Air conditioning plant with 1 hot water preheater, 1 spray humidifier, 1 chilled water cooling coil and 1 hot water reheater N.Q1 B2 N.X1 B1 N.
|
|
- Abel Carter
- 5 years ago
- Views:
Transcription
1 Air conditioning plant with hot water preheater, spray humidifier, chilled water cooling coil and hot water reheater Air conditioning plant for rooms where the supply air temperature shall be kept constant by heating or cooling and the supply air humidity shall be kept constant by humidifying the supply air. Options: inimum and maximum limitation of the supply air temperature Additional maximum selection from internal and external signal Comfort / Economy changeover Plant diagram N. F N.X5 B27 N.X4 N.2 N. N. B2 N.X B N.X2 N.X (0...0 V) S5 N.D S6 N.D2 S0 Function diagrams Extract air temperature control Dew point temperature control inimum / maximum limitation of the supply air temperature D0 D0 SpSu LI AX D02 LI IN 0 SEHEA SECOOL Ex 0 SE IN Dp Su Legend LI AX LI IN SEHEA SECOOL SpSu SE IN aximum limitation inimum limitation Heating setpoint Cooling setpoint Setpoint supply air temperature Setpoint dew point temperature heating Dp Su Ex Dewpoint sensor temperature Supply air temperature Extract air temperature Controller output ade with the Synco Select ool of Siemens Switzerland Ltd CEen088
2 Description of functions Basic functions he universal controller (N) compares the extract air temperature acquired by the extract air temperature sensor (B2) (alternatively: room temperature acquired by the room temperature sensor (B2a)), with the setpoint. If there is a deviation, the controller will readjust the heating valve () or cooling valve () until the required temperature is reached. he controller also compares the temperature acquired with the dewpoint sensor (B27) with the setpoint. If there is a deviation, the controller will readjust the heating valve () until the required temperature is reached. he fan is released when there is no frost signal and no fault status message for control mode, and when the controller is not in commissioning mode. If the plant is shut down, the heating valve and cooling valve are closed. Frost protection with frost protection monitor If connected to the controller, the frost protection monitor (F) prevents the air temperature downstream from the heating coil from falling below the adjusted frost protection value (typically 5 C). If the air temperature at the frost protection monitor falls below the frost protection value, the controller will open the heating valve and, if required, deactivate release of the fan (relay will drop out). Operating mode selection Comfort / Protection An external switch (e.g. time switch) can be used (S5) to switch the controller s operating mode from Comfort to Protection (PR), or vice versa. Operating mode selection Comfort / Economy An external switch (e.g. manual switch) can be used (S6) to switch the controller s operating mode from Comfort to Economy (ECO), or vice versa. Optional functions inimum and maximum limitation of the supply air temperature o activate this function, a supply air temperature sensor (B) must be connected to input X2 as a limit sensor. If the supply air temperature rises above or drops below the limit value (LI AX = 5 C, LI IN = 6 C preset) the normal control function will be overridden by the limit function with PI mode. Summer / winter compensation his function is activated if an outside sensor (B9) or duct temperature sensor (B9a) is used for acquiring the outside temperature. he values SU-D and WIN-D for setpoint compensation are set to 0 K as standard. In that case, no setpoint compensation will take place. o enable the function, the values of SU-D and WIN-D must be preselected (refer to "Parameter settings"). his means that setpoint compensation acts on the Comfort and the Economy setpoint at high and low outside temperatures. Heating: o enhance comfort, the extract air temperature setpoint is continuously raised when the outside temperature falls in the range from 0 C to 0 C (WIN-S = 0 C and WIN-END = 0 C preset) (winter compensation) Cooling: o save cooling energy and to avoid cooling shocks, the extract air temperature setpoint is continuously raised (summer compensation) when the outside temperature rises in the range from 20 C to 0 C (SU-S = 20 C and SU-END = 0 C preset) External controller signal An output signal of some other controller can be fed to the controller's input X (DC V signal). In that case, the controller delivers the maximum value from the external and the internal signal. Function variants Frost protection with frost protection sensor on the airside he standard frost protection function is configured for using a frost protection monitor (DI), but can be changed for using a frost protection sensor (Fa) on the air-side (DC V). Frost protection with frost protection sensor on the water-side he standard frost protection function is configured for using a frost protection monitor (DI), but can be changed for using a frost protection sensor (Fb) on the water-side (L-Ni 000). 2-5 ade with the Synco Select ool of Siemens Switzerland Ltd CEen088
3 Device list Standard Legend Device name Data Sheet ype reference uantity N Synco 200 universal controller, 2 control N0 RLU22 loops B2 Duct temperature sensor N76 A B27 Duct temperature sensor N76 A port valve + VX odulating valve actuator, + S...6 AC 24 V, DC 0 0 V -port valve + VX odulating valve actuator, + S...6 AC 24 V, DC 0 0 V -port valve + VX odulating valve actuator, + S...6 AC 24 V, DC 0 0 V F Frost protection monitor, with capillary N284 AF8... S5 Digital time switch, channel N524 SEH62. Optional Legend Device name Data Sheet ype reference uantity B Duct temperature sensor N76 A Variants Legend Device name Data Sheet ype reference uantity B2a Room temperature sensor N72 AA24 Fa Frost protection sensor, modulating N82 AF6... Fb Immersion temperature sensor N790 AE For selection of the actuators and valves, refer to the Product Catalog Connection diagram L AC 20 V AC 24 V B B B2 B DC V X X2 X B X4 2 B27 F X5 L N D 2 4 S5 D D2 S6 AC V N N H K Legend K otor contactor "Fan release" S6 Operating mode selector Comfort / Economy H Indicator lamp for "Fan not released" -5 ade with the Synco Select ool of Siemens Switzerland Ltd CEen088
4 Parameter settings Path:... > COIS > APPL ID Parameter Setting Function Remarks Select application Path:... > COIS > PARA >FROS Parameter Setting Function Remarks PE NI Assign L-Ni 000 If, in place of the frost protection monitor, a frost protection sensor L-Ni 000 shall be used PE Assign DC 0..0 V If, in place of the frost protection monitor, a frost protection sensor DC V shall be used Engineering A number of settings are plant-specific and may need adjusting after the initial commissioning of the controller he connection diagram does not show all plant interlocks but only those directly connected to the controller or the associated equipment ade with the Synco Select ool of Siemens Switzerland Ltd CEen088
5 SEP SEP 2 SEP 2 SEP SEP 2 SEP Configuration diagram RLU22 Basic type A 5 (ADF2LUH) X X2 X X4 X5 LABEL LABEL LABEL LABEL LABEL ROO EP % EP FRS SINAL SINAL SINAL x x x x x SINAL SINAL x x x x x x x x x LI SE CAS/CON SHIF LI SE SUPPL AIN DIFF FROS yp yp yp yp y p y p p p2 p p2 y y2 x y y2 x y y2 x y y2 x x x 2 ECH ECH 2 PUP PUP 2 HREC Cooler... Pumpe y y2 x y y2 x y y2 x SEP V SEP LIN SEP BIN AO D D2 CLOOP CLOOP 2 2 ODE PUP PUP 2 2 SE2 SE2 P SE SE P SE4 SE4 P SE5 SE5 P DV AL SE SE P SE4 SE4 P en RELEASE AO AO 2 AO HREC 0B05 2 ade with the Synco Select ool of Siemens Switzerland Ltd CEen088
Immersion Temperature Controller
3 333 Synco 100 Immersion emperature Controller with 2 outputs DC 0 RLE162 Immersion temperature controller for water-side control in heating and cooling plants Compact design with 2 analog control outputs
More informationBoiler Sequence Controller
3 132 Synco 700 Boiler Sequence Controller RK770 odular controller for sequencing up to 6 boilers, for boiler temperature, heating circuit and precontrol; supplied with 18 programmed multiboiler plants
More informationRVD120, RVD140 Controllers for district heating and d.h.w. Basic Documentation
RVD120, RVD140 Controllers for district heating and d.h.w. Basic Documentation Edition 2.0 Controller series A, C CE1P2510en 2018-04-30 Building echnologies Published by: Siemens Switzerland Ltd. Building
More informationRVL480. Heating Controller
2 540 Heating Controller RVL480 Multifunctional and communicating heating controller for use in residential and non-residential buildings. Suited for heating circuit control, boiler temperature control
More informationApplication Sheet Fan coil unit with staged fan, 6-way heating/cooling coil (4 pipe) on analog output
Heating with LHW and cooling with CHW changeover Modulating control of heating/cooling coil 6-way valve (4 pipe) on Automatic or manual 3-speed fan control Room temperature and fan speed operation via
More informationRVL481. Heating Controller. including d.h.w. heating
2 541 Heating Controller including d.h.w. heating RVL481 Multifunctional and communicating heating controller for use in residential and non-residential buildings. Suited for heating circuit control with
More informationRVL472. Heating Controller. Building Technologies HVAC Products. Series C. including d.h.w. heating
2 526 Heating Controller including dhw heating Series C RVL472 Multifunctional heating controller for use in residential and non-residential buildings Suited for: Heating zone control with or without room
More informationROOM THERMOSTATS KNX BASIC DOCUMENTATION
ROOM THERMOSTATS KNX BASIC DOCUMENTATION Contents 2 2 2 2 ABOUT THIS DOCUMENT Document use / request to the reader Target audience, prerequisites Glossary 59 59 60 62 63 HANDLING Mounting and installation
More informationHeating and D.h.w. Controller RVL482 Basic Documentation
Heating and D.h.w. Controller RVL482 Basic Documentation Edition: 1.0 Controller series: A CE1P2542en 20.05.2008 Building Technologies Siemens Switzerland Ltd Building Technologies Group International
More informationApplication Sheet Chilled/heated ceiling (4 pipe) with 6-way valve on analog output
Heating or cooling with chilled ceiling with changeover with 6-way valve on analog output Modulating control of heating and cooling valve Condensation monitoring Room temperature operation via KNX PL-Link
More informationRoom Temperature Controllers
3 021 Room Temperature Controllers for two-pipe fan coil units RCC10 Output for on / off valve actuator Outputs for three-speed fan Control depending on the room or return air temperature (RCC10) Automatic
More informationRVL470. Heating Controller. Use. Functions. Series B
2 522 Heating Controller Series B RVL470 Multifunctional heating controller for use in residential and non-residential buildings; suitable for weather-dependent flow temperature control of heating zones
More informationRDJ10. Room temperature controller with 24-hour time switch and large LCD. For heating systems
3 071 Room temperature controller with 24-hour time switch and large LCD For heating systems RDJ10 Operating modes: Automatic, Comfort, Energy Saving, and Frost Protection Large LCD Battery-powered: 2
More informationRoom thermostat with 24-hour time switch and large LCD
Room thermostat with 24-hour time switch and large LCD RDJ100 Programmable, for heating systems Operating modes: Automatic, Comfort, Energy saving, and Frost protection Large LCD display Battery powered:
More informationRVP360 and RVP361 Heating controllers for 2 heating circuits and d.h.w. Basic Documentation
RVP360 and RVP361 Heating controllers for 2 heating circuits and d.h.w. Basic Documentation Edition 1.0 Controller series A CE1P2546en 15.03.2011 Building Technologies Siemens Switzerland Ltd Industry
More informationQAF64.2-J QAF64.6-J. Frost detector. for use on the air side
s Frost detector for use on the air side QAF64.2-J QAF64.6-J With active capillary tube sensing element for acquiring the lowest temperature within a range of 0 15 C With startup function Operating voltage
More informationPRELIMINARY EDITION
3 131 PRELIMINARY EDITION 14.01.2003 Synco 700 Heating Controllers Heating controller for medium-size and large buildings. The is used as a heating circuit or primary controller. The controller is supplied
More informationSelf-learning Room Temperature Controller
2 257 Self-learning Room emperature Controller 5 operating modes and menu selection via roller selector REV16 Mains-independent room temperature controller Straightforward, self-explanatory menu selection
More informationDistrict Heating Controller
2 510 District Heating Controller for 1 heating circuit and d.h.w. heating RVD120 RVD140 ultifunctional heating controller for use in district heating substations and district heating plants with odbus
More informationRDJ10. Room temperature controller with 24-hour time switch and large LCD. For heating systems
3 071 Room temperature controller with 24-hour time switch and large LCD For heating systems RDJ10 Operating modes: Automatic, Comfort, Energy Saving, and Frost Protection Large LCD Battery-powered: 2
More informationRVP340 Heating controller for 1 heating circuit RVP350 and RVP351 Heating controllers for 1 heating circuit and d.h.w. Basic Documentation
RVP340 Heating controller for 1 heating circuit RVP350 and RVP351 Heating controllers for 1 heating circuit and d.h.w. Basic Documentation Edition 2.0 Controller series A CE1P2545en 2018-07-27 Building
More informationRoom Temperature Controller
3 022 Room Temperature Controller for two-pipe fan coil units with electrical heater RCC20 Outputs for on / off valve actuator and electrical heater Output for three-speed fan Control depending on the
More informationRVL479. Heating Controller. for use with a partner unit
2 543 Heating Controller for use with a partner unit RVL479 Communicating heating controller for use in residential and non-residential buildings. For exclusive use on the bus together with heating controllers
More informationAnswers for infrastructure. HVAC control with Synco simple and energy-efficient
Answers for infrastructure. HVAC control with Synco simple and energy-efficient Synco for enhanced comfort and energy efficiency Buildings place different requirements on HVAC control systems depending
More informationApplication Sheet Fan coil unit with staged fan, heating and cooling coil (4 pipe) on triac output including lighting and blinds operation
Heating with LTHW and cooling with CHW Modulating control of heating and cooling valve (4 pipe) on triac output Automatic or manual 3-speed fan control Including the control of 4 lighting zones & 2 blinds
More informationRoom Temperature Controller
3 331 Synco 100 Room Temperature Controller with 2 outputs DC 0 RLA162 Room temperature controller for basic ventilation, air conditioning and heating plants Compact design with 2 analog control outputs
More informationRVP331. Heating Controller for 2 heating circuits, d.h.w. and boiler. Building Technologies HVAC Products
2 478 Heating Controller for 2 heating circuits, d.h.w. and boiler RVP331 Multi-functional heating controller for use in residential and non-residential buildings Suitable for weather-compensated flow
More informationRVL471 Heating and Domestic Hot Water Controller Basic Documentation
RVL471 Heating and Domestic Hot Water Controller Basic Documentation Edition: 2.2 Controller series: C CE1P2524E 23.10.2002 Siemens Building Technologies HVAC Products 2/118 HVAC Products 23.10.2002 Contents
More informationRoom Temperature Controller
3 22 Room Temperature Controller for two-pipe fan coil units with electrical heater RCC2 Outputs for on / off valve actuator and electrical heater Output for three-speed fan Control depending on the room
More informationRVP310. Heating Controller. Building Technologies HVAC Products
2 475 Heating Controller RVP310 Multifunctional heating controller for use in residential and non-residential buildings; suitable for weather-dependent flow temperature control of heating zones with or
More informationSaving energy while ensuring an enhanced room climate
he worldwide standard for home and building control Saving energy while ensuring an enhanced room climate Lower operating costs without loss of room comfort, thanks to communicating room thermostats Energy-efficient
More informationDistrict heating controller
2 515 District heating controller for 2 heating circuits and d.h.w., communicating RVD260 Multifunctional heating controller for district heat transfer stations and plants with LPB and M-bus communication.
More informationHeating Controller. Building Technologies HVAC Products. Synco 700
3 133 Synco 700 Heating Controller RMH760B Heating controller of modular design for medium-size or large buildings with own heat source or a district heating connection. Can be used as a heating circuit
More informationHeating Controller for 2 heating circuits, d.h.w. and boiler, communicating
2 477 Heating Controller for 2 heating circuits, dhw and boiler, communicating RVP330 Multi-functional heating controller for use in residential and non-residential buildings Suitable for weather-compensated
More informationFrost Units for air temperature monitoring
284 284P0 Frost Units for air temperature monitoring QAF8... Robust aluminium die-cast housing Responds to temperature change sensed over any 30 cm length of capillary Small switching differential Good
More informationApplication Guide siemens.com/thermostats
RDG/RDF room thermostats Application Guide siemens.com/thermostats Application overview 2-pipe el. heater or radiator 4-pipe with el. heater Chilled/ heated ceiling Chilled/heated ceiling with el. heater
More informationTouch Screen Flush-mount Room Thermostats with KNX Communications
s 3 74 RDF800KN RDF800KN/NF ouch Screen Flush-mount Room hermostats with KNX Communications For 2-pipe, 2-pipe with electrical heater, and 4-pipe fan coil units For universal applications For use with
More informationSynco 900 Operating instructions
Synco 900 Operating instructions Edition 2.0 Controller series B CE1B2707en 05.07.2007 We congratulate you on the selection of the Siemens Synco 900 system and thank you for your purchase of the central
More informationRoom Temperature. for 2-pipe fan coil units for compressors in DX type equipment
3 057 RDF110 RDF110/IR RDF110.2 RDF110.2/IR Room Temperature Controllers with LCD for 2-pipe fan coil units for compressors in DX type equipment RDF110 Output for on / off valve actuator or 1-stage compressor
More informationRoom thermostat with KNX communications RDG100KN
s Room thermostat with KNX communications RDG100KN Basic Documentation Edition: 1.0 CE1P3191en 22 Jun 2010 Building Technologies Contents 1. About this document...4 1.1 Revision history...4 1.2 Reference
More informationSynco-GAMMA Application Guide. Hotel buildings. Answers for infrastructure.
Synco-GAMMA Application Guide Hotel buildings Answers for infrastructure. Enhanced comfort and energy efficiency in hotels with Synco and GAMMA building systems Requirements Single source Types of integration
More informationDistrict heating controller
2 513 District heating controller for 1 heating circuit and d.h.w., communicating RVD250 Multifunctional heating controller for district heat transfer stations and plants with LPB and M-bus communication.
More informationDESIGO - Answers for infrastructure. Energy-efficient applications: h,x-controlled Economizer tx2. Application data sheet
DESIGO - Energy-efficient applications: h,x-controlled Economizer tx2 Application data sheet Answers for infrastructure. s 2 Table of contents 1 Introduction to Economizer tx2...5 2 Basics...6 3 Economizer
More informationAutomation System TROVIS 5400 Ventilation Controller TROVIS Mounting and Operating Instructions EB 5477 EN. Electronics from SAMSON
Automation System TROVIS 5400 Ventilation Controller TROVIS 5477 ounting and Operating Instructions Electronics from SASON EB 5477 EN Firmware version 2.0x Edition April 2004 Disclaimer of liability Disclaimer
More informationRoom thermostats with LCD for wall mounting
s 3 181 RDG100 / RDG110 RDG140 / RDG100 RDG100/H Room thermostats with LCD for wall mounting for fan coil unit applications for universal applications for use with compressors in dx type equipment RDG1
More informationDuct Temperature Sensors
1 761 1761P03 1761P01 1761P02 Mounting flange AQM63.0 QAM2110.040, QAM2120.040 QAM2120.200, QAM2120.600 Symaro Duct Temperature Sensors QAM21... Passive sensors for acquiring the air temperature in air
More informationUse. Functions. Key function. Other functions
2 466 Heating Control System RVP102/SET Heating control system for use in smaller plants. Control of boiler temperature through direct burner control, pump control, weather-compensated setpoint (with or
More informationSynco 900 Operating Instructions. Edition 1.0 Controller series 1 CE1B2707en Building Technologies HVAC Products
Synco 900 Operating Instructions Edition 1.0 Controller series 1 CE1B2707en 19.07.2006 Building Technologies HVAC Products We congratulate you on the selection of the Siemens Synco 900 system and thank
More informationSemi flush-mount communicating room thermostats
s 3 7 RDF30, RDF600KN RDF30.50, RDF600KN/S RDF30.50H Semi flush-mount communicating room thermostats For 2-pipe, 2-pipe with electric heater, and 4-pipe fan coil units For use with compressors in DX type
More informationRoom thermostat with Auto Timer, Option External Input
s 1 422 Room thermostat with Auto imer, Option External Input for heating systems RDE100.. Room temperature control 2-position control with On/Off output for heating Comfort, Economy, Auto timer and Protection
More informationRadiant Mixing Block
EFFECTIVE: arch 1, 2004 Taco Radiant ade Easy Application Guide Radiant ixing Block Products & Applications PA09 SUPERSEDES: New OVERVIEW Radiant ixing Block The Taco Radiant ixing Block (RB) is a complete
More informationSauter flexotron 800 ventilation Manual
Manual P100012082 Table of contents DISCLAIMER The information in this manual has been carefully checked and is believed to be correct. Fr. Sauter AG however, makes no warranties as regards the contents
More informationQAW70. Room Unit. Building Technologies. for use with heating controllers
1 637 Room Unit for use with heating controllers QAW70 Digital, multi-functional room unit for the convenient operation of heating controllers from the living room A setpoint knob and an economy button
More informationModel experiment concerning the use of ambient heat with the help of the Peltier heat pump ENT 7.3
Model experiment concerning the use of ambient heat ENT Keywords Peltier effect, Peltier element, cooling engine (chiller), heat pump, thermogenerator, and geothermal energy Principle When direct current
More informationfor central air handling with single- or two-speed fans
3 204 EROYR Controller for central air handling with single- or two-speed fans RWI65.02 Compact unit providing control and supervisory functions, operating voltage C 24 V, signal voltage DC 0...10 V. Use
More informationA comprehensive range of controllers, from stand-alone to communicating for any requirement. HVAC control with Synco Simple and energy-efficient
A comprehensive range of controllers, from stand-alone to communicating for any requirement HVAC control with Synco Simple and energy-efficient Answers for infrastructure and cities HVAC control with Synco
More informationSemi-flush mount communicating room thermostats RDF301, RDF , RDF600KN
s RDF301, RDF600KN RDF301.50 RDF301.50H Semi-flush mount communicating room thermostats RDF301, RDF301.50..., RDF600KN Basic Documentation Edition: 2.2 CE1P3171en 2014-05-23 Building echnologies Contents
More information1 Introduction. Continue with any key. Process
1 Introduction Introduction: There are various ways to heat a room. The type determines how many of which actuators are used. Should the control be realised with a 1-bit or 8-bit group address? In this
More informationQAW70. Room Unit. Siemens Building Technologies HVAC Products. for use with heating controllers
1 37 Room Unit for use with heating controllers Digital, multi-functional room unit for the convenient operation of heating controllers from the living room. A setpoint knob and an economy button allow
More informationRoom thermostat with Auto Timer, Option External Input
s 1 422 Room thermostat with Auto imer, Option External Input for heating systems RDE100.. Room temperature control 2-position control with On/Off output for heating Comfort, Economy, Auto timer and Protection
More informationHeating Controller. Synco 700
3 133 Synco 700 Heating Controller RMH760B Heating controller of modular design for medium-size or large buildings with own heat source or a district heating connection. Can be used as a heating circuit
More informationRoom thermostat with independent DHW control
s 1 421 Room thermostat with independent DHW control for heating systems RDD100.1 DHW Room temperature control 2-position control with ON/OFF control output Independent On/Off control of DHW Comfort, Economy
More informationRoom temperature controller with large LCD. Non-programmable, for heating or cooling systems
3 069 Room temperature controller with large LCD Non-programmable, for heating or cooling systems RDH10 Large LCD Battery-powered: 2 x alkaline batteries type AA, 1.5 V Use he RDH10 is used to control
More informationOJ Waterline control system
OJ Waterline control system THERMOSTATS FOR COMFORT HEATING AND SNOW MELTING Product presentation Mk3 It s all about Room Temperature Control! The essential main goals are: Comfort Flexibility Reliability
More informationRDH10. Room temperature controller with large LCD. Non-programmable, for heating or cooling systems
3 069 Room temperature controller with large LCD Non-programmable, for heating or cooling systems RDH10 Large LCD Battery-powered: 2 x alkaline batteries type AA, 1.5 V Use he RDH10 is used to control
More informationG a
G2474 74 319 0081 0 a en Installation Instructions Heating controllers RVP3... Installation Place of installation In a dry room, e.g. in the boiler room Mounting choices: Control cabinet (in the front,
More informationQFM21... Duct Sensors. Building Technologies HVAC Products. Symaro. for relative humidity and temperature
1 864 1864P01 Symaro Duct Sensors for relative humidity and temperature QFM21 Operating voltage AC 24 V / DC 13535 V Signal output DC 010 V / 420 ma for relative humidity Signal output DC 010 V / 420 ma
More informationRoom thermostats with KNX communications RDG100KN, RDG160KN
s Room thermostats with KNX communications RDG100KN, RDG160KN Basic Documentation Edition: 3.2 CE1P3191en 2014-05-23 Building echnologies Contents 1. About this document... 4 1.1 Revision history... 4
More informationDuct Temperature Sensors
1 762 1761P03 1762P01 Mounting flange AQM630 QAM21 Symaro Duct Temperature Sensors QAM2161040 QAM2171040 Active sensors for acquiring the air temperature in air ducts AC 24 V or DC 13535 V Signal output
More informationSynco living Operating Instructions. Edition 3.0 Controller series C CE1B2707en Building Technologies
s Synco living Operating Instructions Edition 3.0 Controller series C CE1B2707en 23.08.2008 Building Technologies Congratulations on choosing the Siemens Synco living system and thank you for purchasing
More informationRoom thermostats with LCD for wall mounting RDG100 RDG100T RDG110, RDG110U RDG160T, RDG160TU RDG100T/H
s RDG100, RDG110, RDG110U RDG100, RDG160, RDG160U RDG100/H Room thermostats with LCD for wall mounting RDG100 RDG100 RDG110, RDG110U RDG160, RDG160U RDG100/H Basic Documentation Edition 4.1 CE1P3181en
More informationOperating Instructions Heating Controllers RVL479, RVL480, RVL481, RVL482
Operating Instructions Heating Controllers RVL479, RVL480, RVL481, RVL482 Content Overview, display, and symbols... 4 Info button... 7 Operating modes... 8 Switching the heating ON... 9 D.h.w. heating...
More informationTIREE FAN COIL CONTROLLER - T6580
TIREE FAN COIL CONTROLLER - T6580 PRODUCT SPECIFICATION SHEET 20 DESCRIPTION A pleasing and modern appearance makes the TIREE ideal for living quarter applications, in particular offices and hotels. In
More informationDescription of the functions, IQlogic
, IQlogic General Control...168 Status...168 IQnavigator hand-held terminal and image management...169 Dashboard...169 Main setup...170 Air flow Regulation mode...171 Boost...171 Unit...171 Air adjustment...171
More informationRoom thermostat with Auto Timer, Option External Input
s 1 422 Room thermostat with Auto imer, Option External Input for heating systems RDE100.. Room temperature control 2-position control with On/Off output for heating Comfort, Economy, Auto timer and Protection
More informationSelf-learning Room Temperature Controller
2 252 Self-learning Room emperature Controller with one weekly operating mode including individual 24-hour modes and three 24-hour modes, cooling function REV22 Use Mains-independent room temperature controller
More informationQFM21... Duct Sensors. Siemens Building Technologies HVAC Products
For latest prices and delivery to your door visit MyTub Ltd - 0845 303 8383 - wwwmytubcouk - info@mytubcouk 1 864 1864P01 Symaro Duct Sensors for relative humidity and temperature QFM21 Use Operating voltage
More informationWall-mounted room thermostat with LCD
3 182 Wall-mounted room thermostat with LCD for VAV heating and cooling systems RDG400 Modulating PI control Control depending on the room or the return air temperature Output for DC 0 10 V actuator and
More informationDESIGN & TECHNICAL MANUAL
AIR CONDITIONER Wall Mounted type DESIGN & TECHNICAL MANUAL INDOOR AS A09LEC AS A12LEC OUTDOOR AO R09LECN AO R12LECN 1.INDOOR UNIT : AS A09LEC AS A12LEC DTR_AS047E_01 2010.10.05 1. INDOOR UNIT CONTENTS
More informationDistrict heating controller for two heating circuits and d.h.w. according to Siemens specifications:
4 319 2984 0 G2384en en Installation Instructions District heating controller for two heating circuits and d.h.w. RVD240 Installation Place of installation In a dry room, e.g. in the heat exchanger room
More informationWireless room thermostat with LCD
s 1 424 RDD100.1RF RCR100RF Wireless room thermostat with LCD for heating systems RDD100.1RFS Roomom temperature control Comfort, Economy and Protection mode 2-position control with On/Off control output
More informationRoom thermostats with display, for fan coil units RDG100, RDG100T, RDG110, RDG140, RDG160
s RDG1 RDG1 Room thermostats ith display, for fan coil units RDG1, RDG1, RDG11, RDG14, RDG16 Basic Documentation Edition: 1. CE1P3181en 28 May 29 Building echnologies Contents 1 About this document...4
More informationOperating Instructions
Operating Instructions Heating Controller Landis & Staefa RVL469 Overview... 2, 3 Symbols used... 4 Info button... 5 Operating modes... 6 Switching the heating on... 7 Room temperature is not correct...
More informationcontrol sequences model QST / EST Series Table 47: QST / EST Analog Electronic Control Strategies Fan Powered Air Terminals
control sequences Table 47: QST / EST Analog Electronic Control Strategies Control Package Number QST EST FS-A-5000 FSE-A-5000 FS-A-5001 FSE-A-5001 FS-A-5002 FSE-A-5002 FS-A-5003 FSE-A-5003 FS-A-5004 FSE-A-5004
More informationCorrigo E - User Manual Ventilation
Corrigo E - User Manual Ventilation DISCLAIMER The information in this manual has been carefully checked and is believed to be correct. Regin however, makes no warranties as regards the contents of this
More informationSemi-flush mount room thermostats with KNX communications RDU341. Basic Documentation. Edition: 1.2. CE1P3172en Building Technologies
s Semi-flush mount room thermostats with KNX communications RDU341 Basic Documentation Edition: 1.2 CE1P3172en 2017-02-17 Building Technologies Contents 1. About this document... 4 1.1 Revision history...
More informationRoom thermostat with Auto Timer, independent DHW
s 1 423 Room thermostat with Auto Timer, independent DHW for heating systems RDE100.1 DHW Room temperature control 2-position / TPI control with On/Off output for heating Optimum Start / Stop Comfort,
More informationQFM21... Duct sensors. Symaro. for relative humidity and temperature
1 864 1864P01 Symaro Duct sensors for relative humidity and temperature QFM21... Operating voltage AC 24 V / DC 13.5...35 V Signal output DC 0...10 V / 4 20 ma for relative humidity Signal output DC 0...10
More informationFUNCTIONAL DESIGN SPECIFICATION
Issue Date: Issued To: Revision: FUNCTIONAL DESIGN SPECIFICATION Specification Number: SP-XXXX Company Name Signature Date Issued By: Manutec Ltd. Approved By: Approved By: Approved By: Approved By: Authorised
More informationRoom thermostats with LCD for wall mounting RDG100, RDG100T, RDG110, RDG140, RDG160, RDG100T/H
s RDG1 RDG1 RDG1/H Room thermostats ith LCD for all mounting RDG1, RDG1, RDG11, RDG14, RDG16, RDG1/H Basic Documentation Edition 2. CE1P3181en 14 Dec 211 Building echnologies Contents 1 About this document...4
More informationRoom Temperature Controller with LCD
3 053 Room Temperature Controller ith LCD for 4-pipe fan coil units for compressors in DX type equipment ith reversing valve Outputs for on / off valve actuators Outputs for 2-stage compressor ith reversing
More informationP20. ECL Comfort. User's Guide. Installer's Guide. ECL Comfort P20. User's Guide. Installer's Guide *VI7BD502* *087R8014* *087R8014* *VI7BD502*
User's Guide VI.7B.D5.02 2005.10 P20 *VI7BD502* *087R8014* www.danfoss.com ECL Comfort User's Guide ECL Comfort Installer's Guide www.danfoss.com *087R8014* *VI7BD502* Boiler controller P20 VI.7B.D5.02
More informationAquastats. Aquatrol Indoor/Outdoor Control. Automatic Changeover Switch 16/05/08
16/05/08 Aquatrol Indoor/Outdoor Control B3 Adjustable settings for boiler maximum temperature, boiler minimum temperature and outdoor low (design) temperature Selectable Warm Weather Shut Down (WWSD)
More informationAutomation System TROVIS 5400 Boiler Controller TROVIS 5474
Automation System TROVIS 5400 Boiler Controller TROVIS 5474 Application Weather-sensitive control of up to two boilers, designed for single-stage, two-stage or also modulating operating mode. Communication
More informationSet 12 - Safety for Buildings Task
Task Monitor the basement for unforeseen water with a water sensor Monitor the ground water level below the basement with a float switch Monitor the basement ducts or windows for housebreaking with reed
More informationRVS43.. RVS63.. AVS75.. AVS37.. QAA75.. QAA78.. QAA55.. Albatros2 Boiler controller User Manual. Building Technologies HVAC Products
Albatros2 Boiler controller User Manual Edition 3.0 Controller series B CE1U2354en 23. August 2007 RVS43.. RVS63.. AVS75.. AVS37.. QAA75.. QAA78.. QAA55.. Building Technologies HVAC Products 2/180 HVAC
More informationFlush-mounted room thermostats
s 3 RDF300, RDF300.02, RDF340 RDF600 076 RDF400.01 RDF600 Flush-mounted room thermostats RDF300 RDF340 RDF400 for 2-pipe, 2-pipe with el. heater and 4-pipe fan coil units for use with compressors in DX
More informationRoom thermostat with KNX communications RDG400KN
s Room thermostat with KNX communications RDG400KN Basic Documentation Edition: 1.0 CE1P3192en 20 Jul 2010 Building Technologies Contents 1. About this document...4 1.1 Revision history...4 1.2 Reference
More informationSemi flush-mount room thermostat with KNX communications For VAV heating and cooling systems
s 3 72 Semi flush-mount room thermostat with KNX communications For VAV heating and cooling systems RDU34 KNX bus communications (S-mode and LTE mode) Backlit display PI / P control Outputs for DC 0 0
More informationN M AirControl AHU. Control manual
N 10.63 M 03-2016 AirControl AHU Control manual EN CONTENTS PAGE 1 - MONITORING AND CONTROL 2 1.1 The program 2 1.2 The HMI terminal 2 1.3 The controller 4 1.4 Description of the air handling units 4
More information