1 COVER SHEET Employer or other Responsible Person: Address of Property: Person(s) Consulted: Assessor: University of Kent; Vice Chancellor; Director of Kent Hospitality Rutherford College (excludes Extension) Reception, Housekeeping & Estates staff; various residents; Master & Assistant; Rob Sherwood (Fire Safety Officer, Kent Fire & Rescue Authority) Andrew Briggs, TechIFSM, MIIRSM Date of Fire Risk Assessment: 16th November th February 2008 Date of Previous Fire Risk Assessment: Suggested Date for Review: 20th February SHOULD BE READ IN CONJUNCTION WITH THIS REVIEW. February 2010, or as per UoK SHEU official schedule, or in event of significant change Document dated 29th February th October amended/updated 13th February amended/updated Fire Risk Assessment in accordance with Publicly Available Standard PAS 79 (British Standards Institute): Fire Risk Assessment - Guidance and a recommended methodology

2 GENERAL BUILDING DESCRIPTION 1.0 The Building 1.1 Number of floors Five 1.2 Approximate floor area: Not reviewed 1.3 Construction Details: Predominantly concrete/block - robust fire performance 1.4 Occupancy: Not reviewed 2.0 The Occupants 2.1 Approximate maximum number: Not reviewed 2.2 Maximum number of staff at any one time: Not reviewed 2.3 Maximum number of members of public: Not reviewed (Add more detail by area or room as appropriate) 3.0 Occupants at Special Risk 3.1 Sleeping occupants: 305 student study bedrooms 3.2 Occupants with disabilities: Disabled access to levels 2, 3 & Occupants in remote areas: Some 11 corridors are dead-end conditions containing excessive travel distances. 3.4 Others: Nil significant 4.0 Fire Loss Experience 4.1 Fires in past 12 years: 11, all relatively minor and rapidly extinguished. See summary on file (SHEU).

3 GENERAL BUILDING DESCRIPTION 5 of above fires originated in residential kitchenettes. 4.2 Cost of fire losses: Not reviewed 5.0 Other Relevant Information 5.1 Detail: N/A 6.0 Relevant Fire Safety Legislation 6.1 Statutory provisions: Regulatory Reform (Fire Safety) Order 2005 & referred Official Guidance

4 FIRE HAZARDS INDE DETAIL YES NO N/A CONTROL MEASURES 7.0 Electrical Sources of Ignition 7.1 Reasonable measures taken to prevent fires of electrical origin? Continue to maintain safe separation distance of ½ metre between appliances and combustible materials throughout building. Switch equipment off at the end 7.2 Fixed installation periodically inspected and tested? Portable appliance testing carried out? Suitable policy regarding use of personal electrical appliances? Suitable limitation of trailing leads and adaptors? of the working day. One item found missed from Portable Appliance Testing (iron in W2.3 laundry) - PAT generally fully implemented but all staff should be trained to remain vigilant as to status and condition of appliances. 7.2 suppl. Recommendation to consider Portable Appliance Testing of student-owned appliances. 8.0 Smoking 8.1 Reasonable measures taken to prevent fires as a result of smoking? Prohibited where appropriate? Arrangements for smokers? Evidence of breaches? Ensure University smoking policy continues to be implemented and enforced insofar as possible. 9.0 Arson 9.1 Does basic security against arson by outsiders appear reasonable? Fire load available for ignition by outsiders? 10.0 Cooking & Heating 10.1 Are reasonable measures taken to prevent fires as a result of cooking & heating? Is all essential maintenance up to date and recorded? Ensure ban on additional cooking and other appliances in residences continues to be enforced insofar as possible. Portable electrical heaters with open elements, such as fan or convector heaters, must not be used Are filters changed and ductwork cleaned regularly? 10.3 Are suitable extinguishing appliances available? Ductwork apparently not cleaned since Clean urgently and implement regular maintenance programme, to include fire dampers Lightning

5 FIRE HAZARDS 11.1 Does the building have a lightning protection system? 12.0 Other Significant Ignition Sources 12.1 Are there other significant ignition sources present? Ensure ban on candles, joss sticks etc continues to be enforced insofar as possible Housekeeping Note: some office & academic areas contain relatively high fire loadings which should be reduced Is the standard of housekeeping adequate? Standard of housekeeping in S3-1 and 'rag store' is unacceptable (see 13.3 below) and must be corrected Are combustible materials separated from ignition Continue to maintain safe separation distance of ½ metre between appliances sources? 13.3 Is there an avoidance of unnecessary accumulation of combustible materials or waste? 13.4 Is there appropriate storage of combustible materials? 13.5 Is there avoidance of inappropriate storage of combustibles materials? 14.0 Outside Contractor and Building Works Hazards 14.1 Is there satisfactory control over works carried out in the building by outside contractors? 14.2 Are adequate fire safety conditions imposed on outside contractors? and combustible materials throughout building. S3-1, S3-3 and the 'rag store' off the E1S stairwell contain very high fire loading. Combustibles content must be reduced significantly and kept in an orderly manner so as to minimise flame spread in the event of a fire Dangerous Substances 15.1 Have the hazardous properties of dangerous substances been considered? 15.2 Is there adequate information on safety provided by the supplier on any relevant safety data sheet? 15.3 Has account been taken regarding:

6 FIRE HAZARDS the special, technical and organisational measures and the substances used and their possible interactions. the amount of the substance involved where the work will involve more than one dangerous substance, the risk presented by such substances in combination the arrangements for the safe handling, storage and transport of dangerous substances and of waste containing dangerous substances any other measures introduced as a result of the RRO 15.4 Are there safe systems of work for maintenance, where there is the potential for a high level of risk? 15.5 Are sufficient control measures in place to counter the likelihood that an explosive atmosphere will occur and its persistence including adjacent areas? 15.6 Are sufficient control measures in place to counter the likelihood that ignition sources, including electrostatic discharges, will be present and become active and effective 15.7 Has account been taken regarding the scale of the anticipated effects? 15.8 Is sufficient additional safety information available to enable the assessment to be completed?

7 FIRE HAZARDS

8 FIRE HAZARDS

9 FIRE PROTECTION INDE DETAIL YES NO N/A CONTROL MEASURES 16.0 Means of Escape 16.1 Is it considered that the building is provided with reasonable means of escape in case of fire? 16.2 Is there adequate provision of exits? (Calculate for room and premises occupancy numbers & types, where relevant.) 16.3 Are exits easily and immediately openable where necessary? (Alarm-linked features such as electronic door release mechanisms to be verified as compliant, functional and suitably failsafe) Exits/widths/occupancies not recalculated at this time (except for Rutherford Bar) but, based on previous Fire Risk Assessment and approximate visual confirmation, appear satisfactory. Verification should be planned for next fire risk assessment review. Satisfactory on sampled basis, not practicable to verify exhaustively Do escape exits open in the direction of escape Double fire doors near W4W/W4N should be reversed or made double swing. where necessary? 16.5 Are there satisfactory means for securing exits? Break-glass hammer for S4E alternative exit missing, to be replaced Are there reasonable travel distances where there is a single direction of travel? Dead end conditions exist in a number of corridors; travel distances grossly exceed guidance values, representing a high risk to sleeping occupants without further mitigating features. Top priority must be given to reducing risk to tolerable levels - recent and continuing improvements are in hand at time of writing (Oct 08) including specific planning meetings Are there reasonable travel distances where there is an alternative means of escape?

10 FIRE PROTECTION 16.8 Is there suitable protection of escape routes? (1) Many fire doors are in poor condition having grossly excessive gaps and ineffective seals, and some are binding on floor/failing to self-close, etc - to be checked throughout, adjusted/repaired/corrected and appropriate intumescent and/or smoke seals fitted. (2) Self-closers found missing from W2S & W4W corridor fire doors - to replace. (3) New double fire doors from common room adjacent Rutherford Bar - self closer defective, to repair. (4) Alarm-linked automatic holdback devices must be fitted to fire doors between servery and kitchen (1 single, 1 double) and washing-up area (1 single) and the self-closing action of these doors corrected. Similar devices are very strongly recommended for the rear kitchen double doors. (5) Designated fire doors must not be propped or wedged open. Every effort must be made to stop the practice of wedging fire doors, e.g. of residential kitchenettes Are all escape routes unobstructed? (1) The alternative exit from the Upper Senior Common Room is habitually obstructed, and the alternative exit from W3.2 Lecture Room 2 is particularly prone to obstruction; signage must be corrected/enhanced and its impact maximised, to control these situations. (2) Vending machines considerably obstruct the escape route corridor adjacent Rutherford Bar (and furthermore should not be present as a potential source of ignition) and should be removed to a suitable location. (3) One leaf of 'old' double door exit from common room adjacent Rutherford Bar was found bolted - both leaves of all such exit route doors must be maintained immediately available at all times. (a) All such bolts/locks should be removed, and (b) in the meantime clear and reliable management responsibilities and procedures should apply Is the building provided with reasonable arrangements for means of escape for occupants with disabilities? 17.0 Fire Spread and Development Limitation Powered door openers to several W2 residential corridors were inoperative at time of inspections, and at least one corridor (W2S) is equipped at the entrance but not at the alternative exit - openers must be fully provided/repaired if any persons with disabilities are in residence supplementary: Basic existing arrangements for assisting the evacuation of all disabled persons from the building in the case of fire should be developed further and a system of PEEPs introduced. (Greater provision of technical, physical, organisational and human resources is necessary to provide comprehensive systems for disabled evacuation, in connection with campus-wide developments.)

11 FIRE PROTECTION 17.1 Is it considered that there is compartmentation of a reasonable standard? (Including e.g. dampers in ductwork; fire-stopping of service penetrations) 17.2 Is it considered that there is reasonable limitation of linings that may promote fire spread? (1) Repair displaced/poor fire stopping above door frame of quiet study room adjacent S3-1. (2) Question as to adequate fire resistance of panels above residential corridor fire doors - to be identified, established and replaced as necessary. (3) Service penetrations though panels above corridor & other fire doors (especially Level 1 and e.g. N3W and store adjacent W2-3) - fire stopping to be applied throughout. (4) Level 1 plant room and two rooms adjacent, Rag store & Trunk store - numerous service penetrations in walls, ceilings & above doors to be fire-stopped to half hour resistance; all vents to stairwell must be sealed to same standard or intumescent seals fitted. (5) Laundry W2.3 - vent to corridor must be sealed with half hour fire resisting material or intumescent seals fitted. (6) Georgian wire glass vision panel in S2E corridor door has dropped leaving a gap - to correct. (7) Similar conditions are highly likely to exist elsewhere - audit must be conducted and remedial fire stopping etc undertaken throughout. Postering of walls in corridor N3W is nearing excessive extent, in terms of area potential for fire spread Escape Lighting 18.1 Is a reasonable standard of escape lighting provided? 19.0 Fire Safety Signs and Notices NOTE: Fire Action Notices must continue to be posted in all residential rooms, especially for the information of short-duration visitors.

12 FIRE PROTECTION 19.1 Does the building have a reasonable standard of fire safety signs and notices? (See also 16.9 item 1 and 20.1 item 2). (1) Escape route signage is inadequate in many areas (variously missing, interfered with, inadequate, incorrect [e.g. (3) below] or noncompliant - needs overall review & correction (to include emergency illumination and disabled signage), noting recent Fire Service instructions. (2) Many fire exit doors are not marked 'keep clear', e.g. most alternative exits from residential corridors - these must be fitted throughout (most critical cases corrected via Estates Helpdesk but many not yet addressed). (3) Disabled muster point signs are incorrectly used in place of directional signs at a number of locations. (4) Entry from roof into Plant Room 4 (alternative escape route from Upper Senior Common Room): "Break Glass" sign to be fitted. (5) Cloister seminar rooms & garden: the need to evacuate via building escape routes is particularly unclear, leaving potential for persons to remain in the garden area; special attention to signage is required here. (6) Redundant signage (e.g. to former call point outside N4-9) must be removed throughout Fire Warning Arrangements Note - flip-up call point covers are to be fitted, contrary to BS5839 but with clear "lift up" indication visible, as a necessary measure to combat malicious activations Is a reasonable manually operated electrical fire alarm system provided? (1) Call points should be provided at Final Exits from staircases serving residential corridors etc. (2) In the meantime additional signs are required to direct persons to call points on landings above Is automatic fire detection provided in building? Smoke detection should be present in the lobby of the film production suite (level 20.3 Is the fire alarm system audible or perceptible throughout the building? 20.4 Is there a remote transmission of alarm signal? 21.0 Portable Fire Extinguishing Appliances 21.1 Is the provision of portable fire extinguishers reasonable? 2 W) - to be verified or corrected. Appears adequate, subject to ongoing verification by Estates that 75dB is attained at every bedhead. Additional 13A water and 2kg CO2 extinguishers to be provided at far end of each dead end corridor (see 16.6) Are hose reels provided? Fire hose reels should be removed and, in locations with no alternative portable extinguisher provision in accordance with official guidance, relaced with same Automatic Fixed Systems

13 FIRE PROTECTION 22.1 Is there a suitable sprinkler or water based system that is adequate for the risk present? 22.2 Is there a suitable gaseous local application or total flooding provided that is adequate for the risk? Other Fixed Systems 22.3 Are there suitable smoke control facilities for the risk present? 23.0 Luminous Discharge Tubes 23.1 Has notice been given to the fire and rescue authority regarding luminous discharge tubes cutoff switch, its colouring and marking.

14 FIRE PROTECTION NOTES Example of travel distance to place of relative safety (applying 2/3 rule within study bedroom) is 25m, as against guidance maximum of 18m.

15 MANAGING FIRE SAFETY INDE DETAIL YES NO N/A CONTROL MEASURES 24.0 Procedures and Arrangements 24.1 Appropriate fire procedures in place (including calling the fire service)? Provide, resource and implement a written Fire Emergency Plan covering all appropriate procedures, responsibilities and features of the building. The Plan should include arrangements to assist disabled persons; for academic staff etc to take responsibility for the evacuation of students in their presence; to conduct a full coordinated sweep of the building to confirm full evacuation or otherwise; and to provide clear instructions for liaising with the fire brigade on arrival and notifying them of any special risks or conditions Training and drills See 19.1 item 5 - a means should be devised of providing extra information & instruction regarding evacuation from the cloister seminar rooms and garden, probably via special signage Are all staff given instruction on induction, and periodic refresher training at suitable intervals? > > > Ensure full & appropriate induction information and training is provided to all employees, with suitable refresher information and training at not less than three year intervals Are all students and visitors given suitable suppl. information and instruction? 25.3 Do key staff have suitable competence & training? (Responsible & competent persons, fire marshals etc, nominated fire extinguisher users, academic staff, etc) > > > Ensure adequate fire safety information and briefing is given to all students and visitors. Fire safety awareness and behaviour should be enhanced by any available means. (1) Sufficient fire marshals etc are not available and should be appointed in order to facilitate evacuation (see 24.1) during staffed times, and for other fire safety requirements such as inspections. (2) Insufficient persons are nominated and trained in the use of fire extinguishers. Management of all departments occupying and operating in the building must cooperate and coordinate in making such provisions Inspection, Testing and Maintenance 26.1 Adequate maintenance and checking of workplace and fire safety features? Ensure that a system of monthly checks of fire extinguishers and other fire safety features is implemented, and records kept. Checks should take account of behavioural aspects such as abuse of fire safety provisions.

16 MANAGING FIRE SAFETY 26.2 Weekly testing and periodic servicing of fire detection and alarm system? 26.3 Monthly, six-monthly and annual testing routines for emergency lighting? 26.4 Annual maintenance of fire extinguishing appliances? 26.6 Weekly testing and periodic inspection of sprinkler installations? 26.7 Other relevant inspections or tests: (including e.g. ductwork dampers, fire shutters, venting systems, door holdback devices, electronic door release systems) 27.0 Records 27.1 Are appropriate records kept for fire training? > > > Ensure appropriate fire safety training records are kept Are appropriate records kept for fire alarm tests? 27.3 Are appropriate records kept for escape lighting tests? 27.4 Are appropriate records kept for the maintenance and testing of other fire protection systems? 28.0 Young Persons Have the following matters been taken into particular account in risk assessment in respect 28.1 of young persons: the inexperience, lack of awareness of risks and immaturity of young persons the fitting-out and layout of the premises > > > Consider providing enhanced comprehensive induction training package to raise awareness levels of young persons (e.g. summer school students).

17 MANAGING FIRE SAFETY the nature, degree and duration of exposure to 28.4 physical and chemical agents the form, range, and use of work equipment and 28.5 the way in which it is handled; 28.6 the organisation of processes and activities Consider re-evaluating the activities and supervision of young persons. the extent of the safety training provided or to be As provided to young persons risks from agents, processes and work listed in the Annex to Council Directive 94/33/EC on the 28.8 protection of young people at work

18 MANAGING FIRE SAFETY NOTES (Extra note) Cannot generalise response - mostly 'yes' but inevitably variable by department Cannot generalise response - inevitably variable by department Cannot generalise response - inevitably variable by department

19 MANAGING FIRE SAFETY Response field left blank - mostly 'yes' but inevitably variable by department Cannot generalise response - QUESTIONABLE

20 MANAGING FIRE SAFETY Ditto Ditto

21 This simple risk level estimator is based on a more general health and safety risk level estimator in BS 8800: Potential consequences of fire Slight harm Moderate harm Extreme harm Fire hazard Low Trivial risk Tolerable risk Moderate risk Medium Tolerable risk Moderate risk Substantial risk High Moderate risk Substantial risk Intolerable risk Taking into account the fire prevention measures observed at the time of this risk assessment, it is considered that the hazard from fire (probability of ignition) at this building is: Low / highly unlikely - following completion of recommendations of this fire risk assessment Medium / unlikely - prior to completion of recommendations of this fire risk assessment High / likely Taking into account the nature of the building and the occupants, as well as the fire protection and procedural arrangements observed at the time of this risk assessment, it is considered that the consequences for life safety in the event of fire would be: Slight harm - following completion of recommendations of this fire risk assessment Moderate harm - prior to completion of recommendations of this fire risk assessment Extreme harm - certain occupants only, at present - see 16.6 In this context, a definition of the above terms is as follows: Slight harm: Moderate harm: Extreme harm: Outbreak of fire unlikely to result in serious injury or death of any occupant (other than an occupant sleeping in a bedroom in which a fire occurs). Outbreak of fire could result in injury of one or more occupants, but it is unlikely to involve multiple fatalities. Significant potential for serious injury or death of one or more occupants.

22 Accordingly, it is considered that the risk to life from fire at this building is: Trivial Tolerable - following completion of ALL recommendations of this fire risk assessment (INCLUDING consigning all rooms with excessive travel distances to unoccupied use Moderate - prior to completion of ALL recommendations of this fire risk assessment Substantial - certain occupants only, at present - see 16.6 Intolerable A suitable risk-based control plan should involve effort and urgency that is proportional to risk. The following risk-based control plan is based on one advocated by BS 8800 for general health and safety risks: Trivial Tolerable Moderate Risk Level Action and Timescale No action is required and no additional detailed records need be kept. No major additional controls required. However, there may be a need for consideration of improvements that involve minor or limited cost, and various corrective actions may be required. It is essential that efforts are made to reduce the risk. Risk reduction measures should be implemented within a defined time period. Where moderate risk is associated with consequences that constitute extreme harm, further assessment may be required to establish more precisely the likelihood of harm as a basis for determining the priority for improved control measures. Substantial Intolerable Considerable resources may have to be allocated to reduce the risk. If the building is unoccupied, it should not be occupied until the risk has been reduced. If the building is occupied, urgent action should be taken. Building (or relevant area) should not be occupied until the risk is reduced.

23 Any significant change, occurrence, finding or development should be reported immediately to the University s Safety, Health & Environment Unit so that mitigating action can be taken and this Fire Risk Assessment reviewed and updated.

24

25 es)

26 ACTION PLAN ORGANISATION: University of Kent BUILDING: RUTHERFORD COLLEGE ASSESSOR: Andrew Briggs, TechIFSM, MIIRSM DATE: 16th November th February 2008 & 13th February 2009 ACTION PLAN It is considered that the following recommendations should be implemented in order to reduce fire risk to the following level: TOLERABLE REFERENCE ACTION REQUIRED TO ELIMINATE OR CONTROL SIGNIFICANT HAZARDS PRIORITY * RESPONSIBILITY TARGET DATE 7.0 Electrical Sources of Ignition 7.2 suppl. Recommendation to consider Portable Appliance Testing of student-owned appliances Cooking & Heating 10.2 Ductwork apparently not cleaned since Clean urgently and implement regular maintenance programme, to include fire dampers. 3A/B 1A/B, URGENT Kent Hospitality/Estates Kent Hospitality/ Estates (TBA) 13.0 Housekeeping 13.3 S3-1, S3-3 and the 'rag store' off the E1S stairwell contain very high fire loading. Combustibles content must be reduced significantly and kept in an orderly manner so as to minimise flame spread in the event of a fire. 1A/B Kent Union 16.0 Means of Escape 16.4 Double fire doors near W4W/W4N should be reversed or made double swing. 2A Estates 16.5 Break-glass hammer for S4E alternative exit missing, to be replaced. 1A HDWR175142

27 ACTION PLAN 16.6 Dead end conditions exist in a number of corridors; travel distances grossly exceed guidance values, representing a high risk to sleeping occupants without further mitigating features. Top priority must be given to reducing risk to tolerable levels - recent and continuing improvements are in hand at time of writing (Oct 08) including specific planning meetings (1) Many fire doors are in poor condition having grossly excessive gaps and ineffective seals, and some are binding on floor/failing to self-close, etc - to be checked throughout, adjusted/repaired/corrected and appropriate intumescent and/or smoke seals fitted. (2) Self-closers found missing from W2S & W4W corridor fire doors - to replace. (3) New double fire doors from common room adjacent Rutherford Bar - self closer defective, to repair. (4) Alarm-linked automatic holdback devices must be fitted to fire doors between servery and kitchen (1 single, 1 double) and washing-up area (1 single) and the self-closing action of these doors corrected. Similar devices are very strongly recommended for the rear kitchen double doors. (5) Designated fire doors must not be propped or wedged open. Every effort must be made to stop the practice of wedging fire doors, e.g. of residential kitchenettes (1) The alternative exit from the Upper Senior Common Room is habitually obstructed, and the alternative exit from W3.2 Lecture Room 2 is particularly prone to obstruction; signage must be corrected/enhanced and its impact maximised, to control these situations. (2) Vending machines considerably obstruct the escape route corridor adjacent Rutherford Bar (and furthermore should not be present as a potential source of ignition) and should be removed to a suitable location. (3) One leaf of 'old' double door exit from common room adjacent Rutherford Bar was found bolted - both leaves of all such exit route doors must be maintained immediately available at all times. (a) All such bolts/locks should be removed, and (b) in the meantime clear and reliable management responsibilities and procedures should apply Powered door openers to several W2 residential corridors were inoperative at time of inspections, and at least one corridor (W2S) is equipped at the entrance but not at the alternative exit - openers must be fully provided/repaired if any persons with disabilities are in residence. 1A 2A 2A 1A/2A Kent Hospitality/Estates (1) Estates (2) HDWR (3) Kent Union (4) Estates/Kent Hospitality (5) Kent Hospitality & all departments NB other specific HDWRs apply to (1) (1) Estates (2) Kent Hospitality (3a) Estates (3b) Kent Hospitality & all departments Estates/Kent Hospitality (HDWR also applies) 17.0 Fire Spread and Development Limitation

28 ACTION PLAN 17.1 (1) Repair displaced/poor fire stopping above door frame of quiet study room adjacent S3-1. (2) Question as to adequate fire resistance of panels above residential corridor fire doors - to be identified, established and replaced as necessary. (3) Service penetrations though panels above corridor & other fire doors (especially Level 1 and e.g. N3W and store adjacent W2-3) - fire stopping to be applied throughout. (4) Level 1 plant room and two rooms adjacent, Rag store & Trunk store - numerous service penetrations in walls, ceilings & above doors to be fire-stopped to half hour resistance; all vents to stairwell must be sealed to same standard or intumescent seals fitted. (5) Laundry W2.3 - vent to corridor must be sealed with half hour fire resisting material or intumescent seals fitted. (6) Georgian wire glass vision panel in S2E corridor door has dropped leaving a gap - to correct. (7) Similar conditions are highly likely to exist elsewhere - audit must be conducted and remedial fire stopping etc undertaken throughout. 2A Estates (1) HDWR175059, others not on HDWRs 19.0 Fire Safety Signs and Notices 19.1 (See also 16.9 item 1 and 20.1 item 2). (1) Escape route signage is inadequate in many areas (variously missing, interfered with, inadequate, incorrect [e.g. (3) below] or noncompliant - needs overall review & correction (to include emergency illumination and disabled signage), noting recent Fire Service instructions. (2) Many fire exit doors are not marked 'keep clear', e.g. most alternative exits from residential corridors - these must be fitted throughout (most critical cases corrected via Estates Helpdesk but many not yet addressed). (3) Disabled muster point signs are incorrectly used in place of directional signs at a number of locations. (4) Entry from roof into Plant Room 4 (alternative escape route from Upper Senior Common Room): "Break Glass" sign to be fitted. (5) Cloister seminar rooms & garden: the need to evacuate via building escape routes is particularly unclear, leaving potential for persons to remain in the garden area; special attention to signage is required here. (6) Redundant signage (e.g. to former call point outside N4-9) must be removed throughout. 2A Estates (some specific aspects covered by HDWRs) 20.0 Fire Warning Arrangements 20.1 (1) Call points should be provided at Final Exits from staircases serving residential corridors etc. (2) In the meantime additional signs are required to direct persons to call points on landings above. 2A Estates

29 ACTION PLAN 20.2 Smoke detection should be present in the lobby of the film production suite (level 2 W) - to be verified or corrected. 2A Estates 21.0 Portable Fire Extinguishing Appliances 21.1 Additional 13A water and 2kg CO2 extinguishers to be provided at far end of each dead end corridor (see 16.6) Fire hose reels should be removed and, in locations with no alternative portable extinguisher provision in accordance with official guidance, relaced with same. 2A 3A Estates Estates 24.0 Procedures and Arrangements 24.1 Provide, resource and implement a written Fire Emergency Plan covering all appropriate procedures, responsibilities and features of the building. The Plan should include arrangements to assist disabled persons; for academic staff etc to take responsibility for the evacuation of students in their presence; to conduct a full coordinated sweep of the building to confirm full evacuation or otherwise; and to provide clear instructions for liaising with the fire brigade on arrival and notifying them of any special risks or conditions Training and drills suppl. Ensure adequate fire safety information and briefing is given to all students and visitors. Fire safety awareness and behaviour should be enhanced by any available means (1) Sufficient fire marshals etc are not available and should be appointed in order to facilitate evacuation (see 24.1) during staffed times, and for other fire safety requirements such as inspections. (2) Insufficient persons are nominated and trained in the use of fire extinguishers. Management of all departments occupying and operating in the building must cooperate and coordinate in making such provisions. 25 suppl. See 19.1 item 5 - a means should be devised of providing extra information & instruction regarding evacuation from the cloister seminar rooms and garden, probably via special signage. 1A 2A 2A 2A Safety Unit & Kent Hospitality Kent Hospitality & Safety Unit All departments Estates/Kent Hospitality/SHEU 28.0 Young Persons 28.2 Consider providing enhanced comprehensive induction training package to raise awareness levels of young persons (e.g. summer school students). 2A Kent Hospitality

30 ACTION PLAN 28.6 Consider re-evaluating the activities and supervision of young persons. 2A Kent Hospitality HDWR = Helpdesk Work Request * PRIORITY (N.B. to Fire Service College Fire Safety Engineering Division scale, not PAS 79) Category A. Fire Risk to Persons: 1A - A serious life safety risk and/or a major or serious contravention of current fire safety legislation. This matter requires immediate attention and must be given high priority. 2A - An important life safety issue and/or a contravention of current fire safety legislation and/or official guidance, that may lead to enforceme This matter requires attention with the minimum of delay. 3A - A significant life safety issue which, in combination with other significant findings, may result in an increased risk to persons. Advised to implement programme of work or action in accordance with good fire safety practice. 4A - A life safety issue recommended for consideration in accordance with good fire safety practice. Advised to implement action or programme of work as appropriate. Category B. Fire Risk to Property, Business Continuity, Environment, Amenity, Heritage etc. 1B - A serious risk of damage by fire (with possible legal implications, depending on the enforcing authority involved). This matter requires immediate attention and must be given high priority. 2B - An important potential fire damage issue (with possible legal implications, depending on the enforcing authority involved). This matter requires attention with the minimum of delay. 3B - A significant potential fire damage issue which, in combination with other significant findings,may result in an increased risk to the prope Advised to implement programme of work or action in accordance with good fire protection/prevention practice. 4B - A property protection issue recommended for consideration as a medium of longer term objective in accordance with good fire preventi Advised to implement action or programme of work as appropriate.

31 ACTION PLAN COMPLETE or = transferred to Estates spreadsheet

32 ACTION PLAN where Estates where Estates

33 ACTION PLAN

34 ACTION PLAN Effectively yes

35 ACTION PLAN ent action if not addressed. erty. ion/protection practice.

FIRE RISK ASSESSMENT REVIEW

FIRE RISK ASSESSMENT REVIEW COVER SHEET REVIEW Employer or other Responsible Person: Address of Property: Person(s) Consulted: Assessor: University of Kent; Council & Vice Chancellor; Director of Estates East Oast, University of

More information

FIRE RISK ASSESSMENT REVIEW

FIRE RISK ASSESSMENT REVIEW COVER SHEET REVIEW Employer or other Responsible Person: Address of Property: Person(s) Consulted: Assessor: Director of Kent Business School in conjunction with Council & the Vice Chancellor Kent Business

More information

Slight Harm Moderate Harm Extreme Harm Low Trivial Risk Tolerable Risk Moderate Risk Medium Tolerable Risk Moderate Risk Substantial Risk

Slight Harm Moderate Harm Extreme Harm Low Trivial Risk Tolerable Risk Moderate Risk Medium Tolerable Risk Moderate Risk Substantial Risk Fire Risk Assessment: ABC Sample House Sample Road SA1 3M2 C J Sparks Ltd 13 Alexandra Gardens Carshalton SM5 4LJ T: 02077577457 W: www.cjsparks.com E: sales@cjsparks.com Ref: 3077 Action Plan Number Action

More information

FIRE RISK ASSESSMENT REVIEW

FIRE RISK ASSESSMENT REVIEW COVER SHEET REVIEW Employer or other Responsible Person: Address of Property: Person(s) Consulted: Assessor: Director of Estates in conjunction with Council & the Vice Chancellor Brotherhood Boiler House,

More information

FIRE RISK ASSESSMENT review

FIRE RISK ASSESSMENT review COVER SHEET review in accordance with Publicly Available Standard PAS 79:2007 (British Standards Institute): Fire Risk Assessment - Guidance and a recommended methodology (with additions) Employer or other

More information

FIRE RISK ASSESSMENT REVIEW

FIRE RISK ASSESSMENT REVIEW COVER SHEET REVIEW Employer or other Responsible Person: Address of Property: Person(s) Consulted: Assessor: University of Kent; Council & Vice Chancellor; Director of Estates CORNWALLIS BUILDING, University

More information

Co-Director, Tizard Centre (P. McGill) in conjunction with Council & the Vice Chancellor

Co-Director, Tizard Centre (P. McGill) in conjunction with Council & the Vice Chancellor COVER SHEET in accordance with Publicly Available Standard PAS 79:2007 (British Standards Institute): Fire Risk Assessment - Guidance and a recommended methodology (with additions) Responsible Person:

More information

Fire Risk Assessment. ABC Car Workshop. Prepared for. Redacted

Fire Risk Assessment. ABC Car Workshop. Prepared for. Redacted Fire Risk Assessment Prepared for ABC Car Workshop Assessor: (Assessor s Name) Date of Assessment: 24/07/17 Date of Next Assessment Review: Upon occupation Introduction and Scope This Fire Risk Assessment

More information

Regulatory Reform (Fire Safety) Order 2005 Category of Premises against the FSO 2005: Sleeping Accommodation

Regulatory Reform (Fire Safety) Order 2005 Category of Premises against the FSO 2005: Sleeping Accommodation FIRE RISK ASSESSMENT Retirement Housing (Independent Living) Developed in conjunction with Cambridge shire Fire and Rescue Service, Housing and Care 21 s primary authority (v3.november 2016) Regulatory

More information

TYPE 1 FIRE RISK ASSESSMENT REVIEW (NO DESTRUCTIVE AUDIT)

TYPE 1 FIRE RISK ASSESSMENT REVIEW (NO DESTRUCTIVE AUDIT) TYPE 1 FIRE RISK ASSESSMENT REVIEW (NO DESTRUCTIVE AUDIT) BRECON TOWERS BLACKBERRY LANE STOCKPORT SK5 8JW Date of this risk assessment review: 4th July 2017 Date of last risk assessment review: 8th May

More information

FIRE RISK ASSESSMENT REVIEW

FIRE RISK ASSESSMENT REVIEW COVER SHEET REVIEW in accordance with Publicly Available Standard PAS 79:2011 (British Standards Institute): Fire Risk Assessment - Guidance and a recommended methodology (with additions) IFSM-accredited

More information

AFEC FIRE ENGINEERING TEMPLATE FOR CLIENTS INTERNALLY COMPLETED RISK ASSESMENT

AFEC FIRE ENGINEERING TEMPLATE FOR CLIENTS INTERNALLY COMPLETED RISK ASSESMENT AFEC FIRE & RISK ENGINEERING SPECIALISTS would like to share an in house Risk Assessment Template we have developed for in house use to assist Facilities Managers and Environmental Health and Safety Staff

More information

Byker Various post codes. Your Homes Newcastle Health and Safety (fire) Officer Date of Fire Risk Assessment 18 th February nd October 2014

Byker Various post codes. Your Homes Newcastle Health and Safety (fire) Officer Date of Fire Risk Assessment 18 th February nd October 2014 Type of Property Owner Address of Properties Responsible Person (s) consulted Multi- occupied housing referred to as the Byker Wall Ground floor and varying upper levels with open deck assess to all areas.

More information

Fire Risk Assessment Keys Meadow Primary School

Fire Risk Assessment Keys Meadow Primary School Fire Risk Assessment Keys Meadow Primary School Issue Date: Issued To: Version Number: Approved By: 19 th May 2016 Jane Jenner 1 CS Fire Risk Assessment - Company Name XXX REGULATORY REFORM (FIRE SAFETY)

More information

FIRE RISK ASSESSMENT Retirement Housing (Independent Living) (v3.november 2016)

FIRE RISK ASSESSMENT Retirement Housing (Independent Living) (v3.november 2016) FIRE RISK ASSESSMENT Retirement Housing (Independent Living) (v3.november 2016) Regulatory Reform (Fire Safety) Order 2005 Category of Premises against the FSO 2005: Sleeping Accommodation The purpose

More information

Fire Risk Assessment Mechanics Institute Manchester Road Burnley BB11 1JA

Fire Risk Assessment Mechanics Institute Manchester Road Burnley BB11 1JA Fire Risk Assessment Mechanics Institute Manchester Road Burnley BB11 1JA Assessment prepared by - Chris Caton MIFireE Pennine Fire & Safety Limited Pleasington Street Blackburn BB2 1UF info@penninefire.co.uk

More information

Management Standard: Fire Safety

Management Standard: Fire Safety OHSS: H&S Management 201 Fire Safety Management : Fire Safety 1. Legal framework This standard is produced to comply with the following legislation in respect to fire safety: 1.1. Regulatory Reform (Fire

More information

REGULATORY REFORM (FIRE SAFETY) ORDER 2005 FIRE RISK ASSESSMENT

REGULATORY REFORM (FIRE SAFETY) ORDER 2005 FIRE RISK ASSESSMENT REGULATORY REFORM (FIRE SAFETY) ORDER 2005 FIRE RISK ASSESSMENT Address of premises: Tel: Responsible person (e.g. employer) or person having control of the premises: Person(s) consulted: Rodwell House

More information

FIRE RISK ASSESSMENT

FIRE RISK ASSESSMENT FIRE RISK ASSESSMENT Full Property Name: St Augustine s Catholic Voluntary Academy Full Property Address: Opposite 93 PE9 1SR Date of Fire Risk Assessment: 6 th June 2017 Name of Fire Risk Assessor: Peter

More information

FIRE RISK ASSESSMENT Self Assessment

FIRE RISK ASSESSMENT Self Assessment FIRE RISK ASSESSMENT Self Assessment Important! This fire risk assessment form is to be filled in by the responsible person within a business or organisation. As this is a free download for the use of

More information

Fire Safety Protocol

Fire Safety Protocol CORPORATE HEALTH AND SAFETY POLICY: Part 3 Arrangements Fire Safety Protocol Document Status: [ ] Guidance for Managers [] Protocol [ ] Procedures Version 0.1/ August 2013 DRAFT EALING NCIL Table of Contents

More information

REGULATORY REFORM (FIRE SAFETY) ORDER 2005 FIRE EMERGENCY PLAN

REGULATORY REFORM (FIRE SAFETY) ORDER 2005 FIRE EMERGENCY PLAN REGULATORY REFORM (FIRE SAFETY) ORDER 2005 FIRE EMERGENCY PLAN This Emergency Plan has been developed following fire risk assessments of the relevant building. The purpose of the Plan is to ensure the

More information

Wellsprings Primary School. Fire Emergency Evacuation Plan

Wellsprings Primary School. Fire Emergency Evacuation Plan Wellsprings Primary School Fire Emergency Evacuation Plan This Emergency Plan has been developed following fire risk assessments of the relevant building. The purpose of the plan is: To ensure the safety

More information

Fire Risk Assessment 2017

Fire Risk Assessment 2017 Fire Risk Assessment 2017 Westmorland House Windermere School Author Paul Brownless Date 11 April 2017 Revised Revised by 04/12/2017 Richard Hennah Reference FRA_WSWH_11042017 1 AUTHOR CLIENT Paul Brownless

More information

REGULATORY REFORM (FIRE SAFETY) ORDER 2005 FIRE RISK ASSESSMENT

REGULATORY REFORM (FIRE SAFETY) ORDER 2005 FIRE RISK ASSESSMENT REGULATORY REFORM (FIRE SAFETY) ORDER 2005 FIRE RISK ASSESSMENT Address of premises: Tel: Responsible person (e.g. employer) or person having control of the premises: Person(s) consulted: Hazeldene House

More information

Operations, contents etc: Managing Director of Kent Union. Locke Building, University of Kent, Canterbury CT2 7UG

Operations, contents etc: Managing Director of Kent Union. Locke Building, University of Kent, Canterbury CT2 7UG COVER SHEET in accordance with Publicly Available Standard PAS 79:2007 (British Standards Institute): Fire Risk Assessment - Guidance and a recommended methodology (with extensive additions) Employer or

More information

REGULATORY REFORM (FIRE SAFETY) ORDER 2005 FIRE RISK ASSESSMENT

REGULATORY REFORM (FIRE SAFETY) ORDER 2005 FIRE RISK ASSESSMENT REGULATORY REFORM (FIRE SAFETY) ORDER 2005 FIRE RISK ASSESSMENT Address of premises: Tel: Responsible person (e.g. employer) or person having control of the premises: Person(s) consulted: Harpwood Care

More information

Fire Safety Policy. Billy Hanafin H & S and Operations Officer. Fife Cultural Trust. Version 1.0 October 2013 Page 1

Fire Safety Policy. Billy Hanafin H & S and Operations Officer. Fife Cultural Trust. Version 1.0 October 2013 Page 1 Billy Hanafin H & S and Operations Officer Version 1.0 October 2013 Page 1 1. General The Trust is a responsible employer that takes its Fire Safety duties seriously. For that reason, this policy has been

More information

Fire Risk Assessment Report - Initial. 23 Newhaven Court, Nantwich, CW5 5GT

Fire Risk Assessment Report - Initial. 23 Newhaven Court, Nantwich, CW5 5GT Fire Risk Assessment Report - Initial Prepared by Your Company Name This report took 5 SECONDS to produce & a few MINUTES to collect the data on site! Download the app for FREE at www.pocketsurvey.com

More information

Health and Safety Policy. Version Author Revisions Made Date 1 Colin Campbell First Draft March 2014

Health and Safety Policy. Version Author Revisions Made Date 1 Colin Campbell First Draft March 2014 Fire Safety Policy Originator name: Section / Dept: Implementation date: Clive Parkinson Health & Safety March 2014 Date of next review: March 2017 Related policies: Health and Safety Policy Policy history:

More information

S12 Fire Safety Risk Assessment H&SFS01-1 / 9

S12 Fire Safety Risk Assessment H&SFS01-1 / 9 S12 Fire Safety Risk Assessment H&SFS01 Risk ratings The following risk ratings are based on two factors: The overall fire risk rating for the site The risk rating for the individual recommendations /control

More information

FIRE RISK ASSESSMENT REVIEW

FIRE RISK ASSESSMENT REVIEW COVER SHEET REVIEW Employer or other Responsible Person: Address of Property: Person(s) Consulted: Assessor: Head of School of Physical Sciences in conjunction with Council & the Vice Chancellor Ingram

More information

REGULATORY REFORM (FIRE SAFETY) ORDER 2005 PERIODIC REVIEW OF FIRE RISK ASSESSMENT

REGULATORY REFORM (FIRE SAFETY) ORDER 2005 PERIODIC REVIEW OF FIRE RISK ASSESSMENT REGULATORY REFORM (FIRE SAFETY) ORDER 005 PERIODIC REVIEW OF FIRE RISK ASSESSMENT Responsible person (e.g. employer) or person having control of the premises: Address of premises: Graham Care Group Cornford

More information

REGULATORY REFORM (FIRE SAFETY) ORDER 2005 FIRE EMERGENCY PLAN

REGULATORY REFORM (FIRE SAFETY) ORDER 2005 FIRE EMERGENCY PLAN REGULATORY REFORM (FIRE SAFETY) ORDER 2005 FIRE EMERGENCY PLAN This Emergency Plan has been developed following fire risk assessments of the relevant building. The purpose of the Plan is to ensure the

More information

Fire Safety Policy 2018/19

Fire Safety Policy 2018/19 Fire Safety Policy 2018/19 Reviewed: March 2016 Next Review: March 2019 1. Policy Statement The School is committed to ensuring, so far as is reasonably practicable, the health, safety and welfare of all

More information

Fire Risk Assessment Report

Fire Risk Assessment Report Fire Risk Assessment Report Fire Risk Assessment Report Company Site Address Contact details Date of Assessment St Augustine s Priory Science Block Hillcrest Rd, London W5 2JL 020 8997 2022 Bursar J Powell

More information

Fire Safety Policy 29/09/2017. Holme Grange School Whole School Policy Including EYFS. Fire Safety Policy

Fire Safety Policy 29/09/2017. Holme Grange School Whole School Policy Including EYFS. Fire Safety Policy Holme Grange School Whole School Policy Including EYFS Fire Safety Policy This document details the school s policy on fire safety in operation at Holme Grange School. The document is split into a number

More information

REGULATORY REFORM (FIRE SAFETY) ORDER 2005 FIRE RISK ASSESSMENT

REGULATORY REFORM (FIRE SAFETY) ORDER 2005 FIRE RISK ASSESSMENT OVERALL COLOUR ACTION CODE RISK AMBER STATUTORY INSTRUMENT 2005:1541 REGULATORY REFORM (FIRE SAFETY) ORDER 2005 FIRE RISK ASSESSMENT Address of Premises: Thuurock CCG, Civic Offices New Road Grays Responsible

More information

REGULATORY REFORM (FIRE SAFETY) ORDER 2005 PERIODIC REVIEW OF FIRE RISK ASSESSMENT

REGULATORY REFORM (FIRE SAFETY) ORDER 2005 PERIODIC REVIEW OF FIRE RISK ASSESSMENT REGULATORY REFORM (FIRE SAFETY) ORDER 2005 PERIODIC REVIEW OF FIRE RISK ASSESSMENT Responsible person (e.g. employer) or person having control of the premises: Address of premises: Graham Care Group Cornford

More information

THE REGULATORY REFORM (FIRE SAFETY) ORDER 2005 FIRE RISK ASSESSMENT NEW BUILDINGS

THE REGULATORY REFORM (FIRE SAFETY) ORDER 2005 FIRE RISK ASSESSMENT NEW BUILDINGS FIRE RISK ASSESSMENT NEW BUILDINGS BUILDING SUMMARY The building is utilised for classroom teaching for Modern Languages. 1. Identification of the hazards 1.1 Identification of sources of fuel. Timber

More information

FIRE RISK ASSESSMENT Waterstones High Street, Solihull, West Midlands, B91 3SW.

FIRE RISK ASSESSMENT Waterstones High Street, Solihull, West Midlands, B91 3SW. Waterstones 69-71 High Street, Solihull, West Midlands, B91 3SW. BAFE Certificate Number: 0040921 CONTENTS: BAFE SP205 Certificate of Compliance 3 Introduction 5 Risk Assessment Methodology 6 PAS 79 Fire

More information

FIRE SAFETY LOG BOOK. (Record of Fire Safety Equipment Testing)

FIRE SAFETY LOG BOOK. (Record of Fire Safety Equipment Testing) FIRE SAFETY LOG BOOK (Record of Fire Safety Equipment Testing) Fire safety log book MARCH 2013 CONTENTS 1.0 PREMISES SPECIFIC INFORMATION 2.0 FIRE SAFETY EQUIPMENT TESTING 2.1 Escape Routes 2.2 Fire Warning

More information

Fire Risk Assessment Report

Fire Risk Assessment Report Fire Risk Assessment Report Fire Risk Assessment Report Company Site Address Contact details Date of Assessment St Augustine s Priory Clockhouse Nursery and Early ears Hillcrest Rd, London W5 2JL 020 8997

More information

REGULATORY REFORM (FIRE SAFETY) ORDER 2005 FIRE EMERGENCY PLAN

REGULATORY REFORM (FIRE SAFETY) ORDER 2005 FIRE EMERGENCY PLAN REGULATORY REFORM (FIRE SAFETY) ORDER 2005 FIRE EMERGENCY PLAN This Emergency Plan has been developed following fire risk assessments of the relevant building. The purpose of the Plan is to ensure the

More information

EMLC Academy Trust. Fire Safety Policy 2017/19. Every child deserves to be the best they can be

EMLC Academy Trust. Fire Safety Policy 2017/19. Every child deserves to be the best they can be EMLC Academy Trust Fire Safety Policy 2017/19 Every child deserves to be the best they can be 1 Scope: EMLC Academy Trust & Academies within the Trust Version: 2 Filename: EMLC Academy Trust Fire Safety

More information

NOTTINGHAM CITY HOMES

NOTTINGHAM CITY HOMES APPENDIX 1 NOTTINGHAM CITY HOMES FIRE SAFETY POLICY 2013/14 Draft for Board Uncontrolled when printed Page 1 of 14 DOCUMENT CONTROL Identification and Approval Status Document Title: Nottingham City Homes

More information

THE REGULATORY REFORM (FIRE SAFETY) ORDER 2005 FIRE RISK ASSESSMENT SPORTS CENTRE

THE REGULATORY REFORM (FIRE SAFETY) ORDER 2005 FIRE RISK ASSESSMENT SPORTS CENTRE FIRE RISK ASSESSMENT SPORTS CENTRE BUILDING SUMMARY The building is used as a Sports Centre and contains a large sports hall with changing rooms, an office for staff and a fitness area. 1. Identification

More information

1970s building housing main school reception and support offices. Well managed buildings with no significant risk of a fire occurring.

1970s building housing main school reception and support offices. Well managed buildings with no significant risk of a fire occurring. Record of significant findings Risk assessment for : Assessment undertaken by : 71a The Close Nigel Billing CMIOSH Date: 21/3/17 Overview of Premises: 1970s building housing main school reception and support

More information

Health & Safety Policy HSP 03 Fire Safety Version Status Date Title of Reviewer Purpose/Outcome

Health & Safety Policy HSP 03 Fire Safety Version Status Date Title of Reviewer Purpose/Outcome Health & Safety Policy HSP 03 Fire Safety Version Status Date Title of Reviewer Purpose/Outcome 1.0 Draft 07.03.2016 David Maine 1 st Draft for consultation/review 1.1 Approved 22.12.2016 David Maine 1

More information

THE REGULATORY REFORM (FIRE SAFETY) ORDER 2005 FIRE RISK ASSESSMENT HORSEFAIR HOUSE

THE REGULATORY REFORM (FIRE SAFETY) ORDER 2005 FIRE RISK ASSESSMENT HORSEFAIR HOUSE FIRE RISK ASSESSMENT HORSEFAIR HOUSE BUILDING SUMMARY The building is utilised for the teaching of Science and contains Laboratories and Chemical storage. 1. Identification of the hazards 1.1 Identification

More information

Fire Risk Assessment. Guidance Notes. Location details. Risk Rating. Assessors. General notes

Fire Risk Assessment. Guidance Notes. Location details. Risk Rating. Assessors. General notes Fire Assessment Location details Company Name Site address Site contact name Phone Guidance Notes looking at the workplace to identify potential A hazard is something that has the potential to cause harm;

More information

REGULATORY REFORM (FIRE SAFETY) ORDER 2005 PERIODIC REVIEW OF FIRE RISK ASSESSMENT

REGULATORY REFORM (FIRE SAFETY) ORDER 2005 PERIODIC REVIEW OF FIRE RISK ASSESSMENT REGULATORY REFORM (FIRE SAFETY) ORDER 2005 PERIODIC REVIEW OF FIRE RISK ASSESSMENT Responsible person (e.g. employer) or person having control of the premises: Address of premises: Tel: Person(s) consulted:

More information

Following a near miss (after a fire or where evidence suggests that a fire could have occurred).

Following a near miss (after a fire or where evidence suggests that a fire could have occurred). Contents: This is your Fire Risk Assessment Revision of this risk assessment Scope of assessment and methodology Executive Summary Risk Rating Assessment Overview The Responsible Person/Duty Holder Persons

More information

LYHA Fire Safety Policy

LYHA Fire Safety Policy LYHA Fire Safety Policy Introduction This Fire Safety Policy shows our approach to Fire Safety in the work place and in our homes. It identifies our approach to Fire Safety in: The workplace Flats with

More information

Fire Safety Policy. Somerville College Woodstock Road Oxford OX2 6HD

Fire Safety Policy. Somerville College Woodstock Road Oxford OX2 6HD Fire Safety Policy Somerville College Woodstock Road Oxford OX2 6HD Table of Contents 1.0 Introduction... 2 2.0 Legislative Requirements... 2 3.0 Fire Risk Assessment... 3 4.0 Management of Fire Safety...

More information

FIRE RISK ASSESSMENT. Hatton House. Page 1 of 21

FIRE RISK ASSESSMENT. Hatton House. Page 1 of 21 FIRE RISK ASSESSMENT Hatton House Page 1 of 21 CONTENTS Page 1 Introduction 3-6 2 Premises Particulars 7 3 General Statement Of Policy 7 4 Management Systems 7 5 General Description Of Premises 9 6 Fire

More information

REGULATORY REFORM (FIRE SAFETY) ORDER 2005 PERIODIC REVIEW OF FIRE RISK ASSESSMENT

REGULATORY REFORM (FIRE SAFETY) ORDER 2005 PERIODIC REVIEW OF FIRE RISK ASSESSMENT REGULATORY REFORM (FIRE SAFETY) ORDER 2005 PERIODIC REVIEW OF FIRE RISK ASSESSMENT Responsible person (e.g. employer) or person having control of the premises: Address of premises: Tel: Person(s) consulted:

More information

5 Key Stages to Risk Assessment

5 Key Stages to Risk Assessment 5 Key Stages to Risk Assessment Stage 1: Identify Fire Hazards For a fire to start, three things are needed: A source of ignition Fuel Oxygen If any one of these is missing, a fire cannot start. Taking

More information

H&S Forum. Fire Safety Policy Glascote Academy

H&S Forum. Fire Safety Policy Glascote Academy Fierte Multi Academy Trust Health and Safety Policy Handbook Reference Number HR 103 Issue 6 Approved By H&S Forum Date September 2016 To be reviewed September2017 Policy Title Fire Safety Policy Glascote

More information

Millfield Schools Fire Risk Prevention Policy

Millfield Schools Fire Risk Prevention Policy Millfield Schools Fire Risk Prevention Policy This policy refers to the Senior School, Preparatory School, Pre-Preparatory School and EYFS 1. Introduction This policy sets out the approach that the school

More information

Well managed building mean risk is normal. Fire action notices should be displayed by all alarm break glass call points.

Well managed building mean risk is normal. Fire action notices should be displayed by all alarm break glass call points. Record of significant findings Risk assessment for : Assessment undertaken by : Horsefair House Nigel Billing CMIOSH Date: 28/3/17 Overview of Premises: 2 buildings on 3 stories in an L shaped configuration,

More information

Fire Risk Management Policy. UK September 2017

Fire Risk Management Policy. UK September 2017 UK September 2017 5 & 7 Diamond Court, Opal Drive, Eastlake Park, Fox Milne, Milton Keynes MK15 0DU, T: 01908 396250, F: 01908 396251, www.cognitaschools.co.uk Registered in England Cognita Limited No

More information

FIRE SAFETY AND PREVENTION POLICY

FIRE SAFETY AND PREVENTION POLICY Effective Date: July 26, 2011 Supersedes /Amends: VRS-49/April 2006 Originating Office: Office of the Vice-President, Services Policy Number: VPS-49 PREAMBLE Concordia University (the University ) has

More information

THE REGULATORY REFORM (FIRE SAFETY) ORDER 2005 FIRE RISK ASSESSMENT NO 68 (ENGLISH AND PHILOSOPHY)

THE REGULATORY REFORM (FIRE SAFETY) ORDER 2005 FIRE RISK ASSESSMENT NO 68 (ENGLISH AND PHILOSOPHY) FIRE RISK ASSESSMENT NO 68 (ENGLISH AND PHILOSOPHY) BUILDING SUMMARY The building was constructed in Victorian times and is constructed of brick with knapped flint in fill on some outer walls. The building

More information

St Edward s Oxford FIRE SAFETY POLICY

St Edward s Oxford FIRE SAFETY POLICY FIRE SAFETY POLICY 1 CONTENTS Section Page No.(s) 1. Policy Statement 3-5 2. Organisation and Responsibilities 6 3. Responsibilities of Responsible Person 7-8 4. Responsibilities of Senior Management 9

More information

FIRE PROCEDURES 1. APPOINTMENTS

FIRE PROCEDURES 1. APPOINTMENTS 12b FIRE PROCEDURES 1. APPOINTMENTS Responsible Person In compliance with the Regulatory Reform (Fire Safety) Order 2005 (FSO), the School s Head, Mrs C Cameron is appointed as the Responsible Person for

More information

KRISHNAMURTI FOUNDATION TRUST FIRE SAFETY POLICY. Last Review Date 30 June Next review date 30 August Health and Safety Officer

KRISHNAMURTI FOUNDATION TRUST FIRE SAFETY POLICY. Last Review Date 30 June Next review date 30 August Health and Safety Officer KRISHNAMURTI FOUNDATION TRUST FIRE SAFETY POLICY Last Review Date 30 June 2015 Policy endorsed by Policy is maintained by ISI reference Trustees Co-Principals/Directors A9, B6, B9 Next review date 30 August

More information

Fire Safety Policy. (The Regulatory Reform (Fire Safety) Order 2005) Last Reviewed: January Next Review: January 2019

Fire Safety Policy. (The Regulatory Reform (Fire Safety) Order 2005) Last Reviewed: January Next Review: January 2019 Fire Safety Policy (The Regulatory Reform (Fire Safety) Order 2005) Last Reviewed: January 2018 Next Review: January 2019 Person Responsible: School Business Manager 1 P age 1. INTRODUCTION a) King Fahad

More information

FIRE SAFETY POLICY. Health and Safety. Reviewed by: Health & Safety Committee (2 May 2018) Approved by: Council (25 June 2018)

FIRE SAFETY POLICY. Health and Safety. Reviewed by: Health & Safety Committee (2 May 2018) Approved by: Council (25 June 2018) FIRE SAFETY POLICY Owner: Health and Safety Reviewed by: Health & Safety Committee (2 May 2018) Approved by: Council (25 June 2018) Review due date: May 2019 Update history: Approved by Council 8 March

More information

Fire safety procedure

Fire safety procedure Fire safety procedure Review date: October 2020 Responsible (s): Health and Safety Applicable to Staff: Accessible to Students: Accessible to general public: (including clients) Yes Yes Yes 1 Contents

More information

The Regulatory Reform (Fire Safety) Order 2005 Fire Risk Assessment Proforma

The Regulatory Reform (Fire Safety) Order 2005 Fire Risk Assessment Proforma Reference Number: This risk assessment and ALL associated documents must be retained. Date : Sept 17 The Regulatory Reform (Fire Safety) Order 2005 Fire Risk Assessment Proforma This Fire Risk Assessment

More information

SOUTHERN HEALTH NHS FOUNDATION TRUST

SOUTHERN HEALTH NHS FOUNDATION TRUST SOUTERN EALT NS FOUNDATION TRUST REGULATORY REFORM (FIRE SAFETY) ORDER 2005 PERIODIC REVIEW OF FIRE RISK ASSESSMENT Address of Property: Person(s) consulted: Parklands ospital, Aldermaston Road Basingstoke

More information

Fire Risk Assessment Safety Checklist

Fire Risk Assessment Safety Checklist Fire Risk Assessment Safety Checklist This checklist has been prepared to help you comply with The Regulatory Reform Fire Safety Order 2005 What is the Regulatory Reform (Fire Safety) Order 2005? The Regulatory

More information

Fire Risk Assessment Guide

Fire Risk Assessment Guide Fire Risk Assessment Guide Thank you for your interest in the Fire Risk Assessment for your block. All of our blocks have had a recent Fire Risk Assessment in line with regulatory requirements and we are

More information

ISLE OF WIGHT FIRE & RESCUE SERVICE

ISLE OF WIGHT FIRE & RESCUE SERVICE ISLE OF WIGHT FIRE & RESCUE SERVICE Record of Fire Safety Equipment Testing Fire Drills & Training CONTENTS 1. MEANS OF ESCAPE 2. FIRE WARNING AND AUTOMATIC FIRE DETECTION 3. FIRE EXTINGUISHERS AND HOSEREELS

More information

Fire Safety Management Audit Specification August 2017

Fire Safety Management Audit Specification August 2017 Fire Safety Management Audit Specification August 2017 Membership Training Qualifications Audit and Consultancy Policy and Opinion Awards Contents Page 1 Introduction to the Fire Safety Management Audit

More information

HEALTH & SAFETY MANAGEMENT ARRANGEMENTS FOR FIRE SAFETY

HEALTH & SAFETY MANAGEMENT ARRANGEMENTS FOR FIRE SAFETY HEALTH & SAFETY MANAGEMENT ARRANGEMENTS FOR FIRE SAFETY INTRODUCTION Cwmni CYNNAL recognises its duty of care to employees and all reasonable steps will be taken to secure the health and safety of employees.

More information

Fire Safety Policy Date: 0

Fire Safety Policy Date: 0 Fire Safety Policy Date: 0 Policy Preparation & Introduction This document format has been produced by Firesafe Solutions (UK) Ltd to aid managers, tenants and others responsible for fire safety in their

More information

Fire Risk Assessment Guide

Fire Risk Assessment Guide Fire Risk Assessment Guide Thank you for your interest in the Fire Risk Assessment for your block. All of our blocks have had a recent Fire Risk Assessment in line with regulatory requirements and we are

More information

UNIVERSITY COLLEGE LONDON EMERGENCY PLAN. Regulatory Reform (Fire Safety) Order 2005 PART ONE - SPECIFIC INSTRUCTIONS & OTHER RELEVANT INFORMATION:

UNIVERSITY COLLEGE LONDON EMERGENCY PLAN. Regulatory Reform (Fire Safety) Order 2005 PART ONE - SPECIFIC INSTRUCTIONS & OTHER RELEVANT INFORMATION: UCL ESTATES & FACILITIES DIVISION Construction Maintenance & Fire Safety UNIVERSITY COLLEGE LONDON EMERGENCY PLAN Regulatory Reform (Fire Safety) Order 2005 Name & Address of Building: Occupying Department(s)

More information

Fire Policy and Procedures. Cañada Blanch Spanish School

Fire Policy and Procedures. Cañada Blanch Spanish School Fire Policy and Procedures Cañada Blanch Spanish School SUMMARY 1. Introduction (p. 3) 2. Roles and responsibilities (p. 3) -- Headteacher -- Fire Team -- All staff -- Contractors 3. Fire procedures (p.

More information

GDST Fire Safety Strategy March 2016

GDST Fire Safety Strategy March 2016 GDST Fire Safety Strategy March 2016 GDST Fire Safety Strategy v1.0 March 2016 Page 1 of 17 Contents 1. Introduction 3 2. Compliance Statement 3 3. Fire Safety Strategy Aims and Objectives 3 Strategic

More information

161 Rosebery Avenue, London, EC1 Fire Safety Management Plan & Evacuation Procedures

161 Rosebery Avenue, London, EC1 Fire Safety Management Plan & Evacuation Procedures 161 Rosebery Avenue, London, EC1 Fire Safety Management Plan & Evacuation Procedures Contents 1.0 Introduction 2.0 Means of Escape in Case of Fire 3.0 Means for Giving Warning in Case of Fire 4.0 Means

More information

Health, Safety and Wellbeing Management Arrangements. Core I Consider I Complex. Fire Safety. Health, Safety and Wellbeing Service

Health, Safety and Wellbeing Management Arrangements. Core I Consider I Complex. Fire Safety. Health, Safety and Wellbeing Service Health, Safety and Wellbeing Management Arrangements Core I Consider I Complex Fire Safety Health, Safety and Wellbeing Service 1. Success Indicators The following indicators will demonstrate success in

More information

Local Rules: Fire Safety

Local Rules: Fire Safety 1. Potential Effects of a Fire A small fire is most likely to cause damage to equipment and furniture, with the potential to cause additional smoke damage to the room of origin. A large and protracted

More information

Charlotte Building, 17 Gresse Street, London W1T 1QL

Charlotte Building, 17 Gresse Street, London W1T 1QL Charlotte Building, 17 Gresse Street, London W1T 1QL Fire Safety Management & Evacuation Procedures Contents 1.0 Introduction 2.0 Means of Escape in Case of Fire 3.0 Means for Giving Warning in Case of

More information

Fire Evacuation Policy

Fire Evacuation Policy Fire Evacuation Procedures Policy Fire Evacuation Policy Contents Page Number Introduction 2 Staff Responsibilities and Training 2 Protective Equipment Fire Extinguishers 3 Inspection Procedures/Good Housekeeping

More information

FIRE SAFETY & EMERGENCY EVACUATION STRATEGY AND POLICY

FIRE SAFETY & EMERGENCY EVACUATION STRATEGY AND POLICY FIRE SAFETY & EMERGENCY EVACUATION STRATEGY AND POLICY Under the terms of the Box Hill School must ensure the safety from fire of all staff, pupils, contractors and visitors. In order to do this the school

More information

Fire Risk Assessment Guide

Fire Risk Assessment Guide Fire Risk Assessment Guide Thank you for your interest in the Fire Risk Assessment for your block. All of our blocks have had a recent Fire Risk Assessment in line with regulatory requirements and we are

More information

Fire Risk Assessment

Fire Risk Assessment Fire Risk Assessment Department The Cockpit Risk Assessment number PM/06/2015 Date. 17 th June 2015 Review due date 17 th June 2016 Activity: Fire safety risk assessment Location: The Cockpit Name of Assessors:

More information

FIRE PREVENTION, PROCEDURES AND RISK ASSESSMENT POLICY

FIRE PREVENTION, PROCEDURES AND RISK ASSESSMENT POLICY FIRE PREVENTION, PROCEDURES AND RISK ASSESSMENT POLICY PART 1: FIRE SAFETY INTRODUCTION Our priority is to minimise the risk to life and to reduce injury by maintaining the physical fire safety of the

More information

Fire Safety Strategy

Fire Safety Strategy SH HS 02 Summary: Keywords (minimum of 5): (To assist policy search engine) Target Audience: The aim of this strategy is the provision and maintenance of a safe environment for all staff, visitors and

More information

Fire Risk Assessment 2016

Fire Risk Assessment 2016 Fire Risk Assessment 2016 Elleray Campus Windermere School Author Paul Brownless Date 07 December 2016 Reviewed Reviewer 20 November 2017 Richard Hennah Reference FRA_EC_07122016 1 AUTHOR CLIENT Paul Brownless

More information

A basic guide to... Fire Safety for Scout Premises

A basic guide to... Fire Safety for Scout Premises A basic guide to... Fire Safety for Scout Premises A basic guide to Fire Safety for Scout Premises This Guide has been designed and produced by Chubb Fire to assist persons responsible for fire safety

More information

NOT PROTECTIVELY MARKED. Fire Legislation

NOT PROTECTIVELY MARKED. Fire Legislation Fire Legislation Contents Policy Statement... 2 Legislation... 2 Fire Extinguisher Usage... 2 Fire Evacuation Procedure... 3... 4 Line Managers/Supervisors... 4 Business Support Officer... 5 Driver/Handy

More information

FIRE SAFETY POLICY LEEDS METHODIST MISSION. Oxford Place Centre

FIRE SAFETY POLICY LEEDS METHODIST MISSION. Oxford Place Centre FIRE SAFETY POLICY LEEDS METHODIST MISSION Oxford Place Centre P a g e 2 8 Version Draft 1 Name of responsible (ratifying) committee Leeds Methodist Mission Council Date ratified Document Manager (job

More information

Fire Risk Assessment DURSTON HOUSE SCHOOL Castlebar Road, Ealing, London, W5 2DR. Prepared by: Steven Cox BA(Hons), ACII, AIOSH

Fire Risk Assessment DURSTON HOUSE SCHOOL Castlebar Road, Ealing, London, W5 2DR. Prepared by: Steven Cox BA(Hons), ACII, AIOSH Fire Risk Assessment DURSTON HOUSE SCHOOL 12-14 Castlebar Road, Ealing, London, W5 2DR Prepared by: Steven Cox BA(Hons), ACII, AIOSH Hettle Andrews & Associates Limited Eleven Brindleyplace 2 Brunswick

More information

WILTSHIRE POLICE FORCE PROCEDURE. Fire Safety Management

WILTSHIRE POLICE FORCE PROCEDURE. Fire Safety Management WILTSHIRE POLICE FORCE PROCEDURE Fire Safety Management Date of Publication: May 2018 Version: 8.0 Next Review Date: May 2019 TABLE OF CONTENTS PROCEDURE OVERVIEW... 3 GLOSSARY OF TERMS... 3 RELATED POLICIES,

More information

Health and Safety Services. Safety Guide 5. Fire drills

Health and Safety Services. Safety Guide 5. Fire drills Health and Safety Services Safety Guide 5 Fire drills Fire drills Contents Summary...iii 1. Scope...1 2. Responsibilities...1 2.1. Duties on managers... 1 2.2. Duties of all building occupants... 1 2.3.

More information

Fire Safety. A TUC guide for trade union activists

Fire Safety. A TUC guide for trade union activists Fire Safety A TUC guide for trade union activists Contents Section one Introduction 3 Section two The law 4 Section three Fire risk assesment 5 Section four Policies and procedures 6 Section five Enforcement

More information