Colibri. Automatic Tank Gauge CL6 Series Installation Guide
|
|
- Elinor Higgins
- 6 years ago
- Views:
Transcription
1 Colibri Automatic Tank Gauge CL6 Series Installation Guide Manual # Revision Date Changes from Previous Revision C Jan Pipe compound brand change, Updated Control drawing. Franklin Fueling Systems 3760 Marsh Rd. Madison, WI USA Tel: Fax:
2 Notice FFS reserves the right to change this document and specifications at any time without notice. FFS makes no expressed or implied warranty with regard to the contents of this manual. FFS assumes no liability for errors or omissions, or for any damages, direct or consequential, that may result from the use of this document or the equipment that it describes. Trademarks FFS, Colibri, TS-5 Series, System Sentinel, SCALD, Brite, BriteBox, BriteBus, and BriteSensors are registered trademarks of Intelligent Controls. All brand and product names are trademarks or registered trademarks of their respective companies. Inspection of Materials Visually inspect all components for defects or damage prior to installation. If any defect or damage is found, do not use the product and contact FFS for further assistance. Contacting Franklin Fueling Systems (FFS) Please feel free to contact us by mail at: Franklin Fueling Systems 3760 Marsh Rd. Madison, WI USA Or contact us by phone, fax or Tel: sales@franklinfueling.com Fax: techserve@franklinfueling.com Tel: US & Canada Tel: México Tel: Europa Tel: Asia Please visit our web site at Copyright 2009 by Franklin Fueling Systems (FFS). No part of this publication may be reproduced in any form without the prior written consent of FFS. All rights reserved. ii
3 Contents Important Safety Messages...1 Introduction...2 Product Description...2 Console Installation...2 Console Location...2 Console Dimensions...3 Standard Installation Materials...4 Wiring the Console...5 Attach the probe wiring in order as shown on the label below... 5 Non-Intrinsically Safe Wiring... 6 Check Electrical Resistance to Earth Ground... 6 Control Drawing...8 iii
4 Important Safety Messages FFS equipment is designed to be installed in association with volatile hydrocarbon liquids such as gasoline and diesel fuel. Installing or working on this equipment means working in an environment in which these highly flammable liquids may be present. Working in such a hazardous environment presents a risk of severe injury or death if these instructions and standard industry practices are not followed. Read and follow all instructions thoroughly before installing or working on this, or any other related, equipment. As you read this guide, please be aware of the following symbols and their meanings: Warning Caution Danger This symbol identifies a warning. A warning sign will appear in the text of this document when a potentially hazardous situation may arise if the instructions that follow are not adhered to closely. A potentially hazardous situation may involve the possibility of severe bodily harm or even death. This is a caution symbol. A caution sign will appear in the text of this document when a potentially hazardous environmental situation may arise if the instructions that follow are not adhered to closely. A potentially hazardous environmental situation may involve the leakage of fuel from equipment that could severely harm the environment. This symbol identifies an electrical danger. An electrical danger sign will appear in the text of this document when a potentially hazardous situation involving large amounts of electricity may arise if the instructions that follow are not adhered to closely. A potentially hazardous situation may involve the possibility of electrocution, severe bodily harm, or even death. Warning Warning Warning Warning Follow all applicable codes governing the installation and servicing of this product and the entire system. Always lock out and tag electrical circuit breakers while installing or servicing this equipment and any related equipment. A potentially lethal electrical shock hazard and the possibility of an explosion or fire from a spark can result if the electrical circuit breakers are accidentally turned on during installation or servicing. Follow all federal, state and local laws governing the installation of this product and its associated systems. When no other regulations apply, follow NFPA codes 30, 30A and 70 from the National Fire Protection Association. Failure to follow these codes could result in severe injury, death, serious property damage and/or environmental contamination. When the Colibri system is used to monitor tanks containing gasoline or other flammable substances, you may create an explosion hazard if you do not follow the requirements in this manual carefully. All wiring must enter the console s enclosure through the designated knockouts. An explosion hazard may result if other openings are used. All wiring from probes to the console must be run in conduit separate from all other wiring. Failure to do so will create an explosion hazard. 1
5 Introduction This manual contains installation and site preparation instructions for FFS s Colibri console. Safety issues, troubleshooting information, warranty, service, and return policies, as defined in this manual, must be followed. Please read this entire manual carefully. Failure to follow the instructions in this manual may result in faulty operation, equipment damage, injury or death. Installer This equipment should only be serviced by an FFScertified technician. Product Description The Colibri is a complete, automatic, continuous monitoring system that performs a variety of functions. Performs inventory monitoring Generates reports automatically in response to preset / programmed conditions and alarms Provides audio-visual annunciation when an alarm or warning condition exists Is able to print reports on an external USB printer. Remotely accessible via Ethernet or RS-232 to any web browser. Leak detection and density monitoring Tank reconciliation and Autocalibration Console Installation Console Location Install the console indoors in an area classified as nonhazardous. Locate the console where personnel can easily make use of it; mount it at eye level for operator convenience. Mount the console level on a vertical surface between 2 feet (0.6 m) and 6 feet (1.9 m) high using the appropriate fasteners. Mounting the Console Removing the cover The cover must be removed by lifting with two hands. Press in on the cover release tabs on both ends to release the cover and lift it straight away from the unit (Figure 1). When reinstalling the cover put it on straight so the LED light pipes are not damaged. Cover Release Tabs LED Light Pipes Console Specifications Line Voltage: Frequency & Power: V~, 1.0 A 50/60 Hz, 150 W maximum Storage Temp.: -20 to 60 C (-4 to 140 F) Operating Temp.: 0 to 40 C (32 to 104 F) Operating Humidity: Cleaning: Splash Resistance: Location: 0 to 95%, non-condensing Relay Rating 240V~ Cloth or sponge slightly dampened in mild detergent Not to be exposed to direct spray, splash or drips Indoors in an office or in a nonhazardous pollution degree 2 environment per IEC60664 Figure 1: Inside Cover The Colibri console must be mounted in a location where explosive or flammable vapors are not present, otherwise an explosion hazard will be created which can result in severe injury, death, serious property damage and/or environmental contamination. Leave a minimum of two inches (5.1 cm) of space around the console open to allow for ventilation, communication port connections, conduit and wiring. Two mounting screw holes are located on the inside of the console. Use fasteners that have sufficient load carrying capacity and which are appropriate for wall construction. Make sure that there is enough room around the console for conduit coming into the unit, communication port connections, probe wiring, and console access. 2
6 Console Dimensions 9.25" (235 mm) Probe Interface Connections Ground stud See note " (25.4 mm) Power / relay Compartment Intrinsically safe wiring compartment 2X 0.21" (5.33 mm) 11.92" (303 mm) LCD Display (Optional) 2.24" (57 mm) 7.27" (185 mm) Cover Release Tab Both Ends Alarm Led Warning Led Power Led Communication Ports Non-Intrinsically Safe Conduit Entries Intrinsically Safe Conduit Entries Figure 2: Console Dimensions 3
7 Standard Installation Materials Circuit Breaker 20 Amp providing power only for the console Weatherproof Junction Boxes Minimum 16 cubic inch (406.4 cubic mm) weatherproof junction box, cover, and cover gasket for the manholes of liquid level probes. Also use ½ inch (16 mm) bushings for probe compression fittings. Use a weatherproof metal pull box for combining several circuits that will run into the console through one or more conduits. Use a separate weatherproof metal pull box to combine intrinsically safe (IS) liquid level probe wiring. Do not run other non-intrinsically safe wiring within the IS pull box. Run ½ inch (16 mm) IS probe conduit from the manholes to the IS pull box, and then run one or two ½ inch (16 mm) conduits to the console s IS conduit knockouts. Conduit Rigid metal conduit (RMC) - male NPT threaded: use ½ (16 mm) for IS probe wiring to the console (from the manholes, use ½ inch conduit), and use ½ inch (16 mm) for non-intrinsically safe accessories and power wiring. Use conduit hardware that is appropriate for the installation and meets local, state and federal requirements. Splice Connector Kits Must Be Used Warranty Requirement Use the FFS-approved, moisture-resistant, no-strip splice connectors for liquid level probes. You may order the TSP-KW30, which contains 30 of the FFS-approved, moisture-resistant connectors. Using moisture resistant splice connectors will: Reduce / eliminate corrosion of the wire connections from repeated exposure to water condensation, which causes eventual signal loss and system failure. Reduce or eliminate equipment damage from water flooding around the connectors, which causes shortcircuit damage. Thread Sealant (UL Classified) Use a non-hardening, stay-soft, gasoline compatible thread sealant to seal and waterproof all tank riser pipe threads. In addition, the thread sealant (or pipe dope as it is commonly known) should also be chemically non reactive to the product in the tank(s). Apply thread sealant to seal / waterproof all outdoor electrical conduit fitting threads including the hole plugs at the weatherproof junction boxes. Riser Pipes ANSI Schedule 40 (or chemically non-reactive) 2" or 4" (50.8 or mm) (8 NPT) riser pipes for liquid level probes. Probe Installation Kit(s) The appropriate FFS 2 or 4 probe installation kit must be used when installing TSP-LL2 (not -I) leak detection probes and / or Density Measurement float kits. Probe Install Kits: Part # TSP-K2A TSP-K2B TSP-K4A TSP-K4S TSP-K4B Description For 2" riser pipes, NPT For 2" riser pipes with BSP threads For 4" riser pipes, NPT 316 stainless steel for 4" riser pipes, NPT For 4" riser pipes with BSP threads Probe Floats Floats for 4 inch (101.6 mm) riser pipes, order: TSP- IGF4 for gasoline applications or TSP-IDF4 for diesel and fuel oil Floats for 3 inch (76.2 mm) riser pipes, order: TSP-IGF3 for gasoline applications or TSP-IDF3 for diesel and fuel oil Floats for 2 inch (50.8 mm) riser pipes, order: TSP-IGF2 for gasoline, TSP-IDF2 for diesel and fuel oils, or TSP-SSP stainless steel float for chemical products Density floats for 4 inch (101.6mm) riser pipes, order: TSP-IGF4D for gasoline applications and TSP-IDF4D for diesel and fuel oil. Manufacturer s Tank Chart for Each Tank The manufacturer s Tank Chart and other documentation will be used for installation and programming, and possibly for future reference. Keep this information do not discard it. 4
8 Wiring the Console Intrinsically Safe Wiring Non-intrinsically safe wiring cannot be run in the same conduit as intrinsically safe wiring. Probe Wiring The probe wiring is intrinsically safe and kept separate from all other wiring. Conduit must only enter the console enclosure through the designated knockouts. Installation may require the conduit to enter on top or bottom. Do not loose the conduit plugs and make sure any openings are covered by the plugs. Probe Terminals Figure 3: Probe Wiring Attach the probe wiring in order as shown on the label below. Number of Channels: 6 Safety Rating: Terms defined Term Uo Io Po Co Lo Probe Input Specifications Class I, Division 1, Group D, [Ex ia] IIA Entity Parameters Uo = V Io = ma Co = 1.04 uf Lo = 1.4 mh Po = 1.1 W Definition Maximum Output Voltage Maximum Output Current Maximum Output Power Maximum External Capacitance Maximum External Inductance Cables Required for Liquid Level Probes Use cables and wires compliant with national and local codes to insure reliable communication between the console and probes. To ensure reliable communication between a console and probes, FFS recommends using the types of cable shown below up to a recommended length of: All cable to be shielded twisted pair, 22AWG or greater and oil / water resistant. Distance feet (m) Capacitance (pf) per foot Inductance (µh) per foot Belden Cable 500 (152) <100 < * 1000 (305) <60 < (457) <20 < * Note: An asterisk (*) indicates cables that may be ordered from FFS. 5
9 Line Power Wiring Non-Intrinsically Safe Wiring Always lock out and tag electrical Warning circuit breakers while installing or servicing this equipment and any related equipment. A potentially lethal electrical shock hazard and the possibility of an explosion or fire from a spark can result if the electrical circuit breakers are accidentally turned on during installation or servicing. Power to the console must be 110 to 240 V~, 50 / 60 Hz. At the electrical power panel, use a 20 amp circuit breaker used only to supply power to the Colibri console. Note: Do not connect other equipment to this circuit. 110/240 VAC Line Power Wire Connection List Electrical Panel 20 Amp Circuit Breaker No. Conductors, Color (Gauge) 1 Black wire, 14 AWG (1.6 mm) min. Neutral 1 White Wire, 14 AWG (1.6 mm) min. Ground Bus 1 Green wire, 14 AWG (1.6 mm) min. Ground Bus 1 Green wire, 12 AWG (2.1 mm) min. Circuit 110/240 VAC Power Neutral Ground Safety Ground Console Ground Connection Attach the ground wire to the grounding stud in the console. Ground Stud Enclosure Nut Cup Washer Earth Ground Conductor Flat Washer Lock Washer Figure 5: Ground Stud Connection Figure 4: Power Wiring Connection The ground bus in the electrical panel must be connected to an earth ground as required by the National Electrical Code (or Canadian Electrical Code) when applicable. If the ground bus is not properly connected to an earth ground or if the IS safety ground is not properly connected at the console, a dangerous condition will be created which could result in an explosion. Check Electrical Resistance to Earth Ground After wiring the IS safety grounds, check the resistance between the IS safety ground terminals at the console and the earth ground this resistance must be less than 1 ohm. 6
10 Communication Ports The Colibri console has several communication ports that can be used to communicate with devices. The communication ports can be used to connect the console to a Local Area Network, Point of Sale device, external printer or modem. USB Modem Requirements In order for the console operating system to communicate with a USB modem, the modem must be CDC-ACM compliant. Printer Requirements The printer has to have a USB interface and support Hewlett-Packard Printer Command Language level 3 (PCL 3) or higher. The printer should not have a power save feature and should be started before starting the console. Relay Wiring Figure 6: Communication Ports Port Connector Type Devices RS-232 Comm 1 Ethernet USB (2) DB9 Male RJ-45 Type A Modem, P.O.S. or local PC Local network or computer External printer, modem or USB flash drive* * The USB flash drive can be used to collect data or load upgraded files RS-232 Communication Connectors One connector for RS-232 interface is provided on the bottom of the console The pin designations for the RS-232 connectors are as follows: Console RS-232 Comm Port 1 DB9 Connector, Male, DTE Figure 7: Relay Wiring Connection Relay Terminal Description Normally Closed 2. Common 3. Normally Open 4. Common 5. Normally Closed 6. Normally Open Note: Pay close attention to the relay connections. The position of the Normally Closed and Common terminals are swapped. Pin No. Function Input/Output 1 DCD I 2 RD I 3 TD O 4 DTE O 5 Signal GND 7 RTS O 8 CTS I 7
11 Control Drawing
12 9
13 Page intentionally blank
14 2013 FFS Rev. C
Fuel Management System Setup Guide
Fuel Management System Setup Guide EVO-EXPC & EVO-EXPC2 Expansion Consoles for TS-5000 evo and TS-550 evo Franklin Fueling Systems 3760 Marsh Rd. Madison, WI 53718 USA Tel: +1 608 838 8786 800 225 9787
More informationFMP-DDS & FMP-DTS. Discriminating Dispenser Sump & Turbine Sump BriteSensor. Installation Instructions
& Discriminating Dispenser Sump & Turbine Sump Brite Installation Instructions Franklin Fueling Systems 3760 Marsh Rd. Madison, WI 53718 USA Tel: +1 608 838 8786 800 225 9787 Fax: +1 608 838 6433 www.franklinfueling.com
More informationFMP-HIS AND FMP-HIS-U INSTALLATION GUIDE
FMP-HIS AND FMP-HIS-U INSTALLATION GUIDE The information in this publication is provided for reference only. While every effort has been made to ensure the reliability and accuracy of the information contained
More informationTS-RA1, TS-RA2 and TS-RK Tank Overfill Alarms
TS-RA1, TS-RA2 and TS-RK Tank Overfill Alarms Installation Guide franklinfueling.com 3760 Marsh Rd. Madison, WI 53718, USA Tel: +1 608 838 8786 Fax: +1 608 838 6433 Tel: USA & Canada +1 800 225 9787 Tel:
More informationFMP-MWS. (Discriminating Monitoring Well Sensor BriteSensor ) Installation Instructions
FMP-MWS (Discriminating Monitoring Well Sensor BriteSensor ) Installation Instructions Franklin Fueling Systems 3760 Marsh Rd. Madison, WI 53718 USA Tel: +1 608 838 8786 800 225 9787 Fax: +1 608 838 6433
More informationFMP-DVS. Monitoring Well Discriminating Vapor Sensor (BriteSensor ) Installation Instructions
FMP-DVS Monitoring Well Discriminating Vapor Sensor (BriteSensor ) Installation Instructions Franklin Fueling Systems 3760 Marsh Rd. Madison, WI 53718 USA Tel: +1 608 838 8786 800 225 9787 Fax: +1 608
More informationFMP-ULS UNIVERSAL LIQUID SENSOR INSTALLATION GUIDE
FMP-ULS UNIVERSAL LIQUID SENSOR INSTALLATION GUIDE The information in this publication is provided for reference only. While every effort has been made to ensure the reliability and accuracy of the information
More informationFMP-DIS & FMP-EIS. Interstitial BriteSensor & Standard Sensor. Installation Instructions
FMP-DIS & FMP-EIS Interstitial BriteSensor & Standard Sensor Installation Instructions FMP-DIS Sensor FMP-EIS Sensor Franklin Fueling Systems 3760 Marsh Rd. Madison, WI 53718 USA Tel: +1 608 838 8786 800
More informationAUTOMATIC TANK GAUGES
EVO TM 200 AND EVO TM 400 AUTOMATIC TANK GAUGES INSTALLATION GUIDE The information in this publication is provided for reference only. While every effort has been made to ensure the reliability and accuracy
More informationPROTEUS Series OEL8000III-K. Tank Gauging System. Installation Manual
OMNTEC PROTEUS Series OEL8000III-K Tank Gauging System Installation Manual Page 1 of 23 PROPRIETARY INFORMATION NOTICE This document contains information and material developed by OMNTEC Mfg., Inc. All
More informationLS500 Auto Learn Line Leak Detection
LS500 Auto Learn Line Leak Detection Installation & User s Guide Manual # Revision date Changes from Previous Revision 000-2145 H September 2014 Added TS-ALNIP / TS-AFALNIP notice to page 16 Franklin Fueling
More informationManual No: Revision: D. Sump Sensor. Installation Guide
Manual No: 576013-301 Revision: D Sump Sensor Installation Guide Notice Veeder-Root makes no warranty of any kind with regard to this publication, including, but not limited to, the implied warranties
More informationFuel Management System Operator s Guide
Fuel Management System Operator s Guide TS-550 evo and TS-5000 evo Franklin Fueling Systems 3760 Marsh Rd. Madison, WI 53718 USA Tel: +1 608 838 8786 800 225 9787 Fax: +1 608 838 6433 www.franklinfueling.com
More informationManual No: Revision: D. Mag Sump Sensor. Installation Guide
Manual No: 577013-812 Revision: D Mag Sump Sensor Installation Guide Notice Veeder-Root makes no warranty of any kind with regard to this publication, including, but not limited to, the implied warranties
More informationManual No: Revision: E. Groundwater Sensor. Installation Guide
Manual No: 576013-763 Revision: E Groundwater Sensor Installation Guide Notice Veeder-Root makes no warranty of any kind with regard to this publication, including, but not limited to, the implied warranties
More informationTank Sentinel Operator s Guide
Tank Sentinel Operator s Guide T5 Series Franklin Fueling Systems 3760 Marsh Rd. Madison, WI 53718 USA Tel: +1 608 838 8786 800 225 9787 Fax: +1 608 838 6433 www.franklinfueling.com Notice Franklin Fueling
More informationManual No: Revision: G. Sensor Products. Application Guide
Manual No: 577013-750 Revision: G Sensor Products Application Guide Notice Veeder-Root makes no warranty of any kind with regard to this publication, including, but not limited to, the implied warranties
More informationManual No: Revision: J. Groundwater Sensor. Installation Guide
Manual No: 576013-763 Revision: J Groundwater Sensor Installation Guide Notice Veeder-Root makes no warranty of any kind with regard to this publication, including, but not limited to, the implied warranties
More informationOperating & Maintenance Manual. Alert-4 Ethernet LCD Master Alarm
Operating & Maintenance Manual Alert-4 Ethernet LCD Master Alarm w w w. a m i c o. c o m Contents User Responsibility 4 Introduction 4 Features 5 Description of the Alarm 5 Shipment Details 5 The Alarm
More informationPre-March 2016 Design - Click to be redirected to newer SBS-H2 design SBS-H2. Hydrogen Gas Detector Kit
Pre-March 2016 Design - Click to be redirected to newer SBS-H2 design N56 W16665 Ridgewood Drive Menomonee Falls, WI 53051 SBS-H2 Hydrogen Gas Detector Kit For battery charging rooms and other areas where
More informationNGC-UIT-ORD User interface terminal for Raychem NGC systems Installation Instructions
NGC-UIT-ORD User interface terminal for Raychem NGC systems Installation Instructions Description The NGC-UIT-ORD is a panel mounted display used in conjunction with other approved Raychem control and
More informationSingle-Point Mini Hydrostatic Sensor for Double-Wall Sumps
Manual No: 577013-838 Revision: B Single-Point Mini Hydrostatic Sensor for Double-Wall Sumps Installation Guide Notice Veeder-Root makes no warranty of any kind with regard to this publication, including,
More informationInterstitial Liquid Sensor - Fiberglass Tanks
Manual No: 576013-617 Revision: J Interstitial Liquid Sensor - Fiberglass Tanks Installation Guide Notice Veeder-Root makes no warranty of any kind with regard to this publication, including, but not limited
More informationVariable Speed Flow Controller
Variable Speed Flow Controller Installation Guide IMPORTANT NOTICE! A V-R PLLD Pressure Transducer must be installed in the STP and connected to the Variable Speed Flow Controller (VSFC) for the VSFC to
More informationSET-2000 Hi Level/Oil
Labkotec Oy Labkotie 1 FI-36240 KANGASALA FINLAND Tel: + 358 29 006 260 Fax: + 358 29 006 1260 13.03.2008 Internet: www.labkotec.fi Alarm Device for Oil Separators Copyright 2008 Labkotec Oy We reserve
More informationPO Box 827 Hawley, MN (218) Fax (218)
Introduction Before proceeding with the installation or operation of the Oil Alert System, read all instructions thoroughly, as well as complying with all Federal, State and Local codes, Regulations and
More informationSAFETY INFORMATION AND WARNINGS
This manual refers to the Model SST-3 control panel manufactured since October 31, 2013, which uses a universal (100 277 VAC; 50/60 Hz) power supply. Older units use a voltage-specific power supply and
More informationTTSIM-2 TRACETEK SENSOR INTERFACE MODULE WITH LCD AND RELAY INSTALLATION/OPERATION INSTRUCTIONS
TTSIM-2 TRACETEK SENSOR INTERFACE MODULE WITH LCD AND RELAY INSTALLATION/OPERATION INSTRUCTIONS GENERAL INFORMATION Please read these instructions and keep them in a safe place. These instructions must
More informationNGC-UIT2-ORD-R Remote User Interface Terminal for Raychem NGC Systems Installation Instructions
NG-UIT2-ORD-R Remote User Interface Terminal for Raychem NG Systems Installation Instructions Description The NG-UIT2-ORD-R is a wall-mounted display which allows the User Interface Terminal (UIT) to be
More informationManual No: Revision: H. MicroSensor. Installation Guide
Manual No: 576013-285 Revision: H MicroSensor Installation Guide Notice Veeder-Root makes no warranty of any kind with regard to this publication, including, but not limited to, the implied warranties
More informationELP21LU3-LF-HLOL THREE CHANNEL
ELP21LU3-LF-HLOL THREE CHANNEL 516-467-5787 HI LEVEL LOW LEVEL LEAK DETECTION 11.00 TEST SYSTEM DETECTING HORN OFF 6.00 SPECIFICATIONS POWER INPUT 85-125 VAC, 47-440 Hz 16 Watts maximum POWER TO SENSORS
More informationCheck It Panel. 1 Phase Simplex Demand Dose Operation, Maintenance & Installation Manual. Introduction. Safety Guidelines
Introduction Before proceeding with the installation or operation of the control panel read all instructions thoroughly, as well as comply with all Federal, State and Local Codes, Regulations and Practices.
More informationTHERMAL BUILDING SOLUTIONS EN-TraceTekTTSIM1A-IM-H /16
TraceTek TTSIM-1A TraceTek Sensor Interface Module with Relay Installation/OPERATION Instructions Approvals and Certifications TYPE NM General Signaling Equipment 76LJ Only AC versions are UL listed and
More informationINSTALLATION INSTRUCTIONS FOR 6532 SERIES PACKAGE HEAT PUMP
INSTALLATION INSTRUCTIONS FOR 6532 SERIES PACKAGE HEAT PUMP RV Products A Division of Airxcel, Inc. P.O. Box 4020 Wichita, KS 67204 1976-360 (1-02) PP TABLE OF CONTENTS 1. Warnings......................................................
More informationSLATE. Base Module INSTALLATION INSTRUCTIONS R8001A1001
SLATE Base Module R8001A1001 INSTALLATION INSTRUCTIONS Scan for more information Application SLATE brings configurable safety and programmable logic together into one single platform. The platform can
More informationOG5000 Ozone Generator Model OG5000B-A. User Manual
OG5000 Ozone Generator Model OG5000B-A Copyright 2017 610-0082-01H DCN7785 Teledyne API 25 September 2017 Contents CONTENTS... 1 FIGURES... 2 TABLES... 2 1. GENERAL PRECAUTIONS... 3 Safety... 5 Safety
More informationSET-2000 Oil/Sludge. Alarm Device for Oil Separators. Installation and Operating Instructions
SET-000 Oil/Sludge Alarm Device for Oil Separators Copyright 007 Labkotec Oy We reserve the right for changes without notice TABLE OF CONTENTS GENERAL... INSTALLATION... 4. SET-000 Oil/Sludge Control Unit...
More informationSensor Interface Module Installation/Operation Instructions
TraceTek TTSIM-1 Sensor Interface Module Installation/Operation Instructions Approvals and Certifications TYPE NM General Signaling Equipment 76LJ Only AC versions are UL listed and VDE Certified. For
More informationMODELS 304GC, 304GCX, 314GC, and 314GCX
2562109A REV. A1 0317 Printed in U.S.A. MODELS 304GC, 304GCX, 314GC, and 314GCX INSTALLATION AND SERVICE INSTRUCTIONS FOR SELECTONE Limited Warranty This product is subject to and covered by a limited
More informationTTSIM-1A. TraceTek Sensor Interface Module with Relay. Installation/Operation Instructions. Installation Items (not supplied) Tools Required.
TTSIM-1A TraceTek Sensor Interface Module with Relay Installation Items (not supplied) General Information Installation/Operation Instructions Please read these instructions and keep them in a safe place.
More informationModel Gas Alarm Panel APPLICABILITY & EFFECTIVITY. This manual provides instructions for the following Sierra Monitor products:
Model 2102 Gas Alarm Panel APPLICABILITY & EFFECTIVITY This manual provides instructions for the following Sierra Monitor products: Model Description 2102-00 Alarm Panel 2 Channel 2102-01 Alarm Panel 2
More informationOilSET Installation and Operating Instructions. Oil Separator Alarm Device with SET/DM3AL sensor
Labkotec UK Ltd Adminicle House 1 Lumb Lane Audenshaw Manchester M34 5WH GREAT BRITAIN Tel: 0844 3350 477 Fax: 0161 4281 179 E-mail: info@labkotec.co.uk 10.8.2012 Internet: www.labkotec.co.uk 1/13 OilSET-1000
More informationAUTOMATIC TANK GAUGES
EVO TM 200 AND EVO TM 400 AUTOMATIC TANK GAUGES OPERATION GUIDE The information in this publication is provided for reference only. While every effort has been made to ensure the reliability and accuracy
More informationModel 9001EXP Alarm. NOTE TO INSTALLER: Please leave this information with the Maintenance Department. LIMITED WARRANTY
INSTALLATION, OPERATION & MAINTENANCE INSTRUCTIONS 1455 Kleppe Lane Sparks, NV 89431-6467 (775) 359-4712 Fax (775) 359-7424 E-mail: haws@hawsco.com website: www.hawsco.com Model 9001EXP Alarm No. 2080203(24)
More informationModel 9001, Alarm
INSTALLATION, OPERATION & MAINTENANCE INSTRUCTIONS 1455 Kleppe Lane Sparks, NV 89431-6467 (775) 359-4712 Fax (775) 359-7424 E-mail: haws@hawsco.com website: www.hawsco.com No. 2080202(27) Model 9001, 9001.5
More informationInstallation, Operation & Service Manual
Installation, Operation & Service Manual WARNING Improper installation, adjustment, alteration, service or maintenance can result in death, injury or property damage. Read the Installation, Operation and
More informationMODEL AV2-C1D1M Hazardous Duty Class I. Div 1, Multitone Alarm Station
MODEL AV2-C1D1M Hazardous Duty Class I. Div 1, Multitone Alarm Station Operator s Installation and Instruction Manual DETCON, Inc. 3200 Research Forest Dr., The Woodlands, Texas 77387 Ph.281.367.4100 /
More informationIMPORTANT SAFETY INFORMATION:
Owner s Manual Model CUH05B31T IMPORTANT SAFETY INFORMATION: Always read this manual first before attempting to install or use this heater. For your safety, always comply with all warnings and safety instructions
More informationModel 9001, Alarm
INSTALLATION, OPERATION & MAINTENANCE INSTRUCTIONS 1455 Kleppe Lane Sparks, NV 89431-6467 (775) 359-4712 Fax (775) 359-7424 E-mail: haws@hawsco.com website: www.hawsco.com Model 9001, 9001.5 Alarm No.
More information1022 R/T Remote Monitor
1022 R/T Remote Monitor INSTRUCTIONS AMC-1022R/T WITH REMOTE SENSOR OR TRANSMITTER INSTALLATION AND OPERATING INSTRUCTIONS FOR THE AMC-1022R/T UNIT IMPORTANT: Please read these installation and operating
More informationINSTALLATION, OPERATION AND MAINTENANCE INSTRUCTIONS FOR PIPE THREAD IMMERSION HEATERS USED IN HAZARDOUS LOCATIONS
INSTALLATION, OPERATION AND MAINTENANCE INSTRUCTIONS FOR PIPE THREAD IMMERSION HEATERS USED IN HAZARDOUS LOCATIONS I. GENERAL Heatrex Explosion-proof Pipe Thread Mounted Immersion Heaters are CSA approved
More informationTank Gauging System Special Safety Instruction
Tank Gauging System www.rosemount-tg.com Rosemount TankRadar REX Table of Contents Contents SPECIAL SAFETY INSTRUCTION........................ 1-1 1. GENERAL REQUIREMENTS....................... 1-2 1.1
More informationSiteSentinel Integra 100 /500 Automatic Tank Gauge System Installation Manual
SiteSentinel Integra 100 /500 Automatic Tank Gauge System Installation Manual Central Technical Support Number: 1-877-OPW-TECH (877-679-8324) Calls outside US and Canada: 1-708-485-4200 Fax: 1 (800) 421-3297
More informationINSTALLATION GUIDE Dual Fuel Ranges
INSTALLATION GUIDE Dual Fuel Ranges Contents Wolf Dual Fuel Ranges......................... 3 Safety Instructions............................ 4 Dual Fuel Range Specifications.................. 5 Dual Fuel
More informationFor use with models: PGM304-1, versions M-B PGM365-1, versions M-E, M-F & M-G
PGM-1 Cooktops For use with models: PGM304-1, versions M-B PGM365-1, versions M-E, M-F & M-G Install ation Instructions Part No. 65476 Rev. B Table of Contents Appliance Safety...1 Important Safety Instructions...2
More information2 To 1 Sensor Input Box
Manual No: 577013-869 Revision: D 2 To 1 Sensor Input Box Installation Guide Notice Veeder-Root makes no warranty of any kind with regard to this publication, including, but not limited to, the implied
More informationOilSET Installation and Operating Instructions. Oil Separator Alarm Device
Labkotec Oy Myllyhaantie 6 FI-33960 PIRKKALA FINLAND Tel: +358 29 006 260 Fax: +358 29 006 1260 18.11.2010 Internet: www.labkotec.fi 1/10 OilSET-1000 Oil Separator Alarm Device Copyright 2010 Labkotec
More informationYP7999A1000 ControLinks Fuel Air Ratio Control Panel
YP7999A1000 ControLinks Fuel Air Ratio Control Panel FEATURES INSTALLATION INSTRUCTIONS Pre-wired and ready to install Includes the R7999A control, wiring subbase and S7999D1048 touchscreen display Commission,
More informationDETCON MODEL AV1/AV2-C1D2M Hazardous Duty Class I. Div 2, Multitone Alarm Station
DETCON MODEL AV1/AV2-C1D2M Hazardous Duty Class I. Div 2, Multitone Alarm Station Operator s Installation and Instruction Manual DETCON, Inc. 3200 Research Forest Dr, The Woodlands, Texas 77387 Ph.281.367.4100
More informationMAINTENANCE & TROUBLESHOOTING GUIDE LEAK ALARM CHANNEL DRY OIL WATER AUX ALARM HIGH LOW CRITICAL WATER TANK LEVEL ALARM MODEL LDE-740 ADVANCE PAPER
PNEUMERCATOR Liquid Level Control Systems Electronic Systems Excluding LC2000 And TMS Series MAINTENANCE & TROUBLESHOOTING GUIDE 400 300 500 FUEL LEVEL LEAK MONITOR 1 200 600 OIL/GAS NORMAL WATER PNEUMERCATOR
More informationINSTALLATION GUIDE Fryer Module
INSTALLATION GUIDE Fryer Module Contents Wolf Fryer Module............................ 3 Fryer Module Specifications..................... 4 Fryer Module Installation....................... 8 Service Information...........................
More informationInstallation Instructions Remote Blowers
Installation Instructions Remote Blowers Models: REMP3, REMP16 Suitable for use in a household cooking area. Suitable for use with solid state controls. To complete this blower, a Dacor hood assembly or
More informationAM54. Armored Variable Area Flowmeter Series AM54331/32 Series AM54371/72/73/74 Series AM54431/32 Series AM54471/72/73/74
AM54 Instruction Bulletin North American Installation Addendum Document Number PN25016 Armored Variable Area Flowmeter Series AM54331/32 Series AM54371/72/73/74 Series AM54431/32 Series AM54471/72/73/74
More informationMODELS ASHP, ASHH, ASUP, and ASUH
2562229A REV. A 1210 Printed in U.S.A. MODELS ASHP, ASHH, ASUP, and ASUH INSTALLATION AND SERVICE INSTRUCTIONS blank page INSTALLATION AND SERVICE INSTRUCTIONS FOR MODELS ASHP, ASHH, ASUP, AND ASUH SAFETY
More informationSingle Point Freeze Protection Heat Trace Control TRACON MODEL FPT 130 Installation and Operation Manual
We manage heat MANUAL Single Point Freeze Protection Heat Trace Control TRACON MODEL FPT 130 Installation and Operation Manual 1850 N Sheridan Street South Bend, Indiana 46628 (574) 233-1202 or (800) 234-4239
More informationInstallation Instructions
50ZPB, C, 50ZHB, C, PA3Z ---A, PH3Z ---A, PA4Z, PH4Z, PAJ4,PHJ4,WJA4,WJH4 SMALL PACKAGED PRODUCTS (SPP) Accessory Electric Heaters 5---20 kw For 14 SEER, R---410A Manufactured Home Installation Instructions
More informationEVO 200 EVO 400 EVO 550 EVO 5000
NEVER STOP INTRODUCING THE EVO SERIES FAMILY OF AUTOMATIC TANK GAUGES Driven by our pursuit to innovate, simplify, and better connect every station owner to their secure system data, we introduce the EVO
More informationInstallation Instructions Millennia Cooktops
Installation Instructions Millennia Cooktops TESTED IN ACCORDANCE WITH THE LATEST EDITION OF ANSI Z21.1 STANDARD FOR HOUSEHOLD COOKING APPLIANCES. IMPORTANT WARNINGS: IMPORTANT: NOTES: 1. Before beginning
More informationC-Bus Pascal Automation Controller 5500PACA. Installation Instructions
C-Bus Pascal Automation Controller 5500PACA Installation Instructions Contents 1.0 Description...3 2.0 Important Notes...3 3.0 Capabilities...3 4.0 Wiring Instructions...4 4.1 Battery Back up...5 4.2 Connecting
More informationRAM3 Remote Alarm Module
RAM3 Remote Alarm Module INSTRUCTIONS Installation and Operation of the AMC-RAM3 with AMC Monitors IMPORTANT: Please read this installation and operating instructions completely and carefully before starting.
More informationSBS-H2. Hydrogen Gas Detector Kit. For battery charging rooms and other areas where hydrogen gas may be present
SBS-H2 Hydrogen Gas Detector Kit For battery charging rooms and other areas where hydrogen gas may be present INSTALLATION, OPERATING & MAINTENANCE INSTRUCTIONS Protects Life, Property, and Profits Compliant
More informationPower Supply Display Module PSDM. Installation and Operation Manual
Power Supply Display Module PSDM Installation and Operation Manual Read this manual before using this product. Failure to follow the instructions and safety precautions in this manual can result in serious
More informationOilSET-1000 (12 VDC)
Labkotec Oy Myllyhaantie 6 FI-33960 PIRKKALA FINLAND Tel: +358 29 006 260 Fax: +358 29 006 1260 Internet: www.labkotec.fi 20.03.2009 1/11 OilSET-1000 (12 VDC) Oil Separator Alarm Device Copyright 2009
More informationLORAIN CIP 4890/48120 DC Power System
DC Power for Business-Critical Continuity Key Features Compact flexibility provides rectifiers, distribution, and controller in one shelf Constant power delivers more current at lower voltages to meet
More informationMulti-Function Cooktop
INSTALLATION GUIDE Multi-Function Cooktop Contents Wolf Multi-Function Cooktop.................... 3 Multi-Function Cooktop Specifications............ 4 Multi-Function Cooktop Installation...............
More informationBID-SPEC_INTEGRA_100 Rev. 0. Bid Specifications and General Description OPW SiteSentinel Integra 100 Automatic Tank Monitoring System
BID-SPEC_INTEGRA_100 Rev. 0 Bid Specifications and General Description OPW SiteSentinel Integra 100 Automatic Tank Monitoring System Part 1. General Overview 1.1 Summary This document describes the minimum
More informationAutomatic Tank Gauging and Line Leak Detection System Bid Specification TS-550evo Fuel Management System
Automatic Tank Gauging and Line Leak Detection System Bid Specification TS-550evo Fuel Management System Franklin Fueling Systems 000-1739 r3, November 2017 An ISO 9001 Registered Company Part 1 General
More informationQuick Start Guide For the
A Leader in Level Measurement Quick Start Guide For the Universal IV Lite and Universal IV Pro Model Transmitters 2-Wire RF Admittance / Capacitance Level Measurement System with HART Protocol For Assistance
More informationSSC-1D installation guide
Phason The Single Stage Control (SSC-1D) automatically controls the temperature in a room by switching fans, lamps, or heaters on or off as the temperature drops below or exceeds the temperature set point.
More informationACSI MODEL 1410 POWER SUPPLY INSTALLATION INSTRUCTIONS
II 1400-3 ACSI MODEL 1410 POWER SUPPLY INSTALLATION INSTRUCTIONS Features: For use with doors or groups of doors that must interlock with each other to regulate control of accessing one area from another,
More informationInstallation Instructions
Electric Heaters 5 --- 20 kw SMALL PACKAGED PRODUCTS (SPP) Accessory Electric Heaters For 13 SEER, R---410A Manufactured Home Installation Instructions NOTE: The Dual Point Kit can only be installed on
More informationRAYCHEM NGC-30 COMPONENTS
PANEL MOUNTED ELECTRONIC MULTI-CIRCUIT HEAT-TRACING CONTROL, MONITORING AND POWER DISTRIBUTION SYSTEM PRODUCT OVERVIEW CABLE DUCT Card Rack Modules TERMINAL STRIP PLINTH MAIN SWITCH 800 mm USER INTERFACE
More informationSentry LIQUID LEVEL ALARM MODEL 100 OPERATING MANUAL.
Sentry LIQUID LEVEL ALARM MODEL 100 OPERATING MANUAL www.aquaticsentry.com TABLE OF CONTENTS 1. SAFETY PRECAUTIONS... 3 2. APPLICATION... 3 2.1 HIGH Liquid Level Alarm 2.2 LOW Liquid Level Alarm 3. INSTALLATION...
More informationT M. User Manual. MarinaGuard. Ground Fault Monitoring Panel For Marina Shore Power
T M User Manual MarinaGuard Ground Fault Monitoring Panel For Marina Shore Power NAE1095810 / 03.2013 T M Bender Inc. USA: 700 Fox Chase Coatesville, PA 19320 Toll-Free: 800-356-4266 Phone: 610-383-9200
More informationRMS/RPX Reader. User Manual
RMS/RPX Reader User Manual Copyright Disclaimer Trademarks and patents Intended use FCC compliance Copyright 2005, GE Security Inc. All rights reserved. This document may not be copied or otherwise reproduced,
More information24 VAC Direct Spark Gas Ignition
Installation Instructions Issue Date March 3, 2017 Quick Reference Guide The Direct Spark Gas Ignition control module is designed for direct burner ignition and supervision. It can be used in new applications
More informationPipe Freeze Protection Control SCFP-CO-F130 Installation and Operation Manual
MANUAL Pipe Freeze Protection Control SCFP-CO-F130 Installation and Operation Manual Model FPT 130 Single Point Freeze Protection Heat Trace Control Table of Contents SCFP-CO-F130 Overview... 3 Installation...
More informationCertificate of Compliance
FF0 001 Certificate of Compliance Certificate: 70116284 (LR 064969_0_00) Issued to: Mine Safety Appliances Company North American Division 1000 Cranberry Woods Dr Cranberry Township, Pennsylvania 16066-5296
More informationLGB Gas fired boiler
LGB Gas fired boiler Control Supplement LGB-5 Series 2 Propane gas CSD-1 Control System Part Number 550-110-682/0304 Please read this page first Hazard definitions To the installer... The following terms
More informationINSTALLATION INSTRUCTIONS FOR 7330C740 FLUSH MOUNT CEILING ASSEMBLY
INSTALLATION INSTRUCTIONS FOR 7330C740 FLUSH MOUNT CEILING ASSEMBLY TABLE OF CONTENTS Warnings...3 Package Contents...3 General Information...3 Supply Ducting And Registers...3 Routing 115 VAC Wiring...5
More informationThermal Stability Systems
Thermal Stability Systems for Oil Tank Heating Unit Model: TSSHU6002 PLEASE READ THESE INSTRUCTIONS PRIOR TO INSTALLATION. THESE INSTRUCTIONS MUST BE LEFT WITH THE USER AND SHOULD BE RETAINED FOR FUTURE
More informationINSTALLATION GUIDE Steamer Module
INSTALLATION GUIDE Steamer Module Contents Wolf Steamer Module.......................... 3 Steamer Module Specifications.................. 4 Steamer Module Installation..................... 8 Service Information...........................
More informationFigure 1. Figure 2. See notes 1 and 2 below.
273 Branchport Avenue Long Branch, N.J. 07740 (800) 631-2148 Thank you for using our products. www.wheelockinc. com INSTALLATION INSTRUCTIONS HORN SPEAKER WITH AMPLIFIER Use this product according to this
More informationMULTI-TEMPERATURE LOOP CONTROL BOARD INSTRUCTIONS
LCB-I-O Rev B MULTI-TEMPERATURE LOOP CONTROL BOARD INSTRUCTIONS Models: KB 81-286, KBXL 400-801, WB 51-211, and WH 55-399 IMG00116 WARNING This manual must only be used by a qualified heating installer
More informationTLS-300 UST Monitoring and Leak Detection System
Part 1 General System Requirements 1.1 Description TLS-300 UST Monitoring and Leak Detection System A. These Specifications are intended to provide information by which prospective bidders may understand
More informationPANEL MOUNTED ELECTRONIC MULTI-CIRCUIT HEAT-TRACING CONTROL, MONITORING AND POWER DISTRIBUTION SYSTEM mm. 100 mm
PANEL MOUNTED ELECTRONIC MULTI-CIRCUIT HEAT-TRACING CONTROL, MONITORING AND POWER DISTRIBUTION SYSTEM Card Rack Modules CABLE DUCT MAIN SWITCH 800 mm USER INTERFACE TERMINAL PRODUCT OVERVIEW The nvent
More informationInstallation Instructions Induction Cooktop
Installation Instructions Induction Cooktop Models: RNCT304 and RNCT365 Part No. 107240 Rev. A Table of Contents Important Safety Instructions... 1 Important Information About Safety Instructions... 1
More informationDuct and Rough Service Carbon Monoxide Sensor
Product Identification and Overview Duct and Rough Service Carbon Monoxide Sensor BAPI s Carbon Monoxide Sensor offers enhanced electrochemical sensing with outstanding accuracy at low concentrations.
More informationM1500 SiteSentinel itouch Tank-Gauge Monitoring System Installation Guide. Part Number: M1500, Rev. 5
Part Number: M1500, Rev. 5 Issue Date: May 17, 2016 Supersedes: May 30, 2012 M1500 SiteSentinel itouch Tank-Gauge Monitoring System Installation Guide 6900 Santa Fe Drive Hodgkins, IL 60525 Tel: (708)
More informationSET-2000 Oil/Sludge 12 VDC
Labkotec Oy Myllyhaantie 6 FI-33960 PIRKKALA FINLAND Tel: + 358 29 006 260 Fax: + 358 29 006 1260 12.2.2015 Internet: www.labkotec.fi 1/14 SET-2000 Oil/Sludge 12 VDC Alarm Device for Oil Separators with
More information