SECTION P3 LINE HEATER
|
|
- Buck Higgins
- 5 years ago
- Views:
Transcription
1 LINE HEATER EI 224 A has one Line Heater. The WOG EI 224 #6 Sub-Sea Well flows into a Well-stream Heater, BAP This heater is a dual unit with natural draft burners. From the Well-stream Line Heater, the flow is directed to H.P. Production Separator #1, MBD Rev: 0 Date: 10/28/11 Page 1 of 5 EI 224 A
2 A. PRE-STARTUP PROCEDURE NOTICE: Refer to Preliminary Considerations in SECTION 3, PART A before beginning any start-up procedures. WARNING: Personnel shall not allow the Flowline Heater burners to heat the transfer medium while the inlet SDVs, heater surface chokes and/or outlet block valves are shut in any combination with each other. To do so will cause the thermal expansion of trapped gas in either of the affected pre-heat or post-heat voids. This will create the possibility of overpressure of the component. 1. Verify facility processes are prepared to resume production 2. Inspect components of the Natural Draft Heater a. Look for leaking or venting valves b. Look for oil or flammables around fire tubes c. Verify heat transfer medium level d. Look for oil or flammables in drains and/or skids adjacent to fire tube e. Inspect condition of fire tube and burner f. Verify the inlet and outlet process block valves to/from the Wellstream Heater are open g. Close Pilot Gas and Main Fuel Gas block valves h. Allow unit to purge for at least 5 minutes NOTICE: Always allow the unit to purge for at least 5 minutes. On calm days, or when the vessel is near the ambient temperature, longer purge times will be required. 3. Verify manual valves are open or closed as necessary to correctly direct flow through each Line Heater Rev: 0 Date: 10/28/11 Page 2 of 5 EI 224 A
3 B. START-UP PROCEDURES Natural Draft Burner 1. Pull to reset the Wellstream Heater relay if tripped 2. Turn the Ignitor/BSL to the On position. Sparking will occur immediately 3. Slowly open the Pilot Gas block valve, gas will now be flowing to the Pilot tip 4. If the Pilot does not light, close the Pilot block valve. Turn the Ignitor/BSL switch to the Off position and repeat steps 2 &3 NOTICE: Always allow 5 minutes before trying to re-ignite pilot, so that fuel gas is not allowed to accumulate in the Fire Tube section. 5. If start up is successful, the flame rod will sense the flame ignition and clear the BSL 6. Place the BSL back in service at the Control Panel 7. Allow the pilot to warm up for at least 5 minutes before lighting the Main Burner. The ideal pilot flame is a lazy blue flame with yellow fingers. 8. SLOWLY open the Main Fuel Gas block valve and monitor the flames inside the firetube through the observation view-port a. Ensure that the flame quality is pencil shaped and not licking against the top of the fire tubes b. If the Main Burner does not light instantly, quickly close the Main Fuel Gas block valve to prevent accumulation of gas in the firetube. Allow 5 minutes then repeat lighting process 9. Begin lighting process for the second burner using steps 2-8 above 10. Allow the heat transfer medium to begin heating Rev: 0 Date: 10/28/11 Page 3 of 5 EI 224 A
4 11. Monitor the Wellstream Heater until liquid flowrate and temperature have stabilized. Adjust the heat control thermostat to the desired temp (approximately 135F), if needed 12. Adjust the manual air dampener for the effected burner if the flame is not being maintained 13. Immediately begin using Normal Operating Procedures to continue monitoring system REFER TO: SECTION 5, PART C Rev: 0 Date: 10/28/11 Page 4 of 5 EI 224 A
5 C. SHUT-DOWN PROCEDURES NOTICE: Refer to Preliminary Considerations in SECTION 4, PART A before beginning any shut-down procedures. 1. Consider the length of time the unit will be shutdown. If the shutdown is for an extended period of time, the loss of heating could cause production problems 2. Close the manual block vales in the Pilot supply 3. Close the manual block valves in the Main Burner supply 4. If necessary, close manual valves to isolate individual components 5. Open manual bleed/drain valves as necessary to bleed/drain components WARNING: Use appropriate fluid collection when draining components. NOTICE: If shut-down was performed as preparation for maintenance work, or if the cause of the shutdown requires corrective action/repair, continue with Lock Out/Tag Out (LO/TO) Procedures REFER TO: Fieldwood Safe Work Practices- Section D Chapter 5 (can be found on the Fieldwood SEMS Portal) Rev: 0 Date: 10/28/11 Page 5 of 5 EI 224 A
TEMPERATURE CONTROLLERS
Instruction Manual: H1 T-12 Thermostat PILOT GUARD INTRODUCTION: SCOPE: This instruction manual includes installation, operation, and parts information for the Kimray Thermostat and Pilot Guard. Refer
More informationClearFire. Startup Guide. Model CFH. Horizontal Steam Boiler
ClearFire Model CFH Horizontal Steam Boiler Startup Guide 750-293 www.cleaverbrooks.com Improper installation, adjustment, service, or maintenance can cause equipment damage, personal injury, or death.
More informationINSTALLATION INSTRUCTIONS FOR SERIES 9 INTERMITTENT PILOT IGNITION CONTROL
INSTALLATION INSTRUCTIONS FOR SERIES 9 INTERMITTENT PILOT IGNITION CONTROL Figure 1 Series 9 Intermittent Pilot Ignition Control Application The Series 9 Intermittent Pilot Ignition Control is a microprocessor
More informationNew Power Vented Rheem FVIR Tanks
Technical Bulletin B06-08 Sept 26/ 2006 New Power Vented Rheem FVIR Tanks In the coming weeks new power vented FVIR tanks will be arriving in the field from our tank manufactures. We are supplying some
More informationAXIAL HEATER TROUBLE SHOOTING GUIDE. Models: AX24 N/PV, AX24 N/PV LT, AX24 LP AX26 N/PV, AX26 N/PV LT, AX26 LP AX28 N/PV, AX28 N/PV NT, AX28 LP
AXIAL HEATER TROUBLE SHOOTING GUIDE Page 1 July 2009 Table of Contents Frequently Asked Questions... 3 Axial Heater CONTROL (Siemens LME69) Troubleshooting Chart... 4 Axial Heater BURNER Troubleshooting
More informationOPERATING AND MAINTENANCE MANUAL
OPERATING AND MAINTENANCE MANUAL NVPOM-0104 TABLE OF CONTENTS Section Page 1 SPECIFICATIONS...1 1.1 Nova Plus Specifications...1-1 1.2 Warranty...1-2 2 GENERAL BURNER DESCRIPTION...2 2.1 Burner...2-1 2.2
More informationFigure 10 or Figure 6
SUPPLEMENT TO INSTRUCTION MANUAL P/N 238-45637-00 and 238-48933-00 (Replaces pg. 32 (238-45637-00) or pg. 28 (238-48933-00) in Wiring Diagram Honeywell A B C VERY HO HO LOW Figure 10 or Figure 6 238-48214-00B
More informationCSD-1 COMMERCIAL BOILER CONTROLS
SUPPLEMENTAL INSTALLATION AND OPERATING INSTRUCTIONS CSD- COMMERCIAL BOILER CONTROLS P/N 400043, Rev. A [/03] CSD- COMMERCIAL BOILER CONTROLS! WARNING Fire, explosion, asphyxiation and electrical shock
More informationSUBMITTAL SCHEDULE & DATA
SUBMITTAL SCHEDULE & DATA Gas- and Oil-Fired Unit Heaters, Infrared Heaters, and Indoor Duct Furnaces Job Name: Date: 10/31/2016 Location: Engineer: Submitted by: Jeff Musto Architect: Contractor: Model
More informationENVI Boiler Controller
GSG Rev. 0.0 6/2/2009 ENVI Boiler Controller Getting Started Guide Installation Date: Harsco Industrial, Patterson-Kelley 100 Burson Street East Stroudsburg, PA 18301 Telephone: (877) 728-5351 Facsimile:
More informationPower Flame Incorporated
Power Flame Incorporated SUGGESTED SPECIFICATION FOR MODEL NVC2 THRU NVC6 ULTRA LOW NOx GAS BURNERS SUB 9 PPM NOx WITH CONTROLINKS CONTROLS THE POWER TO MANAGE ENERGY 2001 South 21st Street, Parsons, Kansas
More informationConversion Instructions Logano G234X. Gas boiler. Please read carefully before installing and servicing. Gas boiler
Gas boiler UPON COMPLETION OF THE INSTALLATION THE INSTALLER MUST INSTRUCT THE OWNER AND OPERATOR ON THE FUNCTIONALITY AND THE PROPER OPERATION OF THE BOILER AND THE HEATING SYSTEM. INSTALLER MUST REVIEW
More informationHEATEC TEC-NOTE. Operation and maintenance Heatec thermal fl uid heaters industrial series IMPOPRTANT NOTICE! CONTENTS. Publication No.
HEATEC TEC-NOTE Operation and maintenance Heatec thermal fl uid heaters industrial series CONTENTS Important Notice...1 Intended users...2 Scope...2 Prior to initial startup...2 Preliminary tasks...2 Purging
More informationXIII Troubleshooting
XIII Troubleshooting The following pages contain troubleshooting charts for use in diagnosing control problems. To use these charts, go to the box marked Start at the top of the chart on page 34 or 36
More informationBGH Series Hot Surface Ignition Control
Installation Instructions BGH Series Issue Date April 14, 2011 BGH Series Hot Surface Ignition Control Application The BASO Gas Products BGH Series Hot Surface Ignition (HSI) control is microprocessor
More informationZG Shown READ ALL INSTRUCTIONS IN THIS MANUAL AND RETAIN FOR FUTURE REFERENCE WARNING
See unit nameplate for manufacturer and address. 507258-04 7/2018 Supersedes 10/2017 ZG 036, 048, 060, 072, 074 (3, 4, 5 and 6 Tons) ZG 092, 102, 120, 150 (7-1/2, 8-1/2, 10 and 12 Tons) ROOFTOP UNITS ZG
More informationEBC 10 Fan Control USA CAN. Product Information. ... Chapter 1+2. Mechanical Installation. ... Chapter 3. Electrical Installation. ...
Installation & Operating Manual EBC 10 Fan Control USA CAN Product Information... Chapter 1+2 Mechanical Installation... Chapter 3 Electrical Installation... Chapter 4 Start Up and Configuration... Chapter
More informationA. Section Common Motor Requirements for HVAC Equipment: Fan motors.
SECTION 235533 - FUEL-FIRED UNIT HEATERS PART 1 GENERAL 1.1 SECTION INCLUDES A. Gas fired unit heaters. B. Oil fired unit heaters. C. Tubular infrared heaters. 1.2 RELATED REQUIREMENTS A. Section 230513
More informationInstallation Instructions for P/N: Algas-SDI thermostat retrofit kit
151 South Michigan Street, Seattle, WA 98108 U.S.A. Phone: 206-789-5410 Fax: 206-789-5414 Internet: www.algas-sdi.com Installation Instructions for P/N: 41073 Algas-SDI thermostat retrofit kit Field Kit
More informationU n i t H e at e r s
Unit Heaters LF Models Enduring performance Allied commercial unit heaters are built to last, season after season Designed and built for durability and peak performance, Allied Commercial unit heaters
More informationREAD ALL INSTRUCTIONS IN THIS MANUAL AND RETAIN FOR FUTURE REFERENCE WARNING
2005 Lennox Industries Inc. Dallas, Texas, USA 505,058M (38152A068) 08/05 Supersedes 06/05 13GCSX Series Units Improper installation, adjustment, alteration, service or maintenance can cause property damage,
More informationAFUE up to 83.9% Heating Input 50,000 to 299,000 Btuh
HEATERS / BOILERS GWB8-E Gas-Fired Hot Water Boiler PRODUCT SPECIFICATIONS Bulletin No. 065 July 06 Supersedes September 05 AFUE up to 83.9% Heating Input 50,000 to 99,000 Btuh MODEL NUMBER IDENTIFICATION
More informationOil and Gas Heaters ZICOM EQUIPMENT PTE LTD
AUSTRALIA 38 Goodman Place Murarrie, Qld 4172 Australia Telephone : +61 7 3390 7962 Facsimile : +61 7 3908 6088 THAILAND 95/15 Moo 1 Tumbon Bankaow Ampur Panthong, Chonburi 20160 Bangkok Telephone : +66
More informationSERVICE AND INSTALLATION MANUAL MODELS HDO(H) OIL FOR YOUR SAFETY
Bousquet Technologies Inc. 2121, Nobel, Ste Julie, Quebec, Canada, J3E1Z9 SERVICE AND INSTALLATION MANUAL MODELS HDO(H) OIL Oil-Fired air heater for industrial and commercial use. FOR YOUR SAFETY Do not
More informationPART 0 A/E INSTRUCTIONS 0.01 DESIGN REQUIREMENTS
PART 0 A/E INSTRUCTIONS 0.01 DESIGN REQUIREMENTS A. General: 1. To obtain maintenance and repair standards for boiler burners (Section 15555A) and boiler tubes (Section 15555B), contact the DPS Project
More informationINSTALLATION, OPERATING & MAINTENANCE INSTRUCTIONS FOR 350 SERIES CIRCULATION HEATERS
INDEECO Circulation Heaters are designed to provide years of trouble free operation if properly installed and maintained. Please read and follow these instructions for installing and maintaining the heater.
More informationBurner Management and Combustion Control. Copyright 2014 Rockwell Automation, Inc. All Rights Reserved.
Burner Management and Combustion Control Rev 5058-CO900E Industrial Combustion Team Overview Background and Industry Experience RA s IC&PG Team Expertise 3 Extensive experience working with Factory Mutual
More informationWHEN TROUBLESHOOTING, PERFORM THE STEPS IN ORDER.
WHEN, PERFORM THE STEPS IN ORDER. BURNER WON T LIGHT Control System 1. Is the main interlock in auto? The burner will not light if the dryer is in manual mode b. No: Switch the main interlock to auto 2.
More informationUSER'S INFORMATION MANUAL
USER'S INFORMATION MANUAL WARNING: If the information in this manual is not followed exactly, a fire or explosion may result causing property damage, personal injury or loss of life. Do not store or use
More informationTechnical
Service Mode (electronic Control Only) Service Mode is entered by pressing down and holding all keys for 5 seconds. Alarm history of the connected appliance is displayed, alarms are indexed by E1 for most
More informationM2 Series Startup Form
M Series Startup Form Job Name: Date: Address: Model Number: Serial Number: Tag: Startup Contractor: Address: Phone: Pre Startup Checklist Installing contractor should verify the following items.. Is there
More informationKG 092 SHOWN READ ALL INSTRUCTIONS IN THIS MANUAL AND RETAIN FOR FUTURE REFERENCE WARNING
See unit nameplate for manufacturer and address. 507350-03 3/2016 Supersedes 9/2015 KG 024, 030, 036, 048, 060, 072, 074, 090 (2, 2-1/2, 3, 4, 5, 6 and 7-1/2 Tons) KG 092, 102, 120, 150 (7-1/2, 8 1/2,
More informationHWX GAS BOILERS USER S INFORMATION MANUAL
UMHWX3-1 22-UMHWX3 HWX GAS BOILERS USER S INFORMATION MANUAL WARNING: If the information in this manual is not followed exactly, a fire or explosion may result causing property damage, personal injury
More informationSULPHUR RECOVERY UNIT
19 October 2015 SULPHUR RECOVERY UNIT START-UP CONSIDERATIONS SHRIKANT KOLI BLACK & VEATCH, MUMBAI Agenda - Burner Management System - Control Loops - Refractory Dry-Out - Start-up Experiences 2 Burner
More informationInternet Version for Reference Only INDUCED DRAFT COMMERCIAL WATER HEATERS SUPPLEMENT INSTRUCTIONS TO PART #
INDUCED DRAFT COMMERCIAL WATER HEATERS SUPPLEMENT INSTRUCTIONS TO PART #238-39387-00 THIS INSTRUCTION SUPPLEMENT IS ONLY INTENDED TO GIVE INSTALLATION INSTRUCTIONS AND INFORMATION RELATED TO THE INDUCED
More informationINSTALLATION AND MANINTENANCE INSTRUCTIONS
INSTALLATION AND MANINTENANCE INSTRUCTIONS Appr. Nr. A 9503 T - 0085 AQ 0765 PEGASUS F2 T HIGH EFFICIENCY GAS-FIRED CAST-IRON BOILERS Models 51-68 - 85-102 2 Contents 1. General technical data 2. Dimensional
More informationMODEL HS115-3, HS115-4 & HS115-5 WIRING DIAGRAM ADDENDUM
TJERNLUND PRODUCTS, INC. 1601 Ninth Street White Bear Lake, MN 55110-6794 PHONE (800) 255-4208 (651) 426-2993 FAX (651) 426-9547 Visit our web site www.tjernlund.com MODEL HS115-3, HS115-4 & HS115-5 WIRING
More informationLATTNER BOILER COMPANY 9.5 HP Low-NOx Installation and Start-Up Checklist for Dry Cleaners
1 1. General Installation Information (to be completed by technician) Date installed: Location (city & state): Cleaner s name: National Board number (boiler): Installed by (company): Installed by (technician):
More informationUSER S GUIDE FOR PASTA COOKER SERIALS
USER S GUIDE FOR PASTA COOKER SERIALS NAME OF APPLIANCE MODEL NO. SPECIFICATION SUPERTRON COMMERCIAL PASTA COOKER NC-400, NC-800, NC-1200 MANUFACTURED BY TU S BROS PTY LTD 77 MAIN ROAD, CLAYTON SOUTH VIC
More informationM2 Series Startup Form
M Series Startup Form Job Name: Date: Address: Model Number: Serial Number: Tag: Startup Contractor: Address: Phone: Pre Startup Checklist Installing contractor should verify the following items.. Is there
More informationSUPER HIGH EFFICIENCY WATER HEATERS SUPPLEMENT TO INSTRUCTION MANUAL P/N (Replaces pg. 2 in instruction manual.) CONGRATULATIONS!
SUPER HIGH EFFICIENCY WATER HEATERS SUPPLEMENT TO INSTRUCTION MANUAL P/N 238-44219-00 (Replaces pg. 2 in instruction manual.) CONGRATULATIONS! You have just purchased one of the finest water heaters on
More informationbring value to your space
PTP unit heaters can use natural or propane gas, and are available in single-stage or optional two-stage controls. bring value to your space with THE NEW PTP HEATER. Introducing the new power vented, PTP
More informationIntermittent Pilot Ignition (IPI) and Direct Spark Ignition (DSI) Applications with Flame Current Probes
Application Note Issue Date February 22, 2018 Intermittent Pilot Ignition (IPI) and Direct Spark Ignition (DSI) Applications with Flame Current Probes Application This document is intended to aid the appliance
More informationLGB Gas fired boiler
LGB Gas fired boiler Control Supplement LGB-5 Series 2 Propane gas CSD-1 Control System Part Number 550-110-682/0304 Please read this page first Hazard definitions To the installer... The following terms
More informationUser Manual FLOWMAX-90. for model. Condensing water heater 85,000 BTU. Installation, operating, commissioning and maintenance instructions.
User Manual for model FLOWMAX-90 Condensing water heater 85,000 BTU WARNING If the information in these instructions is not followed exactly, a fire or explosion may result, causing property damage, personal
More informationAFUE up to 85.2% Heating Input 105,000 to 245,000 Btuh
WATER HEATERS / BOILERS COWB3 Oil-Fired Hot Water Boiler PRODUCT SPECIFICATIONS Bulletin No. 0654 March 08 Supersedes September 05 AFUE up to 85.% Heating Input 05,000 to 45,000 Btuh MODEL NUMBER IDENTIFICATION
More informationsouthbend A MIDDLEBY COMPANY INSTALLATION AND OPERATION MANUAL CG214 (E) CG314 (E) CG414 (E) CG220 (E) CG320 (E) CG325 (E) GAS BOILERS MODELS:
INSTALLATION AND OPERATION MANUAL GAS BOILERS MODELS: CG214 (E) CG314 (E) CG414 (E) CG220 (E) CG320 (E) CG325 (E) southbend A MIDDLEBY COMPANY 1100 Old Honeycutt Road Fuquay-Varina, NC 27526 (919) 552-9161
More informationPower Flame Incorporated
Power Flame Incorporated SUGGESTED SPECIFICATION FOR MODEL NVC ULTRA LOW NOx GAS BURNERS SUB 9 PPM NOx THE POWER TO MANAGE ENERGY 2001 South 21st Street, Parsons, Kansas 67357 Telephone: 620-421-0480,
More informationTECHNICAL SERVICE DEPARTMENT Technical Service Bulletin Ultra Low NOx PowerVent with Honeywell Electronic Control California Only
Error Code Flash TECHNICAL SERVICE DEPARTMENT Gas Valve Status Flash Code Short flash once every four seconds "Heartbeat", alternates bright/dim One Flash, three second pause Two Flash, three second pause
More informationDIRECTIVE NO: D-B
DIRECTIVE NO: D-B6 100604 1 LOW PRESSURE THERMAL FLUID PLANT AUTOMATED CONTROL SYSTEMS Date of Issue: June 4, 2010 General Details This directive is being issued to owners, licensed contractors, consulting
More informationCINCINNATI, OH USA
INSTRUCTION MANUAL Part No. 89731 Revised October 1997 CINCINNATI, OH 45241-4807 USA GAS SAFETY PRECAUTIONS Instructions on what to do when a user smells gas can be obtained from the local gas supplier.
More informationL62GB BASO Safety Shutoff Device
Installation Instructions Issue Date August 18, 2008 L62GB BASO Safety Shutoff Device Installation IMPORTANT: Only qualified personnel should install or service BASO Gas Products. These instructions are
More information150 & 200 RT MG-SERIES GAS FIRED DOUBLE-EFFECT EFFECT ABSORPTION CHILLER-HEATER
GUIDE SPECIFICATIONS 150 & 200 RT MG-SERIES GAS FIRED DOUBLE-EFFECT EFFECT ABSORPTION CHILLER-HEATER HEATER 1. General Description The Contractor shall furnish and install (Qty) Yazaki model CH- Gas Fired,
More informationInstructor: Sales person: Phone: Sales person: Phone: Sales person: Phone: Sales person: Phone: Service Manager: Phone: Service Manager: Phone:
LRZE HEATER Zodiac Pool Systems, Inc. 1-800-822-7933 Regional Extension www.zodiacpoolsystems.com Zodiac Academy zodiac.academy@zodiac.com www.zodiacacademy.com Instructor: Email: Sales person: Phone:
More informationThe key element for your process
The key element for your process Safety Controls and Burner Management Systems (BMS) Paul Chau, P. Eng. Vice-President (Born Heaters Canada Ltd.) www.adico.co info@adico.co Table Of Contents 1. Introduction...
More informationUniversal Fire Tube Boiler Wall Mount Models
Universal Fire Tube Boiler Wall Mount Models USER S INFORMATION MANUAL Models WBRU**80W / 100W / 120W / 140W / 175W / 199W **NG denotes Natural Gas Model, LP Denotes Propane Model Heat Exchanger Bears
More informationUSER'S INFORMATION MANUAL
USER'S INFORMATION MANUAL WARNING: If the information in this manual is not followed exactly, a fire or explosion may result causing property damage, personal injury or loss of life. Do not store or use
More informationTechnical
Service Mode (electronic Control Only) Service Mode is entered by pressing down and holding all keys for 5 seconds. Alarm history of the connected appliance is displayed, alarms are indexed by E1 for most
More informationCommittee on NFPA 85
Committee on NFPA 85 M E M O R A N D U M TO: FROM: NFPA Technical Committee on Single Burner Boilers Patti Mucci, Technical Assistant II DATE: August 5, 2009 SUBJECT: NFPA ROP Letter Ballot The ROP letter
More informationUser s Manual. For the SHORE POWER CONNECTION MONITOR MODEL 9151
User s Manual For the SHORE POWER CONNECTION MONITOR MODEL 9151 Table of Contents: Product Description... 3 Installation... 4 Optional Remote Alarm Installation... 7 Operator Test... 8 Alarms... 9 Figures...
More informationKGA092 SHOWN READ ALL INSTRUCTIONS IN THIS MANUAL AND RETAIN FOR FUTURE REFERENCE WARNING
See unit nameplate for manufacturer and address. 506380 01 11/2009 KGA024, 030, 036, 048, 060, 072 (2, 2 1/2, 3, 4, 5, and 6 Tons) KGA092, 102, 120, 150 (7 1/2, 8-1/2, 10, and 12 Tons) KGA180, 210, 240,
More informationCambridge Engineering, Inc. 24 S-Series Technical Manual
Start-Up Instructions START-UP PROCEDURE 1. Visual Inspection Of Equipment (page 24) 2. Electrical Supply Voltage Verification (page 24) 3. Gas Supply Pressure Verification (page 24) 4. Blower Rotation
More informationUSER'S INFORMATION MANUAL
USER'S INFORMATION MANUAL WARNING: If the information in this manual is not followed exactly, a fire or explosion may result causing property damage, personal injury or loss of life. Do not store or use
More informationUSER'S INFORMATION MANUAL
USER'S INFORMATION MANUAL WARNING: If the information in this manual is not followed exactly, a fire or explosion may result causing property damage, personal injury or loss of life. Do not store or use
More informationWilliams & Davis Boilers
Williams & Davis Boilers Established 1921 3-Pass Water-Back Scotch Marine Boiler SIZES 15HP THROUGH 1500HP GAS, OIL OR COMBINATION BURNER FIRETUBE HOT WATER & PRESSURE STEAM BOILERS 3000W Standard Features
More informationModel 60200FR Gas Primary Control Data Sheet
Programmable, Microprocessor Based Gas Burner Primary Controls On-Board LCD Screen Easy to Understand Icons for Inputs and Outputs Displays micro-amp Flame reading Display operational information Fault
More informationPackaged Gas/Electric Units. Owner s Guide to Operating and Maintaining Your Gas/Electric Unit
Packaged Gas/Electric Units Owner s Guide to Operating and Maintaining Your Gas/Electric Unit ELECTRICAL SHOCK HAZARD. FIRE OR EXPLOSION HAZARD Disconnect power at fuse box or service panel before performing
More informationUSER'S INFORMATION MANUAL
USER'S INFORMATION MANUAL WARNING: If the information in this manual is not followed exactly, a fire or explosion may result causing property damage, personal injury or loss of life. Do not store or use
More informationGAS FURNACES G20RE/ G20RXE EXISTING NEG ENGINEERING DATA EXISTING NEG. Typical Applications
ENGINEERING DATA Typical Applications G20RE and G20RXE WhisperHeat DOWN-FLO GAS FURNACES *78.0% A.F.U.E. 50,000 to 150,000 Btuh Input Add-On Cooling 2 thru 5 Nominal Tons *Isolated Combustion System rating
More informationDOMESTIC HOT WATER Follow operational sequence
DOMESTIC HOT WATER Follow operational sequence Turn Winter/Summer selector to Summer position. The display is switch on. Go to section A Error 110 flashing Error 131 flashing Turn the selector to reset
More informationRapid Response Series (RR e & RR i) OPERATING MANUAL
Rapid Response Series (RR e & RR i) OPERATING MANUAL STADT INDUSTRIES PTY. LTD. MF-01 18/07/04 Operating Manual RR Series Stadt High Efficiency Central Heater. CONTENTS A): Introduction A: Introduction
More informationTGA/KGA024, 030, 036, 048, 060, 072, 090 (2, 2 1/2, 3, 4, 5, 6, and 7 1/2 TONS)
See unit nameplate for manufacturer and address. 506003 01 5/2009 Supersedes 1/2008 TGA/KGA024, 030, 036, 048, 060, 072, 090 (2, 2 1/2, 3, 4, 5, 6, and 7 1/2 TONS) TGA090, 102, 120, 150, TGA120 SHOWN (7
More informationFlame Safeguards LFE10. Building Technologies HVAC Products
7 71 Flame Safeguards LAE LFE Flame safeguards for burners with intermittent operation The LAE is used for the supervision and indication of oil flames The LFE is used for the supervision and indication
More informationMG & SG SERIES BOILERS
S9361A CONTROL SUPPLEMENT MANUAL MG & SG SERIES BOILERS FOR MODELS MG-50-E TO MG-150-E AND SG-135-E TO SG-270-E NEW CONTROLLER This supplement manual must be used in conjunction with the Installation and
More informationLGA... Gas Burner Controls. Siemens Building Technologies Landis & Staefa Division
7 418 ISO 9001 Gas Burner Controls LGA... The LGA... are used for the startup and supervision of atmospheric gas burners of low to medium capacity, without fan assistance, in intermittent operation. The
More informationT-CLASS GAS-FIRED UNIT HEATERS Separated Combustion - Direct Vent - Horizontal - 60 HZ. Thermal Efficiency - up to 82% Input - 40,000 to 300,000 Btuh
PRODUCT SPECIFICATIONS GAS UNIT HEATERS / DUCT FURNACES TU T-CLASS GAS-FIRED UNIT HEATERS Separated Combustion - Direct Vent - Horizontal - 60 HZ Bulletin No. 20402 November 207 Supersedes November 206
More informationEclipse 90 UV Scanner Model A Version 1
85 Instruction Manual 10/14/010 Eclipse 90 UV Model 5600-90A Version 1 C US Introduction This sensor features a high sensitivity ultraviolet (UV) tube for monitoring gas or oil flames that cycle on and
More informationUV Scanner. Model Specification. Introduction. 854 Instruction Manual
854 Instruction Manual 10/11/010 UV Model 5600-91 C US Introduction This sensor features a high temperature and high sensitivity ultraviolet (UV) tube for monitoring gas or oil flames in applications that
More informationSUPER HIGH EFFICIENCY WATER HEATERS SUPPLEMENT TO INSTRUCTION MANUAL P/N (Replaces pg. 2 in instruction manual.) CONGRATULATIONS!
SUPER HIGH EFFICIENCY WATER HEATERS SUPPLEMENT TO INSTRUCTION MANUAL P/N 238-51012-00 (Replaces pg. 2 in instruction manual.) CONGRATULATIONS! You have just purchased one of the finest w ater heaters on
More informationCookshack, Inc. Model FEC100 Fast Eddy Oven. Version /1/10
Cookshack, Inc. Model FEC100 Fast Eddy Oven Operator s Manual Please read this entire manual installation and use of this pellet fired smoker oven. Failure to follow these instructions could result in
More information24 VAC SYSTEM CONTROL KIT
24 VAC SYSTEM CONTROL KIT Model: CK-92F and CK-92FG Designed for use with the SWG Series Power Venter for controlling Natural Gas or L.P. Gas appliances with a 24 VAC Gas Valve and a 30-millivolt controlled
More informationInstallation & Troubleshooting Requirements
Installation & Troubleshooting Requirements Wiring Diagram Operation Sequence Presumptions: Main valve knob should always remain in the ON position Gas is bled to the valve Electrical is properly connected
More informationIndirect gas-fired air heater
Indirect gas-fired air heater SERIES HD INSTALLATION AND SERVICE MANUAL MANUFACTURED BY : BROTHERS LIMITED WARNING Improper installation, modification, adjustment or maintenance may cause damage, injury
More informationLAE10 LFE10. Use. Series 02
ISO 00 Flame Safeguards 7 7 LAE L Series 02 Supplementary data sheets 772 and 773 Flame safeguards for burners with intermittent operation. For safety reasons - self-test of flame supervision circuit,
More informationUSER S INFORMATION MANUAL
USER S INFORMATION MANUAL UPFLOW/HORIZONTAL & DOWNFLOW TWO STAGE INDUCED DRAFT GAS FURNACES Recognize this symbol as an indication of Important Safety Information If the information in this manual is not
More informationUSER'S MANUAL PGE Single Package Rooftop
USER'S MANUAL PGE Single Package Rooftop Gas Heating/Electric Cooling Units Sizes 036-150 3 to 12-1/2 Tons NOTE TO INSTALLER: This manual should be left with the equipment owner. WARNING: If the information
More informationUSER S, MAINTENANCE and SERVICE INFORMATION MANUAL
CONTENTS SAFETY INFORMATION................ 2 FOR YOUR SAFETY...................... 2 SYSTEM OPERATION.................. 2 THERMOSTATS.......................... 2 INTERMITTENT IGNITION DEVICE..........
More informationSERIES 35-63J APPLICATIONS FEATURES SPECIFICATIONS AGENCY CERTIFICATIONS
SERIES 35-63J INSTALLATION INSTRUCTIONS FOR REPLACING JOHNSON CONTROLS G77X AND OTHER MODELS WITH FENWAL SERIES 35-63J IP IGNITION CONTROL APPLICATIONS The Fenwal 35-63J series Intermittent Pilot Ignition
More informationUSER S, MAINTENANCE and SERVICE INFORMATION MANUAL
CONTENTS SAFETY INFORMATION................ 2 FOR YOUR SAFETY....................... 2 SYSTEM OPERATION.................. 2 THERMOSTATS.......................... 2 INTERMITTENT IGNITION DEVICE...........
More informationClearFire - Hydronic Startup Report
ClearFire - Hydronic Startup Report Date Serial No. THIS FORM IS FOR MODEL CFC / CFW CLEARFIRE BOILERS Customer s Name Location Model Design Pressure Working Pressure Rated Input (nameplate rating) BTU/hr
More informationUSER'S INFORMATION MANUAL
USER'S INFORMATION MANUAL Advantage DV GAS - FIRED BOILER WARNING: If the information in this manual is not followed exactly, a fire or explosion may result causing property damage, personal injury or
More informationPackaged Gas/Electric
Packaged Gas/Electric Units Owner's Guide to Operating and Maintaining Your Gas/Electric Unit ELECTRICAL SHOCK HAZARD. FIRE OR EXPLOSION HAZARD Failure to follow this warning can result in Disconnect power
More informationTHE SIGNIFICANCE OF RELIABLE PRESSURE CONTROL IN OILFIELD BURNER SYSTEMS
THE SIGNIFICANCE OF RELIABLE PRESSURE CONTROL IN OILFIELD BURNER SYSTEMS Author: Deepak Sivanandan Oil & Gas Product Manager, Emerson Process Management www.linkedin.com/in/deeksweb Neither Emerson, Emerson
More informationPilot Burner and Direct Spark Ignition (DSI) Applications with Flame Rectification Sensing
Application Note Issue Date September 25, 2017 Pilot Burner and Direct Spark Ignition (DSI) Applications with Flame Rectification Sensing Application This document is intended to aid the appliance engineer
More informationLGA/LGC036, 042, 048, 060, 072 (3, 3-1/2, 4, 5, and 6 TONS) LGA/LGC090, 102, 120, 150, (7-1/2, 8-1/2, 10, and 12-1/2 TONS)
See unit nameplate for manufacturer and address. 504,875M 1/2006 Supersedes 1/2004 LGA/LGC036, 042, 048, 060, 072 (3, 3-1/2, 4, 5, and 6 TONS) LGA/LGC090, 102, 120, 150, (7-1/2, 8-1/2, 10, and 12-1/2 TONS)
More informationProper maintenance of tunnel finisher will prolong its life and enable the equipment to produce the best possible quality.
Maintenance Guide Proper maintenance of tunnel finisher will prolong its life and enable the equipment to produce the best possible quality. Daily Maintenance CAUTION: Lock out main panel disconnect according
More informationCONTENTS. B. System Design and Performance Requirements
15515 Watertube Boilers This document provides design standards only, and is not intended for use, in whole or in part, as a specification. Do not copy this information verbatim in specifications or in
More informationVF/VG700 Jumbo. Construction Heater. Installation and Maintenance Manual
342 N. Co. Rd. 400 East Valparaiso, IN 46383 888-432-8924 Fax 219-462-7985 www.heatwagon.com Installation and Maintenance Manual Please retain this manual for future reference. VF/VG700 Jumbo Construction
More informationEclipse Self-Check UV Scanner
856 Instruction Manual 10/18/2010 Eclipse Self-Check UV Model 5602-91 Version 1 Introduction The self-check UV is used for continuous gas or oil flames. A mechanical shutter in the scanner closes briefly
More informationInstallation, Operation and Maintenance Instructions Thermaflow E Plate Heat Exchanger Package OM013
Installation, Operation and Maintenance Instructions Thermaflow E Plate Heat Exchanger Package OM013 Calorifiers Heat Exchangers Pressurisation Units Sales Tel: 01457 835700 Sales Fax: 01457 832700 E-mail:
More information