EAE/EAES «HEPHEA 248» Product Technical Instructions

Size: px
Start display at page:

Download "EAE/EAES «HEPHEA 248» Product Technical Instructions"

Transcription

1 Page : 1/7 TABLE OF CONTENTS A. GENERAL FEATURES GENERAL INFORMATION DESIGN FUNCTIONAL FEATURES TECHNICAL FEATURES... 3 B. INSTALLATION AND CONNECTING SUPPLY UNIT ORGANISATION INSTALLATION CONNECTION... 5 C. START UP PRELIMINARY CHECKS OPERATION... 6 D. OPERATION AND MAINTENANCE DETAIL OF SIGNS ON FRONT SIDE SPARE PARTS ABOUT LEAD STORAGE CELLS MAINTENANCE INSTRUCTIONS AND MARKINGS... 7 C 25/05/09 Misc. Amendments All B 17/03/09 Misc. Information All A 15/01/09 Document creation. All Index Date Description Page(s) Written by : Yvon Larabi

2 Page : 2/7 A. GENERAL FEATURES 1. GENERAL INFORMATION The Power Supply Equipment is designed to meet the main following standards : Building Product Directive CPD 89/106/CEE, NF EN 54-4 standard : Fire detection and fire alarm system Part 4 : Power Supply Equipment (P.S.E.) and NF EN standard : smoke and heat control systems Part 10 : Power Supply Equipment (P.S.E.) - class A. The product can be used in other areas than fire safety or fire protection subject to complying with the limits provided below in this document. Note : in addition to the main product features, this document describes the installation, connection, start up, operation and maintenance aspects. 2. DESIGN This product uses the cutting technology, which allows : Significant size and weight reduction Outstanding electrical yield leading to energy savings and Outstanding stability over time. HEPHEA 248 is made up of a metal box with an IP30 protection index, which contains the supply unit and the batteries. There are four indicators on the front side of the box, showing the various statuses of the product. Two separate outlets are available, each with their own fuse protection. Three other dry contact relay outlets are provided for distant supply source status information. 3. FUNCTIONAL FEATURES The supply unit supplies continuous voltage ranging from 21.6V to 28.8V depending on operating conditions and the room temperature (battery recharging compensated for temperature). The unit is permanently monitored and reports a defect when any of the following disorders occurs : No mains supply (no source or fuse defect), Battery disconnected, discharged or damaged, Battery fuse defect, No voltage on at least one outlet The batteries are checked via an internal functional test carried out at least every minute. In accordance with amendment A2 of the NF EN54-4 standard, the system also checks the value of the «Ri» internal resistance of the batteries and of the related circuit, and reports a defect when the value reading is 0.16Ω.

3 Page : 3/7 4. TECHNICAL FEATURES Mechanical features Floor space (dimension in mm) Length : 405 height : 390 width : 165. Weight (without batteries) 7kg. Colour Grey - RAL Protection index IP30. Main source features Nature Mains 230Vac (±15%) / 50 to 60Hz.. Consumption 1.5 A maximum. Protection «F1» fuse : 6.3A timed (5x20 format). Breaker type to be provided D curve. Features of secondary source Nature Serial, the product is provided with 2 sealed lead 12V/24Ah storage cells, connected in series and whose battery life should meet the durations related to the application ; for information : Battery life Duration Total max. current available on both outlets 72 hours 0.25A 30 hours 0.6A 12 hours 1.6A 4 hours 4.8A Protection «FBAT» fuse : 16A timed (10x38 format). Discharge limitation DLD Action for voltage 21,6V ± 3% leading to voltage supply interruption on use outlets. Circuit consumption Without mains, the consumption specific to the product (non charged outlets) is 0.05A. Internal resistance Should be < 0.16Ω ±10%, beyond a defect is reported. Features of charger Maximum current 6A. Maximum operational current For 20 hour recharging time : 1.2A. The jumper forced a factory setting (do not move). Features of use outlet Number Protection Voltage Minimum current Maximum current Residual ripple Features of other outlets Number Type Cutting power Climate conditions Functional Storage 2 independent outlets. «F7» and «F8» fuse : 12.5A timed (5x20 format). Between 21.6V and 28.8V with 27.2V rated with mains Not applicable 8A without charging current or 6.8A with C/20 charging current. < 0.5Vpp. 3, respectively with mains failure, battery failure and use voltage failure reproduction. Potential free dry contact. 30V/0.5A in direct current. Temperature range : from -5 C to +40 C. Admissible relative humidity : 93%hr without condensation. Environment class 1 in the meaning of standard NF EN Temperature range : from 5 C to +40 C. Admissible relative humidity : 93%hr without condensation. Other features Components used They meet class 3K5 of CEI

4 Page : 4/7 B. INSTALLATION AND CONNECTING 1. SUPPLY UNIT ORGANISATION Mains Repetition Output 2 Output 1 Battery 1.1. MAIN LINKS Figure 1 : «EV-24V-8A» card «Mains» terminal board Ph N Phase Neutral Electrical grounding «Battery» terminal board + BAT (+) battery links (FBAT protection). - BAT (-) battery links «Outlet 1» and «Outlet 2» terminal board UTILI + (+) from use outlet N 1 (F8 fuse protection). UTILI - (-) from use outlet N 1. UTIL2 + (+) from use outlet N 2 (F7 fuse protection). UTIL2 - (-) from use outlet N «Repetition» terminal board «Mains failure» relay (normally controlled relay) 1 Standby 2 Common 3 Work «Battery failure» relay (normally controlled relay) 4 Standby 5 Common 6 Work «Outlet voltage failure» relay (normally controlled relay) 7 Standby 8 Common 9 Work 1.2. SIGNALS AND ADJUSTMENT PARTS Internal LED P1 Green colour : everything is correct, Intermediate yellow colour (green/red) : mains failure or Red colour : battery failure or use outlet failure (priority on yellow colour). Use voltage setting potentiometer DO NOT CHANGE THIS SETTING.

5 Page : 5/7 2. INSTALLATION In addition to electrician s tools, the following are needed when installing the products : 4 drift bolts, 4 screws and 4 washers (standard 6mm) ; 1 10mm wrench to fasten the metal battery blocking plaque. The box should be installed vertically and fastened to a stable wall adequate for the weight of the device. 3. CONNECTION 3.1. GENERAL RECOMMENDATIONS Qualified personnel should handle the mains connections in compliance with applicable rules. At least the following criteria should be complied with : The mains cable should enter through a different hole than the hole used for the other cables. Use of grommets is required in the event of sideways penetration. Tie all low voltage cables into a bundle. The mains supply cable and low voltage cable bundle cable routes should be separate. For the mains connection, use 3 x 1.5² cable in Category C2 in the meaning of standard NF C For use outlets, use 2x1.5² or 2x2.5² cable in Category CR1 in the meaning of standard NF C For cables using relay outlets, use 1 pair 8/10 screen cable in Category C2 in the meaning of standard NF C Strip enough of the insulated conductors to allow their insertion in the respective terminals ; insert the conductors in the terminal board housings and tighten accordingly, without excessive strength to avoid cutting the conductors. The various conductors should not be tin-plated 3.2. MAINS CABLE CONNECTION Unless there is one already, install, upstream from the connection, a bipolar mains supply cut-off and protection system specifically dedicated to fire safety. Connect to the «Mains» terminal board (see figure 1) INSTALLING THE BATTERIES The batteries should be installed on the bottom of the box and fastened with the metal U bolt provided with the product. The product is supplied with a set of connection accessories allowing to connect the batteries.

6 Page : 6/7 C. START UP 1. PRELIMINARY CHECKS Before starting up the product, check that : The value of the insulation opposite the ground of all use outlet cable and report cable conductors is over 1MΩ ; The voltage on the mains ranges from 195 to 253V. 2. OPERATION Power up the device ; the «BATTERY FAULT», «OUTPUT 1» and «OUTPUT 2» indicators come on. Check the value of the voltage of each use outlets and connect the batteries ; the «BATTERY FAULT» indicator turns off. IMPORTANT COMMENTS : Beware not to switch the battery connections. Switching the polarity could damage the device. Use same type batteries in the same flammability class UL94-HB, UL-V0 or higher. After this, the supply is operational ; then connect the use and report cables. When the source failure reports are used, check the central equipment transmission quality

7 Page : 7/7 D. OPERATION AND MAINTENANCE 1. DETAIL OF SIGNS ON FRONT SIDE Indicator MAINS FAULT BATTERY FAULT OUTPUT 1 OUTPUT 2 2. SPARE PARTS Designation Supply card for HEPHEA V/24Ah Battery 3. ABOUT LEAD STORAGE CELLS Status of supply unit When the battery voltage is correct, the indicator is on to indicate that the main source level is wrong. With the mains on, the indicator is on to indicate that the battery cannot perform. Indicator is on as long as the respective outlet is operational. Indicator is on as long as the respective outlet is operational. Reference EV-24V-8A card (maintenance) Sealed lead UL-V0 Battery manufacturer approved by SEFI The current life of that type of battery is at least 2 years. It is advisable to change them every 4 years. The meaning of the codes on YUASA batteries (DF=21/05/2001, DDLMS=21/05/2002, for instance) is as follows and allows to identify the manufacturing date : Place of Digit 1 Digit 2 Digit 3 Digit 4 Digit 5 Digit 6 Digit 7 Letter Example manufacturi ng. UK or US year month Month day day internal internal code code Japan year year Month month day day internal code 4. MAINTENANCE INSTRUCTIONS AND MARKINGS 21/05/ /03/ SAFETY AND MAINTENANCE INSTRUCTIONS The equipment is designed to be connected to the main 230V network. In order to avoid any electrical shock hazard, the device should be powered down before any work. The products meet the EN :2001 standard. Working with the device on is allowed only when working with the device off is not possible. Any servicing should be carried out by qualified personnel only. An annual maintenance check is required, consisting at least in the following : Checking the battery aspect visually, Input and output (use outlets) voltage reading (mains), Checking the quality of the failure report transmission on each supply source COMPLIANCE MARKING Label affixed on the right hand side of the box)

IFP-2.32 Manual 1) DESCRIPTION ICAS FIRE PANEL IFP 2.32

IFP-2.32 Manual 1) DESCRIPTION ICAS FIRE PANEL IFP 2.32 1) DESCRIPTION IFP-2.2 Manual IFP-2.8 and IFP-2.2 is a microprocessor controlled Fire Panel with 2 loops intended either for privat Homes & Apartments or larger installations. The two loops are balanced

More information

Revision: None DCN No. First Issue Date: November 30, 1998 Product: Standard DCT, 120-volts

Revision: None DCN No. First Issue Date: November 30, 1998 Product: Standard DCT, 120-volts Figure 1Document: SPEC-112 Revision: None DCN No. First Issue Date: November 30, 1998 Product: Standard DCT, 120-volts construction requirements of UL approved Class H (180 C) insulation system. Transformers

More information

FEC400 Series. Installation Manual

FEC400 Series. Installation Manual FEC400 Series Conventional microprocessor controlled fire detection and alarm panels with extinguishing control Installation Manual Version 2.3 / August 2004 Aritech is a GE Interlogix brand. http://www.geindustrial.com/ge-interlogix/emea

More information

Constant voltage 3-phase rectifier.

Constant voltage 3-phase rectifier. 11750a Constant voltage 3-phase rectifier. Page 1 of 11 11750a Mechanical assembly The rectifier is assembled in a cabinet intended for indoor wall mounting. The cabinet has ventilation holes on both sides

More information

User manual and installation instruction Control for Fire Ventilation RV / RV 24-32

User manual and installation instruction Control for Fire Ventilation RV / RV 24-32 User manual and installation instruction Control for Fire Ventilation RV 24-24 / RV 24-32 Fire ventilation Comfort ventilation 24VDC max. 24/32A 2 Actuator outputs 1 Fire ventilation group, 2 comfort groups

More information

1 Description. 2 Specifications. HP600ULM Access Control Power Supply/Charger with Power Distribution Controller PN 52393:A 1/05/06 ECN

1 Description. 2 Specifications. HP600ULM Access Control Power Supply/Charger with Power Distribution Controller PN 52393:A 1/05/06 ECN Honeywell 12 Clintonville Road Northford, CT 06472 http://www.honeywellpower.com HP600ULM Access Control Power Supply/Charger with Power Distribution Controller PN 52393:A 1/05/06 ECN 04-350 Product Installation

More information

FP120-Z1 Power supply kit A (70 W) Technical Manual

FP120-Z1 Power supply kit A (70 W) Technical Manual FP120-Z1 Power supply kit A (70 W) Technical Manual 2015-07-08 Control Products and Systems Legal notice Legal notice Technical specifications and availability subject to change without notice. Transmittal,

More information

Interface and EOL Modules 8

Interface and EOL Modules 8 Interface and EOL Modules Interface Modules Series 420 25 Interface Modules Series 100 291 EOL Modules 293 254 Interface and EOL Modules Interface Modules Series 420 Interface Modules Serie 420 Interface

More information

Instructions for the fan motor control system with integrated wiring terminals SILVER C

Instructions for the fan motor control system with integrated wiring terminals SILVER C Instructions for the fan motor control system with integrated wiring terminals SILVER C 1. General The motor control system is used for controlling the type EC, 0.41-10 kw fan motors in the SILVER C units.

More information

FX FIRE DETECTION SYSTEM

FX FIRE DETECTION SYSTEM FX FIRE DETECTION SYSTEM Installation and commissioning manual Read this manual carefully before installation and commissioning! Installation and commissioning must be performed according to this manual.

More information

RE-PR3-E-27 3-Phase Panel Mount 27kW

RE-PR3-E-27 3-Phase Panel Mount 27kW Page 1 of 6 RE-PR3-E-27 3-Phase Panel Mount 27kW Features: Benefits: 0-10Vdc, 0-5Vdc, 4-20mA or manual via potentiometer control input Over temperature protection with auto reset Enclosed panel mounting

More information

PS1240x Series Dual Voltage Access Control Power Supply Systems Operating and Installation Instructions Rev D.01

PS1240x Series Dual Voltage Access Control Power Supply Systems Operating and Installation Instructions Rev D.01 PS1240x Series Dual Voltage Access Control Power Supply Systems Operating and Installation Instructions Warnings and Notices WARNING - To reduce the risk of fire or electric shock, do not expose this product

More information

Instructions for the fan motor control system, SILVER C

Instructions for the fan motor control system, SILVER C Instructions for the fan motor control system, SILVER C 1. General The motor control system is used for controlling the type EC, 0.41-10 kw fan motors in the SILVER C units. The motor control system is

More information

Rectifier RC-series. Manual RC-series English MA doc. Manual Wall and 19 English

Rectifier RC-series. Manual RC-series English MA doc. Manual Wall and 19 English Rectifier RC-series Manual RC-series English Manual Wall and 19 English Presentation The RC-series is a rectifier for either directly powering the load or for use together with batteries. It is designed

More information

Installation Instructions. Mira LED Light System

Installation Instructions. Mira LED Light System Installation Instructions Mira LED Light System w w w. a m i c o. c o m Contents Symbols Used in This Manual 4 Safety Instructions 5 Variants 7 Scope Of Delivery 8 Installing Mira LED Ceiling Mounted Installing

More information

Installation and user manual for the BiWire / Conventional Repeater Panel

Installation and user manual for the BiWire / Conventional Repeater Panel Panel EFBWCV-REPEATER Contents Introduction.... 3 Purpose... 3 The Panel.... 3 Indication Equipment (IE).... 3 Power Supply Equipment (PSE).... 4 System Wiring.... 5 Status Indications.... 5 Repeater I/O....

More information

Installation Guide for models:

Installation Guide for models: 140 58th St. Brooklyn, NY Access Power Controllers with Power Supplies Installation Guide for models: Maximal11F - Power Supply 1: 12VDC @ 3.3 amp or 24VDC @ 3.6 amp. - Power Supply 2: 12VDC @ 3.3 amp

More information

UltraLITE Model ELU Centralized Emergency Lighting Inverter 4.2 KW- 5 KW

UltraLITE Model ELU Centralized Emergency Lighting Inverter 4.2 KW- 5 KW 12/23/16 Rev 9 UltraLITE Model ELU General Specification 4.2 KW to 5 KW UltraLITE Model ELU Centralized Emergency Lighting Inverter 4.2 KW- 5 KW 1.0 General General Specification This specification describes

More information

CONTENTS AUTOMATIC TRANSFER SWITCHES

CONTENTS AUTOMATIC TRANSFER SWITCHES CONTENTS AUTOMATIC TRANSFER SWITCHES PART 1 GENERAL 1.1 Related Documents 1.2 Summary 1.3 References 1.4 Quality Assurance 1.5 Submittals 1.6 Delivery, Storage and Handling 1.7 Instructions And Training

More information

ISOMETER IRDH375. Insulation monitoring device for unearthed AC, AC/DC and DC systems (IT systems)

ISOMETER IRDH375. Insulation monitoring device for unearthed AC, AC/DC and DC systems (IT systems) Insulation monitoring device for unearthed AC, AC/DC and DC systems (IT systems) IRDH375_D00124_01_D_XXEN/07.2018 Insulation monitoring device for unearthed AC, AC/DC and DC systems (IT systems) Product

More information

EUROBOX SERIES TYPES CM... SM... MM...

EUROBOX SERIES TYPES CM... SM... MM... EUROBOX SERIES TYPES CM... SM... MM... AUTOMATIC GAS BURNER CONTROL SYSTEMS FOR GAS BURNERS AND GAS BURNING APPLIANCES WITH OR WITHOUT FAN Application This range of electronic gas burner control systems

More information

SECTION AUTOMATIC TRANSFER SWITCHES PART 1 - GENERAL

SECTION AUTOMATIC TRANSFER SWITCHES PART 1 - GENERAL SECTION 16400 AUTOMATIC TRANSFER SWITCHES 1.01 RELATED DOCUMENTS PART 1 - GENERAL A. Drawings and general provisions of Contract, including General Conditions and Division 1 Specification sections, apply

More information

Multi-Output Access Control Power Supply Chargers VDC or 24VDC VDC or 4 24VDC.

Multi-Output Access Control Power Supply Chargers VDC or 24VDC VDC or 4 24VDC. M Series Multi-Output Access Control Power Supply Chargers Installation Guide Models Include: AL300ULM AL400ULM - 2.5 amp @ 12VDC or 24VDC. - 3 amp @ 12VDC or 4 amp @ 24VDC. AL600ULM AL1012ULM - 6 amp

More information

Models NFPA 1221-A, NFPA 1221-B Public Safety DAS Annunciator Panel. Revision E 61117

Models NFPA 1221-A, NFPA 1221-B Public Safety DAS Annunciator Panel. Revision E 61117 Models NFPA 1221-A, NFPA 1221-B Public Safety DAS Annunciator Panel Revision E 61117 CAUTION: (Read This First) This panel has been designed to make it nearly bullet proof to mistakes made when wiring

More information

Operating Instructions

Operating Instructions Bracken Hill South West Industrial Estate Peterlee Co Durham SR8 2SW ENGLAND Tel: +44(0)191 5863511 www.seaward.co.uk sales@seaward.co.uk service@seaward.co.uk Part Number 347A550 Revision 1 2006 Seaward

More information

AL600ULX Series. Power Supply/Charger. Installation Guide

AL600ULX Series. Power Supply/Charger. Installation Guide AL600ULX Series Power Supply/Charger Installation Guide Models Include: AL600ULX - Single Output AL600ULPD4 AL600ULPD4CB - Four (4) Fused Outputs - Four (4) PTC Outputs AL600ULPD8 AL600ULPD8CB - Eight

More information

Version 3 Controls for smoke and natural ventilation. CompactSmoke WSC 310 / WSC 320 STANDARD Smoke control panel 10-20A

Version 3 Controls for smoke and natural ventilation. CompactSmoke WSC 310 / WSC 320 STANDARD Smoke control panel 10-20A Version 3 Controls for smoke and natural ventilation CompactSmoke WSC 310 / WSC 320 STANDARD Smoke control panel 10-20A 1.50 Application smoke extraction and daily comfort ventilation 2 smoke / 2 daily

More information

APS-300 SERIES DUAL VOLTAGE UL 294 LISTED ACCESS CONTROL POWER SUPPLIES

APS-300 SERIES DUAL VOLTAGE UL 294 LISTED ACCESS CONTROL POWER SUPPLIES APS-300 SERIES DUAL VOLTAGE UL 294 LISTED ACCESS CONTROL POWER SUPPLIES POWER SUPPLY AND BATTERY CHARGER AC AND DC STATUS INDICATORS ENOUGH POWER TO SUPPORT UP TO 3 MAGLOCKS OR ELECTRIC STRIKES PLUS REQUIRED

More information

Installation Guide for models:

Installation Guide for models: 140 58th St. Brooklyn, NY Access Power Controllers with Power Supplies Installation Guide for models: Maximal3FD - 12VDC @ 4.6 amp or 24VDC @ 5.2 amp. - Sixteen (16) PTC protected power-limited outputs.

More information

M770 ph Controller Owner s Manual

M770 ph Controller Owner s Manual M770 ph Controller Owner s Manual Table of Contents I. Introduction page 2 A. Water Chemistry page 2 B. Safety page 3 C. System Components page 4 D. Specifications page 7 E. Controller Panel Descriptions

More information

Public Safety DAS Annunciator Panel

Public Safety DAS Annunciator Panel Public Safety DAS Annunciator Panel 120 VAC Models: 1221-A, 1221-B, 1221-C Revision D 91117 48 VDC Models: 1221-A-48, 1221-B-48, 1221-C-48 24 VDC Models: 1221A-24, 1221-B-24, 1221-C-24 CAUTION: (Read This

More information

Cat. N. Cat. N (s) 1. DESCRIPTION - USE 3. OVERALL DIMENSIONS. Technology : 4. PREPARATION - CONNECTION 2. PRODUCT RANGE

Cat. N. Cat. N (s) 1. DESCRIPTION - USE 3. OVERALL DIMENSIONS. Technology : 4. PREPARATION - CONNECTION 2. PRODUCT RANGE Cat. N STOP & GO automatic resetting 87045 LIMOGES Cedex - FRANCE Telephone : + 33 5 55 06 87 87 Fax: + 33 5 55 06 88 88 Cat. N (s) : 4 062 88 / 4 062 89 CONTENTS PAGE 1. Description - Use... 1 2. Product

More information

ATD PEDESTAL FAN INSTRUCTIONS

ATD PEDESTAL FAN INSTRUCTIONS ATD-30330 30 PEDESTAL FAN INSTRUCTIONS Item No. Blade Diameter Voltage / Hz Current (A) ATD-30330 30 120V /60Hz 1.4 READ AND SAVE THESE INSTRUCTIONS Failure to properly follow these instructions may lead

More information

- Four (4) Fused Outputs - Four (4) PTC Outputs. - Eight (8) Fused Outputs - Eight (8) PTC Outputs

- Four (4) Fused Outputs - Four (4) PTC Outputs. - Eight (8) Fused Outputs - Eight (8) PTC Outputs AL400ULX Series Power Supply/Charger Installation Guide Models Include: AL400ULX - Single Output AL400ULPD4 AL400ULPD4CB - Four (4) Fused Outputs - Four (4) PTC Outputs AL400ULPD8 AL400ULPD8CB - Eight

More information

FIRE ALARM CONTROL EQUIPMENT. Addendum October 2006 Instructions for new style EN54-4 Power supply unit module

FIRE ALARM CONTROL EQUIPMENT. Addendum October 2006 Instructions for new style EN54-4 Power supply unit module FIRE ALARM CONTROL EQUIPMENT Addendum October 2006 Instructions for new style EN54-4 Power supply unit module MXLK-05 Issue 2.0 June 2007 INSTALLATION Safety Suppliers of articles for use at work are required

More information

Securitron Magnalock Corporation S. 51 st St., Ste. 102 Phoenix, AZ Phone: (800) MAGLOCK

Securitron Magnalock Corporation S. 51 st St., Ste. 102 Phoenix, AZ Phone: (800) MAGLOCK Installation Manual AQM-20 12vdc/24vdc Series Power Supplies AQM20 Supervised Power Supply/Charger 12vdc 20Amp/24vdc 10Amp Life Time Warranty Quality Manufactured in the USA AQM20 Features: The AQM20 has

More information

QPM21 Series Duct CO 2 and Air Quality Sensors

QPM21 Series Duct CO 2 and Air Quality Sensors Document No. CE1N1962 QPM21 Series Duct CO 2 and Air Quality Sensors Description Features Application The Carbon Dioxide (CO 2 ) Duct Sensors are directly wired to the controller via twisted pair and/or

More information

For a red enclosure add an R suffix to the part # e.g. eflow4na8r. Altronix Corp th St. Brooklyn, NY. Installing Company: Service Rep.

For a red enclosure add an R suffix to the part # e.g. eflow4na8r. Altronix Corp th St. Brooklyn, NY. Installing Company: Service Rep. Power Supply/Chargers Installation Guide Models Include: eflow4na8-4a @ 12VDC or 24VDC - Eight (8) Fused Outputs eflow6na8-4a @ 12VDC or 24VDC - Eight (8) Fused Outputs eflow102na8-10a @ 12VDC - Eight

More information

READ AND SAVE THESE INSTALLATION INSTRUCTIONS

READ AND SAVE THESE INSTALLATION INSTRUCTIONS Nomenclature: D F I 0 0 H : Open coil element T: Tubular element F: Finned tubular element I: Slip in type F: Flange type 0: No screen left of the heater 1: Screen left of the heater 0: No screen right

More information

SP-1000X. Panic Device Power Controller Installation Guide. Rev

SP-1000X. Panic Device Power Controller Installation Guide. Rev TM SP-1000X Panic Device Power Controller Installation Guide Rev. 120213 Overview: SP-1000X will operate up to two (2) 24VDC panic hardware devices simultaneously. It is designed to handle the high current

More information

The extent of liability of the signatory/signatories is limited to the work described above as the subject of this certificate.

The extent of liability of the signatory/signatories is limited to the work described above as the subject of this certificate. This safety certificate is an important and valuable document which should be retained for future reference DETAILS OF THE CLIENT Client / DETAILS OF THE INSTALLATION Extent of the installation covered

More information

WSC 204 (WSC / WSC 204MH 0102 / WSC 204KP 0102 / WSC 204BZ 0102)

WSC 204 (WSC / WSC 204MH 0102 / WSC 204KP 0102 / WSC 204BZ 0102) WSC 204 (WSC 204 0102 / WSC 204MH 0102 / WSC 204KP 0102 / WSC 204BZ 0102) Smoke control panel Operating manual / Technical information WSC 204 0102 WSC 204BZ 0102 plastic housing WSC 204KP 0102 plastic

More information

EUROBOX SERIES TYPES CM...N SM...N MM...N

EUROBOX SERIES TYPES CM...N SM...N MM...N EUROBOX SERIES TYPES CM...N SM...N MM...N AUTOMATIC CONTROL SYSTEMS FOR GAS BURNERS AND GAS BURNING APPLIANCES WITH OR WITHOUT FAN (MANUAL RESET) DESCRIPTION This series of electronic systems is suitable

More information

MANUAL RESET ALARM RELEASE

MANUAL RESET ALARM RELEASE Fire Door Release MODEL AR-D2 MANUAL RESET ALARM RELEASE INSTRUCTION MANUAL AR-D2 GENERAL INFORMATION 1. Review all installation instructions, procedures, cautions and warnings contained within this manual

More information

SECURITY LIGHT MODEL NO: CL6PIR OPERATION INSTRUCTIONS PART NO: GC0215

SECURITY LIGHT MODEL NO: CL6PIR OPERATION INSTRUCTIONS PART NO: GC0215 SECURITY LIGHT MODEL NO: CL6PIR PART NO: 4003535 OPERATION INSTRUCTIONS GC0215 INTRODUCTION Thank you for purchasing this CLARKE Security Light with motion sensor. The motion sensor is a small electronic

More information

enproteko.com Specifications Ratings Item voltage to 24 VAC 5/6 Hz 24 VAC 5/6 Hz or 24 VDC Allowable voltage Characteristics 85% to 11% of power suppl

enproteko.com Specifications Ratings Item voltage to 24 VAC 5/6 Hz 24 VAC 5/6 Hz or 24 VDC Allowable voltage Characteristics 85% to 11% of power suppl enproteko.com Temperature Monitoring Relay K8AB-TH Compact and Slim Relay Ideal for Temperature Alarms and Monitoring Excessive increases can be prevented and abnormal s can be monitored. Temperature monitoring

More information

Excel-EN Conventional Fire Control Panel

Excel-EN Conventional Fire Control Panel Available as 2, 4, 6, 8,10 or 12 zones Approved to EN54-2 & 4 Modular expansion zone cards Programmable relays and outputs Optional additional sounder circuits Optional additional programmable outputs

More information

Battery charger modules

Battery charger modules Battery charger modules D8132 and D8132LT en Installation manual Battery charger modules Notices en 3 1 Notices These instructions cover the installation of the D8132 Battery Charger and the D8132LT Battery

More information

Bionics Instrument. Alarm Handling. Gas Alarm Systems

Bionics Instrument. Alarm Handling. Gas Alarm Systems Gas Alarm Systems Controllers and PLC based systems Alarm Handling Complete control at the right time and place Every gas detector consist of a gas sensor and a signal transmitter. In case of a gas leak,

More information

RTA421. Technical Information. Limit alarm switch Alarm switch and power supply for monitoring current or voltage signals

RTA421. Technical Information. Limit alarm switch Alarm switch and power supply for monitoring current or voltage signals Technical Information RTA421 Limit alarm switch Alarm switch and power supply for monitoring current or voltage signals Application Plant and machine construction Panel builders Process monitoring Process

More information

Installation and Operation Manual CLEARVIEW DAY COVER CAUTION: To view a video scan the QR code above

Installation and Operation Manual CLEARVIEW DAY COVER CAUTION: To view a video scan the QR code above Installation and Operation Manual CLEARVIEW DAY COVER To view a video scan the QR code above CAUTION: Please read this manual completely before attempting to install, operate or service this equipment

More information

Manifold Installation Controller MIC-180. Installation and Operation Instructions

Manifold Installation Controller MIC-180. Installation and Operation Instructions Manifold Installation Controller MIC-180 Installation and Operation Instructions For Use With Rheem-Ruud and Paloma Commercial Tankless Water Heaters Table of Contents Safety Information... 1-2 Manifold

More information

SAFETY INFORMATION AND WARNINGS

SAFETY INFORMATION AND WARNINGS This manual refers to the Model SST-3 control panel manufactured since October 31, 2013, which uses a universal (100 277 VAC; 50/60 Hz) power supply. Older units use a voltage-specific power supply and

More information

SMART Electronic control for towel radiators

SMART Electronic control for towel radiators SMART is an electronic thermostat for the automatic control of electric towel radiators. By means of an internal sensor it is capable of keeping the temperature of the towel radiator to a desired value.

More information

Version 4 Controls for smoke and natural ventilation. CompactSmoke WSC 310 / WSC 320 PLUS Smoke control panel 10-20A

Version 4 Controls for smoke and natural ventilation. CompactSmoke WSC 310 / WSC 320 PLUS Smoke control panel 10-20A Version 4 Controls for smoke and natural ventilation 1.55 CompactSmoke WSC 310 / WSC 320 PLUS Smoke control panel 10-20A Natural ventilation Smoke ventilation EN 12101 Rated voltage Maksimal output current

More information

Latest update: Ordinance of the Ministry of Internal Affairs and Communications No. 25 of March 27, 2013

Latest update: Ordinance of the Ministry of Internal Affairs and Communications No. 25 of March 27, 2013 This translation is provisional translation for reference, formally refer to the original text. Ordinance for Technical Specifications pertaining to Transmitters (Ordinance of the Ministry of Home Affairs

More information

- 4 12VDC or 24VDC VDC or 24VDC - Eight (8) Fused Outputs - Eight (8) PTC Outputs. Installing Company: Service Rep.

- 4 12VDC or 24VDC VDC or 24VDC - Eight (8) Fused Outputs - Eight (8) PTC Outputs. Installing Company: Service Rep. 140 58th St. Brooklyn, NY Power Supply/Chargers Installation Guide Models Include: eflow4n/eflow4nx - 4 amp @ 12VDC or 24VDC eflow4n8/eflow4nx8 eflow4n8d/eflow4nx8d - 4 amp @ 12VDC or 24VDC - 4 amp @ 12VDC

More information

- Four (4) Fused Outputs - Four (4) PTC Outputs. - Eight (8) Fused Outputs - Eight (8) PTC Outputs

- Four (4) Fused Outputs - Four (4) PTC Outputs. - Eight (8) Fused Outputs - Eight (8) PTC Outputs AL300ULX Series Power Supply/Charger Installation Guide Models Include: AL300ULX - Single Output AL300ULPD4 AL300ULPD4CB - Four (4) Fused Outputs - Four (4) PTC Outputs AL300ULPD8 AL300ULPD8CB - Eight

More information

Operation and Maintenance Manual

Operation and Maintenance Manual (FKER Series) Repeater Panel (FKER, FKER, FKER8) Operation and Maintenance Manual Man-9EL Issue June Index Section Page. Introduction.... Safety and mounting.... Technical specification.... Control panel

More information

SAFETY WARNINGS. isolated cables with minimum cross-sectional area of 0,75 mm for 230V power supply must be used.

SAFETY WARNINGS. isolated cables with minimum cross-sectional area of 0,75 mm for 230V power supply must be used. SAFETY WARIGS The device must be installed in a place with limited access. The device must be connected to an AC power supply with Protective Earthing: Phase or ive line () black or brown cable, eutral

More information

INSTALLATION AND OPERATING INSTRUCTIONS GN2. HIGH EFFICIENCY CAST IRON BOILER FOR LIQUID and/or GAS FUELS

INSTALLATION AND OPERATING INSTRUCTIONS GN2. HIGH EFFICIENCY CAST IRON BOILER FOR LIQUID and/or GAS FUELS INSTALLATION AND OPERATING INSTRUCTIONS HIGH EFFICIENCY CAST IRON BOILER FOR LIQUID and/or GAS FUELS INDEX 1. Technical information... page 3 2. Dimensional and technical characteristics... page 3 3. Packing

More information

8.0 Table of Contents. Monitoring system WIREM

8.0 Table of Contents. Monitoring system WIREM Table of Contents 8.0 8.0 Table of Contents 8.1 System description 8.100 General system description 8.110 Principle of operation 8.120 Measurement principle 8.2 Planning, inspection plans 8.200 Planning,

More information

ISOMETER IR1575. Insulation monitoring device for unearthed AC/3(N)AC systems up to 480 V and DC systems up to 480 V

ISOMETER IR1575. Insulation monitoring device for unearthed AC/3(N)AC systems up to 480 V and DC systems up to 480 V Insulation monitoring device for unearthed AC/3(N)AC systems up to 480 V and DC systems up to 480 V IR1575_D00116_00_D_XXEN/05.2015 Insulation monitoring device for unearthed AC/3(N)AC systems up to 480

More information

Duct Temperature Sensors

Duct Temperature Sensors 1 762 1761P03 1762P01 Mounting flange AQM630 QAM21 Symaro Duct Temperature Sensors QAM2161040 QAM2171040 Active sensors for acquiring the air temperature in air ducts AC 24 V or DC 13535 V Signal output

More information

For a red enclosure add an R suffix to the part # e.g. eflow4na8dr. Altronix Corp th St. Brooklyn, NY. Installing Company: Service Rep.

For a red enclosure add an R suffix to the part # e.g. eflow4na8dr. Altronix Corp th St. Brooklyn, NY. Installing Company: Service Rep. Power Supply/Chargers Installation Guide Models Include: eflow4na8d - 4A @ 12VDC or 24VDC - Eight (8) PTC Outputs eflow6na8d - 4A @ 12VDC or 24VDC - Eight (8) PTC Outputs eflow102na8d - 10A @ 12VDC - Eight

More information

WELCOME BLUE - NEUTRAL BROWN LIVE GREEN AND YELLOW - EARTH

WELCOME BLUE - NEUTRAL BROWN LIVE GREEN AND YELLOW - EARTH Zephyr 16 DC FAN WELCOME Thank you and congratulation for choosing an EcoAir DC Fan to help you improve the air quality within your home. Inside you will find many helpful tips on how to use and maintain

More information

INSTRUCTION MANUAL T119 1MN0110 REV. 0. operates with ISO9001 certified quality system

INSTRUCTION MANUAL T119 1MN0110 REV. 0. operates with ISO9001 certified quality system INSTRUCTION MANUAL 1MN0110 REV. 0 operates with ISO9001 certified quality system TECSYSTEM S.r.l. 20094 Corsico (MI) Tel.: +39-024581861 Fax: +39-0248600783 http://www.tecsystem.it R. 1.1 25/08/16 ENGLISH

More information

Installation Guide for AL600ULM. Multi-Output Access Control Power Supply Charger. Rev

Installation Guide for AL600ULM. Multi-Output Access Control Power Supply Charger. Rev Installation Guide for AL600ULM Multi-Output Access Control Power Supply Charger Rev. 091800 1 AL600ULM - Multi-Output Access Control Power Supply/Charger Overview: The AL600ULM multi-output access control

More information

Installation and Operation Instructions

Installation and Operation Instructions Smoke and Heat Ventilation Pneumatic - Electronic Control Systems Installation and Operation Instructions Version / SHEVS Control Centre RWZ d K + G Pneumatik GmbH In der Krause 8 9 Eschweiler Deutschland

More information

VACUUM BREAKER MEDIUM VOLTAGE AUTOMATIC TRANSFER SWITCHES

VACUUM BREAKER MEDIUM VOLTAGE AUTOMATIC TRANSFER SWITCHES Part One General 1.01 Scope A. It is the intent of this specification to provide a medium voltage automatic transfer system. B. All components, testing and services specified and required for a complete

More information

KNX module for smoke alarm devices Dual/VdS and Q-Label (Order no )

KNX module for smoke alarm devices Dual/VdS and Q-Label (Order no ) Product definition KNX module for smoke alarm devices Dual/VdS and Q-Label (Order no 2343 00) Art. no 2343 00 Page 1 of 22 Product definition Table of contents 1 Product definition... 3 1.1 Product catalogue...

More information

PANTHER. Condensate removal pump Installation and operating guide

PANTHER. Condensate removal pump Installation and operating guide PANTHER Condensate removal pump Installation and operating guide The PANTHER is a self-contained condensate removal system for use directly inside trunking and highwall-mount air conditioners.the small

More information

HIGH VOLTAGE A.C. PROXIMITY DETECTOR HI-PROX

HIGH VOLTAGE A.C. PROXIMITY DETECTOR HI-PROX HIGH VOLTAGE A.C. PROXIMITY DETECTOR HI-PROX T275HP United States Design Patent : US D474, 705 S INSTRUCTION MANUAL INDEX PAGE Safety Rules... 01 General Description... 02 Low Voltage Testing... 03 Front

More information

02/11/2015

02/11/2015 CTH 46 - CTD 43 / 46 CTD 46 Part number 89422108 CTH 46 Heating / cooling function Measurement and setpoint display CTD 43 Heating or cooling function Measurement display Measurement deviation display-setpoint

More information

Parts and Service Manual

Parts and Service Manual Section II Parts and Service Manual (70241A) CLARKE TECHNOLOGY Operator's Manual - MINI MAX Page -29- Frame and Front Cover Assembly Drawing 2/01 Page -30- CLARKE TECHNOLOGY Operator's Manual -MINI MAX

More information

CONTROL DEVICE SLIDETRONIC HD

CONTROL DEVICE SLIDETRONIC HD CONTROL DEVICE SLIDETRONIC HD to control gravity self-closing fire gates Producer: Somati system s.r.o. Jihlavská 510/2c 664 41 Troubsko, okr.brno - venkov Tel.: 547 427 011 Fax: 547 427 013 E-mail: export@somati-system.cz

More information

Gas Central with built-in Gas Detector for Nitrogen Dioxide (NO 2

Gas Central with built-in Gas Detector for Nitrogen Dioxide (NO 2 Features Integrated (built-in NO2 sensor / detector (Electro chemical sensor type Measuring ranges 0-10 ppm, 0-20 ppm or 0-30 ppm LCD display to show actual in ppm Status LED indication Normal operation

More information

ISOMETER IRDH275BM-7 with coupling device AGH675-7 and AGH675-7MV15

ISOMETER IRDH275BM-7 with coupling device AGH675-7 and AGH675-7MV15 with coupling device AGH675-7 and AGH675-7MV15 Device combination for insulation monitoring in unearthed AC, AC/DC and DC power systems (IT systems) IRDH275BM-7_D00123_03_D_XXEN/01.2017 with coupling device

More information

RPSMLR2 RPSMLR2BB. Panic Device Power Controller Installation Guide LISTED. Rev

RPSMLR2 RPSMLR2BB. Panic Device Power Controller Installation Guide LISTED. Rev RPSMLR2 RPSMLR2BB Panic Device Power Controller Installation Guide LISTED Rev. 102715 Overview: RPSMLR2BB, RPSMLR2 will operate up to two (2) 24VDC panic hardware devices simultaneously. It is designed

More information

MODEL B2 INSTALLATION MANUAL

MODEL B2 INSTALLATION MANUAL RELEASE DEVICES GENERAL DESCRIPTION MODEL B2 INSTALLATION MANUAL S/N: The B2 Series Time Delay Release Devices are UL Listed, Canadian Listed, and CSFM Listed for use on rolling doors, single-slide and

More information

SECTION AUTOMATIC TRANSFER SWITCHES

SECTION AUTOMATIC TRANSFER SWITCHES PART 1 - GENERAL 1.1 DESCRIPTION SECTION 26 36 23 This section specifies the furnishing, complete installation, and connection of automatic transfer switches. 1.2 RELATED WORK A. Section 14 21 00, ELECTRIC

More information

Table of Content LT 5165-UL

Table of Content LT 5165-UL Table of Content LT 565-UL. User manual.... Legal regulations... 3. Safety instructions... 3 4. Technical information... 4 5. Technical data... 4 6. Performance Graph... 5 7. Mounting... 6 8. Mounting

More information

4100S. The operation and functions described in this manual are available from Software Version 4100S onwards.

4100S. The operation and functions described in this manual are available from Software Version 4100S onwards. 4100S The operation and functions described in this manual are available from Software Version 4100S-023-013 onwards. Specifications: Item Specification Details Enclosure Steel IP30 Dimensions H x W x

More information

12W Round LED Wall/Ceiling Light with Microwave Sensor

12W Round LED Wall/Ceiling Light with Microwave Sensor 12W Round LED Wall/Ceiling Light with Microwave Sensor Model: LEDSR12WHMS Installation & Operating Instructions 1 1. General Information These instructions should be read carefully and retained for further

More information

AL400ULACM AL600ULACM - 4 amp - 12VDC or 6 amp. - Fused Outputs - Fused Outputs

AL400ULACM AL600ULACM - 4 amp - 12VDC or 6 amp. - Fused Outputs - Fused Outputs ACM Series Access Power Controllers with Power Supplies Installation Guide Models Include: AL400ULACM AL600ULACM - 12VDC @ 4 amp - 12VDC or 24VDC @ 6 amp. or 24VDC @ 3 amp - Fused Outputs - Fused Outputs

More information

INSTALLATION MANUAL CONDITIONING ENERGY RECOVERY VENTILATOR (CERV) MODEL CERV-001-PARTA, CERV-001-PARTB

INSTALLATION MANUAL CONDITIONING ENERGY RECOVERY VENTILATOR (CERV) MODEL CERV-001-PARTA, CERV-001-PARTB INSTALLATION MANUAL CONDITIONING ENERGY RECOVERY VENTILATOR (CERV) MODEL CERV-001-PARTA, CERV-001-PARTB BUILD EQUINOX SUPPORT@BUILDEQUINOX.COM (773)-492-1893 REV 0.51-06/22/2016 CONTENTS Specifications...

More information

CONTROL PANELS. Tech Data Sheet D01688GB1 10/2012 Fire Detection. Control Panels of the FX 3NET (ALC) Fire Detection System

CONTROL PANELS. Tech Data Sheet D01688GB1 10/2012 Fire Detection. Control Panels of the FX 3NET (ALC) Fire Detection System Tech Data Sheet D01688GB1 10/2012 Fire Detection CONTROL PANELS Control Panels of the FX 3NET (ALC) Fire Detection System The FX 3NET intelligent fire detection and alarm system and panels from Schneider

More information

Residual Current Devices

Residual Current Devices Residual devices F200 Series UL 1053 Residual devices F200 Series Residual Current Devices Description The F200 Series residual devices offer a wide range of product for all of your fault protection needs.

More information

Operating instructions Safety-monitoring module SRB 302X3. 1 About this document

Operating instructions Safety-monitoring module SRB 302X3. 1 About this document 1 About this document Operating instructions... pages 1 to 6 Translation of the original operating instructions 1.1 Function This operating instructions manual provides all the information you need for

More information

FIREFLY II PLUS RELEASE DEVICES INSTALLATION MANUAL

FIREFLY II PLUS RELEASE DEVICES INSTALLATION MANUAL FIREFLY II PLUS RELEASE DEVICES INSTALLATION MANUAL MADE IN THE U.S.A. U.L. LISTED CANADIAN LISTED CSFM: 7300-1418:100 GENERAL DESCRIPTION SERIAL NUMBER The Cookson Company FIREFLY II PLUS Time Delay Release

More information

MSPA-MP METAPACK SERVICE MANUAL. Visual step-by-step guide to easily identify & correct technical problems! Gecko Electronics Inc.

MSPA-MP METAPACK SERVICE MANUAL. Visual step-by-step guide to easily identify & correct technical problems! Gecko Electronics Inc. MSPA-MP METAPACK SERVICE MANUAL Gecko Electronics Inc. Visual step-by-step guide to easily identify & correct technical problems! Table of Contents Power & Ground Check Tools and Parts 3 Electrical Wiring

More information

Series. Access Power Controllers. Installation Guide

Series. Access Power Controllers. Installation Guide Series Access Power Controllers Installation Guide Models Include: Maxim11 - Power Supply 1: 12VDC @ 3.5 amp or 24VDC @ 2.7 amp. - Power Supply 2: 12VDC @ 3.5 amp or 24VDC @ 2.7 amp. - Sixteen (16) fuse

More information

Retrofit Instructions CLEARVIEW DAY COVER CAUTION: Please read this manual completely before attempting to install, operate or service this equipment

Retrofit Instructions CLEARVIEW DAY COVER CAUTION: Please read this manual completely before attempting to install, operate or service this equipment Retrofit Instructions CLEARVIEW DAY COVER CAUTION: Please read this manual completely before attempting to install, operate or service this equipment This manual is Copyright 2019 Duke Manufacturing Co.

More information

Operator: Save these instructions for future use!

Operator: Save these instructions for future use! F145-1328/F145-1378 Indoor /Outdoor INSTALLATION INSTRUCTIONS Operator: Save these instructions for future use! FAILURE TO READ AND FOLLOW ALL INSTRUCTIONS CAREFULLY BEFORE INSTALLING OR OPERATING THIS

More information

8670 & 8651 series No/Bill Acceptor 8671 & 8652 Series with Bill Acceptors. Product Information. Important Safety Instructions Product Dimensions

8670 & 8651 series No/Bill Acceptor 8671 & 8652 Series with Bill Acceptors. Product Information. Important Safety Instructions Product Dimensions Models - 8670 & 8651 series No/Bill Acceptor 8671 & 8652 Series with Bill Acceptors Page 2 Page 3 Page 4 Page 5 Page 6-11 Page 12 Page 13 Page 13-14 Page 15-20 Page 21 Product Information Specifications

More information

18W Round LED Wall/Ceiling Light with Microwave Sensor

18W Round LED Wall/Ceiling Light with Microwave Sensor 18W Round LED Wall/Ceiling Light with Microwave Sensor Model: LEDMR18WHMS Installation & Operating Instructions 1 1. General Information These instructions should be read carefully and retained for further

More information

INSTRUCTION MANUAL. DECKMA HAMBURG GmbH. Type OMD-12. Oil-in-Water Monitor

INSTRUCTION MANUAL. DECKMA HAMBURG GmbH. Type OMD-12. Oil-in-Water Monitor INSTRUCTION MANUAL Oil-in-Water Monitor Type OMD-12 DECKMA HAMBURG GmbH Kieler Straße 316, D-22525 Hamburg Tel.: ++49 40 54 88 76-0, Fax: ++49 40 54 88 76-10, email: post@deckma.com IMPORTANT NOTICE Replacement

More information

User s Manual. For the SHORE POWER CONNECTION MONITOR MODEL 9151

User s Manual. For the SHORE POWER CONNECTION MONITOR MODEL 9151 User s Manual For the SHORE POWER CONNECTION MONITOR MODEL 9151 Table of Contents: Product Description... 3 Installation... 4 Optional Remote Alarm Installation... 7 Operator Test... 8 Alarms... 9 Figures...

More information

10 to 30 VDC Diffuse 40 mm ±10 mm NPN and PNP, switch-selectable

10 to 30 VDC Diffuse 40 mm ±10 mm NPN and PNP, switch-selectable R Label Detection Sensor E3S-CD68/63 Detect Labels Regardless of Label Color or Luster, Bottle Color or Clarity H High-performance circuitry detects wide variety of labels on clear and colored bottles

More information

AL3000 SERIES 100MM CHART MULTI-POINT TYPE HYBRID RECORDER

AL3000 SERIES 100MM CHART MULTI-POINT TYPE HYBRID RECORDER AL3000 SERIES 100MM CHART MULTI-POINT TYPE HYBRID RECORDER MODEL AL3 7 5 - AL3000 series conforming to CE, UL and CSA are 100mm multi-point type hybrid recorders with a simultaneous display of multi-channel

More information