Model FP-424C ma Combustible Gas Sensor (0-100% LEL) Operator s Installation & Instruction Manual. May 18, 2010 Document #2243T Version 3.

Size: px
Start display at page:

Download "Model FP-424C ma Combustible Gas Sensor (0-100% LEL) Operator s Installation & Instruction Manual. May 18, 2010 Document #2243T Version 3."

Transcription

1 detcon inc. Model FP-424C 4-20 ma Combustible Gas Sensor (0-100% LEL) Operator s Installation & Instruction Manual May 18, 2010 Document #2243T Version 3.8 CAUTION: FOR SAFETY REASONS THIS EQUIPMENT MUST BE OPERATED AND SERVICED BY QUALIFIED PERSONNEL ONLY. READ AND UNDERSTAND INSTRUCTION MANUAL COMPLETELY BEFORE OPERATING OR SERVICING. ATTENTION: POUR DES RAISONS DE SECURITE, CET EQUIPEMENT DOIT ETRE UTILISE ENTRETENU ET REPARE UNIQUEMENT PAR UN PERSONNEL QUALI- FIE. ETUDIER LE MANUEL D'INSTRUCTIONS EN ENTIER AVANT D'UTILISER, D'ENTRETENIR OU DE REPARER L'EQUIPEMENT. phone , fax sales@detcon.com

2 Table of Contents 1.0 Description 2.0 Principle of Operation 3.0 Application 4.0 Specifications 5.0 Installation 6.0 Start-up 7.0 Calibration 8.0 Fault Supervision 9.0 Trouble Shooting Guide 10.0 Spare Parts List 11.0 Warranty 12.0 Service Policy Detcon Model FP-424C Combustible Gas Sensor PG.2

3 1.0 DESCRIPTION Detcon Model FP-424C combustible gas detection sensors are designed to monitor ambient air for combustible hydrocarbons in the lower explosive limit range (0-100% LEL). The sensor assembly consists of a plug in replaceable matched pair of catalytic beads mounted in a stainless steel housing, a VDC 4-20 ma DC control transmitter, an explosion proof junction box, and a machine fitted rain shield. 1.1 Catalytic Detector The catalytic detector is supplied as a matched pair of elements mounted in a plug-in replaceable housing. One element is an active catalytic detector and the other is a non-active compensating element. Each element consists of a fine platinum wire embedded in a bead of alumina. A catalytic mixture is applied to the detecting element while the compensating element is treated so that catalytic oxidation of gas does not occur. The beads are mounted in a plug-in module that is enclosed by a sintered porous stainless steel flame arrestor. The plug-in sensor module uses gold plated pins and mounts inside the stainless steel sensor head via mating gold plated sockets. Platinum Wire Catalyst Construction of Detector Bead Alumina Bead Beads Sintered Stainless Steel Can Header Gold Plated Pins 1.2 Control Transmitter Circuit The control transmitter is a remote mounted electronic circuit designed and packaged as a plug-in module. The transmitter assembly consists of several circuit functions: input power conditioning, sensor heater control, sensor signal conditioning, sensor fault supervision, and fault LEDs. A metallic face plate with pull ring identifies test points and calibration adjustments. The plug-in module design supports easy field level maintenance and repair. The mating plug is gold plated for maximum resistance to corrosion. BRDG BRIDGE FLT + DET SIGNAL FLT FP-424C COARSE FINE ZERO % LEL 4-20 ma DC VOLT detcon inc. HOUSTON T E X A S 1.3 Terminal Connector Board The terminal connector board is mounted in the explosion proof enclosure and includes: the mating connector for the control circuit, reverse input and secondary transient suppression, input filter and terminals that do not require lugs for all field wiring. Detcon Model FP-424C Combustible Gas Sensor PG.3

4 To Controller Terminals MA 4-20MA + 24VDC BLUE YELLOW BLACK WHITE Sensor 1.4 Explosion Proof Enclosure The transmitter electronics are packaged in a cast aluminum explosion proof enclosure and given a baked epoxy paint finish. The explosion proof enclosure has 3/4 NPT female entry ports. The enclosure is fitted with a threaded cover. Electrical classification is Class I, Div. 1; Groups B, C, D. 1.5 Rain Shield The machine fitted rain shield is designed to help prevent obstruction of the sintered stainless steel flame arrestor as a result of liquid or solid contact. Material of construction is Dupont Delrin. 2.0 PRINCIPLE OF OPERATION In operation, FP-424C series sensor assemblies are installed in industrial areas where early detection of gas leaks is most likely. The sensor is powered by VDC. Air and gas diffuses through the porous sintered flame arrestor and contacts the active and compensating detector elements. Electronically, the detector elements form part of a bridge circuit as shown below. The balance potentiometer is used to set the output of the bridge circuit referenced to zero gas. As the active detector element reacts to the presence of combustible gas and the compensating element does not react, the bridge voltage output changes. This voltage change is conditioned by the transmitter circuit to provide for a linear 4-20 ma DC signal output. As combustible gas dissipates and the sensor is returned to a zero gas environment the bridge circuit returns to a balanced condition. In application, sensor operation is a continuous reading detection/monitoring method. Detcon Model FP-424C Combustible Gas Sensor PG.4

5 2.7V Zero Set Pot R1 R2 Compensator/Reference Detector/Active Output 2.1 Characteristics The detector elements maintain good sensitivity to combustible hydrocarbons in air in the lower explosive limit range, as shown in the response curve illustration below. However, for gas concentrations above the LEL range, the bridge output decreases. Ambiguous readings above LEL range conditions dictate that alarm circuitry be of the latching type wherein alarms are held in the on position until reset by operations personnel. The performance of the detector elements may be temporarily impaired by operation in the presence of substances described as inhibitors. These are usually volatile substances containing halogens and the detectors may recover after short periods of operation in clean air. When the inhibiting substance produces a permanent effect on the catalyst with a catastrophic reduction in sensitivity, the detector is said to be poisoned. Examples of poisons are; silicone oils and greases, anti-knock petrol additives and phosphate esters. Activated carbon filters will provide adequate protection from poisoning in the majority of cases. Note: If it is suspected that the sensor has been poisoned its sensitivity should be verified by recalibrating. 100 RESPONSE CURVE Bridge Output % ma DC Signal Output % Methane in Air Concentration % LEL (lower explosive limit) 3.0 APPLICATION Model FP-424C sensors are designed to detect and monitor combustible gas in ambient air in the range of 0-100% LEL. Minimum sensitivity and scale resolution is 1%. Operating temperature range is -40 F. to 175 F. While the sensor is capable of operating outside these temperatures, performance specifications are verified within the limit. 3.1 Sensor Placement/Mounting Sensor location should be reviewed by facility engineering and safety personnel. Area leak sources and perimeter mounting are typically used to determine number and location of sensors. The sensors are generally located 2-4 feet above grade. 3.2 Response to Different Gases One of the characteristics of the catalytic type combustible gas detectors is their almost universal response to virtually any and all combustible gases. The partial list of detectable gases that appears in our literature includes a list of response K-Factors. These factors are used to determine cross calibration references when detectors are calibrated with other than the target gas. They may also be used to calculate expected readings when a gas other than the target and calibration substance occurs in the area of the sensor. The following formulas apply when converting to either of these occurrences. Detcon Model FP-424C Combustible Gas Sensor PG.5

6 When calibrating with one gas (Cal Gas) and scale sensitivity is required for a different gas (Target Gas) use the following calculation to determine calibration adjustment requirements: Target Gas K-Factor/Cal Gas K-Factor x Cal Gas concentration = Required adjustment level. For example, when calibrating with 50% LEL methane when propane is the target gas: 1.81/1.00 x.5 = 90.5%. The sensor response is lower to propane than it is to methane. We therefore need to adjust scale sensitivity higher when methane is used as the Cal Gas. When a sensor has been calibrated with one gas and another gas occurs in the area of that sensor, the scale response is calculated as: Cal Gas K-Factor/Target Gas K-Factor. For example, when a sensor has been calibrated with methane and propane occurs in the area: 1.00/1.81 = 55%. If 40% LEL propane occurred the sensor output would equal 22.0%. In all cases remember that these K-Factor ratios are theoretical. Actual response may vary from sensor to sensor. Always use the Target Gas as the Cal Gas when possible. TABLE 1a (alphabetical listing) Gas Acetaldehyde Acetic Acid Acetic Anhydride Acetone Acetylene Alkyl Alcohol Ammonia n-amyl Alcohol Aniline Benzene Biphenyl 1,3-Butadiene Butane iso-butane Butene-1 cis-butene-2 trans-butene-2 n-butyl Alcohol iso-butyl Alcohol tert-buty-alcohol n-butyl Benzene iso-butyl Benzene n-butyric Acid Carbon Disulphide Carbon Monoxide Carbon Oxysulphide Cyanogen Cyclohexane Cyclopropane K Gas Decane Diethylamine Dimethylamine 2,3-Dimethylpentane 2,2-Dimethylpropane Dimethylsulphide 1,4-Dioxane Ethane Ethyl Acetate Ethyl Alcohol Ethylamine Ethyl Benzene Ethylcyclopentane Ethylene Ethyleneoxide Diethyl Ether Ethyl Formate Ethylmercaptan n-heptane n-hexane Hydrazine Hydrogencyanide Hydrogen Hydrogen Sulphide Methane Methyl Acetate Methyl Alcohol Methylamine Methylcyclohexane K Gas Dimethyl Ether Methylethylether Methylethylketone Methyl Formate Methylmercaptan Methylpropionate Methyl n-propylketone Naptha Naphthalene Nitromethane n-nonane n-octane n-pentane iso-pentane Propane n-propyl Alcohol n-propylamine Propylene Propyleneoxide iso-propylether Propyne Toluene Triethylamine Trimethylamine Vinyl Chloride Vinylethylether o-xylene m-xylene p-xylene K TABLE 1b (numerical listing) Gas K Gas K Gas K Ammonia 0.79 Methane 1.00 Carbon Oxysulphide 1.07 Cyanogen 1.12 Methyl Alcohol 1.16 Methylamine 1.29 Hydrogen 1.30 Carbon Monoxide 1.32 tert-buty-alcohol 1.34 Ethyl Alcohol 1.37 Ethylene 1.41 Ethane 1.47 Methyl Formate 1.49 Cyclopropane 1.60 Dimethyl Ether 1.60 Methylmercaptan 1.64 Acetaldehyde 1.66 Butane 1.71 Nitromethane 1.72 Dimethylamine 1.73 Acetylene 1.76 Ethylmercaptan ,3-Butadiene 1.79 Propane 1.81 Acetic Acid 1.84 iso-butyl Alcohol 1.89 Ethylamine 1.90 Acetone 1.93 iso-butane 1.93 Ethyleneoxide Ethyl Acetate Methylpropionate Propylene Alkyl Alcohol trans-butene-2 Methyl Acetate Diethylamine cis-butene-2 Trimethylamine n-propylamine Hydrogencyanide n-propyl Alcohol iso-pentane Diethyl Ether Acetic Anhydride n-pentane Propyleneoxide Butene-1 Hydrazine 1,4-Dioxane Ethyl Formate Methylcyclohexane Methylethylether iso-propylether Dimethylsulphide Vinyl Chloride Vinylethylether Propyne Methylethylketone Cyclohexane Benzene Hydrogen Sulphide Methyl n-propylketone Toluene 2,3-Dimethylpentane Triethylamine 2,2-Dimethylpropane Ethylcyclopentane Aniline m-xylene p-xylene n-heptane n-butyric Acid n-octane n-hexane o-xylene Ethyl Benzene n-butyl Alcohol Naphthalene Naptha Decane n-amyl Alcohol iso-butyl Benzene n-butyl Benzene n-nonane Biphenyl Carbon Disulphide Detcon Model FP-424C Combustible Gas Sensor PG.6

7 4.0 SPECIFICATIONS Method of Detection Catalytic detector diffusion/adsorption Measurement Range 0-100% LEL (lower explosive limit) Accuracy/Repeatability ± 3% LEL in 0-50% LEL Range ± 5% LEL in % LEL Range Response/Clearing Time T50 <10 seconds; T90 <30 seconds Zero Drift < 5% per year Operating Temperature Range -40 to +167 F; -40 to +75 C Operating Humidity Range 0-100% RH (non-condensing) Output Linear 4-20 ma DC Input Voltage VDC Power Consumption (maximum) < VDC Electrical Classification Explosion Proof; Class I, Div. 1; Groups B, C, D Safety Approvals CSA/NRTL (US OSHA Certified) Warranty Sensor: 2 year conditional Transmitter: 2 year Field Wiring 3 conductor; max 10 ohms single conductor resistance Max Ohms Between Sensor and Transmitter (in applications where sensor head is remotely mounted) 1/2 ohm 5.0 INSTALLATION Optimum performance of ambient air/gas sensor devices is directly relative to proper application and installation practice. 5.1 Field Wiring Table Detcon Model FP-424C wiring consists of three conductors: + (+24VDC power), (DC common), and MA (4-20 ma DC signal output referenced to DC common). Maximum single conductor resistance between sensor and controller is 10 ohms. Maximum wire size for termination in the sensor assembly terminal connector board is 14 gauge. Note the wiring table below. AWG Meters Feet Note 1: This wiring table is based on stranded tinned copper wire and is designed to serve as a reference only. Note 2: Shielded cable may be required in installations where cable trays or conduit runs include high voltage lines or other sources of induced interference. Note 3: The supply of power must be from an isolating source with over-current protection as follows: AWG Over-current Protection AWG Over-current Protection 22 3A 16 10A 20 5A 14 20A 18 7A 12 25A Detcon Model FP-424C Combustible Gas Sensor PG.7

8 5.2 Remote Mount Considerations If the application requires that the sensor head be remotely mounted away from the transmitter, maximum line resistance should be 1/2 ohm. Use the wiring table below. AWG Maximum Length (feet) Sensor Location Selection of physical sensor location is critical to the overall safe performance of the product. Five factors play an important role in selection of sensor locations: (1) Density of the gas to be detected (2) Most probable leak sources within the industrial process (3) Ventilation or prevailing wind conditions (4) Personnel exposure (5) Maintenance access Density - Placement of sensors relative to the density of the target gas is such that sensors for the detection of heavier than air gases should be located within 2-4 feet of grade as these heavy gases will tend to settle in low lying areas. For gases lighter than air, sensor placement should be 4-8 feet above grade in open areas or in pitched areas of enclosed spaces. Give consideration to easy access by maintenance personnel as well as the consequences of close proximity to contaminants that may foul the sensor prematurely. Leak Sources - Most probable leak sources within an industrial process include flanges, valves, and tubing connections of the sealed type where seals may either fail or wear. Other leak sources are best determined by facility engineers with experience in similar processes. Ventilation - Normal ventilation or prevailing wind conditions can dictate efficient location of gas sensors in a manner where the migration of gas clouds is quickly detected. Personnel Exposure - The undetected migration of gas clouds should not be allowed to approach concentrated personnel areas such as control rooms, maintenance or warehouse buildings. A more general and applicable thought toward selecting sensor location is combining leak source and perimeter protection in the best possible configuration. Note: In all installations, the sensor in stainless steel housing points down relative to grade (Fig. 1). Improper sensor orientation will result in false reading and permanent sensor damage. Figure #1 T Plug any unused ports. Drain EYS Seal Fitting Detcon Model FP-424C Combustible Gas Sensor PG.8

9 5.4 Local Electrical Codes Sensor and transmitter assemblies should be installed in accordance with all local electrical codes. Use appropriate conduit seals. Drains are required at the bottom of vertical conduit runs. The sensor assemblies are designed to meet NEC and CSA requirements for Class I; Groups B, C, D; Div. 1 environments. Note: An appropriate conduit seal must be located within 18" of the sensor assembly. Crouse Hinds type EYS2, EYD2 or equivalent are suitable for this purpose. 5.5 Installation Procedure Note: See section 5.6 for special information on remote mounting applications in which the sensor (Model FP-424C-RS) is remotely mounted away from the transmitter (Model FP-424C-RT). a) Remove the junction box cover and un-plug the control transmitter by pulling it out via the pull ring. b) Securely mount the sensor junction box in accordance with recommended practice. See dimensional drawing (Fig. 2). 4 3/4" 6 1/8" 5 1/2" 3/4" NPT 3/4" NPT 1/4" Dia. Mounting Holes 7 1/4" Figure #2 Rainshield/ Splashguard 2 1/8" 2" c) Terminate 3 conductor field wiring to the sensor terminal connector board observing correct polarity in accordance with the detail shown in figure 3. To Controller Terminals MA MA 24VDC BLUE YELLOW BLACK WHITE Sensor Figure #3 Detcon Model FP-424C Combustible Gas Sensor PG.9

10 d) Replace the plug-in transmitter module and the junction box cover. 5.6 Remote Mounting Applications Some sensor mounting applications require that the gas sensor head be remotely mounted away from the sensor transmitter. This is usually true in instances where the gas sensor head must be mounted in a location that is difficult to access. Such a location creates problems for maintenance and calibration activities. Detcon provides the FP-424C sensor in a remote-mount configuration in which the sensor (Model FP-424C- RS) and the transmitter (Model FP-424C-RT) are provided in their own condulet housing and are interfaced together with a three conductor cable. There is a limit 0.5 ohm maximum resistance drop per wire over the seperation distance.ω Reference figure 4 for wiring diagram. Also note the jumper that is required on the remote sensor terminal Remote Transmitter FP-424C-RT Remote Sensor FP-424C-RS Install Jumper Plug unused port with 3/4 NPT plug. BLU YEL BLK WHT 1234 WHT BLK YEL BLU Figure #4 Measure Bridge Voltage From White (1) to Blue (4) Target voltage is 2.7v connector board. Failure to install this jumper will cause a sensor fault condition. Remote Mounting Configuration - Bridge Voltage Adjustment When a sensor is remotely mounted away from the transmitter, consideration must be given to the lengths of cable used and how it affects the sensor bridge voltage. Differing lengths of cables will have varying amounts of resistance which will shift the sensor bridge voltage. Because of this, the bridge voltage will need to be adjusted after initial power up. This adjustment is only required after initial installation and will not be necessary thereafter, even in the event of replacement of the plug-in sensor. See section 6.1 for instructions. 6.0 START UP Upon completion of all mechanical mounting and termination of all field wiring, apply system power and observe the following normal conditions: a) Detcon electronic controller Fault LED is off. b) A temporary upscale reading will occur as the sensor powers up. 6.1 Remote Mount Bridge Voltage Set If the sensor has been installed using the remote mounting configuration as described in section 5.6, the sensor bridge voltage must be adjusted after initial power up. If this is not the case skip this section and proceed to Initial Operational Tests. Otherwise follow the steps below to set the sensor bridge voltage. Detcon Model FP-424C Combustible Gas Sensor PG.10

11 Material Requirements * Digital volt meter * Jewelers type screwdriver a) Declassify the area around the sensor. b) Remove the junction box cover from the remote sensor enclosure (see figure 4). c) Using the digital volt/ohm meter, measure the bridge voltage at the remote sensor terminal connector board from the White terminal to the Blue terminal as shown in figure 4. Target voltage is 2.7 volts. d) At the transmitter, adjust the VOLT potentiometer (see figure #5) to achieve a reading of 2.7 vdc (±0.2v) at the remote sensor terminal connector board as described in item c above. Figure #5 BRDG BRIDGE FLT + DET SIGNAL FLT FP-424C COARSE FINE ZERO detcon inc. % LEL 4-20 ma DC VOLT HOUSTON T E X A S e) Replace the junction box cover on the remote sensor enclosure. Bridge voltage set is complete. This procedure need only be done once after initial power up. 6.2 Initial Operational Tests After a warm up period has been allowed for, the sensor should be checked to verify sensitivity to gas. Material Requirements * Digital volt meter * Jewelers type screwdriver * Detcon PN Threaded Calibration Adapter * Span Gas 50% LEL methane in air at a controlled flow rate of 200 ml/min. a) Declassify the area around the sensor. b) Remove the junction box cover. c) Measure the voltage between the bridge test points: The bridge voltage is factory set at 2.7V. Use the Temp potentiometer to make adjustments if necessary. (Note: If the sensor head has been remotely installed away from the transmitter, the bridge voltage must be measured at the sensor head instead of the bridge test points. The voltage is measured between the blue and white wires and should be adjusted to 2.7vdc.) d) Measure the voltage between the signal test points: zero gas conditions should provide a reading of between 39 and 40 mv DC. If necessary, adjust the zero potentiometer to achieve this reading. e) If applicable, remove the rain shield or splash guard from the sensor housing. f) Attach the calibration adapter to the threaded sensor housing. Apply the test gas at a controlled flow rate of 200 ml/m. Observe that the signal voltage increases to a level of 80 mv DC or higher. g) Remove the test gas and observe that the signal decreases to between 39 and 40 mv DC. Initial operational tests are complete. Detcon Model series FP-424C sensors are pre-calibrated prior to ship- Detcon Model FP-424C Combustible Gas Sensor PG.11

12 ment and will, in most cases, not require significant adjustment on start up. However, Detcon recommends that a complete calibration test and adjustment be performed within 24 hours of installation. Refer to calibration instructions in later text. 7.0 CALIBRATION PROCEDURE 7.1 Material Requirements * Digital volt meter * Jewelers type screwdriver * Detcon PN Threaded Calibration Adapter * Span Gas 50% LEL methane in air at a controlled flow rate between 200 ml/min. 7.2 Calibration 1) Declassify the area around the sensor. 2) Remove the junction box cover. 3) Measure the voltage between the bridge test points: The bridge voltage is factory set at 2.7V. Use the temp potentiometer to make adjustments if necessary. 4) Measure the voltage between the signal test points: zero gas conditions should provide a reading of between 39 and 40 mv DC. If necessary, adjust the zero potentiometer to achieve this reading. 5) If applicable, remove the rain shield or splash guard from the sensor housing. 6) Attach the calibration adapter to the threaded sensor housing. Apply the test gas at a controlled flow rate of 200 ml/m. Allow 1-2 minutes for signal stability. 7) Measure the voltage between the signal test points. Use the coarse potentiometer to adjust the signal to a reading of 120 mv DC. Use the fine potentiometer to make finer adjustments as needed. 8) Remove the test gas and observe that the signal decreases to between 39 and 40 mv DC. Note: Because there is interaction between the span and zero functions, it may be necessary to repeat steps 4 through 8. Calibration is complete. Replace the rain shield or splash guard and junction box cover. 7.3 Calibration Notes Detcon Model FP-424C series sensors provide a signal output of 4-20 ma DC which corresponds to 0-100% LEL. This signal is reflected by a mv DC voltage across the signal test points. Therefore the signal output will move by.16 ma (or 1.6 mv across the signal test points) for each 1% of movement. If calibration is being done with a gas concentration other than 50% LEL, you can determine the proper signal voltage by dividing 160 mv by 100 and then multiplying that figure by the concentration of gas. For example, if you are calibrating a sensor with a gas standard that contains 10% LEL, you would divide 160 (mv) by 100 (%) and then multiply that figure by 10 (%). Then add the base line of 40 (mv) to arrive at the proper signal voltage of 56 mv. Refer to the chart below for some sample signal outputs with different gas concentrations applied. % LEL Signal Reading 0 40 mv mv mv mv mv mv 7.4 Calibration Frequency In most applications, monthly to quarterly calibration intervals will assure reliable detection. However, industrial environments differ. Upon initial installation and commissioning, close frequency tests should be performed, weekly to monthly. Records should be kept. Less frequent test schedules should be implemented based on analysis of tests prior to adjustment. Detcon Model FP-424C Combustible Gas Sensor PG.12

13 8.0 FAULT SUPERVISION Model FP-424C sensors incorporate fault circuitry which monitors both the detector loop and the bridge voltage of the catalytic bead sensor element. Should one or both of the catalytic bead circuits become electrically open a Detector Fault condition will occur which will result in the illumination of the DET FLT LED located on the transmitter face plate. Should the bridge voltage drop below 1.8 V, a Bridge Fault condition will occur which will result in the illumination of the BRDG FLT LED located on the transmitter face plate. Either fault condition will cause the 4-20 ma signal to drop to 0 ma. When used with Detcon Model 10 or Model 12 controls, this drop in the ma signal will result in a fault condition on the affected control module creating a dual redundant fault function. 9.0 TROUBLE SHOOTING GUIDE Detector Fault 1. Open Sensor broken wire or contact in sensor. 2. Remove replaceable sensor element and check adjacent pin pairs with ohm-meter. Normal reading is 1-4 ohms and failed reading is an open circuit. 3. Replace sensor if verified as Open Sensor. Bridge Fault 1. Shorted detector bead, shorted transmitter, or faulty transmitter. 2. Make sure that there is no presence of condensation or accumulated water in the sensor housing or condulet. This could cause possible shorting. 3. Swap in new transmitter and/or new sensor. Poor Sensor Performance (Slow Response, Drifting Sensor) 1. Check that correct Heater Voltage is applied to your sensor. Note: Detcon has two version sensors: C-Style and the J-Style. Each uses a different heater voltage setting. The C-Style sensor measures 0.9'' across the exposed stainless steel sinter face and has a serial number format C??-###. The C-Style sensor requires 2.7 VDC The J-Style sensor measures 0.4 across the exposed stainless steel sinter face and has a serial number format J??-###. The J- Style sensor requires 2.2 VDC. 2. If heater voltage is incorrect then adjust it accordingly for the sensor type. Excessive Span Drift or Slow Response 1. Check Heater Voltage Setting (should be 2.7V C-Style and 2.2V J-Style) and check heater voltage at the sensor if remote mounted. 2. Verify correct cal gas flow rate and proper use of the cal gas adapter. 3. Check validity of cal gas via the expiration date and use pull tube if necessary. 4. Check for obstructions through stainless steel sinter element (including being wet). 5. Replace plug-in sensor if necessary. 6. Check area for presence of sensor poisoning gases such as silicon grease vapors, HMDS, high H2S, chlorine or chlorinated compounds if sensor failures persist. Drifting Zero 1. May be correct reading if there are real gas leaks or the sensor was zero calibrated when actual gas was around and subsequently cleared. 2. Check Heater voltage is set correctly for sensor type (check voltage at the sensor if remote mounted). 3. Replace sensor if sensor has experienced large span losses that exaggerate zero drift. 4. If sensor drift is gradual and continuously positive (with a stable span) then contact Detcon for sensor replacement. Detcon Model FP-424C Combustible Gas Sensor PG.13

14 Unstable Output/ Sudden Spiking/Nuisance Alarms 1. Check condulet for accumulated water. 2. Check transmitter and Terminal PCB for abnormal corrosion. 3. Determine if problem correlates with condensation cycles. 4. Add/change Detcon condensation prevention packet PN (replace annually). 5. Check for unstable power supply. 6. Check for inadequate grounding. 7. If correlates with radio communications then use Detcon RFI filter accessory. 8. Contact Detcon for assistance in optimizing shielding, grounding, and RFI protection. Transmitter not Responding 1. Verify condulet has no accumulated water or abnormal corrosion. 2. Verify required DC power is applied to correct terminals. 3. Swap with a known-good transmitter to determine if transmitter is faulty. Bad 4-20 ma output 1. Check that wiring is connected to correct terminal outputs. 2. Swap with a known-good transmitter to determine if transmitter is faulty SPARE PARTS LIST Sensor rain shield Sensor splash guard Threaded Calibration Adapter LEL sensor housing assembly (plug-in detector, PN , not included) Sensor: field replaceable plug in detector Terminal Connector Board NEMA 7 enclosure less cover - 3 port NEMA 7 enclosure cover Condensation prevention packet (replace annually) FP424C Plug-in control circuit Enclosure Cover Rain Shield Calibration Adapter FP-424C Transmitter Assembly Sensor Terminal Board LEL Main Sensor Housing Assembly Condensation Prevention Packet (replace annually) Enclosure Sensor: field replaceable plug-in detector Detcon Model FP-424C Combustible Gas Sensor PG.14

15 11.0 WARRANTY Detcon, Inc., as manufacturer, warrants each new LEL plug-in detector (PN ), for a two year period under the conditions described as follows: The warranty period begins on the date of shipment to the original purchaser and ends two years thereafter. The sensor element is warranted to be free from defects in material and workmanship. Should any sensor fail to perform in accordance with published specifications within the warranty period, return the defective part to Detcon, Inc., 3200 Research Forest Dr., Suite A-1, The Woodlands, Texas 77381, for necessary repairs or replacement SERVICE POLICY Detcon, Inc., as manufacturer, warrants under intended normal use each new sensor signal transmitter to be free from defects in material and workmanship for a period of two years from the date of shipment to the original purchaser. Detcon, Inc., further provides for a five year fixed fee service policy wherein any failed transmitter shall be repaired or replaced as is deemed necessary by Detcon, Inc., for a fixed fee of $ The fixed fee service policy shall effect any factory repair for the period following the two year warranty and shall end five years after expiration of the warranty. All warranties and service policies are FOB the Detcon facility located in The Woodlands, Texas. Shipping Address: 3200 Research Forest Dr., Suite A-1, The Woodlands, Texas Mailing Address: P.O. Box 8067, The Woodlands, Texas phone , fax sales@detcon.com Detcon Model FP-424C Combustible Gas Sensor PG.15

Detcon MicroSafe. FP-624HT Combustible Gas Sensor (0-100% LEL) Specialized Version For High Temperature Operation of Sensor Head

Detcon MicroSafe. FP-624HT Combustible Gas Sensor (0-100% LEL) Specialized Version For High Temperature Operation of Sensor Head detcon inc. Detcon MicroSafe FP-624HT Combustible Gas Sensor (0-100% LEL) Specialized Version For High Temperature Operation of Sensor Head Operator s Installation & Instruction Manual May 18, 2010 Document

More information

INSTRUCTION MANUAL Detcon Model FP-524D

INSTRUCTION MANUAL Detcon Model FP-524D INSTRUCTION MANUAL Detcon PGM 1 MODEL HOUSTON, TEXAS FP-524D MicroSafe TM LEL Gas Sensor ALM ALM FLT 1 2 CAL PGM 2 FP-524D Combustible Gas Sensor (0 100% LEL) DETCON, Inc. 4055 Technology Forest Blvd,

More information

INSTRUCTION MANUAL Detcon Model FP-524D-HRT

INSTRUCTION MANUAL Detcon Model FP-524D-HRT INSTRUCTION MANUAL Detcon Model FP-524D-HRT PGM 1 HOUSTON, TEXAS TM MicroSafe LEL Gas Sensor ALM ALM FLT 1 2 CAL PGM 2 FP-524D-HRT Combustible Gas Sensor (0 100% LEL) with HRT Bridge DETCON, Inc. 4055

More information

INSTRUCTION MANUAL Detcon Model FP-700

INSTRUCTION MANUAL Detcon Model FP-700 INSTRUCTION MANUAL Detcon Model FP-700 FP-700 Combustible Gas Sensor 0-100% LEL 0-50% LEL February 28, 2014 Document #3168 Revision 3.0 DETCON, Inc. 4055 Technology Forest Blvd., The Woodlands, Texas 77381

More information

Operation and Maintenance Manual

Operation and Maintenance Manual Operation and Maintenance Manual GDS-48 Remote Bridge Sensor for Combustible Gases AUTHORIZED DISTRIBUTOR: GasDetectorsUSA.com - Houston, Texas USA sales@gasdetectorsusa.com - 832-615-3588 CAUTION: FOR

More information

Model C Combustible Gas Transmitter. 6 Iron Bridge Drive Unit 1 & 2 Gatehead Business Park

Model C Combustible Gas Transmitter. 6 Iron Bridge Drive Unit 1 & 2 Gatehead Business Park Model C12-17 Combustible Gas Transmitter Home Office European Office Analytical Technology, Inc. ATI (UK) Limited 6 Iron Bridge Drive Unit 1 & 2 Gatehead Business Park Collegeville, PA 19426 Delph New

More information

700 FP Series. Instruction Manual. Combustible Gas Detector OLCT 700 OLCT 710. The Fixed Gas Detection Experts The Fixed Gas Detection Experts

700 FP Series. Instruction Manual. Combustible Gas Detector OLCT 700 OLCT 710. The Fixed Gas Detection Experts The Fixed Gas Detection Experts Instruction Manual 700 FP Series Combustible Gas Detector OLCT 700 OLCT 710 Part Number: NP700FPIMEN Revision: C.0 The Fixed Gas Detection Experts The Fixed Gas Detection Experts OLCT 700/710 FP Instruction

More information

GG-LEL2 COMBUSTIBLE GAS SENSOR. Installation and Operation Manual

GG-LEL2 COMBUSTIBLE GAS SENSOR. Installation and Operation Manual GG-LEL2 COMBUSTIBLE GAS SENSOR Installation and Operation Manual 2 GG-LEL2 Warning Use this product only in the manner described in this manual. If the equipment is used in a manner not specified by Calibration

More information

INSTRUCTION MANUAL Detcon Model IR-700

INSTRUCTION MANUAL Detcon Model IR-700 INSTRUCTION MANUAL Detcon IR700 Combustible Gas Sensor This manual covers the 0-100% LEL range IR-700 CO 2 Carbon Dioxide Gas Sensor This manual covers all ranges of the IR-700 CO 2 Sensor DETCON, Inc.

More information

Operation and Maintenance Manual

Operation and Maintenance Manual Operation and Maintenance Manual GDS-IR Infrared Sensor for Combustible Gases & CO 2 GDS Corp. 2513 Hwy 646 Santa Fe, Texas 77510 409-927-2980 409-927-4180 (Fax) www.gdscorp.com CAUTION: FOR SAFETY REASONS

More information

Detcon MicroSafe Model DM-634C Oxygen Deficiency Sensor (0-25% O2)

Detcon MicroSafe Model DM-634C Oxygen Deficiency Sensor (0-25% O2) Detcon MicroSafe Model DM-634C Oxygen Deficiency Sensor (0-25% O2) Operator s Installation and Instruction Manual DETCON, Inc. 4055 Technology Forest Blvd, Suite 100, The Woodlands, Texas 77381 Ph.281.367.4100

More information

4P-90 CiTipeL Combustible Gas Sensor Part Number: PM

4P-90 CiTipeL Combustible Gas Sensor Part Number: PM Key Features & Benefits: ATEX, UL and CSA Approvals Withstands EN/IEC 60079-0 impact test Enhanced H 2 S and silicone poison resistance 4P-90 CiTipeL Combustible Gas Sensor Part Number: PM143-000 Performance

More information

DESIGN MANUAL MODEL GIR900 INFRARED COMBUSTIBLE GAS SENSOR

DESIGN MANUAL MODEL GIR900 INFRARED COMBUSTIBLE GAS SENSOR DESIGN MANUAL MODEL GIR900 INFRARED COMBUSTIBLE GAS SENSOR 70086 The information in this doucment is applicable to sensors built in September, 2008 or later (Firmware 3.0) The information and technical

More information

GASGUARD LEL 3 OPERATING & INSTALLATION MANUAL

GASGUARD LEL 3 OPERATING & INSTALLATION MANUAL GASGUARD LEL 3 Ammonia Sensor OPERATING & INSTALLATION MANUAL GasGuard LEL 3 Operating and Installation Manual 2 Table of Contents 3GasGuard LEL Operating and Instruction Manual General description. 4

More information

INSTRUCTION MANUAL Detcon Model FP-700

INSTRUCTION MANUAL Detcon Model FP-700 INSTRUCTION MANUAL Detcon FP-700 Combustible Gas Sensor 0-100% LEL 0-50% LEL DETCON, Inc. 4055 Technology Forest Blvd., The Woodlands, Texas 77381 Ph.281.367.4100 / Fax 281.298.2868 www.detcon.com June

More information

4P75 CiTipeL Combustible Gas Sensor Part Number: PM

4P75 CiTipeL Combustible Gas Sensor Part Number: PM Product Datasheet 4P75 Document Purpose The purpose of this document is to present the performance specification of the 4P75 CiTipeL. This document should be used in conjunction with Operating Principles

More information

RK-05 Combustible Gas Transmitter Operator s Manual

RK-05 Combustible Gas Transmitter Operator s Manual 65-2405RK-05 Combustible Gas Transmitter Operator s Manual Part Number: 71-0180RK Revision: 0 Released: 2/16/11 RKI Instruments, Inc. www.rkiinstruments.com WARNING Read and understand this instruction

More information

ESD3000 ESD200 Combustible / Toxic Gas Detector

ESD3000 ESD200 Combustible / Toxic Gas Detector ESD3000 ESD200 Combustible / Toxic Gas Detector Combustible and toxic gas leakage inspection instrument in industrial application Ex-proof certificate Exd ⅡC T6 Gb/Ex d ib ⅡC T6 Gb Dust Ex-proof certificate

More information

MICROpeL 75 Combustible Gas Sensor Part Number: PM

MICROpeL 75 Combustible Gas Sensor Part Number: PM MICROpeL 75 Combustible Gas Sensor Part Number: PM759-000 Key Features & Benefits: ATEX, UL and CSA Approvals Withstands EN/IEC 60079-0 impact test Enhanced H 2 S and silicone poison resistance Reduced

More information

Detcon MicroSafe. IR-640 Carbon Dioxide Sensor (0-5%CO2) IR642 Carbon Dioxide Sensor (10%-100%) Operator s Installation & Instruction Manual

Detcon MicroSafe. IR-640 Carbon Dioxide Sensor (0-5%CO2) IR642 Carbon Dioxide Sensor (10%-100%) Operator s Installation & Instruction Manual detcon inc. Detcon MicroSafe IR-640 Carbon Dioxide Sensor (0-5%CO2) IR642 Carbon Dioxide Sensor (10%-100%) Operator s Installation & Instruction Manual November 26, 2007 Document #2196 Version 6.4 CAUTION:

More information

ULTIMA XIR ULTIMA X 3 ULTIMA XE. ULTIMA X Series. [ State-of-the-Art Gas Monitoring]

ULTIMA XIR ULTIMA X 3 ULTIMA XE. ULTIMA X Series. [ State-of-the-Art Gas Monitoring] ULTIMA XIR ULTIMA X 3 ULTIMA XE ULTIMA X Series [ State-of-the-Art Gas Monitoring] ULTIMA X Gas Monitors [ Providing a unique Range of Capabilities] ULTIMA X are state-of-the-art gas monitors for continuous

More information

GAS PLUS ALARM SYSTEM

GAS PLUS ALARM SYSTEM GAS PLUS -IR SERIES 4688-IR COMBUSTIBLE GAS OR CARBON DIOXIDE TRANSMITTER GAS PLUS -IR TRANSMITTER SERIES 4688-IR COMBUSTIBLE GAS OR CARBON DIOXIDE TRANSMITTER The Scott Gas Plus -IR Model 4688 IR Gas

More information

Model D12-IR. Digital Gas Transmitter...

Model D12-IR. Digital Gas Transmitter... Model D12-IR Digital Gas Transmitter... ATI s Series D12 gas transmitter line now includes a versatile Infrared system that can be configured for LEL or select toxic gases. The D12-IR utilizes a compact

More information

ESD3000IR ESD3000IR. Infrared Gas Detector

ESD3000IR ESD3000IR. Infrared Gas Detector ESD3000IR ESD3000IR Infrared Gas Detector Infrared gas sensor Ex-proof certificate Exd ⅡC T6 Gb Dust Ex-proof certificate Ex td A21 IP66 T80 Site LCD display HART communication Replaceable sensor design

More information

RK Combustible Gas Transmitter Operator s Manual

RK Combustible Gas Transmitter Operator s Manual 65-2400RK Combustible Gas Transmitter Operator s Manual Part Number: 71-0060RK Revision: C Released: 1/31/13 www.rkiinstruments.com WARNING Read and understand this instruction manual before operating

More information

G.O.L.D. GAS OPERATIONS LEAK DETECTION USER MANUAL

G.O.L.D. GAS OPERATIONS LEAK DETECTION USER MANUAL G.O.L.D. GAS OPERATIONS LEAK DETECTION USER MANUAL Part Number: MAN-0045-00 Rev1 August 2003 Copyright 2003 Net Safety Monitoring Inc. Printed in Canada This manual is provided for informational purposes

More information

Explosion-proof Duct Heaters

Explosion-proof Duct Heaters Safety INDEECO explosion-proof ULTRA-SAFE and EP2 duct heaters are Factory Mutual (FM) and CSA Approved. The ULTRA-SAFE duct heater has the only standard product offering and features the industry s lowest

More information

ESD500. ESD500 Combustible / Toxic Gas Detector

ESD500. ESD500 Combustible / Toxic Gas Detector ESD500 ESD500 Combustible / Toxic Gas Detector Combustible and toxic gas leakage inspection instrument in industrial application Ex-proof certificate Exd ⅡC T6 Gb/Ex d ib ⅡC T6 Gb Dust Ex-proof certificate

More information

Tox-COMB/ANA Combustible Gas Transmitter Operator s Manual

Tox-COMB/ANA Combustible Gas Transmitter Operator s Manual Tox-COMB/ANA Combustible Gas Transmitter Operator s Manual Part Number: 71-0132TA Revision: A Released: 4/23/10 www.toxalert.com Product Warranty Toxalert International, Inc. warrants gas alarm equipment

More information

GASGUARD H 2-1% Hydrogen Sensor OPERATING & INSTALLATION MANUAL

GASGUARD H 2-1% Hydrogen Sensor OPERATING & INSTALLATION MANUAL GASGUARD H 2-1% Hydrogen Sensor OPERATING & INSTALLATION MANUAL 2 Table of Contents GasGuard H 2-1% General description. 4 Installation.. 4 Locating the sensor. 4 Installation guidelines 5 Wiring.. 6 Operation..

More information

INSTRUCTION MANUAL Detcon Model IR-700

INSTRUCTION MANUAL Detcon Model IR-700 INSTRUCTION MANUAL Detcon IR-700 Combustible Gas Sensor 0-100% LEL and 0-50% LEL range IR-700 CO 2 Carbon Dioxide Gas Sensor All Ranges DETCON, Inc. 4055 Technology Forest Blvd., The Woodlands, Texas 77381

More information

RK Transmitter Technical Notice

RK Transmitter Technical Notice 65-2450RK Transmitter Technical Notice Although this Operator s Manual was written for the 65-2400RK combustible gas LEL transmitter, the operational instructions are the same for the 65-2450RK hydrogen

More information

GASGUARD NH 3 2% Ammonia Sensor OPERATING & INSTALLATION MANUAL

GASGUARD NH 3 2% Ammonia Sensor OPERATING & INSTALLATION MANUAL GASGUARD NH 3 2% Ammonia Sensor OPERATING & INSTALLATION MANUAL 2 Table of Contents GasGuard NH 3 2% General description. 4 Installation.. 4 Locating the sensor. 4 Installation guidelines 5 Wiring.. 6

More information

Electron Microscopy Sciences

Electron Microscopy Sciences Electron Microscopy Sciences INSTRUCTIONAL MANUAL CAT. 72341-10 Explosion Proof Hot Plate Stirrer Model SF87325 P.O. Box 550 s1560 Industry Road s Hatfield PA 19440 1 Safety Symbols Used in this Instruction

More information

INSTRUCTION MANUAL Detcon Model TP-524D-HRT

INSTRUCTION MANUAL Detcon Model TP-524D-HRT INSTRUCTION MANUAL Detcon Model TP-524D-HRT PGM 1 MODEL HOUSTON, TEXAS TP-524D MicroSafe TM H2S Gas Sensor ALM ALM FLT 1 2 CAL PGM 2 TP-524D-HRT Hydrogen Sulfide Sensor This manual covers the following

More information

User Manual. PolyGard AT-3300 V3. Transmitter for Combustible Gases. Serial No. ET April 2009

User Manual. PolyGard AT-3300 V3. Transmitter for Combustible Gases. Serial No. ET April 2009 PolyGard AT-3300 V3 Transmitter for Combustible Gases Serial No. ET03-002 User Manual April 2009 January 04, 2016 Revision Specifications subject to change without notice. USA 151203 Page 2 of 14 1 Intended

More information

INSTRUCTION MANUAL Detcon Model TP-624D

INSTRUCTION MANUAL Detcon Model TP-624D INSTRUCTION MANUAL Detcon PGM 1 MODEL HOUSTON, TEXAS TP-624D MicroSafe TM H2S Gas Sensor ALM ALM FLT 1 2 CAL PGM 2 TP-624D Hydrogen Sulfide Sensor This manual covers the following ranges: 0-20ppm, 0-50ppm,

More information

Model 100 Duct Mount Kit

Model 100 Duct Mount Kit D ETCON, INC. Model 100 Duct Mount Kit Model 100 DM-100 H2S 100 PPM CAL PORT Operator s Installation and Instruction Manual Covers all versions of the 100 Series Sensor DETCON, Inc. 4055 Technology Forest

More information

RK Multi Point Detector Operator s Manual

RK Multi Point Detector Operator s Manual 65-2480RK Multi Point Detector Operator s Manual Part Number: 71-0198RK Revision: C Released: 11/26/14 RKI Instruments, Inc. www.rkiinstruments.com WARNING Read and understand this instruction manual before

More information

INSTRUCTION MANUAL Detcon Model TP-624D

INSTRUCTION MANUAL Detcon Model TP-624D INSTRUCTION MANUAL Detcon PGM 1 MODEL HOUSTON, TEXAS TP-624D MicroSafe TM H2S Gas Sensor ALM ALM FLT 1 2 CAL PGM 2 TP-624D Hydrogen Sulfide Sensor This manual covers the following ranges: 0-20ppm, 0-50ppm,

More information

APPLICATION DATA SHEET

APPLICATION DATA SHEET APPLICATION DATA SHEET S p e c i f i c a t i o n WWW.-..UK Control Systems Transmitters Sensors Accessories TOCSIN 700 D e t e c t o r C o n t r o l P a n e l Wall mounting 24V DC or 110/230vAC operation

More information

700 IR Series. Instruction Manual. Infrared Gas Detector for Combustible and CO 2 gases OLCT 700 OLCT 710. The Fixed Gas Detection Experts

700 IR Series. Instruction Manual. Infrared Gas Detector for Combustible and CO 2 gases OLCT 700 OLCT 710. The Fixed Gas Detection Experts Instruction Manual 700 IR Series Infrared Gas Detector for Combustible and CO 2 gases OLCT 700 OLCT 710 Part Number: NP700IRIMEN Revision: B.1 The Fixed Gas Detection Experts Copyright Jan 2016 by Oldham

More information

Model 1000 H 2 S E-Chem/ CO 2 Process Analyzer

Model 1000 H 2 S E-Chem/ CO 2 Process Analyzer 24VDC OUT 2.1A 18-36 VDC IN Model 1000 H 2 S E-Chem/ CO 2 Process Analyzer + + SAMPLE FLOW AIR FLOW SAMPLE FLOW Operator s Installation and Instruction Manual Detcon Model 1000 H 2 S/CO 2 Analyzer consists

More information

MERIDIAN UNIVERSAL GAS DETECTOR

MERIDIAN UNIVERSAL GAS DETECTOR MERIDIAN UNIVERSAL GAS DETECTOR MERIDIAN UNIVERSAL GAS DETECTOR The term universal is frequently used in the industry to characterize gas detectors that address both toxic and combustible gases, but it

More information

Intelligent combined sensor for Air Quality (VOC) + Humidity (rh) + Temperature (T) with analogue outputs, Modbus and LCD display. Features.

Intelligent combined sensor for Air Quality (VOC) + Humidity (rh) + Temperature (T) with analogue outputs, Modbus and LCD display. Features. Features To measure and take control of indoor air quality Three noses in same unit Air Quality (VOC), Humidity (rh) and Temperature (T) Selectable outputs 0-10 Vdc, 4-20 ma or 0-5 Vdc via jumpers on pcb

More information

GG-NH3-2% AMMONIA GAS SENSOR. Installation and Operation Manual

GG-NH3-2% AMMONIA GAS SENSOR. Installation and Operation Manual GG-NH3-2% AMMONIA GAS SENSOR Installation and Operation Manual 2 GG-NH3-2% Warning Use this product only in the manner described in this manual. If the equipment is used in a manner not specified by Calibration

More information

Dräger Polytron SE Ex Fixed Gas Detector

Dräger Polytron SE Ex Fixed Gas Detector Dräger Polytron SE Ex Fixed Gas Detector The Dräger Polytron SE Ex... DD sensing heads are gas detectors for the continuous monitoring of flammable gases and vapors in the ambient air. The measurement

More information

RK-05 Carbon Monoxide Transmitter Operator s Manual

RK-05 Carbon Monoxide Transmitter Operator s Manual 65-2432RK-05 Carbon Monoxide Transmitter Operator s Manual Part Number: 71-0113RK Revision: B Released: 11/26/14 www.rkiinstruments.com WARNING Read and understand this instruction manual before operating

More information

P R O D U C T S P E C I F I C A T I O N MSA Ultima X Series Sensor/Transmitter Specification

P R O D U C T S P E C I F I C A T I O N MSA Ultima X Series Sensor/Transmitter Specification P R O D U C T S P E C I F I C A T I O N MSA Ultima X Series Sensor/Transmitter Specification 1.0 This specification details the attributes and operating characteristics of the MSA Ultima X Series sensors/transmitters.

More information

INSTRUCTION MANUAL Detcon Model DM-700

INSTRUCTION MANUAL Detcon Model DM-700 INSTRUCTION MANUAL Detcon DM-700 Toxic Gas Sensors DM-700 O 2 Deficiency Sensors This manual covers all ranges of electrochemical and O 2 deficiency sensors offered in the Detcon Product Line DETCON, Inc.

More information

Meridian. Universal Gas Detector. Description. Features. Minimal drift High specificity Digital ID Broader toxic gas detection

Meridian. Universal Gas Detector. Description. Features. Minimal drift High specificity Digital ID Broader toxic gas detection 3M TM Meridian Description Designed with safety and reliability in mind, the Meridian universal gas detector is suitable for use in SIL-2 and SIL-3-rated systems under the IEC 61508 standards, certified

More information

Explosion Proof Speaker, Ringer & Speaker/Ringer

Explosion Proof Speaker, Ringer & Speaker/Ringer Explosion Proof Speaker, Ringer & Speaker/Ringer Models SR40 and SR60 Installation & Operation P004562 Rev. G 150831 8/31/2015 11:06 AM Ph: 403.258.3100 \ email:info@guardiantelecom.com \ www.guardiantelecom.com

More information

Thank You for Attending Today s Webinar:

Thank You for Attending Today s Webinar: Detect, Measure, Analyze. Thank You for Attending Today s Webinar: Best Practices in Maintaining Gas Detection Systems Featured Speaker John Greivell VP Operations RAECO-LIC LLC johng@raeco.com Featured

More information

TECHNICAL NOTE. Response Factors for Flame Ionization Detector Operation FLAME IONIZATION DETECTOR OPERATION BASICS

TECHNICAL NOTE. Response Factors for Flame Ionization Detector Operation FLAME IONIZATION DETECTOR OPERATION BASICS TECHNICAL NOTE s for Flame Ionization Detector Operation FLAME IONIZATION DETECTOR OPERATION BASICS The DataFID and MicroFID II are portable flame ionization detectors designed to monitor volatile organic

More information

MODELS: Basic, Standard and Premium UNI-TRAN COMBUSTIBLE GAS TRANSMITTER UT-X-SC1100

MODELS: Basic, Standard and Premium UNI-TRAN COMBUSTIBLE GAS TRANSMITTER UT-X-SC1100 MODELS: Basic, Standard and Premium UNI-TRAN COMBUSTIBLE GAS TRANSMITTER UT-X-SC1100 Part Number: MAN-0013-00 Rev 2 Copyright 2003 Net Safety Monitoring Inc. Printed in Canada This manual is provided for

More information

MODEL GC802 NOVA-SENSOR ELITE COMBUSTIBLE GAS DETECTOR

MODEL GC802 NOVA-SENSOR ELITE COMBUSTIBLE GAS DETECTOR DESIGN MANUAL INSTALLATION -- OPERATION -- MAINTENANCE SERVICE MANUAL MODEL GC802 NOVA-SENSOR ELITE COMBUSTIBLE GAS DETECTOR 70098 The information and technical data disclosed by this document may be used

More information

RK Hydrogen Sulfide Transmitter Operator s Manual

RK Hydrogen Sulfide Transmitter Operator s Manual 65-2331RK Hydrogen Sulfide Transmitter Operator s Manual Part Number: 71-0176RK Revision: B Released: 11/26/14 RKI Instruments, Inc. www.rkiinstruments.com WARNING Read and understand this instruction

More information

GASGUARD H2S EXP. Hydrogen Sulfide Sensor OPERATING & INSTALLATION MANUAL

GASGUARD H2S EXP. Hydrogen Sulfide Sensor OPERATING & INSTALLATION MANUAL GASGUARD H2S EXP Hydrogen Sulfide Sensor OPERATING & INSTALLATION MANUAL Operating and Installation Manual Warning Use this product only in the manner described in this manual. If the equipment is used

More information

RK-CH4-4 Combustible Gas Transmitter Operator s Manual

RK-CH4-4 Combustible Gas Transmitter Operator s Manual 65-2394RK-CH4-4 Combustible Gas Transmitter Operator s Manual Part Number: 71-0277RK Revision: P1 Released: 4/9/13 RKI Instruments, Inc. www.rkiinstruments.com WARNING Read and understand this instruction

More information

FLAMMABLE GAS DETECTOR DAX 3F-C INSTALLATION, OPERATING AND MAINTENANCE INSTRUCTIONS. DAX3FC_MAN01_EN.indd Ver. V1R2

FLAMMABLE GAS DETECTOR DAX 3F-C INSTALLATION, OPERATING AND MAINTENANCE INSTRUCTIONS. DAX3FC_MAN01_EN.indd Ver. V1R2 FLAMMABLE GAS DETECTOR INSTALLATION, OPERATING AND MAINTENANCE INSTRUCTIONS DAX3FC_MAN01_EN.indd Ver. V1R2 Introduction These instructions must be read carefully by any person who has or will have the

More information

Product Selection Guide Fixed Gas Detection Systems for Personnel & Equipment Safety

Product Selection Guide Fixed Gas Detection Systems for Personnel & Equipment Safety Product Selection Guide Fixed Gas Detection Systems for Personnel & Equipment Safety GDS Corp gas monitors, controllers and sensors satisfy today s needs for safety and reliability in critical gas detection

More information

RK Carbon Monoxide Transmitter Operator s Manual

RK Carbon Monoxide Transmitter Operator s Manual 65-2432RK Carbon Monoxide Transmitter Operator s Manual Part Number: 71-0070RK Revision: P1 Released: July 8, 2001 RKI Instruments, Inc. 1855 Whipple Road Hayward CA 94544 Phone: 800-754-5165 Fax: 510-441-5650

More information

GG-H2S HYDROGEN SULFIDE GAS SENSOR. Installation and Operation Manual

GG-H2S HYDROGEN SULFIDE GAS SENSOR. Installation and Operation Manual GG-H2S HYDROGEN SULFIDE GAS SENSOR Installation and Operation Manual 2 GG-H2S Warning Use this product only in the manner described in this manual. If the equipment is used in a manner not specified by

More information

GASGUARD Cl 2. Chlorine Sensor OPERATING & INSTALLATION MANUAL

GASGUARD Cl 2. Chlorine Sensor OPERATING & INSTALLATION MANUAL GASGUARD Cl 2 Chlorine Sensor OPERATING & INSTALLATION MANUAL Operating and Installation Manual 2 Table of Contents GasGuard Cl 2 Operating and Instruction Manual General description. 4 Installation..

More information

Type SP87300 SAFE-T SHP9 Explosion Proof Stirring Hot Plate

Type SP87300 SAFE-T SHP9 Explosion Proof Stirring Hot Plate Type SP87300 SAFE-T SHP9 Explosion Proof Stirring Hot Plate OPERATION MANUAL SERIES 873 UL Listed for Class I, Group C and D Hazardous Locations Model # Voltage Description SP87325 120 9.13 X 9.13 (23.2

More information

Dräger PEX 3000 Flammable Gas Detection

Dräger PEX 3000 Flammable Gas Detection Dräger PEX 3000 Flammable Gas Detection The transmitter Dräger PEX 3000 detects flammable gases and vapors in concentrations below their Lower Explosion Limit Its DD-sensor provides a very long-term stable

More information

MODEL: O ELECTROCHEMICAL O2 DETECTOR (Used with ST1400 O2 Sensor) Part Number: MAN Rev. 0

MODEL: O ELECTROCHEMICAL O2 DETECTOR (Used with ST1400 O2 Sensor) Part Number: MAN Rev. 0 MODEL: O2-25-24 ASSEMBLY CONSISTS OF: XP-O2 housing (supersedes PE-EX-O2) ST1400-500-24 sensor (supersedes PE1400-500-24) JB2 junction box CB2 connector board ELECTROCHEMICAL O2 DETECTOR (Used with ST1400

More information

5New features & EXtreme design, now with HART Protocol and DuraSource Technology. Ultima X Series Gas Monitors

5New features & EXtreme design, now with HART Protocol and DuraSource Technology. Ultima X Series Gas Monitors Ultima X Series Gas Monitors Versatile fixed instruments provide continuous monitoring of many hazardous gases using catalytic, electrochemical, and infrared gas detection methods. HART Protocol is now

More information

SAFETY CERTIFIED MODEL FP-700 COMBUSTIBLE GAS DETECTOR

SAFETY CERTIFIED MODEL FP-700 COMBUSTIBLE GAS DETECTOR SAFETY MANUAL SIL 2 Certified Model FP-700 Combustible Hydrocarbon Gas Sensor Version 2.0 1 SAFETY CERTIFIED MODEL FP-700 COMBUSTIBLE GAS DETECTOR This manual addresses the specific requirements and recommendations

More information

SIL 2. Ultima X Series Gas Monitors CERTIFIED

SIL 2. Ultima X Series Gas Monitors CERTIFIED Ultima X Series Gas Monitors 5 Now with SIL 2 CERTIFIED Products Versatile fixed instruments provide continuous monitoring of many hazardous gases using catalytic, electrochemical, and infrared gas detection

More information

STAINLESS STEEL FLAMMABLE GAS DETECTOR DAX 3F-I INSTALLATION, OPERATING AND MAINTENANCE INSTRUCTIONS. DAX3FI_MAN01_EN Ver. V1R2

STAINLESS STEEL FLAMMABLE GAS DETECTOR DAX 3F-I INSTALLATION, OPERATING AND MAINTENANCE INSTRUCTIONS. DAX3FI_MAN01_EN Ver. V1R2 STAINLESS STEEL FLAMMABLE GAS DETECTOR INSTALLATION, OPERATING AND MAINTENANCE INSTRUCTIONS DAX3FI_MAN01_EN Ver. V1R2 1 Introduction These instructions must be read carefully by any person who has or will

More information

SBS-H2 Hydrogen Gas Detector Kit

SBS-H2 Hydrogen Gas Detector Kit SBS-H2 Hydrogen Gas Detector Kit For battery charging rooms and other areas where hydrogen gas may be present INSTALLATION, OPERATION & MAINTENANCE INSTRUCTIONS Protects Life, Property and Profits Electrical

More information

99 Washington Street Melrose, MA Phone Toll Free Visit us at

99 Washington Street Melrose, MA Phone Toll Free Visit us at 99 Washington Street Melrose, MA 02176 Phone 781-665-1400 Toll Free 1-800-517-8431 Visit us at www.testequipmentdepot.com Combustible Gas Leak Detector Instruction and Operation Manual Page 2 Detector

More information

GG-CO-EXP CARBON MONOXIDE SENSOR. Installation and Operation Manual

GG-CO-EXP CARBON MONOXIDE SENSOR. Installation and Operation Manual GG-CO-EXP CARBON MONOXIDE SENSOR Installation and Operation Manual 2 GG-CO-EXP Warning Use this product only in the manner described in this manual. If the equipment is used in a manner not specified by

More information

User Manual. PolyGard CO LC-1112 V3. Electrochemical analog carbon monoxide transmitters serial no. EC-S 002. August 29, 2006

User Manual. PolyGard CO LC-1112 V3. Electrochemical analog carbon monoxide transmitters serial no. EC-S 002. August 29, 2006 PolyGard CO LC-1112 V3 Electrochemical analog carbon monoxide transmitters serial no. EC-S 002 User Manual August 29, 2006 January 04, 2016 Revision Specifications subject to change without notice. USA

More information

GASGUARD O 2. Oxygen Sensor OPERATING & INSTALLATION MANUAL

GASGUARD O 2. Oxygen Sensor OPERATING & INSTALLATION MANUAL GASGUARD O 2 Oxygen Sensor OPERATING & INSTALLATION MANUAL 2 Table of Contents General description. 4 Installation.. 4 Locating the sensor. 4 Installation guidelines 5 Wiring.. 6 Operation.. 7 Start-up...

More information

Operation & Maintenance Manual

Operation & Maintenance Manual Operation & Maintenance Manual GDS-58XP Explosion-Proof Sample Draw System for Toxic & Combustible Gases GDS Corporation 2513 Hwy 646 Santa Fe, Texas 77510 (409) 927-2980 (409) 927-4180 (Fax) www.gdscorp.com

More information

Installation and Wiring 1.

Installation and Wiring 1. Installation and Wiring 1. Please read the Security Notifications in detail firstly. 2. The gas detector might install on wall or steel plate, please refer following drawing to make marking then drill

More information

GG-NO2 NITROGEN DIOXIDE GAS SENSOR. Installation and Operation Manual

GG-NO2 NITROGEN DIOXIDE GAS SENSOR. Installation and Operation Manual GG-NO2 NITROGEN DIOXIDE GAS SENSOR Installation and Operation Manual 2 GG-NO2 Warning Use this product only in the manner described in this manual. If the equipment is used in a manner not specified by

More information

M2A Transmitter Operator s Manual

M2A Transmitter Operator s Manual M2A Transmitter Operator s Manual Part Number: 71-0305RK Revision: F Released: 1/8/18 RKI Instruments, Inc. www.rkiinstruments.com WARNING Read and understand this instruction manual before operating instrument.

More information

RK-02 Multi Point Detector Operator s Manual

RK-02 Multi Point Detector Operator s Manual 65-2485RK-02 Multi Point Detector Operator s Manual Part Number: 71-0237RK Revision: A Released: 11/26/14 RKI Instruments, Inc. www.rkiinstruments.com WARNING Read and understand this instruction manual

More information

Xgard. Fixed detectors For flammable, toxic or oxygen gases

Xgard. Fixed detectors For flammable, toxic or oxygen gases Fixed detectors For flammable, toxic or oxygen gases Xgard Xgard Type 1: Xgard Type 2: Xgard Type 3: Xgard Type 4: Xgard Type 5: Xgard Type 6: Xsafe: Intrinsically safe toxic and oxygen gas detector Flameproof

More information

GG-R REFRIGERANT SENSOR. Installation and Operation Manual

GG-R REFRIGERANT SENSOR. Installation and Operation Manual GG-R REFRIGERANT SENSOR Installation and Operation Manual 2 GG-R Warning Use this product only in the manner described in this manual. If the equipment is used in a manner not specified by Calibration

More information

Digital Gas Transmitters with Auxiliary Inputs & Control. PolyGard 2 DC6

Digital Gas Transmitters with Auxiliary Inputs & Control. PolyGard 2 DC6 Digital Gas Transmitters with Auxiliary s & Control Specifications subject to change without notice. USA 181011 Page 1 of 5 DESCRIPTION Digital RS-485 communicating, addressable toxic and combustible gas

More information

RK Carbon Monoxide Transmitter Operator s Manual

RK Carbon Monoxide Transmitter Operator s Manual 65-2335RK Carbon Monoxide Transmitter Operator s Manual Part Number: 71-0177RK Revision: 0 Released: 4/12/11 RKI Instruments, Inc. www.rkiinstruments.com WARNING Read and understand this instruction manual

More information

GASGUARD SO2 Sulfur Dioxide Sensor OPERATING & INSTALLATION MANUAL

GASGUARD SO2 Sulfur Dioxide Sensor OPERATING & INSTALLATION MANUAL GASGUARD SO2 Sulfur Dioxide Sensor OPERATING & INSTALLATION MANUAL Operating and Installation Manual Warning Use this product only in the manner described in this manual. If the equipment is used in a

More information

RK-03 Hydrogen Detector Operator s Manual

RK-03 Hydrogen Detector Operator s Manual 61-1001RK-03 Hydrogen Detector Operator s Manual Part Number: 71-0371 Revision: P1 Released: 5/26/15 www.rkiinstruments.com WARNING Read and understand this instruction manual before operating detector.

More information

Nanotechnology Metal Oxide Semiconductor (NTMOS) H 2 S Gas Sensor

Nanotechnology Metal Oxide Semiconductor (NTMOS) H 2 S Gas Sensor INSTRUCTIONS Nanotechnology Metal Oxide Semiconductor (NTMOS) H 2 S Gas Sensor APPLICATION The Det-Tronics Nanotechnology Metal Oxide Semiconductor (NTMOS) Hydrogen Sulfide (H 2 S) stand-alone gas sensor

More information

RK-05 Carbon Monoxide Detector Operator s Manual

RK-05 Carbon Monoxide Detector Operator s Manual 65-2433RK-05 Carbon Monoxide Detector Operator s Manual Part Number: 71-0189RK Revision: 0 Released: 5/17/11 RKI Instruments, Inc. www.rkiinstruments.com WARNING Read and understand this instruction manual

More information

INSTALLATION AND OPERATING INSTRUCTIONS R-3F2-LXX

INSTALLATION AND OPERATING INSTRUCTIONS R-3F2-LXX INSTALLATION AND OPERATING INSTRUCTIONS R-3F2-LXX UL APPROVED FOR: CLASS I, DIVISION 2 HAZ LOC CAT III & IV www.pesd.com Part Number Description: The XX specifies the fiber-o cable length in inches. General

More information

REMOTE TOXIC, COMBUSTIBLE, AND OXYGEN GAS SENSORS

REMOTE TOXIC, COMBUSTIBLE, AND OXYGEN GAS SENSORS REMOTE TOXIC, COMBUSTIBLE, AND OXYGEN GAS SENSORS FEATURES Extremely wide range of sensors Easy installation and maintenance Low cost of ownership Replacement of sensors are simple Rugged and reliable

More information

PolyGard Single Point Controller SPC-X3-34XX for Combustible Gases

PolyGard Single Point Controller SPC-X3-34XX for Combustible Gases PolyGard Single Point Controller SPC-X3-34XX for Combustible Gases DESCRIPTION Gas measuring and monitoring controller based on stateof-the-art microtechnology with integrated sensor for continuous monitoring

More information

THE BELGIAN PIONEER IN GAS DETECTION

THE BELGIAN PIONEER IN GAS DETECTION DAX 3F Gas detector INSTRUCTION MANUAL THE BELGIAN PIONEER IN GAS DETECTION Copyright 2016 by DALEMANS s.a. Revision V1R6 07/2016 Any reproduction, whether partial or entire, made of this document, by

More information

RKA-LEL Sample Draw Combustible Gas Detector

RKA-LEL Sample Draw Combustible Gas Detector 35-3000RKA-LEL Sample Draw Combustible Gas Detector Specifications Table 1 lists specifications for the sample draw combustible gas detector. Table 1: Specifications Target Gas Input Power Combustible

More information

CMF, CMX & CMA series

CMF, CMX & CMA series Features Electrochemical sensor element 4-20 ma or 2-10 Vdc output CMF- IP 44 protection CMX- IP 54 protection CMA- IP 65 protection Wide supply voltage range (18-28 Vdc) Overload and short cicuit protected

More information

SIMRAD GD10P - IR GAS DETECTOR OPERATING MANUAL

SIMRAD GD10P - IR GAS DETECTOR OPERATING MANUAL SIMRAD GD10P - IR GAS DETECTOR OPERATING MANUAL P3359E 8th edition - November 2005 Simrad Optronics ASA Kabelgaten 4B P.O. Box 174, Økern NO-0509 OSLO, NORWAY Phone +47 22 66 60 00 Fax +47 22 66 60 01

More information

SEC Millenium Hydrocarbon Gas Detector

SEC Millenium Hydrocarbon Gas Detector SEC Millenium Hydrocarbon Gas Detector Instruction and Operation Manual Sensor Electronics Corporation 12730 Creek View Avenue Savage, Minnesota 55378 USA (952) 938-9486 Fax (952) 938-9617 Email: sales@sensorelectronic.com

More information

RK / RK Methane Detector Operator s Manual

RK / RK Methane Detector Operator s Manual 61-1006RK / 61-0192RK Methane Detector Operator s Manual Part Number: 71-0228RK Revision: 0 Released: 10/29/18 www.rkiinstruments.com WARNING Read and understand this instruction manual before operating

More information

Process Control PIP PCEA001 Fixed Gas Detection Guidelines

Process Control PIP PCEA001 Fixed Gas Detection Guidelines November 2015 Process Control PIP PCEA001 PURPOSE AND USE OF PROCESS INDUSTRY PRACTICES In an effort to minimize the cost of process industry facilities, this Practice has been prepared from the technical

More information

GASGUARD NH 3. Ammonia Sensor OPERATING & INSTALLATION MANUAL

GASGUARD NH 3. Ammonia Sensor OPERATING & INSTALLATION MANUAL GASGUARD NH 3 Ammonia Sensor OPERATING & INSTALLATION MANUAL Operating and Installation Manual 2 Table of Contents GasGuard NH 3 Operating and Instruction Manual General description. 4 Installation.. 4

More information