01RCCBM3 CONVERTIBLE AIRFLOW ECONOMIZERS THIS ACCESSORY IS TO BE INSTALLED BY A QUALIFIED, LICENSED
More informationYour safety and the safety of others are very important.
VARIABLE SPEED ELECTRIC FURNACE INSTALLATION INSTRUCTIONS VARIABLE SPEED ELECTRIC FURNACE SAFETY...1 INSTALLATION REQUIREMENTS...2 Tools and Parts...2 Location Requirements...2 Installation Configurations...3
More informationSINGLE-PACKAGE ROOFTOP HEAT PUMP UNITS INDEX. VOLTAGE (3 Ph, 60 Hz) ACCESSORIES
wiring diagrams SINGLE-PACKAGE ROOFTOP HEAT PUMP UNITS Cancels: New 542J Sizes 150, 180 12-1/2 and 15 Tons WD 542J.150.1 7/15/96 UNIT 542J 150 180 LABEL DIAGRAM TYPE Component Arrangement Schematic Component
More informationInstallation Instructions
Installation Instructions B5BV Series Electric Furnaces For HUD approved installations in manufactured homes and modular homes These instructions are intended to assist qualified individuals experienced
More informationInstallation Instructions
Installation Instructions Electric Heater Packages KFAEH -CIRCUIT GROUND LUG TERMINAL BLOCK MULTI-CIRCUIT GROUND LUG COOLING CONTROL PLATE ADAPTER PLATE (MUST BE REMOVED WHEN INSTALLING LARGE HEATER) BLOCK
More informationInstallation in Standard & Variable Speed Indoor Air Handlers IMPORTANT
H6HK Series Electric Heater Kit INSTALLATION INSTRUCTIONS Installation in Standard & Variable Speed Indoor Air Handlers IMPORTANT These instructions are primarily intended to assist qualified individuals
More informationINSTALLATION INSTRUCTIONS
WARNING: BEFORE INSTALLING READ ALL OF THE MANUFACTURERS INSTALLATION AND MAINTENANCE The 2SD04700524 Smoke Detector Kit contains the parts and hardware to mount the smoke detector in the following applications:
More informationFOSSILFUELKITAXWR02FFA1
FSSILFUELKITAXWR02FFA1 FR USE WITH Heat Pump utdoor Sections These instructions must be read and understood completely before attempting installation. SSTEM MATCH INFRMATIN The Fossil Fuel Kit may only
More informationQUICK REFERENCE GUIDE P.C. BOARD/WALL THERMOSTAT FOR 6536A891, 6536B891 & 6536C891 TWO TON PACKAGED HEAT PUMPS
QUICK REFERENCE GUIDE P.C. BOARD/WALL THERMOSTAT FOR 6536A891, 6536B891 & 6536C891 TWO TON PACKAGED HEAT PUMPS Note: This manual may also be used for 6536-871 series heat pumps if the 6535-3209 Replacement
More informationINSTALLATION, OPERATION & MAINTENANCE IN STRUC TIONS OIL-FIRED WATER HEATERS 72E 361E 541E
TO THE INSTALLER: Please attach these in - struc tions next to the water heater. TO THE CONSUMER: Read these and all com po nent in struc - tions. Please keep for fu ture reference. Waranty, registration
More informationVTC / VTH PRODUCT SPECIFICATIONS. ¾ Ton through 2 Tons VERTICAL TERMINAL AIR CONDITIONER AND HEAT PUMP
VTC / VTH VERTICAL TERMINAL AIR CONDITIONER AND HEAT PUMP PRODUCT SPECIFICATIONS No other unit in the industry offers so many extras already built in as standard on every unit. Don t settle for anything
More informationL SERIES UNITS 504,520M. 10/2001 Supersedes 504,413M
Litho U.S.A. 2 L SERIES UNITS 54,52M /2 Supersedes 54,4M M 6 VERSION 4. INTEGRATED MODULAR CONTROL (IMC) GUIDE TO THE M 6 VERSION 4. INTEGRATED MODULAR CONTROL USED IN L SERIES THROUGH TON UNITS TABLE
More informationEnviroZone-4 & EnviroZone-2 Quick-Start Guide
EnviroZone-4 & EnviroZone-2 Quick-Start Guide This guide is intended to give the installer a brief set of instructions about how to set up the FHP EnviroZone System. For more detailed information about
More informationCAUTION WARNING INSTALLATION INSTRUCTIONS FOR HEALTHY CLIMATE WHOLE HOME DEHUMIDIFIER MODEL HCWH-065 (Y3013) DEHUMIDIFIERS
DEHUMIDIFIERS 506451-01 04/2012 HEALTHY CLIMATE WHOLE HOME DEHUMIDIFIER INSTALLATION INSTRUCTIONS FOR HEALTHY CLIMATE WHOLE HOME DEHUMIDIFIER MODEL HCWH-065 (Y3013) FRONT VIEW (with alternate outlet location
More informationInstallation Instructions
Installation Instructions Electric Heater Packages KFAEH TE: Read the entire instruction manual before starting the installation. This symbol indicates a change since the last issue. SINGLE-CIRCUIT GROUND
More informationINSTALLATION INSTRUCTIONS
INSTALLATION INSTRUCTIONS Models EBP EBX EBXX(R -410A) CAUTION Use ONLY factory listed electric heaters. Safety Labeling and Signal Words Danger, Warning and Caution The signal words DANGER, WARNING and
More informationTHE WALL-MOUNT ONE TON AIR CONDITIONER GREEN REFRIGERANT R-410A. 10,800 Btuh 9.00 EER Right Side Control Panel. Engineered Features
THE WALL-MOUNT ONE TON AIR CONDITIONER W2A,800 Btuh 9.00 EER Right Side Control Panel 60Hz GREEN REFRIGERANT R-A The Bard Wall-Mount One Ton Air Conditioner is a self contained energy efficient heating
More informationINSTALLATION INSTRUCTIONS WALL MOUNT ENERGY RECOVERY VENTILATOR WITH EXHAUST
INSTALLATION INSTRUCTIONS WALL MOUNT ENERGY RECOVERY VENTILATOR WITH EXHAUST Models: ERVF-A2 ERVF-C2 For Use With Bard 1-1/2 Through 2 Ton Wall Mount Air Conditioners and Heat Pumps Bard Manufacturing
More informationSERVICE MANUAL FOR 6633 SERIES PACKAGE AIR CONDITIONER
SERVICE MANUAL FOR 6633 SERIES PACKAGE AIR CONDITIONER TABLE OF CONTENTS 1. Warnings...................................................... 3 2. Component Match-Up...........................................
More informationSERVICE MANUAL FOR 6537 & 6538 SERIES TWO TON HIGH EFFICIENCY PACKAGED HEAT PUMPS
SERVICE MANUAL FOR 6537 & 6538 SERIES TWO TON HIGH EFFICIENCY PACKAGED HEAT PUMPS TABLE OF CONTENTS 1. Warnings.................................................................. 2 2. Accessibility Of Appliance....................................................
More informationQUICK REFERENCE GUIDE P.C. BOARD/WALL THERMOSTAT FOR 6535D, 6537C, 6538 A&B SERIES TWO TON PACKAGED HIGH EFFICIENCY HEAT PUMPS
QUICK REFERENCE GUIDE P.C. BOARD/WALL THERMOSTAT FOR 6535D, 6537C, 6538 A&B SERIES TWO TON PACKAGED HIGH EFFICIENCY HEAT PUMPS RV Products A Division of Airxcel, Inc. P.O. Box 4020 Wichita, KS 67204 1-316-832-4357
More informationFIRE PROTECTION SYSTEMS
CHAPTER 9 FIRE PROTECTION SYSTEMS SECTION 901 GENERAL 901.1 Scope. The pro vi sions of this chap ter shall spec ify where fire pro tec tion sys tems are re quired and shall ap ply to the de - sign, in
More informationB SERIES ELECTRIC FURNACE
MISSISSAUGA, ONTARIO L5T 1H9 TEL.: 905-670-2500 FAX: 905-795-8311 CUSTOMER SERVICE TEL.: 1-888-882-7626 B SERIES ELECTRIC FURNACE! WARNING 1. The user MUST contact a specialized contractor when a failure
More informationOIL-FIRED WATER HEATERS 72E 361E 541E
TO THE INSTALLER: Please attach these in - struc tions next to the water heater. TO THE CONSUMER: Read these and all com po nent in struc - tions. Please keep for fu ture reference. Waranty, registration
More informationInstallation Instructions
H6HK Series Installation Instructions Electric Heater Kits Installation in Standard and Variable Speed Indoor Air Handlers IMPORTANT: The instructions included with this heater kit are for installations
More informationINSTALLATION AND MAINTENANCE INSTRUCTIONS EF Electric Furnace
INSTALLATION AND MAINTENANCE INSTRUCTIONS EF Electric Furnace WARNING Improper installation, adjustment, service, or maintenance can cause injury or property damage. Refer to this manual. For assistance
More informationTECHNICAL SUPPORT MANUAL Fan Coils FVM4X B Series
Fan Coils FVM4X B Series DANGER, WARNING, CAUTION, and NOTE The signal words DANGER, WARNING, CAU- TION, and NOTE are used to identify levels of hazard seriousness. The signal word DANGER is only used
More informationBUILD ING DE SIGN FOR COM MER CIAL BUILD INGS
CHAPTER 8 BUILD ING DE SIGN FOR COM MER CIAL BUILD INGS SECTION 801 GEN ERAL 801.1 Scope. The re quire ments con tained in this chap ter are ap pli ca ble to com mer cial build ings, or por tions of com
More informationINSTALLATION INSTRUCTIONS WALL MOUNT ENERGY RECOVERY VENTILATOR WITH EXHAUST
INSTALLATION INSTRUCTIONS WALL MOUNT ENERGY RECOVERY VENTILATOR WITH EXHAUST Models: ERVF-A3 ERVF-C3 For Use With Bard 2-1/2 through 3 Ton Wall Mount Air Conditioners and Heat Pumps Bard Manufacturing
More informationInstallation Instructions
CCLHA Energy Recovery Ventilator Sizes 50 and 200 Installation Instructions TABLE OF CONTENTS PAGE SAFETY CONSIDERATIONS... INTRODUCTION... INSTALLATION CONSIDERATIONS... COMPONENT DESCRIPTIONS... 2 UNIT
More informationInstallation Instructions
Electric Heater Packages Installation Instructions TE: Read the entire instruction manual before starting the installation. SAFETY CONSIDERATIONS Installing and servicing of heating and air conditioning
More informationInstallation Instructions
Installation Instructions Blower Packages For Gas Furnaces KCBBA00TG KCBBA00TG NOTE: Read the entire instruction manual before starting the installation. INTRODUCTION When upgrading a Coleman, Intertherm,
More informationINSTALLATION INSTRUCTIONS
INSTALLATION INSTRUCTIONS T CLASS TPA Series HEAT PUMPS 7.5 TO 10 TONS 506148 01 12/08 Litho U.S.A. RETAIN THESE INSTRUCTIONS FOR FUTURE REFERENCE IMPORTANT The Clean Air Act of 1990 bans the intentional
More informationSERVICE MANUAL FOR 6636A & 6636B SERIES TWO TON HIGH EFFICIENCY PACKAGED AIR CONDITIONERS
SERVICE MANUAL FOR 6636A & 6636B SERIES TWO TON HIGH EFFICIENCY PACKAGED AIR CONDITIONERS TABLE OF CONTENTS 1. Warnings & Component Match-Up............................................ 2 2. Unit Specifications..........................................................
More informationLGB. Control Supplement. Gas fired boiler. Universal Control System. Series 2 Propane gas. Contents
LGB Gas fired boiler Control Supplement LGB-6 to LGB-23 Series 2 Propane gas Universal Control System Contents I. New installation... 2 II. Existing installation... 4 III. Gas piping... 5 IV. Wiring...
More informationINSTALLATION INSTRUCTION
INSTALLATION INSTRUCTION ELECTRIC HEAT S THRU 05 5 THRU Supersedes: (9) (00) 0-5 FOR SINGLE PACKAGE CONDITIONERS THRU TON SINGLE PACKAGE HEAT PUMPS THRU 5 TON GENERAL This instruction contains all the
More informationINSTALLATION INSTRUCTIONS WALL MOUNTED PACKAGE AIR CONDITIONERS WA121
INSTALLATION INSTRUCTIONS WALL MOUNTED PACKAGE AIR CONDITIONERS Model: WA121 Bard Manufacturing Company Bryan, Ohio 43506 Since 1914...Moving ahead just as planned. Manual : 2100-234 G Supersedes: 2100-234
More informationThe information presented in this manual applies to the 27" negative pressure dryer, both electric and gas models.
INTRODUCTION The information presented in this manual applies to the 27" negative pressure dryer, both electric and gas models. No distinction has been made between the gas and electric models as long
More informationTypical Mount Height. Combustion Chamber
! WARNING: This heater must be installed and serviced by trained gas installation and service personnel only! Improper installation, adjustment, alteration, service or maintenance can cause property damage,
More informationINSTALLATION INSTRUCTIONS WALL MOUNT ENERGY RECOVERY VENTILATOR WITH EXHAUST
INSTALLATION INSTRUCTIONS WALL MOUNT ENERGY RECOVERY VENTILATOR WITH EXHAUST Models: WERV-A5 WERV-C5 For Use With Bard 3-1/2 through 5 Ton Wall Mount Air Conditioners and Heat Pumps Bard Manufacturing
More informationINSTALLATION INSTRUCTIONS ENERGY RECOVERY VENTILATOR WITH EXHAUST MODELS: WGERV-A3A WGERV-C3A WGERV-A5A WGERV-C5A WGSERV-A5 WGSERV-C5
INSTALLATION INSTRUCTIONS ENERGY RECOVERY VENTILATOR WITH EXHAUST MODELS: WGERV-A3A WGERV-C3A WGERV-A5A WGERV-C5A WGSERV-A5 WGSERV-C5 Bard Manufacturing Company, Inc. Bryan, Ohio 4356 Since 1914...Moving
More informationG21/GSR21 SERIES UNITS LENNOXOEMPARTS.COM
Service Literature G2 and GSR2 units are condensing furnaces utilizing the pulse combustion process. Initially, combustion takes place in an enclosed chamber. Then, as combus tion products pass through
More informationTHE WALL-MOUNT ONE TON AIR CONDITIONER. Green Refrigerant. 12,000 Btuh EER Right Side Control Panel. Engineered Features
THE WALL-MOUNT ONE TON AIR CONDITIONER W2AAA 2,000 Btuh.00 EER Right Side Control Panel 60Hz Green Refrigerant R-4A The Bard Wall-Mount One Ton Air Conditioner is a self contained energy efficient heating
More informationINSTALLATION INSTRUCTIONS WALL MOUNT ENERGY RECOVERY VENTILATOR WITH EXHAUST
INSTALLATION INSTRUCTIONS WALL MOUNT ENERGY RECOVERY VENTILATOR WITH EXHAUST Models: WERV-A5 WERV-C5 For Use with Bard 3-1/2 Through 5 Ton Wall Mount Air Conditioners and Heat Pumps Bard Manufacturing
More informationOPERATION INSTRUCTIONS ENERGY RECOVERY VENTILATOR WITH EXHAUST. For Use With Bard 2 Through 5 Ton QW*S Series
OPERATION INSTRUCTIONS ENERGY RECOVERY VENTILATOR WITH EXHAUST Models: 90-09 QWSERV with Occupied Air Capabilities For Use With Bard Through Ton QW*S Series Bard Manufacturing Company, Inc. Bryan, Ohio
More informationINSTALLATION INSTRUCTIONS
INSTALLATION INSTRUCTIONS T CLASS TSA Series 6 to 20 Ton AIR CONDITIONERS 6 20 TONS 506147 01 06/11 Supersedes 3/11 Litho U.S.A. RETAIN THESE INSTRUCTIONS FOR FUTURE REFERENCE IMPORTANT The Clean Air Act
More informationINSTALLATION INSTRUCTIONS
INSTALLATION INSTRUCTIONS CMH-28 Compressor Cutout Thermostat Kit For Use with W18HA, W24HA, W30HA and W36HA Wall-Mount Heat Pumps The CMH-28 is a field-installable compressor cutout outdoor thermostat
More informationInstallation Instructions
Electric Heater Packages Installation Instructions NOTE: Read the entire instruction manual before starting the installation. SAFETY CONSIDERATIONS Installing and servicing of heating and air conditioning
More informationINSTALLATION IN STRUC TION
INSTALLATION IN STRUC TION MODELS FCHP090 & 120 50/60 Hz SPLIT-SYSTEM HEAT PUMPS INDOOR UNITS Su per sedes: 515.41- N2W (692) 515.41- N2W (194) 035-11845 GEN ERAL These com pletely as sem bled in door
More informationUSER'S MANUAL/INSTALLATION INSTRUCTIONS
TM USER'S MANUAL/INSTALLATION INSTRUCTIONS P Series Single Package Convertible Air Conditioner Single Package Convertible Air Conditioner IMPORTANT These instructions are primarily intended to assist qualifi
More informationSOLVING PARAFFIN DEPOSITION PROBLEM IN TUBING BY HEATING CABLE APPLICATION
THERMAL SCIENCE: Year 2010, Vol. 14, No. 1, pp. 247-253 247 SOLVING PARAFFIN DEPOSITION PROBLEM IN TUBING BY HEATING CABLE APPLICATION by Du{an S. DANILOVI] *, Vesna D. KAROVI] MARI^I], and Vojin B. ^OKORILO
More informationIMPORTANT CB26UH CBX26UH. Service Literature. CB26UH and CBX26UH Series Table of Contents. Model Number Information... 2
Service Literature Corp. 0527 L10 Revised May 2011 CB26UH and CBX26UH Series Table of Contents CB26UH CBX26UH Model Number Information................... 2 Specifications / Electrical Data................
More informationINSTALLATION INSTRUCTIONS
INSTALLATION INSTRUCTIONS T CLASS TPA Series 7.5 AND 10 TON HEAT PUMPS 7.5 TO 10 TONS 506148 01 10/2011 Supersedes 06/11 Litho U.S.A. RETAIN THESE INSTRUCTIONS FOR FUTURE REFERENCE IMPORTANT The Clean
More informationInstallation Instructions
Installation Instructions EHMA SERIES ELECTRIC HEATERS FOR PAM3 SERIES PACKAGE AIR CONDITIONERS PHM3 SERIES PACKAGE HEAT PUMPS TABLE OF CONTENTS SAFE INSTALLATION REQUIREMENTS... 2 GENERAL INFORMATION...
More informationINSTALLATION INSTRUCTIONS ENERGY RECOVERY VENTILATOR WITH EXHAUST MODELS: WFERV. Bard Manufacturing Company, Inc.
INSTALLATION INSTRUCTIONS ENERGY RECOVERY VENTILATOR WITH EXHAUST MODELS: WFERV Bard Manufacturing Company, Inc. Bryan, Ohio 4356 Since 1914...Moving ahead, just as planned. Manual: 21-495 Supersedes:
More informationINSTALLATION INSTRUCTIONS ENERGY RECOVERY VENTILATOR WITH EXHAUST
INSTALLATION INSTRUCTIONS ENERGY RECOVERY VENTILATOR WITH EXHAUST MODELS: WGERV-A3 WGERV-C3 WGERV-A5 WGERV-C5 BARD MANUFACTURING COMPANY Bryan, Ohio 4356 Since 1914...Moving ahead, just as planned. Manual:
More informationINSTALLATION MANUAL WARNING WARNING MODULAR NON-VARIABLE SPEED AIR HANDLERS MODELS: MA LIST OF SECTIONS LIST OF FIGURES LIST OF TABLES
INSTALLATION NUAL MODULAR NON-VARIABLE SPEED AIR HANDLERS MODELS: GENERAL.............................................. 1 SAFETY................................................ 1 UNIT INSTALLATION.....................................
More informationOPERATION INSTRUCTIONS ENERGY RECOVERY VENTILATOR WITH EXHAUST. For Use With Bard 2 Through 5 Ton QW*S Series
OPERATION INSTRUCTIONS ENERGY RECOVERY VENTILATOR WITH EXHAUST Models: 90-007 QWSERV 90-08 QWSERV with Intelligent Defrost For Use With Bard Through 5 Ton QW*S Series Bard Manufacturing Company, Inc. Bryan,
More informationACCESSORY KIT INSTALLATION INSTRUCTION 2PH0852* SERIES ELECTRIC HEAT ACCESSORIES SPECIFICATIONS
ACCESSORY KIT INSTALLATION INSTRUCTION 2PH0852* SERIES ELECTRIC HEAT ACCESSORIES SPECIFICATIONS For 13 SEER SJ, PAC R-22 Packaged Air Conditioners JP, PHP R-22 Packaged Heat Pumps NM, NL R-410A Packaged
More informationINSTALLATION INSTRUCTIONS
INSTALLATION INSTRUCTIONS Electric Heat Sections Used with Blower Coil Units ELECTRIC HEAT SECTIONS 505,084M (0655012-30) 05/15 Supersedes 09/11 Litho U.S.A. NOTICE TO INSTALLER IT IS HIGHLY RECOMMENDED
More informationFast Track Troubleshooting
Fast Track Troubleshooting Models: DV338*** DV339*** DV407*** DV409*** DV419*** DV438*** DV448*** Display IMPORTANT SAFETY NOTICE For Technicians ly This svice data sheet is intended for use by psons having
More informationINSTALLATION INSTRUCTIONS MASTER CONTROLLERS MC91AE MC92AE MC93AE MC94AE MC94AEH MC96AEH
INSTALLATION INSTRUCTIONS MASTER CONTROLLERS MODELS: MC91AE MC92AE MC93AE MC94AE MC94AEH MC96AEH Bard Manufacturing Company Bryan, Ohio 43506 Since 1914...Moving ahead, just as planned. Manual: 2100-189I
More informationSchneider Electric Erie T155 Series
Schneider Electric Erie T Series Non-Digital, On/Off Thermostat General Instructions Application The T series thermostat provides on/off control for low voltage and line voltage valves, relays and fan
More informationInstallation Instructions
Installation Instructions Electric Heater Packages With DC Relay KFCEH NOTE: Read the entire instruction manual before starting the installation. This symbol indicates a change since the last issue. SINGLE-CIRCUIT
More informationSUNLINE SERIES SINGLE PACKAGE AIR CONDITIONERS. INSTALLATION INSTRUCTION Supersedes: Nothing N3Y (394) MODELS D*SC360 & 480 INSPECTION
SUNLINE SERIES SINGLE PACKAGE AIR CONDITIONERS INSTALLATION INSTRUCTION Supersedes: Nothing 530.25-N3Y (394) MODELS D*SC360 & 480 035-11820 208/230/575 VOLT ONLY 208/230/460 VOLT ONLY GENERAL This instruction
More informationUnited States Patent (19) Dean
United States Patent (19) Dean 54 (76) 21) 22 63 51 52 58) 56) ARVENTTLATION CONTROL SYSTEM Inventor: Arthur C. Dean, 13403 Vimy Ridge Rd., Alexander, Ark. 72002 Appl. No.: 63,429 Filed: Jun. 18, 1987
More informationAG Series Electric Heaters
AG Series Electric Heaters Installation, Operation and Maintenance Instructions Internal Auxililary Electric Heat 97B0005N03 Table of Contents Overview 3 Vertical Upflow Installation 4 Horizontal Installation
More informationINSTALLATION INSTRUCTIONS
INSTALLATION INSTRUCTIONS TEC40 ELECTRONIC CONTROLLER Bard Manufacturing Company, Inc. Bryan, Ohio 43506 www.bardhvac.com Manual: 200-393O Supersedes: 200-393N Date: 2-26-6 Page of 8 CONTENTS Shipping
More informationSM Field Installed Electric Heat Kit
SM Field Installed Electric Heat Kit HK050 HK100 HK150 HK200 Installation Manual 8733822029 (2018/07) US 2 SM Series Electric Heat Installation Manual Data subject to change 07.2018 8733822029 Installation
More informationLGB Gas fired boiler
LGB Gas fired boiler Control Supplement LGB-5 Series 2 Propane gas CSD-1 Control System Part Number 550-110-682/0304 Please read this page first Hazard definitions To the installer... The following terms
More informationSlow drying Thermostat What is temperature set at on control. Check for adequate makeup air (1.5 sq. Ft.)
Tumbler turns ignition sparks no flame Gas supplymake sure gas supplyis working Gas pressure Make manometer check of gas pressure for 3.5" W.C. or more at supply side Spark electrode Gas valve Check electrode
More informationLOW VOLTAGE CONTROL CIRCUIT WIRING
INSTALLATION INSTRUCTIONS LOW VOLTAGE CONTROL CIRCUIT WIRING MODELS W**A W**L W**A*D W**L*D Bard Manufacturing Company, Inc. Bryan, Ohio 43506 Since 1914...Moving ahead just as planned. Manual : 2100-507A
More informationINSTALLATION, OPERATION & QUICK START GUIDE
INSTALLATION, OPERATION & QUICK START GUIDE Controller CS9B-THOA CS9B-THOCA Models: CS9BE-THOA CS9BE-THOCA Bard Manufacturing Company, Inc. Bryan, Ohio 4506 www.bardhvac.com Manual: 00-684 Supersedes:
More informationUSER'S MANUAL PGE Single Package Rooftop
USER'S MANUAL PGE Single Package Rooftop Gas Heating/Electric Cooling Units Sizes 036-150 3 to 12-1/2 Tons NOTE TO INSTALLER: This manual should be left with the equipment owner. WARNING: If the information
More informationDryAire DRYING CABINET
CONSUMER SERVICES TECHNICAL EDUCATION GROUP PRESENTS L-72 DryAire DRYING CABINET Model LMA1053L JOB AID Part No. 8178202 FORWARD This Whirlpool Job Aid, DryAire Drying Cabinet, (Part No. 8178202), provides
More informationAIR-COOLED CONDENSING UNIT UNITS PRODUCED AFTER JANUARY, 1996 INDEX SCHEMATIC DIAGRAM FIG. NO.
wiring diagrams AIR-COOLED CONDENSING UNIT 566D Sizes 120-240 Cancels: New WD 566D.120.1 11/15/96 UNITS PRODUCED AFTER JANUARY, 1996 INDEX UNIT 566D 120-240 ELECTRICAL CHARACTERISTICS (V-Ph-Hz) SCHEMATIC
More informationFAN POWERED VAV TERMINALS
FAN POWERED VAV TERMINALS Models VFR, CFR and CFRQ INSTALLATION, OPERATION AND MAINTENANCE MANUAL All data herein is subject to change without notice. Refer to www.enviro-tec.com for current catalog data
More informationGeneral Information. FAST-STAT wiring extenders electronically add more wires to a control cable.
General Information FAST-STAT wiring extenders electronically add more wires to a control cable. Saves significant time and expense as compared to repulling of new cables. Causes no damage to walls or
More informationElectronic Air Cleaner
by White-Rodgers Electronic Air Cleaner 240 Volt 50/60 Hz SST Super Slim Twin Model Number 10C27S-010 14C27S-010 20C27S-010 UST Universal Slim Twin Model Number 16C27S-010 OWNERS MANUAL WHITE-RODGERS SUPER
More informationStatement of Responsibilities This document is for use by experienced and trained Qualified Cleveland Range, LLC Authorized Service Representatives who are familiar with both the safety procedures, and
More informationINSTALLATION INSTRUCTIONS MASTER CONTROLLERS MC91AE MC92AE MC93AE MC94AE MC94AEH MC96AEH MC97AE-1
INSTALLATION INSTRUCTIONS MASTER CONTROLLERS MODELS: MC91AE MC92AE MC93AE MC94AE MC94AEH MC96AEH MC97AE-1 Bard Manufacturing Company Bryan, Ohio 43506 Since 1914...Moving ahead, just as planned. Manual:
More informationINSTALLATION INSTRUCTIONS WALL MOUNT ENERGY RECOVERY VENTILATOR WITH EXHAUST
INSTALLATION INSTRUCTIONS WALL MOUNT ENERGY RECOVERY VENTILATOR WITH EXHAUST Models: WERV-A2B WERV-A3C WERV-C2B WERV-C3C For Use With Bard 1-1/2 Through 3 Ton Wall Mount Air Conditioners and Heat Pumps
More informationInstallation Instructions
Installation Instructions PAM3 SERIES PACKAGE AIR CONDITIONERS TABLE OF CONTENTS SAFETY LABELING AND SIGNAL WORDS... 2 UNIT DIMENSIONS... 3 SAFE INSTALLATION REQUIREMENTS... 3 LOCATING THE UNIT... 3 CLEARANCES...
More informationGREEN REFRIGERANT R-410A
WALL-MOUNT HEAT PUMPS - (0HZ) Models: JH to J0H 0Hz Heating Capacities:,000 to,000 Capacities:,00 to,000 Solair Wall-Mount Heat Pump is a self-contained energy efficient heating and cooling system, which
More informationInstallation Instructions
50ZPB, C, 50ZHB, C, PA3Z ---A, PH3Z ---A, PA4Z, PH4Z, PAJ4,PHJ4,WJA4,WJH4 SMALL PACKAGED PRODUCTS (SPP) Accessory Electric Heaters 5---20 kw For 14 SEER, R---410A Manufactured Home Installation Instructions
More informationDIGI3U. Zoning Systems. Installation Guide. That s all we do. Three-Zone, Universal Controller for Gas/Electric or Heat Pump Applications
Installation Guide DIGIU Three-Zone, Universal Controller for Gas/Electric or Heat Pump Applications -Zone Controller for the RNC Market Part #DMAN October 004 Zoning Systems That s all we do. INTRODUCTION
More informationSupersedes: N2Y (498) N2Y (799) MODELS B1HH018 THRU THRU 5 TON (12 SEER)
CHAMPION SERIES SINGLE PACKAGE HEAT PUMPS INSTALLATION INSTRUCTION Supersedes: 511.18-N2Y (8) 511.18-N2Y (7) MODELS B1HH018 THRU 00 1.5 THRU 5 TON (12 SEER) 035-1707-000 GENERAL YORK Model B1HH units are
More informationInstallation Instructions
Single Package Rooftop Cooling Only with NOVATION Coil Sizes 08, 12, and 14 with Puronr (R---410A) Refrigerant Installation Instructions NOTE: Read the entire instruction manual before starting the installation
More information