Engineering and Design of Fire Alarm Systems

Size: px
Start display at page:

Download "Engineering and Design of Fire Alarm Systems"

Transcription

1 Engineering and Design of Fire Alarm Systems Presented by: John P. Stoppi Jr., PE, FPE, CBO, CFI Stoppi Engineering

2 About the Presenter: John P. Stoppi Jr., PE, FPE, CBO, CFI Dual Registered as a Fire Protection Engineer and Mechanical Engineer in NJ, NY, PA & NC. Certified Code Enforcement Official Over 10 years of progressive experience in FP engineering, code consulting, and code enforcement in the public, private, military, and int l sectors Page 2

3 Course Outline 1. Public vs. Private Clients 2. Client Needs 3. Proposal Phase 4. Building and Occupancy Assessment 5. SD, DD, CD Phases 6. Bidding 7. Construction Administration 8. Inspections, Punch Lists, Final Inspections 9. Commissioning 10. Case Study Page 3

4 Public vs. Private Clients Public Client Associated with a governmental body at the municipal, state, or federal level. (i.e. normally, gov t agencies). Funding for engineering and construction from public funds (tax revenue or allocation from federal gov t). Project benefits or serves the public. Design-bid-build projects on the rise. Projects subject to compliance requirements (quals based selection, lowest bid awards, DBE participation, etc.) Page 4

5 Public vs. Private Clients Private Client: Not associated with a governmental body. Include corporations, joint ventures, other A/E/C firms, and even individuals. Funding comes from private sources. Project benefits a specific, private entity. Delivery method varies as design-bid-build, design-build, and CM-at-Risk or some hybrid. Arbitrary secondary goals (e.g., LEED Certification) Page 5

6 Public vs. Private Clients Billing/Contract Methods Public Clients normally require Cost Plus Fixed Fee Consultant paid for direct time, overhead, plus a fixed fee. Compensated for time worked, not to exceed a certain, contractual amount. Overruns are normally at consultant s expense, unless scope is exceeded. Timesheet back-up (evidence of time worked) is normally required, along with proof of actual hourly rates paid. Page 6

7 Public vs. Private Clients Private Clients Billing/Contract Methods Billing methods vary with job, owner, service. Time and Material Generalized billing rates, based on position level/title. Simpler than cost plus. Allows variety of personnel at differing position levels to work on a project without specifying details upfront. Good for multiple departments working on project. Lump Sum Simplest, most preferable, one figure for entire job. Simplest accounting. Chance for greater profit. Page 7

8 Public vs. Private Clients Public Clients, Larger Jobs Phased, defined submittals at various traditional milestones. Monthly billing to match submittals; accounting requirements specified. Private Clients Consultant often specifies submittal schedule and milestones. Submittals Consultant often chooses billing frequency and accounting requirements. Page 8

9 Public vs. Private Clients Summary Client Feature Public Client Private Client Client Example Target End User of Project Typical Delivery/Billing Method Secondary Goals Municipal, State, or Federal Governmental Agency Public (e.g., prison, school, museum, etc.) Design-bid-build (to obtain lowest construction price), Cost Plus Mandatory, by Statute, normally dictates how funding is distributed/spent, how jobs are posted and bid Architecture Firm, Corporate Owner Specific Group (e.g., employees of a company in an office building) Varies depending on project needs Arbitrary, by owner, depending on specific project (e.g., environmental) Page 9

10 Client Needs Code-Based Client is legally required to install or upgrade a fire alarm system as mandated by code or new/renovation projects. Client-Driven Client wants a fire alarm system, or a modification to an existing one, to satisfy their own needs: Reduce costs Provide fire/life safety above and beyond code Insurance requirement Page 10

11 Client Needs: Code-Based (New) IBC, Section Scoping for new fire alarm installations Based on occupancy, occupant load, sprinkler coverage, number of stories, relationship to lowest level of exit discharge, and special occupancy types. Despite its name, NFPA 72 is not a scoping document! Page 11

12 Client Needs: Code Based (Existing) Occupancy change, removal/change of some fire/life safety system, renovation/alteration will require some type of fire alarm system. Example: An existing building without a fire alarm system has an elevator installed. Because of code changes, a fire alarm system dedicated to elevator recall control and supervisory service is required. Page 12

13 Client Needs (Client driven) Save money on: Maintenance Not dealing with nuisance alarms Want MNS system as part of campus type plan Insurance offers lower premium for enhanced FA system Page 13

14 Proposal Phase Formality and requirements of Proposal Phase are heavily dependent on client type. Public clients are more formal and have more requirements. The job may be solely fire alarm or fire alarm may be part of a larger engineering project. New/existing facility/building. Page 14

15 Proposal Phase Public Clients 1. Request for Information (RFI)/Request for Qualifications (RFQ) Proposal containing information about the designer/team, capabilities, staff/firm qualifications. Phase is normally required if the job is over a certain size. The public clients are required, by statute, to solicit bids from the general public. Page 15

16 Proposal Phase Public Clients 2. Shortlisted A selection of finalist teams are asked to submit a detailed proposal. Smaller jobs may have their starting point here. Firms with existing on-call agreements may be contacted. Detailed technical proposal contain a narrative on how the project is going to be designed. Detailed cost proposal outlines how much the project is going to cost to design by project phase and total cost. Key roles and responsibilities of staff are depicted. Page 16

17 Proposal Phase Public Clients, Key Staff For fire alarm design, include such resumes as: Fire Protection Engineer Lead Fire Alarm System Designer (NICET IV) Fire Alarm System Designer (NICET I-III) Job responsibilities outlined for the project. Page 17

18 Proposal Phase Public Clients 3. Site Walkthrough Can occur during RFI/RFQ stage or at Shortlist stage. Purpose is to become familiar enough with site to propose on job. Scope depends on whether it s a new or existing project. New project may just have a bare land survey or just preliminary design docs. Page 18

19 Proposal Phase Public Clients 4. Interview/Presentations Finalists will be invited to interviews, where they will present their project approach. Fire alarm design is either a standalone presentation or a section of a larger one. Page 19

20 Proposal Phase Public Clients 5. Award Notification Client selects winning firm. Contract is negotiated. Pricing and other details may change. Small chance the next ranking firm will be selected. Contracts finalized and signed. 6. Notice to Proceed (NTP) Job/work begins (finally!). Page 20

21 Proposal Phase Public Clients Entire phase can be lengthy with public clients. Can last 6 months between RFI to NTP. RFP will normally specify how firms are selected: Cost-based (price only) Qualifications-based (technical approach/firm capabilities) Value-based (weighted combination) Page 21

22 Proposal Phase Private Clients Initial contact different than public process. Specific, urgent need may arise. May only have contact with one firm. Less formal. Requirements/procedures vary. Small job, smaller client may require a simple letter proposal. Larger jobs, larger clients - may mirror public proposal phase procedures. Page 22

23 Proposal Phase Private Clients Fire Alarm Contractor may be engaged for certain private work by competitive bidding or through existing relationship. FA Contractor may later engage an engineering firm for certain services (sealing, code consulting, drawings). FA Contractor may perform work itself (happens frequently when FA is only discipline in an existing installation). FA Contractor s design capabilities vary widely. Page 23

24 Building and Occupancy Assessment Fire Alarm Design depends on: Occupancy Occupant loading Special uses Number of stories Height (high rise) Architectural details (e.g., location of exit discharge) Presence of certain fire protection systems Page 24

25 Building and Occupancy Assessment Occupancy Classification: Provided by the architect or code consultant Assembly (Groups A-1, A-2, A-3, A-4, & A-5), Business (Group B), Mercantile (Group M), and others. Building may be mixed occupancy, separated or nonseparated. Page 25

26 Building and Occupancy Assessment Occupant Loading Based on use of space, not occupancy. Determined per Section 1004 of the IBC. For example, an assembly use within a Group B occupancy: a conference room in an office building would be loaded at 15 persons/net SF. Spaces added up to obtain occupant loading. Performed by architect, code consultant, or fire protection engineer. Page 26

27 Building and Occupancy Assessment Special Uses Code requirements from Chapter 4 of IBC applied in addition to, or in lieu of general building code requirements. Examples include high rise, hazardous use, and special amusement buildings. May or may not contain FA requirements, but designer should always check. Page 27

28 Building and Occupancy Assessment Where Required Section and Chapter 4 of IBC for scoping. Section 907 Provides other high level fire alarm design requirements. NFPA 72 Standard used for detailed design; calculations; designer qualifications; supervising station requirements; inspection, testing, and maintenance requirements. Page 28

29 Codes/Standards/Listings Code: when and where it is needed (IBC) Properly scoped, designed, installed, and specified system. Compliant System Standard: how you design and install it (NFPA 72) Listing: How the equipment and components must be (UL 268) Page 29

30 SD, DD Phases As in new installations in large, public, multidisciplinary projects. Schematic Design (15%) Fire Alarm code requirements are included in building program and design criteria. Design Development (65%) Equipment sized and located within building. Major conduit (fire-rated, panel to panel) runs shown. Draft list of required specs. Design coordinated with other disciplines. Preliminary cost estimate completed. Page 30

31 CD Phases Construction Documents (85%) Equipment layouts finalized. Initiating devices/notification devices layout performed. Riser diagram. Fire alarm matrix. Specifications. Cost estimate with material list. General notes and specific notes. Page 31

32 CD Phases Construction Documents (100%) All information necessary for bidding, permitting. Finalized specifications. Sealed by Fire Protection Engineer and/or NICET IV Fire Alarm Designer. Site specific work-related info, phasing, or scheduling. Contract Documents. Finalized cost estimate: engineer s estimate and material list. Page 32

33 Bidding Bidding Engineer compiles bidding documents for owner to obtain completive bids from a fire alarm contractor. 100% Approved Contract Documents. Plans, specifications, cost estimate, schedule, forms. Owner engages contractors in competitive bid process. Page 33

34 Bidding Engineer assists owner in making a selection, depending on owner s selection criteria. Cost Qualification Value Engineer s estimate compared to contractor s estimate. Engineer evaluates bids to ensure they meet all requirements. Owner makes final contractor selection. Page 34

35 Construction Administration - Overview Owner Owner maintains separate contracts with engineer and contractor. Engineer Engineer acts as owner s rep, ensuring owner s needs and technical requirements are met. Contractor Contractor extends contract documents into shop drawings and installation, adhering to direction and guidance from the engineer. Page 35

36 CA Shop Drawings Shop Drawings possess greater detail than contract drawings and generally show enough information for field construction. Conceptual point to point wiring runs. Junction boxes. Voltage drop and battery sizing calculations. Specific equipment model numbers shown. Cut sheets for equipment provided as part of shop drawing package. Page 36

37 CA Shop Drawings Page 37

38 CA Shop Drawings Engineer reviews shop drawings for conformance to contract drawings, technical requirements, and design/owner intent. After engineer review, contractor submits shop drawings to AHJ for approval. Shop drawings should be approved before fieldwork begins. Page 38

39 CA Requests for Information Contractor will submit to engineer RFIs during construction should any unusual field conditions be found or any defects in contract drawings (original design). Engineer responds to RFIs based on code requirements, specifications, and any special owner needs. Any serious deviation from original plans, scope will result in change order, which is also evaluated by the engineer. Page 39

40 CA - Inspections Engineer may periodically inspect contractor work during installation. Punch lists are developed and checked for completion. Final inspection and punch list. AHJ inspection(s). Electrical Inspector Fire (alarm) Inspector Both Page 40

41 Commissioning NFPA 72 details commissioning, acceptance test requirements. Detailed, per fire alarm subsystems. Reporting and documentation requirements. Witnessing requirements. Fire alarm commissioning may be part of a larger effort. NFPA 3 outlines guidance for such efforts Fire Commissioning Agent (FCxA) In addition to NFPA 72 requirements! Page 41

42 Case Study 6 Story Office FA Upgrade Real Estate Company owns a six story office building in downtown Newark. The FA system was installed 18 years ago. The building was provided with area smoke detection throughout, 2000 area smoke detectors, and also has automatic sprinkler protection. Page 42

43 Case Study 6 Story Office FA Upgrade The Owner was advised to replace the fire alarm control units in an attempt at FA modernization. Owner is also aware that all the smoke detectors need to be replaced in two years. Owner is unsure about how to proceed with the upgrade so it hires a Consultant, a fire protection engineering firm, to perform a feasibility study for upgrading the system and to recommend preliminary design options. Page 43

44 Case Study 6 Story Office FA Upgrade Consultant writes a letter proposal to perform the work. Feasibility study survey yields the fact that no HVAC return duct detectors were present. The exception in the Code for area detectors (in lieu of duct detectors) explains their absence. Consultant confirms FACP is obsolete; a system compatible replacement FACP is recommended. Consultant recommends area smoke detection be removed and HVAC return duct smoke detectors be added. Page 44

45 Case Study 6 Story Office FA Upgrade Code Analysis Check: 2009 IBC Smoke detection not required for Group B NFPA 72, 2010 Ed says duct detectors not substituted for area detectors Applies only for required area smoke detectors Page 45

46 Case Study 6 Story Office FA Upgrade Remove area smoke detectors. Install HVAC duct detectors where return ductwork intersects vertical return shaft. Replace FACP and balance of remaining smoke detectors. Cost of replacing and maintaining 2000 detectors saved and system is still code compliant. Code (existing) / client-driven combination. Page 46

47 Case Study 6 Story Office FA Upgrade But why was there area smoke detectors installed to begin with when they are not required in current Code? Legacy (BOCA, Standard Building Code, etc.) requirement, HVAC duct detector exception? Past local building code amendment? Substitute for another code variance? At the time, client (potentially different than current client) installed them for another need? All that matters is current requirements. Page 47

48 Case Study 6 Story Office FA Upgrade After consultant recommendation, two options: Consultant prepares contract drawings, gets them approved and then helps Owner hire contractor for shop drawings and installation Contractor prepares shop drawings and installs system based on Consultant study, without any design work by the Consultant What s best for this example and why? Page 48

COMMERCIAL (IBC) FIRE ALARM SUBMITTAL GUIDE

COMMERCIAL (IBC) FIRE ALARM SUBMITTAL GUIDE COMMERCIAL (IBC) FIRE ALARM SUBMITTAL GUIDE SUPERVISION OF AUTOMATIC FIRE SPRINKLER SYSTEMS SUPERVISION OF ALTERNATIVE AUTOMATIC FIRE-EXTINGUISHING SYSTEMS FIRE ALARM AND DETECTION SYSTEMS The Fire Alarm

More information

Minimum Standards for Engineers Practicing Fire Protection Engineering in the State of Oklahoma September 14, 2016

Minimum Standards for Engineers Practicing Fire Protection Engineering in the State of Oklahoma September 14, 2016 1. Introduction The intent of this document is to establish minimum standards for the practice of fire protection engineering within the State of Oklahoma as conducted by licensed professional engineers.

More information

MY BILL OF RIGHTS.ORG COMMISSIONING GUIDELINES & STANDARDS VISION AND PROCESS

MY BILL OF RIGHTS.ORG COMMISSIONING GUIDELINES & STANDARDS VISION AND PROCESS MY BILL OF RIGHTS.ORG CELEBRATING AMERICA S FOUNDING FREEDOMS THE BILL OF RIGHTS MONUMENT PROJECT A LEGACY OF LANDMARK INSTALLATIONS ART AND INSPIRATION IN OUR PUBLIC SQUARE COMMISSIONING GUIDELINES &

More information

Moreno Valley Fire Department Fire Prevention Bureau. New and Existing Fire Alarm & Signaling Systems Guideline

Moreno Valley Fire Department Fire Prevention Bureau. New and Existing Fire Alarm & Signaling Systems Guideline Moreno Valley Fire Department Guideline Approved and Authorized By: Adria Reinertson, Fire Marshal Issued: May 8, 2017 Alarm & Signaling Systems PURPOSE Fire alarm and signaling systems are designed to

More information

1. Floor above/floor below notification. 2. Private alarm notification. 3. Not Used 4. Voice alarm notification. 5. Not Used.

1. Floor above/floor below notification. 2. Private alarm notification. 3. Not Used 4. Voice alarm notification. 5. Not Used. PART 1 GENERAL 1.01 Scope of Standard A. This Standard is intended to assure that fire alarm and signaling systems at Sam Houston State University provide the highest level of life safety possible. This

More information

REQUEST FOR QUALIFICATIONS

REQUEST FOR QUALIFICATIONS REQUEST FOR QUALIFICATIONS for the City of Lake Forest Issue Date: September 23, 2015 Bid Due Date: October 19, 2015 The City of Lake Forest 800 N. Field Drive Lake Forest, Illinois 60045 THE CITY OF LAKE

More information

Rancho Cucamonga Fire Protection District Prevention Bureau Standard

Rancho Cucamonga Fire Protection District Prevention Bureau Standard Rancho Cucamonga Fire Protection District Prevention Bureau Standard Title: Fire Alarm and Monitoring Systems Standard # 9-3 Effective: May 2002 Number of Pages: 7 Updated: December 2016 for consistency

More information

SECTION : FIRE ALARM & DETECTION SYSTEMS

SECTION : FIRE ALARM & DETECTION SYSTEMS SECTION 28 31 10: FIRE ALARM & DETECTION SYSTEMS 1. GENERAL A. This section applies to fire detection/alarm system and carbon monoxide system components and equipment installed during new construction

More information

CHAPTER A-6 FIRE PROTECTION

CHAPTER A-6 FIRE PROTECTION CHAPTER A-6 FIRE PROTECTION 6.1 GENERAL 6.1.1 Scope 6.1.2 Purpose 6.1.3 Qualifications of Fire Prevention Engineer 6.1.4 Required Design 6.1.5 Critical Projects 6.2 APPLICABLE PUBLICATIONS 6.3 PRECONCEPT

More information

SUWANNEE RIVER WATER MANAGEMENT DISTRICT REQUEST FOR BID NO. 15/16-003AO FIRE ALARM SYSTEM INSTALLATION AND MONITORING.

SUWANNEE RIVER WATER MANAGEMENT DISTRICT REQUEST FOR BID NO. 15/16-003AO FIRE ALARM SYSTEM INSTALLATION AND MONITORING. SUWANNEE RIVER WATER MANAGEMENT DISTRICT REQUEST FOR BID NO. 15/16-003AO FIRE ALARM SYSTEM INSTALLATION AND MONITORING Table of Contents Section Title Page 1 Introduction 2 2 Proposed Schedule 2 3 Instructions

More information

SOCIETY OF FIRE PROTECTION ENGINEERS POSITION STATEMENT P THE ENGINEER AND THE TECHNICIAN DESIGNING FIRE PROTECTION SYSTEMS.

SOCIETY OF FIRE PROTECTION ENGINEERS POSITION STATEMENT P THE ENGINEER AND THE TECHNICIAN DESIGNING FIRE PROTECTION SYSTEMS. SOCIETY OF FIRE PROTECTION ENGINEERS POSITION STATEMENT P-01-05 THE ENGINEER AND THE TECHNICIAN DESIGNING FIRE PROTECTION SYSTEMS October, 2005 Society of Fire Protection Engineers - 1 - Position Statement

More information

REQUIREMENTS. For FIRE DEPARTMENTS. State of West Virginia. Bob Wise Governor THE DEPARTMENT OF MILITARY AFFAIRS AND PUBLIC SAFETY

REQUIREMENTS. For FIRE DEPARTMENTS. State of West Virginia. Bob Wise Governor THE DEPARTMENT OF MILITARY AFFAIRS AND PUBLIC SAFETY REQUIREMENTS For FIRE DEPARTMENTS State of West Virginia Bob Wise Governor THE DEPARTMENT OF MILITARY AFFAIRS AND PUBLIC SAFETY Joe Martin Secretary West Virginia State Fire Commission 1207 Quarrier St.,

More information

Narrative Reports As Regulated by 780 CMR, Section 903.0

Narrative Reports As Regulated by 780 CMR, Section 903.0 EXHIBIT 20 Narrative Reports As Regulated by 780 CMR, Section 903.0 903.1.1 - FIRE PROTECTION CONSTRUCTION DOCUMENTS a. Basis (methodology) of design for the protection of the occupancy and hazard for

More information

Tennessee Code/TITLE 62 PROFESSIONS, BUSINESSES AND TRADES/CHAPTER 32 FIRE PROTECTION/PART 1 FIRE PROTECTION SPRINKLER SYSTEMS

Tennessee Code/TITLE 62 PROFESSIONS, BUSINESSES AND TRADES/CHAPTER 32 FIRE PROTECTION/PART 1 FIRE PROTECTION SPRINKLER SYSTEMS Tennessee Code/TITLE 62 PROFESSIONS, BUSINESSES AND TRADES/CHAPTER 32 FIRE PROTECTION/PART 1 FIRE PROTECTION SPRINKLER SYSTEMS PART 1 FIRE PROTECTION SPRINKLER SYSTEMS Source: Tennessee Code/TITLE 62 PROFESSIONS,

More information

2019 COURSE CATALOG (rev )

2019 COURSE CATALOG (rev ) 2019 COURSE CATALOG (rev. 02.07.19) www.afaa.org CEUs Available for NICET, Engineers and Other! 3246 Noe-Bixby Road, Suite 101, Columbus, OH 43232 844-438-2322 Page 1 Page No. Seminar Name 3. A User s

More information

Request for Qualifications. Knowledge Park Pedestrian/Cyclist Connectivity Planning and Design

Request for Qualifications. Knowledge Park Pedestrian/Cyclist Connectivity Planning and Design PUR872 I. Invitation Request for Qualifications Knowledge Park Pedestrian/Cyclist Connectivity Planning and Design The City of Rock Hill is requesting Statements of Qualifications from interested and qualified

More information

Princeton Joint Unified School District Invitation for Bid Installation of District-Wide Lighting Occupancy Sensors

Princeton Joint Unified School District Invitation for Bid Installation of District-Wide Lighting Occupancy Sensors Princeton Joint Unified School District Invitation for Bid Installation of District-Wide Lighting Occupancy Sensors 1. SUMMARY AND BACKGROUND: Princeton Joint Unified School District located in Princeton

More information

FIRE ALARM SYSTEMS & 780 CMR. Dave LeBlanc, PE, FSFPE March 17, 2015

FIRE ALARM SYSTEMS & 780 CMR. Dave LeBlanc, PE, FSFPE March 17, 2015 FIRE ALARM SYSTEMS & 780 CMR Dave LeBlanc, PE, FSFPE March 17, 2015 BIOGRAPHY David J. LeBlanc, PE, FSFPE BS EE & MS FPE - WPI 23 Years PE Technical Committee Member NFPA72 - National Fire Alarm Code NFPA3

More information

Request for Proposals Design Services for Kitchen Remodel and Second Floor Layout

Request for Proposals Design Services for Kitchen Remodel and Second Floor Layout Request for Proposals Design Services for Kitchen Remodel and Second Floor Layout I. About the Agency StopWaste helps Alameda County s businesses, residents and schools waste less, recycle more and use

More information

Electronic Safety and Security

Electronic Safety and Security 28 Electronic Safety and Security NOTE: This is a new section, which includes content from previous sections of the KU Design Standards, along with appropriate revisions and updates. Significant revisions

More information

Standard of Practice - Fire Alarm Systems. NOTE: Significant revisions or additions to the previous standards are highlighted in italics.

Standard of Practice - Fire Alarm Systems. NOTE: Significant revisions or additions to the previous standards are highlighted in italics. A28.1 Standard of Practice - Fire Alarm Systems NOTE: Significant revisions or additions to the previous standards are highlighted in italics. OBJECTIVE OF STANDARD To provide compliant smart addressable

More information

DONALD H. BERG, ARCHITECT

DONALD H. BERG, ARCHITECT DONALD H. BERG, ARCHITECT DVA PROJECT 632-CSI-402 PET/CT ROOM #A0-10 RENOVATION BASEMENT LEVEL, BUILDING 200 ARCHITECT S PROJECT No. 0917-02 ADDENDUM NO. 1 JUNE 25, 2018 Page 1 of 1 ARCHITECTURAL 1. Specifications:

More information

Florida Building Code Chapter 9 Fire Protection Systems Advanced Course

Florida Building Code Chapter 9 Fire Protection Systems Advanced Course Florida Building Code 2010 Chapter 9 Fire Protection Systems Advanced Course 1 Introduction This course will cover specific sections of Chapter 9 that relate to fire alarm systems. While many contractors

More information

D. The work addressed in this section consists of a fire protection system, which may include coordination with one or more of the following:

D. The work addressed in this section consists of a fire protection system, which may include coordination with one or more of the following: PART 1 GENERAL 1.01 Scope of Standard A. This standard provides general requirements of Sam Houston State University for the design and construction of standpipe systems to include combination standpipe

More information

STATE FIRE MARSHAL S REQUIRED FIRE PROTECTION SYSTEMS NARRATIVE REPORT

STATE FIRE MARSHAL S REQUIRED FIRE PROTECTION SYSTEMS NARRATIVE REPORT STATE FIRE MARSHAL S REQUIRED FIRE PROTECTION SYSTEMS NARRATIVE REPORT The interaction of fire protection systems can be extremely complex. The detection of a fire in a building by an automatic device

More information

International Fire Code 2006 Requirements for Construction Plan Reviews of Commercial and Multi-Family Structures

International Fire Code 2006 Requirements for Construction Plan Reviews of Commercial and Multi-Family Structures International Fire Code 2006 Requirements for Construction Plan Reviews of Commercial and Multi-Family Structures Please note this is not an all-inclusive list. The type and complexity of your project

More information

CAN/ULC S Integrated Systems Testing of Fire Protection and Life Safety Systems and Fire Protection Commissioning

CAN/ULC S Integrated Systems Testing of Fire Protection and Life Safety Systems and Fire Protection Commissioning CAN/ULC S1001-11 Integrated Systems Testing of Fire Protection and Life Safety Systems and Fire Protection Commissioning Presentation To: Canadian Fire Alarm Association (CFAA) National Capital Region

More information

CAN/ULC-S1001, INTEGRATED SYSTEMS TEST OF FIRE PROTECTION AND LIFE SAFETY SYSTEMS

CAN/ULC-S1001, INTEGRATED SYSTEMS TEST OF FIRE PROTECTION AND LIFE SAFETY SYSTEMS RANDAL BROWN & ASSOCIATES ENGINEERING LTD. CONSULTING ENGINEERS LIFE SAFETY & FIRE PROTECTION 105 6 LANSING SQUARE TORONTO, ONTARIO CAN/ULC-S1001, INTEGRATED SYSTEMS TEST OF FIRE PROTECTION AND LIFE SAFETY

More information

Bold items are particular to the City of Euless

Bold items are particular to the City of Euless EULESS FIRE DEPARTMENT FIRE MARSHAL S OFFICE INFORMATION LINE: Revised 8/2004 Fire Chief Lee Koontz Fire Marshal Paul Smith EFD-FMO 3-1 2003 International Fire & Building Code as Amended NFPA Standards

More information

CAN/ULC-S1001, INTEGRATED SYSTEMS TESTING OF FIRE PROTECTION & LIFE SAFETY SYSTEMS Simon Crosby, LEL, CET, CFPS October 21, 2015

CAN/ULC-S1001, INTEGRATED SYSTEMS TESTING OF FIRE PROTECTION & LIFE SAFETY SYSTEMS Simon Crosby, LEL, CET, CFPS October 21, 2015 CAN/ULC-S1001, INTEGRATED SYSTEMS TESTING OF FIRE PROTECTION & LIFE SAFETY SYSTEMS Simon Crosby, LEL, CET, CFPS October 21, 2015 Fire Commissioning in Canadian Codes and Standards BACKGROUND Why Commissioning?

More information

You are required to READ ALL PAGES. of this application

You are required to READ ALL PAGES. of this application Fire/Smoke/Heat/CO Application Checklist You are required to READ ALL PAGES of this application NEW ROCHELLE FIRE DEPARTMENT 90 Beaufort Pl, New Rochelle, NY 10801 - (914) 654-2213 APPLICATION FOR FIRE/SMOKE/HEAT/CO

More information

Purpose : Project Manager. Professional. Contractor: devices/system. compatibility

Purpose : Project Manager. Professional. Contractor: devices/system. compatibility I. Title: Fire Alarm Systems Design, Construction and Commissioning II. Purpose : Define activities, identify stakeholders, and assign responsibilities as it relates to the installation of fire alarm devices

More information

LANDSCAPE ARCHITECTURAL ASSISTANT, 7931 LANDSCAPE ARCHITECTURAL ASSOCIATE, 7932 LANDSCAPE ARCHITECT, 7929

LANDSCAPE ARCHITECTURAL ASSISTANT, 7931 LANDSCAPE ARCHITECTURAL ASSOCIATE, 7932 LANDSCAPE ARCHITECT, 7929 2-24-84 LANDSCAPE ARCHITECTURAL ASSISTANT, 7931 Summary of Duties : Performs professional landscape architectural work in the design and preparation of plans, sketches, and drawings for the development

More information

Design & Construction Standards, Revised January

Design & Construction Standards, Revised January PART 1 GENERAL 1.01 Scope of Standard A. This standard provides general requirements of The University of Texas at Austin for the design and construction of standpipe systems to include combination standpipe

More information

APPENDIX H (DESIGN SUBMISSION CRITERIA)

APPENDIX H (DESIGN SUBMISSION CRITERIA) APPENDIX H (DESIGN SUBMISSION CRITERIA) FIRE ALARM SYSTEM As per ACCORD standard Part 5, section 5.7 Fire Alarm System Design to be verified by ACCORD Chief Safety Inspector. Testing of the installation

More information

H BUTCH BROWNING FIRE MARSHAL BUILDING REHABILITATION

H BUTCH BROWNING FIRE MARSHAL BUILDING REHABILITATION STATE OF LOUISIANA Department of Public Safety and Corrections Office of State Fire Marshal Code Enforcement and Building Safety 8181 Independence Boulevard Baton Rouge, Louisiana 70806 225-925-4920 H

More information

El Reno Fire Department Fire Alarm Plan Review Worksheet

El Reno Fire Department Fire Alarm Plan Review Worksheet El Reno Fire Department Fire Alarm Plan Review Worksheet This Fire Alarm Plan Review Checklist is provided as a guide to assist with your Fire Alarm Plan Review Submittal requirements. Please contact us

More information

WEST VIRGINIA UNIVERSITY

WEST VIRGINIA UNIVERSITY WEST VIRGINIA UNIVERSITY Environmental Health and Safety (SOP) WV State Fire Marshal (SFM) Project Plans Review Process & Procedures West Virginia University Environmental Health & Safety Page 1 of 10

More information

CAN/ULC-S INTEGRATED SYSTEMS TESTING OF FIRE PROTECTION AND LIFE SAFETY SYSTEMS

CAN/ULC-S INTEGRATED SYSTEMS TESTING OF FIRE PROTECTION AND LIFE SAFETY SYSTEMS 2013 Randal Brown & Associates Engineering Ltd. 1 RANDAL BROWN & ASSOCIATES ENGINEERING LTD. CONSULTING ENGINEERS LIFE SAFETY & FIRE PROTECTION 105 6 LANSING SQUARE TORONTO, ONTARIO CAN/ULC-S1001-11 INTEGRATED

More information

GATEWAY BUILDING ELEVATOR AND ESCALATOR SERVICES

GATEWAY BUILDING ELEVATOR AND ESCALATOR SERVICES 29 One Gateway Plaza Los Angeles, CA 90012-2952 213.922.2000 Tel metro.net SYSTEM SAFETY AND OPERATIONS COMMITTEE JANUARY 16, 2014 SUBJECT: ACTION: GATEWAY BUILDING ELEVATOR AND ESCALATOR SERVICES APPROVE

More information

SECTION DIGITAL, ADDRESSABLE FIRE-ALARM SYSTEM

SECTION DIGITAL, ADDRESSABLE FIRE-ALARM SYSTEM SECTION 283111 - DIGITAL, ADDRESSABLE FIRE-ALARM SYSTEM PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division

More information

Fire Alarm, Water Flow Alarm & Signaling Systems

Fire Alarm, Water Flow Alarm & Signaling Systems Orange County Fire Authority Community Risk Reduction 1 Fire Authority Road, Building A, Irvine, CA 92602 www.ocfa.org 714-573-6100 Fire Alarm, Water Flow Alarm & Signaling Systems Guideline D-03 Serving

More information

Florida Building Code 2010

Florida Building Code 2010 Introduction Florida Building Code 2010 Chapter 9 Fire Protection Systems This course will cover specific sections of Chapter 9 that relate to fire alarm systems. While many contractors are familiar with

More information

NFPA 72 Code Changes vs 2013

NFPA 72 Code Changes vs 2013 NFPA 72 Code Changes - 2010 vs 2013 AFAA-NE Westborough, MA February 7, 2018 Richard Roux NFPA 72 National Fire Alarm and Signaling Code Overview and 2013 Changes NFPA 72 1993 Edition Aug 20, 1993 1996

More information

PART 1 GENERAL Quality Assurance A. Fire Alarm Contractor Qualifications:

PART 1 GENERAL Quality Assurance A. Fire Alarm Contractor Qualifications: PART 1 GENERAL 1.01 Quality Assurance A. Fire Alarm Contractor Qualifications: 1 The Fire Alarm contractor shall be an Edwards Systems Technology (EST) designated representative and authorized to sell,

More information

1.3 REFERENCE STANDARDS

1.3 REFERENCE STANDARDS SECTION 28 4600 FIRE DETECTION AND ALARM PART 1 -GENERAL 1.1 SECTION INCLUDES A. Fire alarm system design and installation, including all components, wiring, and conduit. B. Circuits from protected premises

More information

FIRE & LIFE SAFTEY STANDARD

FIRE & LIFE SAFTEY STANDARD Title: Effective Date: 01/01/14 Revised Date: 1/1/14 Code References: Title 16, Chapter 16.16 of the Roseville Municipal Code, NFPA 72 Note: This standard is a summary of Fire Department clarifications

More information

I. INTRODUCTION Codes, Rules, Laws, & Requirements

I. INTRODUCTION Codes, Rules, Laws, & Requirements I. INTRODUCTION 1.03 Codes, Rules, Laws, & Requirements A. Buildings and sites are to be designed in conformance to the applicable requirements of the following: 1. The Texas Engineering Practice Act and

More information

Slide 1. Slide 2 Instructor. Slide 3. NFPA 25 The Owner s Manual. Roles & Responsibilities DISCLAIMER

Slide 1. Slide 2 Instructor. Slide 3. NFPA 25 The Owner s Manual. Roles & Responsibilities DISCLAIMER Slide 1 NFPA 25 The Owner s Manual Roles & Responsibilities Presented by: Bob Caputo Slide 2 Instructor Bob is the Executive Vice President of Compliance Solutions with Telgian Corporation. He is the Chairman

More information

SECTION REGULATORY REQUIREMENTS. A. Relationship between Code, Ordinances, Standards and Contract Documents

SECTION REGULATORY REQUIREMENTS. A. Relationship between Code, Ordinances, Standards and Contract Documents SECTION 01410 PART I - GENERAL 1.01 SECTION INCLUDES A. Relationship between Code, Ordinances, Standards and Contract Documents B. Applicable Codes, Laws and Ordinances C. Project Inspections D. Office

More information

DEPARTMENT OF PUBLIC SAFETY DIVISION OF FIRE PREVENTION AND CONTROL

DEPARTMENT OF PUBLIC SAFETY DIVISION OF FIRE PREVENTION AND CONTROL DEPARTMENT OF PUBLIC SAFETY DIVISION OF FIRE PREVENTION AND CONTROL RULES AND REGULATIONS CONCERNING 8 CCR 1507-57 BUILDING AND FIRE CODE ENFORCEMENT AND CERTIFICATION OF INSPECTORS FOR LIMITED GAMING

More information

Brighton Area Fire Authority

Brighton Area Fire Authority 615 W. Grand River Ave. Brighton, MI 48116 o: 810-229-6640 f: 810-229-1619 January 14, 2019 Fire Alarm Contractors RE: Fire Alarm Credential & Submittal Requirements To Whom It May Concern: The following

More information

Annual Fire Systems and Backflow Preventers Testing

Annual Fire Systems and Backflow Preventers Testing Facilities Management Request for Qualifications Annual Fire Systems and Backflow Preventers Testing At Various Facilities Proposals Due: 2:30 PM, Tuesday May 15, 2018 Deliver to: Attn: Sara Winger, Purchasing

More information

National Fire Protection Association. 1 Batterymarch Park, Quincy, MA Phone: Fax:

National Fire Protection Association. 1 Batterymarch Park, Quincy, MA Phone: Fax: National Fire Protection Association 1 Batterymarch Park, Quincy, MA 02169-7471 Phone: 617-770-3000 Fax: 617-770-0700 www.nfpa.org M E M O R A N D U M TO: FROM: NFPA Technical Committee on Notification

More information

Tenant Heat Pump Bulletin Temperature Controls Buildings A1, C1, and H1

Tenant Heat Pump Bulletin Temperature Controls Buildings A1, C1, and H1 12/4/2017 Tenant Heat Pump Bulletin Temperature Controls Buildings A1, C1, and H1 This bulletin is to advise you of the fees and responsibilities associated with the tenant s temperature controls. Tenant

More information

SANTA CLARA COUNTY Winchester Blvd., Los Gatos, CA (408) (408) (fax)

SANTA CLARA COUNTY Winchester Blvd., Los Gatos, CA (408) (408) (fax) FIRE DEPARTMENT SANTA CLARA COUNTY 14700 Winchester Blvd., Los Gatos, CA. 95032-1818 (408) 378-4010 (408) 378-9342 (fax) www.sccfd.org STANDARD DETAILS & SPECIFICATIONS Spec No C-4 Rev. Date 03/10/10 SUBJECT:

More information

Oklahoma. 265: Incorporated national codes and standards The following national codes and standards are incorporated by reference:

Oklahoma. 265: Incorporated national codes and standards The following national codes and standards are incorporated by reference: Oklahoma 310:451-1-3. Adopted references The Board of Health hereby incorporates by reference the International Code Council (ICC) 2006 (IBC) Edition International Building Code; the 2007 Edition Standard

More information

PRIVATE FIRE SERVICE INSTALLATION PACKET

PRIVATE FIRE SERVICE INSTALLATION PACKET PRIVATE FIRE SERVICE INSTALLATION PACKET The 2017 Edition supersedes all previous versions for Private Fire Service Installation To Whom It May Concern: SUBJECT: PRIVATE FIRE SERVICE INSTALLATION Illinois

More information

RESIDENTIAL CARE USER GUIDE UPDATES TO MANITOBA BUILDING/FIRE CODE:

RESIDENTIAL CARE USER GUIDE UPDATES TO MANITOBA BUILDING/FIRE CODE: RESIDENTIAL CARE USER GUIDE UPDATES TO MANITOBA BUILDING/FIRE CODE: Manitoba Regulation 221/2015 and Manitoba Regulation 222/2015 DATE: MARCH 17, 2016 1. INTRODUCTION On April 1, 2016, new building and

More information

SECTION WET-PIPE SPRINKLER SYSTEMS

SECTION WET-PIPE SPRINKLER SYSTEMS SECTION 21 13 13 WET-PIPE SPRINKLER SYSTEMS PART 1 - GENERAL 1.1 SCOPE OF WORK A. Design, installation and testing shall be in accordance with NFPA 13 except for specified exceptions. B. The demolition

More information

American Fire Sprinkler Association. An Introduction to the IBC and IFC

American Fire Sprinkler Association. An Introduction to the IBC and IFC American Fire Sprinkler Association Presents An Introduction to the IBC and IFC October 13, 2005 Speaker Roland Huggins, P.E. Vice President of Engineering and Technical Services American Fire Sprinkler

More information

I. INTRODUCTION SITE DESCRIPTION

I. INTRODUCTION SITE DESCRIPTION Request for Proposals Design Services for the Visitor Access and Engagement Project at Roy s Redwoods Open Space Preserve Marin County Parks & Open Space Preserve Woodacre, Marin County, CA November 12,

More information

MAINTENANCE AND TESTING OF FIRE SPRINKLER SYSTEMS

MAINTENANCE AND TESTING OF FIRE SPRINKLER SYSTEMS MAINTENANCE AND TESTING OF FIRE SPRINKLER SYSTEMS Introduction When properly installed and maintained, automatic fire sprinkler systems have proven to be the most effective means for protecting life and

More information

INVITATION TO QUOTE. Page 1 of 7. Fire & Emergency Safety Plan Control Number: 2018-CFS-003 Issue Date: March 7, Purpose

INVITATION TO QUOTE. Page 1 of 7. Fire & Emergency Safety Plan Control Number: 2018-CFS-003 Issue Date: March 7, Purpose INVITATION TO QUOTE Title: Fire & Emergency Safety Plan Control Number: 2018-CFS-003 Issue Date: March 7, 2018 Purpose The District of Sparwood (Sparwood) invites interested parties (Respondents) to submit

More information

Center for Life Safety Education

Center for Life Safety Education Center for Life Safety Education Fire Sprinklers 101 Introduction, Building Codes, and Water Supplies Reprinted with permission from NFPA 13, Installation of Sprinkler Systems, Copyright 2007, National

More information

Advanced Fire Alarm Systems Training Program Outline (5 Day)

Advanced Fire Alarm Systems Training Program Outline (5 Day) Advanced Fire Alarm Systems Training Program Outline (5 Day) Day 1 Prescriptive and Performance-Based Design Understand the methodology in accessing the threat of fire within a structure. Know the difference

More information

CITY OF LONG BEACH Department of Development Services BUILDING AND SAFETY BUREAU FIRE ALARM / ELECTRICAL FIRE PLAN REVIEW CHECKLIST

CITY OF LONG BEACH Department of Development Services BUILDING AND SAFETY BUREAU FIRE ALARM / ELECTRICAL FIRE PLAN REVIEW CHECKLIST CITY OF LONG BEACH Department of Development Services BUILDING AND SAFETY BUREAU FIRE ALARM / ELECTRICAL FIRE PLAN REVIEW CHECKLIST DATE: PROJECT NO.: EXPIRATION DATE: STATUS: INFORMATION PROJECT ADDRESS:

More information

Western Pennsylvania Conservancy Clairton & Harrison Community Greening Assessment Projects Request for Proposals July 2018

Western Pennsylvania Conservancy Clairton & Harrison Community Greening Assessment Projects Request for Proposals July 2018 Western Pennsylvania Conservancy Clairton & Harrison Community Greening Assessment Projects Request for Proposals July 2018 Proposal Information The Western Pennsylvania Conservancy (WPC) is seeking proposals

More information

Pre-Bid Meeting Minutes 2018 A & E RFP February 6, :00 a.m.

Pre-Bid Meeting Minutes 2018 A & E RFP February 6, :00 a.m. Attendees: Pre-Bid Meeting Minutes 2018 A & E RFP February 6, 2019 10:00 a.m. Anthony Shomin Sue Martin Architectural & Engineer Professionals KCKHA Modernization Coordinator KCKHA Modernization Admin.

More information

Florida Senate SB 982 By Senator Bennett

Florida Senate SB 982 By Senator Bennett By Senator Bennett 1 A bill to be entitled 2 An act relating to electrical and alarm system 3 contracting; amending s. 489.503, F.S.; 4 requiring certain contractors to be certified 5 pursuant to part

More information

CALIFORNIA DEPARTMENT of FORESTRY and FIRE PROTECTION OFFICE OF THE STATE FIRE MARSHAL UL 300

CALIFORNIA DEPARTMENT of FORESTRY and FIRE PROTECTION OFFICE OF THE STATE FIRE MARSHAL UL 300 CALIFORNIA DEPARTMENT of FORESTRY and FIRE PROTECTION OFFICE OF THE STATE FIRE MARSHAL UL 300 FREQUENTLY ASKED QUESTIONS CONCERNING COMMERCIAL COOKING PROTECTION Published by FIRE ENGINEERING DIVISION

More information

Request For Quotations. For The. Fire Sprinkler Retrofit Program For Licensed Small Or Rural Retirement Homes. October 11, 2017

Request For Quotations. For The. Fire Sprinkler Retrofit Program For Licensed Small Or Rural Retirement Homes. October 11, 2017 Request For Quotations For The Fire Sprinkler Retrofit Program For Licensed Small Or Rural Retirement Homes October 11, 2017 1 Table of Contents Introduction... 3 Retirement Home Information... 3 RFQ Overview...

More information

PART 1 GENERAL Quality Assurance A. Fire Alarm Contractor Qualifications:

PART 1 GENERAL Quality Assurance A. Fire Alarm Contractor Qualifications: PART 1 GENERAL 1.01 Quality Assurance A. Fire Alarm Contractor Qualifications: 1 The Fire Alarm contractor shall be an Edwards Systems Technology (EST) designated representative and authorized to sell,

More information

University Design Standard Fire Alarm Systems

University Design Standard Fire Alarm Systems 1.0 Overview University Design Standard Fire Alarm Systems This document provides Virginia Tech s standards for the design and installation of fire alarm systems and equipment in new construction, retrofit

More information

September 30, Dear Fire Suppression System Contractor/Designer:

September 30, Dear Fire Suppression System Contractor/Designer: CITY OF BOZEMAN FIRE DEPARTMENT P.O. Box 1230 Bozeman, Montana 59771-1230 Phone (406) 582-2350 CITY OF BOZEMAN BUILDING DEPARTMENT 20 E Olive St, STE 208 Bozeman, Montana 59715-4790 Phone (406) 582-2375

More information

BULLETIN. Temperature Controls (10/2013)

BULLETIN. Temperature Controls (10/2013) BULLETIN Temperature Controls (10/2013) This bulletin is to advise you of the fees and responsibilities associated with the tenant s temperature controls. This applies to Phase I & II only. Tenant Responsibility:

More information

BULLETIN. Temperature Controls (VAV) (3/11/2010)

BULLETIN. Temperature Controls (VAV) (3/11/2010) BULLETIN Temperature Controls (VAV) (3/11/2010) This bulletin is to advise you of the fees and responsibilities associated with Tenant s temperature controls. Tenant Responsibility: 1. Unit power is by

More information

CHAPTER LOCAL AMENDMENTS TO THE INTERNATIONAL FIRE CODE, 2000 EDITION SECTIONS

CHAPTER LOCAL AMENDMENTS TO THE INTERNATIONAL FIRE CODE, 2000 EDITION SECTIONS CHAPTER 23.45 LOCAL AMENDMENTS TO THE INTERNATIONAL FIRE CODE, 2000 EDITION SECTIONS 23.45.100 Local Amendments To The International Fire Code, 2000 Edition 23.45.102.1 Construction and Design Provisions

More information

DIVISION 21 FIRE SUPPRESSION

DIVISION 21 FIRE SUPPRESSION DIVISION 21 FIRE SUPPRESSION Table of Contents 21 00 01 General 21 00 02 Scope 21 00 03 Codes 21 00 04 Design Intent Report 21 00 05 Coordination with University of Minnesota Departments 21 00 06 Access

More information

COMMISSION ORDER. IT IS FURTHER ORDERED that the Request for Bid and Notice to Bidders be displayed on the Franklin County website.

COMMISSION ORDER. IT IS FURTHER ORDERED that the Request for Bid and Notice to Bidders be displayed on the Franklin County website. 4.e STATE OF MISSOURI County of Franklin ss. COMMISSION ORDER Commission Order No. 2016-316 Third Quarter Term 2016 Tuesday,August,09,2016 Bid Notice IN THE MATTER OF ADVERTISING FOR SEALED BIDS FOR SMOKE

More information

Date of Start and downloading the tender 12 sep 2018

Date of Start and downloading the tender 12 sep 2018 INDRAPRASTHA INSTITUTE OF INFORMATION TECHNOLOGY-DELHI (IIIT-DELHI) Okhla Industrial Estate, Phase III New Delhi 110020 (Tel No 011-26907400, Website: www.iiitd.ac.in) Notice Inviting Tender for Non Comprehensive

More information

FIRE PROTECTION PROGRAM

FIRE PROTECTION PROGRAM Fire Protection Program Page 1 of 13 FIRE PROTECTION PROGRAM 1.0 Objective The objective of this performance assessment is to evaluate the effectiveness of the laboratory's fire protection program as implemented

More information

OF AIRPORT COMMISSIONERS

OF AIRPORT COMMISSIONERS OY i -401 0*11 oir". 4Los Angeles World Airports REPORT TO THE BOARD. OF AIRPORT COMMISSIONERS Meeting Date: Gvt A. Approved by: Aura Moor Chief In ormation Officer c -A/ / v Reviewed by: Samson Mengistu,

More information

CONSTRUCTION REQUIREMENTS

CONSTRUCTION REQUIREMENTS CONSTRUCTION REQUIREMENTS Note: The buildings on the UCCS campus are divided into two categories: General Fund and Auxiliaries. General Fund Buildings include academic and administrative functions. Auxiliary

More information

Challenges of Fire Protection Upgrades in Existing Libraries. Campus Fire Safety Forum

Challenges of Fire Protection Upgrades in Existing Libraries. Campus Fire Safety Forum Challenges of Fire Protection Upgrades in Existing Libraries Campus Fire Safety Forum November 6, 2013 Presentation Overview Code Requirements Goals of Fire Protection Systems Life Safety Property Protection

More information

Residential-based Care Facility R-4 Guideline

Residential-based Care Facility R-4 Guideline Moreno Valley Fire Department Fire Prevention Bureau Residential-based Care Facility R-4 Guideline Approved and Authorized By: Adria Reinertson, Fire Marshal Issued: April 7, 2017 Residential-based Care

More information

ROSWELL INDEPENDENT SCHOOL DISTRICT P.O. Box 1437 Roswell, New Mexico General Bid Conditions

ROSWELL INDEPENDENT SCHOOL DISTRICT P.O. Box 1437 Roswell, New Mexico General Bid Conditions ROSWELL INDEPENDENT SCHOOL DISTRICT P.O. Box 1437 Roswell, New Mexico 88202-1437 General Bid Conditions BID # 19-06 Fire Sprinkler Systems Inspections, Testing and Maintenance SEALED BIDS will be opened

More information

RFP REQUEST FOR PROPOSALS CITY OF PORTSMOUTH, NH. DESIGN ENGINEERING SERVICES North Mill Pond Trail and Greenway

RFP REQUEST FOR PROPOSALS CITY OF PORTSMOUTH, NH. DESIGN ENGINEERING SERVICES North Mill Pond Trail and Greenway RFP 61-18 REQUEST FOR PROPOSALS CITY OF PORTSMOUTH, NH DESIGN ENGINEERING SERVICES North Mill Pond Trail and Greenway Sealed Requests for Proposals, plainly marked RFP 61-18 Design Engineering Services

More information

Understanding and Applying NFPA 25

Understanding and Applying NFPA 25 Understanding and Applying NFPA 25 Texas Edition Learning Objectives Describe the scope of NFPA 25. Distinguish between sprinkler system problems that fall within the scope of NFPA 25 and those that do

More information

Can You Hear Me Now?

Can You Hear Me Now? Fire Alarm Notebook by Dean K. Wilson. P.E. Page 1 Can You Hear Me Now? by Dean K. Wilson, P.E. I am the lead fire alarm system technician at our very extensive multi-building public warehouse complex

More information

2. Closed circuit television, design and installation.

2. Closed circuit television, design and installation. Company: AECO Systems, Inc. is a sound and communicator contractor, affiliated with NECA and IBEW. We specialize in commercial fire alarm systems, providing both sales and engineering. We are also involved

More information

Consent Agenda. Meeting of June 14,2018

Consent Agenda. Meeting of June 14,2018 continued on Page 2 and for automated HVAC building control system maintenance services from Honeywell International Inc., Improvement Fund (3029) in the amount of $12,898.75 from the General Library Improvements

More information

CHAPTER 61G15-32 RESPONSIBILITY RULES OF PROFESSIONAL ENGINEERS CONCERNING THE DESIGN OF FIRE PROTECTION SYSTEMS

CHAPTER 61G15-32 RESPONSIBILITY RULES OF PROFESSIONAL ENGINEERS CONCERNING THE DESIGN OF FIRE PROTECTION SYSTEMS CHAPTER 61G15-32 RESPONSIBILITY RULES OF PROFESSIONAL ENGINEERS CONCERNING THE DESIGN OF FIRE PROTECTION SYSTEMS 61G15-32.001 61G15-32.002 61G15-32.003 61G15-32.004 61G15-32.005 61G15-32.006 61G15-32.007

More information

MINOOKA FIRE PROTECTION DISTRICT Fire Prevention Bureau Fire Inspector Rodney Bradberry

MINOOKA FIRE PROTECTION DISTRICT Fire Prevention Bureau Fire Inspector Rodney Bradberry MINOOKA FIRE PROTECTION DISTRICT Fire Prevention Bureau Fire Inspector Rodney Bradberry Fire Alarm Systems Plan Review Checklist Date: Permit Number: Business Name: Address: Fire Alarm System Submittal

More information

NORTHWESTERN UNIVERSITY PROJECT NAME JOB # ISSUED: 03/29/2017

NORTHWESTERN UNIVERSITY PROJECT NAME JOB # ISSUED: 03/29/2017 SECTION 21 0800 - COMMISSIONING OF FIRE SUPPRESSION SYSTEMS GENERAL 1.1 SUMMARY General 1. Work under this contract shall meet the requirements of Division 01, General Requirements, Conditions of Contract,

More information

FIRE SUPPRESSION SYSTEM REVIEW APPLICATION 1. NEW PLAN REVIEW RESUBMITTAL

FIRE SUPPRESSION SYSTEM REVIEW APPLICATION 1. NEW PLAN REVIEW RESUBMITTAL STATE OF LOUISIANA 10/09/2015 DEPARTMENT OF PUBLIC SAFETY - OFFICE OF STATE FIRE MARSHAL CODE ENFORCEMENT AND BUILDING SAFETY 8181 INDEPENDENCE BLVD., BATON ROUGE, LA 70806 800-256-5452 225-925-4920 FAX:

More information

Public Notice of Amendment to New Shoreham General Ordinances Chapter 5 Fire Prevention and Protection New Article IV Fire Alarm Ordinance

Public Notice of Amendment to New Shoreham General Ordinances Chapter 5 Fire Prevention and Protection New Article IV Fire Alarm Ordinance Public Notice of Amendment to New Shoreham General Ordinances Chapter 5 Fire Prevention and Protection New Article IV Fire Alarm Ordinance It is ordained by the Town Council of the Town of New Shoreham

More information

A. Hydraulic calculations shall be prepared in accordance with Chapter 23 of NFPA 13 with the following exceptions:

A. Hydraulic calculations shall be prepared in accordance with Chapter 23 of NFPA 13 with the following exceptions: SECTION 21 13 13 WET-PIPE FIRE SPRINKLER SYSTEM PART 1 - GENERAL 1.1 RELATED DOCUMENTS: A. The Conditions of the Contract and applicable requirements of Division 1, "General Requirements", and Section

More information

FIRE AND ENVIRONMENTAL SAFETY INSPECTOR II

FIRE AND ENVIRONMENTAL SAFETY INSPECTOR II CITY OF ROSEVILLE FIRE AND ENVIRONMENTAL SAFETY INSPECTOR I FIRE AND ENVIRONMENTAL SAFETY INSPECTOR II DEFINITION To perform technical and professional duties in the fields of fire and life safety inspection,

More information

Can You Hear Me Now?

Can You Hear Me Now? Fire Alarm Notebook Can You Hear Me Now? By Dean K. Wilson, P.E., FSFPE, C.F.P.S. I am the lead fire alarm system technician at our very extensive multi-building public warehouse complex over 2.5 million

More information