10-175UL INSTALLATION. Power Supply UL. Access Control Power Supply/Charger. Installation and Specifications Manual
|
|
- Brandon Jefferson
- 4 years ago
- Views:
Transcription
1 INSTALLATION UL Power Supply UL Access Control Power Supply/Charger Installation and Specifications Manual
2 Overview The UL is a power limited power supply/charger that will convert 115VAC / 60Hz input, into two individually PTC protected 12VDC or 24VDC output, (see specifications). They are intended for use in applications requiring UL Listing for Access Control (UL294) and applications requiring an interface with Fire Alarm Control Panels. It must be installed in accordance with National and Local Electrical Codes and Regulations. Specifications UL listed Access Control (UL294) CSFM approved - California State Fire Marshal MEA approved - NYC Dept. of Buildings E NFPA 101 (Life Safety) Input 115VAC/60 Hz,.6 amps Switch selectable 12VDC or 24VDC power limited output Class 2 rated power limited outputs amps continuous supply 12VDC or 24VDC Latching fire alarm tie-in with manual reset Filtered and electronically regulated output Charge current: 0.4 amps Max Aux relay output: (form C, 1 amp, 28VDC) AC Fail output relay (form C, 1 amp, 28VDC) Enclosure Dimensions: 15.5 H x 12 W x 4.5 D Output Specifications Output VDC Switch Position Max. Stand-by Max. Alarm Battery Load DC Load DC (Optional) 12VDC SW1 Open 1.75 amps 1.75 amps 12VDC 24VDC SW1 Closed 1.75 amps 1.75 amps 24VDC Stand-By Specifications Output 12VDC / 7 AH Battery 24VDC / 7 AH Battery 4Hr. of Stand-by & 5 minutes of alarm Stand-by = 1.25 amps Alarm = 1.25 amps 2
3 Installation Instructions The UL should be installed in accordance with article 760 of The National Electrical Code or NFPA 72 as well as all applicable Local Codes. See Terminal Identification Chart on page 4 for a description of each terminal function. 1. Mount the UL in desired location. 2. Connect AC power (115VAC 60Hz) to the black and white flying leads of the transformer. Secure green wire lead to earth ground. Use 18 AWG or larger for all power connections (Battery, DC output). Use 22 AWG to 18 AWG for power limited circuits (trigger inputs, dry outputs). Keep power limited wiring separate from non-power limited wiring (115VAC/ 60Hz Input, Battery Wires). Minimum.25 (6.4mm) spacing must be provided. 3. Set the UL to the desired DC output voltage by setting switch SW1 to the appropriate position (power supply output specification table). Note: It is good operating practice to measure and verify output voltage before connecting devices to ensure proper operation of equipment. 4. Connect battery to terminals marked [+ BAT -] (battery leads included). Use two (2) 12VDC batteries connected in series for 24VDC operation. Note: For Access Control applications, batteries are optional. When batteries are not used a loss of AC will result in the loss of output voltage. When the use of standby batteries are desired, they must be lead acid or gel type. 5. Connect appropriate signaling notification devices to AC Fail supervisory relay outputs marked [N.C., N.O., C]. Note: To meet UL requirements, AC Supervisory outputs must be connected to the zone of Alarm Control Panel or to visual AC trouble indicator. 6. For Access Control Device & Fire Alarm Interface connections refer to desired Application Diagrams (pg. 6-8) and Terminal Identification Chart. 7. Secure enclosure door with the screws supplied, to assure proper ground. Maintenance Unit should be tested at least once a year for the proper operation as follows: Output Voltage Test: Under normal load conditions, the DC output voltage should be checked for proper voltage level (see power supply output specifications chart). Battery Test: Under normal load conditions check that the battery is fully charged, check specified voltage both at battery terminal and at the board terminals marked [- BAT +] to insure there is no break in the battery connection wires. Note: Maximum charging current under discharges is 0.40 amps. Note: Expected battery life is 5 years, however it is recommended changing batteries in 4 years or less if needed. 3
4 Terminal / Switch Identifcation: Terminal Legend TRGI & TRG2 LOCK+ STRIKE+ N.C., N.O., C AUX+ COM FACP BAT+, BAT SW2 Function/Description These input terminals are designed to connect to the normally closed outputs of an access control or fire alarm relay. These terminals control [LOCK+], and [STRIKE+], as well as UL output relay contacts [N.C., N.O., C] This terminal provides DC output voltage when [TRG1] and [TRG2] are shorted together and are typically used to power Mag Locks. This terminal provides DC output voltage when [TRG1] and [TRG2] are unshorted and are typically used to power Electric Strikes. Isolated dry Form C contacts. Shorting [TRG1] and [TRG2] together causes these contacts to switch. They are typically used for controlling multiple ULs with fire alarm tie-in (Fig. 3 and Fig. 4, pg. 7-8). Continuous positive (+) DC power output voltage. It is not affected by TRG1, TRG2 operation. Common negative (-) output (ground). Spare wiring terminal used for fire alarm tie-in application (Fig. 1, pg. 6). Stand-by battery connections. Momentary reset button (on front door) is used as a manual power supply reset after fire alarm system is restored. LED Diagnostics RED(DC) Green (AC) Power Supply Status (Front Door) ON ON Normal Function ON OFF Battery backup is powering output OFF ON No DC output OFF OFF Loss of AC. Discharged or missing stand-by battery. No DC output. 4
5 115VAC input 60 Hz,.6 amps Reset Switch AC Power LED Black Lead White Lead Green Lead (ground) XFMR JUMPER NC NO C TRG1 TRG2 SW1 CLOSED -24V OPEN - 12V AC FAIL NC NO C DC SW1 AC VR1 AC Molex Connector UL LOCK + STRIKE + COM - AUX + FACP AUX - + BAT -- AC AC Constant output (not affected by trigger) Stand-by Battery (optional) Switched DC output (trigger control) 5
6 Enclosure Dimensions 1-1/2" [38.1mm] 1-1/4" [31.8mm] 12" [304.8mm] 7/8" [22.2mm] 9-7/8" [250.8mm] 1" [25.4mm] 1-1/4" [31.8mm] 2" [50.8mm] 3-3/8" [85.7mm] 15.50" [393.7mm] 3-3/8" [85.7mm] 2-1/8" [54.0mm] 1-1/4" [31.8mm] 1" [25.4mm] 1-1/2" [38.1mm] 1-1/4" [31.8mm] FIG 1. Typical mag lock with fire alarm tie-in using aux output installation. 6
7 FIG 2. Typical Single Mag lock or door strike installation with fire alarm tie-in using trigger controlled output. FIG 3. Typical dual mag lock installation with fire alarm tie-in using trigger controlled outputs. 7
8 FIG 4. Latching fire alarm tie-in with manual reset. Troubleshooting Guide Problem No DC output from terminals. Output voltage is not correct for the connected equipment. Solution - Check AC and DC LED s on power supply board. Both should be on for proper operation. If AC GREEN is offcheck AC Power. If DC RED is offcheck output and battery connections - Disconnect AC power, battery(s) and all connected equipment IMMEDIATELY. - Change voltage selection switch to desired voltage. - Reconnect equipment and re-apply AC power. For Technical Support: or IS10-175UL 2011 RUTHERFORD CONTROLS INT L CORP. USA: 2517 SQUADRON COURT, SUITE 104, VIRGINIA BEACH, VA CANADA: 210 SHEARSON CRESCENT, CAMBRIDGE, ON N1T 1J6 PHONE: FAX: PCN R07/11SH
ACSI Series 1550K-MD and 1550-MD Motor Drive Electric Latch Retraction
ACSI Series 1550K-MD and 1550-MD Motor Drive Electric Latch Retraction Riser and Point-to-Point Drawings for Standard Access Control Applications Using Maintained Latch Retraction Control or Momentary
Installation Guide for AL300ULM. Multi-Output Access Control Power Supply Charger
Installation Guide for AL300ULM Multi-Output Access Control Power Supply Charger R AL300ULM - Multi-Output Access Control Power Supply/Charger Overview: The AL300ULM multi-output access control power supply/charger
Installation Guide for AL600ULM. Multi-Output Access Control Power Supply Charger. Rev
Installation Guide for AL600ULM Multi-Output Access Control Power Supply Charger Rev. 091800 1 AL600ULM - Multi-Output Access Control Power Supply/Charger Overview: The AL600ULM multi-output access control
Installation Guide for AL400ULM. Multi-Output Access Control Power Supply Charger
Installation Guide for AL400ULM Multi-Output Access Control Power Supply Charger R AL400ULM - Multi-Output Access Control Power Supply/Charger Rev. 072500 Overview: The AL400ULM multi-output access control
Multi-Output Access Control Power Supply Charger VDC or 24VDC VDC or 3 24VDC.
M Series Multi-Output Access Control Power Supply Charger Installation Guide Models Include: AL300ULM AL400ULM - 2.5 amp @ 12VDC or 24VDC. - 4 amp @ 12VDC or 3 amp @ 24VDC. AL600ULM AL1012ULM - 6 amp @
Multi-Output Access Control Power Supply Chargers VDC or 24VDC VDC or 4 24VDC.
M Series Multi-Output Access Control Power Supply Chargers Installation Guide Models Include: AL300ULM AL400ULM - 2.5 amp @ 12VDC or 24VDC. - 3 amp @ 12VDC or 4 amp @ 24VDC. AL600ULM AL1012ULM - 6 amp
PDD-8PCI. Power Distribution Board With Supervised Interface. Installation and Specifications Manual
INSTALLATION PDD-8PCI PDD-8PCI Power Distribution Board With Supervised Interface Installation and Specifications Manual Details The PDD-8PCI board is a power distribution/control interface. This board
AL400ULACM AL600ULACM - 4 amp - 12VDC or 6 amp. - Fused Outputs - Fused Outputs
ACM Series Access Power Controllers with Power Supplies Installation Guide Models Include: AL400ULACM AL600ULACM - 12VDC @ 4 amp - 12VDC or 24VDC @ 6 amp. or 24VDC @ 3 amp - Fused Outputs - Fused Outputs
Series. Access Power Controllers. Installation Guide
Series Access Power Controllers Installation Guide Models Include: Maxim11 - Power Supply 1: 12VDC @ 3.5 amp or 24VDC @ 2.7 amp. - Power Supply 2: 12VDC @ 3.5 amp or 24VDC @ 2.7 amp. - Sixteen (16) fuse
Installation Guide for models:
140 58th St. Brooklyn, NY Access Power Controllers with Power Supplies Installation Guide for models: Maximal3FD - 12VDC @ 4.6 amp or 24VDC @ 5.2 amp. - Sixteen (16) PTC protected power-limited outputs.
Installation Guide for AL800UL-ADA. NAC Power Extender. Rev
Installation Guide for AL800UL-ADA NAC Power Extender Rev. 090500 Overview: The Altronix AL800UL-ADA is an extremely cost effective 8 amps voltage regulated remote power supply /battery charger. The AL800UL-ADA
AL600ULADA. NAC Power Extender. Installation Guide
AL600ULADA NAC Power Extender Installation Guide Rev. 122000 AL600ULADA - NAC Power Extender Overview: The Altronix AL600ULADA is an extremely cost effective 6.5 amp voltage regulated remote power supply/battery
Installation Guide for models:
140 58th St. Brooklyn, NY Access Power Controllers with Power Supplies Installation Guide for models: Maximal11F - Power Supply 1: 12VDC @ 3.3 amp or 24VDC @ 3.6 amp. - Power Supply 2: 12VDC @ 3.3 amp
For a red enclosure add an R suffix to the part # e.g. eflow4na8dr. Altronix Corp th St. Brooklyn, NY. Installing Company: Service Rep.
Power Supply/Chargers Installation Guide Models Include: eflow4na8d - 4A @ 12VDC or 24VDC - Eight (8) PTC Outputs eflow6na8d - 4A @ 12VDC or 24VDC - Eight (8) PTC Outputs eflow102na8d - 10A @ 12VDC - Eight
AL800ULADA. NAC Power Extender. Installation Guide
AL800ULADA NAC Power Extender Installation Guide Rev. 122000 AL800ULADA - NAC Power Extender Overview: The Altronix AL800ULADA is an extremely cost effective 8 amp voltage regulated remote power supply/battery
For a red enclosure add an R suffix to the part # e.g. eflow4na8r. Altronix Corp th St. Brooklyn, NY. Installing Company: Service Rep.
Power Supply/Chargers Installation Guide Models Include: eflow4na8-4a @ 12VDC or 24VDC - Eight (8) Fused Outputs eflow6na8-4a @ 12VDC or 24VDC - Eight (8) Fused Outputs eflow102na8-10a @ 12VDC - Eight
AL802ULADA. NAC Power Extender. Installation Guide. (See Application Guide for additional information) Rev
AL802ULADA NAC Power Extender Installation Guide (See Application Guide for additional information) Rev. 031703 Overview: The Altronix AL802ULADA is an extremely cost effective 8 amp voltage regulated
ACM8 & ACM8CB. Access Power Controllers Installation Guide. - Fused Outputs - Fused Outputs. - PTC Outputs - PTC Outputs. Models Include: Rev.
ACM8 & ACM8CB Access Power Controllers Installation Guide Models Include: ACM8 ACM8E - Fused Outputs - Fused Outputs ACM8CBE ACM8CB - PTC Outputs - PTC Outputs Rev. 092503 Overview: These units convert
- Four (4) Fused Outputs - Four (4) PTC Outputs. - Eight (8) Fused Outputs - Eight (8) PTC Outputs
AL300ULX Series Power Supply/Charger Installation Guide Models Include: AL300ULX - Single Output AL300ULPD4 AL300ULPD4CB - Four (4) Fused Outputs - Four (4) PTC Outputs AL300ULPD8 AL300ULPD8CB - Eight
AL600ULX Series. Power Supply/Charger. Installation Guide
AL600ULX Series Power Supply/Charger Installation Guide Models Include: AL600ULX - Single Output AL600ULPD4 AL600ULPD4CB - Four (4) Fused Outputs - Four (4) PTC Outputs AL600ULPD8 AL600ULPD8CB - Eight
- 4 12VDC or 24VDC VDC or 24VDC - Eight (8) Fused Outputs - Eight (8) PTC Outputs. Installing Company: Service Rep.
140 58th St. Brooklyn, NY Power Supply/Chargers Installation Guide Models Include: eflow4n/eflow4nx - 4 amp @ 12VDC or 24VDC eflow4n8/eflow4nx8 eflow4n8d/eflow4nx8d - 4 amp @ 12VDC or 24VDC - 4 amp @ 12VDC
Access Power Controllers with Power Supplies
Access Power Controllers with Power Supplies Installation Guide Models Include: Maximal11FD - Power Supply 1: 12VDC @ 3.3A or 24VDC @ 3.6A. - Power Supply 2: 12VDC @ 3.3A or 24VDC @ 3.6A. - Sixteen (16)
ACM8 Series UL Listed Sub-Assembly Access Power Controllers. Installation Guide. ACM8 - Eight (8) Fuse Protected Outputs
ACM8 Series UL Listed Sub-Assembly Access Power Controllers Installation Guide Models Include: ACM8 - Eight (8) Fuse Protected Outputs ACM8CB - Eight (8) PTC Protected Outputs Rev. 042811 More than just
- Four (4) Fused Outputs - Four (4) PTC Outputs. - Eight (8) Fused Outputs - Eight (8) PTC Outputs
AL400ULX Series Power Supply/Charger Installation Guide Models Include: AL400ULX - Single Output AL400ULPD4 AL400ULPD4CB - Four (4) Fused Outputs - Four (4) PTC Outputs AL400ULPD8 AL400ULPD8CB - Eight
1 Description. 2 Specifications. HP600ULM Access Control Power Supply/Charger with Power Distribution Controller PN 52393:A 1/05/06 ECN
Honeywell 12 Clintonville Road Northford, CT 06472 http://www.honeywellpower.com HP600ULM Access Control Power Supply/Charger with Power Distribution Controller PN 52393:A 1/05/06 ECN 04-350 Product Installation
PS6 SERIES. Installation PS6 SERIES. Power Supplies c/w Fire Panel Interface, EOL Trigger and Standby Power Option
Installation PS6 SERIES Power Supplies PS6 SERIES Power Supplies c/w Fire Panel Interface, EOL Trigger and Standby Power Option Installation and Specifications Manual ISDPS6_SERIES 08121590 PCN15016 R05/15GR
SP-1000X. Panic Device Power Controller Installation Guide. Rev
TM SP-1000X Panic Device Power Controller Installation Guide Rev. 120213 Overview: SP-1000X will operate up to two (2) 24VDC panic hardware devices simultaneously. It is designed to handle the high current
APS-300 SERIES DUAL VOLTAGE UL 294 LISTED ACCESS CONTROL POWER SUPPLIES
APS-300 SERIES DUAL VOLTAGE UL 294 LISTED ACCESS CONTROL POWER SUPPLIES POWER SUPPLY AND BATTERY CHARGER AC AND DC STATUS INDICATORS ENOUGH POWER TO SUPPORT UP TO 3 MAGLOCKS OR ELECTRIC STRIKES PLUS REQUIRED
Rack Mount Series Installation Guide
Rack Mount Series Installation Guide Models Include: Maximal1RHV Maximal1RV - 12VDC @ 4 amp or 24VDC @ 3 amp. - 12VDC @ 4 amp or 24VDC @ 3 amp. - Eight (8) Fuse Protected Outputs. - Sixteen (16) Fuse Protected
ACM4 Series UL Listed Sub-Assembly Access Power Controllers
ACM4 Series UL Listed Sub-Assembly Access Power Controllers Installation Guide Models Include: ACM4 - Four (4) Fuse Protected Outputs ACM4CB - Four (4) PTC Protected Outputs Rev. 051311 More than just
RPSMLR2 RPSMLR2BB. Panic Device Power Controller Installation Guide LISTED. Rev
RPSMLR2 RPSMLR2BB Panic Device Power Controller Installation Guide LISTED Rev. 102715 Overview: RPSMLR2BB, RPSMLR2 will operate up to two (2) 24VDC panic hardware devices simultaneously. It is designed
PDD-FT-3. Fire Panel Interface With EOL Trigger. Installation and Specifications Manual
Installation -3-3 Fire Panel Interface With EOL Trigger Installation and Specifications Manual ISPSFPD-3 PCN16045 R12/17GR 2017 Rutherford Controls Int l dormakaba Group www.rutherfordcontrols.com Phone:
AL802ULADA. NAC Power Extender. Installation Guide. (See Application Guide for additional information)
AL802ULADA NAC Power Extender Installation Guide (See Application Guide for additional information) Rev. 042010 Agency Listings: UL Listed Control Units for Fire Protective Signaling Systems (UL 864).
POWERPATH PS-8 (105531) PS-8E (100263) PS-6 (105530) PS-6E (100262)
PATH PS-8 (105531) PS-8E (100263) PS-6 (105530) PS-6E (100262) NAC ETENDER SUPPLIES Installation Instructions 273 Branchport Avenue, Long Branch, NJ 07740-6899 Ph: (800) 631-2148 Fax: (732) 222-8707 Web
AL1002ULADA. NAC Power Extender. Installation Guide. (See Application Guide for additional information) Rev X
AL1002ULADA NAC Power Extender Installation Guide (See Application Guide for additional information) Rev. 071508X Agency Listings: UL Listed Control Units for Fire Protective Signaling Systems (UL 864).
Installation Instructions. PS902 Power Supply. These instructions cover the following parts: PS902 Power Supply Specifi cations:
F1! 44487023 These instructions cover the following parts: PS902 Power Supply Installation Instructions! DANGER: To avoid risk of electric shock, turn off AC power before installing or servicing PS902
more than just power! Altronix is the professional security industry s leading manufacturer
altronix.com more than just power! Altronix is the professional security industry s leading manufacturer and designer of low voltage electronics that deliver more than just power. With its global reputation
TECHNICAL DATA OBSOLETE
Deluge Devices 270a 1. PRODUCT NAME VIKING PAR-3 Available since 1991 2. MANUFACTURED FOR: THE VIKING CORPORATION 210 N. Industrial Park Road Hastings, Michigan 49058 U.S.A. Telephone: (269) 945-9501 (877)
June 10, 2002 DF C S2424
GENERAL www.firelite.com The Fire Lite FIRE COMMAND 25/50X is a state-of-theart Emergency Voice Evacuation Control Panel (VECP), with significant technological enhancements that set it apart from other
AL1042ULADA. NAC Power Extender. Installation Guide (See Application Guide for additional information) Rev
Altronix Corp. 140 58th St. Brooklyn, NY AL1042ULADA NAC Power Extender Installation Guide (See Application Guide for additional information) Rev. 052313 Agency Listings: UL Listed for Control Units for
AL1042ULADA. NAC Power Extender. Installation Guide. (See Application Guide for additional information) Rev X
AL1042ULADA NAC Power Extender Installation Guide (See Application Guide for additional information) Rev. 071508X Agency Listings: UL Listed for Control Units for Fire Protective Signaling Systems (UL
Securitron Magnalock Corporation S. 51 st St., Ste. 102 Phoenix, AZ Phone: (800) MAGLOCK
Installation Manual AQM-20 12vdc/24vdc Series Power Supplies AQM20 Supervised Power Supply/Charger 12vdc 20Amp/24vdc 10Amp Life Time Warranty Quality Manufactured in the USA AQM20 Features: The AQM20 has
FireNET Plus Wiring Instructions
FireNET Plus Wiring Instructions This manual provides wiring instructions for the 1 loop and 2 loop version of the FireNET Plus panels, which supports our finest Hochiki s DCP protocol. Note: Refer to
MODEL B2 INSTALLATION MANUAL
RELEASE DEVICES GENERAL DESCRIPTION MODEL B2 INSTALLATION MANUAL S/N: The B2 Series Time Delay Release Devices are UL Listed, Canadian Listed, and CSFM Listed for use on rolling doors, single-slide and
Specification/ Data Sheet
Specification/ Data Sheet TRITON RP Agent Release Control Panel FEATURES Agent Release Control Panel designed specifically for suppression release operation with: Four initiating device circuits (IDCs)
PS1240x Series Dual Voltage Access Control Power Supply Systems Operating and Installation Instructions Rev D.01
PS1240x Series Dual Voltage Access Control Power Supply Systems Operating and Installation Instructions Warnings and Notices WARNING - To reduce the risk of fire or electric shock, do not expose this product
GENERAL STANDARD FEATURES. ISO-9001 Engineering and Manufacturing Quality System Certified to International Standard ISO-9001 PATENT PENDING
GENERAL The VEC 25/50 is a state-of-the-art, compact, stand-alone or slave Emergency Voice Evacuation Control. The VEC 25/50 is offered in a self-contained, cost-effective design and includes a 25 Watt,
RELEASE DEVICE CONTROLS
RELEASE DEVICE CONTROLS RELEASE DEVICE MODEL C+ INSTALLATION MANUAL UL LISTED CANADIAN LISTED CSFM: 7300-48:00 GENERAL DESCRIPTION: MADE IN THE U.S.A. S/N: The LM0-C+ Release Device/Control Panel is a
Booster Power Supply Manual
Supply Manual DEVELOPED BY COPYRIGHT NOTICE General Signal Building Systems Corporation 6411 Parkland Drive Sarasota, FL 34243 (941) 739-4300 Copyright 1999 General Signal Building Systems Corporation
July 14, 1999 DF C-100.
www.firelite.com GENERAL The Fire Lite FIRE COMMAND 25/50 is a state-of-theart, compact, stand-alone or slave Emergency Voice Evacuation Control Panel (VECP). The FIRE COMMAND 25/50 is offered in a self-contained,
IP Access FACP Adapters. Installation Guide. Entrada2DMK - IP Access FACP Adapter Kit. Kit Includes: Entrada2DMR - IP Access FACP Receiver
IP Access Adapters Installation Guide Entrada2DMK - IP Access Adapter Kit Kit Includes: - IP Access Receiver - IP Access Transmitter I.T.E. 43KC Doc. No. IIEntrada2DMK Rev. 062015 More than just power.
Data Sheet Fire Safety & Security Products. System Overview. Initiating Circuits SXL-EX FACP 7906
s Data Sheet Fire Safety & Security Products SXL-EX Fire Alarm Control Panel Conventional Zone Fire Alarm Control Panel ARCHITECT AND ENGINEER SPECIFICATIONS Four (4) zones expandable to eight (8) zones
RELEASE DEVICES RELEASE DEVICE-WPS MODELS A/B INSTALLATION MANUAL U.L. LISTED CANADIAN LISTED CSFM: :100 GENERAL DESCRIPTION:
RELEASE DEVICES MADE IN THE U.S.A. RELEASE DEVICE-WPS MODELS A/B INSTALLATION MANUAL U.L. LISTED CANADIAN LISTED CSFM: 7300-1418:100 GENERAL DESCRIPTION: S/N: The "WPS" World Power Series, Time Delay Release
INSTALLATION GUIDE XR5FC AND XR5SL COMMERCIAL FIRE PANELS
INSTALLATION GUIDE XR5FC AND XR5SL COMMERCIAL FIRE PANELS MODEL XR5FC/XR5SL COMMAND PROCESSOR INSTALLATION GUIDE FCC NOTICE This equipment generates and uses radio frequency energy and, if not installed
Power Supplies. Overview
Power Supplies Overview Access control provides enhanced security, audit trails, and custom credentials. The power supply is necessary to make the entire system operational. Power supplies offer accurate
KT-100 Door Controller
WARNING: This manual contains information on limitations regarding product use and function and information on the limitations as to liability of the manufacturer. The entire manual should be carefully
30.45 Electric Release PDRP-2001
The PDRP-2001 Fire Alarm Control Panel (FACP) is a six-zone control panel for single and dual hazard deluge and preaction applications. The FACP is compatible with conventional input devices (2-wire or
FIREFLY II PLUS RELEASE DEVICES INSTALLATION MANUAL
FIREFLY II PLUS RELEASE DEVICES INSTALLATION MANUAL MADE IN THE U.S.A. U.L. LISTED CANADIAN LISTED CSFM: 7300-1418:100 GENERAL DESCRIPTION SERIAL NUMBER The Cookson Company FIREFLY II PLUS Time Delay Release
Fire Control/Communicator
Operation and Installation Manual Fire Control/Communicator 1 2 3 4 5 12V AC,20V A, 60Hz or +24V DC 12V AC, 20V A, 60Hz or -24V DC EARTH GND BATTERY - BATTERY + 6 INITIATING A1-7 INITIATING A2-8 INITIATING
Conventional Releasing Control Panel
s Data Sheet Fire Safety Products Conventional Releasing Control Panel Pre-Action Deluge Agent-Releasing Fire System Model TXR-320 Remote configurable Up to two (2) hazard areas Operable with the following:
TECHNICAL DATA. Humidity: 85% Relative Humidity (non-condensing) at 90 F (32 C) maximum.
September 29, 1997 Firecycle III 433 a 1. PRODUCT NAME VIKING Model E-1 Manufactured 1997 Present 2. MANUFACTURED FOR THE VIKING CORPORATION 210 N Industrial Park Road Hastings, Michigan 49058, U.S.A.
SAFEPATH Mass Notification System (SPMNS)
Supersedes February 2016 SAFEPATH Mass Notification System (SPMNS) SP40S SPB-320 SPB-80/4 SPB-160 PS-8-LP SPMNS-MIC SP4Z-A/B Contents Page SPMNS.... 2-4 SPMNS-MIC...3 Expansion Options SAFEPATH 2-zone
Model PAD-3 Distributed Power Module NAC Expander Installation, Operation, and Maintenance Manual
Fire Safety Model PAD-3 Distributed Power Module NAC Expander Installation, Operation, and Maintenance Manual Siemens Building Technologies, Inc. Siemens Building Technologies, Ltd. 8 Fernwood Road 2 Kenview
Models NFPA 1221-A, NFPA 1221-B Public Safety DAS Annunciator Panel. Revision E 61117
Models NFPA 1221-A, NFPA 1221-B Public Safety DAS Annunciator Panel Revision E 61117 CAUTION: (Read This First) This panel has been designed to make it nearly bullet proof to mistakes made when wiring
FIREFORCE 8 NOTIFICATION APPLIANCE CIRCUIT EXPANDER INSTALLATION & OPERATION MANUAL
FIREFORCE 8 NOTIFICATION APPLIANCE CIRCUIT EXPANDER INSTALLATION & OPERATION MANUAL THE GAMEWELL COMPANY PN: 71981 60 PLEASANT STREET ISSUE A ASHLAND, MA 01721 3/22/2001 This page intentionally blank ii
ACSI AO ELECTRIC LATCH RETRACTION CONTROLLER INSTALLATION INSTRUCTIONS I.D. 1089, REV. F
II 1400-2 ACSI 1406-04-AO ELECTRIC LATCH RETRACTION CONTROLLER INSTALLATION INSTRUCTIONS I.D. 1089, REV. F INSTALLATION Transformer Model BE31763001 by Basler Electric, Transformer Model 2010028 by Galaxy
Commercial and Light Industrial Fire Alarm Control Panel
FireSystem 2000 Commercial and Light Industrial Fire Alarm Control Panel Features Easily expandable. All new plug-in board design Two supervised audible circuits Lamp and system trouble circuit test Ground
MADE IN THE U.S.A. ADVANCE FIRE CONTROL MODEL LM21-AFC MANUAL RELEASE DEVICES TEST WEEKLY TO ASSURE PROPER OPERATION OF RELEASE DEVICE/CONTROL PANEL
RELEASE DEVICES MADE IN THE U.S.A. ADVANCE FIRE CONTROL MODEL LM21-AFC MANUAL The LiftMaster Fire Control (LM21-AFC) Release Device/Control Panel is UL/CUL listed normally energized fail-safe device incorporating
Battery charger modules
Battery charger modules D8132 and D8132LT en Installation manual Battery charger modules Notices en 3 1 Notices These instructions cover the installation of the D8132 Battery Charger and the D8132LT Battery
RDM LOCK G Series Electromagnetic Lock. Listings. Standard Features. Ordering Information:
RDM LOCK G-1 1400 Series Electromagnetic Lock The patented 1400 Series Electromagnetic Lock is universal for all types of applications, including outdoor use. The innovative design will reduce installation
Notification Appliance Circuit Module
Notification Appliance Circuit Module D192G en Installation guide Notification Appliance Circuit Module Notices en 3 1 Notices These instructions cover the installation of the D192G Notification Appliance
FireSystem 2000 Commercial and Light Industrial Fire Alarm Control Panel
PROTECTOWIRE FireSystems Features Easily expandable Two supervised audible circuits Lamp and system trouble circuit test Ground fault detection Initiating device circuit (IDC) alarm test Monitors up to
THE "SS90" SERIES RELEASE DEVICES MODEL B2 INSTALLATION MANUAL
S S S S S S S S 90 OLID TATE ECURITIES, INC SOLID STATE FAIL-SAFE UNIT * PATENT PENDING LISTED U 99Y9 RESET L RELEASING DEVICE SOLID STATE SECURITIES, INC. THE "SS90" SERIES RELEASE DEVICES MADE IN THE
Firefly II Multi Voltage RELEASE DEVICES. Firefly II & IIB-MV INSTALLATION MANUAL
Firefly II Multi Voltage RELEASE DEVICES Firefly II & IIB-MV INSTALLATION MANUAL GENERAL DESCRIPTION: S/N The The Cookson Company Firefly II-MV time delay release devices are designed for use on rolling
WARNING. Installation Tip: Try out this unit before installing onto a fire door system. Test and learn the release INTRODUCTION
WARNING 1. CAUTION: Review all installation instructions, procedures, cautions and warnings contained within this manual prior to installing and/or servicing this product. As with all releasing device
HARDwired Installation/ Owner s Manual
HARDwired Installation/ Owner s Manual Use this manual for circuit - Revision L or higher. For Models:,, and Multi-Door Access Controller Wiegand Compatable --R-- Provides Access Control System to manage
TrueAlert Addressable Notification
UL, ULC Approved* TrueAlert Addressable Notification 4009 IDNAC Repeater; Power and Distance Extender Features IDNAC Repeaters provide enhanced power delivery to TrueAlert/ TrueAlert ES addressable notification
D2071A. Operation & Installation Guide Fire Alarm Control Panel
D2071A EN Operation & Installation Guide Fire Alarm Control Panel D2071A Operations & Installation Guide Contents Contents 1.0 Overview... 4 1.1 Communicator... 4 1.2 RFI and Lightning Protection... 4
CONVENTIONAL FIRE ALARM CONTROL UNITS. MR-2300 SERIES Fire Alarm Control Units MEA
CONVENTIONAL FIRE ALARM CONTROL UNITS MR-2300 SERIES Fire Alarm Control Units Description Secutron s MR-2300 Series fire alarm control panels consist of six and twelve zone models which are equipped with
D9412GV2/D7412GV2. Approved Applications Compliance Guide. Control Panels
D9412GV2/D7412GV2 EN Approved Applications Compliance Guide Control Panels D9412GV2/D7412GV2 Approved Applications Compliance Guide Listings and Approvals Listings and Approvals Fire UL Underwriters Laboratories
Release Control Fire Alarm Systems
SYSTEM ABORT PUSH AND HOLD COIL SUPERVISION MODULE (2 AMP) 2081-9046 RED INSTALLATION INSTRUCTIONS 574-437 REV YEL NAC+ MAINTAIN 1/4" SEPARATION BETWEEN POWER LIMITED (RED/) AND NONPOWER S LIMITED (YEL/)
/9308 External Battery Chargers Installation Instructions
4081-9306/9308 External Battery Chargers Installation Instructions Introduction This publication describes the installation procedure for an External Battery Charger used with the 4100U or 4100ES System.
"SS90" SERIES CONTROLS MODEL C INSTALLATION MANUAL
S S S SS O L I D S S90 TATE ECURITIES, INC SOLID STATE FAIL-SAFE UNIT * PATENT PENDING LISTED U L 99Y9 RESET RELEASING DEVICE SOLID STATE SECURITIES, INC. "SS90" SERIES CONTROLS MADE IN THE U.S.A. MODEL
PSN-1000 & PSN 1000(E) Installation Manual
PSN-1000 & PSN 1000(E) Installation Manual Potter Electric Signal Company, LLC St. Louis, MO Customer Service: (866) 240-1870 Technical Support: (866) 956-1211 Fax: (314) 595-6999 www.pottersignal.com
631RF Amp Power Supply
631RF - 1.5 Amp Power Supply Modular Access Control Power Supply Field Selectable 12VDC or 24VDC Output - Standard Dual 12VDC and 24VDC Output - Optional Quality, Performance and Versatility The SDC 631RF
MS-4012/4024 and CMS-4012/4024. Instruction Manual for the. Fire Alarm Control Panels
R 12 Clintonville Road, Northford, CT 06472 Phone: (203) 484-7161 FAX: (203) 484-7118 Instruction Manual for the MS-4012/4024 and CMS-4012/4024 Fire Alarm Control Panels Document 15586 5/11/93 Revision:
Remote NAC Power Supply D7038
Operation and Installation Guide Remote NAC Power Supply D7038 D7038 REMOTE NAC POWER SUPPLY Page 2 2005 Bosch Security Systems Contents Contents 1.0 Overview...5 1.1 Module Control...5 1.1.1 Option Bus
SOLID STATE SECURITIES, INC. THE "SS90" SERIES RELEASE DEVICES MADE IN THE U.S.A. SS90-WPS MODEL A/B INSTALLATION MANUAL
S S S S S S LISTED L * PATENT PENDING S S 90 OLID TATE ECURITIES, INC SOLID STATE FAIL-SAFE UNIT U 99Y9 RESET RELEASING DEVICE SOLID STATE SECURITIES, INC. THE "SS90" SERIES RELEASE DEVICES MADE IN THE
4100U City and Relay Cards Installation Instructions
4100U City and Relay Cards Installation Instructions Introduction This publication describes the installation procedure for the following: 4100-6031/6032 City Circuit Cards 4100-6033 Alarm Relay Card Inspecting
LiftMaster 300 Windsor Drive Oak Brook, IL LiftMaster.com
LiftMaster 300 Windsor Drive Oak Brook, IL 60523 LiftMaster.com O W N E R S M A N U A L MODELS LM21AFCB LM21AFCBVB B ADVANCE FIRE CONTROL RELEASE DEVICE FM APPROVED TABLE OF CONTENTS INTRODUCTION General
MADE IN THE U.S.A. MODELS A/B INSTALLATION MANUAL
RELEASE DEVICES MADE IN THE U.S.A. MODELS A/B INSTALLATION MANUAL U.L. LISTED CANADIAN LISTED CSFM: 7300-1418:100 GENERAL DESCRIPTION: S/N: These Time Delay Release Devices are U.L. Listed, Canadian Listed,
TECHNICAL DATA SHEET CONVENTIONAL FIRE ALARM SYSTEMS Conventional Fire Alarm Control Panel
CVENTIAL ALARM S Features: Description: The LF-CP Series Fire Alarm Control Panel is manufactured based on advanced technology while maintaining high quality during assembly. It is of solid state circuitry
MR-2602 Two Zone Fire Alarm Control Panel
MR-2602 Two Zone Fire Alarm Control Panel Installation Manual Secutron LT-2015 Rev.3 July 2010 Table of Contents 1 Introduction 1.1 The MR-2602 Fire Alarm Control Unit... 11 1.1.1 General features...
This wiring diagram describes circuit connections for all models of the Series Quaestor-SZU Releasing Fire Control
File: S8485 Wiring Diagram This wiring diagram describes circuit connections for all models of the Series Quaestor-SZU Releasing Fire Control Panel. The operation of this product is intended for indoor
Supplement to The PDRP-1001/PDRP-1001A/PDRP-1001E Deluge Preaction Control Panel Manual
Supplement to The PDRP-1001/PDRP-1001A/PDRP-1001E Deluge Preaction Control Panel Manual Replace the following pages of Document Number 50734 (I56-993-01/D770-19-00), Revision B with the corresponding revised
M O D E L S F I R E G A R D M C V ADVANCE FIRE CONTROL RELEASE DEVICE
Cookson 100 Elmwood Avenue Crestwood Industrial Park Mountaintop, PA 18707 Phone: 800-233-8366 Fax: 800-526-0841 CornellCookson.com O W N E R S M A N U A L M O D E L S F I R E G A R D M C F I R E G A R
Model 17A00 Expansion Enclosure
HOME AUTOMATION, INC. Model 17A00 Expansion Enclosure Installation Manual Document Number 17I00-1 Rev A March, 2002 Home Automation, Inc. Model 17A00 Expansion Enclosure Installation Manual Document Number
CONVENTIONAL FIRE ALARM CONTROL PANELS. SFC-200 Series Fire Alarm Control Panels MEA. Features. Description
CONVENTIONAL FIRE ALARM CONTROL PANELS SFC-200 Series Fire Alarm Control Panels Description Summit s SFC-200 Series fire alarm control panels consist of six and twelve zone models which are equipped with
Model 4001 Series Single Channel Controller
Model 4001 Series Single Channel Controller Sierra Monitor Corporation 1991 Tarob Court, Milpitas, CA 95035 (408) 262-6611 (800) 727-4377 (408) 262-9042 - Fax E-Mail: sales@sierramonitor.com Web site:
ECC-50/100(E) Emergency Command Center. General. Features. Emergency Voice Evacuation TYPICAL APPLICATIONS
ECC-50/100(E) Emergency Command Center DF-60734:A4 General Firelite s ECC-50/100 and ECC-50/100E are multipurpose emergency voice evacuation panels for fire applications, mass notification applications,