HEATING, VENTILATING AND AIR CONDITIONING CONSTRUCTION SPECIFICATION SECTION BUILDING MANAGEMENT SYSTEM

Size: px
Start display at page:

Download "HEATING, VENTILATING AND AIR CONDITIONING CONSTRUCTION SPECIFICATION SECTION BUILDING MANAGEMENT SYSTEM"

Transcription

1 HEATING, VENTILATING AND AIR CONDITIONING CONSTRUCTION SPECIFICATION PART 1 GENERAL SECTION MECHANICAL GENERAL PROVISIONS A. This contractor shall conform to the General and Supplementary Conditions Provisions under Division 1 of the Specifications. B. The following sections constitute related work: 1. Section Basic HVAC Requirements 2. Section Pumps 3. Section Direct Drive Roof Upblast Exhaust Fans 4. Section Natural Gas Fired Unit Heaters 5. Section Hot Water Boilers, Piping & Accessories 6. Section Closed Circuit Evaporative Fluid Coolers 7. Section Modular Dedicated Outside Air Unit and Associated Humidifier 8. Section Mini-Split Ductless Cooling System 9. Section Water Source Heat Pumps 10. Section Electric Humidifiers 1.2 RELATED WORK SPECIFIED ELSEWHERE A. Products Supplied But Not Installed Under This Section: 1. Control valves. 2. Flow switches. 3. Wells, pipe sockets and other inline hardware for water sensors (temperature, pressure, flow). 4. Terminal unit controllers and actuators, when installed by terminal unit manufacturer. B. Products Installed But Not Supplied Under This Section: 1. Gas Fired Prop Heater Thermostats C. Products Not Furnished or Installed But Integrated with the Work of This Section: 1. Heat Pumps 2. Fluid Cooler System 3. Boiler System 4. Humidifiers 5. Dedicated Outside Air Unit 6. Unit Heaters 7. Primary Pumps, Fluid Cooler Freeze Protection Pumps 8. In-line Meters (Heat Pump System Make-Up Water) 9. Fire Alarm System and Smoke Detectors (through alarm relay contacts) 10. Roof Exhaust Fan Project No

2 11. Unified Lighting Controls, however the BAS is to provide scheduled daily on/off control of grow lights in all Grow Rooms. Schedule must be adjustable from the BAS. Coordinate with the Unified Lighting Control System Supplier. D. Work Required Under Division and Related to This Section: 1.3 SUMMARY 1. Power wiring to line side of motor starters, disconnects or variable frequency drives. 2. Provision and wiring of smoke detectors and other devices relating to fire alarm system. 3. Facility LAN (Ethernet) connection adjacent to JACE network management controller to be located in IT Room Unified Lighting Control System. A. Scope: Furnish all labor, materials and equipment necessary for a complete and operating Building Management System (BMS), utilizing Direct Digital Controls as shown on the drawings and as described herein. Drawings are diagrammatic only. All controllers furnished in this section shall communicate on a peer-to-peer bus over a single Fox protocol bus. 1. The intent of this specification is to provide a system that is consistent with BMS systems throughout the owner s facilities running the Niagara AX Framework. 2. System architecture shall fully support a multi-vendor environment and be able to integrate third party systems via existing vendor protocols including, as a minimum, BACnet, and Modbus. 3. System architecture shall provide secure Web access using MS Internet Explorer from any computer on the owner s LAN. 4. All control devices furnished with this Section shall be programmable directly from the Niagara-AX Workbench upon completion of this project. The use of configurable or programmable controllers that require additional software tools for post-installation maintenance shall not be acceptable. 5. Any control vendor that must provide additional BMS server software shall be unacceptable. Only systems that utilize the WEBs Niagara AX Framework shall satisfy the requirements of this section. 6. The BMS server shall host all graphic files for the control system. All graphics and navigation schemes for this project shall match those that are on the existing campus Niagara-AX framework server. 7. A laptop computer including engineering/programming software to modify Operating System Server BMS programs and graphics shall be included 8. OPEN NIC STATEMENTS - All NiagaraAX software licenses shall have the following NiCS: accept.station.in=* ; accept.station.out=* and accept.wb.in=* and accept.wb.out=*. All open NIC statements shall follow Niagara Open NIC specifications 9. All JACE hardware products used on this project must be Made in the USA or come through the Tridium Richmond, VA shipping facility. JACE hardware products not meeting these requirements will not be allowed. Project No

3 B. Approved Manufacturers: Honeywell C. Approved Installation Contractors: Building Control Specialist (BCS) 1.4 SUBMITTALS: 1. Trained and licensed to sell & install Honeywell WEBs-AX 2. Complete access to Honeywell s commercial product portfolio 3. At least 1 WEBs-AX certified technician on staff Building Renovations A. Submit documentation of contractor qualifications, including those indicated in paragraph 1.9 Quality Assurance if requested by the A-E. B. Eight copies of shop drawings of the entire control system shall be submitted and shall consist of a complete list of equipment and materials, including manufacturers catalog data sheets and installation instructions. Samples of written Controller Checkout Sheets and Performance Verification Procedures for applications similar in scope shall be included for approval. C. Shop drawings shall also contain complete wiring and schematic diagrams, sequences of operation, control system bus layout and any other details required to demonstrate that the system has been coordinated and will properly function as a system. Terminal identification for all control wiring shall be shown on the shop drawings. D. Upon completion of the work, provide eight complete sets of as-built drawings and other project-specific documentation in 3-ring hard-backed binders and on compact disc. E. Any deviations from these specifications or the work indicated on the drawings shall be clearly identified in the Submittals. 1.5 AGENCY AND CODE APPROVALS A. All products of the BMS shall be provided with the following agency approvals. Verification that the approvals exist for all submitted products shall be provided on request, with the submittal package. Systems or products not currently offering the following approvals are not acceptable. 1. Federal Communications Commission (FCC), Rules and Regulations, Volume II -July 1986 Part 15 Class A Radio Frequency Devices 2. FCC, Part 15, Subpart J, Class A Computing Devices 3. UL Industrial Control Equipment 4. UL Specialty Transformers 5. UL Test Method for Fire and Smoke Characteristics of Electrical and Optical- Fiber Cables Used in Air-Handling Spaces 6. UL Energy Management Systems All 7. UL 1449 Transient Voltage Suppression 8. Standard Test for Flame Propagation Height of Electrical and Optical - Fiber Cables Installed Vertically in Shafts 9. EIA/ANSI 232-E - Interface Between Data Technical Equipment and Data Circuit Terminal Equipment Employing Serial Binary Data Interchange Project No

4 10. EIA Standard Test Procedures for Fiber Optic Fibers, Cables, Transducers, Connecting and Terminating Devices 11. IEEE C Surge Voltages in Low-Voltage AC Power Circuits 12. IEEE Recommended Practice for Grounding of Industrial and Commercial Power Systems 13. NEMA Enclosures for Electrical Equipment 14. NEMA ICS 1 - Industrial Controls and Systems 15. NEMA ST 1 - Specialty Transformers 16. NCSBC Compliance, Energy: Performance of control system shall meet or surpass the requirements of ASHRAE/IESNA SOFTWARE OWNERSHIP A. The Owner shall have full ownership and full access rights for all network management, operating system server, engineering and programming software required for the ongoing maintenance and operation of the BMS. 1.7 DELIVERY, STORAGE AND HANDLING A. Maintain integrity of shipping cartons for each piece of equipment and control device through shipping, storage, and handling as required to prevent equipment damage. Store equipment and materials inside and protected from weather. 1.8 JOB CONDITIONS A. Cooperation with Other Trades: Coordinate the Work of this section with that of other sections to insure that the Work will be carried out in an orderly fashion. It shall be this Contractor's responsibility to check the Contract Documents for possible conflicts between his Work and that of other crafts in equipment location, pipe, duct and conduit runs, electrical outlets and fixtures, air diffusers, and structural and architectural features. 1.9 QUALITY ASSURANCE A. The manufacturer of the BMS digital controllers shall, if requested, provide documentation supporting compliance with ISO-9001 (Model for Quality Assurance in Design/Development, Production, Installation and Servicing). B. The Control System Contractor shall have a full service DDC office within a 100 mile radius of the job site. This office shall be staffed with applications engineers, software engineers and field technicians. This office shall maintain parts inventory and shall have all testing and diagnostic equipment necessary to support this Work, as well as staff trained in the use of this equipment. C. Single Source Responsibility of Supplier: The Control System Contractor shall be responsible for the complete installation and proper operation of the control system. The Control System Contractor shall exclusively be in the regular and customary business of design, installation and service of computerized building management systems similar in size and complexity to the system specified. The Control System Contractor shall be the manufacturer of the primary DDC system components or shall have been the authorized representative for the primary DDC components manufacturer for at least 5 years. All control panels shall be assembled by the Control System Contractor in a UL-Certified 508A panel shop. Project No

5 D. Equipment and Materials: Equipment and materials shall be cataloged products of manufacturers regularly engaged in the production and installation of HVAC control systems. Products shall be manufacturer's latest standard design and have been tested and proven in actual use SPECIFICATION NOMENCLATURE - Acronyms used in this specification are as follows: A. Actuator: Control device that opens or closes valve or damper in response to control signal. B. AI Analog Input C. AO Analog Output D. Analog Continuously variable state over stated range of values E. BMS Building Management System F. DDC Direct Digital Control G. Discrete Binary or digital state H. DI Discrete Input I. DO Discrete Output J. FC Fail Closed position of control device or actuator. Device moves to closed position on loss of control signal or energy source. K. FO Fail open (position of control device or actuator). Device moves to open position on loss of control signal or energy source. L. GUI Graphical User Interface M. HVAC Heating, Ventilating and Air Conditioning N. IDC Interoperable Digital Controller O. ILC Interoperable Lon Controller P. LAN Local Area Network Q. Modulating Movement of a control device through an entire range of values, proportional to an infinitely variable input value. R. Motorized Control device with actuator S. NAC Network Area Controller T. NC Normally closed position of switch after control signal is removed or normally closed position of manually operated valves or dampers. U. NO Normally open position of switch after control signal is removed; or the open position of a controlled valve or damper after the control signal is removed; or the usual position of a manually operated valve. V. OSS Operating System Server, host for system graphics, alarms, trends, etc. W. Operator Same as actuator X. PC Personal Computer Project No

6 PART 2 Building Renovations Y. Peer-to-Peer Mode of communication between controllers in which each device connected to network has equal status and each shares its database values with all other devices connected to network Z. P Proportional control; control mode with continuous linear relationship between observed input signal and final controlled output element. AA. PI BB. PICS CC. PID DD. Point EE. WAN MATERIALS 2.1 Acceptable Manufacturers Proportional-Integral control, control mode with continuous proportional output plus additional change in output based on both amount and duration of change in controller variable (reset control). BACnet Product Interoperability Compliance Statement Proportional-Integral-Derivative control, control mode with continuous correction of final controller output element versus input signal based on proportional error, its time history (reset) and rate at which it s changing (derivative). Analog or discrete instrument with addressable database value Wide Area Network A. The Building Management System (BMS) shall be comprised of a network of interoperable, stand-alone digital controllers, a network area controller, graphics and programming, and other control devices for a complete system as specified herein. B. The installed system shall provide secure password access to all features, functions and data contained in the overall BMS. C. Building Management System and standard products as manufactured by Honeywell and furnished by DMS Controls Group, LLC. NO EXCEPTIONS. D. Honeywell Authorized Systems Distributor (ASD) to furnish BMS and standard products: DMS Controls Group, LLC 1409 Duncan Avenue, Suite 201 Pittsburgh, PA PHONE: dave@dmscontrolsgroup.com E. Miller Electric Construction, Inc Automation Group (to install and wire BAS System) A Honeywell BCS Controls Contractor NO EXCEPTIONS 4377 William Flynn Highway (Route 8) Allison Park, PA PHONE: : Bill.McQuaide@MillerElectric.com 2.2 OPEN, INTEROPERABLE, INTEGRATED ARCHITECTURE A. The intent of this specification is to provide a peer-to-peer networked, stand-alone, distributed control system utilizing the BACnet technology communication protocol in one open, interoperable system. Project No

7 B. The supplied computer software shall employ object-oriented technology (OOT) for representation of all data and control devices within the system. Physical connection of any BACnet control equipment, such as chillers, shall be via Ethernet. C. All components and controllers supplied under this contract shall be true peer-to-peer communicating devices. Components or controllers requiring polling by a host to pass data shall not be acceptable. D. All components and controllers supplied under this contract shall be true peer-to-peer communicating devices. Components or controllers requiring polling by a host to pass data shall not be acceptable. E. The supplied system must incorporate the ability to access all data using Java enabled browsers without requiring proprietary operator interface and configuration programs. An Open Database Connectivity (ODBC) or Structured Query Language (SQL) compliant server database is required for all system database parameter storage. This data shall reside on the existing Operating System Server currently located in the Facilities Office on the LAN. Systems requiring proprietary database and user interface programs shall not be acceptable. F. A hierarchical topology is required to assure reasonable system response times and to manage the flow and sharing of data without unduly burdening the customer s internal Intranet network. Systems employing a flat single tiered architecture shall not be acceptable. 14. Maximum acceptable response time from any alarm occurrence (at the point of origin) to the point of annunciation shall not exceed 5 seconds for network connected user interfaces. 15. Maximum acceptable response time from any alarm occurrence (at the point of origin) to the point of annunciation shall not exceed 60 seconds for remote or dial-up connected user interfaces. 2.3 SYSTEM NETWORK CONTROLLER (SNC) A. These controllers are designed to manage communications between the programmable equipment controllers (PEC), application specific controllers (ASC), and advanced unitary controllers (AUC) which are connected to its communications trunks, manage communications between itself and other system network controllers (SNC) and with any operator workstations (OWS) that are part of the BAS, and perform control and operating strategies for the system based on information from any controller connected to the BAS. B. The controllers must be fully programmable to meet the unique requirements of the facility it must control. C. The controllers must be capable of peer-to-peer communications with other SNC s and with any OWS connected to the BAS, whether the OWS is directly connected, connected via modem or connected via the Internet. D. The communication protocols utilized for peer-to-peer communications between SNC s will be Niagara AX, BACnet TCP/IP and SNMP. Use of a proprietary communication protocol for peer-to-peer communications between SNC s is not allowed. Project No

8 E. The SNC shall be capable of executing application control programs to provide: 14. Calendar functions 15. Scheduling 16. Trending 17. Alarm monitoring and routing 18. Time synchronization 19. Integration of LonWorks, BACnet, and ModBus controller data 20. Network management functions for all SNC, PEC and ASC based devices F. The SNC must provide the following hardware features as a minimum: 14. One Ethernet Port-10/100 Mdps 15. One RS-232/485 port 16. One BACnet Interface Port 17. Battery Backup 18. Flash memory for long term data backup (If battery backup or flash memory is not supplied, the controller must contain a hard disk with at least 1 gigabyte storage capacity) G. The SNC shall support standard Web browser access via the Intranet/Internet. It shall support a minimum of 16 simultaneous users. H. The SNC shall provide alarm recognition, storage, routing, management and analysis to supplement distributed capabilities of equipment or application specific controllers. I. The SNC shall be able to route any alarm condition to any defined user location whether connected to a local network or remote via dial-up, telephone connection, or wide-area network. 14. Alarm generation shall be selectable for annunciation type and acknowledgement requirements including but not limited to: a. Alarm, b. Return to normal, c. To default. 15. Alarms shall be annunciated in any of the following manners as defined by the user: a. Screen message text, b. of complete alarm message to multiple recipients. c. Pagers via paging services that initiate a page on receipt of message. d. Graphics with flashing alarm object(s). 16. The following shall be recorded by the SNC for each alarm (at a minimum): a. Time and date Project No

9 b. Equipment (air handler #, accessway, etc.) c. Acknowledge time, date, and user who issued acknowledgement. J. Programming software and all controller Setup Wizards shall be embedded into the SNC. 2.4 PROGRAMMABLE EQUIPMENT CONTROLLER (PEC) A. HVAC control shall be accomplished using BACnet based devices. The controller platform shall provide options and advanced system functions, programmable and configurable using Niagara AX Framework, that allow standard and customizable control solutions required in executing the Sequence of Operation. B. All PECs shall be application programmable and shall at all times maintain their BACnet certification. All control sequences within or programmed into the ILC shall be stored in non-volatile memory, which is not dependent upon the presence of a battery to be retained. C. The PECs shall communicate with the SNC at a baud rate of not less than 78.8K baud. The PEC shall provide LED indication of communication and controller performance to the technician, without cover removal. D. Each PEC shall have expansion ability to support additional I/O requirements through the use of remote input/output modules E. PEC Controllers shall support the following control techniques: 14. Ten configurable general-purpose control loops that can incorporate Demand Limit Control strategies, Setpoint reset, adaptive intelligent recovery, and time of day bypass. 15. Ten general-purpose, non-linear control loops. 16. Eight start/stop Loops. 17. Thirty-two If/Then/Else logic loops. 18. Thirty-six Math Function loops (MIN, MAX, AVG, SUM, SUB, SQRT, MUL, DIV, ENTHALPY). 2.5 ADVANCED UNITARY CONTROLLER A. The controller platform shall be designed specifically to control HVAC ventilation, filtration, heating, cooling, humidification, Dehumidification, and distribution. Equipment includes: constant volume air handlers, VAV air handlers, packaged RTU, heat pumps, unit vents, fan coils, natural convection units, and radiant panels. The controller platform shall provide options and advanced system functions, programmable and configurable using Niagara AX Framework, that allow standard and customizable control solutions required in executing the Sequence of Operation as outlined here-in in Section 4. B. Minimum Requirements: 14. The controller shall be capable of either integrating with other devices or stand-alone operation. 15. The controller shall have two microprocessors. The Host processor contains on-chip FLASH program memory, FLASH information memory, and RAM to run the main HVAC application. The second processor for BACnet network communications. Project No

10 a. FLASH Memory Capacity: 372 Kilobytes with 8 Kilobytes for application program. b. FLASH Memory settings retained for ten years. c. RAM: 8 Kilobytes 16. The controller shall have an internal time clock with the ability to automatically revert from a master time clock on failure. a. Operating Range: 24 hour, 365 day, multi-year calendar including day of week and configuration for automatic day-light savings time adjustment to occur on configured start and stop dates. b. Accuracy: ±1 minute per month at 77 F (25 C). c. Power Failure Backup: 24 hours at 32 to 100 F (0 to 38 C), 22 hours at 100 to 122 F (38 to 50 C). 17. The controller shall include Sylk Bus, a two wire, polarity insensitive bus that provides both 18 Vdc power and communications between a Sylk-enabled device and a Sylk-enabled controller. 18. The controller shall have an internal DC power supply to power external sensors. a. Power Output: 20 VDC ±10% at 75 ma. 19. The controller shall have a visual indication (LED) of the status of the device: a. Controller operating normally. b. Controller in process of download. c. Controller is in reflash mode d. No power to controller, low voltage, or controller damage. e. Processor and/or controller are not operating. 20. The controller shall have a visual indication (LED) of the BACnet MS/TP communication status of the device: a. Processor missing bootloader image. b. Bootloader running and no MS/TP token present. c. Bootloader running and there is MS/TP communication. d. BACnet communications processor is not running 21. The minimum controller Environmental ratings a. Operating Temperature Ambient Rating: -40 to 150 F (-40 to 65.5 C). b. Storage Temperature Ambient Rating: -40 to 150 F (-40 to 65.5 C). c. Relative Humidity: 5% to 95% non-condensing. 22. The controller shall have the additional approval requirements, listings, and approvals: a. UL/cUL (E87741) listed under UL916 (Standard for Open Energy Management Equipment) with plenum rating. b. BACnet Application Specific Controller (B-ASC) Project No

11 c. CSA (LR ) Listed Building Renovations d. Meets FCC Part 15, Subpart B, Class B (radiated emissions) requirements. e. Meets Canadian standard C108.8 (radiated emissions). f. Conforms to the following requirements per European Consortium standards: EN ; 2001 (EU Immunity) EN ; 2001 (EU Emissions) 23. The controller housing shall be UL plenum rated mounting to either a panel or DIN rail (standard EN50022; 7.5mm x 35mm). 24. The controller shall have sufficient on-board inputs and outputs to support the application. a. Analog outputs (AO) shall be capable of being configured to support 0-10 V, 2-10 V or 4-20 ma devices. b. Triac outputs shall be capable of switching 30 Volts at 500 ma. c. Input and Output wiring terminal strips shall be removable from the controller without disconnecting wiring. Input and Output wiring terminals shall be designated with color coded labels. d. Universal inputs shall be capable of being configured as binary inputs, resistive inputs, voltage inputs (0-10 VDC), or current inputs (4-20 ma). e. Relay outputs, where applicable, shall be capable of switching 30 Volts at 1 Amp. 25. The controller platform shall have standard HVAC application programs that are modifiable to support both the traditional and specialized sequence of operations as outlined here-in in Section 4. a. Discharge air control and low limit 2.6 OTHER CONTROL SYSTEM HARDWARE (ALL EQUIPMENT LISTED MAY NOT APPLY) A. Motorized control dampers that will not be integral to the equipment shall be furnished by the Control System Contractor. Control damper frames shall be constructed of galvanized steel, formed into changes and welded or riveted. Dampers shall be galvanized, with nylon or bronze bearings. Blade edge seals shall be vinyl. Blade edge and tip seals shall be included for all dampers. Blades shall be 16-gauge minimum and 6 inches wide maximum and frame shall be of welded channel iron. Damper leakage shall not exceed 10 CFM per square foot, at 1.5-inches water gauge static pressure. B. Control damper actuators shall be furnished by the Control System Contractor. Twoposition or proportional electric actuators shall be direct-mount type sized to provide a minimum of 5 in-lb torque per square foot of damper area. Damper actuators shall be spring return type. Operators shall be heavy-duty electronic type for positioning automatic dampers in response to a control signal. Motor shall be of sufficient size to operate damper positively and smoothly to obtain correct sequence as indicated. All applications requiring proportional operation shall utilize truly proportional electric actuators. Project No

12 C. Control Valves: Control valves shall be 2-way or 3-way pattern as shown and constructed for tight shutoff at the pump shut-off head or steam relief valve pressure. Control valves shall operate satisfactorily against system pressures and differentials. Two-position valves shall be line size. Proportional control valves shall be sized for a maximum pressure drop of 5.0 psi at rated flow (unless otherwise noted or scheduled on the drawings). Valves with sizes up to and including 2 inches shall be screwed configuration and 2-1/2 inch and larger valves shall be flanged configuration. All control valves, including terminal unit valves, less than 2 inch shall be globe valves. Electrically-actuated control valves shall include spring return type actuators sized for tight shut-off against system pressures (as specified above) and, when specified, shall be furnished with integral switches for indication of valve position (open-closed). Pneumatic actuators for valves, when utilized, shall be sized for tight shut-off against system pressures (as specified above). D. Control Valve Actuators: Actuators for VAV terminal unit heating coils shall be driveopen; drive-closed type. All actuators shall have inherent current limiting motor protection. Valve actuators shall be 24-volt, electronic type, modulating or two-position as required for the correct operating sequence. Actuators on valves needing fail-safe operation shall have spring return to Normal position. Modulating valves shall be positive positioning in response to the signal. All valve actuators shall be UL listed. E. All control valves 2 ½ or larger shall have position indication. All hot water control valves shall be Normally-Open arrangement; all chilled water control valves shall be Normally- Closed arrangement. F. Wall Mount Room Temperature sensors: Each room temperature sensor shall provide temperature indication to the digital controller, provide the capability for a software-limited occupant set point adjustment (warmer-cooler slider bar or switch) and limited operation override capability. Room Temperature Sensors shall be 20,000-ohm thermistor type with a temperature range of -32 to 120 degrees F. The sensor shall be complete with a decorative cover and suitable for mounting over a standard electrical utility box. These devices shall have an accuracy of 0.36 degrees, F., over the entire range. G. Duct-mounted and Outside Air Temperature Sensors: 20,000-ohm thermistor temperature sensors with an accuracy of ± 0.2ºC. Outside air sensors shall include an integral sun shield. Duct-mounted sensors shall have an insertion measuring probe of a length appropriate for the duct size, with a temperature range of -40 to 160 degrees F. The sensor shall include a utility box and a gasket to prevent air leakage and vibration noise. For all mixed air and preheat air applications, install bendable averaging duct sensors with a minimum 8 - foot long sensor element. These devices shall have accuracy of 0.5 degrees, F., over the entire range. H. Humidity sensors shall be thin-film capacitive type sensor with on-board nonvolatile memory, accuracy to plus or minus three percent (3%) at 20% to 80% RH, VDC input voltage, analog output (0-10 VDC or 4-20mA output). Operating range shall be 5% to 95% RH and 32 to 125 degree F. Sensors shall be selected for wall, duct or outdoor type installation as appropriate. Project No

13 I. Carbon Dioxide Sensors (CO 2): Sensors shall utilize Non-dispersive infrared technology (N.D.I.R.), repeatable to plus or minus 20 PPM. Sensor accuracy of 75 ppm over a range of ppm. Accuracy shall be plus or minus five percent (5%) or 75 PPM, whichever is greater. Response shall be less than one minute. Input voltage shall be 20 to 30 VAC or DC. Output shall be 0-10 VDC. Sensor shall be wall or duct mounted type, as appropriate for the application, housed in a high impact plastic enclosure. J. Current Sensitive Switches: Solid state, split core current switch that operates when the current level (sensed by the internal current transformer) exceeds the adjustable trip point. Current switch to include an integral LED for indication of trip condition and a current level below trip set point. K. Differential Analog (duct) Static Pressure Transmitters Provide a pressure transmitter with integral capacitance type sensing and solid-state circuitry. Accuracy shall be plus or minus 1% of full range; range shall be selected for the specific application. Provide zero and span adjustment capability. Device shall have integral static pickup tube. L. Differential Air Pressure Switches: Provide SPDT type, UL-approved, and selected for the appropriate operating range where applied. Switches shall have adjustable setpoints and barbed pressure tips. M. Water Flow Switches: Provide a SPST type contact switch with bronze paddle blade, sized for the actual pipe size at the location. If installed outdoors, provide a NEMA-4 enclosure. Flow switch shall be UL listed. N. Temperature Control Panels: Furnish temperature control panels of code gauge steel with locking doors for mounting all devices as shown. All electrical devices within a control panel shall be factory wired. Control panel shall be assembled by the BMS in a UL- Certified 508A panel shop. A complete set of as-built control drawings (relating to the controls within that panel) shall be furnished within each control panel. O. Pipe and Duct Temperature sensing elements: 20,000-ohm thermister temperature sensors with and accuracy of ±1% accuracy. Their range shall be -5- to 250 deg. F. Limited range sensors shall be acceptable provided they are capable of sensing the range expected for the point at the specified accuracy. Thermal wells with heat conductive gel shall be included. P. Low Air Temperature Sensors: Provide SPST type switch, with 15 to 55 degrees F., range, vapor-charged temperature sensor. Honeywell model L482A, or approved equivalent. Q. Relays: Start/stop relay model shall provide either momentary or maintained switching action as appropriate for the motor being started. All relays shall be plugged in, interchangeable, mounted on a subbase and wired to numbered terminals strips. Relays installed in panels shall all be DPDT with indicating lamp. Relays installed outside of controlled devices shall be enclosed in a NEMA enclosure suitable for the location. Relays shall be labeled with UR symbol. RIB-style relays are acceptable for remote enable/disable. R. Mushroom Type Emergency Stop Switch: Provide toggle-type switch with normally-closed contact. Switch shall be labeled BOILER/WATER HEATER EMERGENCY SHUTOFF, NORMAL - OFF.. S. Transducers: Differential pressure transducers shall be electronic with a 4-20 ma. output signal compatible to the Direct Digital Controller. Wetted parts shall be stainless steel. Unit shall be designed to operate in the pressure ranges involved. Project No

14 T. Control Power Transformers: Provide step-down transformers for all DDC controllers and devices as required. Transformers shall be sized for the load, but shall be sized for 50 watts, minimum. Transformers shall be UL listed Class 2 type, for 120VAC/24VAC operation. U. Line voltage protection: All DDC system control panels that are powered by 120 VAC circuits shall be provided with surge protection. This protection is in addition to any internal protection provided by the manufacturer. The protection shall meet UL, ULC 1449, IEEE C62.41B. A grounding conductor, (minimum 12 AWG), shall be brought to each control panel. 2.7 PORTABLE OPERATOR S TOOL (LAPTOP COMPUTER) A. The laptop computer shall consist of an Intel Pentium based laptop computer (minimum processing speed of 2.0 GHz with 2 GB RAM and a 80-gigabyte minimum hard drive). It shall include a CD-ROM drive, and appropriate connectors and cables for communication with the Ethernet network. SEQUENCE OF OPERATION 1. SYSTEM NETWORK CONTROLLER (SNC) A. The system network controller shall control the water loop and coordinate control of individual equipment controllers. B. The SNC shall provide a central operator interface, including but not limited to alarming, outdoor and space temperature and humidity setpoint and monitoring, occupancy scheduling, CO2 monitoring, and lighting schedule. C. The SNC controller will monitor the facility utilities: electric, natural gas, and water. D. Alarms 1) If a Fire Alarm is detected, the SNC will broadcast a Shutdown to all units. All equipment will stop. 2) Heat Pump Water Temperature: Generate a high and low alarm if the water temperature is above 90 degrees or below 60 degrees respectively for more than 15 minutes. E. Schedules 1) Office Space Occupied/Unoccupied Mode of Operation for lighting and HVAC control. Provide an occupied/unoccupied schedule with holiday, special events, and 2-hour unoccupied override. 2) Grow Space Day/Night Mode of Operation for lighting and HVAC control for each type of grow room: Propagation, Vegetative, Flower, and Curing Room. 3) The BAS system shall provide a staged start-up and shut-down to avoid large demand changes and provide power failure restart delay. 2. HEAT PUMP WATER SUPPLY SYSTEM A. PRIMARY PUMPS The primary pumps supply water to the heat pump system. Project No

15 1) The primary pump system is comprised of the following: a. Two primary pumps. b. Two VFDs for pump control. c. Two triple duty valves. d. Inlet and discharge pressure gauges. e. Two differential pressure sensors to be averaged. redundant pressure transmitters located on the common discharge line. f. One flow sensor and transmitter on the common return line. 2) One (1) pump is duty; one (1) pump is standby. 3) Pumps shall switch duty according to a schedule initially on a monthly basis, however the Owner is to be consulted during set-up of the BAS as to what schedule they require. 4) The ATC Sub-Contractor is to furnish and install two (2) Variable Frequency Drive (VFD s), one for each pump. Power wiring will be furnished and installed by the Electrical Contractor. The ATC Sub-Contractor is to provide two (2) pressure differential sensors stats in the water piping to be averaged to provide a pre-set amount of pressure in the system via the VFD s. 5) Once a primary pump has started, it will run for a minimum of 15 minutes to prevent cycling. Limit the maximum number of motor starts to 3 per hour. Alarm if limit is met. 6) When there is at least one WSHP demand, the duty pump will operate to maintain a loop supply pressure to be field determined. The duty pump should be operating constantly when the facility is in operation. However, there will be times when the facility will not be in full operation. If the water pressure is greater than 10 psig over the operating pressure for more than 60 seconds, a Water Supply Loop High Pressure alarm is generated and the heat pump controllers will open the isolation valves to reduce pressure. 7) Generate an alarm if there is no flow in the loop and outdoor air temperature is less than or equal to 40 degrees F to protect against freezing. B. CLOSED CIRCUIT EVAPORATIVE FLUID COOLER 1) The fluid cooler system is comprised of the following: a. Two closed circuit evaporative fluid coolers that are factory furnished with: 1. Two (2) water circulating pumps (to circulate water from the cooler sump to cascade over the cooler coil that contains the closed circuit glycol solution. 2. Air circulation fans to cause increased evaporation of the sump water as air is circulated around the cooler coils. 3. VFDs for fan control. b. Two fluid cooler freeze protection pumps. c. Two, motor operated, on-off valves on fluid cooler supply line. 2) The cooler is to be factory furnished with a control system that is BACNet compatible to allow BAS to read and monitor all functions of the unit. Coordinate with the unit manufacturer. Project No

16 3) Power wiring will be furnished and installed by the Electrical Contractor. 4) The unit manufacturer is to provide two (2) immersion thermostats with wells to be installed by the ATC Sub-Contractor in the water piping to control cooler circulating pumps and VFD s to maintain a preset maximum 85 F water temperature. The cooler manufacturer is to provide all transmitters and other controls. 5) The freeze protection pumps shall operate when the ambient air temperature is 40 ⁰F or below and either the control valve has closed (and therefore there is no flow thru the cooler) or normal power is lost. 6) The fluid coolers water pumps and if necessary the fans shall operate whenever the water supply temperature is above 85 degrees. 7) Fluid cooler water temperature is to be set-up via the manufacturer s controls and monitored by the BAS system. 8) Fluid coolers shall operate on lead-lag duty and are to switch on a monthly basis; however, the Owner is to be consulted during set-up of the controls as to what schedule they require. C. BOILER SYSTEM 1) The boiler system is comprised of the following: a. Two natural gas fired boilers b. Two boiler circulation pumps c. One three way mixing valve d. Two, redundant, thermowells, temperature elements, and transmitters to be located on the return line. e. One (1) thermowell, temperature sensing element and transmitter to be located on the main heat pump return downstream of the boiler supply connection to serve as a high limit control. f. Two flow proving switches one per boiler. 2) Boilers and boiler circulating pumps are to be energized whenever the water temperature in the heat pump system piping drops below 60 F. Provide a flow proving switch to be proved before the boiler is allowed to operate. 3) Boiler water temperature is also to be set-up via the BAS system. 4) Boilers are to be set-up lead/lag with the duty to be switched based upon a schedule setup in the BAS system. 5) A three way modulating mixing valve is to be furnished by the ATC Sub-Contractor and installed by the HVAC Contractor. Valve is to operate to bleed hot water into the water source heat pump piping system to maintain water temperature. 6) Provide, install and wire a mushroom type emergency shut-down switch to be located at the Boiler Room exit door. Wire this switch to shut-down the boilers and water heaters D. Heat Pump Water Supply System Make-up Water Meter 1) The BAS system will monitor the make-up water flow and total with supervisor reset. Project No

17 3. WATER SOURCE HEAT PUMPS (WSHP) A. Each WSHP Unit shall have the following standard features: Building Renovations 1) 4-way reversing valve which fail to the heating position. When unit reversing valve fails to heating and the room sensor is calling for cooling. This shall generate an alarm. 50VQP units can only fail to heating. 50PCV units are fail to heating as standard and may be able to 2) Refrigerant high pressure switch 3) Low pressure sensor to detect loss of refrigerant. 4) Low air temperature sensor to protect against freezing 5) Water loop temperature monitoring 6) Water coil freeze protection 7) Condensate overflow shutdown 8) Low and High Voltage protection 9) Anti-short compressor cycle protection 10) Selectable 24V or pilot duty dry contact alarm output with selectable constant output or pulse output for communication of specific fault alarm. 11) VFD for fan speed control (to be furnished, installed and wired by the ATC Sub- Contractor only for units in Propagation 120 & 122, Vegetative 123, Flower 124, 125 & 126 and R&D Grow Room 152). B. Each unit will have a 24V, 2-way, motorized water valve. C. Space sensors shall be BACnet on the same network as the units that serve the space. D. Schedules and set points shall be managed through the BAS Supervisory Station. E. The units shall be shut down on fire or smoke detection (2000 cfm and above). Smoke detectors are to be furnished by the Electrical Contractor and wired to the BAS System by the BAS System Sub-Contractor. The Electrical Contractor is to wire smoke detectors into the Fire Alarm System. F. Fan speeds shall be controlled to provide the cfm specified based on the fan curve provided by the manufacturer. G. WSHP Unit Mode of Operation There are five possible modes of operation for each unit; Dehumidification, Cooling, Heating, Fan, Vent, and Off. 1) Off Mode - The unit is off and no overrides are active. 2) Fan Mode No heating or cooling demand exists during the occupied mode of operation. The fan will operate as described below for the area serviced. 3) Cool Mode A cooling demand is generated when the space temperature rises above the cooling setpoint and is satisfied when space temperature falls below the cooling setpoint. Provide PID temperature control. A minimum of 2 ⁰F shall separate the cooling and heating setpoints. Project No

18 4) Heat Mode A heating demand is generated when the space temperature drops below the heating setpoint and is satisfied when space temperature rises above the heating setpoint. Provide PID temperature control. A minimum of 2 ⁰F shall separate the cooling and heating setpoints. 5) Dehumidification Mode Where required, the unit will operate in cooling mode to control the relative humidity of the space instead of temperature control. Provide PID relative humidity control (15 tons and above as well as Curing Room units). H. WSHP Operation Upon Demand from Unit 1) The Heat Pump Water Supply System will provide a proof of flow Enable signal. 2) Once the minimum off cycle time has expired, open the isolation valve. 3) If a mode change from heating or cooling is required, switch the Reversing Valve and implement a 10 second delay. 4) After the reversing valve delay is complete, energize the Compressor. The compressor shall have a minimum run time of 10 minutes. I. Dual heat pump units serving Propagation 120 & 122, Vegetative 123, Flower 124, 125 & 126: 1) Both unit fans are to run continuously. 2) One (1) unit is to provide cooling/heating ( day or night setting). 3) One (1) unit is to provide dehumidification. 4) Units are to, on a pre-set schedule, automatically switch functions from cooling/heating to dehumidification. Schedule is to initially be switched on a monthly basis, however, the Owner is to consulted during set-up of the BAS as to what schedule they require. 5) Each unit is to have a Variable Frequency Drive (VFD) to control the speed of the unit fans. a. When the unit is in the cooling/heat mode the VFD is to operate the unit fans to provide the scheduled cfm to provide maximum sensible cooling. b. When the unit is in dehumidifying mode the VFD is to operate at the standard 400 cfm per ton to provide dehumidification. 6) Each unit is to have a two-way, motorized, shut-off valve to be provided by the unit manufacturer that is to shut-off the water flow to the unit whenever the unit compressor is shut down. Provide a 5-minute period between compressor run cycles. 7) Each unit is to have a manufacturer provided sensor in the condensate drain pan to provide an alarm whenever an overflow condition is sensed. The BAS system is to monitor this sensor and provide an alarm to the Owner. 8) Should one (1) unit fail the other unit is to provide cooling/heating until the room temperature is satisfied, then that unit is to switch to dehumidification duty. J. Three (3) heat pump units serving the R&D Grow Room 152: 1) Fans in all three (3) units are to run continuously. Project No

19 2) Two (2) units are to provide cooling/heating. 3) One (1) unit is to provide dehumidification. 4) Units are to, on a pre-set schedule, automatically switch functions from cooling/heating to dehumidification. Schedule is to initially be switched on a monthly basis, however, the Owner is to consulted during set-up of the BAS as to what schedule they require. 5) Each unit is to have a Variable Frequency Drive (VFD) to control the speed of the unit fans. a. When the unit is in the cooling/heat mode the VFD is to operate the unit fans to provide the scheduled cfm to provide maximum sensible cooling. b. When the unit is in dehumidifying mode the VFD is to operate at the standard 400 cfm per ton to provide dhimmification. 6) Each unit is to have a two-way, motorized, shut-off valve to be provided by the unit manufacturer that is to shut-off the water flow to the unit whenever the unit compressor is shut down. Manufacturer provided integral controls are to provide a 5-minute period between compressor run cycles. 7) Each unit is to have a manufacturer provided sensor in the condensate drain pan to provide an alarm whenever an overflow condition is sensed. The BAS system is to monitor this sensor and provide an alarm to the Owner. 8) Should one (1) of the units fail the other two (2) are to provide cooling/heating until the room temperature is satisfied then one (1) unit is to switch to dehumidification duty. C. Single water source heat pumps serving various rooms/areas of the building: 1) During occupied hours unit fan is to run continuously. During unoccupied hours the unit fan is to cycle with the unit compressor to maintain unoccupied thermostat setting. 2) Unit compressor is to provide cooling/heating to satisfy the room temperature occupied setting or unoccupied setting based on the room temperature sensor. 3) Each unit is to have a two-way, motorized, shut-off valve to be provided by the unit manufacturer that is to shut-off the water flow to the unit whenever the unit compressor is shut down. Manufacturer provided integral controls are to provide a 5-minute period between compressor run cycles. 4) Each unit is to have a manufacturer provided sensor in the condensate drain pan to provide an alarm whenever an overflow condition is sensed. The BAS system to monitor this sensor and provide an alarm to the Owner. 5) Heat Pumps #3 and #5 serving the two (2) Curing Rooms: in addition to heating and cooling these heat pumps are to provide dehumidification to satisfy the setting of the room humidistat. Coordinate humidistat settings with room humidifiers. 6) Heat Pump Unit #1 serving the exterior office zone including the Conference Room: install two (2) identical thermostats and an electronic timer switch. Timer switch to be mounted adjacent to the thermostat in the Conference Room. When switch is indexed to on the thermostat in the Conference Room is to be in control of the heat pump. When it times out, control is to revert to the thermostat in the Corner Office. Project No

20 4. DEDICATED OUTSIDE AIR UNIT Building Renovations A. The Outside Air Unit is to be factory furnished (by the unit manufacturer) with a control system that is BACNet compatible to allow the BAS to read and monitor all functions of the unit. Coordinate with the unit manufacturer. 5. MINI SPLIT DUCTLESS COOLING SYSTEM - IT ROOM 138 A. This system is to be provided with a wall mounted system controller by the unit manufacturer. The ATC Sub-Contractor is to install and wire this controller. B. Under the BAS installation furnish, install and wire a wall mounted temperature sensor to read room temperature and provide an alarm if a preset temperature is exceeded. 6. NATURAL GAS FIRED UNIT HEATERS a. Natural Gas Fired Unit Heaters are to be factory furnished wall mountable thermostat to be installed and wired by the ATC Sub-Contractor. Note: These units are to be on both normal and emergency power and are to only be used during power outages or if the room heat pump units are inoperable. The BAS shall monitor the on-off status of the heaters. b. The units shall be shut down on fire or smoke detection. 7. HUMIDIFIERS CURING ROOMS a. Humidifiers are to be factory furnished with integral controls. Interconnect the humidifiers to the BAS via manufacturer s provided interface. Wiring to BAS is to be by the ATC Sub- Contractor. Coordinate humidity setting with room humidistat to eliminate simultaneous humidifying and dehumidifying. 8. QUARANTINE ROOM ROOF FAN REF-1 a. The Quarantine Room Roof Fan is to be controlled by a wall switch with pilot light (switch by the Electrical Contractor) in the room. The BAS system is to monitor if fan is on or off. 9. GROW LIGHTS to be controlled by the BAS System in the following rooms: Propagation 120, Propagation 122, Vegetative 123, Flower 124, 125 and 126 and R&D Grow Room 152. PART 3 a. All grow lights in each room (BUT INDIVIDUAL ROOM CONTROL) are to be controlled by the BAS system either on or off. All lights, power wiring, breakers, relays, panels. Etc. are to be furnished and installed by the Electrical Contractor. The ATC Sub- Contractor is to provide a on or off signal to the relay panels to control all grow lights in each room. Also a Graphical Representative is to be part of the BAS system graphics package to represent lights are on or off in each room. 3.1 GENERAL INSTALLATION A. Install system and materials in accordance with manufacturer s instructions, and as detailed on the project drawing set. B. Line and low voltage electrical connections to control equipment shown specified or shown on the control diagrams shall be furnished and installed by the Control System Contractor in accordance with these specifications. C. Equipment furnished by the Mechanical Contractor that is normally wired before installation shall be furnished completely wired. Control wiring normally performed in the field will be furnished and installed by the Control System Contractor. Project No

SECTION SEQUENCE OF OPERATION FOR HVAC CONTROLS PART 1 GENERAL

SECTION SEQUENCE OF OPERATION FOR HVAC CONTROLS PART 1 GENERAL SECTION 15910 SEQUENCE OF OPERATION FOR HVAC CONTROLS PART 1 GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and other Division

More information

SECTION SEQUENCE OF OPERATIONS FOR HVAC CONTROLS

SECTION SEQUENCE OF OPERATIONS FOR HVAC CONTROLS SECTION 23 09 93 SEQUENCE OF OPERATIONS FOR HVAC CONTROLS PART 1 - GENERAL 1.1 SUMMARY A. This Section includes control sequences for HVAC systems, subsystems, and equipment. B. See Division 23 Section

More information

I/O ZONE 560/583 USERS GUIDE

I/O ZONE 560/583 USERS GUIDE I/O ZONE 560/583 USERS GUIDE 641-224 641-242 641-237 1 Table of Contents Hot Gas Re-Heat Valve On/Off:... 15 THE ZONE CONTROLLER...4 Modulating Re-Heat Valve:... 16 SPECIFICATIONS...5 CONTROLLER COMPONENTS...6

More information

CONTROLS UPGRADE. 106 Morgan Lane West Haven, Connecticut PROJECT MANUAL

CONTROLS UPGRADE. 106 Morgan Lane West Haven, Connecticut PROJECT MANUAL PROJECT MANUAL 419A Whitfield Street Guilford, CT 06437 Phone: (203) 453-8596 www.icdsllc.com Innovative Construction & Design Solutions, LLC 106 Morgan Lane West Haven, Connecticut CONTROLS UPGRADE Issued

More information

INSTRUMENTATION AND CONTROL DEVICES FOR HVAC

INSTRUMENTATION AND CONTROL DEVICES FOR HVAC PART 1 GENERAL 1.01 RELATED REQUIREMENTS SECTION 23 0913 INSTRUMENTATION AND CONTROL DEVICES FOR HVAC A. Section 26 2717 - Equipment Wiring: Electrical characteristics and wiring connections. 1.02 ADMINISTRATIVE

More information

Integrated Automation Instrumentation & Terminal Devices

Integrated Automation Instrumentation & Terminal Devices Sections Included In This Standard: 1.1 Building Systems Control 1.2 Building Aumotation Systems (BAS) 1.1 BUILDING SYSTEMS CONTROL A. HVAC CONTROLS: 1. General: Temperature control zones shall not combine

More information

SECTION SEQUENCE OF OPERATIONS FOR HVAC CONTROLS

SECTION SEQUENCE OF OPERATIONS FOR HVAC CONTROLS PART 1 - GENERAL SECTION 23 09 93 SEQUENCE OF OPERATIONS FOR HVAC CONTROLS 1.1 SUMMARY A. This Section includes control sequences for HVAC systems, subsystems, and other equipment. B. See Division 23 Section

More information

15900 HVAC INSTRUMENTATION AND CONTROLS

15900 HVAC INSTRUMENTATION AND CONTROLS 15900 HVAC INSTRUMENTATION AND CONTROLS PART 1 GENERAL - Andover Controls BAS system is the standard for the University, and may be specified as a proprietary item. 1.0 RELATED DOCUMENTS A. Drawings and

More information

WebStat Temperature Control System WITH WEB-BASED BUILDING MANAGEMENT

WebStat Temperature Control System WITH WEB-BASED BUILDING MANAGEMENT WebStat Temperature Control System WITH WEB-BASED BUILDING MANAGEMENT ENGINEERING GUIDE SPEC 1. GENERAL 1.1 SUMMARY A. Furnish all labor, materials, equipment, and service necessary for a complete and

More information

DENVER PUBLIC SCHOOLS DESIGN AND CONSTRUCTION STANDARDS This Standard is for guidance only. SECTION IBAS LIGHTING CONTROL

DENVER PUBLIC SCHOOLS DESIGN AND CONSTRUCTION STANDARDS This Standard is for guidance only. SECTION IBAS LIGHTING CONTROL PART 0 A/E INSTRUCTIONS 0.01 DESIGN REQUIREMENTS A. Minimum lighting control (base scope of work) shall include all corridors. The lighting in all the corridors shall be turned on (if not already on) if

More information

A. Base Bid: 1. Heating Contractor provide: a. Control sequences for HVAC systems, subsystems, and equipment.

A. Base Bid: 1. Heating Contractor provide: a. Control sequences for HVAC systems, subsystems, and equipment. SECTION 23 09 93 - SEQUENCE OF OPERATIONS FOR HVAC CONTROLS PART 1 - GENERAL 1 WORK INCLUDES A. Base Bid: Heating Contractor provide: Control sequences for HVAC systems, subsystems, and equipment. B. Alternate

More information

RE: Phase 2 Improvements DATE: July 1, 2016 New Administration Building Wernle Youth & Family Treatment Center 2000 Wernle Road Richmond, Indiana

RE: Phase 2 Improvements DATE: July 1, 2016 New Administration Building Wernle Youth & Family Treatment Center 2000 Wernle Road Richmond, Indiana ADDENDUM NO. 2 RE: Phase 2 Improvements DATE: July 1, 2016 New Administration Building Wernle Youth & Family Treatment Center 2000 Wernle Road Richmond, Indiana TO: All Bidders Gentlemen: This Addendum

More information

Virginia Tech Standards for Building Automation System

Virginia Tech Standards for Building Automation System March 1, 2016 Virginia Tech Standards for Building Automation System A. Existing Conditions: The Campus Building Automation System is Siemens Apogee and controls all significant campus facilties. Virginia

More information

Digital Precise Air Control - DPAC

Digital Precise Air Control - DPAC Digital Precise Air Control - DPAC Mode Enable Sensor Options The temperature of this sensor will determine if the unit is in heating, cooling or vent mode during Occupied operation. The following options

More information

PURCHASING SECTION th Street, Surrey, B.C. V3S 3C7 Tel: Fax: ADDENDUM NO.

PURCHASING SECTION th Street, Surrey, B.C. V3S 3C7 Tel: Fax: ADDENDUM NO. PURCHASING SECTION 6645 148 th Street, Surrey, B.C. V3S 3C7 Tel: 604-590-7274 Fax: 604-599-0956 E-mail: purchasing@surrey.ca ADDENDUM NO. 2 REQUEST FOR QUOTATIONS (RFQ) NO.: 1220-040-2014-001 TITLE: DISTRICT

More information

SECTION AUTOMATIC TRANSFER SWITCHES

SECTION AUTOMATIC TRANSFER SWITCHES SECTION 26 36 23 AUTOMATIC TRANSFER SWITCHES PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. General provisions of the Contract, including General and Supplementary Conditions and Division 01 Specification Sections,

More information

UltraLITE Model ELU Centralized Emergency Lighting Inverter 4.2 KW- 5 KW

UltraLITE Model ELU Centralized Emergency Lighting Inverter 4.2 KW- 5 KW 12/23/16 Rev 9 UltraLITE Model ELU General Specification 4.2 KW to 5 KW UltraLITE Model ELU Centralized Emergency Lighting Inverter 4.2 KW- 5 KW 1.0 General General Specification This specification describes

More information

UNIFIED FACILITIES GUIDE SPECIFICATIONS

UNIFIED FACILITIES GUIDE SPECIFICATIONS USACE / NAVFAC / AFCEC / NASA UFGS-23 09 93 (November 2015) ----------------------------- Preparing Activity: USACE Superseding UFGS-23 09 23 (May 2011) UNIFIED FACILITIES GUIDE SPECIFICATIONS References

More information

Integrated Automation

Integrated Automation Revision 04/27/2017 Purpose: The Architect and/or Engineer shall incorporate the Rice specific requirements indicated in this standard s section into their design. The Architect and/or Engineer shall further

More information

SECTION BUILDING AUTOMATION SYSTEM

SECTION BUILDING AUTOMATION SYSTEM SECTION 25 10 00 BUILDING AUTOMATION SYSTEM PART 1 GENERAL 1.01 SUMMARY A. Work hereunder includes a complete and operational, fully-tested, distributed logic, direct digital control system for control

More information

SECTION LIGHTING CONTROLS

SECTION LIGHTING CONTROLS PART 1 - GENERAL 1.1 DESCRIPTION SECTION 26 09 23 LIGHTING CONTROLS SPEC WRITER NOTE: 1. Delete between //----// if not applicable to project. Also, delete any other item or paragraph not applicable to

More information

SEQUENCE OF OPERATIONS

SEQUENCE OF OPERATIONS SEQUENCE OF OPERATIONS DDC CONTROLLER: Controller with integral LCD readout for changing set points and monitoring unit operation. Provided with required sensors and programming. Factory programmed, mounted,

More information

ADDENDUM NO.1. March 4, 2013 HEAT PUMP REPLACEMENT FOR: GATE CITY ELEMENTARY SCHOOL

ADDENDUM NO.1. March 4, 2013 HEAT PUMP REPLACEMENT FOR: GATE CITY ELEMENTARY SCHOOL ADDENDUM NO.1 March 4, 2013 HEAT PUMP REPLACEMENT FOR: GATE CITY ELEMENTARY SCHOOL The data included hereinafter is issued by the Engineer (Engineered Systems Associates, 1355 East Center, Pocatello, ID

More information

SCC Inc. Master Panel. Specifications. Document No. TS 2010 February 11, Product Description. Sample Specification

SCC Inc. Master Panel. Specifications. Document No. TS 2010 February 11, Product Description. Sample Specification February 11, 2019 Master Panel Product Description The Master Panel shall provide lead/lag control and time based, automatic rotation of up to eight (8) boilers, when used in conjunction with LMV3 or LMV5

More information

Building Automation System

Building Automation System University of New Hampshire University of New Hampshire Scholars' Repository Division 25 Integrated Automation Chapter 5 Technical Construction and Renovation Standards 8-1-2014 250000 - Building Automation

More information

CAREL heatersteam Electric Element Steam Humidifiers

CAREL heatersteam Electric Element Steam Humidifiers Suggested Engineering Specifications Section 23 84 13 CAREL heatersteam Electric Element Steam Humidifiers 1. GENERAL SCOPE 1. Furnish and install as indicated on the drawings and plans, in-duct [space]

More information

Guide Spec Summary. Option List. Date: 05/21/2001. EarthWise VAV Terminal Units Full Spec. Prepared by: Phone Number: Prepared for:

Guide Spec Summary. Option List. Date: 05/21/2001. EarthWise VAV Terminal Units Full Spec. Prepared by: Phone Number: Prepared for: Date: 05/21/2001 Time: 02:57:44 PM Job Name: EarthWise VAV Terminal Units Full Spec Location: AnyTown, Earth Prepared by: Phone Number: Prepared for: Guide Spec Summary Option List SINGLE & DUAL DUCT UNIT

More information

November 11, City of Sparks 215 S. 21 st St. Sparks, NV

November 11, City of Sparks 215 S. 21 st St. Sparks, NV November 11, 2014 City of Sparks 215 S. 21 st St. Sparks, NV 89432-0857 Attn: Brian Cason Re: Sparks City Hall HVAC Upgrade Project-Alerton Direct Digital HVAC Control System to Match Existing City of

More information

ModSync Sequencing System Installation & Operation Manual. For use with Fulton Steam Boilers.

ModSync Sequencing System Installation & Operation Manual. For use with Fulton Steam Boilers. ModSync Sequencing System Installation & Operation Manual For use with Fulton Steam Boilers. Revision 3.0 8/21/2008 - 2 - Table of Contents Introduction Page 4 Features Page 4 Sequence of Operation Page

More information

DIRECT-DIGITAL CONTROL SYSTEM FOR HVAC

DIRECT-DIGITAL CONTROL SYSTEM FOR HVAC PART 1 GENERAL SECTION 23 0923 DIRECT-DIGITAL CONTROL SYSTEM FOR HVAC 1.01 RELATED WORK UNDER OTHER SECTIONS: A. In addition to the general building construction, work directly related to the automatic

More information

Power Flame Incorporated

Power Flame Incorporated Power Flame Incorporated SUGGESTED SPECIFICATION FOR MODEL NVC ULTRA LOW NOx GAS BURNERS SUB 9 PPM NOx THE POWER TO MANAGE ENERGY 2001 South 21st Street, Parsons, Kansas 67357 Telephone: 620-421-0480,

More information

SECTION DIGITAL, ADDRESSABLE FIRE-ALARM SYSTEM

SECTION DIGITAL, ADDRESSABLE FIRE-ALARM SYSTEM SECTION 283111 - DIGITAL, ADDRESSABLE FIRE-ALARM SYSTEM PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division

More information

Feature Summary. I. System

Feature Summary. I. System I. System A. Supports up to 60 VAV HVAC Units 1. Each HVAC Unit Can Support up to 59 VAV Boxes 2. Constant Volume Units Can Be Integrated With VAV Units 3. System Can Support Over 3000 Controllers B. Fill-in

More information

KINGS COUNTY JAIL EXPANSION PHASE III COUNTY OF KINGS SECTION

KINGS COUNTY JAIL EXPANSION PHASE III COUNTY OF KINGS SECTION SECTION 237433, PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 01 Specification Sections, apply to

More information

1.1 DESCRIPTION A. The purpose of this section is to specify Division 23 responsibilities in the commissioning (Cx) process.

1.1 DESCRIPTION A. The purpose of this section is to specify Division 23 responsibilities in the commissioning (Cx) process. SECTION 239950 MECHANICAL COMMISSIONING SYSTEMS PART 1 - GENERAL 1.1 DESCRIPTION A. The purpose of this section is to specify Division 23 responsibilities in the commissioning (Cx) process. B. Commissioning

More information

0 C to 50 C ( 32 F to 122 F ) 0% to 95% R.H. non-condensing. 30 to 95% R.H. Dry contact across terminal BI1, BI2 & UI3 to Scom

0 C to 50 C ( 32 F to 122 F ) 0% to 95% R.H. non-condensing. 30 to 95% R.H. Dry contact across terminal BI1, BI2 & UI3 to Scom Viconics VT7350 Series PIR Ready Fan-coil Controllers General The VT7350 series are PIR Ready low-voltage microprocessor-based fan-coil controllers. Models are available controlling single speed and multi-speed

More information

Job Name Control Systems Description Date

Job Name Control Systems Description Date Job Name Control Systems Description Date Project Overview The project is a describe the building and its major HVAC systems (e.g. three-story office building, served by a rooftop unit VAV system ). In

More information

SECTION AUTOMATIC TRANSFER SWITCHES

SECTION AUTOMATIC TRANSFER SWITCHES PART 1 - GENERAL 1.1 DESCRIPTION SECTION 26 36 23 This section specifies the furnishing, complete installation, and connection of automatic transfer switches. 1.2 RELATED WORK A. Section 14 21 00, ELECTRIC

More information

LMV52 Control. Specifications. Document No. LV February 3, Product Description. Sample Specification

LMV52 Control. Specifications. Document No. LV February 3, Product Description. Sample Specification LMV52 Control Product Description February 3, 2017 The LMV52 is a microprocessor-based burner management system with matching system components for the control and supervision of forced draft burners.

More information

Predator Controller Hardware Family

Predator Controller Hardware Family Predator Controller Hardware Family Figure1: Predator Controller Only. Figure 2: Predator VAV Actuator. The LONMARK certified configurable Predator Controller provides direct digital control of a variety

More information

opti-visor ultra-efficient chiller plant automation Typical specification

opti-visor ultra-efficient chiller plant automation Typical specification opti-visor ultra-efficient chiller plant automation Typical File No: 90.893 Date: february 9, 2015 Supersedes: 90.893 Date: april 20, 2012 contents 1.0 Chilled water plant 4 1.1 General system requirements

More information

FUNCTIONAL DESIGN SPECIFICATION

FUNCTIONAL DESIGN SPECIFICATION Issue Date: Issued To: Revision: FUNCTIONAL DESIGN SPECIFICATION Specification Number: SP-XXXX Company Name Signature Date Issued By: Manutec Ltd. Approved By: Approved By: Approved By: Approved By: Authorised

More information

C. The system shall be capable of turning luminaires on/off (where supported by the luminaire) as well as full range dimming.

C. The system shall be capable of turning luminaires on/off (where supported by the luminaire) as well as full range dimming. SECTION 260943 SPECIFICATIONS - Wireless Network Lighting Controls. PART 1 - GENERAL 1.1 RELATED DOCUMENTS 1.2 SUMMARY AND KEY SYSTEM DIFFERENTIATORS A. The lighting control system specified herein shall

More information

Application Manual LT-6617 Rev. 1 July 2017

Application Manual LT-6617 Rev. 1 July 2017 Application Manual LT-6617 Rev. 1 July 2017 Table of Contents 1.0 Frequently Asked Questions 4 2.0 OpenBAS Wiring Guidelines 6 3.0 Wiring 9 4.0 Glossary 11 3 1.0 Frequently Asked Questions 1.1 What is

More information

Suggested Specification: Benchmark 1.5 Low NOx Gas-Fired Hydronic Boiler(s)

Suggested Specification: Benchmark 1.5 Low NOx Gas-Fired Hydronic Boiler(s) Furnish and install as shown on AERCO International plans and operation and maintenance manuals, with all applicable codes and authorities having local, state and federal jurisdiction, Benchmark Series

More information

Honeywell SLATE ICM Platform

Honeywell SLATE ICM Platform Honeywell SLATE ICM Platform SUBMITTAL SPECIFICATION Note to specifiers: To specify Honeywell SLATE Integrated Combustion Management System with specified packaged boiler manufactures, Copy and Paste both

More information

Revitalize Building Mechanical Systems (4619)

Revitalize Building Mechanical Systems (4619) SECTION 235216 FIRE-TUBE CONDENSING BOILERS PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 01 Specification

More information

TAP v2.10 Version Date: 6/12/13. Document Microprocessor Controller for Tempered Air Products

TAP v2.10 Version Date: 6/12/13. Document Microprocessor Controller for Tempered Air Products Document 475595 Microprocessor Controller for Tempered Air Products Reference Guide for the Microprocessor Controller Please read and save these instructions. Read carefully before attempting to operate

More information

Two-Channel Gas Controller

Two-Channel Gas Controller Two-Channel Gas Controller Specifications subject to change without notice. USA 09 Page of DESCRIPTION Highly configurable, UL 0 performance-tested and -certified, and wall-mounted gas monitor; continuously

More information

SECTION PACKAGED HEAT TRANSFER SYSTEM

SECTION PACKAGED HEAT TRANSFER SYSTEM PACKAGED HEAT TRANSFER SYSTEM Page 1 of 6 SECTION PACKAGED HEAT TRANSFER SYSTEM 1 GENERAL 1.1 SUMMARY A. Packaged steam-to-water heat transfer system 1.2 REFERENCES A. ASHRAE American Society of Heating,

More information

ONYX FirstVision Specification Interactive Firefighters Display

ONYX FirstVision Specification Interactive Firefighters Display ONYX FirstVision Specification Interactive Firefighters Display NOTIFIER is a registered trademark, and ONYX FirstVision, NOTI FIRE NET, and VeriFire are trademarks of Honeywell International Inc. Microsoft

More information

Section PERIMETER SECURITY SYSTEMS

Section PERIMETER SECURITY SYSTEMS Section 28 16 43 PERIMETER SECURITY SYSTEMS PART 1 GENERAL 1.1 SUMMARY A. Provide and install a perimeter security system as herein specified for the purpose of detecting entry into a designated security

More information

Updated: September 12, 2018 DIVISION INTEGRATED AUTOMATION. INTEGRATED AUTOMATION Page 1 of INTEGRATED AUTOMATION

Updated: September 12, 2018 DIVISION INTEGRATED AUTOMATION. INTEGRATED AUTOMATION Page 1 of INTEGRATED AUTOMATION Page 1 of 7 25 00 00 25 10 00 NETWORK EQUIPMENT Standby Power 1. Consider whether the controls system should be on standby/emergency power, or UPS when central applications are controlled or the equipment

More information

Document # R01

Document # R01 Viconics VT7600 Series PIR-Ready Rooftop Unit Controllers Part 1 General The VT7600 series is designed for single-stage and multi-stage control of heating/cooling equipment such as rooftop and self-contained

More information

Verasys System Operation Overview Technical Bulletin

Verasys System Operation Overview Technical Bulletin Contents subject to change. Verasys System Operation Overview Technical Bulletin Code No. LIT-12012370 Issued January 2016 Refer to the QuickLIT Web site for the most up-to-date version of this document.

More information

SECTION ROTARY-SCREW WATER CHILLERS

SECTION ROTARY-SCREW WATER CHILLERS PART 1 GENERAL 1.01 SECTION INCLUDES A. Factory-assembled packaged chiller. B. Charge of refrigerant and oil. C. Controls and control connections. D. Chilled water connections. E. Electrical power connections.

More information

SECTION SEQUENCE OF OPERATIONS FOR BUILDING CONTROLS

SECTION SEQUENCE OF OPERATIONS FOR BUILDING CONTROLS PART 1 GENERAL 1.01 SECTION INCLUDES SECTION 23 0993 SEQUENCE OF OPERATIONS FOR BUILDING CONTROLS A. This section defines the manner and method by which controls function. Requirements for each type of

More information

VCM-X Controller Technical Guide

VCM-X Controller Technical Guide 2 2 www.orioncontrols.com VCM-X Controller Technical Guide VCM-X Controller Code: SS1026 & Y200920 Version 2.0 and up; VCM-X Modular Controller: Tulsa - SS1030; Coil - SS1034 VCM-X WSHP Controller: Tulsa

More information

Cultivator & Hybrid Cultivator

Cultivator & Hybrid Cultivator Cultivator & Hybrid Cultivator Precision Temperature & Humidity Packaged Unit INTRODUCTION The Cultivator Series package unit is the industry s MOST ENERGY EFFICIENT and HIGHEST capacity dehumidifier on

More information

Soft Start Series MP700 Solid State, Reduced Voltage

Soft Start Series MP700 Solid State, Reduced Voltage Metron Fire Pump Controls and Accessories Soft Start Series MP700 Solid State, Reduced Voltage Metron Fire Pump Controllers conform to the latest requirements of National Fire Protection Association s

More information

Model D12-IR. Digital Gas Transmitter...

Model D12-IR. Digital Gas Transmitter... Model D12-IR Digital Gas Transmitter... ATI s Series D12 gas transmitter line now includes a versatile Infrared system that can be configured for LEL or select toxic gases. The D12-IR utilizes a compact

More information

CommStat 4. Controller for Redundant Telecom HVAC Systems PRODUCT DATA SHEET. Features and Benefits

CommStat 4. Controller for Redundant Telecom HVAC Systems PRODUCT DATA SHEET. Features and Benefits CommStat 4 PRODUCT DATA SHEET Controller for Redundant Telecom HVAC Systems General Description The CommStat 4 is an HVAC controller designed specifically for controlling two redundant air conditioners,

More information

SECTION AUTOMATIC TRANSFER SWITCHES PART 1 - GENERAL

SECTION AUTOMATIC TRANSFER SWITCHES PART 1 - GENERAL SECTION 16400 AUTOMATIC TRANSFER SWITCHES 1.01 RELATED DOCUMENTS PART 1 - GENERAL A. Drawings and general provisions of Contract, including General Conditions and Division 1 Specification sections, apply

More information

The ultimate fresh air solution.

The ultimate fresh air solution. Fresh Access The ultimate fresh air solution. Introducing Fresh Access TM. Expertly designed, our innovative energy recovery ventilator (ERV) unit, split dedicated outside air system (DOAS), and packaged

More information

City of Duluth Festival Center 04/25

City of Duluth Festival Center 04/25 SECTION 230593 - TESTING, ADJUSTING, AND BALANCING FOR HVAC PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and

More information

SECTION LOW VOLTAGE LIGHTING CONTROLS

SECTION LOW VOLTAGE LIGHTING CONTROLS SECTION 26 09 26 LOW VOLTAGE LIGHTING CONTROLS PART 1 - GENERAL 1.01 RELATED DOCUMENTS: A. The Conditions of the Contract and applicable requirements of Division 1, "General Requirements", and Section

More information

Trinity Lx200 High Efficiency Gas Condensing Boiler & Water Heater

Trinity Lx200 High Efficiency Gas Condensing Boiler & Water Heater Part I - General Part II - Product Part III - Installation Project Name: Location: Engineer: Contractor: I. GENERAL Rep: Date: A. Supply and install modulating and condensing boiler(s)/water heater(s)

More information

(Formerly SECTION BACNET BUILDING AUTOMATION SYSTEM DIRECT DIGITAL CONTROLS GUIDE SPECIFICATION) CONTENTS

(Formerly SECTION BACNET BUILDING AUTOMATION SYSTEM DIRECT DIGITAL CONTROLS GUIDE SPECIFICATION) CONTENTS 25 50 00 INTEGRATED AUTOMATION FACILITY CONTROLS (BACNET) (Formerly SECTION 23 06 06 BACNET BUILDING AUTOMATION SYSTEM DIRECT DIGITAL CONTROLS GUIDE SPECIFICATION) CONTENTS SECTION HEADERS ARE HOT-LINKABLE.

More information

CommStat 6. Controller for Redundant HVAC Systems PRODUCT DATA SHEET

CommStat 6. Controller for Redundant HVAC Systems PRODUCT DATA SHEET CommStat 6 Controller for Redundant HVAC Systems PRODUCT DATA SHEET General Description The CommStat 6 HVAC controller is designed for controlling up to six redundant air conditioners in an E-House or

More information

FIRE DETECTION SYSTEM SPECIFICATION FOR MODEL XR200

FIRE DETECTION SYSTEM SPECIFICATION FOR MODEL XR200 FIRE DETECTION SYSTEM SPECIFICATION FOR MODEL XR200 1.0 General 1.1 Manufacturer Manufacturer of the Fire Alarm Control Panel (FACP) equipment shall be: Digital Monitoring Products, Incorporated 2500 N.

More information

Instrumentation and Control for HVAC

Instrumentation and Control for HVAC 23 09 00 Instrumentation and Control for HVAC 1. All controls to be corporate Trane or Honeywell, no substitutes. 2. Factory Mounted controls to be Trane only, otherwise provide terminal strips for TC

More information

C. ASME Compliance: Fabricate and label water chiller heat exchangers to comply with ASME Boiler and Pressure Vessel Code: Section VIII, Division 1.

C. ASME Compliance: Fabricate and label water chiller heat exchangers to comply with ASME Boiler and Pressure Vessel Code: Section VIII, Division 1. SECTION 236426 - ROTARY-SCREW WATER CHILLERS PART 1 - GENERAL 1.1 SUMMARY A. This Section includes packaged, water cooled or air cooled as scheduled, electric-motor-driven, rotary-screw water chillers

More information

Model LTN-3R Outdoor Rated Uninterruptible Power System Single Phase

Model LTN-3R Outdoor Rated Uninterruptible Power System Single Phase Model LTN-3R Outdoor Rated Uninterruptible Power System Single Phase General Specification 550 VA/Watts 1300 VA/Watts 1.0 GENERAL This specification defines the electrical and mechanical characteristics

More information

B. Unit construction shall comply with ASHRAE 15 Safety Code, NEC, and ASME applicable codes (U.S.A. codes).

B. Unit construction shall comply with ASHRAE 15 Safety Code, NEC, and ASME applicable codes (U.S.A. codes). Guide Specifications PART 1 GENERAL 1.01 SYSTEM DESCRIPTION Microprocessor controlled, air-cooled liquid chiller utilizing scroll compressors, low sound fans, hydronic pump system and optional fluid storage

More information

LMV51 Control. Specifications. Document No. LV February 7, Product Description. Sample Specification

LMV51 Control. Specifications. Document No. LV February 7, Product Description. Sample Specification SCC Inc. LMV51 Control Product Description February 7, 2017 The LMV51 is a microprocessor-based burner management system with matching system components for the control and supervision of forced draft

More information

DIVISION FINNED WATER-TUBE BOILERS

DIVISION FINNED WATER-TUBE BOILERS MVB, TYPE H - MODELS 504A-2004A SUGGESTED SPECIFICATIONS Catalog No.: 2000.933C Effective: 06-25-15 Replaces: 12-21-09 DIVISION 23 52 33.13 FINNED WATER-TUBE BOILERS PART 1 - GENERAL 1.1 SUMMARY A. Section

More information

Project Name: Location: Engineer: Contractor: I. GENERAL

Project Name: Location: Engineer: Contractor: I. GENERAL Part I - General Part II - Product Part III - Installation Project Name: Location: Engineer: Contractor: I. GENERAL I. PRODUCT Rep: Date: A. Supply and install modulating and condensing boiler(s) as specified

More information

Guide Specification - MasterFormat 2017 Style SECTION FLOW INSTRUMENTS PART 2 PRODUCTS 2.1 SECTION INCLUDES 2.2 ACCEPTABLE MANUFACTURERS

Guide Specification - MasterFormat 2017 Style SECTION FLOW INSTRUMENTS PART 2 PRODUCTS 2.1 SECTION INCLUDES 2.2 ACCEPTABLE MANUFACTURERS SECTION 230923.14 FLOW INSTRUMENTS Data contained in this guide specification may be placed in either of the following sections, depending on the specifics of the system design, or incorporated within

More information

DX-9100 Applications from Engineering Services

DX-9100 Applications from Engineering Services System 9100 Technical Manual 636.4 Application Examples Section Technical Bulletin Issue Date 0896 DX-9100 Applications from Engineering Services Introduction Page 3 Overview 3 Air Handling Unit Applications

More information

Corrigo E. Second generation which contains all applications and languages

Corrigo E. Second generation which contains all applications and languages revision 05 2009 Corrigo E Second generation which contains all applications and languages The controllers in the Corrigo E series are intended for applications within heating, boiler and ventilation control

More information

BMS Specification. Lonix Ltd.

BMS Specification. Lonix Ltd. BMS Specification 1 (18) BMS Specification Lonix Ltd www.lonix.com BMS Specification 2 (18) INDEX 1 System Architecture...3 1.1 System Integration...3 1.2 Layered System Architecture...3 1.2.1 Service

More information

Flexible & Innovative. Cooling Solutions

Flexible & Innovative. Cooling Solutions Flexible & Innovative Cooling Solutions Flexible & Innovative Compu-Aire Inc. offers a variety of high performance precision cooling systems that can adapt to your application needs. With today s rapidly

More information

Introduction. What is the W2W Open controller?

Introduction. What is the W2W Open controller? W2W Open CARRIER CORPORATION 2017 A member of the United Technologies Corporation family Stock symbol UTX Catalog No. 11-808-538-01 2/8/2017 Verify that you have the most current version of this document

More information

Carbon Monoxide Transmitter

Carbon Monoxide Transmitter Introduction The CO Transmitter uses an electrochemical sensor to monitor the carbon monoxide level and outputs a field-selectable 4-20 ma or voltage signal. The voltage signal may also be set to 0-5 or

More information

SAMPLE SPECIFICATION FOR RIELLO ARRAY MODULATING BOILER

SAMPLE SPECIFICATION FOR RIELLO ARRAY MODULATING BOILER SAMPLE SPECIFICATION FOR RIELLO ARRAY MODULATING BOILER PART 1 GENERAL 1.01 RELATED DOCUMENTS A. ANSI Z21.13 American National Standard for Gas-Fired Low Pressure Steam and Hot Water Boilers B. ASME Section

More information

CONTENTS AUTOMATIC TRANSFER SWITCHES

CONTENTS AUTOMATIC TRANSFER SWITCHES CONTENTS AUTOMATIC TRANSFER SWITCHES PART 1 GENERAL 1.1 Related Documents 1.2 Summary 1.3 References 1.4 Quality Assurance 1.5 Submittals 1.6 Delivery, Storage and Handling 1.7 Instructions And Training

More information

CARD ACCESS CONTROL SYSTEM

CARD ACCESS CONTROL SYSTEM SECTION 13851 CARD ACCESS CONTROL SYSTEM PART 1 GENERAL 1.01 SUMMARY A. Section Includes: A complete, operable, tested, integrated proximity access control system, to operate on a proximity principle where

More information

March 9, 2009 Project TRINITY COUNTY COURTHOUSE RESTORATION Groveton, Texas ADDENDUM NO. 2

March 9, 2009 Project TRINITY COUNTY COURTHOUSE RESTORATION Groveton, Texas ADDENDUM NO. 2 March 9, 2009 Project 874.001 TRINITY COUNTY COURTHOUSE RESTORATION Groveton, Texas A. PURPOSE AND INTENT ADDENDUM NO. 2 This addendum is issued for the purpose of modifying the plans and specifications

More information

ZonexCommander. ZonexCommander(Plus) Installation and Applications Manual. Network All Your HVAC Equipment

ZonexCommander. ZonexCommander(Plus) Installation and Applications Manual. Network All Your HVAC Equipment ZonexCommander ZonexCommander(Plus) Network All Your HVAC Equipment Centralized DDC Communications for Stand-Alone HVAC and Zoned Systems Installation and Applications Manual Part #ZCMAN Rev. Oct 2014

More information

Specification for On-Line UPS Battery Monitoring and Data Management System

Specification for On-Line UPS Battery Monitoring and Data Management System 1 Scope This specification defines the minimum requirements for a predictive on-line Battery Monitoring BMDMS with test, analysis, and remote monitoring control capabilities. Unless noted otherwise, the

More information

WaterFurnace FX10 Application Guide Reversible Chiller

WaterFurnace FX10 Application Guide Reversible Chiller 2011 WaterFurnace FX10 Application Guide Reversible Chiller Introduction This manual provides information about the FX10 Water Source Heat Pump (WSHP) controller as it relates to dual compressor water

More information

SAMPLE SPECIFICATIONS CONTINUOUS MONITORING SYSTEM (Insitu)

SAMPLE SPECIFICATIONS CONTINUOUS MONITORING SYSTEM (Insitu) PART 1 - GENERAL A. RELATED DOCUMENTS SAMPLE SPECIFICATIONS CONTINUOUS MONITORING SYSTEM (Insitu) Federal, State, and local requirements as applicable. Attached Permit Attached drawings B. SUMMARY 1. Provide

More information

Trinity Lx400 High Efficiency Gas Condensing Boiler & Water Heater

Trinity Lx400 High Efficiency Gas Condensing Boiler & Water Heater Part I - General Part II - Product Part III - Installation Project Name: Location: Engineer: Contractor: I. GENERAL Rep: Date: A. Supply and install modulating and condensing boiler(s)/water heater(s)

More information

Hydronic & HVAC Control Systems

Hydronic & HVAC Control Systems tekmar 218 Full Line Catalog Hydronic & HVAC Control Systems HVAC Multi-Staging Alternative Energy Zoning Snow Melting Setpoint tekmarcontrols.com tekmarcontrols.com Better Design, Better Control, Better

More information

SECTION AUTOMATIC TRANSFER SWITCHES

SECTION AUTOMATIC TRANSFER SWITCHES PART 1 - GENERAL 1.1 DESCRIPTION SECTION 26 36 23 SPEC WRITER NOTE: Use this section only for NCA projects. Delete between //--// if not applicable to project. Also, delete any other item or paragraph

More information

SECTION SAMPLE SPECIFICATION FOR BOILER CONTROLLER CONVERSION KIT

SECTION SAMPLE SPECIFICATION FOR BOILER CONTROLLER CONVERSION KIT SECTION 23 09 33 SAMPLE SPECIFICATION FOR BOILER CONTROLLER CONVERSION KIT HARSCO INDUSTRIAL, PATTERSON-KELLEY NURO CONTROL CONVERSION KIT Part 1 - GENERAL 1.01 RELATED DOCUMENTS A. ANSI Z21.13 / CSA 4.9

More information

CONsOlIDATOR 4 & 8. MulTI- C h ANNEl CONTROllERs. ConsoliDator 4 Model PD940 ConsoliDator 4 Features. ConsoliDator 8 Features.

CONsOlIDATOR 4 & 8. MulTI- C h ANNEl CONTROllERs. ConsoliDator 4 Model PD940 ConsoliDator 4 Features. ConsoliDator 8 Features. CONsOlIDATOR 4 & 8 MulTI- C h ANNEl CONTROllERs ConsoliDator 4 Model PD940 ConsoliDator 4 Features Four 4-20 Four 4-20 Outputs ConsoliDator 8 Features Eight 4-20 Two 4-20 Outputs Common Features Four Pulse

More information

Control Panel. 1.0 GENERAL SCOPE OF WORK Introduction... 2

Control Panel. 1.0 GENERAL SCOPE OF WORK Introduction... 2 Architectural & Engineering Specifications Control Panel 1.0 GENERAL... 2 1.1 SCOPE OF WORK... 2 1.1.1 Introduction... 2 1.2 GENERAL CONDITIONS... 2 1.2.1 After-Sales Support... 2 1.2.2 Quality assurance...

More information

Across-the-Line SERIES MP300 Combined Manual and Automatic

Across-the-Line SERIES MP300 Combined Manual and Automatic Across-the-Line SERIES MP300 Combined Manual and Automatic Metron Fire Pump Controllers conform to the latest requirements of National Fire Protection Association s Standard for Centrifugal Fire Pumps

More information

Master devices. Type X-AIR-ZMAS. Zone master module for up to 25 zone modules, with integral webserver and interfaces to higher-level systems

Master devices. Type X-AIR-ZMAS. Zone master module for up to 25 zone modules, with integral webserver and interfaces to higher-level systems X X testregistrierung Type Web server, also for mobile devices Zone modules Zone master module for up to 25 zone modules, with integral webserver and interfaces to higher-level systems X-AIRCONTROL zone

More information