DECKMA. GmbH. Decksmaschinen und Automation Vertriebs GmbH BEDIENUNGSANLEITUNG FÜR FEUERMELDEANLAGE USER MANUAL FOR FIRE ALARM SYSTEM

Size: px
Start display at page:

Download "DECKMA. GmbH. Decksmaschinen und Automation Vertriebs GmbH BEDIENUNGSANLEITUNG FÜR FEUERMELDEANLAGE USER MANUAL FOR FIRE ALARM SYSTEM"

Transcription

1 DECKMA GmbH Decksmaschinen und Automation Vertriebs GmbH BEDIENUNGSANLEITUNG FÜR FEUERMELDEANLAGE USER MANUAL FOR FIRE ALARM SYSTEM VERSION 03/2003 Tel.: +49 (0)4105 / * DECKMA GmbH * Fax: +49 (0)4105 / info@deckma-gmbh.de * Internet:

2 OPERATING INSTRUCTIONS Fire Alarm Panel GL and GL Type approved by Germanischer Lloyd Certificate No HH DESCRIPTION CHAPTER A. Construction 2 B. Mode of Operation C. Function Test 4-5 D. Reset of Detectors with Memory 5 E. Data 5 F. Detector List 6 G. Installation Instruction 7 - Firealarmpanel flush mounting 8 - Firealarmpanel wall mounting 9 - Connections diagram 10 - GL Certificate 11 Tel.: +49 (0)4105 / * DECKMA GmbH * Fax: +49 (0)4105 / info@deckma-gmbh.de * Internet:

3 A. C O N S T R U C T I O N The Central Cabinet is constructed for desk mounting Page.8 or wall mounting Page. 9. The central cabinet of one unit, containing: 1. Working lamp 2. Two or Six detector groups - 1 accommodation and 1 engine room or 2 accommodation of 2 engine rooms with belonging indication for fire and fault. 3. Internal acoustic sounder 4. Relay for control of fire bell, fire and fault relay with each a set of potential free change over switches. 5. Function test respectively of fire and for fault in the two detector groups. B. M O D E O F O P E R A T I O N The central cabinet is in normal state: The central cabinet is connected to primary and secondary power supply with 24 V DC rated voltage. All lamps are dark, except for the green working lamp mark "Mains". At voltage drop-out from either primary or secondary power supply the following is indicated: A. Green pilot lamp labelled "Mains" flashes B. Internal acoustic signal C. Faulty relay changes over You can reset by the push button labelled "Reset". Then: A. The internal acoustic signal stops B. Fault relay change back to normal condition The green pilot lamp does not stop flashing until both primary and secondary voltage is connected to the central cabinet and you have reset by the push-button labelled "Reset".

4 Mode of operation of the detector groups: The detector groups are working after the one-loop-principle where the detectors are parallel connected to the line and the line is finished with an end resistor. The end resistor determines the current of rest in the loop. If the fault has stopped the light in the yellow lamp mark "Fault" of the group in question stops, if the fault is stationary, nothing happens. The yellow fault lamp of the group in question will not stop lighting until the fault has been repaired and the button mark "Reset" has been pushed. Fire Alarm: Fire Alarm occurs when a detector has been released. At release of a detector a resistance is connected parallel on the line (parallel with the end resistor) then the current (no-signal current) will increase. Fire Alarm is indicated by: A. Internal acoustic signal B. External acoustic signal C. Fire relay changes over D. Light in the red fire lamp of the group in question You can reset by pushing the button mark "Reset", then: A. The internal acoustic signal stops B. The external acoustic signal stops C. Fire relay changes back to normal condition D. If the detector is in normal state, light in the red fire lamp of the group in question stops lighting - if the Detector is in alarm state, nothing happens. The red fire lamp of the group in question will stop lighting until the detector is in normal state and the button mark "Reset" has been pushed. If the central cabinet looses it is working voltage, the green working lamp mark "Mains" goes out.

5 C. F U N C T I O N T E S T Test of fire is achieved by pushing the button placed below the red fire lamp. Indication as mentioned in the passage about fire alarm. Test of fault in the detector loop is achieved by pushing the button placed below the yellow fault lamp. Normal state. A fixed current of rest passes through the loop. Both the fault and fire alarm lamps are dark. Fault Alarm If a loop is broken the current of rest ceases and the group in question will indicate "Fault". Fault is indicated by A. Internal acoustic signal B. Fault relay changes over C. Light in the yellow lamp mark "Fault" of the group in question You can see reset by pushing the button mark "Reset", then: A. The internal acoustic signal stops B. Fault relay changes back to normal condition Indication as mentioned in the passage about fault alarm. Test to fire alarm bells are achieved at the same time as test of fire is done. Test of power supply fault: Is obtained by switching-off of primary and secondary power supply of by removing primary of secondary fuse in central cabinet. D. RESET OF DETECTOR WITH ELECTRICAL MEMORY Detectors with electrical memory and which are connected with the central cabinet can be reseted by pushing the function test button "Fault" of the group in question, then te detector loop is broken and the connected detectors are reseted.

6 E. D A T A E1. Voltage The operating voltage is 2x 24 V DC +30% -25 % E2. Current consumption Normal state, detectors not incl. app. 100 ma Alarm state, detector and bells not incl. app. 250 ma Detector, normal state app. 0,1 ma Detector, alarm state app. 40 ma E3. Limits Max. load of fire bell output Max. number of detectors per group Max. number of man call points 2,0 A 25 pcs unlimited

7 F. D E T E C T O R L I S T Engine room Opt. Smoke detector Heat detector Type 130A AS Type SLR-EM+ YBM-R4M+ MBB-1 Type 215A AS Type DCD-1EM+ YBM-R4M+ MBB-1 60 C Type DCD-1REM+ YBM-R4M+ MBB-1 90 C Manual call point Type NS-CPWP WR 4072 UV-Flame Detector Type 810A AS Type NS DUV Accommodation Opt. Smoke detector Type 130A A Surface Type 130A UH Flushm. Type SLR-EM+ YBM-R4M. Heat detector Type 215 A A Surface Type 215 A UH Flushm. DCD-1EM+ YBM-R4M 60 C DCD-1REM+ YBM-R4M 90 C Manual call point Type NS-CP WR 2072

8 G. I N S T A L L A T I O N I N S T R U C T I O N Installation instruction for automatic fire alarm and fire indication system, type (2) GL. 1. The central is mounted on the navigation bridge as the screw for the 2 upper holes in the cabinet are screwed in the bulkhead until approx. 3 mm from the bulkhead surface. The cabinet is "pulled" down over the screws and kept to the bulkhead by means of internal mounted plate springs. Further the cabinet is fastened with a third screw at the bottom in the middle. 2. The detector group/s is/are connected with the central cabinet; remember the end resistance at the last detector in each group; and so are fire bells and voltage supply 24 V. The central cabinet is put back into normal state. 3. The system is ready for tests, which are to be done according to the check list, see this.

9

10

11

12 Type Approval Certificate This is to certify that the undernoted product(s) has/have been tested in accordance with the relevant requirements of the GL Type Approval System. Certificate No HH Company DECKMA GmbH Bahnhofstraße 79 D Rosengarten-Klecken Product Description Fire Detection System Type Environmental Category Technical Data / Range of Application C, EMC1 Power supply: 2 x 24 V DC Connection: up to 6 conventional fire detection lines Loop voltage: 24 V DC Output: 1 c/o contact each for failure and fire alarm Contact rating: 2 A 24 V DC Degree of protection: IP 42 Test Standard Guidelines for the Performance of Type Approvals, Edition 2003 Documents Manual: Circuit diagram: 821.5A S529, S525, S526, S527 Drawing: S530, S528, Test reports: DASA , EMV Services 01/ , EMV Services 03/ Remarks None Valid until Page 1 of 1 File No. I.A.01 Hamburg, Type Approval Symbol J. Wittburg T. Huthoff This certificate is issued on the basis of "Regulations for the Performance of Type Tests, Part 0, Procedure". Internet Publication: GL-Approvals

Precept Marine Control Panel Application Guide

Precept Marine Control Panel Application Guide Precept Marine Control Panel Application Guide Contents Page 1.0 Cabinet Specifications 2 2.0 Panel Hardware Specifications 5 3.0 Panel Configuration 8 4.0 Technical Specifications 8 5.0 Battery Sizes

More information

BA AFMS3000 Operating instructions

BA AFMS3000 Operating instructions 20140208BA AFMS3000 Operating instructions DECKMA GMBH FIREALARMSYSTEM AFMS 3000 ALARM IN SEQU. MAINS DISCO NNECT PRE - ALARM FIRE TEST MODE A 1 2 3 FAULT A RESET 4 7 5 6 8 9 0 Version history Version

More information

Intelligent Security & Fire Ltd

Intelligent Security & Fire Ltd OPERATIONAL NOTES FOR CONCEPT FIRE PANEL. NOTE ON NEW FIRE PANELS, POSITION 1 ON THE SIX WAY INTERNAL OPTION SWITCH IS TURNED ON, DISABLING THE ZONAL SOUNDERS. TO ENABLE ZONAL SOUNDERS TURN OFF. Operation

More information

System 800 Addressable Fire Detection & Alarm System

System 800 Addressable Fire Detection & Alarm System SECTION 5: page 1 Section 5: System 800 Addressable Fire Detection & Alarm System SECTION 5: page 3 10 reasons to specify 800 1 Plug and Play A user friendly panel not requiring special software tools

More information

User manual and installation instruction Control for Fire Ventilation RV / RV 24-32

User manual and installation instruction Control for Fire Ventilation RV / RV 24-32 User manual and installation instruction Control for Fire Ventilation RV 24-24 / RV 24-32 Fire ventilation Comfort ventilation 24VDC max. 24/32A 2 Actuator outputs 1 Fire ventilation group, 2 comfort groups

More information

Fire Alarm System FMS3000 Installation Instructions

Fire Alarm System FMS3000 Installation Instructions Fire Alarm System FMS3000 Installation Instructions Version history Version Date Author Checked Note 0.1 16/09/13 JB TK Produced based on the old operating instructions 0.2 27/09/16 TK STO Configuration

More information

DICTATOR Hold-Open Systems for Hazardous Areas

DICTATOR Hold-Open Systems for Hazardous Areas DICTATOR for Hazardous Areas Products to be used in hazardous areas obviously have to meet special demands. The European ATEX directives (first the EN 94/9/EG and then the directive 2014/34/ EU) brought

More information

CONTROL DEVICE SLIDETRONIC HD

CONTROL DEVICE SLIDETRONIC HD CONTROL DEVICE SLIDETRONIC HD to control gravity self-closing fire gates Producer: Somati system s.r.o. Jihlavská 510/2c 664 41 Troubsko, okr.brno - venkov Tel.: 547 427 011 Fax: 547 427 013 E-mail: export@somati-system.cz

More information

QA16 Addressable System

QA16 Addressable System QA16 Addressable System Operating Manual HORING LIH INDUSTRIAL CO., LTD. www.horinglih.com QA16 System Characteristics Each loop can connect with 250 devices. Easy system programming through PC to panel.

More information

Technical Manual. Level Alarm Unit CARLA & WIDS

Technical Manual. Level Alarm Unit CARLA & WIDS CARLA & WIDS Technical Manual SAS au Capital de 2 158 244-444 871 933 R.C.S. Bourges - APE : 2651B Headquarter : 9, rue Isaac Newton - 18000 Bourges - France Technical Manual CARLA for Tankers Cargo Tanks

More information

Control Panel Engineering and Commissioning Instructions

Control Panel Engineering and Commissioning Instructions Twinflex - V3 Fire Detection & Alarm System Control Panel Engineering and Commissioning Instructions (TO BE RETAINED BY THE COMMISSIONING ENGINEER) 26-0338 Issue 9 Fike s policy is one of continual improvement

More information

Sigma. K1000 Series 1, 2, 4 & 6 Zone Fire Control Panels. Operation and Maintenance Manual. Man-1048 Issue 05 October 2009

Sigma. K1000 Series 1, 2, 4 & 6 Zone Fire Control Panels. Operation and Maintenance Manual. Man-1048 Issue 05 October 2009 Sigma K1000 Series 1, 2, 4 & 6 Zone Fire Control Panels Operation and Maintenance Manual Man-1048 Issue 05 October 2009 CONTENTS Contents... Page Safety & Installation...2 Installation - continued...3

More information

ZIOU/230 - MAINS IO INSTRUCTION MANUAL

ZIOU/230 - MAINS IO INSTRUCTION MANUAL Description ZIOU/230 - MAINS IO INSTRUCTION MANUAL The Mains IO Modules are fully monitored loop powered devices which permit the interfacing of third party equipment with the Fire Alarm Control panel

More information

Product Data Sheet. Remote Terminals. Features:

Product Data Sheet. Remote Terminals. Features: Remote Terminals Product Data Sheet Features: Based around two core products, the Mx- 4010 Remote Display Terminal (RDT) and the fully functional Mx-4020 Remote Control Terminal (RCT). Both remote terminals

More information

BSR Addressable Fire Detection control panel. Installation operation manual

BSR Addressable Fire Detection control panel. Installation operation manual BSR-1116 Addressable Fire Detection control panel Installation operation manual ATTENTION!!! READ THE MANUAL BEFORE THE INSTALLATION AND PAY ATTENTION TO PARAGRAPH 2.6.3 AND 2.6.4. Page 2 from 36 Contents

More information

Rectifier RC-series. Manual RC-series English MA doc. Manual Wall and 19 English

Rectifier RC-series. Manual RC-series English MA doc. Manual Wall and 19 English Rectifier RC-series Manual RC-series English Manual Wall and 19 English Presentation The RC-series is a rectifier for either directly powering the load or for use together with batteries. It is designed

More information

High bay PIR presence detector 1-10V dimming. PIR Sensor. IR Receiver. Light Level Sensor. Status LEDs. IR Receiver

High bay PIR presence detector 1-10V dimming. PIR Sensor. IR Receiver. Light Level Sensor. Status LEDs. IR Receiver Product Guide EBDSPIR-HB-AD High bay PIR presence detector 1-10V dimming Overview The EBDSPIR-HB-AD PIR (passive infrared) presence detector provides automatic control of lighting loads with optional manual

More information

BS-100 DYFI. Installation handbook. Protecting environment, life and property... P-BS100/DCE

BS-100 DYFI. Installation handbook.  Protecting environment, life and property... P-BS100/DCE BS-100 DYFI Protecting environment, life and property... P-BS100/DCE P-BS100/DCE/Doc/961023 2 Autronica Fire and Security AS Contents Please observe! This handbook contains installation instructions for

More information

Addressable and Conventional Fire Protection

Addressable and Conventional Fire Protection Addressable and Conventional Fire Protection Simply reliable F I R E P R O T E C T I O N The MAGPro and Fireline systems has been created to balance performance, reliability and aesthetics whilst being

More information

EBDSPIR-PRM-VFC & EBDSPIR-PRM-VFC-NC

EBDSPIR-PRM-VFC & EBDSPIR-PRM-VFC-NC Product Guide EBDSPIR-PRM-VFC & EBDSPIR-PRM-VFC-NC Ceiling PIR presence/absence detector Overview The EBDSPIR-PRM-VFC PIR (passive infrared) presence detector provides automatic control of lighting loads

More information

CONTENTS Introduction and Characteristics. 1 Fire Alarm System Assembly Diagram.. 2 Fire Alarm Signal Flow Chart.. 2 Panel Descriptions 3 Standard

CONTENTS Introduction and Characteristics. 1 Fire Alarm System Assembly Diagram.. 2 Fire Alarm Signal Flow Chart.. 2 Panel Descriptions 3 Standard CONTENTS Introduction and Characteristics. 1 Fire Alarm System Assembly Diagram.. 2 Fire Alarm Signal Flow Chart.. 2 Panel Descriptions 3 Standard Detector Wiring Method. 4 Method of Wiring.. 5 Wiring

More information

Panel Mounted Fault Annunciator Series

Panel Mounted Fault Annunciator Series Panel Mounted Fault Annunciator Series BSM / USM Panel-mounted fault annunciator Annunciators for panel mounting with 8, 16, 24, 32, 40 and 48 signal inputs Status retention of inputs and sequence in case

More information

MWS5. Miniature Microwave Presence Detector (standalone) Product Guide. Overview. Features

MWS5. Miniature Microwave Presence Detector (standalone) Product Guide. Overview. Features Product Guide MWS5 Miniature Microwave Presence Detector (standalone) Overview The MWS5 series of miniature microwave presence detectors provide automatic control of lighting loads with optional manual

More information

Intelligent Security & Fire Ltd

Intelligent Security & Fire Ltd full installation, commissioning and operating manuals can be downloaded from www.haes-systems.co.uk combined addressable / conventional fire alarm control panel User Guide Approved Document No. MFBU-04

More information

PNC 1000 SERIES 2, 4, 8 Zone Fire Alarm Control Panel

PNC 1000 SERIES 2, 4, 8 Zone Fire Alarm Control Panel PNC 1000 SERIES 2, 4, 8 Zone Fire Alarm Control Panel INSTALLATION, OPERATION AND MAINTENANCE MANUAL Version: CN-PM-1000.VER1.1-12/2012 EN54 INFORMATION In accordance with EN 54-2 clause 13.7, the maximum

More information

compact office 24V compact office 24V Lux

compact office 24V compact office 24V Lux Presence detector compact office 24V compact office 24V Lux Art. Nr. 201 4 000 Art. Nr. 201 4 001 D F GB E I NL S N FIN DK Bedienungsanleitung 2 Notice d utilisation 21 Installation manual 40 Manual de

More information

Ceiling Microwave presence/absence detector 12-24V AC/DC

Ceiling Microwave presence/absence detector 12-24V AC/DC MWS3A-PRM-LV Product Guide Ceiling Microwave presence/absence detector 12-24V AC/DC Overview The MWS3A-PRM-LV Microwave presence detector provides automatic control of low voltage loads including lighting

More information

Ceiling Microwave presence detector - DALI / DSI 12-24V AC/DC. Microwave Sensor. IR Receiver. Light Level Sensor. Status LEDs.

Ceiling Microwave presence detector - DALI / DSI 12-24V AC/DC. Microwave Sensor. IR Receiver. Light Level Sensor. Status LEDs. MWS6-DD-LV Product Guide Ceiling Microwave presence detector - DALI / DSI 12-24V AC/DC Overview The MWS6-DD-LV microwave presence detector provides automatic control of lighting loads with optional manual

More information

Parameterisable compact fault annunciator with permanent display

Parameterisable compact fault annunciator with permanent display Parameterisable compact fault annunciator with permanent display FSM 10 Drop-flap fault annunciator 31.08.2010 Permanent display even on power failure Compact module for 10 alarms Supply and alarm signal

More information

ED820-24V MODEL INSTRUCTION MANUAL. fire DETECTOR

ED820-24V MODEL INSTRUCTION MANUAL. fire DETECTOR ED820 24V MODEL fire DETECTOR INSTRUCTION MANUAL Address: Enigma House, Enigma Business Park, Malvern, Worcestershire, WR14 1GD Tel: 44 (0)1684 891500 Fax: 44 (0)1684 891600 Email: sales@electronicdevices.co.uk

More information

Installation, Operating and Maintenance Manual

Installation, Operating and Maintenance Manual STATUS ZONES CONTROLS FIRE FAULT DISABLED FIRE 1 2 3 4 5 6 7 8 TEST FAULT DISABLED 1 5 BUZZER SILENCE RESET 1 2 TEST 2 6 LAMP TEST 3 SUPPLY 3 7 SYSTEM FAULT 4 8 SOUNDERS ACTIVATE/ SILENCE 4 FAULTS INSTRUCTIONS

More information

U ser's Guide PC6010

U ser's Guide PC6010 User's Guide PC6010 Quick Reference Guide This manual is for Basic and Advanced users. Each of these types of user can access a different set of functions. The and symbols next to the title of each procedure

More information

TECHNICAL DATA SHEET CONVENTIONAL FIRE ALARM SYSTEMS Conventional Fire Alarm Control Panel

TECHNICAL DATA SHEET CONVENTIONAL FIRE ALARM SYSTEMS Conventional Fire Alarm Control Panel CVENTIAL ALARM S Features: Description: The LF-CP Series Fire Alarm Control Panel is manufactured based on advanced technology while maintaining high quality during assembly. It is of solid state circuitry

More information

Input module, input/output modules

Input module, input/output modules Sinteso / Cerberus PRO Input module, input/output modules FDCI222, FDCIO222, FDCIO224 Input module and input/output modules for the automatically addressed detector line Input module FDCI222: Four monitored

More information

compact office 24V compact office 24V Lux

compact office 24V compact office 24V Lux Presence detector compact office 24V compact office 24V Lux Art. Nr. 201 4 000 Art. Nr. 201 4 001 D F GB E I NL S N FIN DK Bedienungsanleitung 2 Notice d utilisation 22 Installation manual 42 Manual de

More information

FX NET FIRE DETECTION SYSTEM Installation and commissioning manual

FX NET FIRE DETECTION SYSTEM Installation and commissioning manual FX NET FIRE DETECTION SYSTEM Installation and commissioning manual Read this manual carefully before installation and commissioning! Installation and commissioning must be performed according to this manual.

More information

M1000 Alarm Annunciator

M1000 Alarm Annunciator Data Sheet Alarm Annunciator Reliable Supervision and Control 10 inputs with LED indications Supports both NO/NC input contacts 10 open collector outputs Built-in siren relay Text label for alarm descriptions

More information

High bay PIR presence detector DALI / DSI dimming. PIR Sensor. IR Receiver. Light Level Sensor. Status LEDs. IR Receiver

High bay PIR presence detector DALI / DSI dimming. PIR Sensor. IR Receiver. Light Level Sensor. Status LEDs. IR Receiver EBDSPIR-HB-DD Product Guide High bay PIR presence detector DALI / DSI dimming Overview The EBDSPIR-HB-DD PIR (passive infrared) presence detector provides automatic control of lighting loads with optional

More information

FX FIRE DETECTION SYSTEM

FX FIRE DETECTION SYSTEM FX FIRE DETECTION SYSTEM Installation and commissioning manual Read this manual carefully before installation and commissioning! Installation and commissioning must be performed according to this manual.

More information

ISOMETER IR425. Insulation monitoring device for unearthed AC/DC control circuits (IT systems)

ISOMETER IR425. Insulation monitoring device for unearthed AC/DC control circuits (IT systems) ISOMETER IR425 Insulation monitoring device for unearthed AC/DC control circuits (IT systems) IR425-D4_D00039_04_D_XXEN/05.2017 ISOMETER IR425 Insulation monitoring device for unearthed AC/DC control circuits

More information

Installation and user manual for the FX range of fire panels. 1, 2, 4 and 8 zone panels

Installation and user manual for the FX range of fire panels. 1, 2, 4 and 8 zone panels Installation and user manual for the FX range of fire panels 1, 2, 4 and 8 zone panels Contents Panel installation 3 Panel connections 3 Wiring connection drawings 4 Panel facilities 6 Installation check

More information

Key-Operated Switch GMA 41 / GMA 44 SW. Operation Manual

Key-Operated Switch GMA 41 / GMA 44 SW. Operation Manual Key-Operated witch GMA 41 / GMA 44 W Operation Manual Table of contents Page Introduction... 4 Key function... 4 Distinction of GMA 41/44 W models... 4 Relays... 5 P.C. boards of GMA 41/44 W... 7 Terminal

More information

HA-263K HA-263D. OWNER'S MANUAL Installation And Operation 8-ZONE ALARM CONTROL PANEL FOR HOME AND OFFICE PROTECTIONS OPEN THE CABINET FOR SERVICE

HA-263K HA-263D. OWNER'S MANUAL Installation And Operation 8-ZONE ALARM CONTROL PANEL FOR HOME AND OFFICE PROTECTIONS OPEN THE CABINET FOR SERVICE D (OPERATION) INITIATE A DYNAMIC BATTERY TEST The system tests the back-up battery once every 24 hours. The owner can initiate a dynamic battery test at any time with the following codes while the system

More information

Operating Manual UV Monitor UVT 18

Operating Manual UV Monitor UVT 18 Operating Manual UV Monitor UVT 18 Software Version 1.2 stand: 21/11/2016 UV - Monitor UVT 18 Intended use The signal monitor UVT 18 was developed to control small- and medium-sized UV systems and is fully

More information

Silencer Preheater unit Electric post-heating unit Water circulated post-heating unit CO 2 sensor %RH sensor Pressure difference switch LON converter

Silencer Preheater unit Electric post-heating unit Water circulated post-heating unit CO 2 sensor %RH sensor Pressure difference switch LON converter VALLOX Product Code: 3158400 L 3158410 R SILENCER (OPTIONAL) INSTRUCTIONS FOR USE AND MAINTENANCE WATER CIRCULATED POST-HEATING UNIT (OPTIONAL) ELECTRIC POST-HEATING UNIT (OPTIONAL)) PREHEATER (OPTIONAL)

More information

Insulation fault evaluator EDS460-DG

Insulation fault evaluator EDS460-DG Insulation fault evaluator for localising insulation faults in DC IT systems with a number of branch circuits where high system leakage capacitances are involved Preliminary data sheet TDB108021en/09.2008

More information

Input module, input/output module

Input module, input/output module Sinteso / Cerberus PRO Input module, input/output module FDCI221, FDCIO221 Input module and input/output module for the automatically addressed detector line Input module FDCI221: Monitorable contact input

More information

OPERATION AND ALARM PANELS

OPERATION AND ALARM PANELS OPERATION AND ALARM PANELS Memory and blink function Flat cable connection between the master and slave panel Programmable for normally open or normally closed alarm Quick and easy installation Individually

More information

Flame detector FD 2011 / FD 2012

Flame detector FD 2011 / FD 2012 only for existing plants EN 298 / EN 230 2003 19 PCB 3HE / 6TE DIN 41612 2-chanal system continuous operation ionisation with common or separate spark and supervision electrode intermitted UV-mode integrated

More information

Ceiling PIR presence detector DALI / DSI dimming. PIR Sensor. IR Receiver. Light Level Sensor. Status LEDs. PIR Sensor.

Ceiling PIR presence detector DALI / DSI dimming. PIR Sensor. IR Receiver. Light Level Sensor. Status LEDs. PIR Sensor. Product Guide EBDSM-DD Ceiling PIR presence detector DALI / DSI dimming Overview The EBDSM-DD PIR (passive infrared) presence detector provides automatic control of lighting loads with optional manual

More information

Sita200plus. 200detectors. Single loop analogue addressable System

Sita200plus. 200detectors. Single loop analogue addressable System Single loop analogue addressable System Fast short circuit isolator in every device 15 combinations of smoke & heat detection modes Loop length up to 2km long with spurs INTELLIGENT FIRE TECHNOLOGY A D

More information

LC1 & 2. Fire Alarm Panel 6\VWHPLQVWDOODWLRQRSHUDWLQJ PDLQWHQDQFH LQVWUXFWLRQV

LC1 & 2. Fire Alarm Panel 6\VWHPLQVWDOODWLRQRSHUDWLQJ PDLQWHQDQFH LQVWUXFWLRQV LC1 & 2 Fire Alarm Panel 6\VWHPLQVWDOODWLRQRSHUDWLQJ PDLQWHQDQFH LQVWUXFWLRQV ZIRCONLC1 One Zone Conventional Fire Panel ZIRCONLC2 Two Zone Conventional Fire Panel Compliant with EN54-2:1998 & EN54-4:1998

More information

EBDSPIR-PRM-2CH, EBDSPIR-PRM-2CH-NC

EBDSPIR-PRM-2CH, EBDSPIR-PRM-2CH-NC Product Guide EBDSPIR-PRM-2CH, EBDSPIR-PRM-2CH-NC Ceiling PIR presence/absence detector 2 channel Overview The EBDSPIR-PRM-2CH PIR (passive infrared) presence detector provides automatic control of lighting

More information

SWARCO TRAFFIC SYSTEMS GMBH. TDD1-MW Traffic Detector User Manual TDD1-MW_BE_00

SWARCO TRAFFIC SYSTEMS GMBH. TDD1-MW Traffic Detector User Manual TDD1-MW_BE_00 TDD1-MW Traffic Detector User Manual TDD1-MW_BE_00 CONTENTS 1 Introduction... 3 1.1 About this manual... 3 1.2 Usage according to regulations... 3 1.3 Label... 4 1.4 Symbols... 4 1.5 Safety instructions...

More information

operating device LOD , 144x72mm designed for retrofit

operating device LOD , 144x72mm designed for retrofit BNWAS le guardian 225 sm electrics operating device LOD 2.24.., 44x72mm designed for retrofit connecting module LCM 2.24.. over 5 installations easy and comfortable use simple connections to all peripheral

More information

PräsenzLight PräsenzLight PräsenzLight A.. PräsenzLight A..

PräsenzLight PräsenzLight PräsenzLight A.. PräsenzLight A.. Presence detector PräsenzLight 180.. PräsenzLight 360.. PräsenzLight 180-100A.. PräsenzLight 360-100A.. D F GB E I NL S N FIN DK Bedienungsanleitung 2 Notice d utilisation 26 Installation manual 50 Manual

More information

WIO200 Water In Oil measuring instrument

WIO200 Water In Oil measuring instrument WIO200 Water In Oil measuring instrument You have made the right decision by choosing a measuring instrument from PAJ Systemteknik. Many customers buy our high standard products every year. There are at

More information

ISOSCAN EDS460-DG. Insulation fault locator for DC IT systems with high system leakage capacitances

ISOSCAN EDS460-DG. Insulation fault locator for DC IT systems with high system leakage capacitances ISOSCAN Insulation fault locator for DC IT systems with high system leakage capacitances _D00108_00_D_XXEN/05.2015 ISOSCAN Insulation fault locator for DC IT systems with high system leakage capacitances

More information

IFP-2.32 Manual 1) DESCRIPTION ICAS FIRE PANEL IFP 2.32

IFP-2.32 Manual 1) DESCRIPTION ICAS FIRE PANEL IFP 2.32 1) DESCRIPTION IFP-2.2 Manual IFP-2.8 and IFP-2.2 is a microprocessor controlled Fire Panel with 2 loops intended either for privat Homes & Apartments or larger installations. The two loops are balanced

More information

FDOOT221, FDO221, FDT221

FDOOT221, FDO221, FDT221 Sinteso C-LINE FDOOT221, FDO221, FDT221 Automatic fire detectors For the automatically addressed detector bus FDnet The ideal fire detector for every application Signal processing with detection algorithms

More information

500-IDx Conventional Fire Detectors with Siren!

500-IDx Conventional Fire Detectors with Siren! 00-IDx Conventional Fire s with Siren! Fig. : 00-IDx, x: O=Optical, I=Ionic, T=Temp. Description ICAS Model 00-IDx is a system detector series to be connected with a standard EN classified fire central.

More information

GMA4100-DP. Control Panel. Operation Manual. Worldwide Supplier of Gas Detection Solutions

GMA4100-DP. Control Panel. Operation Manual. Worldwide Supplier of Gas Detection Solutions Worldwide upplier of Gas Detection olutions GfG Instrumentation 1194 Oak Valley Drive, uite 20 Ann Arbor, MI 48108 800-959-0329 tel 734-769-1888 fax email: info@gfg-inc.com GMA4100-DP Control Panel Operation

More information

Saffire User & Installation Manual. IMPORTANT This manual should be left with the panel after installation.

Saffire User & Installation Manual. IMPORTANT This manual should be left with the panel after installation. Saffire+ 8-12 User & Installation Manual IMPORTANT This manual should be left with the panel after installation. We reserve the right to change product specifications without prior notice. Copyright VRC

More information

VITMR-EBDSPIR-PRM. PIR Presence/Absence Detector IR with Ceiling Rose. Product Guide. Overview. Features

VITMR-EBDSPIR-PRM. PIR Presence/Absence Detector IR with Ceiling Rose. Product Guide. Overview. Features Product Guide VITMR-EBDSPIR-PRM PIR Presence/Absence Detector IR with Ceiling Rose Overview The VITMR-EBDSPIR-PRM PIR (passive infrared) presence detector provides automatic control of lighting loads.

More information

MANUAL Oil Level Sensor

MANUAL Oil Level Sensor PROCESS AUTOMATION MANUAL Oil Level Sensor KVF-104-PF ISO9001 0102 With regard to the supply of products, the current issue of the following document is applicable: The General Terms of Delivery for Products

More information

KSUF CONTROL AND MONITORING UNIT. Description. Installation Designed for wall installation.

KSUF CONTROL AND MONITORING UNIT. Description. Installation Designed for wall installation. KSUF can then be grouped into a maximum of four fire zones. One output for fan control. CONTROL AND MONITORING UNIT Valid from week of manufacture 06/2014 Description The KSUF is a control and monitoring

More information

TCM-2 Thyristor Control Module DATA SHEET

TCM-2 Thyristor Control Module DATA SHEET TCM-2 Thyristor Control Module TCM-2 Thyristor DATA DATA SHEET Control Module DATA SHEET Alarm panels Type Compact Q96 design Extremely easy push-button programming (no jumpers or the like) Individual

More information

ABLOY DA460 SWING DOOR OPERATOR. Installation and commissioning manual

ABLOY DA460 SWING DOOR OPERATOR. Installation and commissioning manual ABLOY DA460 SWING DOOR OPERATOR Installation and commissioning manual APPROVALS / STANDARDS 73/23/EEC (Low Voltage directive) 93/68/EEC (Low Voltage directive) 89/336/EEC (EMC directive) Statement of fire

More information

5, SE GÅNGHESTER,

5, SE GÅNGHESTER, KSUB Control and monitoring unit Valid from week of manufacture 48/2005 Description The KSUB is a control and monitoring unit designed to control various types of fire/smoke dampers and fans in a flexible

More information

GM420. Digital Ground Continuity Relay For AC Systems. Technical Bulletin NAE /

GM420. Digital Ground Continuity Relay For AC Systems. Technical Bulletin NAE / 3 GM20 Digital Ground Continuity Relay For AC Systems Technical Bulletin NAE03230 / 0.20 GM20 Ground continuity monitor For AC systems Description The GM20 monitors the loop resistance of ground conductors

More information

FLAME AMPLIFIER MODULE 3001

FLAME AMPLIFIER MODULE 3001 SYSTEM 3000 / 4000 FLAME AMPLIFIER MODULE 3001 TECHNICAL DESCRIPTION EDITION TB_3001_EN_REV03 BFI Automation Mindermann GmbH, Eggerscheidter Str. 57, D-40883 Ratingen Phone +49 (0) 2102 96 82 0, Fax +49

More information

EBMHS (standard & slim-line PSU)

EBMHS (standard & slim-line PSU) Product Guide EBMHS (standard & slim-line PSU) Miniature HS PIR Presence Detector (luminaire fitting) Overview The EBMHS series of miniature PIR (passive infrared) presence detectors provide automatic

More information

ECO-IR 360C NT. Presence detector. Art. Nr Bedienungsanleitung 2. Notice d utilisation 22. Installation manual 42

ECO-IR 360C NT. Presence detector. Art. Nr Bedienungsanleitung 2. Notice d utilisation 22. Installation manual 42 Presence detector ECO-IR 360C NT Art. Nr. 202 0 400 D F GB E I NL S N FIN DK Bedienungsanleitung 2 Notice d utilisation 22 Installation manual 42 Manual de instrucciones 62 Istruzioni per l uso 82 Gebruikershandleiding

More information

Remote alarm indicator and test combination MK2430

Remote alarm indicator and test combination MK2430 Dipl.-Ing. W. Bender GmbH & Co. KG Londorfer Str. 5 35305 Grünberg Tel.: 040 807-0 Fax: 040 807-259 Remote alarm indicator and test combination MK2430 Remote alarm indicator and test combination with LC

More information

Panel Mounted Fault Annunciator Series

Panel Mounted Fault Annunciator Series Panel Mounted Fault Annunciator Series BSM / USM Panel-mounted fault annunciator Annunciators for panel mounting with,,,, 0 and signal inputs Storage of the last state of inputs and sequence in the case

More information

OilSET-1000 (12 VDC)

OilSET-1000 (12 VDC) Labkotec Oy Myllyhaantie 6 FI-33960 PIRKKALA FINLAND Tel: +358 29 006 260 Fax: +358 29 006 1260 Internet: www.labkotec.fi 20.03.2009 1/11 OilSET-1000 (12 VDC) Oil Separator Alarm Device Copyright 2009

More information

LINETRAXX VME420. Multi-functional relay for overvoltage, undervoltage and frequency monitoring in AC/DC systems with external supply voltage

LINETRAXX VME420. Multi-functional relay for overvoltage, undervoltage and frequency monitoring in AC/DC systems with external supply voltage LINETRAXX VME420 Multi-functional monitoring relay for undervoltage, overvoltage and frequency monitoring in AC/DC systems with separate supply voltage VME420_D00026_01_D_XXEN/06.2016 LINETRAXX VME420

More information

MWS6-PRM. Ceiling microwave presence/absence detector. Product Guide. Overview. Features

MWS6-PRM. Ceiling microwave presence/absence detector. Product Guide. Overview. Features Product Guide MWS6-PRM Ceiling microwave presence/absence detector Overview The MWS6-PRM microwave presence detector provides automatic control of lighting loads with optional manual control. The MWS6-PRM

More information

Ceiling PIR HS presence detector 1-10V, low temperature. PIR Sensor. IR Receiver. Light Level Sensor. Status LEDs. IR Receiver

Ceiling PIR HS presence detector 1-10V, low temperature. PIR Sensor. IR Receiver. Light Level Sensor. Status LEDs. IR Receiver Product Guide EBDHS-AD-LT30 Ceiling PIR HS presence detector 1-10V, low temperature Overview The EBDHS-AD-LT30 PIR (passive infrared) presence detector provides automatic control of lighting loads with

More information

Residual current monitor RCM470LY/RCM475LY. for TN and TT systems (AC and pulsating DC currents)

Residual current monitor RCM470LY/RCM475LY. for TN and TT systems (AC and pulsating DC currents) Residual current monitor RCM470LY/RCM475LY for TN and TT systems (AC and pulsating DC currents) TDB401003en/03.2010 Residual current monitor RCM470LY Residual current monitor for TN and TT systems (AC

More information

Master Code Arming Auto-Bypass Option - Home-Away Arming Entry Delay Off Arming

Master Code Arming Auto-Bypass Option - Home-Away Arming Entry Delay Off Arming Master Code The 4 digit Master Code is used for arming and disarming the system, for programming additional access codes, and for changing other features. The Master Code will be supplied to you by your

More information

1.7. Insulation fault evaluators EDS460/490 EDS461/491

1.7. Insulation fault evaluators EDS460/490 EDS461/491 Bender Incorporated 700 Fox Chase, Coatesville PA 1930 Tel.: (800) 356-466 Fax: (610) 383-7100 Insulation fault evaluators EDS460/490 EDS461/491 Insulation fault evaluators with display and control function

More information

EBDSPIR-PRM-LV Product Guide

EBDSPIR-PRM-LV Product Guide EBDSPIR-PRM-LV Product Guide Ceiling PIR presence/absence detector 12-24V AC/DC Overview The EBDSPIR-PRM-LV PIR (passive infrared) presence detector provides automatic control of low voltage loads including

More information

Intelligent Security & Fire Ltd

Intelligent Security & Fire Ltd Sigma CP (K and T Series) and Sigma CP-A Conventional Fire Control Panel (K11020M2, K11040M2, K11080M2) (T11020M2, T11040M2, T11080M2) (KA11020M2, KA11040M2, KA11080M2) User Manual Man-1082 Issue 05 August

More information

DUAL MONITORED INPUT/OUTPUT UNIT BN-305-2

DUAL MONITORED INPUT/OUTPUT UNIT BN-305-2 DUAL MONITORED INPUT/OUTPUT UNIT BN-305-2 Interactive fire detection systems Product Datasheet Features Interactive For interfacing and controlling external units to Autronica s interactive fire detection

More information

FDS229-R / FDS229-A Alarm sounder with supplementary optical indication

FDS229-R / FDS229-A Alarm sounder with supplementary optical indication FDS229-R / FDS229-A Alarm sounder with supplementary optical indication For the automatic addressable detector bus C-NET and FDnet Cerberus PRO Sinteso Alarm sounder with 11 tonalities selectable, 2 activation

More information

Building Technologies. FDUL221 en Line tester operating instructions for electricians

Building Technologies. FDUL221 en Line tester operating instructions for electricians FDUL221 en Line tester operating instructions for electricians 1. Intended use The FDUL221 line tester is used to diagnose an addressed detector line in FDnet/C-NET. During diagnosis, the detector line

More information

Operating Manual VMD420

Operating Manual VMD420 Operating Manual VMD420 Voltage and frequency monitor for monitoring of 3(N)AC systems up to 0...500 V for undervoltage and overvoltage and under and overfrequency Software version: D238 V2.2x Power in

More information

HOKKIM INTEGRATED AMF CONTROL BOARD MANUAL FOR MODELS: HAMF-8 AND HAMF-4

HOKKIM INTEGRATED AMF CONTROL BOARD MANUAL FOR MODELS: HAMF-8 AND HAMF-4 HOKKIM INTEGRATED AMF CONTROL BOARD MANUAL FOR MODELS: HAMF-8 AND HAMF-4 INTRODUCTION Thank you for purchasing the Hokkim Integrated Automatic Mains Failure Control Board model HAMF- 8 or HAMF-4. We shall

More information

MSM - Expansion modules

MSM - Expansion modules MSM - Expansion modules Transistor- and relay modules for devices of the MSM-product family Free assignment of the output arrays to the input arrays of the annunciator Triggering of relays or transistor

More information

The complete conventional fire warning system

The complete conventional fire warning system The complete conventional fire warning system www.espuk.com MAG2P 2 Zone Fire Panel 2 programmable zones Active end of line monitoring and head removal 30 fire detectors per zone Unlimited number of call

More information

DATASHEET. Burner control unit FDA 601x

DATASHEET. Burner control unit FDA 601x EN 298 / EN 230 2012 19 PCB 100x160mm 3HE/8TE socket DIN 41612 2-channel microprocessor controlled program air valve control for heating / cooling preventilation continuous operation with ionisation intermittent

More information

Installation / Monitoring Technique

Installation / Monitoring Technique Installation / Monitoring Technique INFOMSTER Common larm System, us Connection New- / First- /Common Signal nnunciator RP 5994, RP 5995 Replacements for: N 5969, N 5970, N 597 055005 Circuit Diagrams

More information

Analogue Dimming Microwave Presence/Absence Detector

Analogue Dimming Microwave Presence/Absence Detector Product Guide MWS3A-AD Analogue Dimming Microwave Presence/Absence Detector Contents Section Contents Page 1 Dimensional information 1 2 Description and operation 2 3 Wiring & Fixing 3 4 Installation 3

More information

1.7. Insulation fault evaluators EDS460/490 EDS461/491

1.7. Insulation fault evaluators EDS460/490 EDS461/491 Dipl.-Ing. W. Bender GmbH & Co. KG Londorfer Str. 65 35305 Grünberg Tel.: 06401 807-0 Fax: 06401 807-59 Insulation fault evaluators EDS460/490 EDS461/491 Insulation fault evaluators with display and control

More information

FC330A-ECO Auto-addressing analogue 1-Loop fire detection panel

FC330A-ECO Auto-addressing analogue 1-Loop fire detection panel FC330A-ECO Auto-addressing analogue 1-Loop fire detection panel Synova TM Commissioning in no time thanks to automatic address allocation Auto-addressing makes setting dip switches unnecessary Automatic

More information

GMA 301. Operation Manual. Worldwide Supplier of Safety Solutions. Part Number

GMA 301. Operation Manual. Worldwide Supplier of Safety Solutions. Part Number Worldwide Supplier of Safety Solutions GfG Instrumentation 1194 Oak Valley Drive #20 Phone: 734-769-0573 Fax: 734-769-1888 E-Mail: info@gfg-inc.com Internet: www.gfg-inc.com GMA 301 Operation Manual Part

More information

INSTRUCTION MANUAL. DECKMA HAMBURG GmbH. Type OMD-12. Oil-in-Water Monitor

INSTRUCTION MANUAL. DECKMA HAMBURG GmbH. Type OMD-12. Oil-in-Water Monitor INSTRUCTION MANUAL Oil-in-Water Monitor Type OMD-12 DECKMA HAMBURG GmbH Kieler Straße 316, D-22525 Hamburg Tel.: ++49 40 54 88 76-0, Fax: ++49 40 54 88 76-10, email: post@deckma.com IMPORTANT NOTICE Replacement

More information

LAE10 LFE10. Use. Series 02

LAE10 LFE10. Use. Series 02 ISO 00 Flame Safeguards 7 7 LAE L Series 02 Supplementary data sheets 772 and 773 Flame safeguards for burners with intermittent operation. For safety reasons - self-test of flame supervision circuit,

More information

C Note! LGI16... Burner Controls. Building Technologies

C Note! LGI16... Burner Controls. Building Technologies 7 786 Burner Controls LGI16... Burner controls For use on industrial furnaces For burners in continuous operation Without fan control and air pressure supervision Flame supervision - with QR53... / QR55,

More information