Building Research Note

Size: px
Start display at page:

Download "Building Research Note"

Transcription

1 Ser THl R92 no, 2h3 em 2 BDC National Research Conseil national 19 Council Canada de recherches Canada Institute for lnstitut de Research in recherche en Construction construction Building Research Note Measurements and Observations Made during Residential Sprinkler Demonstrations BRN 243

2 MEASUREMENTS AND OBSERVATIONS MADE DURING RESIDENTIAL SPRINKLER DEMONSTRATIONS *? by I. Oleszkiewicz Fire Research Section Institute for Research in Construction BRN 243 ISSN Ottawa, April Research Council Canada Serving the construction industry IRC Au service de la construction

3 ABSTRACT Measurements and observations made during demonstration tests of resideri~ial sprinkler systems, conducted in Charlottetown, Prince Edward Island,',in June 1984, are presented. '+2 Ce document fait 6tat des mesures et observations faites lors dpessais de d6monstration d'extinct~urs automatiqyes pour habitations men& en juin Charlottetown, 3 1'IleduPrinceEdouard. INTRODUCTION Statistics show that most fire fatalities occur in residential fires. The low ceiling heights and the small size of compartments in the typical home cause the hot fire gases to descend quickly to below eye level. An obvious solution to the problem is the early detection and suppression of the fire. The use of smoke detectors has decreased the number of residential fire fatalities, but detection alone is not sufficient. It cannot save lives if the occupants of the building are incapacitated due to age, disability or other factors. Traditional sprinklers have proven unsuccessful, due to their slow response time, in providing life safety for the occupants of the compartment of fire origin. Fast response is important, but so is the capability of the sprinkler to discharge a sufficient quantity of water in the right spray pattern from an ordinary household water supply. A new type of sprinkler, referred to as the residential sprinkler, has been developed to meet the needs of residential buildings. The Institute for Research in Construction, National Research Council o$ Canada, agreed to participate in two demonstration tests of residential sprinkler systems in Charlottetown, P.E.I., in June The tests had been devised jointly by manufacturers of fire protection equipment and by fire protection authorities. The objectives of the demonstration tests were: i) to show the ability of residential sprinklers to extinguish a fire before conditions in the room of fire origin became untenable; ii) to demonstrate the suitability of plastic piping for use in residential sprinkler systems; iii) to demonstrate the operation of an "intelligent" fire alarm system. Although the tests were primarily for demonstration purposes, useful data were collected concerning the performance of residential sprinklers. TEST FACILITY The test facility consisted of two rooms built adjacent to the Fire Fighters Training Tower (Figure 1). The interiors of the rooms were

4 :?. o SPRINKLER 8 PRESSURE GAUGE 2 THERMOCOUPLE THERMOCOUPLE LOCATION ROOM NO. 1 1 AT THE SIDEWALL S PR I NKLER m ABOVE THE FLOOR m ABOVE THE FLOOR m BELOW THE CEILING 5 AT THE SIDEWALL SPRINKLER ROOM NO. 2 1 TO 4 AT THE PENDANT SPRINKLERS m ABOVE THE FLOOR m ABOVE THE FLOOR m BELOW THE CEl Ll NG m ABOVE THE FLOOR, 0.1 m FROM THE WALL Figure 1. Test setup

5 3 finished with gypsum board painted with latex paint; the floors were bare concrete. A c;losedcircuit TV with monitors was installed in the tower and a nearby t+aining centre. V SPRINKLER INSTALLATIONS Two types of sprinklers, both having a temperature rating of 60 C (140 F) were installed: horizontal sidewall residential sprinklers in Room 1, and pendant residential sprinklers in Room 2. Figure 1 shows the distribution of the sprinklers. Plastic piping of 25.4 mm (1 in.) nominal diameter, made from either chlorinated PVC (poly(viny1 chloride)) or Poly B (polybutylene), was used. The pipes were exposed. FIRE ALARM SYSTEM The fire alarm system consisted of 8 addressable ionizationtype smoke detectors in each room (giving a total of 16 detectors) with a microprocessorcontrolled central unit. The sensitivity of the detectors could be adjusted individually from the keyboard of the control unit. INSTRUMENTATION During the tests, the air temperature and CO level in the room, and the pressure and water flow rate in the sprinkler piping were measured. The vertical distribution of temperature was monitored by bare 'thermocouples fixed at 915 mrn (3 ft), and 1525 mm (5 ft) above the floor and 75 mm (3 in.) below the ceiling. Other thermocouples were located close to the sprinklers. The CO level was measured using a sampling set with an air pump and a Draeger device (chosen because of its portability). Air samples were taken 1525 mm (5 ft) above the floor. Water pressure was measured with a pressure gauge at a point just before the burn room. The flow rate and total quantity of water were measured using a Signet paddlewheel flowmeter/accumulator. The flowmeter and all the thermocouples were automatically read and recorded by a data logger. Other data, together with sprinkler activation times, were recorded manually. The smoke detectors were not monitored individually because of the limited scanning speed of the data logger. FIRE SCENARIOS Six trial and two demonstration burns, simulating fires in health care and hotel rooms, were carried out. The trial fires were conducted in order to establish proper scenarios for the demonstration tests.

6 4 To reduce the testing time, flaming fires were chosen. A wastepaper basket filled with crumpled newspaper was used as the source of fire. The flames issuing from the basket ignited a nearby piece of furniture (bed or The arrangement of furniture during the demonstration tests is shown in Figure 1: it is a reproduction of the arrangement used during Trial * RESULTS Trial Test 1 i n Room 1 and Trial Test 1 in Room 2 were conducted before the instrumentation was completely installed. Figures 2 to 7 show air temperature vs. time at the thermocouple locations during the two demonstration tests and the four trial tests for which instrumentation was available. Activation times for the sprinkler and the first smoke detector are indicated on the time axis. Trial Test 2, Room 1 (Figure 2) The fire was very small. The sprinkler at location 5 activated 48 seconds after ignition and extinguished the fire almost immediately. The air temperature remained low during the test. The CO level, however, reached 8000 ppm one minute after ignition. The water pressure was 290 kpa (42 psi) and the flow rate was 1.37 L/s (21.7 U.S. gpm). The first smoke detector activated 17 seconds after ignition. l ~ l ~ l ~ l ~ l ~ l ~ l ~ " 120 W C C v SPRINKLER v SMOKE DETECTOR 1 5 THERMOCOUPLE LOCATIONS v 2 v TIME, Figure 2. Air temperature vs. time; Trial Test 2, Room 2 s

7 Trial Test 3, Room 1 (Figure 3) The fire grew bigger and lasted longer than in the previous test. The sprinkler at location 5 activated 101 seconds after ignition. The gas temperature was higher than during the previow test, but not sufficiently high to cause flashover. The CO level remained low. The water pressure was 160 kpa (23 psi) and the flow rate was L/s (31.5 U.S. gpm). The first smoke detector activated 107 seconds after ignition. l ~ l [ ~ ~ Il I, I I l I I 1 l l i v SPRINKLER v SMOKE DETECTOR 1 5 THERMOCOUPLE LOCATIONS TIME, s Figure 3. Air temperature vs. time; Trial Test 3, Room 1 $rial Test 2, Room 2 (Figure 4) Because of the arrangement of the furnishings and their high combustibility, and the use of sprinklers with a temperature rating higher than that required, the fire was vigorous and gas temperatures were high. The sprinkler at location 3 activated 128 seconds after ignition and promptly extinguished the fire. The CO level was not recorded. The water pressure was 290 kpa (42 psi) and the flow rate was 1.4 L/s (22.2 U.S. gpm). The first smoke detector activated 20 seconds after ignition. Trial Test 3. Room 2 (Figure 5) The arrangement of the furnishings was modified. A highly combustible privacy curtain, used in the previous test, was not reinstalled. Sprinklers with a temperature rating of 60 C were used. The fire developed more slowly than during the previous test. Two sprinklers activated (locations 2 and 3) and suppressed the fire before the eyelevel gas temperature (thermocouple 6) reached 75OC. The sprinkler at location 2 activated 76 seconds after ignition, followed a few seconds later by the sprinkler at

8 ?v SPRINKLER r SMOKE DETECTOR 17 THERMOCOUPLE TIME, s Figure 4. Air temperature vs. time; Trial Test 2, Room v SPRINKLER 120 SMOKE DETECTOR THERMOCOUPLE TIME, s Figure 5. Air temperature vs. time; Trial Test 3, Room 2

9 location 3. The following CO levels were recorded: 0 pprn after 30 seconds, 0 pprn after 2 minutes, 500 pprn after 3 minutes, and 300 pprn after 4 minutes. The water pressure was 324 kpa (47 psi) and the flow rate was 1.57 L/s (24.8 U;S. gpm). The first smoke detector activated 30 seconds after ignition. X Demonstration Test, Room 1 (Figure 6) The fire development was similar to that during Trial Test 3 in Room 1 except for a slower start which was caused by a difference in the randomly arranged ignition source (wastepaper basket with crumpled paper). The sprinkler at location 5 activated 3 minutes after ignition. The following CO levels were recorded: 0 pprn after 1 minute, 150 pprn after 3 minutes, and 300 pprn after 4 minutes. The water pressure was 269 kpa (39 psi) and the flow rate was 1.63 L/s (26 U.S. gpm). The first smoke detector activated 34 seconds after ignition. Several people remained inside the room until the fire was extinguished. They reported no untenable conditions, although they experienced some discomfort due to smoke and water spray. They stressed that they did not feel hot, although the temperature reached lll C at the 1525 mm level (Figure 6, thermocouple 3). l ~ l ~ l ~ l ~ l ~ l ~ v SPRINKLER v SMOKE DETECTOR 1 5 THERMOCOUPLE LOCATIONS v v l 1 ~ ~ ~ TIME, s Figure 6. Air temperature vs. time; demonstration test, Room 1 Demonstration Test, Room 2 (Figure 7) The fire development was similar to that during Trial Test 3 in Room 2. Only one sprinkler activated (at location 3), 2 minutes after ignition. The following CO levels were recorded: 0 pprn after 1 minute, 200 pprn after

10 2.5 minutes, 400 ppm after 3.5 minutes, and 300 ppm after 5 minutes. The water pressure was 324 kpa (47 psi) and the flow rate was 1.6 L/s (254 U.S. gpm). The first smoke detector activated 19 seconds after ignition. u V SPRINKLER SMOKE DETECTOR 1 7 THERMOCOUPLE v TIME, s Figure 7. Air temperature vs. time; demonstration test, Room 2 SUMMARY The purpose of the tests was to demonstrate new sprinkler technology in action. The test conditions were chosen to be appropriate for demonstration purposes rather than to yield information for research. Nevertheless, it is considered desirable to report what was measured and observed as there is little published information on the early stage of fire development coupled with the dynamic response of residential sprinklers. The reports from people exposed to the fire environment in Room 1 indicate that the National Fire Protection Association tenability criterion for temperature, selected as 65OC (l), is conservative for short exposures. ACKNOWLEDGEMENTS These tests were carried out under the auspices of the International Association of Fire Chiefs. Participants in these tests included the Canadian Automatic Sprinkler Association, Canadian Fire Alarm Manufacturers Association, Bow Plastics Ltd., B.F. Goodrich Chemical Group and Grinnell Fire Protection Systems Co. Ltd. The author gratefully acknowledges the technical assistance provided by J.W. MacLaurin and R.C. Monette, who participated in the tests in

11 Charlottetown, and J.E. graphs. Berndt, who processed the data and prepared the 1. Cot6, Arthur E., "Field Test and Evaluation of Residential Sprinkler Systems: Part 11", Fire Technology, Vol. 20, No. 1, February 1984, p. 48.

How to Use Fire Risk Assessment Tools to Evaluate Performance Based Designs

How to Use Fire Risk Assessment Tools to Evaluate Performance Based Designs How to Use Fire Risk Assessment Tools to Evaluate Performance Based Designs 1 ABSTRACT Noureddine Benichou and Ahmed H. Kashef * Institute for Research in Construction National Research Council of Canada

More information

Fire Suppression Performance of Manually Applied CAF and Other Water Based System

Fire Suppression Performance of Manually Applied CAF and Other Water Based System Fire Suppression Performance of Manually Applied CAF and Other Water Based System Andrew Kim and George Crampton Fire Suppression Research and Applications A Technical Working Conference (SUPDET2012) Outline

More information

Sprinklers in Combustible Concealed Spaces

Sprinklers in Combustible Concealed Spaces Sprinklers in Combustible Concealed Spaces G.D. Lougheed and J.K. Richardson Fire Research Section Institute for Research in Construction National Research Council Canada Ottawa, Ontario SUMMARY NFPA 13

More information

ASSESSMENT OF FIRE BEHAVIOUR OF TIMBER PARTITION MATERIALS WITH A ROOM CALORIMETER

ASSESSMENT OF FIRE BEHAVIOUR OF TIMBER PARTITION MATERIALS WITH A ROOM CALORIMETER , Volume 9, Number 1, p.38-58, 2007 ASSESSMENT OF FIRE BEHAVIOUR OF TIMBER PARTITION MATERIALS WITH A ROOM CALORIMETER C.W. Leung and W.K. Chow Department of Building Services Engineering, The Hong Kong

More information

Indicative hoarding fire experiment. Prepared for: London Fire Brigade. 21 May 2014 Client report number

Indicative hoarding fire experiment. Prepared for: London Fire Brigade. 21 May 2014 Client report number Indicative hoarding fire experiment Prepared for: London Fire Brigade 21 May 2014 Client report number 292366 1 Hoarding fire demonstration Prepared on behalf of BRE Fire and Security by Name Dr Sung-Han

More information

Considerations in the Design of Smoke Management Systems for Atriums

Considerations in the Design of Smoke Management Systems for Atriums Construction Technology Update No. 48 Considerations in the Design of Smoke Management Systems for Atriums by G.D. Lougheed This Update discusses the use of an engineered approach to the design of smoke

More information

Real-scale dwelling fire tests with regard to tenability criteria

Real-scale dwelling fire tests with regard to tenability criteria Real-scale dwelling fire tests with regard to tenability criteria Eric GUILLAUME a,*, Franck DIDIEUX a, Aurélien THIRY b, Axel BELLIVIER b a: Laboratoire national de métrologie et d essais (LNE), 1 rue

More information

Explosion Protection of an Armoured Vehicle Crew Compartment with Water Mist. Andrew Kim and George Crampton

Explosion Protection of an Armoured Vehicle Crew Compartment with Water Mist. Andrew Kim and George Crampton Explosion Protection of an Armoured Vehicle Crew Compartment with Water Mist Andrew Kim and George Crampton Fire Research Program, National Research Council of Canada 1200 Montreal Road, Ottawa, Ontario,

More information

How design fires can be used in fire hazard analysis

How design fires can be used in fire hazard analysis How design fires can be used in fire hazard analysis Yung, D.T.; Bénichou, N. NRCC-44511 A version of this document is published in / Une version de ce document se trouve dans : Fire Technology, v. 38,

More information

Characterising the smoke produced from modern materials and evaluating smoke detectors

Characterising the smoke produced from modern materials and evaluating smoke detectors www.bre.co.uk Briefing Paper Characterising the smoke produced from modern materials and evaluating smoke detectors Raman Chagger 01 Contents Abstract 02 Introduction 02 Background 03 The current test

More information

Figure 1. Structure Used For the Simulations.

Figure 1. Structure Used For the Simulations. OVERVIEW: Vent, Enter, Search (VES) is one of the most talked about tactics in the fire service today. When used correctly, its positive impact can be measured by the lives it saves. The VES method is

More information

SCHULTE & ASSOCIATES Building Code Consultants 880D Forest Avenue Evanston, IL /

SCHULTE & ASSOCIATES Building Code Consultants 880D Forest Avenue Evanston, IL / SCHULTE & ASSOCIATES Building Code Consultants 880D Forest Avenue Evanston, IL 60202 fpeschulte@aol.com 847/866-7479 SPRINKLER PROTECTION BASICS: TYPES OF : SPRAY - standard response - quick response -

More information

NUMERICAL STUDIES ON BARE CABIN FIRES WITH OPERATION OF SMOKE EXTRACTION SYSTEM

NUMERICAL STUDIES ON BARE CABIN FIRES WITH OPERATION OF SMOKE EXTRACTION SYSTEM , Volume 11, Number 2, p.43-48, 2012 NUMERICAL STUDIES ON BARE CABIN FIRES WITH OPERATION OF SMOKE EXTRACTION SYSTEM Q. Kui Institute of Building Fire Research, China Academy of Building Research, Beijing,

More information

An experimental study of the impact of tunnel suppression on tunnel ventilation

An experimental study of the impact of tunnel suppression on tunnel ventilation An experimental study of the impact of tunnel suppression on tunnel ventilation Yoon J. Ko and George Hadjisophocleous Civil and Environmental Engineering, Carleton University 1125 Colonel By Drive, Ottawa,

More information

Intertek. REPORT NUMBER: SAT-005 ORIGINAL ISSUE DATE: October 29,2008 REVISED DATE: November 19, 2008

Intertek. REPORT NUMBER: SAT-005 ORIGINAL ISSUE DATE: October 29,2008 REVISED DATE: November 19, 2008 Intertek I 0:: o D.. W 0:: I en w I REPORT NUMBER: 3161466SAT-005 ORIGINAL ISSUE DATE: October 29,2008 REVISED DATE: EVALUATION CENTER Intertek Testing Services NA Inc. 16015 Shady Falls Rd. Elmendorf,

More information

ASSESSMENT OF TIMBER PARTITION MATERIALS WITH FIRE RETARDANTS WITH A ROOM CALORIMETER

ASSESSMENT OF TIMBER PARTITION MATERIALS WITH FIRE RETARDANTS WITH A ROOM CALORIMETER , Volume 6, Number 3, p.122-154, 2004 ASSESSMENT OF TIMBER PARTITION MATERIALS WITH FIRE RETARDANTS WITH A ROOM CALORIMETER C.W. Leung, W.K. Chow Department of Building Services Engineering, The Hong Kong

More information

RADIATION BLOCKAGE EFFECTS BY WATER CURTAIN

RADIATION BLOCKAGE EFFECTS BY WATER CURTAIN , Volume 6, Number 4, p.248-254, 04 RADIATION BLOCKAGE EFFECTS BY WATER CURTAIN C.L. Choi Department of Building Services Engineering, The Hong Kong Polytechnic University, Hong Kong, China ABSTRACT Water

More information

FIBERSHIELD EW NEW PRODUCT LOW RADIANT HEAT TRANSFER ( PARTIAL PARTIAL INSULATION ) FIRE CURTAINS. Supported by full scale fire test data

FIBERSHIELD EW NEW PRODUCT LOW RADIANT HEAT TRANSFER ( PARTIAL PARTIAL INSULATION ) FIRE CURTAINS. Supported by full scale fire test data LOW RADIANT HEAT TRANSFER ( PARTIAL PARTIAL INSULATION ) GENERAL Fibershield EW is a NEW and INNOVATIVE low radiation attenuation and partially insulating automatic fire curtain. It was developed to meet

More information

Residential Fire Sprinkler Systems

Residential Fire Sprinkler Systems Residential Fire Sprinkler Systems Life Safety and Fire Protection: 24/7 February 1, 2005 Oxford Township Fire Facts How many people die annually from fires? More than 4,000 Who are the victims? Children

More information

PERFORMANCE OF CLT ASSEMBLIES IN FIRE

PERFORMANCE OF CLT ASSEMBLIES IN FIRE PERFORMANCE OF CLT ASSEMBLIES IN FIRE Noureddine Benichou, Ph.D., National Research Council Canada Christian Dagenais, Eng., M.Sc., FPInnovations May 28, 2015 Background Mass timber, such as CLT, are generally

More information

How to know if a residential or domestic water mist system is performance compliant to BS 8458:2015?

How to know if a residential or domestic water mist system is performance compliant to BS 8458:2015? Plumis White Paper April 2017 How to know if a residential or domestic water mist system is performance compliant to BS 8458:2015? As with the introduction of every new formal product category through

More information

COSTCO, SAN FRANCISCO A PRESCRIPTIVE AND PERFORMANCE BASED ANALYSIS OF FIRE PROTECTION SYSTEMS AND DESIGN

COSTCO, SAN FRANCISCO A PRESCRIPTIVE AND PERFORMANCE BASED ANALYSIS OF FIRE PROTECTION SYSTEMS AND DESIGN COSTCO, SAN FRANCISCO A PRESCRIPTIVE AND PERFORMANCE BASED ANALYSIS OF FIRE PROTECTION SYSTEMS AND DESIGN Presented by Ian Levine June, 2016 Photo courtesy of Google Maps PRESENTATION OVERVIEW BUILDING

More information

NZS 4517:2010. New Zealand Standard. Fire sprinkler systems for houses. Superseding NZS 4517:2002 NZS 4517:2010

NZS 4517:2010. New Zealand Standard. Fire sprinkler systems for houses. Superseding NZS 4517:2002 NZS 4517:2010 New Zealand Standard Fire sprinkler systems for houses Superseding NZS 4517:2002 NZS 4517:2010 NZS 4517:2010 COMMITTEE REPRESENTATION This Standard was prepared under the supervision of the P 4517 Committee,

More information

Research on fire protection methods and a case study "Futurum"

Research on fire protection methods and a case study Futurum Available online at www.sciencedirect.com Procedia Engineering 40 (2012 ) 339 344 Steel Structures and Bridges 2012 Research on fire protection methods and a case study "Futurum" J. Outinen a *, J. Samec

More information

Anatomy of a Fire. Christopher Crivello, MSFPE, PE. Douglas Nadeau, MSFPE, PE, CFPS, LEED AP

Anatomy of a Fire. Christopher Crivello, MSFPE, PE. Douglas Nadeau, MSFPE, PE, CFPS, LEED AP Anatomy of a Fire Douglas Nadeau, MSFPE, PE, CFPS, LEED AP President of RAN Fire Protection Engineering, PC Vice President of truvue Inspection Technology Christopher Crivello, MSFPE, PE Fire Protection

More information

Test One: The Uncontrolled Compartment Fire

Test One: The Uncontrolled Compartment Fire The University of Edinburgh BRE Centre for Fire Safety Engineering One Day Symposium on The Dalmarnock Fire Tests: Experiments & Modelling Test One: The Uncontrolled Compartment Fire Cecilia Abecassis

More information

Case Study 1 Underground Car Park

Case Study 1 Underground Car Park Case Study 1 Underground Car Park Dorota Brzezińska 1, Janusz Paliszek 2, Piotr Smardz 2, Renata Ollesz 1, Karol Kaczor 2 1 Lodz University of Technology, GRID - Lodz, 2 INBEPO Wroclaw, Poland Building

More information

International Water Mist Conference, Istanbul October 22-23, 2014 The background and development of the guidelines in IMO Resolution A.

International Water Mist Conference, Istanbul October 22-23, 2014 The background and development of the guidelines in IMO Resolution A. International Water Mist Conference, Istanbul October 22-23, 2014 The background and development of the guidelines in IMO Resolution A.800(19) Magnus Arvidson SP Fire Research SP Technical Research Institute

More information

Potential Impact of New UL Fire Test Criteria

Potential Impact of New UL Fire Test Criteria Potential Impact of New UL Fire Test Criteria Thomas G. Cleary Fire Research Division National Institute of Standards and Technology March 7, 2014 Outline Background Recent History Task Group Progress

More information

The Science Behind Water Mist Protection of Typical Building Hazards

The Science Behind Water Mist Protection of Typical Building Hazards The Science Behind Water Mist Protection of Typical Building Hazards SUPDET 2014 Zachary Magnone, P.E. Zachary.Magnone@tycofp.com Presentation Goals What is water mist? How does it work? How is it tested

More information

Smoke Alarm Research at NIST

Smoke Alarm Research at NIST Smoke Alarm Research at NIST Thomas G. Cleary Fire Research Division National Institute of Standards and Technology Smoke Alarm Summit March 31, 2015 Outline Supporting ANSI/UL 217 268 Task Group on adding

More information

A Comparison of Carbon Monoxide Gas Sensing to Particle Smoke Detection in Residential Fire Scenarios

A Comparison of Carbon Monoxide Gas Sensing to Particle Smoke Detection in Residential Fire Scenarios A Comparison of Carbon Monoxide Gas Sensing to Particle Smoke Detection in Residential Fire Scenarios Thomas Cleary, Amy Mensch National Institute of Standards and Technology, Gaithersburg, MD, USA Abstract

More information

SECTION WET-PIPE SPRINKLER SYSTEMS EASY RISER CHECK VALVE

SECTION WET-PIPE SPRINKLER SYSTEMS EASY RISER CHECK VALVE SECTION 21 1313 WET-PIPE SPRINKLER SYSTEMS PART 1 GENERAL 1.01 SECTION INCLUDES A. Wet-pipe sprinkler system. B. System design, installation, and certification. C. Fire department connections. 1.02 RELATED

More information

Experimental Study to Evaluate Smoke Stratification and Layer Height in Highly Ventilated Compartments

Experimental Study to Evaluate Smoke Stratification and Layer Height in Highly Ventilated Compartments Experimental Study to Evaluate Smoke Stratification and Layer Height in Highly Ventilated Compartments Jason Huczek a, Marc Janssens a, Kentaro Onaka b, Stephen Turner c a SwRI, 6220 Culebra Road, San

More information

Case Study of Underground Car Park. Team Japan

Case Study of Underground Car Park. Team Japan 11th Conference on Performance Based Codes and Fire Safety Design Methods Case Study of Underground Car Park Team Japan We focused on the characteristics of the fire behavior of car fire. Car fire is not

More information

Performance of Smoke Detectors and Sprinklers in Residential and Health-Care Occupancies

Performance of Smoke Detectors and Sprinklers in Residential and Health-Care Occupancies Performance of Smoke Detectors and Sprinklers in Residential and Health-Care Occupancies James A. Milke, Ph.D., P.E., A.J. Campanella, Cathleen T. Childers and Brittany D. Wright Department of Fire Protection

More information

FIRE PREVENTION AND PROTECTION FACT SHEET

FIRE PREVENTION AND PROTECTION FACT SHEET Print FIRE PREVENTION AND PROTECTION FACT SHEET MODULE DESCRIPTION In this module, we ll cover the precautions to take to prevent fires and the steps to take in order to protect yourself if a fire occurs

More information

1. Revise and A to read as follows:

1. Revise and A to read as follows: NFPA 13D-2010 Standard for the Installation of Sprinkler Systems in One- and Two-Family Dwellings and Manufactured Homes TIA Log No.: 1028R Reference: 8.1.2, 8.1.3, A.8.1.2, and A.8.1.3 Comment Closing

More information

Artificial Trees and Fire Performance

Artificial Trees and Fire Performance 2017 NFPA Conference & Expo Artificial Trees and Fire Performance Presented by: Dwayne Sloan Manager, Principal Engineers Building Materials & Suppression UL LLC Learning Objectives Frame the Fire Problem

More information

CBD-11. Fire and the design of buildings

CBD-11. Fire and the design of buildings Page 1 of 5 CBD-11. Fire and the design of buildings Originally published November 1960. J. H. McGuire Fire is one of the major hazards to life and property in buildings. Regulations in respect of fire

More information

Results from a Full-Scale Smoke Alarm Sensitivity Study

Results from a Full-Scale Smoke Alarm Sensitivity Study Results from a Full-Scale Smoke Alarm Sensitivity Study Thomas Cleary Building and Fire Research Laboratory National Institute of Standards and Technology Gaithersburg, MD (301) 975-6858 thomas.cleary@nist.gov

More information

Water-mist systems in mass-production industries: A successful application to a tissue-converting plant

Water-mist systems in mass-production industries: A successful application to a tissue-converting plant Water-mist systems in mass-production industries: A successful application to a tissue-converting plant Paolo E. Santangelo a, Paolo Tartarini a, Massimiliano Bettati b, Luca Tarozzi b, Silvano Pane c

More information

( )

( ) Course Title: Fire Dynamics (3087) Course Number: FST - 3087 Course Credit Hours: (3) Three Semester Hours Instructor Information: Bernard W. Becker, III, MS (937-751-7371) ccfdchiefbecker@yahoo.com Textbook:

More information

FULL-SCALE FIRE TESTS OF A TWO-STORY CROSS-LAMINATED TIMBER STRUCTURE

FULL-SCALE FIRE TESTS OF A TWO-STORY CROSS-LAMINATED TIMBER STRUCTURE FULL-SCALE FIRE TESTS OF A TWO-STORY CROSS-LAMINATED TIMBER STRUCTURE Laura E. Hasburgh 1, Samuel L. Zelinka 1, Keith J. Bourne 1, David R. Tucholski 2, Jason P. Ouellette 2 ABSTRACT: There is a current

More information

RESULTS FROM HOUSE APPLIANCE SAFETY AND DEPRESSURIZATION TESTS CONDUCTED ON SINGLE FAMILY HOUSES UNDERGOING SOUND INSULATION

RESULTS FROM HOUSE APPLIANCE SAFETY AND DEPRESSURIZATION TESTS CONDUCTED ON SINGLE FAMILY HOUSES UNDERGOING SOUND INSULATION RESULTS FROM HOUSE APPLIANCE SAFETY AND DEPRESSURIZATION TESTS CONDUCTED ON SINGLE FAMILY HOUSES UNDERGOING SOUND INSULATION DL Bohac * Center for Energy and Environment, Minneapolis, MN USA ABSTRACT Extensive

More information

Date and Time of Incident. Jan 28, Breakout at 00:55 (approx) Detected at 00:55 Notified by a call to the police station Extinguished by 01:50

Date and Time of Incident. Jan 28, Breakout at 00:55 (approx) Detected at 00:55 Notified by a call to the police station Extinguished by 01:50 Building Name Address Use (as per FSA Annexed Table 1) Date and Time of Incident Structure and Stories Area Extent of Damage (Damaged Area/ Total Area) No. of Casualties Nodaya Kyoryuan Inn 741-1 Suzenji,

More information

Fire Protection System and Life Safety Evaluation of Building X. Anthony W. Sublett

Fire Protection System and Life Safety Evaluation of Building X. Anthony W. Sublett Fire Protection System and Life Safety Evaluation of Building X Presented by Anthony W. Sublett Culminating Project Master of Science in Fire Protection Engineering California Polytechnic State University

More information

6B-2 6th Asia-Oceania Symposium on Fire Science and Technology 17-20, March, 2004, Daegu, Korea

6B-2 6th Asia-Oceania Symposium on Fire Science and Technology 17-20, March, 2004, Daegu, Korea 6B-2 6th Asia-Oceania Symposium on Fire Science and Technology 17-20, March, 2004, Daegu, Korea CONDUCTING A FULL-SCALE EXPERIMENT ON A RAIL PASSENGER CAR ABSTRACT N. White and V.P. Dowling CSIRO Fire

More information

Modeling a real backdraft incident fire

Modeling a real backdraft incident fire Advanced Computational Methods in Heat Transfer IX 279 Modeling a real backdraft incident fire A. Tinaburri 1 & M. Mazzaro 2 1 Central Direction for Prevention and Technical Safety, Firefighters, Public

More information

Fire Safety Audit: Part B - Questionnaire (Questionnaire Devised By Mr.R.R.Nair) Yes No x

Fire Safety Audit: Part B - Questionnaire (Questionnaire Devised By Mr.R.R.Nair) Yes No x Fire Safety Audit: Part B - Questionnaire (Questionnaire Devised By Mr.R.R.Nair) Yes No x Name & Address of the Society IDENTIFY PEOPLE AT RISK 01 Have you identified who is at risk? 02 Have you identified

More information

Copyright 2018 American Wood Council 1

Copyright 2018 American Wood Council 1 Fire Tests in Support of Tall Mass Timber Buildings DES603 Sam Francis Senior Director, National Programs American Wood Council Jason Smart, P.E. Manager, Engineering Technology American Wood Council The

More information

Measurements Conducted Heat release rate (HRR) was measured in all tests. HRR measurements were conducted under the 3 m by 3 m calorimeter

Measurements Conducted Heat release rate (HRR) was measured in all tests. HRR measurements were conducted under the 3 m by 3 m calorimeter Table A-1. Tests Conducted and Ambient Conditions at Beginning of Each Test Notes: PAL stands for pallet and CRA ( Community Risk Assessment ) is the designator for the configuration of pallets burned

More information

FIRE RESCUE NSW RESEARCH PROJECT FOR SPRINKLERS IN BUILDINGS UNDER 25 METRES IN HEIGHT

FIRE RESCUE NSW RESEARCH PROJECT FOR SPRINKLERS IN BUILDINGS UNDER 25 METRES IN HEIGHT FIRE RESCUE NSW RESEARCH PROJECT FOR SPRINKLERS IN BUILDINGS UNDER 25 METRES IN HEIGHT John Clampett & Morgan Cook (Churchill Fellow 2012) Consultant & Team Leader Fire Research John Clampett Consulting

More information

The Theory and Practice of Variable Orifice in Automatic Sprinkler Systems

The Theory and Practice of Variable Orifice in Automatic Sprinkler Systems The Theory and Practice of Variable Orifice in Automatic Sprinkler Systems Abstract In the industry of Fire Protection a large number of Automatic Fire Sprinklers has been developed trying to cover all

More information

Construction Innovation Center Building 186

Construction Innovation Center Building 186 Construction Innovation Center Building 186 FPE 596 Professors Presented Culminating Experience in Fire Protection Engineering Christopher Pascual & Frederick W. Mowrer Christopher Torres Objective / Overview

More information

Occupant Tenability in Single Family Homes: Part I Impact of Structure Type, Fire Location and Interior Doors Prior to Fire Department Arrival

Occupant Tenability in Single Family Homes: Part I Impact of Structure Type, Fire Location and Interior Doors Prior to Fire Department Arrival Fire Technology, 53, 1589 1610, 2017 Ó 2017 The Author(s). This article is published with open access at Springerlink.com Manufactured in The United States DOI: 10.1007/s10694-017-0651-5 Occupant Tenability

More information

Fire Scenario Influence of Material of Boundary Condition on Results

Fire Scenario Influence of Material of Boundary Condition on Results Fire Scenario Influence of Material of Boundary Condition on Results HUGHES ASSOCIATES EUROPE, srl FIRE SCIENCE & ENGINEERING Luciano Nigro Andrea Ferrari Elisabetta Filippo Hughes Associates Europe srl

More information

ZONE MODEL VERIFICATION BY ELECTRIC HEATER

ZONE MODEL VERIFICATION BY ELECTRIC HEATER , Volume 6, Number 4, p.284-290, 2004 ZONE MODEL VERIFICATION BY ELECTRIC HEATER Y.T. Chan Department of Building Services Engineering, The Hong Kong Polytechnic University, Hong Kong, China ABSTRACT Selecting

More information

COST-EFFECTIVE FIRE-SAFETY RETROFITS FOR CANADIAN GOVERNMENT OFFICE BUILDINGS

COST-EFFECTIVE FIRE-SAFETY RETROFITS FOR CANADIAN GOVERNMENT OFFICE BUILDINGS , Volume 1, Number 3, p.123-128, 1999 COST-EFFECTIVE FIRE-SAFETY RETROFITS FOR CANADIAN GOVERNMENT OFFICE BUILDINGS D. Yung and G.V. Hadjisophocleous Fire Risk Management Program, Institute for Research

More information

1.0 INTRODUCTION. Shaw Industries Group 2 SwRI Project No c

1.0 INTRODUCTION. Shaw Industries Group 2 SwRI Project No c 1.0 INTRODUCTION This report presents the results of a fire performance evaluation in accordance with the 2011 Edition of National Fire Protection Association (NFPA) Standard 265, Standard Methods of Fire

More information

Large-scale fire test for interior materials of the Korean high speed train

Large-scale fire test for interior materials of the Korean high speed train Copyright 2012 Tech Science Press SL, vol.7, no.1, pp.13-18, 2012 Large-scale fire test for interior materials of the Korean high speed train W.H. Park 1, D.H. Lee 1, W.S. Jung 1 Abstract: A large-scale

More information

The Swedish National Board of Housing, Building and Planning s general recommendations on the analytical design of a building s fire protection, BBRAD

The Swedish National Board of Housing, Building and Planning s general recommendations on the analytical design of a building s fire protection, BBRAD The Swedish National Board of Housing, Building and Planning s general recommendations on the analytical design of a building s fire protection, BBRAD BFS 2011:27 with amendments up to BFS 2013:12 The

More information

FIRE SAFETY AND THE NATIONAL DISABILITY INSURANCE SCHEME

FIRE SAFETY AND THE NATIONAL DISABILITY INSURANCE SCHEME FIRE SAFETY AND THE NATIONAL DISABILITY INSURANCE SCHEME Hank Van Ravenstein and Dr Ian Bennetts OVERVIEW OF PRESENTATION Regulatory Framework What is the NDIS? Rationale Duty of Care Capital Development

More information

HOME FIRE SPRINKLER SYSTEMS. the future of fire safety here today

HOME FIRE SPRINKLER SYSTEMS. the future of fire safety here today HOME FIRE SPRINKLER SYSTEMS the future of fire safety here today UNDERSTANDING FIRE SPRINKLER PROTECTION FOR HOMES Fire kills more people in the United States annually than all natural disasters combined.

More information

Review of Residential Fire Sprinkler Systems for One- and Two-Family Dwellings

Review of Residential Fire Sprinkler Systems for One- and Two-Family Dwellings Review of Residential Fire Sprinkler Systems for One- and Two-Family Dwellings Reprinted with permission from NFPA 13D Installation of Sprinkler Systems in One- and two-family Dwellings and Manufactured

More information

Analysis of Two Typical Barriers to Fire Spread. Assignment #1. Prepared by STUDENT NAME. For Professor XXXXXXXXXXX

Analysis of Two Typical Barriers to Fire Spread. Assignment #1. Prepared by STUDENT NAME. For Professor XXXXXXXXXXX Analysis of Two Typical Barriers to Fire Spread Assignment #1 Prepared by STUDENT NAME For Professor XXXXXXXXXXX FPE 570 Building Firesafety 1 Worcester Polytechnic Institute DATE Barriers 1 Contents STRUCTURE....2

More information

DOMESTIC SMOKE ALARMS AND SPRINKLERS. Introduction. Materials and methods. Frank SWANN 1. Legislative impact. Review article

DOMESTIC SMOKE ALARMS AND SPRINKLERS. Introduction. Materials and methods. Frank SWANN 1. Legislative impact. Review article DOMESTIC SMOKE ALARMS AND SPRINKLERS Frank SWANN 1 Abstract: Key words: Making further inroads into the reduction of fire deaths and injuries in the home is a clear ambition of the UK Chief Fire Officers

More information

Sprinkler systems. A presentation for fire brigade staff

Sprinkler systems. A presentation for fire brigade staff Sprinkler systems A presentation for fire brigade staff Sprinkler systems Content Sprinkler system benefits Operation by fire brigade FAQ System description Basic system design Sprinkler systems In this

More information

Culminating Project. Fire Protection and Life Safety Engineering Analysis. Cal Poly. Center for Science and Mathematics. Fire Protection Engineering

Culminating Project. Fire Protection and Life Safety Engineering Analysis. Cal Poly. Center for Science and Mathematics. Fire Protection Engineering Culminating Project Fire Protection and Life Safety Engineering Analysis Fire Protection Engineering California Polytechnic State University Center for Science and Mathematics Cal Poly San Luis Obispo,

More information

Objective 1: Describe fire alarm systems.

Objective 1: Describe fire alarm systems. Chapter 20 Test Name: Date: Directions: Write the correct letter on the blank before each question. Objective 1: Describe fire alarm systems. 1. The purpose of a fire alarm system is to: (1178) A. prevent

More information

Modelling Concepts for the Risk-cost Assessment Model FIRECAMTM and its Application to a Canadian Government Office Building

Modelling Concepts for the Risk-cost Assessment Model FIRECAMTM and its Application to a Canadian Government Office Building Modelling Concepts for the Risk-cost Assessment Model FIRECAMTM and its Application to a Canadian Government Office Building D. YUNG, G.V. HADJISOPHOCLEOUS and G. PROULX National Fire Laboratory Institute

More information

SIMULATION OF A COMPARTMENT FLASHOVER FIRE USING HAND CALCULATIONS, ZONE MODELS AND A FIELD MODEL

SIMULATION OF A COMPARTMENT FLASHOVER FIRE USING HAND CALCULATIONS, ZONE MODELS AND A FIELD MODEL Reference : Spearpoint M J, Mowrer F W, McGrattan K. Simulation of a single compartment flashover fire using hand calculations, zone models and a field model. Proc. 3 rd International Conference on Fire

More information

Hazardous Material Safety Program

Hazardous Material Safety Program Hazardous Material Safety Program Lithium Battery History and Testing Presented By: Date: Discussion Topics Challenges for mitigating lithium battery risks as technology advances What do we know from research

More information

Tunnel Fire Dynamics and Evacuation Simulations

Tunnel Fire Dynamics and Evacuation Simulations Tunnel Fire Dynamics and Evacuation Simulations James Priest, PhD & James Niehoff DGS-SEE Seminar on Fire Protection for Physics Research Facilities 7 & 8 October 2015 Introduction (Background) Presentation

More information

Recent BRANZFIRE enhancements and validation

Recent BRANZFIRE enhancements and validation Recent BRANZFIRE enhancements and validation Michael Spearpoint University of Canterbury Summary BRANZFIRE is a multi-compartment fire zone model that has been under development since 1996 predominately

More information

Sprinkler Permit Applications

Sprinkler Permit Applications REQUIREMENTS FOR NFPA 13 SYSTEM Building Inspections Sprinkler Permit Applications A complete application for a Sprinkler Permit will comply with the requirements of Chapter 8 of NFPA 13. Hydraulic calculations

More information

Fire Extinguisher Use. Fire Extinguisher Review. and Fire Safety

Fire Extinguisher Use. Fire Extinguisher Review. and Fire Safety Fire Extinguisher Use Fire Extinguisher Review and Fire Safety Topics to be discussed Fire Safety Fire Extinguisher Use Inspections and Maintenance Simulator Training Fire Safety The ABC s of Fire In order

More information

Report from the Division for Investigation of Maritime Accidents

Report from the Division for Investigation of Maritime Accidents Report from the Division for Investigation of Maritime Accidents Engine room fire MAERSK MASTER Factual information MAERSK MASTER, OXEI2, IMO No. 8409379 is an anchor handling supply tug of 3949 BT. The

More information

Comment on Hawker Stall Fires

Comment on Hawker Stall Fires Comment on Hawker Stall Fires Started: 28 April 2013 Revised: 26 December 2013 In-depth version: 3 May 2014 Final: 16 June 2014 W.K. Chow, JP FHKEng Fellow Elected, Hong Kong Academy of Engineering Sciences

More information

A DESCRIPTION OF THE PROBABILISTIC AND DETERMINISTIC MODELLING USED IN FIRECAM

A DESCRIPTION OF THE PROBABILISTIC AND DETERMINISTIC MODELLING USED IN FIRECAM , Volume 1, Number 1, p.18-26, 1999 A DESCRIPTION OF THE PROBABILISTIC AND DETERMINISTIC MODELLING USED IN FIRECAM D. Yung, G.V. Hadjisophocleous and G. Proulx Fire Risk Management Program, National Research

More information

Lamorinda CERT - Unit 2 09/15/2016

Lamorinda CERT - Unit 2 09/15/2016 Contra Costa County CERT Program Unit 2 Fire Safety Released: 15 September 2016 Community Emergency Response Team Personal safety is ALWAYS the number one priority Work as a team Wear personal protective

More information

WATER MIST FIRE PROTECTION SYSTEMS FOR INDUSTRIAL CABLE TUNNELS AND TURBINE HALLS

WATER MIST FIRE PROTECTION SYSTEMS FOR INDUSTRIAL CABLE TUNNELS AND TURBINE HALLS WATER MIST FIRE PROTECTION SYSTEMS FOR INDUSTRIAL CABLE TUNNELS AND TURBINE HALLS Jukka Vaari 1, Amit Lior 2 1 2 VTT Technical Research Centre of Finland, Espoo, Finland Marioff Corporation Oy, Vantaa,

More information

DEPARTMENTAL GUIDELINES CHAPTER 6 TACTICAL OPERATIONS

DEPARTMENTAL GUIDELINES CHAPTER 6 TACTICAL OPERATIONS Section 400.000 Suppression Systems The purpose of this guide is to assist the Incident Commander (IC), Fire Officers and Firefighters with the planning of effective operations for supporting water-based

More information

ARC MAPPING Things to Consider

ARC MAPPING Things to Consider ARC MAPPING By David M. Wheeler, IAAI-CFI, CFEI, CFII Featured in Fire & Arson Investigator, July 2015 Volume 1, Issue 1 Submit your assignment: Call: (800) 675-8500 Email: services@nefco.net Online: www.nefco.net

More information

Copy of article submitted to Fire Safety Engineering for publication January/February 2009

Copy of article submitted to Fire Safety Engineering for publication January/February 2009 Copy of article submitted to Fire Safety Engineering for publication January/February 2009 Metal faced sandwich panels with plastic foam cores - a challenge to fire safety by Gordon Cooke Confusion, misleading

More information

A sprinkler operates automatically when the heat-actuated element is heated to, or above, its thermal rating.

A sprinkler operates automatically when the heat-actuated element is heated to, or above, its thermal rating. Control / Residential / Suppression Mode Sprinklers Automatic sprinkler protection is recommended for industrial and other buildings having combustible construction or combustible occupancies. There are

More information

ICC CODE CORNER 2012 IFC Code & Commentary

ICC CODE CORNER 2012 IFC Code & Commentary SECTION 910 SMOKE AND HEAT VENTS 910.1 General. Where required by this code or otherwise installed, smoke and heat vents or mechanical smoke exhaust systems and draft curtains shall conform to the requirements

More information

J. R. Qualey III, L. Desmarais, J. Pratt Simplex Time Recorder Co., 100 Simplex Drive, Westminster, MA 01441

J. R. Qualey III, L. Desmarais, J. Pratt Simplex Time Recorder Co., 100 Simplex Drive, Westminster, MA 01441 J. R. Qualey III, L. Desmarais, J. Pratt Simplex Time Recorder Co., 100 Simplex Drive, Westminster, MA 01441 Response-Time Comparisons of Ionization and Photoelectric/Heat Detectors 1. Introduction Despite

More information

Vaults 5/03/2015. Introduction. Vault Types. Stand alone building Free standing structure VAULTS

Vaults 5/03/2015. Introduction. Vault Types. Stand alone building Free standing structure VAULTS Protect your Media Vault Protect your Assets Fire Protection Services Vaults Presented by Peter Glodic Introduction Vault Types VAULTS Vault Types Vault Construction Media Types Fire Types Extinguishing

More information

MECKLENBURG COUNTY FIRE MARSHAL S OFFICE

MECKLENBURG COUNTY FIRE MARSHAL S OFFICE Effective Date: 11/01/02 Purpose: MECKLENBURG COUNTY To establish a set of guidelines for performance testing of all newly installed or upgraded fire alarm systems in order to ensure that all devices and

More information

HOME FIRE SPRINKLER SYSTEMS. fire safety. the future of. here today

HOME FIRE SPRINKLER SYSTEMS. fire safety. the future of. here today HOME FIRE SPRINKLER SYSTEMS the future of HFSC-FutureBro-17.indd 1 fire safety here today UNDERSTANDING FIRE SPRINKLER PROTECTION FOR HOMES Fire kills more people in the United States annually than all

More information

Smoke and Heat Detector Performance: Field Demonstration Test Results. Distributed compliments -.

Smoke and Heat Detector Performance: Field Demonstration Test Results. Distributed compliments -. 'IRE JOURNAL _- January 1984 Smoke and Heat Detector Performance: Field Demonstration Test Results Distributed compliments of -. Reprinted from the January 1984 Fire Journal@ (Vol. 78, No. 1). Copyright@

More information

This document is a preview generated by EVS

This document is a preview generated by EVS TECHNICAL REPORT ISO/TR 15657 First edition 2013-06-15 Fire resistance tests Guidelines for computational structural fire design Essais de résistance au feu Lignes directrices sur la conception statistique

More information

Available online at ScienceDirect. Procedia Engineering 84 (2014 )

Available online at  ScienceDirect. Procedia Engineering 84 (2014 ) Available online at www.sciencedirect.com ScienceDirect Procedia Engineering 84 (2014 ) 553 557 2014ISSST, 2014 International Symposium on Safety Science and Technology Research on fire endurance of tempered

More information

An Analysis of Compartment Fire and Induced Smoke Movement in Adjacent Corridor

An Analysis of Compartment Fire and Induced Smoke Movement in Adjacent Corridor 2C-1 6th Asia-Oceania Symposium on Fire Science and Technology 17-20, March, 2004, Daegu, Korea An Analysis of Compartment Fire and Induced Smoke Movement in Adjacent Corridor Soo-Young Kim *, Eung-Sik

More information

American Society of Safety Engineers Professional Development Conference June 9-12, Fire Protection. Stephen J.

American Society of Safety Engineers Professional Development Conference June 9-12, Fire Protection. Stephen J. American Society of Safety Engineers Professional Development Conference June 9-12, 2008 Session No. 101F Fire Protection Stephen J. Musur CSP, CFPS Chubb Group of Insurance Companies June 12, 2008 1 Fundamentals

More information

Chapter 12 HOT WORK OPERATIONS. Purpose:

Chapter 12 HOT WORK OPERATIONS. Purpose: Chapter 12 Hot Work Operations Chapter 12 HOT WORK OPERATIONS Purpose: To provide written procedures to prevent the outbreak of fire, fire alarm activations, and smoke and odor migration in buildings resulting

More information

ESFR sprinkler system

ESFR sprinkler system Protection, prevention and environmental impact of fire in a tire storage SNCP experience feedback report ESFR sprinkler system Recommendations on fire protection in tyre storage facilities using ESFR

More information

Edward K. Budnick Hughes Associates, Inc. Wheaton, Maryland, U.S.A SUMMARY. that is entrained or otherwise mixed into the mass.

Edward K. Budnick Hughes Associates, Inc. Wheaton, Maryland, U.S.A SUMMARY. that is entrained or otherwise mixed into the mass. THE CAPABILITIES OF SMOKE CONTROL: FUNDAMENTALS AND ZONE SMOKE CONTROL John H. Klote Center for Fire Research National Institute of Standards and Technology Gaithersburg, Maryland, U.S.A. 20899 Edward

More information

SECTION DRY PIPE SPRINKLER SYSTEMS MODEL G SERIES DRY VALVE

SECTION DRY PIPE SPRINKLER SYSTEMS MODEL G SERIES DRY VALVE SECTION 21 1316 DRY PIPE SPRINKLER SYSTEMS MODEL G SERIES DRY VALVE PART 1 GENERAL 1.01 SECTION INCLUDES A. Dry-pipe sprinkler system. B. System design, installation, and certification. C. Fire department

More information