Specifying High-Efficiency Water Heaters for Food Service
|
|
- Horatio Norton
- 5 years ago
- Views:
Transcription
1 Specifying High-Efficiency Water Heaters for Food Service May 14 th, 2010 Presented by: Don Fisher
2 Water Heater Selection and Specification Selection Efficiency Economics Myths & Limitations Tank versus Tankless Sizing To Meet Food Safety Regulations Recommendations
3 System Efficiency
4 Favorable Economics for Condensing Storage
5 Myth #1 Standby Heat Loss Standby losses can be as high as 30% with storage heaters in residential applications Solution energy benefit of tankless in residential applications will translate to similar savings in restaurants -- FALSE Water Use Storage Heater Standby Heat Loss (gal/d) Standard Efficiency High Efficiency Residential 60 30% 23% QSR % 2.7% FSR % 0.5% Large FSR % 0.3%
6 Myth #2 Tankless is Less Expensive to Operate A fundamental difference: A tank-type heater will always deliver water at or above its thermostat setpoint A tankless heater will always deliver water at or below its thermostat setpoint Field monitoring by FSTC has shown that water supplied by tankless is approx. 10 F below the temperature supplied by a storage heater Thus at the same setpoint, the tankless will inherently use less energy by doing less work
7 Limitations Storage Can run out of hot water during heavy usage if undersized
8 Limitations Tankless Startup sequence creates an additional lag in hot water delivery A couple of seconds before it wakes up seconds before its close to set temperature Cold water sandwich effect Difficulty working with door-type dishwashers and low flow aerators on hand-washing sinks
9 Limitations Tankless Doesn t work well with recirculation systems w/o expansion of system Most heaters are not designed to modulate down to accommodate a 5 to 15 F temp rise May nullify or shorten manufacturer s warranty Making it work requires additional investment Plumbing recirculation line to one sacrificial unit in a multi-unit system may be an option
10 Limitations Filling a 3-compartment sink Faucets typically flow at 15 gpm The 3-comp sink is one of the most demanding hot appliances in QSR and coffee shops Tank-type may fill two 40-gal sinks in 4 minutes One standard eff. tankless takes 14 min in winter At best cond. tankless in summer can fill in 15 min The additional fill time can effect behavior of staff At ~4 gpm flow (199 kbtu/h) several tankless units are needed to meet demand
11 Tank vs. Tankless = 1 condensing tank = 2 condensing tankless Without recirc system Quick-service restaurant
12 Tank vs. Tankless = 2 tanks = 4 tankless+storage tank+pump+controller With recirc system Full-service restaurant
13 Water Heater Sizing for Food Safety Sizing to meet a minimum recovery rate at the highest temperature rise encountered in winter
14 Fixture Types and Fixture Counts Fixture Type Deli QSR Small FSR Large FSR Bathroom sinks Hand sinks Compartment sink Dishmachine Door-type Conveyor Pre-rinse valve 1 1 Mop sink Utility and Prep sinks Dipper well 1
15 Flow Rate Guidelines Fixture Type Tankless (gpm) Tank (gph) Bathroom sinks Hand sinks comp. sink (18 X 18 ) comp. sink (bar) 2 18 Door-type dishwasher 4.4* 30** Conveyor dishwasher Pre-rinse spray valve Mop sink 2 15 Utility sink 2 5 Utensil pre-soak sink 2 5 Dipper well *Rate of rinse flow for door-type rated at 0.74 gal/rack, 58 racks/h and 10 seconds of rinse/rack **Door-type maximum rinse consumption of 43 gph x 0.7 (rack loading factor) = 30 gph
16 Tank-Type Heater Sizing Recovery Rate (gph) Deli QSR Small FSR Large FSR Bathroom sinks Hand sinks compartment sink Dishwasher Pre-rinse spray valve Mop sink Utility or pre-soak sink Dipper well 30 Min. recovery rate (gph)* 54** 66** Minimum input rate (Btu/h) 76,000 76, , ,000 Est. Street price $2,000 $2,000 $4,400 $9,200 *Minimum recovery 90 F temp. rise **Discount factor of 20% for using single service utensils
17 Tankless Heater Sizing Tankless Flow Rate (gpm) Deli QSR Small FSR Large FSR Bathroom sinks Hand sinks compartment sink Dishwasher Pre-rinse spray valve Mop sink Utility or pre-soak sink Dipper well 0.5 Minimum flow rate (gpm)* Minimum input rate (Btu/h) 200, , ,000 1,000,000 Number of condensing heaters Est. street price w/recirculation $1,750 $3,500 $7,000 + $1700 $9,750 + $1700 *Smaller facilities require hot water at 120 F equating to a 70 F temp rise in winter (condensing heater at 5.3 gpm). In larger facilities, a 90 F temp rise is required (4.1 gpm).
18 Number of Occurrences FSR Daily Hot Water Consumption Average = 2100 gal/day Daily Hot Water Consumption (gal)
19 Hot Water Flow (gal/min) 24-Hour Flow Rate Profile min data 6 per. Mov. Avg. (5 min data) 3741 gallons After hours cleaning 550 gal/h :00 4:00 6:00 8:00 10:00 12:00 14:00 16:00 18:00 20:00 22:00 0:00 2:00 Time
20 Water Heater Sizing Recommendations Cleaning practices can heavily sway these requirements, ballooning the minimum recovery rate of storage heaters Sizing for cleanup practices or for redundancy (in case one heater fails) improves the operating life of storage heaters Hosing down a full-service restaurant at 15 gpm requires 450 gallons of hot water over the ½-hour use phase. Two 100 gallon (240,000 Btu/h) heaters are needed to meet this load at a 70 F temperature rise. Approximately 1.5 to 3 times the designed input rate is required to meet the after hours cleanup load.
Hot Water. The Efficiency Challenge!
Hot Water The Efficiency Challenge! and all restaurants use hot water! but how much hot water? How much hot water do you use? Without this you don t know! What we see in the field U.S.
More informationSustainable Hot Water: Better Design, Delivery, and Use
Sustainable Hot Water: Better Design, Delivery, and Use March 24, 2009 Don Fisher Amin Delagah Fisher-Nickel, inc. PG&E Food Service Technology Center The Food Service Technology Center (FSTC) program
More informationRFMA 2016 March 13 15
Your Hot Water System: The Hidden Costs and Opportunities? Amin Delagah Research Engineer 03/15/16 Working with Utilities, Government, & Industry Groups AND the Countless End Users! 1 What we ve been doing
More informationUpdates From an In-Depth Hot Water System Replacement Project in a Full-Service Restaurant
Updates From an In-Depth Hot Water System Replacement Project in a Full-Service Restaurant Restrooms Heater Kitchen Bar Don Fisher Fisher Consultants 02/23/16 Your online toolbox Reports Energy saving
More informationSanitation: Ware Washers, Water Heaters and the Plumbing of the Future
Food Service Technology Center Sanitation: Ware Washers, Water Heaters and the Plumbing of the Food Service Technology Center 1 Water Heating is a System Business As Usual Hot water systems in restaurants
More informationHot Water System Performance Testing at PG&E s Applied Technology Services: Mimicking a Full-Service Restaurant in the Laboratory
Hot Water System Performance Testing at PG&E s Applied Technology Services: Mimicking a Full-Service Restaurant in the Laboratory Amin Delagah Project Engineer Fisher Nickel, a division of Frontier Energy
More informationCommercial Water Heater Performance: Laboratory Testing and Modeling
Commercial Water Heater Performance: Laboratory Testing and Modeling Edwin Huestis, P.E. Mechanical Engineer PG&E Applied Technology Services ACEEE Hot Water Forum November 4, 2013 Presentation Objectives
More informationMultifamily Buildings: Real World Monitored Data on Hot Water Energy and Water Use
Multifamily Buildings: Real World Monitored Data on Hot Water Energy and Water Use BuildingEnergy Boston Conference March 8, 2017 Presented by: Andrew Proulx, P.E., LEED AP Neil Donnelly, E.I.T. New Ecology,
More informationPumped Rinse Dishmachines
Pumped Rinse Dishmachines Michael Slater, Engineer ACEEE Hot Water Forum March 12, 2019 Acknowledgements Learning Objectives Why are dishmachines important to restaurants? How do they work? What is a pumped
More informationBenefits of ENERGY STAR Commercial Water Heaters in the Food Service Industry
Benefits of ENERGY STAR Commercial Water Heaters in the Food Service Industry Nov 5 th, 2012 Presented by: Amin Delagah Lab Research Test Method Development Product Test & Evaluation Field Research Product
More informationThe (Hot) Water Efficient Commercial Kitchen. Charles M. Bohlig East Bay Municipal Utility District
The (Hot) Water Efficient Commercial Kitchen Charles M. Bohlig East Bay Municipal Utility District cbohlig@ebmud.com 2 Foodservice is energy intensive... 600 500 BTU per FT2 400 300 200 100 0 Retail Office
More informationGeneral Session Lab Meets the Real World: Case Studies of Energy Efficient Upgrades that Saved Money
General Session Lab Meets the Real World: Case Studies of Energy Efficient Upgrades that Saved Money Richard Young Saturday, April 16 8:45-10:00 a.m. Presentation by: Richard Young Director of Education
More informationCASE STUDY: HIGH EFFICIENCY HOT WATER SYSTEMS IN A COMMERCIAL KITCHEN. For the 2019 ACEEE Hot Water Forum, Nashville, TN
CASE STUDY: HIGH EFFICIENCY HOT WATER SYSTEMS IN A COMMERCIAL KITCHEN For the 2019 ACEEE Hot Water Forum, Nashville, TN March 12, 2019 Stephen Walmsley 1 4 Purpose and Goals» Understand the importance
More informationPROCEDURE FOR THE SUBMISSION OF A PLAN REVIEW
PROCEDURE FOR THE SUBMISSION OF A PLAN REVIEW 1. Fully complete the plan review application package-be sure to include a phone number for a contact person who can answer questions. 2. Provide a drawing
More informationTOE RIVER HEALTH DISTRICT PLAN REVIEW CHECKLIST
TOE RIVER HEALTH DISTRICT PLAN REVIEW CHECKLIST 1. The plans should be a minimum of 11 X 14 inches with the layout of the floor plan accurately drawn to a minimum scale of 1/4 inches = 1 foot. 2. The plans
More informationGUIDELINES FOR SIZING WATER HEATERS California Conference of Directors of Environmental Health September, 1995
GUIDELINES FOR SIZING WATER HEATERS California Conference of Directors of Environmental Health September, 1995 I. BACKGROUND A critical factor in preventing foodborne illnesses in a food facility is the
More informationInnovative Technologies [and Design Concepts] in Commercial Foodservice
Innovative Technologies [and Design Concepts] in Commercial Foodservice Don Fisher, P. Eng. Fisher Consultants PG&E Food Service Technology Center 925-866-5770 dfisher@fishnick.com Food Service Technology
More informationHow to Heat Water in All-Electric Homes & Apartments?
How to Heat Water in All-Electric Homes & Apartments? March 2015 NEW YORK, NY WASHINGTON, DC NORWALK, CT Robb Aldrich Steven Winter Associates, Inc. raldrich@swinter.com 1 AIA CEU Info Credit(s) earned
More information25 Energy Saving Tips
25 Energy Saving Tips Easy Money Todd Bell, Victor Kong, & Richard Young Copyright 2010 Fisher Nickel. All Rights Reserved. Vern Smith Vernon.A.Smith@gmail.com 720-320-9154 The Food Service Technology
More informationEmerging Technologies in the Dishroom: Exhaust-Air Heat Recovery. May 14 th, 2010 Presented by: Amin Delagah Project Engineer
Emerging Technologies in the Dishroom: Exhaust-Air Heat Recovery May 14 th, 2010 Presented by: Amin Delagah Project Engineer The Relationship of Hot Water Systems and Dishwashers Dishwashers consume 20%
More informationGREASE SEPARATION DEVICE SIZING OPTIONS
GREASE SEPARATION DEVICE SIZING OPTIONS Method 1. Evaluation Based upon 20-25 Minute Hydraulic Retention Grease Separation Device Sizing Table Maximum, worst-case hydraulic loading conditions typified
More informationHigh Efficiency Commercial Water Heating
High Efficiency Commercial Water Heating Cyclone History Production began in 1996 Originally 4 model sizes 300 added in 2003 400 added in 2004 BTX-80 added in 2006 500 added in 2007 Xi redesign BTH/SUF
More informationEnergy Efficient Options for Residential Water Heating
Energy Efficient Options for Residential Water Heating Feb 2018 Ben Schoenbauer, Senior Research Engineer Center for Energy and Environment In accordance with the Department of Labor and Industry s statute
More informationMul$family Buildings: Real World Monitored Data on Hot Water Energy and Water Use
Mul$family Buildings: Real World Monitored Data on Hot Water Energy and Water Use 2015 ACEEE Hot Water Forum February 24, 2015 Presented by: Andrew Proulx, P.E., LEED AP Neil Donnelly, E.I.T. New Ecology,
More informationFood Service Establishment Plan Review Application
ENVIRONMENTAL SERVICES Tel 919 856 7400 Fax 919 743 4772 Plan Review & Recreational Sanitation Section 336 Fayetteville St. P.O. Box 550 Raleigh, NC 27602 www.wakegov.com Food Service Establishment Plan
More informationRetail Food Establishment Plan Review Form
Retail Food Establishment Plan Review Form The Colorado Revised Statutes (CRS) require that complete plans and specifications be submitted, reviewed, and approved before any construction and or remodeling
More informationREGULATIONS GOVERNING WATER SERVICE TO CUSTOMERS OF THE EAST BAY MUNICIPAL UTILITY DISTRICT SECTION 31 WATER EFFICIENCY REQUIREMENTS
PAGE NUMBER 31-A These regulations identify the types of water efficiency requirements for water service and the procedure for notification to Applicants that water efficiency measures are required. The
More informationWater Conservation Information. Regarding water well pump selection
Water Conservation Information Regarding water well pump selection A critical function of the GCGCD groundwater management is conservation of groundwater and prevention of waste. The GCGCD water level
More informationMeasured Performance of Residential Gas Water Heaters
Measured Performance of Residential Gas Water Heaters Dan Cautley ACEEE Hot Water Forum May 13, 2010 Today s topics Intro Efficiency & operating costs Flow in venting system, added infiltration Vent spillage
More informationFood Establishment Plan Review Application
N.C. Department of Health & Human Services Division of Public Health Environmental Health Section Plan Review Unit Food Establishment Plan Review Application Type of Construction: NEW REMODEL Name of Establishment:
More informationThe Revised Method of Test for Residential Water Heating and Its Impact on Incentive Programs
The Revised Method of Test for Residential Water Heating and Its Impact on Incentive Programs Paul Glanville ACEEE Hot Water Forum Tuesday, February 24 th, 2015 Nashville, TN Overview >How Water Heaters
More informationPrecision Temp PT-56 Gas-Fired Booster Heater Performance Tests
Precision Temp PT-56 Gas-Fired Booster Heater Performance Tests Application of ASTM Standard Test Method F 2022-00 FSTC Report 5011.03.28 October 2003 Prepared by: David Cowen David Zabrowski Fisher-Nickel,
More informationHow To Size A Big Dipper Unit
Sizing Big Dipper Systems In Food Service Operations How To Size A Big Dipper Unit The purpose of this sizing procedure is to give a specifying engineer a simple method for determining the proper size
More informationIREDELL COUNTY ENVIRONMENTAL HEALTH
IREDELL COUNTY ENVIRONMENTAL HEALTH Food Protection and Facilities FOOD SERVICE ESTABLISHMENT PLAN REVIEW CHECKLIST* Plans must be a minimum of 11 x 14 inches with the layout of the floor plan accurately
More informationDesign of Precast Concrete Grease Interceptors
Design of Precast Concrete Grease Interceptors Claude Goguen, PE National Precast Concrete Association 2015 Onsite Wastewater Mega Conference Terminology Terminology Terminology Grease is the Word If you
More informationEnergy-Efficiency Options for Residential Water Heating
Energy-Efficiency Options for Residential Water Heating Dave Bohac, PE Director of Research Center for Energy and Environment Duluth Energy Design Conference February, 2015 In accordance with the Department
More informationEvaluating Domestic Water Heater Performance for NY Homes NYSERDA Agreement 15606
Evaluating Domestic Water Heater Performance for NY Homes NYSERDA Agreement 15606 Report 1 Laboratory Test Results Deliverable 7a http://cloud.cdhenergy.com/dhw_lab November 2013 Submitted to: NYSERDA
More informationWATER WISE SURV EY. Santa Barbara City College
WATER WISE SURV EY FI N AL REPORT Santa Barbara City College August 21, 2013 Prepared By City of Santa Barbara Water Conservation Program WATER WISE SURVEY OF SANTA BARBARA CITY COLLEGE EXECUTIVE SUMMARY
More informationMailing Address: City: State: Zip: CONTACT PERSON FOR PLAN STATUS NOTIFICATION: Contact Person: Contact Phone: ( )
Environmental Health 500 N. Main Street Suite #47 Monroe, NC 28112 T. 704.283.3553 unioncountyeh@unioncountync.gov www.unioncountync.gov APPLICATION TYPE: NEW FOOD SERVICE ESTABLISHMENT ($250) - Complete
More informationGrease Interceptors and Oil Separators
Grease Interceptors and Oil Separators 1) All food service establishments and vehicle maintenance facilities shall have devices installed for separating and retaining grease and oils known as grease interceptors
More informationCOMMERCIAL Washington Incentives
COMMERCIAL Washington Incentives MAKE IT YOUR BUSINESS TO SAVE. BRING US IN. COMMERCIAL GAS STANDARD INCENTIVES FOR BUSINESS CUSTOMERS OF NW NATURAL IN WASHINGTON EFFECTIVE JANUARY 2019 ENERGY TRUST OF
More informationAPPENDIX F: GREASE SEPARATION DEVICE SIZING OPTIONS
APPENDIX F: GREASE SEPARATION DEVICE SIZING OPTIONS 55 Method 1. Evaluation Based upon 20-25 Minute Hydraulic Retention Grease Separation Device Sizing Table Maximum, worst-case hydraulic loading conditions
More informationRetail and Medical Marijuana Products Manufacturing Facility Plan Review Form
Retail and Medical Marijuana Products Manufacturing Facility Plan Review Form Prior to inspection for approval and licensing of a retail or medical Marijuana Product Manufacturing Facility for a local
More informationPG&E s Applied Technology Services Hot Water Technology Performance Laboratory
PG&E s Applied Technology Services Hot Water Technology Performance Laboratory Edwin Huestis, P.E. Senior Mechanical Engineer PG&E Applied Technology Services ACEEE Hot Water Forum February 23, 2016 Presentation
More informationHot-Water Circulation
Hot-Water Circulation By delivering hot water to the tap quickly, on-demand systems save water, energy, and time by Leigh Marymor When you turn on a hot-water tap, it can take a long time before hot water
More informationFROM: FORSYTH COUNTY DIVISION OF ENVIRONMENTAL HEALTH
TO: FOODSERVICE ESTABLISHMENT OPERATORS FROM: FORSYTH COUNTY DIVISION OF ENVIRONMENTAL HEALTH This office has been notified of your intent to operate a Foodservice Establishment in Forsyth County. Please
More informationFood Service Plan Review Information
Food Service Plan Review Information New or remodeled food preparation facilities, and those changing ownership, must undergo a plan review process prior to a health permit being issued. The purpose of
More informationHot Water Distribution System Losses in a Net-Zero Home
Hot Water Distribution System Losses in a Net-Zero Home March 22, 2018 ACEEE Hot Water Forum William Healy Tania Ullah National Institute of Standards and Technology Overview of Presentation Purpose: To
More informationenergy-efficient Hot Water Never Looked So Good
the Rinnai Luxury Series tankless Water Heaters energy-efficient Hot Water Never Looked So Good Whole-House and commercial Tankless Water Heating Solutions why tankless? at a glance Model Hot water supply
More informationTHE RINNAI LUXURY SERIES TANKLESS WATER HEATERS ENERGY-EFFICIENT HOT WATER NEVER LOOKED SO GOOD
THE RINNAI LUXURY SERIES TANKLESS WATER HEATERS ENERGY-EFFICIENT HOT WATER NEVER LOOKED SO GOOD WHOLE-HOUSE ANd COMMERCIAL TANkLESS WATER HEATING SOLUTIONS endless options flexibility + control MC-91-1-S
More informationVanguard Powermax 200 Gas-Fired Booster Heater Performance Tests
Vanguard Powermax 200 Gas-Fired Booster Heater Performance Tests Application of ASTM Standard Test Method F 2022-01 FSTC Report 5011.02.10 November 2002 Prepared by: David Cowen David Zabrowski Fisher-Nickel,
More informationCL64eN-BAS DISHWASHER
Item # Quantity C.S.I. Section 110 DISHWASHER STANDARD FEATURES 342 racks per hour Opti-RinSe system Rapid return conveyor drive mechanism Insulated hinged double doors with door interlock switches 19.5
More informationInstantaneous Water Heaters (IWH)
FILE NO.: 115.20 DATE: Mar. 28, 2002 SUPERSEDES: New DATE: New Instantaneous Water Heaters Instantaneous Water Heaters (IWH) IWH Application Case Study Handbook Introduction This handbook provides the
More informationMichigan Department of Agriculture and Rural Development
Michigan Department of Agriculture and Rural Development Fixed Food Establishment Plan Review Worksheet To be completed by the operator and submitted to the local health department or the Michigan Department
More informationCL44eN-BAS DISHWASHER
Item # Quantity C.S.I. Section 11400 CL44eN-BAS DISHWASHER STANDARD FEATURES 202 racks per hour Opti-RinSe system Rapid return conveyor drive mechanism Insulated hinged double doors with door interlock
More informationPREMIER SERIES APARTMENT HOUSE SIZING
APARTMENT HOUSE SIZING _ Number of Apartments, A Average number of People per Apartment, P Sizing Commercial Premier Modules for Apartment Buildings Determine whether the apartment building usage should
More informationCLPS86eN-BAS DISHWASHER
Item # Quantity C.S.I. Section 110 CLPS86eN-BAS DISHWASHER STANDARD FEATURES 342 racks per hour Opti-RinSe system Insulated hinged double doors with door interlock switches 19.5 inch chamber height opening
More informationThe Finest Tankless Electric Water Heaters Available! Commercial Application Point-of-Use Tankless Electric
Commercial Application Point-of-Use Tankless Electric DHC -E DHC-E Tempra The Finest Tankless Electric Water Heaters Available! On-demand, continuous, unlimited hot water No venting required Exclusive
More informationCL44eR DISHWASHER STANDARD FEATURES MODEL OPTIONS AT EXTRA COST ACCESSORIES DIRECTION OF OPERATION VOLTAGE. Item # Quantity C.S.I.
Item # Quantity C.S.I. Section 11400 DISHWASHER STANDARD FEATURES Energy recovery 202 racks per hour Opti-RinSe system 30 KW electric booster heater Rapid return conveyor drive mechanism Insulated hinged
More informationINSTALLATION AND OPERATING INSTRUCTIONS
17 West Street West Hatfield, MA 01088 Phone: (413) 247-3380 * (800) 582-8423 Fax: (413) 247-3369 E-mail: info@stiebel-eltron-usa.com SB 150, SB 200 Glass Lined Indirectly Fired Water Heaters With Single
More informationResults from Baseline Monitoring of Belas Hall Dishroom and Boiler Room and Next Steps. Amin Delagah, Michael Slater Fisher-Nickel Inc.
Results from Baseline Monitoring of Belas Hall Dishroom and Boiler Room and Next Steps Amin Delagah, Michael Slater Fisher-Nickel Inc. Balas Hall Dishroom Research Focus Areas Quantify energy and water
More informationFood Establishment Plan Review Worksheet
Food Establishment Plan Review Worksheet To be completed by the operator and submitted to the local health department Establishment Information Name: Address: City, State, Zip:- 1 Pages 6-10 ask structural
More informationTake Control of Your Water Use
Take Control of Your Water Use Kickstart the Conservation Habit Gwinnett County Department of Water Resources Our Water Cycle Water is continuously recycled through the water cycle Water is not destroyed
More informationECONOMICAL, EFFICIENT PERFORMANCE
[WATERHEATERS] ECONOMICAL, EFFICIENT PERFORMANCE CHRONOMITE TANKLESS ELECTRIC WATER HEATERS Since 1966, Chronomite Laboratories Inc. has been the innovative leader in providing solutions for commercial
More informationDISHWASHER, UNDERCOUNTER
Project: From: Alan Rogers Hobart Diswashers Alaska Restaurant Supply, Inc. Nick Hornshuh 2511 Eagle Street Anchorage, AK 99503 907.276.7044 907.276.7044 (Contact) Quote: 16212 Job Reference Number: 2133
More informationCL64e DISHWASHER DISHWASHER STANDARD FEATURES MODEL OPTIONS AT EXTRA COST ACCESSORIES DIRECTION OF OPERATION VOLTAGE
Item # Quantity C.S.I. Section 11400 DISHWASHER STANDARD FEATURES 342 racks per hour Opti-RinSe system Rapid Return Conveyor Drive Mechanism Insulated hinged double doors with door interlock switches 19.5
More informationHOKE COUNTY Department of Public Health Environmental Health Section 683 East Palmer Road Raeford, North Carolina 28376
Helene Edwards, MS, RD, LDN Health Director HOKE COUNTY Department of Public Health Environmental Health Section 683 East Palmer Road Raeford, North Carolina 28376 $250.00 Food Establishment Plan Review
More informationNational Grid s Direct Install Program for Commercial Customers
National Grid s Direct Install Program for Commercial Customers Reduce your energy costs, water usage, and increase the value of your property. Energy represents the single fastest-growing operating cost
More informationHotel & motel checklist
Hotel & motel checklist Hotels and motels use an average of 21,537 gallons per day of water Water CHAMP is our Water Conservation Hotel and Motel Program Join our free program to help save water for our
More informationCLPS66e DISHWASHER DISHWASHER STANDARD FEATURES MODEL OPTIONS AT EXTRA COST ACCESSORIES DIRECTION OF OPERATION VOLTAGE
Item # Quantity C.S.I. Section 11400 DISHWASHER STANDARD FEATURES 202 racks per hour Opti-RinSe system Rapid Return Conveyor Drive Mechanism Insulated hinged double doors with door interlock switches 19.5
More informationLXGeR and LXGePR GLASSWASHER
Item # Quantity C.S.I. Section 11400 and STANDARD FEATURES Racks per hour Light Normal 30 24 38 29.62 gallons of water per rack 1.14 gallons of water per rack Hot water or chemical sanitation units available
More informationHARNETT COUNTY PLAN REVIEW APPLICATION COVER LETTER FOOD SERVICE ESTABLISHMENTS CHANGE OF OWNERSHIP
HARNETT COUNTY PLAN REVIEW APPLICATION COVER LETTER FOOD SERVICE ESTABLISHMENTS CHANGE OF OWNERSHIP Potential owners are required to complete this application so we may collect the necessary information
More information10 : 1 Turndown Ratio
+ Residential Gas Hybrid The Best Features of Both a Tank & Tankless Combined into 1 Superior Unit Endless Hot Tank Tankless = 10 : 1 Turndown Ratio SCAQMD Rule 1146.2 Residential Gas Hybrid High Efficiency:
More informationCrossover. Hybrid Water Heater HIGH EFFICIENCY. Advanced Heating & Hot Water Systems. w w w.htproducts.com
HIGH EFFICIENCY Crossover Advanced Heating & Hot Water Systems Hybrid Water Heater The Best Features of Both a Tank & Tankless Water Heater Combined into 1 Superior Unit w w w.htproducts.com SCAQMD Rule
More informationResidential Water Heating
Residential Water Heating Energy Design Conference, Duluth Ben Schoenbauer, CEE February, 25 th, 2014 In accordance with the Department of Labor and Industry s statute 326.0981, Subd. 11, This educational
More informationFCSI Conference April 20 th and 21 st Presentation by: Richard Young Senior Engineer and Director of Education
FCSI Conference April 20 th and 21 st 2012 Presentation by: Richard Young Senior Engineer and Director of Education 1 5 New FSTC Blog! www.fishnick.com/blog 2 While you are there... please like us on Facebook
More informationCrossover. Hybrid Water Heater. High Efficiency. Advanced Heating & Hot Water Systems.
Advanced Heating & Hot Water Systems High Efficiency Crossover Hybrid Water Heater The Best Features of Both a Tank & Tankless Water Heater Combined into 1 Superior Unit To place an order contact your
More informationHARNETT COUNTY PLAN REVIEW APPLICATION COVER LETTER FOOD SERVICE ESTABLISHMENTS
HARNETT COUNTY PLAN REVIEW APPLICATION COVER LETTER FOOD SERVICE ESTABLISHMENTS Unless directed otherwise, all items are to be submitted through the Central Permitting Office at 108 East Front St., Lillington,
More informationIndoor Water Use SECTION 31 REGULATIONS AND CALGREEN CODE COMPLIANCE. Fixture & Appliance Requirements. Water Efficiency Review
Effective 06/25/18 Water Efficiency Review SECTION 31 REGULATIONS AND CALGREEN CODE COMPLIANCE Indoor Water Use Fixture & Appliance Requirements www.ebmud.com Water Conservation Division Water Efficiency
More informationCAUTION. Installation Manual
System Controller SC-301-6M CAUTION Installation Manual In order to use this product safely, read this installation manual carefully and follow the installation instructions. Potential dangers from accidents
More informationBOHEC R CRS86A DISHWASHER STANDARD FEATURES MODEL ACCESSORIES DIRECTION OF OPERATION VOLTAGE OPTIONS AT EXTRA COST
Item # Quantity C.S.I. Section 11400 DISHWASHER STANDARD FEATURES 244 racks per hour Opti-RinSe system Ball detent clutch conveyor drive mechanism Top mounted controls Stainless steel anti-clogging wash
More informationASSESSMENT INFORMATION
checklist Water Audit Data Collection Sheet This data collection sheet is designed to assist auditors during assessments. Some items may not be applicable for all assessment situations or conditions. ASSESSMENT
More informationCLCS76eN-BAS DISHWASHER
Item # Quantity C.S.I. Section 11400 DISHWASHER STANDARD FEATURES 245 racks per hour Opti-RinSe system Rapid return conveyor drive mechanism Insulated hinged double doors with door interlock switches 19.5
More informationWater Heaters. energy-efficient Hot Water Never Looked So Good #1 PRODUCT FOUR CONSECUTIVE YEARS IN BUILDER MAGAZINE S FAVORITE 50
the Rinnai LS Series tankless Water Heaters energy-efficient Hot Water Never Looked So Good Whole-House and commercial Tankless Water Heating Solutions NEW! 0.4 GPM Activation Rate #1 PRODUCT FOUR CONSECUTIVE
More informationInnovative, Compact Design
Innovative, Compact Design Easy, Effective Compliance What in the world is? The Thermaco, Inc. Trapzilla Supercapacity Grease Trap collects free-floating (non-emulsifed) grease & oils contained in kitchen
More informationFT900 FLIGHT-TYPE DISHWASHER
Item # Quantity C.S.I. Section 11400 FT900 FLIGHT-TYPE DISHWASHER STANDARD FEATURES Opti-RinSe system Water usage 120 gph @ 20 psi Microprocessor controls Low temperature alert Single point vent connection
More informationCopyright 2003 IBACOS, Inc. All rights reserved.
Domestic Hot Water Research Research conducted by Bill Rittelmann Presented by Duncan Prahl Partners for High Performance Homes Meeting Westminster, CO, June 23, 2005 DHW Systems: Current Technologies
More informationThis presentation premiered at WaterSmart Innovations 2010 Join us this fall in Las Vegas, October, watersmartinnovations.
This presentation premiered at WaterSmart Innovations 2010 Join us this fall in Las Vegas, October, 2011 watersmartinnovations.com Commercial Dish Washing Equipment By H. W. (Bill) Hoffman, P.E. Water
More informationTECHNICAL SUPPORT MATERIAL Routine and Preventative Maintenance Spray Arm Pressure Testing Tool ( )
1 AMERICAN DISH SERVICE TECHNICAL SUPPORT MATERIAL Routine and Preventative Maintenance Spray Arm Pressure Testing Tool (088-1048) 088-1048, Tool, Spray Arm with pressure gauge for low temp machines Note:
More informationFT900SDBD DUAL RINSE FLIGHT-TYPE DISHWASHER
Item # Quantity C.S.I. Section 11400 FT900SDBD DUAL RINSE FLIGHT-TYPE DISHWASHER STANDARD FEATURES Opti-RinSe system with dual rinse Water usage 72 gph @ 20 psi Microprocessor controls Low temperature
More informationFT900S FLIGHT-TYPE DISHWASHER
Item # Quantity C.S.I. Section 11400 FT900S FLIGHT-TYPE DISHWASHER STANDARD FEATURES Opti-RinSe system Water usage 114 gph @ 20 psi (standard height) Microprocessor controls Low temperature alert Single
More informationFT900S FLIGHT-TYPE DISHWASHER
Item # Quantity C.S.I. Section 11400 FT900S FLIGHT-TYPE DISHWASHER STANDARD FEATURES Opti-RinSe system Water usage 102 gph @ 20 psi (standard height) Microprocessor controls Low temperature alert Single
More informationCLCS76eN-EGR ENERGY RECOVERY DISHWASHER
Item # Quantity C.S.I. Section 11400 CLCS76eN-EGR ENERGY RECOVERY DISHWASHER STANDARD FEATURES Drain Water Energy Recovery (DWER) 22 inch corner power scrapper with 2 HP motor 245 racks per hour Drain
More informationMANDATORY CHECKLIST FOR NEW CONSTRUCTION OR REMODEL OF FOOD ESTABLISHMENT REMODEL NEW SQUARE FEET OF FACILITY DATE
County of Santa Cruz ENVIRONMENTAL HEALTH HEALTH SERVICES AGENCY 701 OCEAN STREET, ROOM 312, SANTA CRUZ, CA 95060-4073 (831) 454-2022 FAX: (831) 454-3128 TDD: 711 www.scceh.com MANDATORY CHECKLIST FOR
More informationFT900D DUAL RINSE FLIGHT-TYPE DISHWASHER
Item # Quantity C.S.I. Section 11400 FT900D DUAL RINSE FLIGHT-TYPE DISHWASHER STANDARD FEATURES Opti-RinSe system with dual rinse Water usage 90 gph @ 20 psi Microprocessor controls Low temperature alert
More informationLet s Go Back to the Future!
Let s Go Back to the Future! Welcome to the 2 nd Hot Water Forum Larry Weingarten and Gary Klein The Water-Energy-Greenhouse Gas Connection A Birdseye View Near Raleigh and Durham, North Carolina December
More informationPresentation Outline. Commercial 1 Track. Unit #4: Commercial Water Heating
Track: Commercial Natural Gas I Unit #4: Commercial Water Heating An overview of Water Heating Technologies Mr. Eric Burgis, Energy Solutions Center Copyright 2016 Energy Energy Solutions Solutions Center
More informationCommercial Applications
Tankless Water Heaters for Outside the Home Commercial Applications ProTankless Water Heaters for the Professional Bosch Meets the Commercial Needs Bosch Tankless Water Heaters install far beyond the typical
More informationEvaluating the Water Savings Potential of Commercial Connectionless Steamers. FINAL REPORT (Revised) April Angelo Karas Don Fisher
Evaluating the Water Savings Potential of Commercial Connectionless Steamers FINAL REPORT (Revised) April 2006 Prepared by: Angelo Karas Don Fisher Fisher-Nickel, inc. Food Service Technology Center 12949
More informationCL64eN-EGR ENERGY RECOVERY/CL64eN-ADV DISHWASHER
Item # Quantity C.S.I. Section 110 CL64eN-EGR ENERGY RECOVERY/ CL64eN-ADV DISHWASHER STANDARD FEATURES Drain Water Energy Recovery (DWER) Automatic Soil Removal (ASR) (Standard on models only) 342 racks
More information