Thermal and air quality effects on the performance of schoolwork by children
|
|
- Leon Byron Bradley
- 5 years ago
- Views:
Transcription
1 Thermal and air quality effects on the performance of schoolwork by children David P. Wyon Technical University of Denmark Swegon Air Academy Stockholm
2 Field intervention experiments This lecture reports the findings of a series of field intervention experiments that was carried out in schools in Denmark and Sweden on behalf of ASHRAE DTU was awarded the research contract in open competition with bidders from USA, Europe, Australia and the Far East The project was known as ASHRAE 1257
3 Final Report of ASHRAE 1257 The effects of temperature, outdoor air supply rate and airborne particles on children in school classrooms David P. Wyon and Pawel Wargocki Technical University of Denmark
4 Main ASHRAE 1257 Objective To determine whether improving classroom air quality and ensuring classrooms do not become warm can improve the performance of schoolwork by children Window opening behavior was passively recorded during the experiments
5 Methods Indoor air quality was modified by increasing the outdoor air supply rate from an existing mechanical ventilation system Air temperature was reduced in hot weather by installing & operating split cooling units Windows could be opened as usual Window opening behavior was recorded as All windows closed or 1 or more open Door opening was also recorded
6 Selected school in Denmark School at Rungsted DTU
7 Schools Elementary school with no IEQ problems South-facing facades Mechanically ventilated Energy conservation measures in place
8 Plan of the selected classrooms Selected classrooms Fig. 4 Plan of selected classrooms
9 Selected classrooms
10 View of classroom
11 Ventilation system Split cooling Electrostatic air cleaners
12 Split cooling was installed and either operated or idled in summer
13 Silent electrostatic air cleaners were installed and operated or idled
14 4th to 6th grade year old ~300 pupils Pupils
15 Physical measurements Continuous measurements (with pupils): CO 2, Air T, RH, window opening state recorders Effective outdoor air supply rate in L/sp was estimated from CO 2 rate of increase each time children entered the classroom. Note that this includes air entering through windows or doors as well as supply air from the ventilation system
16 Measurements of perceptions and symptoms The children marked Visual-Analogue scales at the end of the week They reported the: Classroom environment Intensity of the symptoms they experienced How is the classroom right now? Too cold The air is draughty It is humid The air is poor Too dark Too noisy How do I feel right now? Nose is blocked Throat is dry Lips are dry Skin is dry I am very hungry I slept badly last night I feel very tired I slept too little last night I do not feel like working I have a headache Too warm The air is still It is dry The air is fresh Too much light Too dark I can breathe freely Throat is not dry Lips are not dry Skin is not dry I am full I slept well last night I am not at all tired I slept long last night I feel like working today I do not have a headache
17 Measurements of performance Tasks appropriate to children s age were developed in consultation with class teachers 4 language-based: Acoustic proof-reading Reading and comprehension Logical reasoning Proof-reading 4 numerical: Subtraction Multiplication Number comparison Addition Tasks were performed in mathematics or language lessons
18 Sensory assessments of air quality by visiting adult panel ACCEPTABILITY SCALE Clearly acceptable Just acceptable Just not acceptable Clearly not acceptable After classes ended
19 Permission was obtained from: Parents School Headmaster School Board Teachers Local Authority Danish Ethics Review Board Swedish Ethics Review Board
20 Design of experiments Interventions always improved conditions Interventions were for 1 week at a time in balanced order of presentation Cross-over design (one classroom with existing conditions and one with improved conditions) The ventilation system was modified to provide more air to one classroom at a time Split cooling was installed in both but operated in one classroom at a time
21 2x2 design Temperature Current Cool Ventilation rate current high
22 Estimated effective L/s p 10 8 L/s per person AC No AC 0 Low L/s High L/s
23 Mean classroom CO2 ppm Mean CO2 ppm AC No AC 0 Low L/s High L/s
24 Peak classroom CO2 ppm Peak CO2 ppm AC No AC 0 Low L/s High L/s
25 Teaching environment and routines No restrictions on normal daily activities No changes in class schedules Doors and windows could be opened No contact between researchers and children (no white coats or stop-watches)
26 Reduced classroom temperature 2 independent experiments in August/September : 1st experiment: temperature reduced from 23.5 to 20 o C at two ventilation rates 2nd experiment: temperature reduced from 25 to 21 o C with no mechanical ventilation Other parameters of classroom IEQ were unchanged
27 Typical time-course of classroom temperature in the two classrooms
28 Children s perception of temperature Too warm (P<0.001) Too cold Low temp High temp Estimated PMV PMV=0 PMV=0.7
29 Performance of schoolwork as a function of classroom temperature 1,4 Performance 1,2 1 0,8 R 2 = , Temperature 1 o C lower temperature ~3.5% higher performance
30 Earlier experiments by DP Wyon in Sweden in 1967 Raising classroom temperature from 20 C to 30 C reduced most types of schoolwork performance by up to 30% For 40 years this was widely believed to be an overestimate The present results confirm the size of the thermal effect first reported in 1967: +10 C would lead to 35% less schoolwork
31 Increased outdoor air supply rate Three independent field intervention experiments with 100% outdoor air supplied through new filters: was increased to 9.5 L/sp was increased to 6.5 L/sp was increased to 9.5 L/sp (with and without cooling
32 Time-course of classroom CO 2 concentration, example
33 Children s perception of IAQ Fresh air (P<0.001) Poor air Low vent High vent
34 Sensory assessments of air quality made by an untrained panel after children had left the classroom % 40 (P<0.001) Dissatisfied Low vent High vent
35 Effect of increasing ventilation rate on performance: increase in speed % Experiment 1 Experiment 2 Experiment 3 * 25 * * * * 15 * * * * 5-5 Subtraction Multiplication Number comparison Addition Logical reasoning Reading and comprehension
36 Performance of schoolwork as a function of classroom ventilation 1,4 Performance 1,2 1 0,8 R 2 = , Ventilation (L/sp) Doubling ventilation rate ~14.5% higher performance
37 Classroom air quality matters Windows are often not opened Outdoor air supply rates are often low CO2 levels are often above 1000 ppm Increasing the air supply rate from 2.5 to 5 to 10 L/sp would improve the performance of schoolwork by 29% Poor air quality is a major disadvantage for children, and especially for slow workers
38 CO2 in 1663 Scandinavian classrooms October 2009
39 Natural Ventilation only Classrooms in: CO2 >1000 ppm Denmark 69 % Sweden 47 % Norway 48 %
40 Taking all 1663 Scandinavian classrooms together:
41 CO2 was then measured in 100 classrooms in Denmark Random selection Structured representative sample CO2 recorded throughout school hours 2 weeks in November Outdoor temperature was 0-15 C Proportion with mean CO2 > 1000 ppm : 66%
42 ASHARE 1257 Results Condition of supply air filter Two studies in January No consistent effects on perceptions, symptoms or perceived air quality when a used filter was replaced with a new one
43 Installing a new filter had no effect on children s performance
44 Interpretation Results differ from our office findings, but: Very little dust was retained in the used supply air filter Supply air was 100% outdoor air, so all the dust originated outdoors
45 Operation of electrostatic air cleaners 2 independent experiments in January and March/April in 1 Danish and 4 Swedish schools Concentration of particles in classrooms was considerably reduced when electrostatic air cleaners were in operation
46 Number of particles per cm Placebo units Air cleaners >0.75 >1.0 >2.0 >3.5 >5.0 >7.5 >10 >15
47 Concentration of particles per cm3 (with/without electrostatic deposition) Reduction greater in the 2 poorly ventilated classrooms
48 Operating electrostatic air cleaners had no effects on performance
49 Conclusions on filters and airborne particles Electrostatic air cleaners reduced the concentration of airborne particles but had no effects on schoolwork Installing a new filter in the outdoor air supply flow had no effects on schoolwork However, reducing airborne particle concentration may reduce the long-term effects of IAQ on health
50 Main 1257-RP conclusions Reducing even slightly warm classroom temperatures eliminated thermal discomfort and improved children s performance Increasing outdoor air supply rate improved classroom air quality and children s performance Schoolwork was performed faster, with no increase in errors, in both cases
51 Field experiments in the UK Bakó-Biró et al. (2012) Building & Environment 48, Air supply 1 or 8 l/sp in 16 classrooms Air T changed very little (0.6 o C) Diagnostic tests, not schoolwork Significant improvement at 8 l/sp Test performance improved by 2-15%
52 Implications Removing airborne particles had no effect, so the IAQ effects were due to gas-phase pollutants in classroom air Replacing supply air filters had no effect but increasing the outdoor air supply rate did, so pollutants must originate indoors The active pollutants could be bioeffluents or emissions from materials, or both
53 IAQ effects on adults Emissions: performance of office work was reduced when office materials were present behind a screen in a clean room Bioeffluents: performance of office work was reduced when the outdoor air supply was reduced in a clean room Conclusion: both classroom emissions and bioeffluents are likely to affect the performance of schoolwork by children
54 Window opening In the DK experiments, the opening of windows and doors was recorded Teachers and children opened windows and doors as usual This is the first intervention experiment on window-opening behaviour in response to raised temperature or decreased outdoor air supply rate in school classrooms
55 Summertime classroom T in C (NB: Different classes with natural/mechanical ventilation) No AC AC 15 Off Low High Mechanical ventilation
56 Observations Split cooling reduced air T by only 1.7 C at the highest ventilation rate, but by 5.4 C at the lower rate) With natural ventilation, cooling reduced T by only 3.3 C (NB: this could be due to poor mixing, as T was recorded at 2.2m height)
57 Outdoor air supply rate (L/sp) (NB: Different classes with natural/mechanical ventilation) 10 5 No AC AC 0 Off Low High Mechanical ventilation
58 Hours/week with windows open (NB: Different classes with natural/mechanical ventilation) No AC AC 0 Off Low High Mechanical ventilation
59 Observations Windows were opened much more when it was warm in the classroom Even at 10 L/sp, a 1.7 C increase in T increased window opening by 75% With no cooling, opening windows provided only 3.7 L/sp Split cooling reduced window opening by 65%, reducing the outdoor air supply rate to only 2.7 L/sp
60 Classroom T (NB: different classes in winter & summer) 25 C 20 Summer Winter 15 Low High Ventilation (with no AC)
61 Outdoor air supply rate (L/sp) 10 (NB: different classes in winter & summer) Summer Winter 2 0 Low High Ventilation (with no cooling)
62 Hours/week with windows open 10 (NB: different classes in winter & summer) Summer Winter 2 0 Low High Ventilation (with no cooling)
63 Hours/week with windows open and with cross ventilation 10 (2 classes in winter, 2 other classes in summer) Windows open Cross ventilation 2 0 Winter Summer (With mechanical ventilation set to low in both seasons)
64 Hours per week with windows open and with cross ventilation 15 (Summer, same 2 classes in all 4 conditions) 10 5 Windows open Cross ventilation 0 T low (A/C) T high (No A/C) (With mechanical ventilation set to low throughout)
65 Observations Windows were open 4x as long in summer (when classroom T was 5 C warmer) This raised the total outdoor air supply rate from 6.5 to 9.5 L/sp Both windows and doors were used adaptively to achieve cross-ventilation Window opening was triggered by warmth but NOT by poor air quality
66 Conclusions on window opening Windows were opened to reduce classroom temperatures, not to improve IAQ Natural ventilation did not ensure adequate ventilation, even with cross-ventilation Split cooling, by eliminating the perceived need to open windows, decreased the air quality still further Both slightly raised T and poor IAQ decreased children s performance
67 SOLUTIONS (In order of first cost and sophistication) CO2 sensor signals windows open/close Computer operates windows optimally CO2 controlled by variable exhaust flow Balanced 100% fresh air supply + exhaust Pre-heat supply air and remove ozone Recover heat from exhaust airflow Remove pollutants from return air using a desiccant wheel purged with outdoor air
68 Our thanks are due to ASHRAE, STVF, Asthma and Allergifond and Formas for funding Sophie Irgens (mid-term project student) Bartlomiej Matysiak, Line Jark, Maria Schaub- Hansen, Kasper Lynge Jensen, Mateusz Komenda (M.Sc. students) Cristina Pirvu, Henry Willem (Ph.D. students) Pupils, teachers, schools, municipalities School Technical Services in Rungsted & Lund
69 Further reading ASHRAE Journal, October 2006 (Summary of T, IAQ effects) ASHRAE HVAC&R Research J, March 2007 (2 papers: T, IAQ effects) ASHRAE HVAC&R Research J, May 2008 (e-filters) Indoor Air 2008, September 2008 (Observations of window opening)
series of field intervention experiments Thermal and air quality effects on the performance of schoolwork by children
Thermal and air quality effects on the performance of schoolwork by children David P. Wyon Technical University of Denmark Swegon Air Academy Lisbon 26.5.29 Field intervention experiments This lecture
More informationEXPERIMENTAL INVESTIGATION OF THE AIR CLEANING EFFECT OF A DESICCANT DEHUMIDIFIER ON PERCEIVED AIR QUALITY
EXPERIMENTAL INVESTIGATION OF THE AIR CLEANING EFFECT OF A DESICCANT DEHUMIDIFIER ON PERCEIVED AIR QUALITY L Fang 1,2,, G Zhang 1,2 and PO Fanger 1,2 1 International Centre for Indoor Environment and Energy,
More informationVentilation Strategies for Healthy IEQ and Energy Efficiency
Ventilation Strategies for Healthy IEQ and Energy Efficiency Lars Ekberg Energy Management AB A Chalmers Industriteknik Company The purpose of ventilation + - Pollution Climate Heat Pollution 2 Examples
More informationUse of local convective and radiant cooling at warm environment: effect on thermal comfort and perceived air quality
Use of local convective and radiant cooling at warm environment: effect on thermal comfort and perceived air quality Arsen K. Melikov 1,*, Marcin Duszyk 1, Barbora Krejciríková 1,2, Tomonori Sakoi 3, Jan
More informationAir Distribution and Ventilation Effectiveness in a room with Floor/Ceiling Heating and Mixing/Displacement Ventilation
Downloaded from orbit.dtu.dk on: Mar 02, 2018 Air Distribution and Ventilation Effectiveness in a room with Floor/Ceiling Heating and Mixing/Displacement Ventilation Wu, Xiaozhou; Fang, Lei; Olesen, Bjarne
More informationHome Heating MORE THAN JUST STAYING WARM
Home Heating MORE THAN JUST STAYING WARM Types of Home Heating Fuel Sources Propane (LP) Natural Gas Fuel Oil Wood Coal Kerosene Pellets Outdoor wood boilers Electric Combustion CH4 + O2 CO2 + H2O Less
More informationA STUDY OF THE IAQ OF RESIDENTIAL BUILDINGS IN SINGAPORE
A STUDY OF THE IAQ OF RESIDENTIAL BUILDINGS IN SINGAPORE NH Wong, BRJ Huang, KW Tham, C Sekhar and DKW Cheong Dept. Of Building, School of Design and Environment, National University of Singapore, Singapore
More informationFor sales and service in Australia & NZ, contact:
Our philosophy Blueair believes in cleaner indoor air for everyone. Removing air impurities down to the tiniest particle requires a deep commitment to continuous innovation and a greener global environment.
More informationThermal Comfort with Convective and Radiant Cooling Systems
Proceedings of 9 th Windsor Conference: Making Comfort Relevant Cumberland Lodge, Windsor, UK, 7-10 April 2016. Network for Comfort and Energy Use in Buildings, http://nceub.org.uk Thermal Comfort with
More informationHuman response to thermal environment in rooms with chilled beams
Human response to thermal environment in rooms with chilled beams Arsen Melikov 1, Boryana Yordanova 1, Lyuben Bozkhov 1, Viktor Zboril 1,2, Risto Kosonen 3 1 International Center for Indoor Environment
More informationHealthy Climate Indoor Air Quality Solutions. Solutions that fit your unique needs
i n d o o r a i r q u a l i t y s o l u t i o n s Healthy Climate Indoor Air Quality Solutions Solutions that fit your unique needs Healthy Climate Indoor Air Quality Solutions Custom, whole-home product
More informationGreen Flag Level Two Survey: Indoor Air Quality Program
Green Flag Level Two Survey: Indoor Air Quality Program You have chosen to work on the Indoor Air Quality (IAQ) program to earn a Green Flag award. Answering these survey questions will take you on a tour
More informationHealthy Buildings 2017 Europe July 2-5, 2017, Lublin, Poland
Healthy Buildings 2017 Europe July 2-5, 2017, Lublin, Poland Paper ID 0188 ISBN: 978-83-7947-232-1 Dispersion of pollutants released at floor level under three types of heating systems: A CFD study. Laura
More informationEnergy Recovery Ventilation Introduction
Energy Recovery Ventilation Introduction An emphasis on energy conservation resulted in tighter buildings with minimum amounts of fresh air being heated or cooled and brought into air-conditioned spaces.
More informationDisplacement Ventilation in Classrooms
TWO DIFFUSERS, THE WHITE COLUMNS ON EACH SIDE OF THE WHITEBOARD, PROVIDE COOL SUPPLY AIR TO THE DEMONSTRATION DV CLASSROOM. THE DV CLASSROOM DEMONSTRATION FEATURED A CUSTOMIZED ROOFTOP HVAC UNIT. Displacement
More informationVariable Air Volume with Indoor Air Quality
Variable Air Volume with Indoor Air Quality and a Cure for the Spread of the Airborne Flu Virus January 11, 2017 Dinner Meeting Golden Gate ASHRAE Chapter Presented By: Thomas S. Weaver, P.E., Member ASHRAE
More informationOptimisation of cooling coil performance during operation stage for improved humidity control
Indoor Air 2008, 17-22 August 2008, Copenhagen, Denmark - Paper ID: 741 Optimisation of cooling coil performance during operation stage for improved humidity control S.C. Sekhar * and L.T. Tan National
More informationThe Performance of Diffuse Ceiling Inlet and other Room Air Distribution Systems Nielsen, Peter Vilhelm; Jakubowska, Ewa
Aalborg Universitet The Performance of Diffuse Ceiling Inlet and other Room Air Distribution Systems Nielsen, Peter Vilhelm; Jakubowska, Ewa Published in: COLD CLIMATE HVAC 2009 Publication date: 2009
More informationRESULTS FROM HOUSE APPLIANCE SAFETY AND DEPRESSURIZATION TESTS CONDUCTED ON SINGLE FAMILY HOUSES UNDERGOING SOUND INSULATION
RESULTS FROM HOUSE APPLIANCE SAFETY AND DEPRESSURIZATION TESTS CONDUCTED ON SINGLE FAMILY HOUSES UNDERGOING SOUND INSULATION DL Bohac * Center for Energy and Environment, Minneapolis, MN USA ABSTRACT Extensive
More informationVentilation in Humid Climates: Data from Field Experiments
Gaylord Texan Resort & Convention Center October 20-23, 2004 - Dallas, Texas Ventilation in Humid Climates: Data from Field Experiments Neil Moyer FSEC Yearly Housing Starts Past 3 Years Source: NAHB x
More informationCenter for the Built Environment October 2013
Thermal Comfort in the Context of Radiant Systems Center for the Built Environment University of California Berkeley Center for the Built Environment October 2013 Overview of talk A brief summary of research
More informationCARRIER edesign SUITE NEWS. Modeling 100% OA Constant Volume Air Systems. Volume 6, Issue 1. Page 1 Modeling 100% OA Constant Volume Air Systems
Volume 6, Issue 1 CARRIER edesign SUITE NEWS Modeling 100% OA Constant Volume Air Systems This article provides an overview of how to model a stand-alone constant air volume (CAV) 100% OA system in HAP.
More informationCRAWL SPACE MOISTURE CONTROL - A Fundamental Misunderstanding By Peter Carpenter, member ASHRAE, SBCCI
CRAWL SPACE MOISTURE CONTROL - A Fundamental Misunderstanding By Peter Carpenter, member ASHRAE, SBCCI A crawl space needs to be ventilated with outside air. Without ventilation there will be growth of
More informationLIMITED MICROBIAL & IAQ SURVEY CLOSING REPORT SOUTHEASTERN SCHOOL DISTRICT 02/12/2015
HOME OFFICE PO Box 326 MT AETNA PA 19544 MEMBERS OF: VOICE 717-933-9475 FAX 717-933-1403 TOLL FREE 877-255-0558 Web Page: proaccorp.com CLOSING REPORT SOUTHEASTERN DISTRICT 02/12/2015 PROJECT LOCATION:
More informationHealthy Climate Indoor Air Quality Solutions. Solutions that fit your unique needs
i n d o o r a i r q u a l i t y s o l u t i o n s Healthy Climate Indoor Air Quality s s that fit your unique needs Healthy Climate Indoor Air Quality s Custom, whole-home product solutions that reduce
More informationApril 2012 Researched and written by Johan Wennerström, R&D Manager at Blueair AB, Stockholm, Sweden.
Blueair White Paper April 2012 Researched and written by Johan Wennerström, R&D Manager at Blueair AB, Stockholm, Sweden. The Growing Threat Of Air Pollution The air we breathe indoors can be up to 100
More informationOn the Architectural Engineering Competences in Architectural Design MSc in Engineering with Specialization in Architecture Kirkegaard, Poul Henning
Downloaded from vbn.aau.dk on: april 04, 2019 Aalborg Universitet On the Architectural Engineering Competences in Architectural Design MSc in Engineering with Specialization in Architecture Kirkegaard,
More informationTo describe human body heat transfer, the concept. Thermal comfort with radiant and convective cooling systems. Articles. REHVA Journal June
Thermal comfort with radiant and convective cooling systems Risto Kosonen Halton Oy and Aalto University risto.kosonen@halton.com Panu Mustakallio Halton Oy The difference in thermal conditions between
More informationClean air is a human right
Clean air is a human right HEPASilent Air Purification Systems 10 tips for choosing the best air purifier 1 Filter efficiency When selecting an air purifier, consider performance first. Compare air purifiers
More informationThe Research of Performance Comparison of Displacement and Mixing Ventilation System in Catering Kitchen *
Journal of Environmental Protection, 2013, 4, 638-646 http://dx.doi.org/10.4236/jep.2013.46073 Published Online June 2013 (http://www.scirp.org/journal/jep) The Research of Performance Comparison of Displacement
More informationExperience just how clean your indoor air can be
Experience just how clean your indoor air can be Life is a miracle that needs clean air Airborne pollutants are constantly bombarding your home causing allergies, asthma, congested sinuses, headaches and
More informationBlueair 500/600 Series. User Manual
Blueair 500/600 Series Blueair 500/600 Series User Manual Contents 2 Welcome 3 Getting started 4 Getting the most from your Blueair system 6 Changing the filters 7 Filters Welcome Thank you for choosing
More informationRe: AHRI Comments on Proposed Addendum be to ASHRAE Standard 189.1
January 31, 2013 Standing Standard Project Committee (SSPC) 189.1 Re: AHRI Comments on Proposed Addendum be to ASHRAE Standard 189.1 Dear Members of SSPC 189.1: These comments are submitted by the Air-Conditioning,
More informationIndoor Air Quality Test Report
Indoor Air Quality Test Report kirk wilson 1216 greenway dr. allen tx 75013-5404 Test Period 1/8/2006 12:00:00AM 1/11/2006 12:00:00AM Monitor Serial No. 9114 Dear kirk, Today, we spend over 90% of our
More informationHEPASilent Air Purification Systems. Clean air is a human right
HEPASilent Air Purification Systems Clean air is a human right 10 tips for choosing the best air purifier 1 Filter efficiency When selecting an air purifier, consider performance first. Compare air purifiers
More informationLaboratory study on the cooling effect of flash water evaporative cooling technology for ventilation and air-conditioning of buildings
Downloaded from orbit.dtu.dk on: May 5, 218 Laboratory study on the cooling effect of flash water evaporative cooling technology for ventilation and air-conditioning of buildings Fang, Lei; Yuan, Shu;
More informationInvestigation of Thermal Environments in Humid Tropical Classroom in Indonesia
Journal of Engineering and Architecture June 2017, Vol. 5, No. 1, pp. 1-14 ISSN: 2334-2986 (Print), 2334-2994 (Online) Copyright The Author(s). All Rights Reserved. Published by American Research Institute
More informationWORKSHOP VENTILATION- PSYCHROMETRICS-AHU
Alkis Triantafyllopoulos Mechanical Engineer Member TEE, MASHRAE a.trianta@gmail.com WORKSHOP VENTILATION- PSYCHROMETRICS-AHU Based on ASHRAE 62 Purpose Set minimum Outdoor Air ventilation Rates Air Quality
More informationAalborg Universitet. Diffuse Ceiling Inlet Systems and the Room Air Distribution Nielsen, Peter Vilhelm; Jensen, Rasmus Lund; Rong, Li
Aalborg Universitet Diffuse Ceiling Inlet Systems and the Room Air Distribution Nielsen, Peter Vilhelm; Jensen, Rasmus Lund; Rong, Li Published in: Clima 2010 : 10th Rehva World Congress Publication date:
More informationEuropean Cities and Sustainable Urban Planning Practices
European Cities and Sustainable Urban Planning Practices Munich-Berlin-Copenhagen-Stockholm May 8-30, 2019 Jesus J. Lara, PhD Associate Professor City and Regional Planning European Cities and Sustainable
More informationSIMULATION ANALYSIS OF BUILDING HUMIDITY CONTROL AND ENERGY CONSUMPTION FOR DIFFERENT SYSTEM CONFIGURATIONS USA
Ninth International IBPSA Conference Montréal, Canada August 15-18, 25 SIMULATION ANALYSIS OF BUILDING HUMIDITY CONTROL AND ENERGY CONSUMPTION FOR DIFFERENT SYSTEM CONFIGURATIONS Chaoqin Zhai 1, Xiaohong
More informationPassivhaus school kitchens
Passivhaus school kitchens Alan Clarke & Nick Grant, The Woodlands, Whitecroft, Lydney, GL15 4PL, UK 1 Introduction Schools in the UK provide a mid-day meal, usually cooked at the school. Accommodating
More informationIndoor Moisture Control of Auckland Houses with Different Ventilation Systems
Indoor Moisture Control of Auckland Houses with Different Ventilation Systems Bin Su International Science Index, Architectural and Environmental Engineering waset.org/publication/17141 Abstract Auckland
More informationCAP600AWS Compact Air Purifier with Plasma Ionizer USER MANUAL
CAP600AWS Compact Air Purifier with Plasma Ionizer USER MANUAL Thank you for choosing this innovative Air Purifier. Please read this user manual before using the product and keep it safe for future reference.
More informationEnergy consumption in the comfortable home: practices, perceptions and conventions
Energy consumption in the comfortable home: practices, perceptions and conventions PhD defence 21.04.2017 I Line Valdorff Madsen Danish Building Research Institute I AAU-CPH 22/06/2017 1 BACKGROUND UserTEC:
More informationFrancesco Causone CURRICULUM VITAE. Profile Summary. Expertise. Area of Interest
Via Lambruschini 4 20156 Milano, Italy e-mail: francesco.causone@polimi.it tel. +39 02 2399 8621 CURRICULUM VITAE Francesco Causone Profile Summary Expertise Area of Interest LEED AP BD+C REHVA Young Scientist
More informationAn Efficient Cold Store Facility
The following article was published in ASHRAE Journal, September 1997. Copyright 1997 American Society of Heating, Refrigerating and Air-Conditioning Engineers, Inc. It is presented for educational purposes
More informationMechanical Technical Report 1. ASHRAE Standard 62.1 Ventilation Compliance Evaluation
Mechanical Technical Report 1 Standard 62.1 Ventilation Compliance Evaluation Lutheran Theological Seminary at Philadelphia The New Learning Center Prepared For: William P. Bahnfleth, Ph.D., P.E. Department
More informationDirect Ventilation Design. Smart Ventilation Units.
Direct Ventilation Design Smart Ventilation Units www.sav-systems.com Rev: 2 01/08/2018 Optimum indoor climate, minimum energy usage The air is damp and warm. Your eyes are dry and irritated. Your head
More informationHUG+ Product Report. Product report // MSc4 ID3 // May 2014 // Collaboration with Højer Møbler A/S
HUG+ Product Report Product report // MSc4 ID3 // May 2014 // Collaboration with Højer Møbler A/S Kristina Ekkelund Jensen // Rikke Møller // Christine Fanny Olsen Title sheet Project team MSc04 ID3 Master
More informationAN ANALYSIS OF THE ACTUAL THERMAL PLUMES OF KITCHEN APPLIANCES DURING COOKING MODE
AN ANALYSIS OF THE ACTUAL THERMAL PLUMES OF KITCHEN APPLIANCES DURING COOKING MODE R Kosonen 1,*, H Koskela 2 and P Saarinen 2 1 Halton Oy, Haltonintie 1-3, 474 Kausala, Finland 2 Finnish Institute of
More informationVENTILATIVE COOLING CONTROL STRATEGIES APPLIED TO PASSIVE HOUSE IN ORDER TO AVOID INDOOR OVERHEATING
VENTILATIVE COOLING CONTROL STRATEGIES APPLIED TO PASSIVE HOUSE IN ORDER TO AVOID INDOOR OVERHEATING Rebeca Barbosa 1, Martin Barták 1, Jan L. M. Hensen 1, 2, Marcel G. L. C. Loomans 2 1 Czech Technical
More informationNew Standard Requirements and Possibilities using UV-LED lamps for fluorescent Magnetic- Particle- (MPI) and Penetrant Inspection (FPI) in Aerospace
New Standard Requirements and Possibilities using UV-LED lamps for fluorescent Magnetic- Particle- (MPI) and Penetrant Inspection (FPI) in Aerospace 1 Marc Breit Managing Director and Head of development
More informationThermal Environment Evaluation in Commercial Kitchens of United States
Downloaded from orbit.dtu.dk on: Jul 25, 2018 Thermal Environment Evaluation in Commercial Kitchens of United States Simone, Angela; Olesen, Bjarne W. Publication date: 2013 Link back to DTU Orbit Citation
More informationNUMERICAL STUDIES ON BARE CABIN FIRES WITH OPERATION OF SMOKE EXTRACTION SYSTEM
, Volume 11, Number 2, p.43-48, 2012 NUMERICAL STUDIES ON BARE CABIN FIRES WITH OPERATION OF SMOKE EXTRACTION SYSTEM Q. Kui Institute of Building Fire Research, China Academy of Building Research, Beijing,
More informationTHE ROLE OF GREEN ROOFS IN URBAN DRAINAGE A REVIEW OF THE CASE FROM AUGUSTENBORG ECO-CITY
THE ROLE OF GREEN ROOFS IN URBAN DRAINAGE A REVIEW OF THE CASE FROM AUGUSTENBORG ECO-CITY Justyna Czemiel Berndtsson, PhD The work done at Water Resources Eng., Lund University, Sweden Currently Sydvatten
More informationOPTIMUM CLASSROOM ENVIRONMENT, MINIMUM ENERGY USAGE
OPTIMUM CLASSROOM ENVIRONMENT, MINIMUM ENERGY USAGE DESIGN GUIDE SMART VENTILATION UNITS sav-systems.com/smart Rev 3 2018 INTRODUCTION TO SVUs SMART VENTILATION UNITS (SVUs) EVOLVED IN NORDIC SCHOOLS TO
More informationIndoor Pool Design Considerations Colorado Springs, Colorado
Indoor Pool Design Considerations Colorado Springs, Colorado September 20, 2018 Presentation by Eric S. Johnson, P.E. LifeMember, ASHRAE, Austin Chapter DESIGN CONSIDERATIONS HUMIDITY CONTROL FOR INDOOR
More informationIDES-EDU. Educational Package Ventilation. Lecture 1 :Typical ventilation design concepts and strategies IEE/09/631/SI
Educational Package Ventilation Lecture 1 :Typical ventilation design concepts and strategies IEE/09/631/SI2.558225 28.10.2011 Summary Ventilation background Why ventilate? Two ways of building ventilation
More informationWorried aboutthe air quality in your schools?
Worried aboutthe air quality in your schools? Now you can breathe a little easier. (And so can everyone else.) EMA Chicago, Inc. The Situation The Environmental Protection Agency Documented that in 1995
More informationDelivering More Clean Air, At a Faster Rate With Less Noise
Our philosophy Blueair believes in cleaner indoor air for everyone. Removing air impurities down to the tiniest particle requires a deep commitment to continuous innovation and a greener global environment.
More informationMeasuring And Understanding Energy Efficiency
28Mar2011 www.fahrenergy.co.uk P: 1 Measuring And Understanding Energy Efficiency Knowledge makes the difference. It is the base for improvements. INSTRUMENTS NEEDED... 1 INTRODUCTION... 2 ENERGY RECOVERY
More informationHEX390. Balanced Pressure Ventilation with Heat Recovery. for healthy indoor air
HEX390 Balanced Pressure Ventilation with Heat Recovery for healthy indoor air MADE IN NZ HEX390 Made in New Zealand for New Zealand conditions. BALANCED PRESSURE The HEX390 is a balanced pressure system.
More informationCOMPARISON OF THE THERMAL ENVIRONMENT IN ROOMS WITH CHILLED BEAM AND RADIANT PANEL SYSTEMS
COMPARISON OF THE THERMAL ENVIRONMENT IN ROOMS WITH CHILLED BEAM AND RADIANT PANEL SYSTEMS Risto Kosonen, Panu Mustakallio Arsen Melikov 2, Marcin Duszyk 2 Oy Halton Group Ltd., Helsinki, Finland. 2 International
More informationUserGuide. Blueair501/Blueair601 FEATURING HEPASILENT TECHNOLOGY
UserGuide Blueair501/Blueair601 FEATURING HEPASILENT TECHNOLOGY THANK YOU FOR CHOOSING BLUEAIR Ready to start breathing cleaner air? First, read this User Guide to ensure that you use the Blueair 501/Blueair
More informationFIRE DYNAMICS IN FAÇADE FIRE TESTS: Measurement, modeling and repeatability
Proceedings of the International Conference in Dubrovnik, 15-16 October 2015 FIRE DYNAMICS IN FAÇADE FIRE TESTS: Measurement, modeling and repeatability Johan Anderson a, Lars Boström a, Robert Jansson
More informationBlueair EC010. User Manual
Blueair ECO10 Blueair EC010 User Manual Contents 3 Welcome 4 Getting started 6 Getting the most from your Blueair system 7 How it works 8 Changing the filters 10 Specifications 11 Limited Warranty Customer
More informationEFFECTS OF EXTREMELY LOW HUMIDITY ON COMFORT AND FATIGUE OF JAPANESE OCCUPANTS
EFFECTS OF EXTREMELY LOW HUMIDITY ON COMFORT AND FATIGUE OF JAPANESE OCCUPANTS Hitomi Tsutsumi 1, Yoshitaka Hoda 1, Hayato Ohashi 1, Yuta Ezaki 1, Junkichi Harigaya 1, Shin-ichi Tanabe 1, and Toshihiko
More informationAvailable online at Energy Procedia 6 (2011) MEDGREEN 2011-LB
Available online at www.sciencedirect.com Energy Procedia 6 (2011) 759 768 MEDGREEN 2011-LB Comparison of two methods of improving dehumidification in air conditioning systems: hybrid system (refrigeration
More informationA Method to Disaggregate Structural and Behavioral Determinants of Residential Electricity Consumption Stanford ARPA-E Buildings Research
A Method to Disaggregate Structural and Behavioral Determinants of Residential Electricity Consumption Stanford ARPA-E Buildings Research Amir Kavousian, PhD Student Stanford University 1 Outline Background
More informationWhite Bear Lake Area Schools District 624 ENERGY GUIDELINES
White Bear Lake Area Schools District 624 ENERGY GUIDELINES Developed by: White Bear Lake Area Schools Energy Steering Committee as part of the Schools for Energy Efficiency (SEE) Program ISD 624 Energy
More informationBenefits Offered by Passive Dehumidification Wheel Speed Control
Benefits Offered by Passive Dehumidification Wheel Speed Control White paper By John Fischer Benefits Offered by Passive Dehumidification Wheel Speed Control The most significant advantage of the Pinnacle
More information1. COOL ROOFS. What is a Cool Roof
2 COOL ROOFS IN EUROPE: INITIATIVES AND EXAMPLES 1. COOL ROOFS What is a Cool Roof surfaces cool under the sun. This is due to the pro atmosphere. As the roof stays cooler, this reduces the amount of heat
More informationNATURAL VENTILATION CONTROL SYSTEMS
...... CI/SfB (57.9) Uniclass L755 September 2005 NATURAL VENTILATION CONTROL SYSTEMS... . 2 ...... Passivent ventilation control systems have been have been specially developed to meet the requirements
More informationSolar shading control Automated natural ventilation and solar shading control
Solar shading control Automated natural ventilation and solar shading control A joint strategy between two of the most important passive measures in a room, automated natural ventilation and solar shading,
More informationAchieving Dry Outside Air in an Energy-Efficient Manner
AT-01-7-2 Achieving Dry Outside Air in an Energy-Efficient Manner Stanley A. Mumma, Ph.D., P.E. Fellow ASHRAE Kurt M. Shank Student Member ASHRAE ABSTRACT The central thrust of this paper is to develop
More informationPupil Details. Term Dates
Name: NOTEBOOK Pupil Details Name... Head of Year... Tutor... Tutor Room... House... Library No... Locker No... Parent/s signature/s...... Term Dates 2018-2019 Autumn Term Spring Term Summer Term Begin
More informationEnergy consumption in properties
Energy consumption in properties Glenn Malmberg, Availability of energy Energy and the environment are areas that are in focus both globally and nationally, not least since Al Gore travelled around the
More informationHome Performance Science
Home Performance Science Symptoms of a Sick House Too hot/too cold rooms Respiratory problems Headaches/nausea Smoky fireplace Foggy windows Stuffy air and lingering odors Peeling paint Constant dust problems
More informationLecture 1 :Typical ventilation design concepts and strategies
Educational Package Ventilation Lecture 1 :Typical ventilation design concepts and strategies Zoltán MAGYAR, PhD Department of Building Energetics and Building Service Engineering Summary Ventilation background
More informationA GARDEN IN EVERY SCHOOL A SCHOOL IN EVERY GARDEN. March 3, 2016 Workshop
A GARDEN IN EVERY SCHOOL A SCHOOL IN EVERY GARDEN March 3, 2016 Workshop PROGRAM PARTNERS & SPONSORS CALIFORNIA IS IN A HISTORIC DROUGHT Oroville Reservoir August, 2008 Lake Mead February, 2008 This view
More informationfor family composition, time allocation of people, ownership and specification of home appliances. This paper first presents the simulation procedure
Validation of an Energy Demand Model of Residential Buildings Yohei Yamaguchi 1*, Yoshiyuki Shimoda 1 1 Graduate School of Engineering Osaka University, S4 Building, 2-1 Yamadaoka, Suita, Osaka, 565-871,
More informationDemand-Controlled Ventilation For Commercial Kitchens
Demand-Controlled Ventilation For Commercial Kitchens Tetra Images/Corbis By Derek Schrock, Member ASHRAE; Jimmy Sandusky, Associate Member ASHRAE; Andrey Livchak, Ph.D., Member ASHRAE Food service facilities
More informationINDIVIDUAL APARTMENT SUBSTATION TESTING DEVELOPMENT OF A TEST AND INITIAL RESULTS
INDIVIDUAL APARTMENT SUBSTATION TESTING DEVELOPMENT OF A TEST AND INITIAL RESULTS Martin Crane CEng 1, 1 Carbon Alternatives Ltd Keywords: district heating, substation, low return temperature, performance
More informationReducing Allergens and Improving Your Overall Indoor Air Quality
Save Energy. Save Money. Save The Environment. Whitepaper: Reducing Allergens and Improving Your Overall Indoor Air Quality Written By: Mark Cannella Founder & Chief Technical Officer Pro Energy Consultants
More informationDAIKIN S URURU SARARA
DAIKIN S URURU SARARA FOUR TREATMENTS IN ONE UNIT COOL HEAT HUMIDIFY DEHUMIDY PURIFY VENTILATE Daikin Ururu Sarara is a unique split system reverse cycle unit, which can heat and cool, humidify and dehumidify,
More informationCITY OF DANA POINT. COMMUNITY DEVELOPMENT, BUILDING AND SAFETY Golden Lantern, Suite 209 Dana Point, CA
CITY OF DANA POINT COMMUNITY DEVELOPMENT, BUILDING AND SAFETY 33282 Golden Lantern, Suite 209 Dana Point, CA 92629 949 248 3594 www.danapoint.org INDOOR AIR QUALITY B011 AIR 2013 CALIFORNIA CODES CODE
More informationLesson Plan for Fire Safety Starts with You!
Students can be a powerful influence on family and loved ones by taking home fire safety messages learned at school. A great tool for helping them learn about fire safety is The You! activity pamphlet.
More informationEffects of Latent/Sensible Heat Separation Air-Conditioning and Natural Ventilation on Indoor Thermal Environment in Environment-Friendly Office
Effects of Latent/Sensible Heat Separation -Conditioning and Natural Ventilation on Indoor Thermal Environment in Environment-Friendly Office Shotaro Sakai 1,*, Takashi Akimoto 1, Yumiko Miyasaka 2 1 Shibaura
More informationPINNACLE SERIES DEDICATED OUTDOOR AIR SYSTEM ENERGY EFFICIENT DEHUMIDIFICATION
ENERGY EFFICIENT DEHUMIDIFICATION PINNACLE SERIES DEDICATED OUTDOOR AIR SYSTEM Provides a very high degree of latent cooling using only a minimal amount of conventional cooling input Substantial energy
More informationSMART ERV Energy Recovery Ventilator. Build It Tight / Ventilate It Right!
SMART ERV Energy Recovery Ventilator SMART air & energy solutions SMART products include Indoor Air Quality (IAQ) and Energy efficiency products Primarily targeting the residential market Products include:
More informationTwenty Examples of Design/Construction Issues Impacting IAQ
Twenty Examples of Design/Construction Issues Impacting IAQ Dale Walsh, MS, CIH, LEED-AP BD+C Walsh Certified Consultants, Inc. Las Vegas, Nevada AIHA GBIAQ Management Planner Registry Team ASTM D22 Air
More informationBrine Generation Study
DOE/WIPP 00-2000 Brine Generation Study April 2000 Waste Isolation Pilot Plant Carlsbad, New Mexico Processing and final preparation of this report was performed by the Waste Isolation Pilot Plant Management
More informationTHE EFFECT OF HEAT LOAD ARRANGEMENT ON THE PERFORMANCE OF RADIANT PANELS
THE EFFECT OF HEAT LOAD ARRANGEMENT ON THE PERFORMANCE OF RADIANT PANELS Panu Mustakallio 1, Arsen Melikov 2, Marcin Duszyk 2, Risto Kosonen 1 1 Oy Halton Group Ltd., Helsinki, Finland. 2 International
More informationintelligent fire alarm ID60series panels
intelligent fire alarm ID60series panels features LPCB approved to EN54 Parts 2 and 4 One loop capacity (99 sensors and 99 modules) 16 fire zones, 16 non fire zones Supports advanced detection such as
More informationSocial Care Alarms and more moving from analog to digital
Social Care Alarms and more moving from analog to digital Pär Kindstrand I have worked for the municipality since 1986 Assistant nurse for homecare services, in city and rural areas Works with social care
More informationHumidity Control Systems for Civil Buildings in Hot Summer and Cold. Winter Zone in China
Humidity Control Systems for Civil Buildings in Hot Summer and Cold Winter Zone in China Xiaoping Yu Doctoral Candidate Chongqing University of Science & Technology Chongqing, China, 400042 xiaoyup@163.com
More informationDynamic performance of a novel dew point air conditioning for the UK buildings
*Corresponding author: xudongzhao@nottingham. ac.uk Dynamic performance of a novel dew point air conditioning for the UK buildings... Xudong Zhao *, Zhiyin Duan, Changhong Zhan and Saffa B. Riffat School
More informationEXPERIMENTAL STUDY OF CENTRIFUGAL HUMIDIFIER FITTED IN AN INDUSTRIAL SHED LOCATED IN TROPICAL CLIMATES
THERMAL SCIENCE, Year 2011, Vol. 15, No. 2, pp. 467-475 467 EXPERIMENTAL STUDY OF CENTRIFUGAL HUMIDIFIER FITTED IN AN INDUSTRIAL SHED LOCATED IN TROPICAL CLIMATES by Krishnasamy SENTHILKUMAR a* and Pss
More informationTHE AMOUNT OF ACCUMULATED DUST IN DUCTS OF NEW HVAC INSTALLATIONS
THE AMOUNT OF ACCUMULATED DUST IN DUCTS OF NEW HVAC INSTALLATIONS R Holopainen 1*, M Tuomainen 1, V Asikainen 2, P Pasanen 2, J Säteri 3, O Seppänen 1 1 Helsinki University of Technology, Laboratory of
More information