1 INTERNATIONAL JOURNAL OF ADVANCED RESEARCH IN ENGINEERING AND TECHNOLOGY (IJARET) International Journal of Advanced Research in Engineering and Technology (IJARET), ISSN ISSN (Print) ISSN (Online) Volume 4, Issue 3, April 2013, pp IAEME: Journal Impact Factor (2013): (Calculated by GISI) IJARET I A E M E PERFORMANCE EVALUATION OF A AIR CONDITIONER ACCORDING TO DIFFERENT TEST STANDARDS K. Ravi Kumar, Asst Prof., Department of Mechanical Engineering, AHCET, Chevella, Ranga Reddy (A.P.), India. K. Ganesh Babu Asst Prof., Department of Mechanical Engineering, SITECH, Chevella, Ranga Reddy (A.P.), India S. Udaya Bhaskar Asso Prof., Department of Mechanical Engineering, AHCET, Chevella, Ranga Reddy (A.P.), India. ABSTRACT The Paper reports on the performance of Air Conditioner at different test standards. The future design of air conditioners is being driven primarily by (a) increased energy efficiency standards and (b) the need to eliminate ozone-depleting working fluids. Various national and international agencies continue to impose more stringent requirements for energy efficiency. In addition, consumer pressure to select units with lower operating costs further drives the need for improved performance. The main objective of this paper is to give wide understand of the standards and to maintain the standard conditions in Psychrometric room (Air conditioner test room), which has been constructed to test the air conditioners and to establish different test procedures. The tests that should be performed in Air conditioner test room are cooling capacity test, power consumption test. The main objective of the manufacturers is to produce the systems according to requirements of customers which can give more cooling, low power consumption, high EER to with stand competition in the market. In every country, the manufacturers follow some standards according to the climatic conditions to test the appliances. Keywords: Psychrometric room; EER; cooling capacity test; power consumption test; climatic conditions 178

2 I INTRODUCTION India falls in the hot zone therefore the comfort air-conditioning has always been felt to be a necessity for mankind. To achieve comfort, heat is extracted from the comfort region and transferred to the environment, which is at a higher temperature. This is done with the help of refrigeration. Though there are many methods to achieve cooling, one process that is predominantly applied in refrigeration equipment and its application is vapor compression cycle. One of the applications of vapor compression system is in Air conditioning units, the more commonly used one is Room Air- till 50Ton. conditioners, and then comes the Packaged systems which are used for higher tonnages Ever since the invention of Air Conditioning as one of Refrigeration application by W H Carrier in US in earlier 19 th Century, there has been a radical change in the methods and process used in manufacturing air-conditioning equipment but there is no change in the principle i.e. Vapor compression system used in the cycle. II.EXPERIMENTAL SETUP Air conditioner test room is constructed according to ASHREA standards. It consistss of two rooms made of adiabatic material of rigid polyurethane, one is indoor side room and another is outdoor side room. The outside room ambient is controlled from 25 o C to 55 o C. While indoor side has either temperature control or load control. For testing or air conditioner, maintaining of temperatures is important so these two rooms are made of adiabatic material. The method use in air conditioner test room for finding capacity is air enthalpy method. These two rooms are separated by an opening in to which the non-ducted equipment (test air conditioner) is mounted which the non-ducted equipment (test air conditioner) is mounted. The equipments associated with air conditioner test room as follows: (a) Panel Boards (b) Split AC Indoor Unit Installation (c) Split AC Outdoor Unit Installation (d) Packaged Air conditioners (e) Humidifiers (f) Code Tester (g) Temperature measuring instrument (h) Heaters (g) Sampling device Fig.1. Psychrometric Laboratory view Fig.2 Split AC Indoor Unit Installation 179

3 Fig.3 Split AC Outdoor Unit Installation Fig.4. Code Tester Fig.5. Temperature Measuring Device III. COOLING CAPACITY TEST AND CALCULATIONS TEST CONDITIONS: The test conditions that should be maintained are as follows: ISO 5151 standard Indoor side Outdoor side DBT o C WBT o C DBT o C WBT o C PROCEDURE Out let of air conditioner (which is going to be tested) is attached to the receiving chamber of the code tester through the proper ducting. Before starting the main switch, ensure that all the switches of panel Board are in disable or not. Before starting the test, clean all the sensors and fill water in all sampling devices. Set the temperatures values, which are going, to be maintained in PID S of the panel boards Switch on the test unit by adjusting dimmer to 230 volts. 180

4 For example: we are maintaining DBT 35 C, WBT-24 c in outdoor side and DBT-27 C, WBT- 19 C indoor side (according to ISO standard) When temperature is stabilized there arithmetic mean value should have Outdoor side conditions o C Outdoor side conditions o C DBT 35±0.3 DBT 27±0.3 WBT 24±0.2 WBT 19±0.2 After stabilization, to maintain the test conditions for 4 hours, and record the data after 30 minutes so that there are 7 set of readings for every 5 min. During this 30 min duration, record the code tester nozzle pressure drop. When receiving chamber pressure shows 0.0 and record code tester DBT and WBT readings also. The sensor temperature that should be recorded are: 102 Indoors side DBT 103 Indoors side WBT 104 Outdoors side DBT 105 Outdoors side WBT 106 Indoor side Code tester DBT 107 Indoor side Code tester WBT Average the recorded data. So that we can get more appropriate one value. For convenience not indoor side room temperature from 102 and 103 sensors and leaving air condition from 106 and 107 sensors. For calculation of CFM: Cfm =C i *A i *Y i * 2D p /p*3600* Where ρ=density of air at the air sampling condition kg/m 3. C i = Discharge co-efficient of its nozzle dimensionless. Ai=Area of the nozzle in m 2. Yi=expansion factor, dimensionless. Dp=pressure drop across the nozzle in Pa. C i, Y i can be calculated from ASHRAE 41 FORMULAE FOR COOLING CAPACITY CALCULATIONS: Volume Flow rate of air Q va (m 3 /sec)= Cfm/ Enthalpy difference D h = Enthalpy of moist air entering - Enthalpy of moist air leaving Mass flow rate of air M a (kg/s) =Volume flow rate of air/specific volume of air Cooling capacity in KW =Mass flow rate of air*enthalpy difference Cooling capacity in Btu/hr=Cooling capacity in KW* Cooling capacity in Ton of refrigeration=cooling capacity in KW/ CALCULATIONS Calculations at 35 o C Ambient: Entering air conditions: DBT o C,WBT o C Saturation pr.at DBT, Ps= *EXP(DBT/(DBT+238.3)* )/1000 = *EXP(27.11/( )* )/1000 = kpa 181

5 Saturation pr. at WBT, P l = *EXP(WBT/(WBT+238.3)* )/1000 v = *EXP(19.27/( )* )/1000 = kpa Actual vapour pressure, l l P v = P v -(((P t - P v )*(DBT-WBT)*(1.8))/( ((1.8*DBT)+32)) = ((( )*( )*(1.8))/( ((1.8*27.11)+32)) = kpa Humidity ratio, W = 0.622*(Pv/(Pt-Pv)) = 0.622*(1.7042/( )) = Enthalpy of moist air, hen = (1.005*DBT) + (W*(2500+(1.88*DBT))) = (1.005*27.11) + ( *(2500+(1.88*27.11))) = kj/kg Specific volume of air, Ven = (287.3*(273+DBT))/((Pt-Pv)*1000) = (287.3*( ))/(( )*1000) Density of moist air, Den = 1/Ven = 1/ = kg/m 3 = m 3 /kg Leaving air conditions: DBT o C,WBT o C Saturation pr. at DBT, Ps = *EXP(DBT/(DBT+238.3)* )/1000 = *EXP(13.78/( )* )/1000 = kpa Saturation pr. At WBT, P = *EXP(WBT/(WBT+238.3)* )/1000 = *EXP(12.25/( )* )/1000 = kpa40 Actual vapour pressure, l Pv = Pv -(((Pt- Pv )*(DBT-WBT)*(1.8))/( ((1.8*DBT)+32)) = ((( )*( )*(1.8))/( ((1.8*13.78)+32)) = kpa Humidity ratio, W = 0.622*(Pv/(Pt-Pv)) = 0.622*(1.3199/( )) = Enthalpy of moist air, hle = (1.005*DBT) + (W*(2500+(1.88*DBT))) = (1.005*13.78) + (0.0082*(2500+(1.88*13.78))) = kj/kg 182

6 Specific volume of air, Vle = (287.3*(273+DBT))/((Pt-Pv)*1000) = (287.3*( ))/(( )*1000) = m 3 /kg Density of moist air, Dle = 1/Vle = 1/ = kg/m 3 Calculations for Cooling capacity : Area, Ai = ((22/7*4)*SQRT(48.66/1000))+((22/7*4)*SQRT(99.43/1000)) = m 2 Cubic flow per minute, Cfm = Ci*Yi*Ai*SQRT((2*Dp)/Dle)*3600* =0.985*0.998* *SQRT((2*445)/1.2138)*3600* = or 543 Volume flow rate,qva= Cfm/ = 543/ Enthalpy difference, Dh = hen-hle = = kj/kg = m 3 /sec Mass flow rate, Ma = Volume flow rate (Qva)/Specific volume of leaving air (Vle) = / = kg/sec Cooling capacity in KW = Mass flow rate (Ma)*Enthalpy difference (Dh) = * = kw Cooling capacity in Btu/hr = cooling capacity in kw* = * = Btu/hr Cooling capacity in TON of refrigeration = cooling capacity in kw / = / = Ton Energy efficiency ratio,eer = (cooling capacity in Btu/hr) / (Input power in watts) = 21032/2240 = Btu/W-hr 183

7 POWER CONSUMPTION TEST Test conditions: The various test conditions that should be maintained for Power consumption test are as Follows:ISO 5151 Standard Indoor side Outdoor side DBT o C WBT o C DBT o C WBT o C CALCULATIONS Power Consumption Test of AC at 35 o C Ambient Power consumed by air conditioner for 24hr = Final Energy meter reading Initial Energy meter reading = = 16.5 Kw-hr Power consumed of 1hr = 16.5/24 =0.687 Kw/hr Power Consumption Test of AC at 46 o C Ambient Power consumed by air conditioner for 24hr = Final Energy meter reading Initial Energy meter reading = = 24.5 Kw-hr Power consumed of 1hr = 24.5/24 =1.021 Kw/hr STARTABILITY TEST Test conditions: - The various test conditions that should be maintained are given below: (a) BIS 1391:1992 Indoor side room C Outdoor side room C Voltage DBT WBT DBT WBT V % &110% of rated voltage. (b) BIS 1391:1992(For Export A &B) Indoor side room C Outdoor side room C Voltage DBT WBT DBT WBT V % &110% of rated voltage % minimum voltage&110% of maximum voltage with dual rated voltage. 184

8 Procedure for Down Trip: (1) Take the cold resistance of the system (i.e. Main, Auxiliary and Total resistances) before starting the system. (2) Start the appliance at 220/ /230V according to the request by maintaining Indoor sideroom DBT27 o C, WBT-19 o C and Outdoor side room DBT-35 o C, WBT-24 o C. After reaching the stable conditions and optimizing for 3 to 4 hours record the data of pressures (standard suction 70±5 psig anddischarge 300±10 psig), temperatures, current and power. Sensors are placed at different places in the appliance to record the temperatures of the following (a) Indoor side room DBT and WBT (b) Outdoor side room DBT and WBT (c) Top shell and bottom shell (d) Condenser in and condenser out (e) Evaporator in an evaporator out (f) Suction line and Discharge line IV RESULTS AND CONCLUSIONS Every product that is manufactured is tested to know how it works and up to what level it can satisfy the requirements of customers. The main objective of this project is testing the Air conditioner appliance according to different standards by maintaining different climatic conditions in Air conditioner test room. The testing includes cooling test, power consumption test. From capacity test, cooling capacity of system at different temperatures is known. Cooling capacity test is done on air conditioner appliance. The specification given by manufacturer for cooling capacity of Air Conditioner at 35 o C ambient is Btu/hr, by conducting capacity test in the Air conditioner test room it is found that its capacity is lower by 1.4% i.e Btu/hr at 35 o C ambient. Similarly cooling capacity at 46 o C and 54 o C ambient is found as 19332Btu/hr and 5582 Btu/hr. Figure 6 EER Vs Temperature Power consumption test is done on air conditioner and found that it consumes when operated for 24 hr 16.5 Kwhr units power i.e kw/hr at 35 o C Ambient. At 46 o C Ambient it is found that it consumes 24.5 Kwhr units of power i.e kw/hr in Air conditioner test room. 185

9 EER Figure 7 Power(Units) Vs Temperature The various factors observed amidst the testing were, amount of charge of refrigerant, pressure drop, suction and discharge pressures, power, current etc. From these work different procedures for testing air conditioners are established. The test results will give awareness to the customers and manufacturers. Useful data is generated for the air conditioning engineers. REFERENCES [1] Akintunde, M.A. 2004b. Experimental Investigation of The performance of Vapor Compression Refrigeration Systems. Federal University of Technology, Akure, Nigeria [2] American Society Heating Refrigeration and Air Conditioning. ASHRAE Hand Book [3] Wernick, B.J. Effectiveness method, RACA journal [4]. C.P Arora, Refrigeration and Air conditioning. Tata McGraw-Hill Book Company [5]. Stoecker, W.F. and Jones J.W. (1982), Refrigeration & Air Conditioning. McGraw-Hill Book Company, Singapore [6] Analytical expressions for optimum flow rates in evaporators and condensers of heat pumping systems International Journal of Refrigeration, Volume 33, Issue 7, November 2010, Pages Granryd, E. [7] Yumrutas R, kunduz M, Kanoglu M. Exergy analysis of vapor compression refrigeration systems. Exergy, An international journal 2002;2(4); [8] Dr.S.S. Banwait and Dr.S.C. Laroiya, Properties of refrigerant and psychometric tables and charts [9] Technical Manual Air-conditioning application, Tecumseh. Tecumseh Products India Pvt. Ltd., Hyderabad. [10] Calorimeter Test Facility Lab manual (CTFLM) Tecumseh Products India Pvt. Ltd. [11] Eckert, E.R.G.; Goldstein, R.J.; Ibele, W.E.; Patankar, S.V.; Simon, T.W.; Strykowski, P.J.; Tamma, K.K.; Kuehn, T.H.; Bar-Cohen, A.; Heberlein, J.V.R.; (Sep 1997), Heat transfer--a review of 1994 literature, International Journal of Heat and Mass Transfer 40-16, [12] N. Thangadurai and Dr. R. Dhanasekaran, Effective Power Consumption Model for a Network With Uniform Traffic Pattern, International Journal of Computer Engineering & Technology (IJCET), Volume 3, Issue 2, 2012, pp , ISSN Print: , ISSN Online: [13] Kapil Chopra, Dinesh Jain, Tushar Chandana and Anil Sharma, Evaluation of Existing Cooling Systems for Reducing Cooling Power Consumption, International Journal of Mechanical Engineering & Technology (IJMET), Volume 3, Issue 2, 2012, pp , ISSN Print: , ISSN Online:

Experimental Investigation on Domestic Refrigerator by Shell and Tube Heat Exchanger after the Condenser Using Sub Colling of Refregaring Fluid

Experimental Investigation on Domestic Refrigerator by Shell and Tube Heat Exchanger after the Condenser Using Sub Colling of Refregaring Fluid IOSR Journal of Mechanical and Civil Engineering (IOSR-JMCE) e-issn: 2278-1684,p-ISSN: 2320-334X, Volume 12, Issue 2 Ver. V (Mar - Apr. 2015), PP 63-67 www.iosrjournals.org Experimental Investigation on

More information

Improvement Of Energy Efficiency Ratio Of Refrigerant Compressor

Improvement Of Energy Efficiency Ratio Of Refrigerant Compressor Improvement Of Energy Efficiency Ratio Of Refrigerant Compressor K.Harshavardhan Reddy, M. Rama Narasimha Reddy, A.VENKATASWAMI, Dr M.YOHAN Abstract: - At first glance, calculating the of any type of compression

More information

Optimum Length of a Condenser for Domestic Vapor Compression refrigeration System

Optimum Length of a Condenser for Domestic Vapor Compression refrigeration System Optimum Length of a Condenser for Domestic Vapor Compression refrigeration System T. Mahaboob Basha 1, H.Ranganna 2,G. Maruthi Prasad Yadav 3 1.PG Student, Mechanical Engineering Dept, St Johns College

More information

PERFORMANCE EVALUATION OF TWO STAGE AIR COOLER IN DIFFERENT SPEED

PERFORMANCE EVALUATION OF TWO STAGE AIR COOLER IN DIFFERENT SPEED International Journal of Mechanical Engineering and Technology (IJMET) Volume 7, Issue 3, May June 2016, pp.329 341, Article ID: IJMET_07_03_030 Available online at http://www.iaeme.com/ijmet/issues.asp?jtype=ijmet&vtype=7&itype=3

More information

Effect of Operating Parameters on the Performance of Direct Evaporative Cooler

Effect of Operating Parameters on the Performance of Direct Evaporative Cooler International Journal of Thermal Technologies E-ISSN 2277 4114 2015 INPRESSCO, All Rights Reserved Available at http://inpressco.com/category/ijtt/ Research Article Effect of Operating Parameters on the

More information

Experimental Study on Performance Parameters for Refrigerants R22, R410a and R404a at Various Air Outlet Temperatures

Experimental Study on Performance Parameters for Refrigerants R22, R410a and R404a at Various Air Outlet Temperatures Experimental Study on Performance Parameters for Refrigerants, R41a and R44a at Various Air Outlet Temperatures P. Nagaraju P. G. Student Sanketika Institute of Technology and Management Ch. Kiran Kumar

More information

Analysis of Constant Pressure and Constant Area Mixing Ejector Expansion Refrigeration System using R-1270 as Refrigerant

Analysis of Constant Pressure and Constant Area Mixing Ejector Expansion Refrigeration System using R-1270 as Refrigerant Analysis of Constant Pressure and Constant Area Mixing Ejector Expansion Refrigeration System using R-1270 as Refrigerant Ravi Verma 1, Sharad Chaudhary 2 1, 2 Department of Mechanical Engineering, IET

More information

MECHANICAL DEPARTMENT, OITM SEM: 6 TH REFRIGERATION & AIR-CONDITIONING PAPER: ME-302-E UNIT-I Q.1 (a) Derive an expression for the COP of Bell-Coleman refrigeration cycle in terms of pressure. (10) [May-09]

More information

s. Properties for R134a are as follows : Saturated R-134a Superheated R-134a

s. Properties for R134a are as follows : Saturated R-134a Superheated R-134a CHAPTER 9 REFRIGERATION & AIR-CONDITIONING YEAR 2012 ONE MARK Common Data For Q. 1 and Q.2 A refrigerator operates between 120 kpa and 800 kpa in an ideal vapour compression cycle with R-134a as the refrigerant.

More information

PERFORMANCE OF VCRS SYSTEM WITH HEAT EXCHANGER AND PHASE CHANGE MATERIAL

PERFORMANCE OF VCRS SYSTEM WITH HEAT EXCHANGER AND PHASE CHANGE MATERIAL PERFORMANCE OF VCRS SYSTEM WITH HEAT EXCHANGER AND PHASE CHANGE MATERIAL K.Thejeswarudu 1, R. Meenakshi Reddy 2 and E. Siva Reddy 2 1 PG Student, Department of Mechanical Engineering, G. Pulla Reddy College

More information

Theoretical Performance Analysis Of Direct Evaporative Cooler In Hot And Dry Climates

Theoretical Performance Analysis Of Direct Evaporative Cooler In Hot And Dry Climates INTERNATIONAL JOURNAL OF SCIENTIFIC & TECHNOLOGY RESEARCH VOLUME 3, ISSUE 4, APRIL 214 ISSN 2277-8616 Theoretical Performance Analysis Of Direct Evaporative Cooler In Hot And Dry Climates Ibrahim U. Haruna,

More information

R10. IV B.Tech I Semester Regular/Supplementary Examinations, Nov/Dec REFRIGERATION & AIR-CONDITIONING (Mechanical Engineering)

R10. IV B.Tech I Semester Regular/Supplementary Examinations, Nov/Dec REFRIGERATION & AIR-CONDITIONING (Mechanical Engineering) Set No. 1 IV B.Tech I Semester Regular/Supplementary Examinations, Nov/Dec - 2014 REFRIGERATION & AIR-CONDITIONING (Mechanical Engineering) Time: 3 hours Max. Marks: 75 Answer any FIVE Questions All Questions

More information

Performance of an Improved Household Refrigerator/Freezer

Performance of an Improved Household Refrigerator/Freezer Performance of an Improved Household Refrigerator/Freezer D. O. Ariyo Department of Mechanical Engineering, School of Engineering, Federal Polytechnic, Offa, Nigeria Y. L. Shuaib-Babata Department of Mechanical

More information

Performance Evaluation of R290 as Substitution to R22 & Mixture of Them in Vapour Compression Refrigeration System

Performance Evaluation of R290 as Substitution to R22 & Mixture of Them in Vapour Compression Refrigeration System Performance Evaluation of R29 as Substitution to & Mixture of Them in Vapour Compression System Pawan Kumar Mishra #1, Amol Tripathi *2 #RIT Department of Mechanical Engineering Department, RGPV,Bhopal

More information

Performance Enhancement of Refrigeration Cycle by Employing a Heat Exchanger

Performance Enhancement of Refrigeration Cycle by Employing a Heat Exchanger Performance Enhancement of Refrigeration Cycle by Employing a Heat Exchanger Abstract Shoeb J. Inamdar 1 H.S. Farkade 2 M. Tech student. (Thermal Engineering) 1, Asst. Professor 2 Department of Mechanical

More information

UNIT 1 AIR CONDITIONING 1. Write the various psychometric processes? Explain any four processes with neat sketches?

UNIT 1 AIR CONDITIONING 1. Write the various psychometric processes? Explain any four processes with neat sketches? SIDDHARTH INSTITUTE OF ENGINEERING & TECHNOLOGY :: PUTTUR (AUTONOMOUS) (Approved by AICTE, New Delhi & Affiliated to JNTUA, Anantapuramu) (Accredited by NBA & Accredited by NAAC with A Grade) (An ISO 9001:2008

More information

EXPERIMENTAL INVESTIGATION OF COMPARISION OF AIR COOLED AND WATER COOLED CONDENSER ATTACHED WITH COOLING TOWER

EXPERIMENTAL INVESTIGATION OF COMPARISION OF AIR COOLED AND WATER COOLED CONDENSER ATTACHED WITH COOLING TOWER EXPERIMENTAL INVESTIGATION OF COMPARISION OF AIR COOLED AND WATER COOLED CONDENSER ATTACHED WITH COOLING TOWER Gourav Roy; Taliv Hussain; Rahul Wandra Department of Mechanical Engineering, Lovely Professional

More information

Teaching and Examination Scheme PAPER HRS TH PR OR TW TOTAL TH TU PR

Teaching and Examination Scheme PAPER HRS TH PR OR TW TOTAL TH TU PR Course Name : Diploma in Mechanical Engineering Course Code : ME/MH/MI Semester : Sixth for ME and Seventh for MH/MI Subject Title : (Elective) Subject Code : 17612 Teaching and Examination Scheme Teaching

More information

ME 410 MECHANICAL ENGINEERING SYSTEMS LABORATORY MASS & ENERGY BALANCES IN PSYCHROMETRIC PROCESSES EXPERIMENT 3

ME 410 MECHANICAL ENGINEERING SYSTEMS LABORATORY MASS & ENERGY BALANCES IN PSYCHROMETRIC PROCESSES EXPERIMENT 3 ME 410 MECHANICAL ENGINEERING SYSTEMS LABORATORY MASS & ENERGY BALANCES IN PSYCHROMETRIC PROCESSES EXPERIMENT 3 1. OBJECTIVE The objective of this experiment is to observe four basic psychrometric processes

More information

Design, Manufacturing of Chilled Water System for Process Cooling Application

Design, Manufacturing of Chilled Water System for Process Cooling Application IJSTE - International Journal of Science Technology & Engineering Volume 2 Issue 11 May 2016 ISSN (online): 2349-784X Design, Manufacturing of Chilled Water System for Process Cooling Application Prof.

More information

Energy Consumption Reduction of AHU using Heat Pipe as Dehumidifier

Energy Consumption Reduction of AHU using Heat Pipe as Dehumidifier Energy Consumption Reduction of AHU using Heat Pipe as Dehumidifier Rohit R. Parab Mechanical Engineering Department Vishwakarma Institute of Technology, Pune, India Laxmikant D. Mangate Mechanical Engineering

More information

Institute of Aeronautical Engineering (Autonomous) Dundigal, Hyderabad B.Tech (III II SEM) MECHANICAL ENGINEERING

Institute of Aeronautical Engineering (Autonomous) Dundigal, Hyderabad B.Tech (III II SEM) MECHANICAL ENGINEERING Institute of Aeronautical Engineering (Autonomous) Dundigal, Hyderabad- 500 043 B.Tech (III II SEM) MECHANICAL ENGINEERING REFRIGERATION AND AIR CONDITIONING Prepared by, Dr. CH V K N S N Moorthy, Professor

More information

Performance Evaluation of R290 as Substitution to R22 & Mixture of Them in Vapour Compression Refrigeration System

Performance Evaluation of R290 as Substitution to R22 & Mixture of Them in Vapour Compression Refrigeration System Performance Evaluation of R290 as Substitution to R22 & Mixture of Them in Vapour Compression Refrigeration System Pawan Kumar Mishra #1, Amol Tripathi *2 # RIT Department of Mechanical Engineering Department,

More information

ANALYSIS OF DESICCANT COOLING SYSTEM

ANALYSIS OF DESICCANT COOLING SYSTEM Int. J. Mech. Eng. & Rob. Res. 2012 Gaurav Pundir and S N Mishra, 2012 Research Paper ISSN 2278 0149 www.ijmerr.com Vol. 1, No. 3, October 2012 2012 IJMERR. All Rights Reserved ANALYSIS OF DESICCANT COOLING

More information

Numerical Simulation of Window Air Conditioner

Numerical Simulation of Window Air Conditioner Numerical Simulation of Window Air Conditioner Mathewlal T 1, Kalpesh Patil 2, Gauri Thorat 3, Anisha Ankush 4, Ambarish Pote 5, Kartik Doshi 6 ( 1 Associate ProfessorMechanical Engineering Department,

More information

Design and Development of Water Cooled Condenser for Domestic Refrigerator

Design and Development of Water Cooled Condenser for Domestic Refrigerator Design and Development of Water Cooled Condenser for Domestic Refrigerator Anil S. Patil Research PG Student, GF s Godavari College of Engineering, Jalgaon Dr. Atul A Patil Assot. Prof. GF s Godavari College

More information

R07. Answer any FIVE Questions All Questions carry equal marks *****

R07. Answer any FIVE Questions All Questions carry equal marks ***** Set No: 1 III B.Tech. II Semester Supplementary Examinations, April/May 2013 REFRIGERATION AND AIR CONDITIONING (Mechanical Engineering) Time: 3 Hours Max Marks: 80 Answer any FIVE Questions All Questions

More information

Keywords : Evaporative cooling, Saturation efficiency, Cooling capacity, Cooling pad, Cellulose, Aspen, Coconut coir. IJSER

Keywords : Evaporative cooling, Saturation efficiency, Cooling capacity, Cooling pad, Cellulose, Aspen, Coconut coir. IJSER International Journal of Scientific & Engineering Research, Volume 5, Issue 10, October-2014 676 Performance Evaluation of Alternative Evaporative Cooling Media Rajesh Maurya*, Dr. Nitin Shrivastava, Vipin

More information

η second law = Second law efficiency

η second law = Second law efficiency EXERGY ANALYSIS OF VAPOUR COMPRESSION REFRIGERATION CYCLE BASED AUTOMOTIVE AIR CONDITIONER USING ECO FRIENDLY REFRIGERANTS Vijender Singh Saini 1, Balvinder 2, Pardeep Kumar 3 1 M.Tech Scholar, 2,3 Assistant

More information

Modified Air Cooler with Split Cooling Unit

Modified Air Cooler with Split Cooling Unit Modified Air Cooler with Split Cooling Unit Nishant Dhanore 1, Krishna Shrivastava 2 1 SSBT s College of Engineering and Technology, Jalgaon (M.S.), India 2 Associate Professor, Mech. Engg. Dept. SSBT

More information

SIDDHARTH GROUP OF INSTITUTIONS :: PUTTUR Siddharth Nagar, Narayanavanam Road AUTONOMOUS QUESTION BANK (DESCRIPTIVE) UNIT I

SIDDHARTH GROUP OF INSTITUTIONS :: PUTTUR Siddharth Nagar, Narayanavanam Road AUTONOMOUS QUESTION BANK (DESCRIPTIVE) UNIT I SIDDHARTH GROUP OF INSTITUTIONS :: PUTTUR Siddharth Nagar, Narayanavanam Road 517583 AUTONOMOUS QUESTION BANK (DESCRIPTIVE) Subject with Code : Refrigeration and Air Conditioning (16ME8806) Course & Branch:

More information

Performance Optimization of the Evaporative Condenser Design

Performance Optimization of the Evaporative Condenser Design Performance Optimization of the Evaporative Condenser Design Mit. C. Patel P.G.Student, Mech. Engg.Dept. Institute of Technology, Nirma University, Ahmadabad, Prof. B. A. Shah Mechanical Engineering Department

More information

PERFORMANCE OF DEEP FREEZER BY USING HYDROCARBON BLENDS AS REFRIGERANTS

PERFORMANCE OF DEEP FREEZER BY USING HYDROCARBON BLENDS AS REFRIGERANTS Int. J. Chem. Sci.: 14(S2), 2016, 665-674 ISSN 0972-768X www.sadgurupublications.com PERFORMANCE OF DEEP FREEZER BY USING HYDROCARBON BLENDS AS REFRIGERANTS J. THAVAMANI *, MARRIPUDAGALA KOMALI, SHAIK

More information

ME 410 MECHA ICAL E GI EERI G SYSTEMS LABORATORY

ME 410 MECHA ICAL E GI EERI G SYSTEMS LABORATORY ME 410 MECHA ICAL E GI EERI G SYSTEMS LABORATORY MASS & E ERGY BALA CES I PSYCHROMETRIC PROCESSES EXPERIME T 3 1. OBJECTIVE The object of this experiment is to observe four basic psychrometric processes

More information

Air Conditioning System with Modified Condenser Ducts and Evaporative Cooling

Air Conditioning System with Modified Condenser Ducts and Evaporative Cooling Air Conditioning System with Modified Condenser Ducts and Evaporative Cooling Dr. Akash Langde 1, Zeeshan Jamal 2, Shahrukh Jamal 3, Mohammad Shumoil Ansari 4 1Professor, Department of Mechanical Engineering,

More information

Waghmare Tushar Ramrao, D.S.Nakate

Waghmare Tushar Ramrao, D.S.Nakate International Engineering Research Journal Performance analysisof vapor compression system by using capillary tube suction line heat exchanger and helical condenser for R134a Waghmare Tushar Ramrao, D.S.Nakate

More information

Performance Comparison of Ejector Expansion Refrigeration Cycle with Throttled Expansion Cycle Using R-170 as Refrigerant

Performance Comparison of Ejector Expansion Refrigeration Cycle with Throttled Expansion Cycle Using R-170 as Refrigerant International Journal of Scientific and Research Publications, Volume 4, Issue 7, July 2014 1 Performance Comparison of Ejector Expansion Refrigeration Cycle with Throttled Expansion Cycle Using R-170

More information

Experimental Study of Modified Refrigerator Cum Air Conditioning and Water Cooler System

Experimental Study of Modified Refrigerator Cum Air Conditioning and Water Cooler System 216 IJSRSET Volume 2 Issue 4 Print ISSN : 2395-199 Online ISSN : 2394-499 Themed Section: Engineering and Technology Experimental Study of Modified Refrigerator Cum Air Conditioning and Water Cooler System

More information

ME Mechanical Engineering Systems Laboratory. Experiment 3 - Mass and Energy Balances in Psychrometric Processes

ME Mechanical Engineering Systems Laboratory. Experiment 3 - Mass and Energy Balances in Psychrometric Processes ME 410 - Mechanical Engineering Systems Laboratory Experiment 3 - Mass and Energy Balances in Psychrometric Processes Assist.Prof.Dr. Özgür BAYER, A-123 AIR-CONDITIONING (A/C) Goal: Control temperature

More information

Enhancement of COP in Vapour Compression Refrigeration System

Enhancement of COP in Vapour Compression Refrigeration System Enhancement of COP in Vapour Compression Refrigeration System M. Krishna Prasanna #1 M.E student, Heat Transfer studies in Energy Systems Department of Mechanical Engg., Andhra University Visakhapatnam-530003,

More information

Experimental Investigations of Different Types of Condensers on the Performance of Household Refrigerators

Experimental Investigations of Different Types of Condensers on the Performance of Household Refrigerators IJIRST International Journal for Innovative Research in Science & Technology Volume 3 Issue 11 April 2017 ISSN (online): 2349-6010 Experimental Investigations of Different Types of Condensers on the Performance

More information

Dhulapally, Secunderabad Subject: REFRIGERATION AND AIR CONDITIONING QUESTION BANK

Dhulapally, Secunderabad Subject: REFRIGERATION AND AIR CONDITIONING QUESTION BANK St.MARTIN S ENGINEERING COLLEGE Dhulapally, Secunderabad-500 014 Subject: REFRIGERATION AND AIR CONDITIONING Class : ECE III 1 Define Unit of refrigeration. 2 Define C.O.P. QUESTION BANK 3 What is the

More information

Performance of window air conditioner using alternative refrigerants with different configurations of capillary tube

Performance of window air conditioner using alternative refrigerants with different configurations of capillary tube ISSN: 2347-3215 Volume 1 Number 4 (2013) pp. 46-54 www.ijcrar.com Performance of window air conditioner using alternative refrigerants with different configurations of capillary tube Richa Soni 1*, P.K.Jhinge

More information

Subscripts 1-4 States of the given system Comp Compressor Cond Condenser E Evaporator vol Volumetric G Gas L Liquid

Subscripts 1-4 States of the given system Comp Compressor Cond Condenser E Evaporator vol Volumetric G Gas L Liquid Simulation Analysis of Compression Refrigeration Cycle with Different Refrigerants P.Thangavel, Dr.P.Somasundaram, T.Sivakumar, C.Selva Kumar, G.Vetriselvan Abstract --- In this analysis, the performance

More information

Design & Fabrication of Hybrid Cooler

Design & Fabrication of Hybrid Cooler IJIRST International Journal for Innovative Research in Science & Technology Volume 2 Issue 11 April 2016 ISSN (online): 2349-6010 Design & Fabrication of Hybrid Cooler Shashank Chauragade Mukul Kshirsagar

More information

COMPARATIVE ANALYSIS OF SINGLE AND DOUBLE EFFECT LiBr-WATER ABSORPTION SYSTEM

COMPARATIVE ANALYSIS OF SINGLE AND DOUBLE EFFECT LiBr-WATER ABSORPTION SYSTEM COMPARATIVE ANALYSIS OF SINGLE AND DOUBLE EFFECT LiBr-WATER ABSORPTION SYSTEM Suhail Ahmad Khan Department of Mechanical Engineering, Aligarh Muslim University, Aligarh (India) ABSTRACT Energy analysis

More information

TEST REPORT #47. System Drop-in Test of R-32 and Refrigerant Blends ARM-71a, HPR2A, L-41-2 and DR-5A in a Five-Ton R-410A Rooftop Packaged Unit

TEST REPORT #47. System Drop-in Test of R-32 and Refrigerant Blends ARM-71a, HPR2A, L-41-2 and DR-5A in a Five-Ton R-410A Rooftop Packaged Unit Air-Conditioning, Heating, and Refrigeration Institute (AHRI) Low-GWP Alternative Refrigerants Evaluation Program (Low-GWP AREP) TEST REPORT #47 System Drop-in Test of R-32 and Refrigerant Blends ARM-71a,

More information

S.A. Klein and G.F. Nellis Cambridge University Press, 2011

S.A. Klein and G.F. Nellis Cambridge University Press, 2011 12.A-1 A mixture of helium and water vapor is flowing through a pipe at T= 90 C and P = 150 kpa. The mole fraction of helium is y He = 0.80. a.) What is the relative humidity of the mixture? b.) What is

More information

Performance of Shell and Tube Heat Exchanger under Varied Operating Conditions

Performance of Shell and Tube Heat Exchanger under Varied Operating Conditions Performance of Shell and Tube Heat Exchanger under Varied Operating Conditions N. Prabhu Kishore 1, N. Alekhya 2, J. Ugandhar 3 Asst. Professor, Department of Mechanical Engineering, MLR Institute of Technology,

More information

Volume 3, Issue 4 (2015) ISSN International Journal of Advance Research and Innovation

Volume 3, Issue 4 (2015) ISSN International Journal of Advance Research and Innovation Thermodynamic Comparison Using HFO-1234yf and HFO-1234ze in the Refrigeration s and in Applications R. S. Mishra Department of Mechanical Engineering, Delhi Technological University, Delhi, India Article

More information

INSTITUTE OF AERONAUTICAL ENGINEERING

INSTITUTE OF AERONAUTICAL ENGINEERING 1 P a g e INSTITUTE OF AERONAUTICAL ENGINEERING (Autonomous) Dundigal, Hyderabad -00 043 MECHANICAL ENGINEERING QUESTION BANK Name : REFRIGERATION AND AIR CONDITIONING Code : A60334 Class : III B. Tech

More information

Performance and Analytical Study of Cooler Cum Air Conditioner based on Vapour Compression Refrigeration System

Performance and Analytical Study of Cooler Cum Air Conditioner based on Vapour Compression Refrigeration System IJSTE - International Journal of Science Technology & Engineering Volume 2 Issue 10 April 2016 ISSN (online): 2349-784X Performance and Analytical Study of Cooler Cum Air Conditioner based on Vapour Compression

More information

3. (a) Explain the working of a rotary screw compressor. [10] (b) How the capacity control is achieved in refrigerant compressor?

3. (a) Explain the working of a rotary screw compressor. [10] (b) How the capacity control is achieved in refrigerant compressor? Code No: RR410305 Set No. 1 IV B.Tech I Semester Regular Examinations, November 2006 REFRIGERATION & AIR CONDITIONING (Mechanical Engineering) Time: 3 hours Max Marks: 80 Answer any FIVE Questions All

More information

An Experiment of Heat Exchanger Produces Hot Water Using Waste Heat Recovery from Air Conditioning

An Experiment of Heat Exchanger Produces Hot Water Using Waste Heat Recovery from Air Conditioning ISBN 978-93-84468-94-1 International Conference on Education, Business and Management (ICEBM-2017) Bali (Indonesia) Jan. 8-9, 2017 An Experiment of Heat Exchanger Produces Hot Water Using Waste Heat Recovery

More information

IJSRD - International Journal for Scientific Research & Development Vol. 4, Issue 04, 2016 ISSN (online):

IJSRD - International Journal for Scientific Research & Development Vol. 4, Issue 04, 2016 ISSN (online): IJSRD - International Journal for Scientific Research & Development Vol. 4, Issue 04, 2016 ISSN (online): 2321-0613 Design of Compact Condenser for Waste Heat Recovery and Cop Enhancement of Refrigerator

More information

Thermal Design of Condenser Using Ecofriendly Refrigerants R404A-R508B for Cascade Refrigeration System

Thermal Design of Condenser Using Ecofriendly Refrigerants R404A-R508B for Cascade Refrigeration System Thermal Design of Condenser Using Ecofriendly Refrigerants R404A-R508B for Cascade Refrigeration System A D Parekh, and P R Tailor Abstract Because of damaging effect of CFC refrigerants on stratospheric

More information

An experimental study of the effect of evaporator temperature on the compressor work of a simple vapour compression refrigeration system

An experimental study of the effect of evaporator temperature on the compressor work of a simple vapour compression refrigeration system ISSN (ONLINE): 2321-3051 INTERNATIONAL JOURNAL OF RESEARCH IN AERONAUTICAL AND MECHANICAL ENGINEERING An experimental study of the effect of evaporator temperature on the of a simple vapour compression

More information

EXPERIMENTAL INVESTIGATION OF WATER COOLER SYSTEM BY USING ECO-FRIENDLY REFRIGERANT (R-134a)

EXPERIMENTAL INVESTIGATION OF WATER COOLER SYSTEM BY USING ECO-FRIENDLY REFRIGERANT (R-134a) EXPERIMENTAL INVESTIGATION OF WATER COOLER SYSTEM BY USING ECO-FRIENDLY REFRIGERANT (R-134a) Abstract- With the recent government regulations, of banning the ozone depleting substances and Kyoto protocol

More information

Experimental investigation of Hybrid Nanofluid on wickless heat pipe heat exchanger thermal performance

Experimental investigation of Hybrid Nanofluid on wickless heat pipe heat exchanger thermal performance Experimental investigation of Hybrid Nanofluid on wickless heat pipe heat exchanger thermal performance #1 Jaydev S. Bade, #2 Dr. Nitin U. Korde 1 Department of Mechanical Engineering, Savitribai Phule

More information

IJESRT. Scientific Journal Impact Factor: (ISRA), Impact Factor: 1.852

IJESRT. Scientific Journal Impact Factor: (ISRA), Impact Factor: 1.852 IJESRT INTERNATIONAL JOURNAL OF ENGINEERING SCIENCES & RESEARCH TECHNOLOGY Experimental Study on Performance of Condenser of Two Different Types Used in Window Air Conditioner Madhu Jhariya *1, P.K. Jhinge

More information

Enhancement of COP using Nanoadditives in Domestic Refrigerator

Enhancement of COP using Nanoadditives in Domestic Refrigerator ISSN 2395-1621 Enhancement of COP using Nanoadditives in Domestic Refrigerator #1 Mr.Sajjan Kawade, #2 Prof P.T.Kharat 1 sajjankawade@gmail.com 2 pradip5872@gmail.com #1 P.G. Student, Mechanical Engineering

More information

A Generalized Correlation for Pressure Drop of Refrigerant R-134a through Helical Capillary Tubes

A Generalized Correlation for Pressure Drop of Refrigerant R-134a through Helical Capillary Tubes ISSN 2395-1621 A Generalized Correlation for Pressure Drop of Refrigerant R-134a through Helical Capillary Tubes #1 N. Dhekale, #2 Dr. P. A. Patil 1 amardhekale@gmail.com #12 Research Laboratory, Department

More information

An Investigation Into The Influence Of Improved Refrigeration Cycle And Refrigerants On An Energy Efficient Domestic Refrigerator

An Investigation Into The Influence Of Improved Refrigeration Cycle And Refrigerants On An Energy Efficient Domestic Refrigerator Purdue University Purdue e-pubs International Refrigeration and Air Conditioning Conference School of Mechanical Engineering 2002 An Investigation Into The Influence Of Improved Refrigeration Cycle And

More information

International Journal of Informative & Futuristic Research ISSN (Online):

International Journal of Informative & Futuristic Research ISSN (Online): Reviewed Paper Volume 2 Issue 9 May 2015 International Journal of Informative & Futuristic Research ISSN (Online): 2347-1697 Performance Comparison of R22 and R290 Refrigerants Using Smaller Paper ID IJIFR/

More information

International Journal of Engineering & Technology Sciences Volume 03, Issue 01, Pages 55-64, 2015

International Journal of Engineering & Technology Sciences Volume 03, Issue 01, Pages 55-64, 2015 International Journal of Engineering & Technology Sciences Volume 03, Issue 01, Pages 55-64, 2015 ISSN: 2289-4152 Performance Evaluation of Vapour Compression Refrigeration System Using Double Effect Condensing

More information

[Vali*, 5(2): February, 2016] ISSN: (I2OR), Publication Impact Factor: 3.785

[Vali*, 5(2): February, 2016] ISSN: (I2OR), Publication Impact Factor: 3.785 IJESRT INTERNATIONAL JOURNAL OF ENGINEERING SCIENCES & RESEARCH TECHNOLOGY PERFORMANCE ANALYSIS OF VCR SYSTEM WITH VARYING THE DIAMETERS OF HELICAL CONDENSER COIL BY USING R-134A REFRIGERANT R.Hussain

More information

VORTEX TUBE REFRIGERATION SYSTEM BASED ON COMPRESSED AIR

VORTEX TUBE REFRIGERATION SYSTEM BASED ON COMPRESSED AIR International Journal of Mechanical Engineering and Technology (IJMET) Volume 6, Issue 7, July 2015, pp. 97-102, Article ID: 30120150607012 Available online at http://www.iaeme.com/currentissue.asp?jtype=ijmet&vtype=6&itype=7

More information

Experimentation and Fabrication of Iceplant Using Ecofriendly Refrigerant

Experimentation and Fabrication of Iceplant Using Ecofriendly Refrigerant Experimentation and Fabrication of Iceplant Using Ecofriendly Refrigerant Shubham Rangari 1, Shubham Mahakalkar 2, Shubham Tiple 3, Praharsh Marathe 4, Sameer Bansod 5, Sunnyraj Katam 6, Suraj Nagrare

More information

A/C Cooling Load calculation and measurement

A/C Cooling Load calculation and measurement Testo Inc. 40 White Lake Rd. Sparta NJ 07871 (800) 227-0729 A/C Cooling Load calculation and measurement When we talk about sizing an air conditioning appliance (tons of cooling, BTU/h or KW), we are specifying

More information

ICMIEE-PI Design and Construction of a portable air cooler

ICMIEE-PI Design and Construction of a portable air cooler International Conference on Mechanical, Industrial and Energy Engineering 20 22 December, 20, Khulna, BANGLADESH ICMIEEPI0412 Design and Construction of a portable air cooler Gopesh Dey, Suvro Deb Sikder,

More information

International Research Journal of Engineering and Technology (IRJET) e-issn: Volume: 04 Issue: 05 May p-issn:

International Research Journal of Engineering and Technology (IRJET) e-issn: Volume: 04 Issue: 05 May p-issn: Comparison of Second Law Efficiency and Exergy Analysis of Refrigerants R-12, R-22, R-407C Influenced by Evaporator Temperature for Vapour Compression Refrigeration System Md Ozair Arshad Guest Faculty,

More information

IJISET - International Journal of Innovative Science, Engineering & Technology, Vol. 2 Issue 12, December

IJISET - International Journal of Innovative Science, Engineering & Technology, Vol. 2 Issue 12, December Performance Analysis of Eco-Friendly HC Mixture (R290/R600a) Refrigerant as an Alternative to in a Vapour Compression Refrigeration System for Sub-cooling using Heat Exchanger at Condenser Outlet and Diffuser

More information

Waste Heat Utilization of Vapor Compression Cycle for Operation of Vapor Absorption System

Waste Heat Utilization of Vapor Compression Cycle for Operation of Vapor Absorption System Waste Heat Utilization of Vapor Compression Cycle for Operation of Vapor Absorption System 1 Avnish Chandra Pandey, 2 M. Akash Rao, 3 Sabyasachi Sahoo, 4 Narendra Kumar Students, Department of Mechanical

More information

Development of a Psychrometric Test Chamber. Michael J. Swedish. Associate Professor Mechanical Engineering Department Milwaukee School of Engineering

Development of a Psychrometric Test Chamber. Michael J. Swedish. Associate Professor Mechanical Engineering Department Milwaukee School of Engineering Session 2633 Development of a Psychrometric Test Chamber Michael J. Swedish Associate Professor Mechanical Engineering Department Milwaukee School of Engineering Acknowledgments The design of the Psychrometric

More information

AR/IA/UP 241 Lecture 5: Psychrometrics

AR/IA/UP 241 Lecture 5: Psychrometrics Faculty of Architecture and Planning Thammasat University AR/IA/UP 241 Lecture 5: Psychrometrics Author: Asst. Prof. Chalermwat Tantasavasdi 1. Definition of Psychrometric Chart The word psychrometry is

More information

Comparative Study of Transcritical CO 2 Cycle with and Without Suction Line Heat Exchanger at High Ambienttemperature

Comparative Study of Transcritical CO 2 Cycle with and Without Suction Line Heat Exchanger at High Ambienttemperature International Journal Of Computational Engineering Research (ijceronlinecom) Vol 3 Issue 3 Comparative Study of Transcritical CO 2 Cycle with and Without Suction Line Heat Exchanger at High Ambienttemperature

More information

EXERGY ANALYSIS OF DOMESTIC REFRIGERATOR WITH DIFFERENT REFRIGERANTS

EXERGY ANALYSIS OF DOMESTIC REFRIGERATOR WITH DIFFERENT REFRIGERANTS International Journal of Scientific & Engineering Research Volume 3, Issue 7, July-2012 1 EXERGY ANALYSIS OF DOMESTIC REFRIGERATOR WITH DIFFERENT REFRIGERANTS Rahul ukey, Sharad chaudhary Abstract Electricity

More information

Economical and Energy Efficient Air Conditioner Using Calcium Liquid as a Secondary Refrigerant.

Economical and Energy Efficient Air Conditioner Using Calcium Liquid as a Secondary Refrigerant. Economical and Energy Efficient Air Conditioner Using Calcium Liquid as a Secondary Refrigerant. Rahul Bhoyar, Dept. of Mechanical, BIT, Ballarsha,(rahulbhoyar08@gmail.com) Dr. M. Basavaraj, Dept. of Mechanical,

More information

Effect of Modification in Refrigerant Passage of an Automotive Air Conditioning Compressor

Effect of Modification in Refrigerant Passage of an Automotive Air Conditioning Compressor Purdue University Purdue e-pubs International Compressor Engineering Conference School of Mechanical Engineering 2006 Effect of Modification in Refrigerant Passage of an Automotive Air Conditioning Compressor

More information

Available online at ScienceDirect. Energy Procedia 109 (2017 ) 56 63

Available online at   ScienceDirect. Energy Procedia 109 (2017 ) 56 63 Available online at www.sciencedirect.com ScienceDirect Energy Procedia 109 (2017 ) 56 63 International Conference on Recent Advancement in Air Conditioning and Refrigeration, RAAR 2016, 10-12 November

More information

Use of fourth generation ecofriendly refrigerants in two and three cascade refrigeration systems for reducing global warming and ozone depletion

Use of fourth generation ecofriendly refrigerants in two and three cascade refrigeration systems for reducing global warming and ozone depletion International Journal of Research in Engineering and Innovation Vol-2, Issue-2 (2018), 201-208 International Journal of Research in Engineering and Innovation (IJREI) journal home page: http://www.ijrei.com

More information

0.4 In the preparation of this standard, assistance has been derived from the following standards:

0.4 In the preparation of this standard, assistance has been derived from the following standards: FOREWORD 0.1 Formal clauses will be added later. 0.2 The committee identified IS 10617(Pt 1), IS 10617(Pt 2) and IS 10617(Pt 3) for the first revision in the light of CFC free/hfc refrigerants and need

More information

System-CoolAC. Bharatividyapeeth College of Engineering, Deekshant Bharti Scholar, New Delhi, India

System-CoolAC. Bharatividyapeeth College of Engineering, Deekshant Bharti Scholar, New Delhi, India A Novel Design of Low Cost Domestic Cooling System-CoolAC Abhishek Gandhar Associate Prof., abhishek.gandhar@gmail.com Deekshant Bharti bravo9421@gmail.com Aditya Jain adityajn710@gmailcom Shiv Wadhwa

More information

Study of R-161 refrigerant as an Alternate Refrigerant to various other refrigerants

Study of R-161 refrigerant as an Alternate Refrigerant to various other refrigerants International Journal of Current Engineering and Technology E-ISSN 2277 4106, P-ISSN 2347 5161 2016 INPRESSCO, All Rights Reserved Available at http://inpressco.com/category/ijcet Research Article Study

More information

Performance investigation of Air-conditioning system using ejector as expansion device

Performance investigation of Air-conditioning system using ejector as expansion device International Journal of Current Engineering and Technology E-ISSN 2277 416, P-ISSN 2347 161 216 INPRESSCO, All Rights Reserved Available at http://inpressco.com/category/ijcet Research Article Performance

More information

Experimental Investigation of Closed Loop Oscillating Heat Pipe as the Condenser for Vapor Compression Refrigeration

Experimental Investigation of Closed Loop Oscillating Heat Pipe as the Condenser for Vapor Compression Refrigeration Purdue University Purdue e-pubs International Refrigeration and Air Conditioning Conference School of Mechanical Engineering 2010 Experimental Investigation of Closed Loop Oscillating Heat Pipe as the

More information

EVALUATION OF REFRIGERANT R290 AS A REPLACEMENT TO R22

EVALUATION OF REFRIGERANT R290 AS A REPLACEMENT TO R22 EVALUATION OF REFRIGERANT R290 AS A REPLACEMENT TO R22 Ameya P. Shrivastava 1, Choudhari Chandrakishor S. 2 1,2 Mechanical Department, AISSMS College of Engineering, Pune 411001, (India) ABSTRACT HCFC

More information

HEFAT th International Conference on Heat Transfer, Fluid Mechanics and Thermodynamics Sun City, South Africa Paper number:pp1

HEFAT th International Conference on Heat Transfer, Fluid Mechanics and Thermodynamics Sun City, South Africa Paper number:pp1 HEFAT27 5 th International Conference on Heat Transfer, Fluid Mechanics and Thermodynamics Sun City, South Africa Paper number:pp PERFORMANCE ANALYSIS OF AIR-COOLED CONDENSER USING MICRO-FIN TUBES P.A.Patil

More information

International Engineering Research Journal Performance Analysis of Ejector Based Solar Air Conditioning System

International Engineering Research Journal Performance Analysis of Ejector Based Solar Air Conditioning System International Engineering Research Journal Performance Analysis of Ejector Based Solar Air Conditioning System Aniket Neve, Anita A. Nene Department of Mechanical Engineering, MIT Pune, Savitribai Phule

More information

Experimental Investigations of Heat Pump for Domestic and Light Commercial Market.

Experimental Investigations of Heat Pump for Domestic and Light Commercial Market. Experimental Investigations of Heat Pump for Domestic and Light Commercial Market. Mr. Mohite Sachin Kumar Sr. Lecturer, Mechanical Department,A.G. Patil Polytechnic Institute, Vijapur Road, Solapur (Maharashtra),

More information

Performance Analysis of Li-Br Water Refrigeration System with Double Coil Anti-Swirl Shell and Coil Heat Exchangers

Performance Analysis of Li-Br Water Refrigeration System with Double Coil Anti-Swirl Shell and Coil Heat Exchangers e-issn 2455 1392 Volume 2 Issue 5, May 2016 pp. 108-116 Scientific Journal Impact Factor : 3.468 http://www.ijcter.com Performance Analysis of Li-Br Water Refrigeration System with Double Coil Anti-Swirl

More information

TEST REPORT #4. Travis Crawford Dutch Uselton. Lennox Industries Inc Metrocrest Drive Carrollton, TX 75006

TEST REPORT #4. Travis Crawford Dutch Uselton. Lennox Industries Inc Metrocrest Drive Carrollton, TX 75006 Air-Conditioning, Heating, and Refrigeration Institute (AHRI) Low-GWP Alternative Refrigerants Evaluation Program (Low-GWP AREP) TEST REPORT #4 System Drop-in Test of Refrigerant R-32 in Split System Heat

More information

An Experimental Study of a Simple Vapour Compression Refrigeration System with Varying Parameters

An Experimental Study of a Simple Vapour Compression Refrigeration System with Varying Parameters An Experimental Study of a Simple Vapour Compression Refrigeration System with Varying Parameters #1 Harshad D Kopurwar, #2 Pravin T Nitnaware, #3 Tapobrata Dey 1 harshvardhan1590@gmail.com #1 Mechanical

More information

Experimental Analysis Of Vapour Compression Refrigeration System With Superheating By Using R-134a, R-12, R-717 Refrigerant

Experimental Analysis Of Vapour Compression Refrigeration System With Superheating By Using R-134a, R-12, R-717 Refrigerant Experimental Analysis Of Vapour Compression Refrigeration System With Superheating By Using R-134a, R-12, R-717 Refrigerant Satish parmar 1, Ravindra Randa 2 1M.TECH. Scholar, Department Of Mechanical

More information

Design of LPG Refrigeration System

Design of LPG Refrigeration System Design of LPG Refrigeration System Sethu Sathayan 1, Gopakumar M G 2, Jaya Krishnan S 3, Nanda Gopan 4, Nithin S 6 Assistant Professor, Department of Mechanical Engineering, SNIT Adoor, Kerala, India 1

More information

Performance Characteristics of Air-Conditioner Under Tropical Ambient Condition

Performance Characteristics of Air-Conditioner Under Tropical Ambient Condition Purdue University Purdue e-pubs nternational Refrigeration and Air Conditioning Conference School of Mechanical Engineering 2 Performance Characteristics of Air-Conditioner Under Tropical Ambient Condition

More information

Session: HVAC 101 HVAC 101. Steve Sain Sain Engineering Associates, Inc. August 9, Rhode Island Convention Center Providence, Rhode Island

Session: HVAC 101 HVAC 101. Steve Sain Sain Engineering Associates, Inc. August 9, Rhode Island Convention Center Providence, Rhode Island Session: HVAC 101 HVAC 101 Steve Sain Sain Engineering Associates, Inc. August 9, 2016 Rhode Island Convention Center Providence, Rhode Island Why? 2 Acknowledgements 3 Disclaimer I m gonna shoot down

More information

Design and Development of Combined Direct and Indirect Evaporative Cooling System

Design and Development of Combined Direct and Indirect Evaporative Cooling System ISSN 2395-1621 Design and Development of Combined Direct and Indirect Evaporative Cooling System #1 Pallavi B. Bedre, #2 H.U.Tiwari 1 pallavi.bedre@gmail.com 2 sharvay12 @rediffmail.com #12 Pimpri-Chinchwad

More information

Comparison Simulation between Ventilation and Recirculation of Solar Desiccant Cooling System by TRNSYS in Hot and Humid Area

Comparison Simulation between Ventilation and Recirculation of Solar Desiccant Cooling System by TRNSYS in Hot and Humid Area Comparison Simulation between Ventilation and Recirculation of Solar Desiccant Cooling System by TRNSYS in Hot and Humid Area MMS DEZFOULI, SOHIF MAT, K.SOPIAN Solar Energy Research Institute (SERI, Universiti

More information

PERFORMANCE OF SOLID DESICCANT COOLING WITH SOLAR ENERGY IN HOT AND HUMID CLIMATE

PERFORMANCE OF SOLID DESICCANT COOLING WITH SOLAR ENERGY IN HOT AND HUMID CLIMATE Journal of Sustainability Science and Management Volume 9 Number 1, June 2014: 150-155 ISSN: 1823-8556 Penerbit UMT PERFORMANCE OF SOLID DESICCANT COOLING WITH SOLAR ENERGY IN HOT AND HUMID CLIMATE ARFIDIAN

More information