1 Electrical Safety Myths and Facts 2 Copyright Material IEEE Paper No. ESW James R. White Senior Member IEEE Shermco Industries, Inc.2425 E. Pioneer Drive Irving, Texas jrwhite@shermco.com Abstract This paper reviews some of the more common electrical safety myths and misconceptions field electrical workers often have. Many of these misconceptions continue in spite of training and education. Some are handed down from worker to worker, similar to tribal knowledge. The real danger from these misconceptions is that they impede the truth and cause electrical workers to misjudge hazards and risks. Index Terms Myths, misconceptions, electrical safety, electrical shock, NFPA 70B, NFPA 70E, OSHA. I. INTRODUCTION This is the second paper concerning the electrical myths and misconceptions that electrical workers may have. Because of the hazardous nature of the job, these misconceptions can cause injury or even death to the worker who believes them, and possibly to those around him or her. This paper reviews some of the more common myths and misconceptions electrical workers may have concerning electricity and electrical safety. Readers are encouraged to use all or parts of the presentation as considered necessary to enlighten field workers and possibly prevent accidents that may be caused by them. II. HAZARD IS RISK AND RISK IS HAZARD When talking to people about hazards and risks, they seem to get the two confused. I often hear someone say, The hazard increased because the door was open or That s a way higher hazard because I am in a tight spot. What they are really talking about is the risk associated with a given task. The best explanation is to say the hazard is what the hazard is. In other words, the hazard does not change because of the task or other factors that may arise. If a piece of switchgear or MCC is energized, the hazard is the available short circuit current, the nominal voltage and the total clearing time of the OCPD (overcurrent protective device). Whatever task is being performed, that hazard does not change. The only way to eliminate the hazard is to shut the equipment off, which is the preferred approach. The task being performed will change the amount of risk involved with a task. The risk from reading a panelboard meter is far different than when racking a circuit breaker in or out of its cubicle. The risk can change due to environmental issues, aging equipment, lack of maintenance, etc., but the actual hazard is the same for a given piece of equipment. When using NFPA 70E (1) Table 130.7(C)(15)(a) there will be several Hazard/Risk Categories for a specified type of equipment. The hazard is provided in the heading for that equipment type. For example, for the equipment type Panelboards or other equipment rated >240 V and up to 600 V the hazard is given as a maximum of 25kA short circuit current available; maximum of 0.03 sec (2 cycle) fault clearing time at the voltages stated. The hazard is what the hazard is and does not change. The changes in HRC number (from HRC-0 to HRC-2) are task dependent and reflect what the 70E Technical Committee perceives as the risk that may be involved in that specific task. III. FR AND AR MEAN THE SAME THING Not really. In previous editions of NFPA 70E the term flame-resistant (FR) was used. In the 2004 edition the term arc rating was introduced. The 2000 through 2009 editions of NFPA 70E used FR exclusively to describe arc-rated clothing and PPE. In the 2012 edition of NFPA 70E wording was added to qualify what arc-rating was and to discontinue the use of flame resistant (FR). The preferred term is now arcrated (AR). In abbreviated terms, all arc-rated (AR) equipment is also flame resistant (FR), but not all FR is arc-rated. The best examples of this are the FR clothing used by fire fighters or steel and aluminum smelter workers. It is constructed of many of the same materials, but has not been specifically tested and certified for use to protect a worker from the electrical arc flash hazard. NFPA 70E Article 100, Definitions Informational Note No. 1 for arc rating states Informational Note No. 1: Arc-rated clothing or equipment indicates that it has been tested for exposure to an electric arc. Flame-Resistant (FR) clothing without an arc rating has not been tested for exposure to an electric arc. IV. VEHICLE TIRES ARE INSULATORS This one sort of makes sense. Tires are rubber and rubber is an insulator, right? Tires haven t been made solely of rubber since the 1950 s. Modern tires are made of synthetic rubber, carbon black (to provide color), with additives such as 1

2 silica, sulfur and zinc oxide, as well as anti-oxidants and antiozonants to prevent materials from breaking apart due to constant exposure to sunlight, heat, and ozone. Tires will be reinforced with layers (plies) of rayon, nylon or polyester and steel belts to provide strength and reduce the likelihood of puncture. The bead around the edge of the tire is reinforced with steel cable to provide a good seal against the rim. Some small amount of natural rubber is used by some manufacturers, but the rubber tire is a thing of the past. The steel belts and bead, along with the additives make tires fairly conductive to electricity. Numerous accounts have been publicized of trucks lifting their dump beds into overhead power lines, resulting in their tires blowing out or the driver exiting the vehicle, only to be electrocuted by the flow of current through the tires to ground, setting up voltage ground gradients. V. CURRENT-LIMITING FUSES ALWAYS LIMIT CURRENT Current-limiting fuses can be a great aid in reducing the arc flash hazard. They reduce the short circuit current with a characteristic known as let-through current and reduce the clearing time to less than ½ cycle. Figure 1 is the typical operating characteristic of a current-limiting fuse. Note the tremendous decrease in let-through current and the operating time. Even though the typical operating time is less than ½ cycle, most fuse manufacturers claim it will be less than ¼ cycle. One or the other would be a boon to electrical safety, but having both is akin to arc flash nirvana, right? engineers who are experienced in the finer points of electrical system characteristics. Without a full understanding of the quirks of electrical power systems, a facility safety director may believe his workers are protected, but instead they could be placed in grave danger by relying on faulty arc flash hazard warning labels. VI. ELECTRICITY TAKES THE PATH OF LEAST RESISTANCE I ve heard this one as long as I ve been in the trade. It s not that it s untrue; electricity does take the path of least resistance. It also takes any other path to ground that s available. The problem with truisms is that they have an element of truth, but may be misleading because you don t get all the information. As Figure 2 shows, if there are multiple paths to ground, some current will flow through them all. The path with the least resistance will have the most current flow; the path with the highest resistance will have the least current flow. If a piece of equipment has a loose ground lug or the equipment grounding conductor is partially broken or corroded, the intended ground may not present the lowest resistance. In this situation a person that touches the exterior of that piece of equipment may actually have a lower resistance than the intended grounding path and could be shocked or electrocuted. This is referred to as touch potential. 2A 5.33A 0.666A Figure 2 Multiple Paths to Earth Ground Figure 1 Typical Current-Limiting Fuse Characteristic Courtesy Cooper-Bussmann When properly applied, yes. The trick to current-limiting devices, whether they are fuses or circuit breakers, is that the short circuit current must be high enough to push the fuse (or circuit breaker) into its current-limiting region. If not, the fuse will respond as a dual-element fuse. One such situation that could cause the short circuit current to be less than anticipated would be a motor (or other device) fed from a long cable run. The impedance of the cable could reduce the short circuit current and the fuse would not respond with its current-limiting characteristic. This example is one of the reasons why arc flash studies must be conducted by Note in Figure 2 that R2, which has the lowest resistance also has the highest amount of current flow. A good, clean and tight ground or bonding connection is important to provide a safe work environment. VII. CIRCUIT BREAKER CONTACTS ARE DAMAGED DURING PRIMARY INJECTION TESTING On the surface, the logic is hard to deny. I m pumping sometimes tens of thousands of amps through a circuit breaker, causing it to trip. The situation is even worse when testing the Instantaneous function. The reality is that primary injection testing is the only method to fully test not only the programmer (OCPD), but also the power supply, interconnecting wiring and sensors. Secondary injection testing, although good for testing the programmer calibration, misses these critical items. Primary injection testing involves connecting a circuit breaker to a large high-current test set. These test sets are 2

3 portable in the sense that they have wheels. The largeroutput test sets weigh several hundred pounds. Figure 3 shows a typical primary injection test on a low-voltage power circuit breaker. the safety devices in automobiles. I had one student tell me I ve got lap belts, shoulder harnesses, crumple zones, air bags and side barriers in my doors. I can go as fast as I want to. I hope he was kidding. Since tens of thousands of people still die on the highways today, even after all the safety improvements in automobiles it is safe to say that statement is not true. The same false sense of security can raise its ugly head when discussing the arc-rated PPE and clothing available today. Once a worker puts it all on, he feels protected, safe. It s almost like wearing a suit of armor. Let the games begin! This attitude displays a lack of understanding about the issues involved with arc flash. Figure 3 High Current Primary Injection Test of a LVPCB By connecting to the test set through the circuit breaker s primary disconnects, large amounts of current can be driven through the circuit breaker, testing all elements of the OCPD. Because the voltage output from the test set is so low, the contacts are not materially damaged. Unlike interrupting a fault at 480 V, interrupting one at 7 to 12 V places much less stress on the device. Usually, polishing the contacts with a nonconductive abrasive pad is adequate to remove any marking that could take place. As far as hazards connected to using a primary injection test set, there can be considerable heating of the stabs and other current-carrying components, so sometimes wearing leather gloves is helpful. The voltage is so low that the shock hazard is almost non-existent and there is no arc flash hazard, again due to the very low voltage source. One last point is that when testing the Instantaneous function, the circuit breaker is only tested to the pickup of the Instantaneous function; not the interrupting rating. Instantaneous set points, even though they can be high, are still much lower than the interrupting rating, so the circuit breaker is not really being stressed. There is nothing wrong in doing a secondary injection test annually on the OCPD. Every three to five years, though, the full OCPD system needs to be tested and verified to ensure proper and safe operation. VIII. I M PROTECTED My Dad would often say There s no such thing as foolproof. As soon as you make it, along comes a better fool. Such is life. If there is a down-side to arc-rated PPE it s that people have a false sense of security. It can be compared to The first issue is that as good as IEEE 1584 (2) is, it is flawed. This was first pointed out by Dr. David Sweeting and Professor Stokes soon after it was first released. Further study has shown Dr. Sweeting s assertions to be correct. Users must understand that 1584 is at best an estimate, not a final conclusion. Secondly, incident energy is proportional to time. If the circuit breaker or other OCPD doesn t function in accordance with its manufacturer s specifications, the incident energy released during a fault could greatly exceed the estimated values. Lastly, working distance is critical, as incident energy will vary greatly depending on the distance to the arc source. Incident energy decreases by the inverse square of the distance, which is a good thing. As we move away from the arc source the incident energy drops rapidly. However, the opposite is also true. As we decrease the distance, the incident energy increases by the square of the distance. Just a few inches can make a considerable difference in the incident energy a worker would receive during an arc flash event. Body position is important to a worker s safety. This is illustrated by Informational Note No. 3 for the definition of arc rating (2012 NFPA 70E Article 100, Definitions ). Informational Note No. 3: ATPV is defined in ASTM F as the incident energy on a material or a multilayer system of materials that results in a 50 percent probability that sufficient heat transfer through the tested specimen is predicted to cause the onset of a second degree skin burn injury based on the Stoll curve, cal/cm 2. Even if all the circumstances are correct and the incident energy values are accurate, there is a 50% probability of a second-degree burn through the arc-rated clothing and PPE where bare skin is next to it. A difference of just 2 or 3 cal/cm 2 incident energy can increase that probability greatly. The up-side to this is that any injury that may be received will certainly be less than if no arc-rated clothing or PPE was worn, but certainly the ASTM F1509 definition provides clear indication that arc-rated does not mean injury-free. IX. THERE S NO ARC FLASH HAZARD IF THE DOOR IS 3

4 SHUT It s amazing how many workers actually believe this, even though NFPA 70E has clearly stated since 2009 that doors provide little or no protection from an arc flash. The following is from the 2012 edition of NFPA 70E: Informational Note No. 2: The collective experience of the task group is that, in most cases, closed doors do not provide enough protection to eliminate the need for PPE for instances where the state of the equipment is known to readily change (for example, doors open or closed, rack in or rack out). Table 130.7(C)(15)(a) [formerly 130.7(C)(9)] shows that when performing the task of inserting or removing (racking) circuit breakers from their cubicles, no reduction in HRC class is allowed for doors closed. Doors often have vents and other openings which allow the arc plasma and heat to pass through it. The latches on the typical 480 V equipment will pop open during an arcing event and the hinges could possibly separate. My experience has been that the hinge side holds better than the latch side, so I always stand to the hinge side. NFPA provides minimum safe work practice requirements, not necessarily best safe work practice requirements. When operating larger circuit breakers or other devices I prefer to wear arc-rated clothing with a rating of 8 to 12 cal/cm 2. In situations where I m unsure of its state of maintenance or condition, I will suit up in 65 cal/cm 2 arc-rated clothing and PPE. This is, of course only if the equipment cannot be deenergized. X. YOU CAN T OPERATE 480 V EQUIPMENT UNLESS WEARING ARC-RATED CLOTHING AND PPE Actually, NFPA 70E says the exact opposite. Under the definition for Arc Flash Hazard in NFPA 70E, Informational Note No. 1 states An arc flash hazard may exist when energized electrical conductors or circuit parts are exposed or when they are within equipment in a guarded or enclosed condition, provided a person is interacting with the equipment in such a manner that could cause an electric arc. This would lead one to believe that opening and closing a switch or circuit breaker would create an arc flash hazard. That is, until the rest of IN No. 1 is read, Under normal operating conditions, enclosed energized equipment that has been properly installed and maintained is not likely to pose an arc flash hazard. Interacting, in this context, is any task where the switch or device is installed or removed from an energized bus without the aid of arc extinguishers, such as bus bar, bus duct or a MCC bucket. Section 130.7(A) Informational Note No. 2 states It is the collective experience of the Technical Committee on Electrical Safety in the Workplace that normal operation of enclosed electrical equipment, operating at 600 volts or less, that has been properly installed and maintained by qualified persons is not likely to expose the employee to an electrical hazard. The operative words in this section are properly installed and maintained. The NFPA 70E Technical Committee grappled with this and agreed that this would not be an easy thing to do. Maintenance records and test results could be reviewed prior to the start of work, if they are available. If the equipment was maintained, those records should be available. The other method used by some service companies, such as NETA-member companies is to place calibration and test labels on their equipment. NFPA 70B (4) Recommended Practice for Electrical Equipment Maintenance 2013 edition added section Test or Calibration Decal System it states, General. After equipment testing, device testing, or calibration, a decal on equipment, in conjunction with test records, can communicate the condition of electrical equipment to maintenance and service personnel. This can be important for assessing the hazard identification and risk assessment for electrical safety procedures as well as the condition of electrical equipment. Such labels are shown in Figure 4. These labels are supposed to be color coded as red, yellow or white. Figure 4 Test or Calibration Decal System From NFPA 70B The red label indicates the equipment has a major defect and should not be placed into service. The yellow label indicates a minor issue that does not affect operation or safety and the white label indicates equipment that is fully serviceable. Since NFPA 70B is printed in black-and-white, the colors are described in the text, but not shown. Since NFPA 70E provides minimum requirements, it is also necessary to state that a worker should always follow his/her instincts and wear whatever PPE and clothing they believe is warranted. NFPA 70E does not prevent a worker from wearing such arc-rated clothing and PPE, but leaves it up to the worker to determine the need based on the equipment as it is found in service. XI. CIRCUIT BREAKERS WILL ALWAYS FUNCTION PROPERLY People tend to be optimistic about things, which is good. However, being over-optimistic is not so good. Why is it that a worker will walk up to a circuit breaker and operate it without ever giving a thought as to whether or not it will actually function correctly? Every day this scenario is repeated throughout the US over and over again. Most times nothing happens. Sometimes, especially if the circuit breaker has not received any maintenance in several years, bad things do happen. NFPA 70B recommends maintenance and testing of circuit breakers every three years, according to Table L.1 from Annex L, Maintenance Intervals. Figure 5 is from NFPA 70B, Annex L. The international Electrical Testing Association (NETA) has an ANSI standard for electrical equipment maintenance, ANSI/NETA MTS-2011 (5). Annex B of ANSI/NETA MTS-2011 offers a frequency of maintenance matrix that is based on 4

5 condition of the equipment and the reliability required. This method provides some flexibility based on these two factors and may be more appropriate for some facilities. Why is this level of maintenance required for circuit breakers? They are primarily mechanical devices. They are lubricated from the factory and adjusted. When in service, circuit breakers have current flowing through them lots of current. Whenever there is a large amount of current flow through a conductor, heat is created in the form of I 2 R (copper losses). The heat causes the factory-applied lubricants to dry out and they will flake off. Once that occurs, metal-to-metal wear begins. Adjustments can be affected by the wear, as well as the normal wear and tear or the circuit breaker can seize up and not work at all. I ve seen one circuit breaker partially open its contacts during a fault, which resulted in complete destruction of the circuit breaker. 43% had mechanical issues, mostly due to lack of lubrication and 11% failed to operate. Both of these surveys indicate that circuit breakers must be maintained and serviced on a regular basis or they will not function in accordance with their manufacturer s specifications. Depending on loading and environment, there is a three to five year interval that s required for maintenance and testing. XII. TURN IT OFF? I CAN DO THIS WITH MY EYES CLOSED There s an old saying in the electrical field There s old electricians and there s bold electricians, but there s no old, bold electricians. There s a lot of truth to that truism. However, it is also a fact that testosterone shrinks brain cells, or at least that s what my wife tells me. A quick look at YouTube and the point is difficult to argue with. A newspaper I was reading once had an article about a medical university that had just completed a multi-year study and had concluded that in men under the age of 25 the part of the brain that recognizes danger is underdeveloped. YouTube is filled with young men (and some not so young) risking life and limb to pull off some stunt and the results are usually not favorable. Even though this has humorous aspects to it, it also illustrates that younger men will take unwarranted risks, while (most) older men will not. Younger workers must be monitored more closely to ensure they do not become a victim of their egos. XIII. MEN AND WOMEN FACE THE SAME RISK FROM ELECTRICAL SHOCK Figure 5 Partial Table L.1 from NFPA 70B Annex L During the Technical Committee meetings for NFPA 70E, the question came up How do you know it is properly maintained? As discussed in the previous section, it s not easy, but the Test and Calibration Decal System would help if enough companies implemented it. Otherwise, a check of the maintenance records and test data is in order. The Reliability Subcommittee of the IEEE Industrial and Commercial Power Systems Committee, in IEEE Standard 493 (6) (the Gold Book) conducted a survey that included 1,469 failures of electrical equipment. In the survey, respondents were asked to describe their opinion of the maintenance quality in their plant. Inadequate maintenance was blamed for 16.4% of failures for all types of equipment. Table 5-2 in Std. 493 shows the facility s percentage of failures caused by inadequate maintenance vs. months since maintained. At 12 to 24 months the failure rate was 19%, when the circuit breakers had been in service more than 24 months the failure rate escalated to almost 78%! NETA (international Electrical Testing Association) surveyed their member companies about problems with circuit breakers (7). They received 340,000 responses. 22% of the circuit breakers had defects with their OCPD, while IEEE Standard 80 (8) Guide for Safety in AC Substation Grounding states that the average resistance for a 150 lb. man is 1,000Ω, while the average resistance for women is 750Ω. If both are exposed to a 120 V shock, the woman will have more current flow through her body, resulting in more injury. For 120-volt exposure: Men 120V = 120mA 1,000 Ω Women 120V = 160mA 750 Ω Figure 6, from Dr. Charles Dalziel s 1961 study (9) on the effects of electric shock contained the information in Figure 6. When looking at the heading labeled 60 Hz there are two columns; one for men and the other for women. Note that for every effect listed in this table, women suffered injury at a lower current value than men did. Women must be more conscious of the electrical shock hazard than men, as they are very likely to have more injury for the same exposure. This is not to say it is okay for men to make contact with any energized conductor or circuit part, only that women are at increased risk from the shock hazard. 5

6 Effects Direct Current Figure 6 From Deleterious Effects of Electric Shock, Dr. Charles Dalziel, 1961 XIV. CONCLUSIONS Information is one extremely important part of electrical safety. Misinformation can undue years of work and damage credibility to the point that nothing that is said further will correct the problem. Workers exposed to electrical hazards must have accurate information in order to make acceptable and safe decisions when working in the field. As with last year s paper, it is important to note that NFPA 70E requires an electrical system to be properly installed and maintained in order for the requirements of Chapter 1 to be met. If the maintenance requirements are not met in accordance with NFPA 70E Chapter 2, the requirements of Chapter 1 would very difficult to apply. NFPA 70B, as well as ANSI/NETA MTS-2011 can provide guidance for those needing information on maintenance requirements of electrical power systems and components. XVII. REFERENCES Current, ma Alternating Current 60 Hz 10 khz Men Women Men Women Men Women Slight sensation on hand Perception threshold Shock - not painful, muscular control not lost Shock - painful, muscular control not lost Shock - painful, let-go threshold Shock - painful and severe, muscular contractions, breathing difficult NFPA 70E, Standard for Electrical Safety in the Workplace, 2012 edition, Chapters 1 and 2 2. IEEE 1584, Guide for Performing Arc Flash Hazard Calculations 3. Stokes, A.D. and Sweeting, D.K. "Electric Arcing Burn Hazards", IEEE PCIC Conference Record, Paper PCIC , 9pp. 4. NFPA 70B, Recommended Practice for Electrical Equipment Maintenance, 2013 edition, Annex L 5. ANSI/NETA MTS-2011, Standard for Maintenance Testing Specifications for Electrical Power Distribution Equipment and Systems 6. IEEE Standard 493, IEEE Recommended Practice for Design of Reliable Industrial and Commercial Power Systems (Gold Book) 7. Widup, Ron and Heide, Kerry NETA Maintenance Testing Research on Electrical Power System Component Performance, Paper PCIC- 8. ANSI/IEEE, Guide for Safety in AC Substation Grounding, Std , pg Dalziel, Charles F., Deleterious Effects of Electric Shock, Meeting of Experts on Electrical Accidents and Related Matters, Geneva, October 1961 XVIII. VITA James White CESCP is the Training Director for Shermco Industries, Inc. located in Irving, Texas. He is a Senior member of the IEEE, the recipient of the 2011 IEEE/PCIC Electrical Safety Excellence Award, the 2008 IEEE Electrical Safety Workshop Chairman, Alternate international Electrical Testing Association (NETA) representative on NFPA 70E, Primary NETA representative on NFPA 70B, Primary NETA representative on NEC CMP-13 and is the NETA representative to ASTM F18. James is also a certified Level IV Senior Substation Technician with NETA, a Certified Electrical Safety Compliance Professional by NFPA, an inspector member of IAEI and serves on the NETA Safety and Training Committees. James is the author of Electrical Safety, A Practical Guide to OSHA and NFPA 70E and Significant Changes to NFPA 70E 2012 Edition both published by American Technical Publishers. 6

Electrical Safety Myths and Facts

Electrical Safety Myths and Facts Electrical Safety Myths and Facts Copyright Material IEEE Paper No. ESW James R. White Senior Member IEEE Shermco Industries, Inc.2425 E. Pioneer Drive Irving, Texas 75061 jrwhite@shermco.com Abstract

More information

2012 Edition. Tech Topics: Standards & Codes. Note 4, Issue 1. Points of Interest: Introduction. Background. Changes to Definitions in Article 100

2012 Edition. Tech Topics: Standards & Codes. Note 4, Issue 1. Points of Interest: Introduction. Background. Changes to Definitions in Article 100 Significant Changes to the NFPA 70E Standard 2012 Edition Tech Topics: Standards & Codes Note 4, Issue 1 Peter Walsh, PE Sr. Field Engineer Points of Interest: Arc-Rated (AR) vs. Flame-Resistant (FR) Training

More information

HESNI ANNUAL CONFERENCE May 3, 2012 Aramark Conference Center, Downers Grove

HESNI ANNUAL CONFERENCE May 3, 2012 Aramark Conference Center, Downers Grove HESNI ANNUAL CONFERENCE May 3, 2012 Aramark Conference Center, Downers Grove Jim Dungar, P.E. Principal Engineer Schneider Electric Engineering Services Jim.dungar@schneider-electric.com (920-766-8012)

More information

NFPA 70E Edition Update

NFPA 70E Edition Update NFPA 70E- 2018 Edition Update Paul Colangelo- STSC, CHST, CET, CRIS National Director of Compliance Programs ClickSafety 1 ASSE Construction Practice Specialty Quarterly Meeting 11/17/2017 Agenda Overview

More information

NFPA 70E. Electrical Safety in the Workplace. KTR Associates. Joseph Deane, PE. Engineering Solutions

NFPA 70E. Electrical Safety in the Workplace. KTR Associates. Joseph Deane, PE. Engineering Solutions NFPA 70E Electrical Safety in the Workplace KTR Associates Engineering Solutions Joseph Deane, PE Goal for Today Better understanding of NFPA 70E Raise the awareness of Electrical Hazards Why the sudden

More information

Safety Meeting Topic #37 NFPA 70E What is it?

Safety Meeting Topic #37 NFPA 70E What is it? Safety Meeting Topic #37 NFPA 70E What is it? The National Fire Protection Association (NFPA) 70E is the standard for Electrical Safety Requirements for Employee Workplaces and is a supplement to the NFPA70

More information

Changes to NFPA 70E. - The Role of PdM &Safe PdM Work Practices. Tim Rohrer Exiscan LLC

Changes to NFPA 70E. - The Role of PdM &Safe PdM Work Practices. Tim Rohrer Exiscan LLC Changes to NFPA 70E - The Role of PdM &Safe PdM Work Practices Tim Rohrer Exiscan LLC Tim@Exiscan.com 585-705-7775 Joe Gierlach ABM Joseph.Gierlach@ABM.com 412-394-4678 Preview Electrical Safety Risk Management

More information

NECA. Standard for Electrical Safety in the Workplace

NECA. Standard for Electrical Safety in the Workplace 4/23/2018 N E R C e- A di st N rib ot ut Fo io r n NECA Significant Changes to the 2018 NFPA 70E Standard for Electrical Safety in the Workplace NFPA 70E Standard for Electrical Safety in the Workplace

More information

IEEE Std IEEE Recommended Practice for Electrical Installations on Shipboard Safety Considerations

IEEE Std IEEE Recommended Practice for Electrical Installations on Shipboard Safety Considerations IEEE Std 45.5-2014 IEEE Recommended Practice for Electrical Installations on Shipboard Safety Considerations Presented by Dennis K. Neitzel, CPE, CESCP Director Emeritus Keeping People Safe from Electrical

More information

Applying the 2012 NFPA 70E. Arc Flash Standard

Applying the 2012 NFPA 70E. Arc Flash Standard Applying the 2012 NFPA 70E Arc Flash Standard Suncoast Industrial Services, Inc. 80-6A Industrial Loop N. Orange Park, Fl 32073 904-269-4403 904-269-4404 (fax) wehbysis@suncoastind.com 1 Suncoast Suncoast

More information

NFPA 70E Arc Flash Considerations for MV Equipment. By: Dominik Pieniazek, P.E. HV Engineering, LLC

NFPA 70E Arc Flash Considerations for MV Equipment. By: Dominik Pieniazek, P.E. HV Engineering, LLC NFPA 70E Arc Flash Considerations for MV Equipment By: Dominik Pieniazek, P.E. dominik@hv-eng.com HV Engineering, LLC http://sites.ieee.org/houston/ Full link for PDF copies of presentations: http://sites.ieee.org/houston/communities/ie

More information

May is National Electrical Safety Month, an AND THE ELECTRICAL INSPECTOR. by Mark Hilbert and Laura L. Hildreth

May is National Electrical Safety Month, an AND THE ELECTRICAL INSPECTOR. by Mark Hilbert and Laura L. Hildreth by Mark Hilbert and Laura L. Hildreth AND THE ELECTRICAL INSPECTOR May is National Electrical Safety Month, an annual effort to help reduce electricallyrelated fatalities, injuries, and property loss both

More information

How to reduce exposure to arc flash hazards

How to reduce exposure to arc flash hazards GE Electrical Distribution How to reduce exposure to arc flash hazards Multiple solutions for new and existing facilities imagination at work Multiple Issues Today s power system engineer must not only

More information

ANSI/NETA Standards Update

ANSI/NETA Standards Update Specifications and Standards Activity ANSI/NETA Standards Update NOW AVAILABALE!!!! NETA Standard for Acceptance Testing Specifications for Electrical Power Equipment and Systems The NETA Acceptance Testing

More information

Electrical Safety Compliance: NFPA 70E

Electrical Safety Compliance: NFPA 70E Electrical Safety Compliance: NFPA 70E From Graybar and Schneider Electric Risks associated with shock and electrocution from inadvertent contact with energized parts have long been recognized as a threat

More information

Electrical Safety Program

Electrical Safety Program Electrical Safety Program Developed by: The Office of Environmental Health and Safety June, 2010 Table of Contents Introduction 3 Scope..3 Definitions.3-5 CSU Electrical Shop...5 Responsibilities.5-6 Employees.....5

More information

Electrical Hazards and NFPA-70E: Protecting Your Employees

Electrical Hazards and NFPA-70E: Protecting Your Employees Electrical Hazards and NFPA-70E: Protecting Your Employees Presented By Mark B. Haskins, MS, CSP Practical Safety Solutions, LLC At the CBIA Safety Health and Wellness Conference May 22, 2014 PRESENTATION

More information

Webinar November 12, 2014

Webinar November 12, 2014 Webinar November 12, 2014 Dennis L. Mater dennis.l.mater@dupont.com FR Apparel Sales Technical Leader North America Webinar Overview Introduction Hazard Risk Types Contrast Short Duration Fire and Arc

More information

WHY ELECTRICAL PREVENTIVE MAINTENANCE IS ESSENTIAL TO A SAFE AND PRODUCTIVE WORKPLACE

WHY ELECTRICAL PREVENTIVE MAINTENANCE IS ESSENTIAL TO A SAFE AND PRODUCTIVE WORKPLACE WHY ELECTRICAL PREVENTIVE MAINTENANCE IS ESSENTIAL TO A SAFE AND PRODUCTIVE WORKPLACE AGENDA SCRWA 14 SEPTEMBER 2016 Definition Why EDPM is essential to productivity Fiscal sustainability Why EDPM is essential

More information

Arc Flash Protection Training - NFPA 70e Electrical Safety

Arc Flash Protection Training - NFPA 70e Electrical Safety Arc Flash Protection Training - NFPA 70e Electrical Safety Contact us Today for a FREE quotation to deliver this course at your company?s location. https://www.electricityforum.com/onsite-training-rfq

More information

ELECTRICAL PANEL SAFETY ALERT I N S T I T U T E

ELECTRICAL PANEL SAFETY ALERT I N S T I T U T E ELECTRICAL PANEL SAFETY ALERT CONSUMER SAFETY I N S T I T U T E Dangerous Panels brochure.indd 1 9/29/08 11:41:48 AM The Electrical Panel The Heart of a Home s Electrical System The home s electrical system

More information

NECA S System Approach to Electrical Safety for NFPA 70E

NECA S System Approach to Electrical Safety for NFPA 70E NECA S System Approach to Electrical Safety for NFPA 70E NECA s Systems Approach to NFPA 70E Easy to understand NFPA 70E employer requirements, Provides Supervisors with key on the job information, De-energize

More information

Guide to Compliance with the Electrical Workplace Safety Standards in the United States

Guide to Compliance with the Electrical Workplace Safety Standards in the United States Guide to Compliance with the Electrical Workplace Safety Standards in the United States July 2011/1910DB1102 by Joseph H. Weigel, Product Manager Schneider Electric USA, Inc. Make the most of your energy

More information

SEL Arc-Flash Solutions

SEL Arc-Flash Solutions SEL Arc-Flash Solutions Arc-Flash Protection at the Speed of Light Protect personnel and equipment Detect arc-flash events and send a trip signal in as little as 2 ms to enhance safety and minimize equipment

More information

Electrical Safety for Facility Managers and Building Owners

Electrical Safety for Facility Managers and Building Owners CEU s Copy of Slides Evaluation Form Follow up information Disclaimer. This seminar was produced to help explain the importance and need for electrical safety specifically for Facility Managers. It does

More information

SEL Arc-Flash Solutions

SEL Arc-Flash Solutions SEL Arc-Flash Solutions Arc-Flash Protection at the Speed of Light Protect personnel and equipment. Detect arc-flash events and send a trip signal in as little as 2 ms to enhance safety and minimize equipment

More information

SUMMARY: Policy Title: Electrical Safety Work Practice Program. Policy Number: UNIV-EHS 430 Policy Approved: January 2014

SUMMARY: Policy Title: Electrical Safety Work Practice Program. Policy Number: UNIV-EHS 430 Policy Approved: January 2014 Policy Title: Electrical Safety Work Practice Program Policy Number: UNIV-EHS 430 Policy Approved: January 2014 Policies Superseded: FINA-730 Policy Management Area: Environmental Health and Safety Created/Revision(s):

More information

White Paper. NFPA 70E 2018 Edition Changes and Implications for. Personnel Performing Condition Based Maintenance. Abstract: iriss.

White Paper. NFPA 70E 2018 Edition Changes and Implications for. Personnel Performing Condition Based Maintenance. Abstract: iriss. NFPA 70E 2018 Edition Changes and Implications for Personnel Performing Condition Based Maintenance By Rudy Wodrich, P.Eng., MBA, CRL, L1 Thermographer, VP Engineering Services, IRISS Inc. Abstract: The

More information

NFPA 70E Elevates Safety. with Heightened Risk Awareness

NFPA 70E Elevates Safety. with Heightened Risk Awareness NFPA 70E 2015 Elevates Safety with Heightened Risk Awareness Next Page NFPA 70E 2015 Elevates Safety with Heightened Risk Awareness: Significant Changes Since 2012 Compel Updated Electrical Safety Training

More information

Safety Best Practices Manual

Safety Best Practices Manual CHAPTER 24 OSHA Compliance Checklist te: This is not a comprehensive checklist. It is designed for a typical corporate aviation maintenance department. You must consult the OSHA 1910 Regulations for specific

More information

Arc Flash Analysis: IEEE Method versus the NFPA 70E Tables July 2017 / 1910DB1702

Arc Flash Analysis: IEEE Method versus the NFPA 70E Tables July 2017 / 1910DB1702 Arc Flash Analysis: IEEE Method versus the NFPA 70E Tables July 2017 / 1910DB1702 by Reza Tajali, Schneider Electric Engineering Services Summary 1.0 Abstract 2.0 OSHA and NFPA Rules 3.0 Use of NFPA 70E

More information

NECA S System Approach to Electrical Safety for NFPA 70E

NECA S System Approach to Electrical Safety for NFPA 70E NECA S System Approach to Electrical Safety for NFPA 70E NECA s Systems Approach to NFPA 70E Easy to understand NFPA 70E employer requirements, Provides Supervisors with key on the job information, De

More information

IR Viewing Windows and Arc Ratings Dispelling the myth of Arc-Resistant IR Viewing Windows

IR Viewing Windows and Arc Ratings Dispelling the myth of Arc-Resistant IR Viewing Windows IR Viewing Windows and Arc Ratings Dispelling the myth of Arc-Resistant IR Viewing Windows Abstract There exists a dangerous misconception regarding the Arc Rating of IR viewing windows or viewing panes.

More information

DEMYSTIFYING FR CLAIMS: AN ERGODYNE WHITE PAPER

DEMYSTIFYING FR CLAIMS: AN ERGODYNE WHITE PAPER DEMYSTIFYING FR CLAIMS: AN ERGODYNE WHITE PAPER Each year, hundreds of burn injuries and deaths are recorded from workers encountering open flame and high heat or exposure to flash fires and electrical

More information

PREVIEW COPY. Table of Contents. Annexes and Supplemental Materials Lesson One Article 90: Introduction and Purpose... 3

PREVIEW COPY. Table of Contents. Annexes and Supplemental Materials Lesson One Article 90: Introduction and Purpose... 3 Table of Contents Lesson One Article 90: Introduction and Purpose... 3 Lesson Two Articles 100 and 105: Terms and Definitions... 17 Lesson Three Article 110: General Requirements for Work Practices...

More information

The Basics Arc Flash Protection

The Basics Arc Flash Protection 2008 The Basics Arc Flash Protection An arcing fault can be defined as the flow of current through a path where it is not intended to flow Rob Vajko 12/15/2008 What is an Arc Flash? An arc flash starts

More information

T22 - Arc Flash Hazards and Arc Resistant Equipment- Understanding the Standards

T22 - Arc Flash Hazards and Arc Resistant Equipment- Understanding the Standards T22 - Arc Flash Hazards and Arc Resistant Equipment- Understanding the Standards v2-5058-co900h Copyright 2016 Rockwell Automation, Inc. All Rights Reserved. 1 Agenda 1. Background 2. Related Electrical

More information

IMPROVE SAFETY WITH ARC FLASH LABELING COMPLY WITH THE 2015 NFPA 70E REGULATIONS

IMPROVE SAFETY WITH ARC FLASH LABELING COMPLY WITH THE 2015 NFPA 70E REGULATIONS IMPROVE SAFETY WITH ARC FLASH LABELING COMPLY WITH THE 2015 NFPA 70E REGULATIONS By Thomas Smith, Product Specialist, Brady Corporation Last updated: February, 2015 The Occupational Safety and Health Administration

More information

NATIONAL ELECTRICAL CODE (NEC) & NFPA 70E ARC FLASH ELECTRICAL SAFETY

NATIONAL ELECTRICAL CODE (NEC) & NFPA 70E ARC FLASH ELECTRICAL SAFETY A new twist on the National Electrical Code - a practical application workshop. If you sign up in this class, prepare to work! Day 1: Fundamentals of OSHA requirements for performing electrical work -

More information

PROTECTING AGAINST ARC FLASH HAZARDS

PROTECTING AGAINST ARC FLASH HAZARDS PROTECTING AGAINST ARC FLASH HAZARDS Presented by: Andrew J. Fitzpatrick, P.E. Electricity Simply stated electricity is the flow of electrons Electricity is governed by laws: Ohms Law : V=IR Kirchoff s

More information

Implementing an Energized Electrical Work Program. SESHA Hill Country Chapter. Brett Jay Davis, PE Zephyr Environmental Corporation

Implementing an Energized Electrical Work Program. SESHA Hill Country Chapter. Brett Jay Davis, PE Zephyr Environmental Corporation Implementing an Energized Electrical Work Program SESHA Hill Country Chapter May 22, 2009 Brett Jay Davis, PE Zephyr Environmental Corporation bdavis@zephyrenv.com, 512 879-6628 Presentation Outline 1.

More information

2014 National Electrical Code & NFPA 70E/Arc Flash

2014 National Electrical Code & NFPA 70E/Arc Flash Gain an understanding of the 2014 NEC s latest additions, revisions and changes. Learn the precautions needed when working with and around electricity. People and property need to be safeguarded from the

More information

VeriSafe Absence of Voltage Tester The safe way to verify the absence of voltage

VeriSafe Absence of Voltage Tester The safe way to verify the absence of voltage VeriSafe Absence of Voltage Tester The safe way to verify the absence of voltage www.panduit.com/verisafe What is an Absence of Voltage Tester? Absence of Voltage Testers (AVTs) are permanently-mounted

More information

Welcome DISCLAIMER. Testing Electric Fire Pumps You Need to Understand the Arc Flash Hazard 5/1/ NFPA Conference & Expo

Welcome DISCLAIMER. Testing Electric Fire Pumps You Need to Understand the Arc Flash Hazard 5/1/ NFPA Conference & Expo 2017 NFPA Conference & Expo Testing Electric Fire Pumps You Need to Understand the Arc Flash Hazard Presented by: Tracey D. Bellamy, PE, CFPS Chief Engineering Officer Telgian Corporation Welcome Instructor

More information

NFPA 70E Electrical Safety & Arc Flash Training

NFPA 70E Electrical Safety & Arc Flash Training NFPA 70E Electrical Safety & Arc Flash Training OSHA 1910.332(a) Training, 1910.332(a) Scope. The training requirements contained in this section apply to employees who face a risk of electric shock that

More information

The safe way to verify the absence of voltage.

The safe way to verify the absence of voltage. VeriSafe Absence of Voltage Tester The safe way to verify the absence of voltage www.panduit.com/verisafe What is an Absence of Voltage Tester? Absence of Voltage Testers (AVTs) are permanently-mounted

More information

6/23/ National Electrical Contractors Association and Intec, Inc.

6/23/ National Electrical Contractors Association and Intec, Inc. 2012 National Electrical Contractors Association and Intec, Inc. 1 Palmer Hickman Director of Codes and Standards electrical training ALLIANCE Jim Dollard Safety IBEW 98 Objectives Explain why work should

More information

Monitoring of Electrical Equipment Failure Indicators and Alarming

Monitoring of Electrical Equipment Failure Indicators and Alarming Past, Present and Future Maintenance Practices: Monitoring of Electrical Equipment Failure Indicators and Alarming Author: Gabe Paoletti, P.E. Eaton Corporation Senior Member, IEEE gabrieljpaoletti@eaton.com

More information

Reducing Arc Flash Risks with Electrical Maintenance Safety Devices - Part 2

Reducing Arc Flash Risks with Electrical Maintenance Safety Devices - Part 2 Reducing Arc Flash Risks with Electrical Maintenance Safety Devices - Part 2 By: Martin Robinson, CEO of IRISS Group and Level III Thermographer Abstract Every year thousands electrical workers are injured

More information

Data Bulletin. Determining the Cause of AFCI Tripping Class 760

Data Bulletin. Determining the Cause of AFCI Tripping Class 760 Data Bulletin 0760DB0204 06/2002 Cedar Rapids, IA, USA Determining the Cause of AFCI Tripping Class 760 Retain for future use. INTRODUCTION DANGER HAZARD OF ELECTRIC SHOCK, BURN, OR EXPLOSION This document

More information

Understanding 2015 Changes to NFPA 70E Safety-related work practices and maintenance requirements mandate more robust electrical safety programs for

Understanding 2015 Changes to NFPA 70E Safety-related work practices and maintenance requirements mandate more robust electrical safety programs for Understanding 2015 Changes to NFPA 70E Safety-related work practices and maintenance requirements mandate more robust electrical safety programs for data centers Executive Summary Every three years, the

More information

Electrical Preventive Maintenance (EPM) Program

Electrical Preventive Maintenance (EPM) Program Electrical Preventive Maintenance (EPM) Program Only qualified and properly trained persons may work on electric circuit parts or equipment. Such persons shall be capable of working safely and shall be

More information

NFPA 70E Electrical Safety in the Workplace

NFPA 70E Electrical Safety in the Workplace NFPA 70E Electrical Safety in the Workplace Objectives What NFPA 70E covers Understand Arc Flash, Incident Energy, & Flash Protection Boundary Standards, Enforcement, & Safe Practices Arc Flash Hazard

More information

Centennial Energized Electrical Work Permit Instructions

Centennial Energized Electrical Work Permit Instructions Centennial Energized Electrical Work Permit Instructions PART I. GENERAL INFORMATION DESCRIPTION OF CIRCUIT/EQUIPMENT/JOB LOCATION: The description of the circuit to be worked in an energized state shall

More information

Fire ground electrocution

Fire ground electrocution Fire ground electrocution By VINCENT DUNN Ret Chief FDNY To survive firefighting, firefighters must know how other firefighters have died fighting fires. Electrocution is one cause of fire ground death.

More information

Protection from Electric Shock and Arc Flash. Meeting OSHA Regulations and NFPA 70E Standards.

Protection from Electric Shock and Arc Flash. Meeting OSHA Regulations and NFPA 70E Standards. Be Smart. Be Safe. Protection from Electric Shock and Arc Flash. Meeting OSHA Regulations and NFPA 70E Standards. ISO 9001:2000 Registered SALISBURY 7520 N Long Ave Skokie Il 60077 Toll Free 877.406.4501

More information

Infrared Windows and Arc Ratings: Dispelling the Myth of Arc-Resistant IR Windows

Infrared Windows and Arc Ratings: Dispelling the Myth of Arc-Resistant IR Windows Infrared Windows and Arc Ratings: Dispelling the Myth of Arc-Resistant IR Windows Tim Rohrer, VP of Sales & Marketing Martin Robinson, President and IRISS, Inc. 4914 Lena Road, Suite 105 Bradenton, FL

More information

Electric Fire Pump Controller Inspection, Test & Maintenance Arc Flash Hazard White Paper

Electric Fire Pump Controller Inspection, Test & Maintenance Arc Flash Hazard White Paper Electric Fire Pump Controller Inspection, Test & Maintenance Arc Flash Hazard White Paper March 27, 2017 Prepared by: Tracey D. Bellamy, PE, CFPS Telgian Corporation Submitted on behalf of: The Home Depot

More information

NFPA 70B and CSA Z463 Standards for Electrical Maintenance Where Does Airborne Ultrasound Fit In?

NFPA 70B and CSA Z463 Standards for Electrical Maintenance Where Does Airborne Ultrasound Fit In? NFPA 70B and CSA Z463 Standards for Electrical Maintenance Where Does Airborne Ultrasound Fit In? Adrian Messer, Manager of US Operations UE Systems, Inc. Ph: 864-224-4517 Cell: 914-282-3504 Web: www.uesystems.com

More information

ESCONDIDO FIRE DEPT TRAINING MANUAL Section Truck Module Page 1 of 6 Utilities Electrical Emergencies Revised

ESCONDIDO FIRE DEPT TRAINING MANUAL Section Truck Module Page 1 of 6 Utilities Electrical Emergencies Revised Truck Module Page 1 of 6 ELECTRICAL EMERGENCIES Classification of Voltage For firefighting purposes, voltage can be considered in one of two classes, either high or low. As a general rule, the larger the

More information

NFPA 70E Update: Key Changes You Need to Know to Assure Compliance

NFPA 70E Update: Key Changes You Need to Know to Assure Compliance NFPA 70E Update: Key Changes You Need to Know to Assure Compliance Presented by: Andrew Reisinger EHS International Inc. Thursday, August 22, 2013 1:30 p.m. to 3:00 p.m. Eastern 12:30 p.m. to 2:00 p.m.

More information

PANELBOARDS & BUILDING DISTRIBUTION

PANELBOARDS & BUILDING DISTRIBUTION 262416 PANELBOARDS & BUILDING DISTRIBUTION PART 1 GENERAL 1.01 SUMMARY A. Section Includes: 1. Distribution panelboards 2. Power panelboards B. Related Sections: 1.02 POLICY 1. CU Standard 260500, Basic

More information

Before you begin. Introduction About construction work 1. Topic 1 How health and safety laws apply to you 3

Before you begin. Introduction About construction work 1. Topic 1 How health and safety laws apply to you 3 Contents Before you begin v Introduction About construction work 1 Topic 1 How health and safety laws apply to you 3 1A Health and safety laws and your work 4 Activity 1: Legislation, roles and duty holders

More information

US Navy Leading the Way in Switchboard Protection

US Navy Leading the Way in Switchboard Protection US Navy Leading the Way in Switchboard Protection Rick Kurek Naval Sea Systems Command (NAVSEA) 2341 Jefferson Davis Highway Arlington, VA 22202 Ph: 202-781-1274 rick.kurek@navy.mil Abstract According

More information

NFPA Edition Review

NFPA Edition Review This is a photographic template your photograph should fit precisely within this rectangle. NFPA 70 & 99 How Recent Code Changes Effect Healthcare Facilities Sam C. Terry, P.E. Application Engineer Eaton

More information

Arc Flash Codes & Compliance: What You Need to Know to Deliver Both Protection and Performance

Arc Flash Codes & Compliance: What You Need to Know to Deliver Both Protection and Performance Arc Flash Codes & Compliance: What You Need to Know to Deliver Both Protection and Performance An arc flash can cause serious injury or death to anyone in its path. The National Electrical Code provides

More information

PREPARING YOUR ORGANIZATION FOR NFPA 70E 2015

PREPARING YOUR ORGANIZATION FOR NFPA 70E 2015 PREPARING YOUR ORGANIZATION FOR NFPA 70E 2015 Presenter Name Date JOSE DE LA MAZA April 27, 2016 Region IX VPPPA Safety Summit Agenda 1 Electrical Safety Basics Electrical Safety Statistics OSHA & NFPA

More information

Brian McCauley December 2017

Brian McCauley December 2017 Brian McCauley December 2017 ELECTRICAL SAFETY COMPLIANCE & NFPA 70E 2018 Agenda 1 Introduction Electrical Safety Basics Electrical Safety Statistics NFPA 70E 2018 Updates PPE Questions A Little bit of

More information

EFCOG BEST PRACTICE # 203. Best Practice Title: Risk Assessment / Operation of Overcurrent Protection Devices

EFCOG BEST PRACTICE # 203. Best Practice Title: Risk Assessment / Operation of Overcurrent Protection Devices EFCOG BEST PRACTICE # 203 Best Practice Title: Risk Assessment / Operation of Overcurrent Protection Devices Facility: DOE Complex Point of Contact: Gregory Christensen, Phone: (208)526-5380, email: gregory.christensen@inl.gov

More information

Arc Fault Detection Devices (AFDDs) Protecting People and Property

Arc Fault Detection Devices (AFDDs) Protecting People and Property Arc Fault Detection Devices (AFDDs) Protecting People and Property Singapore Standard : CP5 Code of practice for electrical installations - Foreword 2 BS 7671 : the 18 th Edition report Short Brief 3 BS

More information

NFPA Updates (c) 2015 SSR, Inc. All rights reserved Florida AHCA Conf

NFPA Updates (c) 2015 SSR, Inc. All rights reserved Florida AHCA Conf Training presentation for: 2015 Florida AHCA Conference NFPA 110 Updates for 2016 David Stymiest, CHFM, CHSP, FASHE, (PE in LA MS MA) DStymiest@ssr-inc.com, cell 504.232.1113 Copyright 2015, Smith Seckman

More information

HOW TO CHOOSE THE RIGHT PROTECTION FOR FIRES, FLASH FIRES & ARC FLASHES

HOW TO CHOOSE THE RIGHT PROTECTION FOR FIRES, FLASH FIRES & ARC FLASHES PAPER HOW TO CHOOSE THE RIGHT PROTECTION FOR FIRES, FLASH FIRES & ARC FLASHES How to Choose the Right Protection for Fires, Flash Fires & Arc Flashes An employee in Arkansas is killed when an overhead

More information

SERVICE MANUAL FOR ROOF TOP AIR CONDITIONERS

SERVICE MANUAL FOR ROOF TOP AIR CONDITIONERS SERVICE MANUAL FOR ROOF TOP AIR CONDITIONERS PREFACE This service manual is primarily intended for the use of qualified individuals specially trained and experienced in the service of this type of equipment

More information

in the United States Home fires are a major problem Older Homes Pose an Even Greater Threat Put Into Perspective Electrocutions Can Be Prevented

in the United States Home fires are a major problem Older Homes Pose an Even Greater Threat Put Into Perspective Electrocutions Can Be Prevented Home fires are a major problem in the United States Each year, home electrical problems alone account for an estimated 53,600 fires. These fires cause more than 500 deaths, 1,400 injuries, and $1.4 billion

More information

MODEL FPT-130 SINGLE POINT FREEZE PROTECTION HEAT TRACE CONTROL

MODEL FPT-130 SINGLE POINT FREEZE PROTECTION HEAT TRACE CONTROL TRACON MODEL FPT-130 SINGLE POINT FREEZE PROTECTION HEAT TRACE CONTROL TABLE OF CONTENTS FPT 130 Overview... 2 Installation... 3 Power Source and Load Connections... 4 Temperature Sensor... 5 External

More information

Chapter 1 General...9 Article 100 Definitions...11 Article 100 Questions Article 110 Requirements for Electrical Installations...

Chapter 1 General...9 Article 100 Definitions...11 Article 100 Questions Article 110 Requirements for Electrical Installations... Article 90 Introduction...1 90.1 Purpose of the NEC...1 90.2 Scope of the NEC...2 90.3 Code Arrangement...4 90.4 Enforcement...5 90.5 Mandatory Requirements and Explanatory Material...6 90.6 Formal Interpretations...6

More information

9/7/2010. Chapter , The McGraw-Hill Companies, Inc. AND BONDING. 2010, The McGraw-Hill Companies, Inc.

9/7/2010. Chapter , The McGraw-Hill Companies, Inc. AND BONDING. 2010, The McGraw-Hill Companies, Inc. Chapter 1 GROUNDING AND BONDING 1 Proper grounding practices protect people from the hazards of electric shock and ensure the correct operation of overcurrent protection devices. Grounding is the intentional

More information

EC Electricity... Our Unseen Friend

EC Electricity... Our Unseen Friend University of Nebraska - Lincoln DigitalCommons@University of Nebraska - Lincoln Historical Materials from University of Nebraska- Lincoln Extension Extension 1966 EC66-761 Electricity... Our Unseen Friend

More information

Regional Training. Seminar. » EasyPower Hands-On» Protective Device Coordination» Arc Flash Hazard Analysis. March 12-16, 2018 Austin, TX

Regional Training. Seminar. » EasyPower Hands-On» Protective Device Coordination» Arc Flash Hazard Analysis. March 12-16, 2018 Austin, TX Regional Training» EasyPower Hands-On» Protective Device Coordination» Arc Flash Hazard Analysis Seminar March 12-16, 2018 Austin, TX DoubleTree Austin EasyPower, state-of-the-art Power System Analysis

More information

ELECTRICAL SAFETY GUIDELINE

ELECTRICAL SAFETY GUIDELINE ELECTRICAL SAFETY GUIDELINE November 2015 Electrical Safety Guidelines Table of Contents I. General II. General Electrical Safety A. Definitions B. Circuit Breaker Loads C. Electrical Grounding D. Electrical

More information

2017 NEC: Impact to Electrical System Designs

2017 NEC: Impact to Electrical System Designs 2017 NEC: Impact to Electrical System Designs We will begin shortly. Turn up your speakers in order to hear the hold music. Feel free to ask questions now in the Q&A widget! Today s broadcast is sponsored

More information

Title: Electrical Safety Effective Date: 11/28/2014 Control Number: THG_0038 Revision Number: 1 Date: 10/22/2015 Annual Review Completed: 5/13/2015

Title: Electrical Safety Effective Date: 11/28/2014 Control Number: THG_0038 Revision Number: 1 Date: 10/22/2015 Annual Review Completed: 5/13/2015 Title: Electrical Safety Effective Date: 11/28/2014 Control Number: THG_0038 Revision Number: 1 Date: 10/22/2015 Annual Review Completed: 5/13/2015 Electrical Safety CONTENTS I. PURPOSE II. SCOPE III.

More information

Electrical Safety Requirements

Electrical Safety Requirements Electrical Safety Requirements Purpose This document defines the minimum required control measures to reduce the risk of injury or illness related to electricity. Scope Applicable to all Coca-Cola system

More information

HAZARDOUS MATERIALS/WASTE EMERGENCY CONTINGENCY PLAN University of Southern Maine Portland Campus

HAZARDOUS MATERIALS/WASTE EMERGENCY CONTINGENCY PLAN University of Southern Maine Portland Campus HAZARDOUS MATERIALS/WASTE EMERGENCY CONTINGENCY PLAN University of Southern Maine Portland Campus Issued By: Office of Finance and Administration Name: Chief Financial Officer Effective Date: November

More information

This section applies to the use of cord- and plug-connected equipment, including cord sets (extension cords).

This section applies to the use of cord- and plug-connected equipment, including cord sets (extension cords). (B) Portable Electric Equipment. This section applies to the use of cord- and plug-connected equipment, including cord sets (extension cords). (1) Handling. Portable equipment shall be handled in a manner

More information

NATIONAL TRAINING BOARD (ELECTRICIAN) REGULATIONS 2008 BR 54/2008 NATIONAL OCCUPATIONAL CERTIFICATION ACT :38

NATIONAL TRAINING BOARD (ELECTRICIAN) REGULATIONS 2008 BR 54/2008 NATIONAL OCCUPATIONAL CERTIFICATION ACT :38 BR 54/ NATIONAL OCCUPATIONAL CERTIFICATION ACT 2004 2004 :38 The National Training Board, with the approval of the Minister responsible for the National Training Board, in exercise of the powers conferred

More information

Brown University Revised June 29, 2012 Facilities Design & Construction Standards SECTION ELECTRICAL DESIGN CRITERIA

Brown University Revised June 29, 2012 Facilities Design & Construction Standards SECTION ELECTRICAL DESIGN CRITERIA PART 1 - GENERAL 1.1 Background SECTION 26 00 10- ELECTRICAL DESIGN CRITERIA A. Brown University maintains it own campus electrical distribution system which serves the majority of the buildings and facilities

More information

The Electrical Safety Guide

The Electrical Safety Guide Leviton Learning Lab Presents The Electrical Safety Guide An Educational Training Manual for Industry Professionals Learning Lab Series a EDUCATION & TRAINING - Source: www.hospitalconnect.com Electrical

More information

OWNER S MANUAL ELECTRIC FIREPLACE INSERT. Model No.: WESTERN (EF42D-45D) WARNING CAUTION

OWNER S MANUAL ELECTRIC FIREPLACE INSERT. Model No.: WESTERN (EF42D-45D) WARNING CAUTION ELECTRIC FIREPLACE INSERT Model No.: WESTERN (EF42D-45D) OWNER S MANUAL WARNING Read and understand this entire owner s manual, including all safety information, before plugging in or using this product.

More information

PGR-8800 TECHNICAL FAQ

PGR-8800 TECHNICAL FAQ PGR-8800 SOLAR ARC-FLASH PRODUCTS RELAY CATALOG TECHNICAL FAQ What are the typical applications / system voltages? The PGR-8800 can be used on electrical systems operating at any voltage (AC or DC) since

More information

Your Global Automation Partner. Minimizing Arc Flash Exposure in Industrial Applications. White Paper - W1000

Your Global Automation Partner. Minimizing Arc Flash Exposure in Industrial Applications. White Paper - W1000 Your Global Automation Partner Minimizing Arc Flash Exposure in Industrial Applications White Paper - W1000 Industrial environments present multiple safety challenges, including fire hazards that require

More information

UNDERSTANDING 2015 CHANGES TO NFPA 70E

UNDERSTANDING 2015 CHANGES TO NFPA 70E UNDERSTANDING 2015 CHANGES TO NFPA 70E Safety-related work practices and maintenance requirements mandate more robust electrical safety programs for commercial and industrial facilities TWO STAGE POWER

More information

INSTALLATION, OPERATION AND MAINTENANCE MANUAL

INSTALLATION, OPERATION AND MAINTENANCE MANUAL GE Digital Energy Power Quality INSTALLATION, OPERATION AND MAINTENANCE MANUAL GE TRANQUELL Enhanced Thermal Protection (ETP) Series Integrally Mounted Medium and High Exposure Surge Protective Devices

More information

"EVACUATION PROCEDURES"

EVACUATION PROCEDURES PRESENTER'S GUIDE "EVACUATION PROCEDURES" Part of the "SAFETY MEETING KIT" Series Quality Safety and Health Products, for Today...and Tomorrow OUTLINE OF MAJOR PROGRAM POINTS OUTLINE OF MAJOR PROGRAM POINTS

More information

White Paper. Reducing Arc Flash Risks with Electrical Maintenance. Safety Devices. Abstract: iriss.com

White Paper. Reducing Arc Flash Risks with Electrical Maintenance. Safety Devices. Abstract: iriss.com Reducing Arc Flash Risks with Electrical Maintenance By Martin Robinson, CMRP Level III Thermographer President, IRISS Inc. Abstract: Electrical accidents, such as arc flashes, happen daily; however, there

More information

Leader s Guide Marcom Group Ltd.

Leader s Guide Marcom Group Ltd. 1520 EVACUATION PROCEDURES Leader s Guide Marcom Group Ltd. Structure and Organization Information in this program is presented in a definite order so that employees will see the relationships between

More information

HARDWOOD INDUSTRY FACILITY & SAFETY INSPECTION CHECKLIST

HARDWOOD INDUSTRY FACILITY & SAFETY INSPECTION CHECKLIST Company: Inspection Completed By: Date: Administrative: 1. Written safety rules/safe job procedures in place 2. OSHA log updated/safety posters displayed 3. Management Safety Policy in place 4. All planned

More information

THE ALLIANCE FOR BANGLADESH WORKER SAFETY BOILER SAFETY

THE ALLIANCE FOR BANGLADESH WORKER SAFETY BOILER SAFETY THE ALLIANCE FOR BANGLADESH WORKER SAFETY BOILER SAFETY 1 Boiler Room Hazards A Risk Of Explosion Exists High Pressure steam Combustion Gases Chemicals Moving Machinery Hot Surfaces www.bangladeshworkersafety.org

More information

Today, we re going to talk about emergency action and fire prevention. We hope we never have to face an emergency situation like a fire in our

Today, we re going to talk about emergency action and fire prevention. We hope we never have to face an emergency situation like a fire in our Today, we re going to talk about emergency action and fire prevention. We hope we never have to face an emergency situation like a fire in our workplace, but we must always be prepared, just in case. Your

More information

Electrical Safety Program.

Electrical Safety Program. University of North Carolina Wilmington Environmental Health & Safety Workplace Safety Electrical Safety Program GENERAL The UNCW Environmental Health & Safety Department (EH&S) is authorized by UNCW Policy

More information