A.U.C. 180 March 15, 1997 PROCEDURES FOR FIRES AND EMERGENCIES IN MANHOLES AND/OR RELATED INSTALLATIONS 1. GENERAL

Size: px
Start display at page:

Download "A.U.C. 180 March 15, 1997 PROCEDURES FOR FIRES AND EMERGENCIES IN MANHOLES AND/OR RELATED INSTALLATIONS 1. GENERAL"

Transcription

1 A.U.C. 180 PROCEDURES FOR FIRES AND EMERGENCIES IN MANHOLES AND/OR RELATED INSTALLATIONS 1. GENERAL 1.1 The Officer in Command at the scene shall determine the cause and severity of the fire or emergency. Using signal 10-25, this officer shall transmit particulars to the dispatcher for immediate notification to the utility company concerned: Manhole or Transformer Fire or Emergency Any type of manhole or transformer fire or emergency. Without Code: Situation other than as described in Codes 1, 2, 3, or 4. Code 1: Code 2: Code 3: Code 4: Note: Fire has extended from a manhole, conduit, or transformer into a building. Fire has blown one or more manhole covers, or smoke is issuing from a manhole under pressure. Smoke is seeping from a manhole. Fire or smoke condition from a transformer at any location, i.e., pole, vault, room, etc. Utility Company will dispatch an emergency crew immediately upon receipt of a Code 1 or Code 4 signal. 1.2 Should conditions change after original report, a supplementary report shall be transmitted immediately to describe the existing conditions in accordance with the above code. 1.3 Utility company will dispatch an emergency crew immediately upon receipt of a Code 1 or Code 4 signal. If all crews are engaged, utility company will detach a crew operating at other than a Code 1 or Code 4 signal and direct such crew to respond immediately. 1.4 Units should be alert to the possibility that a manhole/transformer incident could have damaged the adjacent gas piping. If an odor of natural gas is encountered at these incidents, the dispatcher must be notified to request the immediate response of a utility's gas crew in addition to their electric crew. Additionally, downed overhead primary and secondary wires have the potential to damage underground gas piping. All gas piping (plastic, steel, cast iron and copper) can be impacted by burning, arching or smoldering electric cables. 2. OPERATIONAL GUIDELINES 2.1 The area shall be cordoned off to vehicular and pedestrian traffic. All apparatus shall be clear of the area in a safe location. Area shall be taped off. This marks the danger area for civilians and FD personnel. 1

2 2.2 Inspect electrical services in surrounding buildings. Units should use carbon monoxide meters when performing these inspections. Possible extension. This may also be the cause of the problem. 2.3 Members shall not attempt to move vehicles located in the danger area. 2.4 Precautionary hoselines shall be stretched as necessary. Units should not operate into manholes unless requested by a Con Edison employee at the scene. If requested to place water into a manhole, do not direct the stream directly into the manhole. Instead, let water flow or pour into the manhole. Use a fog nozzle to reduce or prevent any shock hazard. 2.5 The Officer in Charge shall order response of a utility company emergency crew and shall request the expected time of arrival. 2.6 When operations are within the capability of a single unit, the Officer in Command may leave one unit (preferably an Engine Company) to await the arrival of the emergency crew. If the expected time of arrival is more than 30 minutes, the Officer in Charge, based on evaluation of existing conditions, may order one of the following: A. The unit remaining on the scene may respond to assigned alarms received via department radio; one member shall be left at the scene. B. One member shall be left at the scene and the unit shall return to quarters. Company officers shall provide relief for members. C. When a member is left at the scene, the company officer shall at frequent intervals contact the dispatcher for re-notification of the utility company. D. The manhole shall be protected by traffic cones and tape, and all units placed in service. 2.7 During periods of multiple incidents within an area, the following actions may be authorized by the deputy chief in charge: One or more units shall be relieved from response assignments and utilized as follows: A. A member of the unit shall be left at the scene of each incident. B. The officer and the chauffeur shall remain with the apparatus to perform surveillance of the incident locations. C. Battalion chiefs shall provide for necessary relief of units or members. D. Deputy Chiefs may authorize the use of messenger vans and spare cars for travel and shelter of members at incident locations. 2.8 Members left at the scene of an incident shall: A. Be alert to changing conditions and shall call for assistance when necessary. B. Maintain surveillance of surrounding properties. C. Prevent entry to area by pedestrian or vehicular traffic. D. Obtain information necessary for required reports, under the direction of the immediate superior officer. 2 Rev. 10/04/11

3 2.9 Officers in Command shall request adequate Police Department response, depending upon the scope and severity of the fire or emergency. Such assistance shall be utilized where deemed necessary and with particular reference to sections 2.1, 2.3, 2.6.B, 2.6.D, 2.7.A, 2.8.C and Note #5 of this circular. NOTES: 1. Members are reminded that explosions in manholes are not uncommon and that they have caused serious burns to members of this department. 2. Members should not pull covers off electrical manholes at manhole fires or if a manhole fire is in the area. It is the responsibility of utility crews to open manhole covers at these incidents. Pulling covers may cause an explosion by mixing air with the gaseous products of combustion in the presence of an ignition source e.g., manhole fire and/or electric arcing. Note: This does not change Department policy of pulling electric manhole covers under certain circumstances at gas emergencies. (See Training Bulletin Emergencies 2). Be cautious of the PELLET EFFECT from the dirt and gravel that is trapped on the sides of the cover if an explosion occurs. 3. Explosions can take place after considerable time has elapsed and when the conditions in the manhole appear dormant. When a cover blows, do not run. Keep your eyes on the cover so you can approximate where it will land. 4. Serious explosions have also occurred in adjacent manholes that are connected by conduits with the originally involved manhole. 5. When operating at manhole emergencies, the location of traffic control boxes must be taken into consideration when deciding the size and location of the "AREA OF DANGER". The smoke and gases from a manhole incident can travel up the hollow pole of a nearby light stanchion and at times accumulate with considerable pressure. The gaseous mixture may be ignited by a spark inside the control box. 6. Hose lines stretched in the street to prevent involvement of adjacent properties should be positioned at a point beyond the predictable limits of fire or explosion damage. 7. Close and continuous supervision is required to keep citizens and Fire Department personnel at a safe distance and avoid injuries. 8. Where conditions indicate the electric lines in a building are becoming hot, hose lines shall be stretched and a thorough examination made. 9. Fire Department representation at the scene shall continue until all dangerous conditions are alleviated, or until informed by utility company emergency crew at scene that Fire Department presence is no longer required. Information for the required reports shall be obtained from the utility company personnel at the scene. 3 Rev. 04/19/11

4 3. TRANSFORMER VAULTS Members of this Department must recognize that underground transformer vaults present a highly volatile situation when encountered. All members must exercise extreme caution when these incidents occur. The use of full Personal Protection Clothing and SCBA, even in light smoke conditions, should be stressed when operating. 3.1 A word about sub-surface transformer vaults: A. CON EDISON distributes electricity throughout New York City by means of both overhead and underground power lines. Overhead transformers are easily recognizable since they are bolted to the tops of poles in the many residential areas throughout the city except in the Borough of Manhattan (See REFERENCE # 2). Underground transformers are not easily noticed since they are located in subsurface concrete structures. CON EDISON has stated that there are approximately 75,800 transformers citywide. The subsurface structures, known as transformer vaults, come in various sizes but a typical vault is approximately 12' x 4'. These vaults are installed either in the street or the sidewalk below grade level. B. To prevent subsurface transformers from overheating, slotted gratings are usually installed over the vaults to allow air to circulate and cool the transformer. Vaults in the street sometimes have solid gratings since heavy vehicles may cause damage to the weaker slotted gratings. The gratings are usually rectangular in shape. C. The transformers convert primary voltage (27,000 Volts) to secondary voltage (120 Volts) for use by CON EDISON customers. Either of these voltages can cause fatal injury if not handled properly. Some vaults contain submersible equipment, meaning that they function properly even if the vault is filled with water. Other vaults contain non-submersible equipment and must have a sump pump installed to prevent flooding. D. All transformers that are in the vaults contain dielectric oil, which acts as a coolant, in amounts ranging from 200 gallons to 600 gallons. The trade name for the newer oil that CON EDISON is presently using is SUN-OIL or MOBIL-X. This oil contains PCBs in the range of PPM and therefore is considered a Non-PCB Transformer. However, CON EDISON still has in use vault transformers that are considered PCB-CONTAMINATED TRANSFORMERS that contain PPM of PCBs. Note: The New York City Fire Department considers a transformer with any amount of PCBs as a PCB Transformer. Operate accordingly. 3.2 Hazard potential: A. Transformer Vaults can present many hazards to civilians and fire personnel. B. Environmental and physical dangers presented by transformer vaults include the presence of carbon monoxide or other gases in high concentrations, PVC in wire insulation, PCBs in transformers, high vapor pressures and the possibility of explosions. 4 Rev. 04/19/11

5 C. The possibility of asbestos may also be present, although the Environmental Protection Agency has mandated that any asbestos present must be removed in electrical vault systems. D. The greatest hazard of course is the amount of electricity that is contained in these vaults. 3.3 Safety precautions for operations: A. Units are to operate in accordance with guidelines as set forth in sections 1 & 2 of this bulletin & A.U.C. 266 PCBs Incidents B. Added emphasis shall be placed on the following: Cordon off and secure an area a safe distance from the vault for members and apparatus. It is not necessary for members to closely examine these vaults. Remember the potential dangers involved and the likelihood of an explosion that exists. There is inherent danger for serious injury, if the latter occurs. (See REFERENCE # 1) Full use of Personal Protective Clothing (PPC) and SCBA shall be adhered to. This type of incident can escalate very easily and unexpectedly. Be prepared to protect yourself. Stretch a precautionary handline. Due to the amount of flammable liquid contained in these transformers, Engine Companies shall also be prepared to initiate a foam operation if the need arises. Examination of surrounding exposures for extension of fire and/or gases through electrical conduits which service electricity to buildings. The main service panel is usually located in the cellar or basement. Units instructed to initiate this examination shall be guided by the following: 1) Teams of two members shall be used to examine an exposure. Each member shall be fully equipped with PPC, SCBA and Handi- Talkie. In addition, they shall carry a Carbon Monoxide Monitor. Readings shall be taken in the Meter Room, surrounding rooms, and on first floor, if necessary. High levels of CO have been found in exposures at these incidents. 2) Due to nature of these incidents and possible duration, it will be necessary to re-examine these exposures on a periodic basis. C. Monitor the situation and await arrival of Con Edison. 3.4 Remember the primary consideration at these types of incidents is the safety of civilians and fire personnel. BY ORDER OF THE FIRE COMMISSIONER AND CHIEF OF DEPARTMENT 5 Rev. 04/19/11

6 REFERENCE # 1 (FORMERLY SAFETY MESSAGE # 88) 1. INTRODUCTION The following narrative is an excerpt from a report on an unusual fire incident involving a Con Ed transformer vault. On Arrival Units Found A Light Smoke Condition Issuing From A Sidewalk Transformer Vault Adjacent To A 40 Story High Rise Office Building. Conditions At The Vault Deteriorated Rapidly With A Heavy Smoke Condition And Two Explosions Emanating From The Vault. After The Explosions, Conditions Some What Subsided And A Smoldering Fire Resulted Until Con Edison Cut The Power. Electricity To The High Rise Office Building Was Cut And An Examination Revealed No Extension. Units Stood By While Con Ed Made An Examination Of The Vault. Con Ed Found That The Cause Of The Fire Was The Theft Of Copper Bus Bars In The Vault. The Fire Involving The Vault Was Routine. The Cause Of The Fire Is Unusual In That Someone Entered This Vault And Remove Con Edison Equipment With The Power Still On. A Con Edison Official At The Scene Stated That The Theft Of These Copper Bus Bars Has Taken Place In The Past. 2. CONSIDERATIONS 2.1 Units arriving at the above incidents should be aware that there is a possibility that the perpetrator of these crimes has been trapped and/or electrocuted in the vault during the theft. 2.2 Units shall be guided by A.U.C For operational procedures for fires and emergencies in this type of installation. 2.3 Members are not to enter these vaults until Con Edison has made their examination. 2.4 Con Edison will make the determination that the vault is safe for entry, if necessary, by F.D. personnel. 2.5 F.D. personnel receiving this authorization will conduct a cursory search of the vault for victims. 6

7 REFERENCE # 2 (FORMERLY SAFETY MESSAGE # 56) Pole Mounted Transformers Con Edison does not test pole mounted transformers for PCB content. Almost all of Con Edison's overhead transformers are not, or were not, designed to be PCB liquid filled. They are mineral oil transformers. However, due to past storage and/or servicing practices some of these transformers have become PCB contaminated, i.e., PPM PCB. A small percentage of these transformers have attained levels of 500 PPM PCB or greater which classifies them as PCB transformers. All new transformers being installed by Con Edison as replacements for existing ones and/or new installations are non PCB transformers. All officers at operations involving overhead pole transformers shall insure that all proper precautions are taken to provide for the safety of all members on the scene as outlined in All Units Circular No. 266 (Revised) and Fire Tactics and Procedures, Hazardous Materials 2. 7

ESCONDIDO FIRE DEPT TRAINING MANUAL Section Truck Module Page 1 of 6 Utilities Electrical Emergencies Revised

ESCONDIDO FIRE DEPT TRAINING MANUAL Section Truck Module Page 1 of 6 Utilities Electrical Emergencies Revised Truck Module Page 1 of 6 ELECTRICAL EMERGENCIES Classification of Voltage For firefighting purposes, voltage can be considered in one of two classes, either high or low. As a general rule, the larger the

More information

TRANSMISSION AND DISTRIBUTION SUBSTATIONS

TRANSMISSION AND DISTRIBUTION SUBSTATIONS A.U.C. 338, ADDENDUM 2 October 20, 2011 1. INTRODUCTION 1.1 Transmission Substations receive 345,000 volts from generating stations and then step it down to 138,000 volts for delivery to Distribution Substations.

More information

A.U.C. 150 March 31, 2004 IROQUOIS NATURAL GAS PIPELINE AT CON EDISON HUNTS POINT FACILITY 1. DESCRIPTION

A.U.C. 150 March 31, 2004 IROQUOIS NATURAL GAS PIPELINE AT CON EDISON HUNTS POINT FACILITY 1. DESCRIPTION March 31, 2004 IROQUOIS NATURAL GAS PIPELINE AT CON EDISON HUNTS POINT FACILITY 1. DESCRIPTION 1.1 The Iroquois pipeline consists primarily of a single 24" (OD) high strength steel pipeline, various valves

More information

DCN: ENGINE COMPANY OPERATIONS CHAPTER 4 March 15, 1997 FIRE SCENE OPERATIONS

DCN: ENGINE COMPANY OPERATIONS CHAPTER 4 March 15, 1997 FIRE SCENE OPERATIONS DCN: 4.05.01 ENGINE COMPANY OPERATIONS CHAPTER 4 March 15, 1997 FIRE SCENE OPERATIONS 4. FIRE SCENE OPERATIONS 4.1 FIREFIGHTING OBJECTIVES 4.1.1 The objectives of firefighting are to protect life and property

More information

Structural Firefighting Policy

Structural Firefighting Policy Section Policy Number Effective Date C C1 09/01/2015 Policy Issued As Reference Policy # B1-B4, B6, C2-C10, C12, D1, and TBD Subject Approval: Policy Donald Norman, Fire Chief PURPOSE The purpose of this

More information

Fire ground electrocution

Fire ground electrocution Fire ground electrocution By VINCENT DUNN Ret Chief FDNY To survive firefighting, firefighters must know how other firefighters have died fighting fires. Electrocution is one cause of fire ground death.

More information

Carbon Monoxide Poisoning

Carbon Monoxide Poisoning National Grid Group Training Exercise #4 This training reflects industry best practices but does not replace your organization s SOPs/SOGs. This material can be utilized to provide a perspective as you

More information

Truro Police Department. Fire Emergencies. Policy Number: OPS-9.02 Effective Date: June 1, 2000 REFERENCE:

Truro Police Department. Fire Emergencies. Policy Number: OPS-9.02 Effective Date: June 1, 2000 REFERENCE: Truro Police Department Fire Emergencies Policy Number: OPS-9.02 Effective Date: June 1, 2000 REFERENCE: Accreditation Standards: Mass. Gen. Law: Chap. 89 sec 7A, 268 sec 32A Other: Policy: It is the policy

More information

San Ramon Valley Fire Protection District GREEN SHEET

San Ramon Valley Fire Protection District GREEN SHEET San Ramon Valley Fire Protection District GREEN SHEET Informational Summary Report of Serious San Ramon Valley Injury, Illness, Accident and Near-Miss Incident Near-Miss Incident Firefighters in close

More information

FIREFIGHTER II MANIPULATIVE SKILL OBJECTIVES

FIREFIGHTER II MANIPULATIVE SKILL OBJECTIVES 10 FIREFIGHTER II MANIPULATIVE SKILL OBJECTIVES GENERAL 1- Demonstrate procedures for assuming and transferring command at an emergency scene, utilizing an incident management system. REFERENCE: NFPA 1001,

More information

Radio Communications Guideline

Radio Communications Guideline Page 3-1 Radio Communications Guideline This Radio Communications Guideline shall provide a plan for uniform procedures in radio communications. Sections covered in this guideline will cover guidelines

More information

Outline. Standards of Coverage. ICS Features 2/12/2016 ICS

Outline. Standards of Coverage. ICS Features 2/12/2016 ICS Outline Fire Department Operations Standards of Coverage What does it look like in your town? Standard Assignment House Fire, Commercial Fire, Smoke in Structure Incident Command System Arrival Reports

More information

Emergency Action Plan for Sycamore House 3818 Winding Way

Emergency Action Plan for Sycamore House 3818 Winding Way Psychological Services Center Emergency Action Plan for Sycamore House 3818 Winding Way Xavier University November 17, 2006 Ken Grossman Page 1 11/7/2013 Table of Contents Emergency Action Plan Introduction...

More information

Table of Contents. EMERGENCY PROCEDURES Policy 190

Table of Contents. EMERGENCY PROCEDURES Policy 190 Table of Contents EMERGENCY PROCEDURES Policy 190 1. TRAINING ON EMERGENCY PROCEDURES... 2 2. EVACUATION PLAN... 2 2.1 Purpose... 2 2.2 Initiation Of Evacuation Alarm... 2 2.3 Evacuation Procedures...

More information

CARBON MONOXIDE (CO)

CARBON MONOXIDE (CO) DCN: 3.02.16 FIRE TACTICS AND PROCEDURES HAZARDOUS MATERIALS 4 March 15, 1997 (CO) 1. INTRODUCTION 1.1 Due to increased public awareness and the availability of carbon monoxide (CO) detectors for the home,

More information

GREEN SHEET. Los Angeles Fire Department. Informational Summary Report of Serious LAFD Injuries, Illnesses, Accidents and Near-Miss Incidents

GREEN SHEET. Los Angeles Fire Department. Informational Summary Report of Serious LAFD Injuries, Illnesses, Accidents and Near-Miss Incidents GREEN SHEET Los Angeles Fire Department Informational Summary Report of Serious LAFD Injuries, Illnesses, Accidents and Near-Miss Incidents FIREFIGHTER INJURY SOLANO AVENUE VEHICLE FIRE This report is

More information

SCALES NW EMERGENCY ACTION PLAN

SCALES NW EMERGENCY ACTION PLAN Purpose Each SCALES NW, INC location shall have a written Emergency Action Plan, appropriate to the hazards of the workplace, in order to respond to an emergency that may require rescue or evacuation.

More information

Emergency Action Plan For Alumni Center 1507 Dana Avenue

Emergency Action Plan For Alumni Center 1507 Dana Avenue University Relations Division Department of Physical Plant Human Resources Community Building Institute Office of University Communications and Administrative Office Building Emergency Action Plan For

More information

Austin Independent School District Police Department Policy and Procedure Manual

Austin Independent School District Police Department Policy and Procedure Manual Austin Independent School District Police Department Policy and Procedure Manual Policy 4.08A Emergency/Non-Emergency Response - Vehicle I. POLICY (7.15.1; 7.26.1 TPCAF) The AISD Police Department s primary

More information

Xavier Field Office Emergency Action Plan. For. Xavier Field Office Dana Avenue

Xavier Field Office Emergency Action Plan. For. Xavier Field Office Dana Avenue Xavier Field Office Emergency Action Plan For Xavier Field Office 1601 Dana Avenue January 30, 2012 Ken Grossman Staff 10/22/2013 Page 1 Table of Contents Emergency Action Plan Introduction... 3 Responsibilities...

More information

FIRE EVACUATION PLAN PRATT STREET PARKING GARAGE AND ATHLETIC CENTER POLICE FIRE MEDICAL EMERGENCY

FIRE EVACUATION PLAN PRATT STREET PARKING GARAGE AND ATHLETIC CENTER POLICE FIRE MEDICAL EMERGENCY University of Maryland FIRE EVACUATION PLAN PRATT STREET PARKING GARAGE AND ATHLETIC CENTER POLICE - 711 FIRE - 711 MEDICAL EMERGENCY - 711 Anyone discovering excessive heat, smoke, or fire inside your

More information

Enactment Date: Rapid Intervention Team and RIT Officer

Enactment Date: Rapid Intervention Team and RIT Officer Section 1: Scope Section 2: Team Requirements Section 3: Establishment of RIT Section 4: Reporting to the Scene Section 5: Scene Size-Up Section 6: Primary RIT Tasks Section 7: RIT Activation Procedures

More information

Chapter 17 Test. Directions: Write the correct letter on the blank before each question.

Chapter 17 Test. Directions: Write the correct letter on the blank before each question. Chapter 17 Test Name: Date: Directions: Write the correct letter on the blank before each question. Objective 1: Describe initial factors to consider when suppressing structure fires. 1. Which strategy

More information

EMERGENCY RESPONSE GUIDEBOOK South Hamilton Campus February 2016 Reviewed and Updated

EMERGENCY RESPONSE GUIDEBOOK South Hamilton Campus February 2016 Reviewed and Updated EMERGENCY RESPONSE GUIDEBOOK South Hamilton Campus February 2016 Reviewed and Updated Emergency Phone Numbers To report any police, fire, or medical emergency, call: Using campus phone: 911 (You will be

More information

SUBJECT FIRE OPERATIONS GUIDELINE (F.O.G.) #F510 Issued: 1/2014 Last Revision: 1/2014 Pages: 9 By Order Of: J.S. Thompson, Fire Chief

SUBJECT FIRE OPERATIONS GUIDELINE (F.O.G.) #F510 Issued: 1/2014 Last Revision: 1/2014 Pages: 9 By Order Of: J.S. Thompson, Fire Chief THE COLONY FIRE DEPARTMENT FIRE OPERATIONS GUIDELINE SUBJECT FIRE OPERATIONS GUIDELINE (F.O.G.) #F510 Issued: 1/2014 Last Revision: 1/2014 Pages: 9 By Order Of: J.S. Thompson, Fire Chief Review Reviewed

More information

Based on NFPA 1001: Standard for Fire Fighter Professional Qualifications, 2013 Edition.

Based on NFPA 1001: Standard for Fire Fighter Professional Qualifications, 2013 Edition. Based on NFPA 1001: Standard for Fire Fighter Professional Qualifications, 2013 Edition. Revised 02/10/2017 Alabama Fire College Firefighter II Instructional JPR Verification Sheet Full Name: Fire Department:

More information

University of Maryland FIRE EVACUATION PLAN NATIONAL DENTAL MUSEUM POLICE FIRE MEDICAL EMERGENCY Anyone discovering excessive heat,

University of Maryland FIRE EVACUATION PLAN NATIONAL DENTAL MUSEUM POLICE FIRE MEDICAL EMERGENCY Anyone discovering excessive heat, University of Maryland FIRE EVACUATION PLAN NATIONAL DENTAL MUSEUM POLICE - 711 FIRE - 711 MEDICAL EMERGENCY - 711 Anyone discovering excessive heat, smoke, or fire inside your building will immediately

More information

Emergency Action Plan for

Emergency Action Plan for Kuhlman Hall Emergency Action Plan for Kuhlman Hall 3824 Ledgewood Drive Xavier University November 9, 2006 Ken Grossman Page 1 11/7/2013 Table of Contents Emergency Action Plan Introduction... 3 Responsibilities...

More information

Risk Management Services

Risk Management Services Risk Management Services FIRE PROTECTION IMPAIRMENT PROGRAM Introduction Fire protection systems represent a significant capital investment for organizations. Companies want to make sure that they are

More information

IMPORTANCE of FIREGROUND VENTILATION PRACTICES and DYNAMICS IN FIREFIGHTING (PART I)

IMPORTANCE of FIREGROUND VENTILATION PRACTICES and DYNAMICS IN FIREFIGHTING (PART I) IMPORTANCE of FIREGROUND VENTILATION PRACTICES and DYNAMICS IN FIREFIGHTING (PART I) By Lt. Mike Mason As we have stated previously there are two prominent areas that drive every fire ground and that is

More information

Essentials of Fire Fighting, Fourth Edition Transition Guide. Chapter 1: The History of the Fire Service (Essentials, Chapter 1)

Essentials of Fire Fighting, Fourth Edition Transition Guide. Chapter 1: The History of the Fire Service (Essentials, Chapter 1) Essentials of Fire Fighting, Fourth Edition Transition Guide Chapter 1: The History of the Fire Service (Essentials, Chapter 1) This chapter covers the history of the fire service, the organization of

More information

FIRE SAFETY FOR OFFICE WORKERS

FIRE SAFETY FOR OFFICE WORKERS 2746 FIRE SAFETY FOR OFFICE WORKERS Leader s Guide ERI Safety Videos FIRE SAFETY FOR OFFICE WORKERS This easy-to-use Leader s Guide is provided to assist in conducting a successful presentation. Featured

More information

STOCKTON POLICE DEPARTMENT GENERAL ORDER OPERATION OF EMERGENCY VEHICLE SUBJECT FROM: CHIEF ERIC JONES TO: ALL PERSONNEL

STOCKTON POLICE DEPARTMENT GENERAL ORDER OPERATION OF EMERGENCY VEHICLE SUBJECT FROM: CHIEF ERIC JONES TO: ALL PERSONNEL STOCKTON POLICE DEPARTMENT GENERAL ORDER OPERATION OF EMERGENCY VEHICLE SUBJECT DATE: February 21, 2018 NO: FROM: CHIEF ERIC JONES TO: ALL PERSONNEL INDEX: Emergency Vehicle Response Emergency Vehicle

More information

Emergency Notification Plan. Developed By: Cleveland State University Police Department Office of Emergency Management

Emergency Notification Plan. Developed By: Cleveland State University Police Department Office of Emergency Management Emergency Notification Plan Developed By: Cleveland State University Police Department Office of Emergency Management 216.687.2184 Rev.2.0 June, 2015 EMERGENCY NOTIFICATION, RESPONSE AND EVACUATION The

More information

CONSOLIDATED EDISON CO. OF NEW YORK INC. 4 IRVING PLACE NEW YORK, N.Y DISTRIBUTION ENGINEERING CABLE SYSTEMS

CONSOLIDATED EDISON CO. OF NEW YORK INC. 4 IRVING PLACE NEW YORK, N.Y DISTRIBUTION ENGINEERING CABLE SYSTEMS CONSOLIDATED EDISON CO. OF NEW YORK INC. 4 IRVING PLACE NEW YORK, N.Y. 10003 DISTRIBUTION ENGINEERING CABLE SYSTEMS SPECIFICATION EO-4082 REVISION 2 May, 1998 OPERATION AND MAINTENANCE OF CONDUIT SYSTEM,

More information

UC Irvine Environmental Health & Safety TITLE: FIRE WATCH AND OUT OF SERVICE NOTIFICATION

UC Irvine Environmental Health & Safety TITLE: FIRE WATCH AND OUT OF SERVICE NOTIFICATION SECTION: UC Irvine Environmental Health & Safety TITLE: FIRE WATCH AND OUT OF SERVICE NOTIFICATION INITIATOR: DALE SAUNDERS REVISION DATE: September 2015 1. Program Description 2. Scope 3. Definitions

More information

"EVACUATION PROCEDURES"

EVACUATION PROCEDURES PRESENTER'S GUIDE "EVACUATION PROCEDURES" Part of the "SAFETY MEETING KIT" Series Quality Safety and Health Products, for Today...and Tomorrow OUTLINE OF MAJOR PROGRAM POINTS OUTLINE OF MAJOR PROGRAM POINTS

More information

EMERGENCY PREPAREDNESS: EVACUATIONS

EMERGENCY PREPAREDNESS: EVACUATIONS GUIDELINE I. EMERGENCY PREPAREDNESS: EVACUATIONS 1.0 PURPOSE 1.1 To provide guidance for the safe and orderly evacuation of faculty, staff, students and visitors to the University of Pennsylvania campus

More information

ADVANCED EXTERIOR FIRE BRIGADE MEMBER MANIPULATIVE SKILL OBJECTIVES GENERAL

ADVANCED EXTERIOR FIRE BRIGADE MEMBER MANIPULATIVE SKILL OBJECTIVES GENERAL ADVANCED EXTERIOR FIRE BRIGADE MEMBER MANIPULATIVE SKILL OBJECTIVES GENERAL 1- Utilize a pre-incident plan so that the industrial fire brigade member implements the responses detailed by the plan. NFPA

More information

A.U.C. 207 March 15, 1997 SUBWAY AND RAILROAD TRACK OPERATIONS 1. INTRODUCTION

A.U.C. 207 March 15, 1997 SUBWAY AND RAILROAD TRACK OPERATIONS 1. INTRODUCTION March 15, 1997 SUBWAY AND RAILROAD TRACK OPERATIONS 1. INTRODUCTION This Department, on many occasions, will be called upon to operate in the track areas of the numerous subway and railroad systems that

More information

Travis County Emergency Services District #1 Standard Operating Guidelines

Travis County Emergency Services District #1 Standard Operating Guidelines Section Policy Number Effective Date C C8 07/05/2015 Policy Issued As Reference Policy # Overhaul B1, C1, TBD Subject Approval: Overhaul Donald Norman, Fire Chief PURPOSE This standard operating guideline

More information

Emergency Procedures for Clients

Emergency Procedures for Clients Emergency Procedures for Clients We are happy to welcome you to our facility, and we want you to know that your event is very important to us. We plan to do everything possible to ensure that your event

More information

NATIONAL FIRE PROTECTION ASSOCIATION Fourth Survey of the Needs of the U. S. Fire Service

NATIONAL FIRE PROTECTION ASSOCIATION Fourth Survey of the Needs of the U. S. Fire Service NATIONAL FIRE PROTECTION ASSOCIATION Fourth Survey of the Needs of the U. S. Fire Service MAKE IT EASY Complete the Survey Online www.nfpa.org/2015needsassessment **NFPA FDID top left corner** **PASSWORD

More information

Travis County Emergency Services District #1 Standard Operating Guidelines

Travis County Emergency Services District #1 Standard Operating Guidelines Section Policy Number Effective Date C C11 07/10/2015 Policy Issued As Reference Policy # B1-B4, C2, C4, C12, C14, E1, TBD Subject Approval: Donald Norman, Fire Chief PURPOSE This document is intended

More information

FIRE SAFETY DURING CONSTRUCTION, ALTERATION AND DEMOLITION

FIRE SAFETY DURING CONSTRUCTION, ALTERATION AND DEMOLITION CHAPTER 14 FIRE SAFETY DURING CONSTRUCTION, ALTERATION AND DEMOLITION SECTION FC 1401 GENERAL 1401.1 Scope. This chapter shall govern fire safety measures during the construction, alteration, or demolition

More information

WARNING: FOR OUTDOOR USE ONLY

WARNING: FOR OUTDOOR USE ONLY Fire Pit Owner s Manual BLZ-FP-PELLET : FOR OUTDOOR USE ONLY ATTENTION INSTALLER: PLEASE LEAVE THESE INSTRUCTIONS WITH THE CONSUMER. CONSUMER: PLEASE READ & RETAIN THESE INSTRUCTIONS FOR FUTURE REFERENCE

More information

HOT WORK SAFETY PROGRAM:

HOT WORK SAFETY PROGRAM: HOT WORK SAFETY PROGRAM: 1.0 Purpose. To establish safe procedure for open flame or hot work process at Oklahoma City Community College (OCCC) to avoid loss of property and injury to personnel. 2.0 Scope.

More information

As firefighters dismounted their apparatus, they recognized the life hazard that was presented. WNYF 2 nd issue 1967

As firefighters dismounted their apparatus, they recognized the life hazard that was presented. WNYF 2 nd issue 1967 FDNY PHOTO UNIT In the early morning hours of January 13, 1967, the Jamaica area of Queens would be rocked by a gas leak and fire that would destroy several buildings and test the New York City Fire Department

More information

I. INTRODUCTION. A. Purpose: To provide procedures and guidelines for personnel responding to and operating at working structure fire incidents.

I. INTRODUCTION. A. Purpose: To provide procedures and guidelines for personnel responding to and operating at working structure fire incidents. I. INTRODUCTION A. Purpose: To provide procedures and guidelines for personnel responding to and operating at working structure fire incidents. B. Scope: This instruction applies to all personnel responsible

More information

STANDARD OPERATING PROCEDURES RESPONDING TO EMERGENCIES DEPARTMENT RESPONSE PROCEDURES EFFECTIVE: AUGUST 2007

STANDARD OPERATING PROCEDURES RESPONDING TO EMERGENCIES DEPARTMENT RESPONSE PROCEDURES EFFECTIVE: AUGUST 2007 STANDARD OPERATING PROCEDURES RESPONDING TO EMERGENCIES 208.002 DEPARTMENT RESPONSE PROCEDURES EFFECTIVE: AUGUST 2007 PURPOSE The purpose of this policy is to provide standard response procedures for members

More information

RAMBLER PARK FIRE SAFETY INFORMATION

RAMBLER PARK FIRE SAFETY INFORMATION RAMBLER PARK FIRE SAFETY INFORMATION Parmenter Realty Partners 7557 Rambler Rd. Dallas, Texas 75231 214-373-9561 214-373-9620 (fax) RAMBLER PARK RAMBLER PARK FIRE SAFETY INFORMATION II. Objective To provide

More information

RE: BASIC FIRE SAFETY PROCEDURES AND OPERATION OF FIRE EQUIPMENT

RE: BASIC FIRE SAFETY PROCEDURES AND OPERATION OF FIRE EQUIPMENT March 15, 2016 Security Staff Training Memo RE: BASIC FIRE SAFETY PROCEDURES AND OPERATION OF FIRE EQUIPMENT Dear Staff Officers: As part of your daily rounds, security officers must look out for any unsafe

More information

SEPTEMBER-NEWSLETTER-ELEVATOR DANGERS

SEPTEMBER-NEWSLETTER-ELEVATOR DANGERS SEPTEMBER-NEWSLETTER-ELEVATOR DANGERS Each year, firefighters are brought up to fire floors in high-rise buildings by elevator and are forced to run for their lives through a gauntlet of flame, heat and

More information

I. It shall be the responsibility of the department officers to implement this operating guideline.

I. It shall be the responsibility of the department officers to implement this operating guideline. Procedure Effective Date Rescinds HIGH RISE INCIDENTS New Reference FIRE CHIEFS ASSOCIATION OF CENTRAL OHIO Page 1 of 11 NORWICH TOWNSHIP FIRE DEPARTMENT SOG# 8 Purpose: The purpose of this procedure is

More information

Second Revision No. 1-NFPA [ Section No. 2.2 ] Submitter Information Verification. Committee Statement

Second Revision No. 1-NFPA [ Section No. 2.2 ] Submitter Information Verification. Committee Statement Second Revision No. 1-NFPA 1410-2014 [ Section No. 2.2 ] 2.2 NFPA Publications. National Fire Protection Association, 1 Batterymarch Park, Quincy, MA 02169-7471. NFPA 1500, Standard on Fire Department

More information

Leader s Guide Marcom Group Ltd.

Leader s Guide Marcom Group Ltd. 1520 EVACUATION PROCEDURES Leader s Guide Marcom Group Ltd. Structure and Organization Information in this program is presented in a definite order so that employees will see the relationships between

More information

Talking about NFPA History of NFPA NFPA Standard 1710: Organization and Deployment of Fire Suppression Operations, EMS

Talking about NFPA History of NFPA NFPA Standard 1710: Organization and Deployment of Fire Suppression Operations, EMS NFPA Standard 1710: Organization and Deployment of Fire Suppression Operations, EMS and Special Ops The History The Right Description and The 2015 Revision Recognized early aggressive and offensive primary

More information

INTERIOR FIRE BRIGADE MEMBER MANIPULATIVE SKILL OBJECTIVES GENERAL

INTERIOR FIRE BRIGADE MEMBER MANIPULATIVE SKILL OBJECTIVES GENERAL INTERIOR FIRE BRIGADE MEMBER MANIPULATIVE SKILL OBJECTIVES GENERAL 1- Utilize a pre-incident plan so that the industrial fire brigade member implements the responses detailed by the plan. NFPA 1081, 2012

More information

WELDING, CUTTING, AND BRAZING SAFETY PROGRAM

WELDING, CUTTING, AND BRAZING SAFETY PROGRAM WELDING, CUTTING, AND BRAZING SAFETY PROGRAM HOT WORK TABLE OF CONTENTS 1.0 Introduction 1.1 Purpose 1.2 Scope 2.0 Responsibilities 2.1 Building Office 2.2 Building Personnel 2.3 Individuals Performing

More information

Whitestown Fire Department Standard Operating Procedure

Whitestown Fire Department Standard Operating Procedure Whitestown Fire Department Standard Operating Procedure Title: Fire Investigation No: 6.01 Date: 7/29/2016 Adopted 8/1/16 Page: 1 of 1 Purpose: The purpose of the Fire Investigation Program is to investigate

More information

Pro Board Assessment Methodology Matrices for NFPA 1001

Pro Board Assessment Methodology Matrices for NFPA 1001 Pro Board Assessment Methodology Matrices for NFPA 1001 NFPA 1001 - Fire Fighter I - 2013 Edition INSTRUCTIONS: In the column titled Cognitive/Written Test place the number of questions from the Test Bank

More information

INCIDENT TYPE: Structure Fire Fire in mobile property used as a fixed structure

INCIDENT TYPE: Structure Fire Fire in mobile property used as a fixed structure INCIDENT TYPE: Structure Fire 110 Structure fire, other 111 Building fire 112 Fires in structure other than in a building 113 Cooking fire, confined to container 114 Chimney or flue fire, confined to chimney

More information

2013 Compliance Report RCW 52.33

2013 Compliance Report RCW 52.33 2013 Compliance Report RCW 52.33 Revised Code of Washington (RCW) 52.33 requires substantially career fire protection districts to declare their department as established and set performance standards

More information

ATTIC FIRES. Part 2 LIGHT SMOKE SHOWING

ATTIC FIRES. Part 2 LIGHT SMOKE SHOWING ATTIC FIRES Part 2 LIGHT SMOKE SHOWING OBJECTIVES When developing this plan for fighting an attic fire, the first thing we considered is the potential hazard to firefighters on the fireground. Recognize

More information

Emergency Preparedness Guide

Emergency Preparedness Guide Emergency Preparedness Guide GRAYSLAKE CAMPUS The College of Lake County Emergency Preparedness Guide has been developed to provide you with practical guidelines to follow before, during and after an emergency.

More information

Department of School Safety and Security MONTGOMERY COUNTY PUBLIC SCHOOLS Rockville, Maryland

Department of School Safety and Security MONTGOMERY COUNTY PUBLIC SCHOOLS Rockville, Maryland Department of School Safety and Security MONTGOMERY COUNTY PUBLIC SCHOOLS Rockville, Maryland Shelter-In-Place Guidelines for a Chemical, Biological, or Radiological Incident and Exposure to Hazardous

More information

Title: Fire Prevention During Welding, Cutting and Other Hot Work Plan (formerly the Cutting & Welding Policy)

Title: Fire Prevention During Welding, Cutting and Other Hot Work Plan (formerly the Cutting & Welding Policy) Indiana University Northwest Environmental Health & Safety Title: Fire Prevention During Welding, Cutting and Other Hot Work Plan (formerly the Cutting & Welding Policy) Applies to: Issue Date: Latest

More information

DCN: COMMUNICATIONS MANUAL CHAPTER 1 January 1, 1997 ALARM TRANSMISSION SYSTEMS

DCN: COMMUNICATIONS MANUAL CHAPTER 1 January 1, 1997 ALARM TRANSMISSION SYSTEMS CHAPTER 1 January 1, 1997 ALARM TRANSMISSION SYSTEMS TABLE OF CONTENTS 1.0 INTRODUCTION...1 1.1 BARS (Box Alarm Readout Systems) ALARM BOXES...1 1.2 ERS (Emergency Reporting System) ALARM BOXES...2 1.3

More information

Mulch fires, trash can fires, or other fire outside a building should be reported by the following methods:

Mulch fires, trash can fires, or other fire outside a building should be reported by the following methods: University of Maryland FIRE EVACUATION PLAN HEALTH SCIENCE FACILITY I (HSF I) POLICE - 711 FIRE - 711 MEDICAL EMERGENCY - 711 Anyone discovering excessive heat, smoke, or fire inside your building will

More information

2.1 CO is a colorless, odorless, tasteless, non-irritating, toxic gas.

2.1 CO is a colorless, odorless, tasteless, non-irritating, toxic gas. FIRE TACTICS AND PROCEDURES March 15, 1997 (CO) 1. INTRODUCTION 1.1 Due to increased public awareness and the availability of carbon monoxide (CO) detectors for the home, the Fire Department is being called

More information

DEPARTMENTAL GUIDELINES CHAPTER 6 TACTICAL OPERATIONS

DEPARTMENTAL GUIDELINES CHAPTER 6 TACTICAL OPERATIONS Section 400.000 Suppression Systems The purpose of this guide is to assist the Incident Commander (IC), Fire Officers and Firefighters with the planning of effective operations for supporting water-based

More information

Wilson County Emergency Management Agency 110 Oak Street Lebanon, Tennessee 37087

Wilson County Emergency Management Agency 110 Oak Street Lebanon, Tennessee 37087 SOG Name: Multi Family Dwelling SOG Number: 403.15 Effective Date: February 2, 2015 Approved: Joey Cooper, Director Reviewed: Scope This procedure has been developed to provide WEMA with a set of guidelines

More information

FIRE PREVENTION MANUAL CHAPTER 12, FPIB 44 May 14, 2008 EMERGENCY ACTION PLAN (EAP) NON-FIRE EMERGENCIES IN CLASS E OFFICE BUILDINGS 1.

FIRE PREVENTION MANUAL CHAPTER 12, FPIB 44 May 14, 2008 EMERGENCY ACTION PLAN (EAP) NON-FIRE EMERGENCIES IN CLASS E OFFICE BUILDINGS 1. EMERGENCY ACTION PLAN (EAP) NON-FIRE EMERGENCIES IN CLASS E OFFICE BUILDINGS FIRE PREVENTION MANUAL CHAPTER 12, FPIB 44 May 14, 2008 1. INTRODUCTION 1.1 Local Law 26 of 2004 required that the Fire Commissioner

More information

COUNTY OF ALAMEDA County Administrator s Office Risk Management Unit th Street, 3 rd Floor, Oakland, CA 94607

COUNTY OF ALAMEDA County Administrator s Office Risk Management Unit th Street, 3 rd Floor, Oakland, CA 94607 SAMPLE COUNTY OF ALAMEDA County Administrator s Office Risk Management Unit 125 12 th Street, 3 rd Floor, Oakland, CA 94607 EMERGENCY ACTION PLAN (As of October 2010) TO REPORT AN EMERGENCY: 1. Activate

More information

Additional Materials: Instructor s PowerPoint, Question Files

Additional Materials: Instructor s PowerPoint, Question Files Course Delivery Formats: Online Interactive Course Online Streamed Video DVD Additional Materials: Instructor s PowerPoint, Question Files When it comes to mastering the basics for certification or refresher

More information

Non-Emergency Direct Line Telephone Numbers. Emergency Direct Line Telephone Numbers

Non-Emergency Direct Line Telephone Numbers. Emergency Direct Line Telephone Numbers Introduction The Emergency Evacuation Plan (EEP) is the building s official response to fire and other life safety emergencies, and serves as an operational guide for the security and protection of building

More information

Property Name & Address [ Property Name ] - [ Property Address ]

Property Name & Address [ Property Name ] - [ Property Address ] Emergency Procedure FIRE Property Name & Address [ Property Name ] - [ Property Address ] Purpose To ensure effective response and evacuation, by the property s Emergency Response Organization, to a fire

More information

BUILDING INSPECTION SAFETY PROGRAM MANUAL CHAPTER 5, REFERENCE # 1.4 August 1, 2009 OUT OF SERVICE (OOS) SPRINKLER AND STANDPIPE SYSTEMS

BUILDING INSPECTION SAFETY PROGRAM MANUAL CHAPTER 5, REFERENCE # 1.4 August 1, 2009 OUT OF SERVICE (OOS) SPRINKLER AND STANDPIPE SYSTEMS BUILDING INSPECTION SAFETY PROGRAM MANUAL CHAPTER 5, REFERENCE # 1.4 August 1, 2009 OUT OF SERVICE (OOS) SPRINKLER AND STANDPIPE SYSTEMS Note: For information on OOS Fire Alarms please see Inspectional

More information

Vacant Building Loss Prevention Best Practices

Vacant Building Loss Prevention Best Practices Vacant Building Loss Prevention Best Practices Vacant properties are susceptible to a unique set of hazards that should be considered and addressed to avoid losses. Occupants are often the eyes and ears

More information

Electrical Preventive Maintenance (EPM) Program

Electrical Preventive Maintenance (EPM) Program Electrical Preventive Maintenance (EPM) Program Only qualified and properly trained persons may work on electric circuit parts or equipment. Such persons shall be capable of working safely and shall be

More information

Enter Department Name Emergency Action Plan

Enter Department Name Emergency Action Plan Enter Department Name Emergency Action Plan In compliance with: California Code of Regulations Title 8, Section 3220 Implementation Date: Enter Date Annual Review Date*: *Reviewed and initialed by Department

More information

BROWNSVILLE VOLUNTEER FIRE DEPARTMENT

BROWNSVILLE VOLUNTEER FIRE DEPARTMENT BROWNSVILLE VOLUNTEER FIRE DEPARTMENT USTANDARD OPERATING GUIDELINES U TABLE OF CONTENTS 100 - PROTECTIVE CLOTHING AND PERSONAL SAFETY 200 - DISPATCH 300 - DRIVER OPERATIONS 400 - APPARATUS RESPONSE/ASSIGNMENT

More information

Fire Cause Determination

Fire Cause Determination Fire Cause Determination Objectives (1 of 3) Describe the role and relationship of the fire fighter to criminal investigators and insurance investigators. Differentiate accidental fires from incendiary

More information

INCINERATOR / COMPACTOR FIRES

INCINERATOR / COMPACTOR FIRES FIRES 7 March 15, 1997 INCINERATOR / COMPACTOR FIRES 1 SIZE-UP: INCINERATORS AND COMPACTORS 1.1 New York City Regulations encourage the use of compactors rather than incinerators, and require that incinerators

More information

FIRE AND FIRE FITTING By Mr. Prashant Sansare

FIRE AND FIRE FITTING By Mr. Prashant Sansare FIRE AND FIRE FITTING By Mr. Prashant Sansare What is mean by fire? CASE STUDY What Happened? Late one evening, a large storage tank containing a flammable liquid began to overflow. It was not detected

More information

FIRE PREVENTION PLAN EMERGENCY ACTION

FIRE PREVENTION PLAN EMERGENCY ACTION FIRE PREVENTION PLAN EMERGENCY ACTION 1.0 PURPOSE This Plan is presented for University employees to be informed so that they react safely and effectively during an emergency situation. The Plan also reinforces

More information

CAMDEN COUNTY FIRE COORDINATOR

CAMDEN COUNTY FIRE COORDINATOR SECTION OPERATIONS EFFECTIVE REVISED 02-20-19 SOG 3-1 CAMDEN COUNTY FIRE COORDINATOR Purpose To establish an appointment protocol for the Camden County Fire Coordinator, and Deputy Camden County Fire Coordinator

More information

1.1.0 Protocols for the response to fires involving MRI Machines

1.1.0 Protocols for the response to fires involving MRI Machines MRI Responding to Fires Involving MRI Machines 1.1.0 Protocols for the response to fires involving MRI Machines 1.1.1 It is incumbent upon all Fire Department Personnel to remain knowledgeable about the

More information

Risk Management Department. Fire Extinguishers

Risk Management Department. Fire Extinguishers Risk Management Department Fire 1 Introduction to Fire Every school facility is equipped with fire extinguishers for staff to use to suppress fires. Used properly, a fire extinguisher can be an effective

More information

Portable Generator Safety Lloyd Shank, P.E. Director of Electric and Gas Utilities 4/12/2005

Portable Generator Safety Lloyd Shank, P.E. Director of Electric and Gas Utilities 4/12/2005 Portable Generator Safety Lloyd Shank, P.E. Director of Electric and Gas Utilities 4/12/2005 Page 1 of 10 Portable Generator Safety During the process of restoring electric power to a neighborhood Line

More information

Mount Prospect Fire Department

Mount Prospect Fire Department Location Study Mount Prospect Fire Department 2018 Created by: Illinois Fire Chiefs Association Mount Prospect Fire Department Mission Statement: To protect people, property, and the environment by reducing

More information

House Fire IAP. Staffing Assumptions

House Fire IAP. Staffing Assumptions Staffing Assumptions Engine Companies staffed with (1) Driver and (1) Officer Medic Units staffed with (1) Driver and (1) Paramedic/Officer Aid Units staffed with (1) Driver and (1) Officer Battalion Chief

More information

INSTRUCTOR GUIDE COURSE: FIREFIGHTER PRE-BASIC SESSION REFERENCE: 1 TOPIC: ORIENTATION AND FIRE BEHAVIOR LEVEL OF INSTRUCTION:

INSTRUCTOR GUIDE COURSE: FIREFIGHTER PRE-BASIC SESSION REFERENCE: 1 TOPIC: ORIENTATION AND FIRE BEHAVIOR LEVEL OF INSTRUCTION: COURSE: FIREFIGHTER PRE-BASIC SESSION REFERENCE: 1 INSTRUCTOR GUIDE TOPIC: ORIENTATION AND FIRE BEHAVIOR LEVEL OF INSTRUCTION: TIME REQUIRED: THREE HOURS MATERIALS: APPROPRIATE AUDIO VISUAL AIDS REFERENCES:

More information

Promotional Prep Fire Service Promotional Test Preparation

Promotional Prep Fire Service Promotional Test Preparation Promotional Prep Fire Service Promotional Test Preparation Scenario # 13 - Taxpayer Fire Oral Assessment exercise: At 04:30 hours on a cold March morning, you are dispatched to a reported fire at 220 Madison

More information

P.O. Box , Dallas, TX USER'S INFORMATION MANUAL Single-Stage Warm Air Gas Furnaces

P.O. Box , Dallas, TX USER'S INFORMATION MANUAL Single-Stage Warm Air Gas Furnaces P.O. Box 799900, Dallas, TX 75379-9900 USER'S INFORMATION MANUAL Single-Stage Warm Air Gas Furnaces This is a safety alert symbol and should never be ignored. When you see this symbol on labels or in manuals,

More information

Kaufert Laboratory Building Emergency Plan

Kaufert Laboratory Building Emergency Plan Kaufert Laboratory Building Emergency Plan Building #387 2004 FOLWELL AVENUE ST. PAUL, MN 55108 Information Desk Phone: 612-625-5200 Information Desk Email: bbe@umn.edu NEVER ENDANGER YOUR PERSONAL SAFETY

More information

ESCONDIDO FIRE DEPT TRAINING MANUAL Section Truck Module Page 1 of 5 High Rise On Scene Revised

ESCONDIDO FIRE DEPT TRAINING MANUAL Section Truck Module Page 1 of 5 High Rise On Scene Revised Truck Module Page 1 of 5 HIGH RISE FIRE ON SCENE The Truck Module 1000.00 sections are designed to be companion documents to EOM section 503.00 Objectives The objective of this section is to explain the

More information

3330 N Clayton. C - Side Date: 11/18/2017 Time: 21:48 Incident Number: Address: 3330 N Clayton

3330 N Clayton. C - Side Date: 11/18/2017 Time: 21:48 Incident Number: Address: 3330 N Clayton C - Side Date: 11/18/2017 Time: 21:48 Incident Number: 17-124948 Address: 3330 N Clayton Overview: District 4 report Group response to reported structure fire at 3338 Clayton. E09 on scene reporting fire

More information

Cumru Township Fire Department 4/27/10 Standard Operating Guidelines Page: 1 of 6 Section 15.07

Cumru Township Fire Department 4/27/10 Standard Operating Guidelines Page: 1 of 6 Section 15.07 Standard Operating Guidelines Page: 1 of 6 15.07 Scope: Commercial properties shall include businesses, schools and shops with very limited special hazards. 15.0701 First engine placement: Positioning

More information

[Name/title] is the Alternate Safety Officer/ Alternate Emergency Coordinator.

[Name/title] is the Alternate Safety Officer/ Alternate Emergency Coordinator. Community Health Center ================================================================= Subject: EMERGENCY EVACUATION PROCEDURE ================================================================= Policy

More information