Sprinklers Modeling for Tunnel Road Fire Fighting

Size: px
Start display at page:

Download "Sprinklers Modeling for Tunnel Road Fire Fighting"

Transcription

1 Sprinklers Modeling for Tunnel Road Fire Fighting P. Ciambelli, M.G. Meo, P. Russo, S. Vaccaro Department of Chemical and Food Engineering, University of Salerno - ITALY 1. INTRODUCTION Loss of lives and strong damages to tunnel structures consequent to fires in European tunnels, placed a focus on fire safety issues concerning tunnels. Beside traditional means of fire control and protection, new innovative measures such as water mist and sprinkler systems have been proposed. However, their employment, although accepted as good standard in other applications [1], is controversial for tunnel fires as its benefit is strongly connected to fire scenario, ventilation conditions and fire reliable detection [2]. Ventilation, instead, is by far the best known mitigation system and, then, it is widely applied in existing tunnels although there is no guarantee that it will efficiently work in all fire scenarios. Computational Fluid Dynamics (CFD) may be usefully employed to assess the performance of different mitigation measures and to design properly fire protection systems. The present authors in previous studies [3,4] used a CFD code, JASMINE, to assess the effectiveness of several fire protection systems in a m long tunnel where a car incident evolved in a severe gasoline pool fire. They found that the only natural ventilation was not sufficient to assure safety conditions for escape and rescue operations and that, among the various tunnel forced ventilation systems (axial and transverse), the axial proved to be very effective for immediately creating upstream the fire a safe route for evacuation and rescue, although very unsafe conditions took place downstream the fire. The authors also investigated the mitigation effect on the hypothesized tunnel fire of the presence of a sprinkler system alone [5]. They found that it helps in confining the fire and in reducing the spread and the temperature of the hot gases along the tunnel on both sides with respect to the fire site, and strongly limits tunnel structural damages. Negative effects of the presence of sprinklers were found on the oxygen concentration close to the fire location and on the visibility distance. The focus of the current study was to investigate the mitigation effect of the simultaneous presence of a sprinklers system and of a system on the hypothesized tunnel fire consequent to an car crash and gasoline spilling from a tank truck. 2. CASE STUDY A gasoline pool fire in a tunnel was assumed as scenario. The tunnel is a two-tubes (each tube one-way) road tunnel located between Pontecagnano and Salerno along the Italian highway A3. It is about m long, with an arched cross section of 12 m x 7 m and it is equipped only with natural ventilation and has no fire mitigation systems. A 1 x 1 m 2 pool fire with a burning rate of.4 kg/m 2 s was assumed at the tunnel centre, with a very fast growth rate (up to 17 MW in 9 s) followed by a constant HRR phase until 1 min. 3. NUMERICAL SIMULATIONS 3.1. The CFD-Sprinkler model The JASMINE code by FRS/BRE, uses CFD to describe the heat and mass transfer processes associated with the dispersion of combustion products from a fire. An Eulerian-Lagrangian sprinkler particle-tracking model, SPARTA, is coupled to the CFD model to allow to predict the interaction of the water spray with the combustion gas. The computed motion, heating and IX-4, 1

2 31st Meeting on Combustion evaporation of the droplets are fully coupled to the gas phase CFD calculations to incorporate momentum, mass and heat transfer between gas phase and droplets [1, 6, 7]. The simulations were run using the modified k- model for turbulence and the eddy break-up model for combustion. The total energy available for convection was assumed to be 7% of the real HRR to take into account the energy loss for radiation. An extended domain was employed to ensures realistic simulation of the plume outside the tunnel. A grid with variable cell size was set. A 5 s time step was set for the simulations without sprinklers and 2 s for the simulations with sprinklers. The maximum number of iterations per time step was 1. A forced with a global 6 m 3 /s air flow rate was simulated by two ceiling axial fans located close to the entrance portal. A sprinklers system set up in the tunnel central zone was hypothesized by 5 pendant automatic bulb-activated heads with a flow rate of 9 dm 3 /min each arranged in a 2 (across) by 25 (along) grid, spaced 5 m x 1 m. The sprinklers were assumed to be Early Suppression Fast Response, extended coverage type, going into action if they were heated to their actuation temperature (8 C). During the simulations in the case of the sprinklers system alone, they resulted symmetrically activated along the tunnel progressively in 12 s, while in the case of the combined sprinklers and system all the heads downstream and those restricted to 4 m upstream resulted activated after 9 s The simulation results Simulations results yielded fire-induced temperatures, species and pollutants concentrations. The visibility distance was estimated assuming a smoke particulate yield of.5 kg/kg of fuel. The performance of the single and combined mitigation systems ( and sprinkler) in managing and containing the consequences of the hypothesized tunnel fire was evaluated by comparing values of calculated gas temperature, CO, CO 2 and O 2 concentrations, visibility and radiation heat flux at the breathing height of 2 m, on the tunnel centreline, at the presumed distances walked down by pedestrians escaping from the tunnel centre and at the pertaining times with the accepted safety values for tunnel users. The presumed distances walked down by escaping pedestrians and at the pertaining times were calculated considering an escape delay of 9 s after the fire ignition and a pedestrian flight velocity of 1.2 m/s Accepted safety criteria for tunnel users The survival aims for tunnel users are: i) pollutants and toxic species concentrations below dangerous values (IDLH is 5 ppm for CO 2 and 15 ppm for CO [8]); ii) minimum 16 vol % O 2 concentration to allow breathing without impairing thinking and coordination [9]; iii) smoke concentration such that illuminated signs should be discernible at 1 m [1]; iv) gas temperatures not exceeding 6 C, or 5 C when water based suppression are activated [1]; v) radiation heat flux below 5 kw/m 2 [1]. 4. RESULTS Simulations results are reported in Fig. 1 as space profiles of the gas temperature at different times (t = 2, 3, 4 and 5 min) after the fire start during the early phase of the fire and in Fig. 2 as time profiles of temperature (Fig. 2a and 2b), oxygen concentration (Fig. 2c and 2d) and visibility (Fig. 2e and 2f). These time profiles, however, are not obtained at a fixed distance from the fire but, for each time, at the distance, both upstream and downstream the fire, presumably (according to the assumption reported under section 3.2) walked down by pedestrians who were close to the fire location when the fire started. In Fig. 2 there is also a red hatched zone, which represents for each variable the region where the survival criteria, IX-4, 2

3 Italian Section of the Combustion Institute reported under the section 3.3, are not fulfilled. Therefore, if the value of the variable is in the red hatched zone it gives rise to unsafe conditions for people. The results in Fig. 1 show how the keeps very low the temperature upstream the fire, but at the same time it rapidly increases the temperature along the whole tunnel portion downstream the fire by carrying over there the combustion gases. With the sprinklers system alone a global beneficial effect on confining the fire, cooling the gases and reducing their spread along the tunnel occurs, as it is clearly shown particularly by the temperature profiles in Fig. 1c and 1d. When the forced ventilation and the sprinklers are simultaneously operated, Fig. 1 shows very safe conditions upstream the fire (a little better than with the only forced ventilation) but unsafe conditions take place downstream the fire. Actually, the gas temperature is much lower than with the only forced ventilation but in any case much higher than that necessary to survive. The combined effect of the sprinklers and of forced ventilation limits the temperature of the smoke layer throughout the tunnel zone downstream the fire. Compared to the longitudinal ventilation alone, the automatic sprinklers greatly cool the hot layer along all the downstream zone when the fire is fully developed (t = 4 min, 5 min). However, while the sprinklers system alone was able to contain most of the combustion products within the fire zone cooling the smoke layer, the combined added effect of the ventilation system extends the smoke movement along the tunnel in a shorter time. At t = 4 min, with the combined ventilationsprinklers systems, the combustion gases spread downstream throughout the tunnel, and at the height of 2 m the hot black smoke completely fills the tunnel. a) b) sprinklers sprinkers tunnel length - distance from fire (m) c) tunnel length - distance from fire (m) d) tunnel length - distance from fire (m) tunnel length - distance from fire (m) Fig. 1 Temperature profiles along the tunnel centreline at 2 m from the floor. a) t = 2 min; b) t = 3 min; c) t = 4 min; d) t = 5 min. The survival possibility, yielded by the various fire protection systems, for people located close to the fire location when the fire starts can be assessed on the basis of data shown in Fig. 2. Specifically, for what concerns gas temperature, only the simultaneous action of forced ventilation and sprinklers assures safe conditions upstream the fire (Fig. 2 a) but none of the IX-4, 3

4 31st Meeting on Combustion protection systems guarantees safety flight downstream the fire (Fig. 2 b). The oxygen concentration upstream the fire results safe for all the protection systems but for the sprinklers alone (Fig. 2 c) while downstream the fire it is unsafe whatever the protection measure but the natural ventilation (Fig. 2 d). For what concerns the visibility, irrespective of the fire protection system, very unsafe conditions for escaping people are found downstream the fire (Fig. 2 f). Upstream the fire, instead, the visibility is always below the safety values for natural ventilation and sprinklers alone (Fig. 2 e). However, and the combination of and sprinklers give rise to safe values of visibility except in the time interval 6-1 s, that is when people who stands close to the fire when it starts, initiates the escape. This would mean that such a people could never initiate the escape. UPSTREAM THE FIRE DOWNSTREAM THE FIRE T ( C) 1 T ( C) 1 a) b) O 2 concentration (v/v) O 2 concentration ( C) c) visibility distance (m) d) visibility distance (m) natural ventilation sprinklers sprinklers + safety value e) f) Fig. 2 (a, b) Temperature, (c, d) oxygen concentration and (e, f) visibility profiles along the time at the respective escape distance from the fire location (at 2 m from the floor, at the tunnel centreline). a), c), e): escape in the upstream direction; b), d), f): escape in the downstream direction. Red hatched: unsafe conditions. Compared to the alone, the simultaneous presence of sprinklers cools IX-4, 4

5 Italian Section of the Combustion Institute down the temperatures, but in any case at values above the safety limit of 5 C. Similarly, the oxygen concentration is below the 16 vol. % minimum concentration downstream the fire up to the exit portal. The smoke downdrag occurs mainly at the location of the sprinklers, in the tunnel section downstream the fire where the activation temperature is reached in very short time because of the asymmetry of the airflow conditions, thus affecting the visibility distance. The presence of sprinklers alone and when combined with the forced ventilation has a further positive effect: it strongly limits tunnel structural damages because very high gas temperatures occurs only in a small region and for short time. This can be appreciated from Fig. 3 where the profiles along the tunnel of the ceiling temperature at 5 min from the fire start, i.e. when the fire is fully developed, are reported by (Fig. 3). 1 sprinklers sprinklers + T ( C) tunnel lenght - distance from fire (m) Fig. 3 Ceiling gas temperatures along tunnel length at the tunnel centerline, t = 5 min. 5. CONCLUSIONS Numerical simulations of a proposed tunnel have indicated the benefits and the limits of a combined system of mechanical smoke management () and sprinklers. Parametric studies could be performed with different ventilation and sprinkler systems to help optimise the design of future tunnel fire mitigation strategies. 6. REFERENCES 1. Miles, S., Kumar, S., Chong, K.: Fourth International. Conference on Tunnel Fires, Basel, Switzerland, December, p. 329 (22). 2. Fielding, L.: International Symposium on Catastrophic Tunnel Fires, Borås, Sweden, November, p. 23 (23). 3. Ciambelli, P., Meo, M.G., Russo, P., Vaccaro, S.: Third International Conference on Tunnel Safety and Ventilation, Graz, Austria, May, p. 324 (26). 4. Ciambelli P., Meo M.G., Russo P., Vaccaro S.: Proceedings of the 29 th Meeting on Combustion of The Italian Section of The Combustion Institute, I15.1 (26).. 5. Ciambelli, P., Meo, M.G., Russo, P., Vaccaro, S.: Fifth International Seminar on Fire And Explosion Hazards, Edinburgh, UK, April, in press (27). 6. Miles, S., Kumar, S.: Fifth International Conference on Tunnel Fires, London, UK, October, p. 23 (24). 7. Kumar, S.: First International Symposium on Safe and Reliable Tunnels. Innovative European Achievements, Prague, Czech Republic, February, p. 97 (24). IX-4, 5

6 31st Meeting on Combustion 8. NIOSH-CDC, Documentation for Immediately Dangerous to Life or Health Concentrations (IDLH). Available from: 9. Rom, W.: Environmental and Occupational Medicine. Little Brown, Boston, (1992). 1. Opstad, K., Stensaas, J.P.: Second International Symposium on Safe and Reliable Tunnels. Innovative European Achievements, Lausanne, Switzerland, May (26). IX-4, 6

An experimental study of the impact of tunnel suppression on tunnel ventilation

An experimental study of the impact of tunnel suppression on tunnel ventilation An experimental study of the impact of tunnel suppression on tunnel ventilation Yoon J. Ko and George Hadjisophocleous Civil and Environmental Engineering, Carleton University 1125 Colonel By Drive, Ottawa,

More information

CHOOSING A FIRE VENTILATION STRATEGY FOR AN UNDERGROUND METRO STATION

CHOOSING A FIRE VENTILATION STRATEGY FOR AN UNDERGROUND METRO STATION - 165 - CHOOSING A FIRE VENTILATION STRATEGY FOR AN UNDERGROUND METRO STATION Wojciech Węgrzyński, Grzegorz Krajewski, Paweł Sulik Fire Research Department, Building Research Institute (ITB), Poland ABSTRACT

More information

Using FDS Modelling to Establish Performance Criteria for Water Mist Systems on Very Large Fires in Tunnels

Using FDS Modelling to Establish Performance Criteria for Water Mist Systems on Very Large Fires in Tunnels Using FDS Modelling to Establish Performance Criteria for Water Mist Systems on Very Large Fires in Tunnels Jack R. Mawhinney, P. Eng., FSFPE Javier J. Trelles, Ph.D. Authors & acknowledgement J. R. Mawhinney

More information

Impact of quick incident detection on safety in terms of ventilation response

Impact of quick incident detection on safety in terms of ventilation response Impact of quick incident detection on safety in terms of ventilation response P. J. Sturm 1) ; C. Forster 2) ; B. Kohl 2) ; M. Bacher 1) 1) Institute for Internal Combustion Engines and Thermodynamics

More information

CFD STUDY OF FIRE PROTECTION SYSTEMS IN TUNNEL FIRES

CFD STUDY OF FIRE PROTECTION SYSTEMS IN TUNNEL FIRES UDC 614.84 : 628.854 : 52-17 DOI: 10.7562/SE2011.1.01.03 Original article www.safety.ni.ac.rs DARKO ZIGAR 1 DESIMIR JOVANOVIĆ 2 MARTINA ZDRAVKOVIĆ 3 1-4 University of Niš, Faculty of Occupational Safety

More information

Water Mist-Based Fire Suppression Modelling of an Office Space Scenario

Water Mist-Based Fire Suppression Modelling of an Office Space Scenario Water Mist-Based Fire Suppression Modelling of an Office Space Scenario Hai Jiang, Vaidya Sankaran, Med Colket, May Corn United Technologies Research Center Kati Laakkonen Marioff Corporation 14th International

More information

NUMERICAL STUDIES ON BARE CABIN FIRES WITH OPERATION OF SMOKE EXTRACTION SYSTEM

NUMERICAL STUDIES ON BARE CABIN FIRES WITH OPERATION OF SMOKE EXTRACTION SYSTEM , Volume 11, Number 2, p.43-48, 2012 NUMERICAL STUDIES ON BARE CABIN FIRES WITH OPERATION OF SMOKE EXTRACTION SYSTEM Q. Kui Institute of Building Fire Research, China Academy of Building Research, Beijing,

More information

SOLIT PROJECT: WATER MIST FIRE SUPPRESSION SYSTEMS AS PART OF THE TUNNEL SAFETY SYSTEM

SOLIT PROJECT: WATER MIST FIRE SUPPRESSION SYSTEMS AS PART OF THE TUNNEL SAFETY SYSTEM - 157 - SOLIT PROJECT: WATER MIST FIRE SUPPRESSION SYSTEMS AS PART OF THE TUNNEL SAFETY SYSTEM Kratzmeir S. FOGTEC Fire Protection, Research & Development, Germany Keywords: Fire Protection, Fire suppression,

More information

Shalaby Institute of Fire Protection Heyrothsberge, Germany.

Shalaby Institute of Fire Protection Heyrothsberge, Germany. International Water Mist Conference November 3-4, 2010, Prague, Czech Republic The Influence of Droplet Size of Water Mist on Extinguishment Fire Plume Dr.Hemdan Shalaby Institute of Fire Protection Heyrothsberge,

More information

Modeling water-mist based suppression of 34 GJ car-deck fires using FDS

Modeling water-mist based suppression of 34 GJ car-deck fires using FDS Modeling water-mist based suppression of 34 GJ car-deck fires using FDS S. Li, R. Acharya, M. Colket, V. Sankaran, G. Poncia United Technologies Research Center L. Torpo Marioff Corporation March 1 st,

More information

and Sprinkler System in Resalat Tunnel of Tehran

and Sprinkler System in Resalat Tunnel of Tehran CFD Simulation of Water Mist and Sprinkler System in Resalat Tunnel of Tehran Motivation Resalat tunnel is the first road tunnel in Tehran one of most crowded tunnels of Tehran my every day route, home

More information

STUDY FOR SAFETY AT A RELATIVELY SHORT TUNNEL WHEN A TUNNEL FIRE OCCURRED

STUDY FOR SAFETY AT A RELATIVELY SHORT TUNNEL WHEN A TUNNEL FIRE OCCURRED - 133 - STUDY FOR SAFETY AT A RELATIVELY SHORT TUNNEL WHEN A TUNNEL FIRE OCCURRED Y. Mikame 1,2, N. Kawabata 1, M. Seike 1, M. Hasegawa 1 1 Kanazawa University, Japan 2 Metropolitan Expressway Company

More information

ASSESSMENT OF FIRE BEHAVIOUR OF TIMBER PARTITION MATERIALS WITH A ROOM CALORIMETER

ASSESSMENT OF FIRE BEHAVIOUR OF TIMBER PARTITION MATERIALS WITH A ROOM CALORIMETER , Volume 9, Number 1, p.38-58, 2007 ASSESSMENT OF FIRE BEHAVIOUR OF TIMBER PARTITION MATERIALS WITH A ROOM CALORIMETER C.W. Leung and W.K. Chow Department of Building Services Engineering, The Hong Kong

More information

FINDINGS FROM FIRE TESTS IN TUNNEL CONSTRUCTIONS WITH VENTILATION SYSTEMS AND FIXED FIRE SUPPRESSION SYSTEMS

FINDINGS FROM FIRE TESTS IN TUNNEL CONSTRUCTIONS WITH VENTILATION SYSTEMS AND FIXED FIRE SUPPRESSION SYSTEMS - 203 - FINDINGS FROM FIRE TESTS IN TUNNEL CONSTRUCTIONS WITH VENTILATION SYSTEMS AND FIXED FIRE SUPPRESSION SYSTEMS Hofer R., IBS Institute for Technical Fire Protection and Safety Research, Linz / Austria

More information

A Numerical study of the Fire-extinguishing Performance of Water Mist in an Opening Machinery Space

A Numerical study of the Fire-extinguishing Performance of Water Mist in an Opening Machinery Space Available online at www.sciencedirect.com Procedia Engineering 31 (2012) 734 738 International Conference on Advances in Computational Modeling and Simulation A Numerical study of the Fire-extinguishing

More information

Tunnel Fire Dynamics and Evacuation Simulations

Tunnel Fire Dynamics and Evacuation Simulations Tunnel Fire Dynamics and Evacuation Simulations James Priest, PhD & James Niehoff DGS-SEE Seminar on Fire Protection for Physics Research Facilities 7 & 8 October 2015 Introduction (Background) Presentation

More information

WATER MIST FIRE PROTECTION SYSTEMS FOR INDUSTRIAL CABLE TUNNELS AND TURBINE HALLS

WATER MIST FIRE PROTECTION SYSTEMS FOR INDUSTRIAL CABLE TUNNELS AND TURBINE HALLS WATER MIST FIRE PROTECTION SYSTEMS FOR INDUSTRIAL CABLE TUNNELS AND TURBINE HALLS Jukka Vaari 1, Amit Lior 2 1 2 VTT Technical Research Centre of Finland, Espoo, Finland Marioff Corporation Oy, Vantaa,

More information

Modeling a real backdraft incident fire

Modeling a real backdraft incident fire Advanced Computational Methods in Heat Transfer IX 279 Modeling a real backdraft incident fire A. Tinaburri 1 & M. Mazzaro 2 1 Central Direction for Prevention and Technical Safety, Firefighters, Public

More information

Computer Models For Fire and Smoke

Computer Models For Fire and Smoke Computer Models For Fire and Smoke Model Name: JASMINE Version: 3.1 Classification: Very Short Description: CFD or Field A CFD or field model for predicting consequences of fire to evaluate design issues

More information

NUMERICAL SIMULATION OF FIRE SPREAD IN TERMINAL 2 OF BELGRADE AIRPORT. PO Box 522, Belgrade, Serbia and Montenegro

NUMERICAL SIMULATION OF FIRE SPREAD IN TERMINAL 2 OF BELGRADE AIRPORT. PO Box 522, Belgrade, Serbia and Montenegro Ninth International IBPSA Conference Montréal, Canada August 15-18, 2005 NUMERICAL SIMULATION OF FIRE SPREAD IN TERMINAL 2 OF BELGRADE AIRPORT Z. Stevanovic 1, T. Valentina 1, N. Kadic 1, Z. Markovic 1,

More information

Case Study 1 Underground Car Park

Case Study 1 Underground Car Park Case Study 1 Underground Car Park Dorota Brzezińska 1, Janusz Paliszek 2, Piotr Smardz 2, Renata Ollesz 1, Karol Kaczor 2 1 Lodz University of Technology, GRID - Lodz, 2 INBEPO Wroclaw, Poland Building

More information

CFD-AIDED TENABILITY ASSESSMENT OF RAILWAY TUNNEL TRAIN FIRE SCENARIOS

CFD-AIDED TENABILITY ASSESSMENT OF RAILWAY TUNNEL TRAIN FIRE SCENARIOS CFD-AIDED TENABILITY ASSESSMENT OF RAILWAY TUNNEL TRAIN FIRE SCENARIOS Yunlong Liu*, Xijuan Liu and Bradley Paroz Fire Science and Technology Laboratory CSIRO Manufacturing and Infrastructure Technology

More information

Developing a Fire Test Strategy for Storage Protection Under Sloped Ceilings

Developing a Fire Test Strategy for Storage Protection Under Sloped Ceilings Developing a Fire Test Strategy for Storage Protection Under Sloped Ceilings Justin A. Geiman, Noah L. Ryder Fire & Risk Alliance, Rockville, MD, USA André W. Marshall Custom Spray Solutions, Silver Spring,

More information

SCHULTE & ASSOCIATES Building Code Consultants 880D Forest Avenue Evanston, IL /

SCHULTE & ASSOCIATES Building Code Consultants 880D Forest Avenue Evanston, IL / SCHULTE & ASSOCIATES Building Code Consultants 880D Forest Avenue Evanston, IL 60202 fpeschulte@aol.com 504/220-7475 A CRITIQUE OF HUGHES ASSOCIATES, INC. PAPER TITLED: Analysis of the Performance of Ganged

More information

The first tunnel fire. Benefits of fire

The first tunnel fire. Benefits of fire Benefits of fire suppression Quantifying the effects of suppression on energy release. This article by Fathi Tarada, managing director of fire safety, risk management, ventilation and CFD consultant Mosen

More information

CFD ASSESSMENT OF RAILWAY TUNNEL TRAIN FIRE SCENARIOS

CFD ASSESSMENT OF RAILWAY TUNNEL TRAIN FIRE SCENARIOS CFD ASSESSMENT OF RAILWAY TUNNEL TRAIN FIRE SCENARIOS Yunlong Liu*, Xijuan Liu and Bradley Paroz Fire Science and Technology Laboratory CSIRO Manufacturing and Infrastructure Technology PO Box 310 North

More information

6B-2 6th Asia-Oceania Symposium on Fire Science and Technology 17-20, March, 2004, Daegu, Korea

6B-2 6th Asia-Oceania Symposium on Fire Science and Technology 17-20, March, 2004, Daegu, Korea 6B-2 6th Asia-Oceania Symposium on Fire Science and Technology 17-20, March, 2004, Daegu, Korea CONDUCTING A FULL-SCALE EXPERIMENT ON A RAIL PASSENGER CAR ABSTRACT N. White and V.P. Dowling CSIRO Fire

More information

Considerations in the Design of Smoke Management Systems for Atriums

Considerations in the Design of Smoke Management Systems for Atriums Construction Technology Update No. 48 Considerations in the Design of Smoke Management Systems for Atriums by G.D. Lougheed This Update discusses the use of an engineered approach to the design of smoke

More information

Impact of Tunnel Ventilation on Tunnel Fixed Fire Suppression System

Impact of Tunnel Ventilation on Tunnel Fixed Fire Suppression System Impact of Tunnel Ventilation on Tunnel Fixed Fire Suppression System Igor Maevski, PhD, PE Jacobs Engineering, ASHRAE Member Raymond C. Klein, PE Jacobs Engineering, ASHRAE Member ABSTRACT Recently there

More information

How to Use Fire Risk Assessment Tools to Evaluate Performance Based Designs

How to Use Fire Risk Assessment Tools to Evaluate Performance Based Designs How to Use Fire Risk Assessment Tools to Evaluate Performance Based Designs 1 ABSTRACT Noureddine Benichou and Ahmed H. Kashef * Institute for Research in Construction National Research Council of Canada

More information

Gerd Koffmane, Henrik Hoff, AP Sensing GmbH, Böblingen

Gerd Koffmane, Henrik Hoff, AP Sensing GmbH, Böblingen Linear Heat Series Under Test: Extensive fire tests prove Distributed Temperature Sensing (DTS) enables fast and reliable control of fire protection systems in road and rail tunnels Gerd Koffmane, Henrik

More information

Numerical Stability Analysis of a Natural Circulation Steam Generator with a Non-uniform Heating Profile over the tube length

Numerical Stability Analysis of a Natural Circulation Steam Generator with a Non-uniform Heating Profile over the tube length Numerical Stability Analysis of a Natural Circulation Steam Generator with a Non-uniform Heating Profile over the tube length HEIMO WALTER Institute for Thermodynamics and Energy Conversion Vienna University

More information

EMERGENCY VENTILATION FOR SMOKE CONTROL IN ROADWAY TUNNELS (NCHRP PROJECT TASK 363)

EMERGENCY VENTILATION FOR SMOKE CONTROL IN ROADWAY TUNNELS (NCHRP PROJECT TASK 363) EMERGENCY VENTILATION FOR SMOKE CONTROL IN ROADWAY TUNNELS (NCHRP PROJECT 20-07 TASK 363) Louis Ruzzi PennDOT District 11 Igor Maevski, PhD, PE - Jacobs Agenda AASHTO T20 Technical Committee Roadway Tunnels

More information

Fire and smoke management in a uni-directional road tunnel for a congested traffic condition

Fire and smoke management in a uni-directional road tunnel for a congested traffic condition Fire and smoke management in a uni-directional road tunnel for a congested traffic condition Y Liu, J Munro Parsons Brinckerhoff Australia B Dandie Thiess Pty Ltd., Australia ABSTRACT Emergency smoke ventilation

More information

Underground fires in metro systems failures, accidents and terrorism

Underground fires in metro systems failures, accidents and terrorism Underground fires in metro systems failures, accidents and terrorism Dr Fathi Tarada Mosen Ltd RIFA Seminar 22-03-2018 Issues Higher threat of fire & explosions in congested underground metro stations?

More information

NUMERICAL SIMULATION OF THE NEW SOUTH WALES FIRE BRIGADE COMPARTMENT FIRE BEHAVIOUR TRAINING TEST CELL

NUMERICAL SIMULATION OF THE NEW SOUTH WALES FIRE BRIGADE COMPARTMENT FIRE BEHAVIOUR TRAINING TEST CELL , Volume 9, Number 4, p.154-162, 7 NUMERICAL SIMULATION OF THE NEW SOUTH WALES FIRE BRIGADE COMPARTMENT FIRE BEHAVIOUR TRAINING TEST CELL D. Mackay and T. Barber School of Mechanical and Manufacturing

More information

Engineering Simulation in Built Environment and Civil Engineering Projects

Engineering Simulation in Built Environment and Civil Engineering Projects Engineering Simulation in Built Environment and Civil Engineering Projects Fluid Dynamics Simulation Mark Owens ANSYS UK Ltd 2010 ANSYS, Inc. All rights reserved. 1 ANSYS, Inc. Proprietary Fires and Smoke

More information

Third Runway Project APM Depot Fire Engineering Design. Presented by Ir Wilson Sau-kit TSANG

Third Runway Project APM Depot Fire Engineering Design. Presented by Ir Wilson Sau-kit TSANG 1 Third Runway Project APM Depot Fire Engineering Design Presented by Ir Wilson Sau-kit TSANG 1 2 Presentation Overview 1. Project Background and Depot Overview 2. Building Information and Challenge for

More information

CFD Analysis of Fire Characteristics on Subway Junction Station

CFD Analysis of Fire Characteristics on Subway Junction Station ISGSR27 First International Symposium on Geotechnical Safety & Risk Oct. 18~19, 27 Shanghai Tongji University, China CFD Analysis of Fire Characteristics on Subway Junction Station G. H. Wu, X. Han, Q.Q.

More information

IMPROVING VENTILATION AND PASSIVE PROTECTION WITH FFFS

IMPROVING VENTILATION AND PASSIVE PROTECTION WITH FFFS - 195 - IMPROVING VENTILATION AND PASSIVE PROTECTION WITH FFFS Rajko Rothe; IFAB, Berlin, Germany Max Lakkonen and Dirk Sprakel, FOGTEC Fire Protection, Cologne, Germany ABSTRACT This paper discusses the

More information

Interaction of Water Extinguishing Systems and Smoke and Heat Exhaust Ventilation Systems (SHEVS)

Interaction of Water Extinguishing Systems and Smoke and Heat Exhaust Ventilation Systems (SHEVS) Fire Protection Leaflet Interaction of Water Extinguishing Systems and Smoke and Heat Exhaust Ventilation Systems (SHEVS) 0 General Regulations and recommendations missing from this leaflet do not entitle

More information

OPTIMIZATION OF VENTILATION MODE OF SMOKE CONTROL SYSTEM IN HIGH-RISE BUILDING FIRE

OPTIMIZATION OF VENTILATION MODE OF SMOKE CONTROL SYSTEM IN HIGH-RISE BUILDING FIRE OPTIMIZATION OF VENTILATION MODE OF SMOKE CONTROL SYSTEM IN HIGH-RISE BUILDING FIRE 1 RU ZHOU, 2 WEI ZHANG 1 School of Urban Construction and Safety Engineering, Nanjing University of Technology, Nanjing

More information

Case Study of Underground Car Park. Team Japan

Case Study of Underground Car Park. Team Japan 11th Conference on Performance Based Codes and Fire Safety Design Methods Case Study of Underground Car Park Team Japan We focused on the characteristics of the fire behavior of car fire. Car fire is not

More information

American Society of Heating, Refrigerating and Air-Conditioning Engineers

American Society of Heating, Refrigerating and Air-Conditioning Engineers Flow Pattern and Thermal Comfort in Office Environment with Active Chilled Beams Journal: American Society of Heating, Refrigerating and Air-Conditioning Engineers, Inc. Manuscript ID: Draft Publication:

More information

The Mont Blanc tunnel project. Eric CESMAT, Sylvain DESANGHERE

The Mont Blanc tunnel project. Eric CESMAT, Sylvain DESANGHERE The Mont Blanc tunnel project Eric CESMAT, Sylvain DESANGHERE 24/09/2009 International water mist conference 2009 Fires in tunnel Car fire > 4 to 8 MW Van fire > 15 MW HGV fire > 30 MW Big HGV fire > 100

More information

incorporating Contractors guide to car park ventilation A no-nonsense guide to the safe ventilation of underground and covered car parks

incorporating Contractors guide to car park ventilation A no-nonsense guide to the safe ventilation of underground and covered car parks incorporating Contractors guide to car park ventilation A no-nonsense guide to the safe ventilation of underground and covered car parks Car park ventilation What are the regulations? Ventilation of car

More information

Tunnel Fire Dynamics

Tunnel Fire Dynamics Tunnel Fire Dynamics Haukur Ingason Ying Zhen Li Anders Lönnermark Tunnel Fire Dynamics 1 3 Haukur Ingason Fire Research SP Technical Research Institute of Sweden Borås Sweden Anders Lönnermark Fire Research

More information

REVIEW OF TECHNICAL STANDARDS AND CALCULATION METHODS FOR DIMENSIONING OF SMOKE AND HEAT CONTROL SYSTEMS IN CASE OF FIRE IN UNDERGROUND CAR PARKS

REVIEW OF TECHNICAL STANDARDS AND CALCULATION METHODS FOR DIMENSIONING OF SMOKE AND HEAT CONTROL SYSTEMS IN CASE OF FIRE IN UNDERGROUND CAR PARKS REVIEW OF TECHNICAL STANDARDS AND CALCULATION METHODS FOR DIMENSIONING OF SMOKE AND HEAT CONTROL SYSTEMS IN CASE OF FIRE IN UNDERGROUND CAR PARKS Nikola TANASIĆ, Tomislav SIMONOVIĆ, Miloš IVOŠEVIĆ, Branislav

More information

TECHNICAL TRADE-OFFS USING FIXED FIRE FIGHTING SYSTEMS

TECHNICAL TRADE-OFFS USING FIXED FIRE FIGHTING SYSTEMS - 12 - TECHNICAL TRADE-OFFS USING FIXED FIRE FIGHTING SYSTEMS H. Ingason and Y.Z. Li, SP Technical Research Institute of Sweden ABSTRACT The increasing use of fixed fire-fighting system (FFFS) in tunnels

More information

Computational simulation of road tunnel fire protection by sprinklers

Computational simulation of road tunnel fire protection by sprinklers European Journal of Environmental and Safety Sciences 2014 2(2): 48-52 ISSN 1339-472X European Science and Research Institute (Original Research Paper) Computational simulation of road tunnel fire protection

More information

Smoldering Propagation Characteristics of Flexible Polyurethane Foam under Different Air Flow Rates

Smoldering Propagation Characteristics of Flexible Polyurethane Foam under Different Air Flow Rates Smoldering Propagation Characteristics of Flexible Polyurethane Foam under Different Air Flow Rates Zhou Y., Fei Y.*, Hu S. Q. Nanjing Tech University, College of Fire Safety Science and Engineering &

More information

ANALYSIS OF SMOKE MOVEMENT IN A BUILDING VIA ELEVATOR SHAFTS

ANALYSIS OF SMOKE MOVEMENT IN A BUILDING VIA ELEVATOR SHAFTS ANALYSIS OF SMOKE MOVEMENT IN A BUILDING VIA ELEVATOR SHAFTS Prepared for Smoke Safety Council 6775 SW 111 th Avenue, Suite 10 Beaverton, OR 97008 Prepared by Jesse J. Beitel Alison J. Wakelin Craig L.

More information

Fire Protection and Safety in Tunnels Conference Opening Remarks. Dr Fathi Tarada Secretary, PIARC Tunnel Operations Committee

Fire Protection and Safety in Tunnels Conference Opening Remarks. Dr Fathi Tarada Secretary, PIARC Tunnel Operations Committee Fire Protection and Safety in Tunnels Conference Opening Remarks Dr Fathi Tarada Secretary, PIARC Tunnel Operations Committee Agenda Background to the conference Key themes Recent tunnel fires Major infrastructure

More information

RETOS Y TENDENCIAS DESARROLLO DE INFRAESTRUCTURA EN AUSTRIA. Leonardo Rosas Sánchez Bogotá Agosto 9 de 2018

RETOS Y TENDENCIAS DESARROLLO DE INFRAESTRUCTURA EN AUSTRIA. Leonardo Rosas Sánchez Bogotá Agosto 9 de 2018 RETOS Y TENDENCIAS DESARROLLO DE INFRAESTRUCTURA EN AUSTRIA Leonardo Rosas Sánchez Bogotá Agosto 9 de 2018 Table of content 1. Safety standards for road and railway tunnels 2. Upgrading the Alrberg Tunnel

More information

Compression of Fins pipe and simple Heat pipe Using CFD

Compression of Fins pipe and simple Heat pipe Using CFD Compression of Fins pipe and simple Heat pipe Using CFD 1. Prof.Bhoodev Mudgal 2. Prof. Gaurav Bhadoriya (e-mail-devmudgal.mudgal@gmail.com) ABSTRACT The aim of this paper is to identify the advantages

More information

SCALE MODEL STUDIES ON SMOKE MOVEMENT IN INCLINED TUNNEL WITH LONGITUDINAL VENTILATION AND SMOKE BARRIERS

SCALE MODEL STUDIES ON SMOKE MOVEMENT IN INCLINED TUNNEL WITH LONGITUDINAL VENTILATION AND SMOKE BARRIERS , Volume 11, Number 2, p.21-26, 212 SCALE MODEL STUDIES ON SMOKE MOVEMENT IN INCLINED TUNNEL WITH LONGITUDINAL VENTILATION AND SMOKE BARRIERS C.Y. Tso and W.K. Chow Research Centre for Fire Engineering,

More information

Test One: The Uncontrolled Compartment Fire

Test One: The Uncontrolled Compartment Fire The University of Edinburgh BRE Centre for Fire Safety Engineering One Day Symposium on The Dalmarnock Fire Tests: Experiments & Modelling Test One: The Uncontrolled Compartment Fire Cecilia Abecassis

More information

Fire Investigation in Italian Waste Treatment Plant: lessons learned and future development

Fire Investigation in Italian Waste Treatment Plant: lessons learned and future development Fire and Evacuation Modeling Technical Conference (FEMTC) 2018 Gaithersburg, Maryland, October 1-3, 2018 Fire Investigation in Italian Waste Treatment Plant: lessons learned and future development Ing.

More information

Tunnel Axial Flow Fan

Tunnel Axial Flow Fan Tunnel Axial Flow Fan TUNNEL AXIAL FLOW FAN Tunnel fans are an axial flow fans and moves an airstream along the axis of the fan. The air is pressurized by the aerodynamic lift generated by the fan blades,

More information

Advantages and Disadvantages of Fire Modelling

Advantages and Disadvantages of Fire Modelling Advantages and Disadvantages of Fire Modelling Dr Guillermo Rein School of Engineering University of Edinburgh & Imperial College London Dr Guillermo Rein 9 May 2012 Chief Fire Officers Association Annual

More information

POSITION PAPER ON WATER MIST FOR FIRE FIGHTING APPLICATIONS

POSITION PAPER ON WATER MIST FOR FIRE FIGHTING APPLICATIONS FIRE EXTINGUISHING INSTALLATIONS SECTION POSITION PAPER ON WATER MIST FOR FIRE FIGHTING APPLICATIONS Version 1 29-09-04 0 Eurofeu position paper on water mist for fire fighting applications 1 Scope The

More information

CFD Model of a Specific Fire Scenario

CFD Model of a Specific Fire Scenario 16 th Australasian Fluid Mechanics Conference Crown Plaza, Gold Coast, Australia 2-7 December 27 CFD Model of a Specific Fire Scenario D. Mackay, T. Barber and E. Leonardi School of Mechanical and Manufacturing

More information

5B-3 6th Asia-Oceania Symposium on Fire Science and Technology 17-20, March, 2004, Daegu, Korea

5B-3 6th Asia-Oceania Symposium on Fire Science and Technology 17-20, March, 2004, Daegu, Korea 5B-3 6th Asia-Oceania Symposium on Fire Science and Technology 17-20, March, 2004, Daegu, Korea PRACTICAL APPLICATIONS OF FIRE MODELING IN INDUSTRIAL APPLICATIONS By James M. Dewey, Advisor Risk Management

More information

Fire Engineering in High Rise 15 November 2013

Fire Engineering in High Rise 15 November 2013 Fire Engineering in High Rise 15 November 2013 Neal Butterworth Arup UK www.arup.com Neal.Butterworth@arup.com Contents How do we protect against fire? How do we know this works? Why evacuate? What assumptions

More information

Factors Affecting Efficiency of Water Mist Suppression of Solid Combustible Fires in Open Environment

Factors Affecting Efficiency of Water Mist Suppression of Solid Combustible Fires in Open Environment Factors Affecting Efficiency of Water Mist Suppression of Solid Combustible Fires in Open Environment Hong-Zeng (Bert) Yu FM Global 16 th International Water Mist Conference September 21-22, 2016 Vienna,

More information

Explosion Protection of an Armoured Vehicle Crew Compartment with Water Mist. Andrew Kim and George Crampton

Explosion Protection of an Armoured Vehicle Crew Compartment with Water Mist. Andrew Kim and George Crampton Explosion Protection of an Armoured Vehicle Crew Compartment with Water Mist Andrew Kim and George Crampton Fire Research Program, National Research Council of Canada 1200 Montreal Road, Ottawa, Ontario,

More information

Virtual Compartment: An Alternative Approach to Means of Egress Design in Airport Pedestrian Tunnel

Virtual Compartment: An Alternative Approach to Means of Egress Design in Airport Pedestrian Tunnel Virtual : An Alternative Approach to Means of Egress Design in Airport Pedestrian Tunnel Xiaolei Chen, PhD California State University, Los Angeles, United States Ning (Frank) Wang, P.E. Jensen Hughes,

More information

Experimental Room Fire Studies with Perforated Suspended Ceiling

Experimental Room Fire Studies with Perforated Suspended Ceiling Experimental Room Fire Studies with Perforated Suspended Ceiling FIONA S.C. TSUI 1, W.K. CHOW 1, N.K. FONG 1, Y. GAO 2, H. DONG 2, and G.W. ZOU 2 1 Research Centre for Fire Engineering Department of Building

More information

Quantitative risk assessment for a fire suppression system in the New Tyne Crossing. Dr Fathi Tarada

Quantitative risk assessment for a fire suppression system in the New Tyne Crossing. Dr Fathi Tarada Quantitative risk assessment for a fire suppression system in the New Tyne Crossing Dr Fathi Tarada Contents The brief Feasibility study Risk assessment Cost-benefit analysis Primary assumptions Risk parameters

More information

FIXED FIRE FIGHTING SYSTEMS IN TUNNELS INTEGRATION AND COMPENSATION

FIXED FIRE FIGHTING SYSTEMS IN TUNNELS INTEGRATION AND COMPENSATION FIXED FIRE FIGHTING SYSTEMS IN TUNNELS INTEGRATION AND COMPENSATION Stefan Kratzmeir*, IFAB Institute for applied fire safety research, Rostock, Germany Max Lakkonen, FOGTEC Fire Protection, Cologne, Germany

More information

THE COMPARISON OF THE RESULTS OF A FULL SCALE EVACUATION TEST TO THE CALCULATION METHOD OF HUNGARIAN REGULATIONS AND TO THE PATHFINDER SOFTWARE

THE COMPARISON OF THE RESULTS OF A FULL SCALE EVACUATION TEST TO THE CALCULATION METHOD OF HUNGARIAN REGULATIONS AND TO THE PATHFINDER SOFTWARE Application of Structural Fire Engineering, 19-20 April 2013, Prague, Czech Republic THE COMPARISON OF THE RESULTS OF A FULL SCALE EVACUATION TEST TO THE CALCULATION METHOD OF HUNGARIAN REGULATIONS AND

More information

Hot Issues in Fire Engineering July 2014

Hot Issues in Fire Engineering July 2014 Hot Issues in Fire Engineering July 2014 Crowded Railway Stations and Train Compartments to Watch Y.W. Ng and W.K. Chow, JP FHKEng Research Centre for Fire Engineering, Department of Building Services

More information

Gothenburg dance hall, Sweden, 1998

Gothenburg dance hall, Sweden, 1998 Gothenburg dance hall, Sweden, 1998 The fire occurred on 28 October 1998 in a crowded dance hall in Gothenburg. 63 people died, 120 were injured and about 60 were rescued by the fire brigade. The hall

More information

Design of Fire safety in Multi Occupancy Residential Accommodation

Design of Fire safety in Multi Occupancy Residential Accommodation Design of Fire safety in Multi Occupancy Residential Accommodation Myth vs Reality Myth. Fire is bright Reality. It isn t. Flames are bright Outside fires have bright flames because of the availability

More information

A study for a fire spread mechanism of residential buildings with numerical modeling

A study for a fire spread mechanism of residential buildings with numerical modeling Safety and Security Engineering IV 185 A study for a fire spread mechanism of residential buildings with numerical modeling C.-S. Ahn & J.-Y. Kim Fire Safety Research Division, Korea Institute of Construction

More information

IFireSS International Fire Safety Symposium Coimbra, Portugal, 20 th -22 nd April 2015

IFireSS International Fire Safety Symposium Coimbra, Portugal, 20 th -22 nd April 2015 IFireSS International Fire Safety Symposium Coimbra, Portugal, 20 th -22 nd April 2015 SCALE MODEL EXPERIMENTS ON SMOKE MOVEMENT IN A TILTED TUNNEL photo Author 1 30 mm 40 mm photo Author 2 30 mm 40 mm

More information

Impact of heat load distribution and strength on airflow pattern in rooms with exposed chilled beams

Impact of heat load distribution and strength on airflow pattern in rooms with exposed chilled beams Impact of heat load distribution and strength on airflow pattern in rooms with exposed chilled beams Risto Kosonen 1, Arsen Melikov 2, Boryana Yordanova 2 and Lyuben Bozkhov 2 1 Halton Oy 2 International

More information

Investigating the Effects of Sprinkler Sprays on Fire-Induced Doorway Flows: A Two-Part Study. Jeremiah Crocker and Dr. Bin Xiao New Technology Team

Investigating the Effects of Sprinkler Sprays on Fire-Induced Doorway Flows: A Two-Part Study. Jeremiah Crocker and Dr. Bin Xiao New Technology Team Jeremiah Crocker and Dr. Bin Xiao New Technology Team Copyright 2010 Tyco Fire Suppression & Building Products. All rights reserved. The products and specifications published herein are for general evaluation

More information

Survey of the Burning Behaviour of the Refrigerant HFO-1234yf Brief Report

Survey of the Burning Behaviour of the Refrigerant HFO-1234yf Brief Report D M T G m b H & C o. K G B u i l d i n g S a f e t y Expert Body for Fire Protection Tremoniastraße 13 44137 Dortmund GERMANY Phone +49 231-5333-0 Fax +49 231-5333-299 Emaill: gs@dmt.de http://www.dmt.de

More information

CFD Analysis of a 24 Hour Operating Solar Refrigeration Absorption Technology

CFD Analysis of a 24 Hour Operating Solar Refrigeration Absorption Technology IJIRST International Journal for Innovative Research in Science & Technology Volume 1 Issue 11 April 2015 ISSN (online): 2349-6010 CFD Analysis of a 24 Hour Operating Solar Refrigeration Absorption Technology

More information

Fire protection of emergency electrical devices: effect on the level of risk a case study of a rail tunnel

Fire protection of emergency electrical devices: effect on the level of risk a case study of a rail tunnel Safety and Security Engineering VI 73 Fire protection of emergency electrical devices: effect on the level of risk a case study of a rail tunnel M. Lombardi & G. Rossi Dipartimento di Ingegneria Chimica

More information

Innovative Solutions for Active Fire Protection in Road/Rail Tunnels and Underground Facilities

Innovative Solutions for Active Fire Protection in Road/Rail Tunnels and Underground Facilities Innovative Solutions for Active Fire Protection in Road/Rail Tunnels and Underground Facilities Roger A. Dirksmeier, FOGTEC Fire Protection, Germany Fire Protection Conference Tel Aviv, 4 th of April 2016

More information

This document is a preview generated by EVS

This document is a preview generated by EVS TECHNICAL REPORT ISO/TR 15657 First edition 2013-06-15 Fire resistance tests Guidelines for computational structural fire design Essais de résistance au feu Lignes directrices sur la conception statistique

More information

Anatomy of a Fire. Christopher Crivello, MSFPE, PE. Douglas Nadeau, MSFPE, PE, CFPS, LEED AP

Anatomy of a Fire. Christopher Crivello, MSFPE, PE. Douglas Nadeau, MSFPE, PE, CFPS, LEED AP Anatomy of a Fire Douglas Nadeau, MSFPE, PE, CFPS, LEED AP President of RAN Fire Protection Engineering, PC Vice President of truvue Inspection Technology Christopher Crivello, MSFPE, PE Fire Protection

More information

Computer Simulation Investigation on the Effect of Channelled and Unchannelled Screens on Smoke Contamination in Atriums Upper Balconies

Computer Simulation Investigation on the Effect of Channelled and Unchannelled Screens on Smoke Contamination in Atriums Upper Balconies MATEC Web of Conferences 13, 27 (214) DOI: 1.151/ matecconf/ 21413 27 C Owned by the authors, published by EDP Sciences, 214 Computer Simulation Investigation on the Effect of Channelled and Unchannelled

More information

An Analysis of Compartment Fire and Induced Smoke Movement in Adjacent Corridor

An Analysis of Compartment Fire and Induced Smoke Movement in Adjacent Corridor 2C-1 6th Asia-Oceania Symposium on Fire Science and Technology 17-20, March, 2004, Daegu, Korea An Analysis of Compartment Fire and Induced Smoke Movement in Adjacent Corridor Soo-Young Kim *, Eung-Sik

More information

Technical Information

Technical Information How to design easily a smoke management system? Mechanical smoke extraction for enclosed car park Car park: specificity of the smoke extraction system Car parks are nowadays integrated directly inside

More information

Application of the New Italian Fire Safety Code (D.M. 3 agosto 2015) to Case Study 3 Mall. Enrico Danzi Luca Fiorentini Luca Marmo Vincenzo Puccia

Application of the New Italian Fire Safety Code (D.M. 3 agosto 2015) to Case Study 3 Mall. Enrico Danzi Luca Fiorentini Luca Marmo Vincenzo Puccia Application of the New Italian Fire Safety Code (D.M. 3 agosto 2015) to Case Study 3 Mall Enrico Danzi Luca Fiorentini Luca Marmo Vincenzo Puccia A Challenging Application for the New Italian Fire Code

More information

Road tunnel safety rules in Italy: the tunnel country

Road tunnel safety rules in Italy: the tunnel country Safety and Security Engineering II 317 Road tunnel safety rules in Italy: the tunnel country M. Guarascio, M. Lombardi, G. Rossi & G. Sciarra Safety Engineering Sapienza, Rome University, Italy Abstract

More information

LOW-NOX BURNER RETROFIT CHALLENGE

LOW-NOX BURNER RETROFIT CHALLENGE LOW-NOX BURNER RETROFIT CHALLENGE By Craig Lieb Applications Engineer Zeeco, Inc. Rutland, UK Ryan Roberts Project Engineering Manager Zeeco, Inc. Broken Arrow, OK, U.S.A. Ryan Roberts has more than 20

More information

An Overview of Extinguishing Systems for Computer Equipment

An Overview of Extinguishing Systems for Computer Equipment Risk Solutions An Overview of Extinguishing Systems for Computer Equipment Various types of automatic suppression systems are available for protecting computer equipment. This report discusses the uses

More information

Research Needs for the Fire Safety Engineering Profession

Research Needs for the Fire Safety Engineering Profession Research Needs for the Fire Safety Engineering Profession Note: Items highlighted in RED are identified as the highest priority for each thread. Items highlighted in BOLD are identified as the highest

More information

Healthy Buildings 2017 Europe July 2-5, 2017, Lublin, Poland

Healthy Buildings 2017 Europe July 2-5, 2017, Lublin, Poland Healthy Buildings 2017 Europe July 2-5, 2017, Lublin, Poland Paper ID 0188 ISBN: 978-83-7947-232-1 Dispersion of pollutants released at floor level under three types of heating systems: A CFD study. Laura

More information

Full-Scale Measurement and Numerical Analysis of Liquefied Petroleum Gas Water Heaters with Ventilation Factors in Balcony

Full-Scale Measurement and Numerical Analysis of Liquefied Petroleum Gas Water Heaters with Ventilation Factors in Balcony Journal of Civil Engineering and Architecture 9 (215) 1341-1353 doi: 1.17265/1934-7359/215.11.9 D DAVID PUBLISHING Full-Scale Measurement and Numerical Analysis of Liquefied Petroleum Gas Water Heaters

More information

How design fires can be used in fire hazard analysis

How design fires can be used in fire hazard analysis How design fires can be used in fire hazard analysis Yung, D.T.; Bénichou, N. NRCC-44511 A version of this document is published in / Une version de ce document se trouve dans : Fire Technology, v. 38,

More information

2. Gas B. The column of hot gases, flames, and smoke rising above a fire; also called convection column, thermal updraft, or thermal column

2. Gas B. The column of hot gases, flames, and smoke rising above a fire; also called convection column, thermal updraft, or thermal column Fire Behavior Workbook Activities The following activities have been designed to help you. Your instructor may require you to complete some or all of these activities as a regular part of your fire fighter

More information

PHASED CONSTRUCTION AND SAFETY IN MALA KAPELA TUNNEL

PHASED CONSTRUCTION AND SAFETY IN MALA KAPELA TUNNEL - 119 - ABSTRACT: PHASED CONSTRUCTION AND SAFETY IN MALA KAPELA TUNNEL Darko Šaric Civil Engineering Institute of Croatia Croatia, 10.000 Zagreb, J. Rakuše 1 e-mail: dsaric@zg.igh.hr Goran Legac Croatian

More information

Computational Study of Effects of Drop Size Distribution in Fire Suppression Systems

Computational Study of Effects of Drop Size Distribution in Fire Suppression Systems ILASS-Americas 22nd Annual Conference on Liquid Atomization and Spray Systems, Cincinnati, OH, May 2010 Computational Study of Effects of Drop Size Distribution in Fire Suppression Systems G. Tanner *,

More information

CFD Analysis of temperature dissipation from a hollow metallic pipe through circular fins using Ansys 14.5

CFD Analysis of temperature dissipation from a hollow metallic pipe through circular fins using Ansys 14.5 IJAET International Journal of Application of Engineering and Technology ISSN: 2395-3594 Vol-1 No.-2 CFD Analysis of temperature dissipation from a hollow metallic pipe through circular fins using Ansys

More information

Fire and Smoke Management in a Uni-Directional Road Tunnel for a Congested Traffic Condition

Fire and Smoke Management in a Uni-Directional Road Tunnel for a Congested Traffic Condition International Journal of Ventilation ISSN 1473-3315 Volume 8 No 4 Fire and Smoke Management in a Uni-Directional Road Tunnel for a Congested Traffic Condition Y. Liu 1, J. Munro 1 and B. Dandie 2 1 Parsons

More information