1 COSTCO, SAN FRANCISCO A PRESCRIPTIVE AND PERFORMANCE BASED ANALYSIS OF FIRE PROTECTION SYSTEMS AND DESIGN Presented by Ian Levine June, 2016 Photo courtesy of Google Maps
2 PRESENTATION OVERVIEW BUILDING DESCRIPTION STRUCTURAL DESIGN ALARM AND DETECTION EGRESS SPRINKLER SYSTEM ANALYSIS PERFORMANCE BASED ANALYSIS Photo credit to FrenchiesGigiandLola via youtube
3 BUILDING OVERVIEW Area: 122,000 sq.ft. Ceiling Height: 30 ft. Open floor plan Mixed Occupancy Construction Mercantile High Piled Storage Restaurant Kitchen, Bakery Office Concrete slab Exposed, noncombustible 3 PLAN NORTH TRUE NORTH Satellite Image courtesy of Google Maps Photo courtesy of Google Maps
4 A LOOK INSIDE Ventilation Steel deck Steel open web truss 4 Draft curtains Steel wide flange beam Rack storage Presented by Ian Levine Winter 2016 Wide flange steel column Concrete floor Wide aisles Photo courtesy of Google Maps Details shown typical of all Costco stores
5 STRUCTURAL DESIGN: What type of construction is allowed for this 122,000 sq.ft. structure? 5 Building Area: 122,000 sq.ft. Factor of increase based on frontage and automatic fire protection: 3.48 Maximum floor area per IBC 2012 Table 503: 35,000 sq.ft. Allowable construction type: I-A, I-B Presented by Ian Levine Winter 2016 California Building Code 2012 Photo courtesy of Google Maps
6 FIRE RESISTANCE RATINGS SUMMARY 6 IBC 2012 Tables 601 & 602; code & 716.5
7 WHAT IF?
8 DETECTION AND ALARM - OVERVIEW 7 Combination heat/ smoke detector Horn Strobe Notification Appliance Emergency Response Automatic fire sprinkler system Fire alarm control panel Backup power source Central monitoring station
9 ALARM AND DETECTION SYSTEM LAYOUT 8 PLAN NORTH TRUE NORTH
10 DETECTION RESPONSE ANALYSIS HEAT RELEASE RATES OF POTENTIAL FUEL LOADS 9 SOURCES: SFPE Handbook, 4 th ed; AIAA
11 HEAT DETECTOR RESPONSE DETACT Input Parameters 10 DETACT Results Response Time = 53s HRR = 1250 kw Note: Sprinkler response time = 95s Manual pull stations are required Is this layout cost effective?
12 NOTIFICATION 12 Required NA sound level: 40 db + 15 db = 55 db (15 dba above ambient) Requirement met using 99 dba alarm (6 dba Rule) Required strobe candela intensity per NFPA 72, Table (b) Note: EVACS is not recommended for this building
13 EGRESS CAPACITY 13 EGRESS CAPACITY > TOTAL OCCUPANT LOAD = OK!
14 EXIT PLAN 14 DEAD END: 98 ft PLAN NORTH Maximum travel distance: 225 ft (250 ft limit)
15 DECISION MAKING DURING EGRESS Recognition: Become aware of some danger. (smoke, alarm, seeing fire) 2. Validation: Gather more information (talk to others, look for smoke/fire) 3. Definition: Assess the threat, understand its seriousness 4. Evaluation: Decide how to respond (behaviors of others? Exit locations?) 5. Commitment: Take action 6. Reassessment: If necessary, take additional action. Stress levels rise. NFPA Fire Protection Handbook, ed. 20
16 EXPECTED EVACUATION TIME 16 Actual 1 story department store data
17 OCCUPANCY MAP 17
18 SYSTEM AREA MAP 18
19 SPRINKLER RESPONSE DETACT 11 TYCO ELO-231 Standard Spray Upright 11.2 k-factor ¾ orifice Response Time = 95s HRR = 4500 kw
20 PRESCRIPTIVE APPROACH SUMMARY STRUCTURAL: Fire resistance ratings requirements are satisfied Foams sprays, protective membranes, concrete wraps if additional protection is required A&D: Heat/Smoke detectors not required Manual pull stations o Occupancy > 500 Horn-strobes spaced to 68 ft o 6 db rule Heat detection by sprinklers o 53s vs. 95s response time EGRESS: Occupant load = 3,208 Egress capacity = 4,340 Total exit time = 4 min SPRINKLERS: 4 systems Extremely high demand Large orifice sprinklers System redesign to lower pressure and flow required from the source Pump with secondary water source if necessary
21 PERFORMANCE BASED DESIGN (PBD) Past vs. Future Specific to building, location, occupancy, and use NFPA 101 Life Safety Code (LSC) Goals and Objectives Prescriptive: o Protection of occupants not intimate with initial fire development o Improvement of survivability of occupants intimate with initial fire development o Added benefit to non-fire emergencies and crowd movement o Provide occupant protection during time to evacuate, relocate, or defend in place o Maintain structural integrity
22 PBD - OVERVIEW Meet prescriptive goals and objectives Limit exposure to instantaneous or cumulative untenable conditions (4 methods) Establish design specifications, inputs, assumptions, building safety features Determine design fire o o Realistic Challenging with respect to initial fire location, early rate of growth in fire severity, and/or smoke generation Design Fire Scenarios (8 Scenarios)
23 PBD FIRE SCENARIO Performance Criteria: Method 2, LSC o Complete building evacuation before hot gas layer extends less than 6 ft above floor (ASET > RSET?) Design Scenario: Scenario 2, LSC o Ultrafast-developing fire in the primary means of egress with interior doors open at the start of the fire o Focus on reduction in number of means of egress o Can all occupants escape before being exposed to smoke? Design Fire: electronics section in front of primary entrance and exit
24 PBD EGRESS: NFPA CALCULATION Increase by 100: confusion, searching for new exit Decrease to 0 due to inaccessibility Methodology and data from NFPA Handbook, 20 th edition
25 PBD EGRESS: PATHFINDER Calculation of movement time, not including premovement time 3208 occupants randomly spread throughout room Single doors: 36 Double doors: 72 Walls placed around tables, displays, and racks as obstructions All interior doors open OCCUPANTS FIRE BLOCKING EXIT t = 0s
26 PBD EGRESS: PATHFINDER Occupants moving toward doors Jams occurring at doors OCCUPANTS FIRE BLOCKING EXIT t = 30s
27 PBD EGRESS: PATHFINDER Most occupants have reached an escape route OCCUPANTS FIRE BLOCKING EXIT t = 60s
28 PBD EGRESS: PATHFINDER All occupants are experiencing jamming at doors Floor is completely cleared FIRE BLOCKING EXIT t = 120s
29 PBD EGRESS: PATHFINDER Very few occupants remain Maximum egress time: 191s t = 180s
30 PBD EGRESS: PATHFINDER RESULTS Occupants Occupants Inside Costco During Evacuation OBSERVATIONS Evacuation complete 3.2 min after begins Including 1.7 min maximum pre-movement time and 1.2 factor of safety, total time = 5.3 minutes Close agreement with NFPA method results (5.5 min) Note: linear evacuation rate supports egress time is limited by exit capacity of exits rather than travel time to exits Time (s)
31 PBD CFAST ENVIRONMENT & LAYOUT SINGLE-WIDE AND DOUBLE- WIDE EMERGENCY EXITS AROUND PERIMETER DETECTION DEVICES LOCATION OF FIRE MAIN ENTRY AND EXIT
32 DESIGN FIRE FIRE INPUT PARAMETERS P6 FIRE Full scale test 2 pallets of 12 boxed computer monitors 1m x 1m x 1m, side by side Soot and CO yields from polystyrene Ignition using kw line burner Modeled as t 2 fire reaching steady burning after 25s SFPE Handbook Table
33 PBD DETECTION AND ALARM 700 Heat Detector Temperatures in Design Fire - CFAST Temperature (⁰C) PEAK HRR REACHED STEADY STATE BURNING Hot Gas Heat Detector 1 Heat Detector 2 Heat Detector 3 Heat Detector HEAT DETECTOR ACTUATION = 5s Delay has negligible impact on 1.7 min pre-movement time Time (s)
34 DESIGN FIRE CFAST SIMULATION T = 0s T = 10s Initial temperature at 22 ⁰C Plume develops quickly Hot gas layer forms immediately
35 DESIGN FIRE CFAST SIMULATION T = 20s T = 30s Hot gas layer has reached ceiling Smoke already gathering at the ceiling Peak HRR is reached Temperature of hot gas layer rapidly increasing Interface height: 8.87m
36 DESIGN FIRE CFAST SIMULATION T = 60s T = 120s Temperature of hot gas layer continues to increase Interface height: 8.67m Smoke layer remains high Interface height: 8.3m Alarm and pre-movement time periods have passed. Occupants are now moving to exits. Some have exited already.
37 DESIGN FIRE CFAST SIMULATION T = 240s T = 300s Average lower layer temperature increasing (29 ⁰C) Interface height: 7.63m Interface height: 7.32m After 5 minutes, all occupants have reached an exit and are evacuating
38 DESIGN FIRE CFAST SIMULATION Hot Gas Layer Height and Layer Temperatures in Design Fire 1 - CFAST Simulation T = 330s Layer Height (m) Temperature (C) All occupants have exited building Final interface height: 7.18m Final lower layer temperature: 32.2 ⁰C Time (s) Layer Height Upper Layer Temperature Lower Layer Temperature
39 PERFORMANCE BASED DESIGN SUMMARY ASET > RSET: SUCCESS Extremely rapid heat and smoke production offset by massive volume of compartment Impact of smoke development unlikely to put occupants at risk Overall performance from life safety perspective: very good ASSUMPTIONS Sprinklers do not activate demonstrate safe egress is possible given worst case scenario Peak HRR maintained during steady burning period o Fuel source large enough to supply continuous burning for entire duration of building egress Occupants spread evenly to all available exits during egress o If gathering occurs near one exit with another exit available, occupants travel to available exit
40 CONCLUSION Prescriptive requirements for structural design, alarm and detection system, egress, and sprinkler system were considered. Structural, A&D, egress requirements were satisfied Recommendations made for sprinkler compliance (system redesign, pump, secondary water source) Performance-based analysis using Pathfinder egress modeling software and CFAST 7 with real-life (albeit, exaggerated) fire test data showed that the life safety criteria of ASET>RSET was satisfied with large margin, even with highly challenging design fire.
41 RECOMMENDATIONS Determine if pump is required for sprinkler system Examine impact of staff trained to help with egress Explore more complex modeling in Pathfinder: response times, seeking new exits, travel speeds Compare CFAST and FDS smoke height interface results Performance based design for protection of property and valuables FDS to model alternative suppression systems, examine cost impact
42 THANK YOU!
Will Clay Spring 2014
Will Clay Spring 2014 1. Project Overview 2. Prescriptive Requirements 3. Existing Requirements 4. Performance Evaluation 5. Conclusions RJA-Houston since 2010 Hired as FP/LS consultants by architect in
More informationBy: Russell Bainbridge March 18th, 2016 FPE 596
By: Russell Bainbridge March 18th, 2016 FPE 596 Egress Analysis and Design California Polytechnic State University's Engineering IV building Fire Detection, Alarm and Communication Systems A warehouse
More informationConstruction Warehouse. FPE 596 Culminating Experience In Fire Protection Engineering Final Project (Spring 2014) By Ben Johnson
Construction Warehouse FPE 596 Culminating Experience In Fire Protection Engineering Final Project (Spring 2014) By Ben Johnson 1 Statement of Disclaimer This project report is a result of a class assignment;
More informationFire Hazard Analysis of Technical Area 53 Building 1
Fire Hazard Analysis of Technical Area 53 Building 1 June 11, 2015 LA-UR-15-23589 Slide 1 Introduction Brett Noakes Los Alamos National Laboratory Los Alamos, New Mexico Slide 2 Outline Background of the
More informationCULMINATING EXPERIENCE IN FIRE PROTECTION ENGINEERING ANALYSIS OF COSTCO, SAN FRANCISCO
CALIFORNIA POLYTECHNIC STATE UNIVERSITY, SAN LUIS OBISPO CULMINATING EXPERIENCE IN FIRE PROTECTION ENGINEERING ANALYSIS OF COSTCO, SAN FRANCISCO PREPARED BY: IAN LEVINE 380 4 TH AVE SAN FRANCISCO, CA 94118
More informationCulminating Project. Fire Protection and Life Safety Engineering Analysis. Cal Poly. Center for Science and Mathematics. Fire Protection Engineering
Culminating Project Fire Protection and Life Safety Engineering Analysis Fire Protection Engineering California Polytechnic State University Center for Science and Mathematics Cal Poly San Luis Obispo,
More informationConstruction Innovation Center Building 186
Construction Innovation Center Building 186 FPE 596 Professors Presented Culminating Experience in Fire Protection Engineering Christopher Pascual & Frederick W. Mowrer Christopher Torres Objective / Overview
More informationHuman Factors - Egress Analysis for High Hazard Occupancies. Presented by: Michael J. Klemenz, PE, SFPE
Human Factors - Egress Analysis for High Hazard Occupancies Presented by: Michael J. Klemenz, PE, SFPE Group H Other SFPE presenters today discussed issues relevant to Group H This presentation addresses
More informationHow to Use Fire Risk Assessment Tools to Evaluate Performance Based Designs
How to Use Fire Risk Assessment Tools to Evaluate Performance Based Designs 1 ABSTRACT Noureddine Benichou and Ahmed H. Kashef * Institute for Research in Construction National Research Council of Canada
More informationFire Protection System and Life Safety Evaluation of Building X. Anthony W. Sublett
Fire Protection System and Life Safety Evaluation of Building X Presented by Anthony W. Sublett Culminating Project Master of Science in Fire Protection Engineering California Polytechnic State University
More informationPrescriptive and Performance Analysis of Cold Machine Shop FPE 596 Culminating Project
Prescriptive and Performance Analysis of Cold Machine Shop FPE 596 Culminating Project John Kline 8/8/2018 Statement of Disclaimer This project report is a result of a class assignment; it has been graded
More informationTunnel Fire Dynamics and Evacuation Simulations
Tunnel Fire Dynamics and Evacuation Simulations James Priest, PhD & James Niehoff DGS-SEE Seminar on Fire Protection for Physics Research Facilities 7 & 8 October 2015 Introduction (Background) Presentation
More informationStatue of Liberty: A Risk Analysis
Statue of Liberty: A Risk Analysis Bruce Campbell, FSFPE VP DOE Services National Park Service Agenda Overview of Project Scope Evaluation Steps Task 1 Code Analysis Task 2 Fire Modeling Task 3 Egress
More informationFIRE PROTECTION AND SAFETY ANALYSIS FOR AN OFFICE HIGH RISE BUILDING. Fabio Mazza June 2016
FIRE PROTECTION AND SAFETY ANALYSIS FOR AN OFFICE HIGH RISE BUILDING Fabio Mazza June 2016 Introduction Codes & Standards Building description Performance based design Prescriptive based design Structural
More informationCase Study 1 Underground Car Park
Case Study 1 Underground Car Park Dorota Brzezińska 1, Janusz Paliszek 2, Piotr Smardz 2, Renata Ollesz 1, Karol Kaczor 2 1 Lodz University of Technology, GRID - Lodz, 2 INBEPO Wroclaw, Poland Building
More informationVirtual Compartment: An Alternative Approach to Means of Egress Design in Airport Pedestrian Tunnel
Virtual : An Alternative Approach to Means of Egress Design in Airport Pedestrian Tunnel Xiaolei Chen, PhD California State University, Los Angeles, United States Ning (Frank) Wang, P.E. Jensen Hughes,
More informationSimple Equations for Predicting Smoke Filling Time in Fire Rooms with Irregular Ceilings
Fire Science and Technorogy Vol.24 No.4(2005) 165-178 165 Simple Equations for Predicting Smoke Filling Time in Fire Rooms with Irregular Ceilings Jun-ichi Yamaguchi 1, Takeyoshi Tanaka 2 1 Technical Research
More informationTable EXIT ACCESS TRAVEL DISTANCE a OCCUPANCY SYSTEM SYSTEM. A, E, F-1, I-1, M, b,d R, S-1. B c. F-2, S-2, U c
Table 1015.1 EXIT ACCESS TRAVEL DISTANCE a WITHOUT SPRINKLER WITH SPRINKLER OCCUPANCY SYSTEM SYSTEM A, E, F-1, I-1, M, 200 250 b,d R, S-1 B 200 300 c F-2, S-2, U 300 400 c No Change to Other Entries in
More informationFire Protection System and Life Safety Evaluation. Building X. Anthony W. Sublett. Culminating Project
Fire Protection System and Life Safety Evaluation Of Building X By Anthony W. Sublett Culminating Project Presented to the Faculty of the Graduate School of California Polytechnic State University in Partial
More informationFire Alarm System Fundamentals
Fire Alarm System Fundamentals Mircom is the largest and oldest privately owned fire alarm and life safety manufacturer in North America and 5th largest overall with 50 years of industry experience. Mircom
More informationSMOKE MANAGEMENT AND EGRESS ANALYSIS OF A SPORTS ARENA USING THE PERFORMANCE-BASED DESIGN
, Volume 4, Number 2, p.73-83, 2003 SMOKE MANAGEMENT AND EGRESS ANALYSIS OF A SPORTS ARENA USING THE PERFORMANCE-BASED DESIGN K.H. Yang and C.S. Yang Mechanical Engineering Department, National Sun Yat-Sen
More informationConsiderations in the Design of Smoke Management Systems for Atriums
Construction Technology Update No. 48 Considerations in the Design of Smoke Management Systems for Atriums by G.D. Lougheed This Update discusses the use of an engineered approach to the design of smoke
More informationToday's Topics & Sustainability Themes
2012 Chicago Symposium Fire Safety Design and Sustainable Buildings: Challenges and Opportunities Research Efforts in Fire Protection Engineering are Contributing to Sustainability Goals Dan O Connor,
More informationPerformance Based Design: Fire Alarm Visual Notification Appliances - Mathematical Guide. Ernesto Vega Jánica, EE, MSc, MEng
Performance Based Design: Fire Alarm Visual Notification Appliances - Mathematical Guide Ernesto Vega Jánica, EE, MSc, MEng 1 Performance Based Design Introduction Change on Philosophy 1999-2002-2007-2010-2013
More informationEVACUATION MODELING DEPENDENCE ON INPUT PARAMETERS
PROCEEDINGS, Fire and Evacuation Modeling Technical Conference 211 Baltimore, Maryland, August 15-16, 211 EVACUATION MODELING DEPENDENCE ON INPUT PARAMETERS Brian Salyers, Bevan Jones Holmes Fire 13 Sutter
More informationEl Reno Fire Department Fire Alarm Plan Review Worksheet
El Reno Fire Department Fire Alarm Plan Review Worksheet This Fire Alarm Plan Review Checklist is provided as a guide to assist with your Fire Alarm Plan Review Submittal requirements. Please contact us
More informationPotential Impact of New UL Fire Test Criteria
Potential Impact of New UL Fire Test Criteria Thomas G. Cleary Fire Research Division National Institute of Standards and Technology March 7, 2014 Outline Background Recent History Task Group Progress
More informationFire Safety Evaluation of Existing Manufactured Educational Building Covered by Section 423 of the Florida Building Code
Walker Engineering, Inc. 833 Rockingham Road Birmingham Alabama 35235-2625 205-854-0160 205-854-0160 (Fax) Fire Safety Evaluation of Existing Manufactured Educational Building Covered by Section 423 of
More informationCase Study of Underground Car Park. Team Japan
11th Conference on Performance Based Codes and Fire Safety Design Methods Case Study of Underground Car Park Team Japan We focused on the characteristics of the fire behavior of car fire. Car fire is not
More informationChallenges of Fire Protection Upgrades in Existing Libraries. Campus Fire Safety Forum
Challenges of Fire Protection Upgrades in Existing Libraries Campus Fire Safety Forum November 6, 2013 Presentation Overview Code Requirements Goals of Fire Protection Systems Life Safety Property Protection
More informationROBERT E. KENNEDY LIBRARY CAL POLY, SAN LUIS OBISPO FIRE PROTECTION ANALYSIS FPE CULMINATING PROJECT. Prepared For:
ROBERT E. KENNEDY LIBRARY Page i ROBERT E. KENNEDY LIBRARY CAL POLY, SAN LUIS OBISPO Prepared For: Dr. Frederick W. Mowrer & Dr. Christopher Pascual California Polytechnic State University College of Engineering
More informationFire and Life Safety Analysis
Fire and Life Safety Analysis Grant M. Brown Engineering Building #41 California Polytechnic State University, San Luis Obispo Daniel Gregory Blanchat June 12 th, 2014 1 B l a n c h a t 1 Statement of
More informationISO/TR TECHNICAL REPORT. Fire-safety engineering Technical information on methods for evaluating behaviour and movement of people
TECHNICAL REPORT ISO/TR 16738 First edition 2009-08-01 Fire-safety engineering Technical information on methods for evaluating behaviour and movement of people Ingénierie de la sécurité incendie Informations
More informationENFP 102: Engineering and Testing Creative Fire Safe Building Designs
ENFP 102: Engineering and Testing Creative Fire Safe Building Designs Instructors: Jim Milke, Ph.D., P.E., milke@umd.edu, Room 3104B JMP, 301-405-3995 Ken Isman, P.E., kisman@umd.edu, Room 3104L JMP, 301-405-
More informationAmerican Fire Sprinkler Association. An Introduction to the IBC and IFC
American Fire Sprinkler Association Presents An Introduction to the IBC and IFC October 13, 2005 Speaker Roland Huggins, P.E. Vice President of Engineering and Technical Services American Fire Sprinkler
More informationPrepared for: Professor Frederick W. Mowrer, PhD, P.E. Professor Christopher Pascual, PhD, P.E
Fire and Life Safety Analysis of The Production Facility (PF) - 870 Sandia National Laboratories, Albuquerque, New Mexico USA November 3, 2017 FPE596 Culminating Final Project Report By Nolan J. Baker,
More informationCase Study 2 Production and Storage. SFPE Polish Chapter Wojciech Węgrzyński, Grzegorz Krajewski Building Research Institute (ITB)
Case Study 2 Production and Storage SFPE Polish Chapter Wojciech Węgrzyński, Grzegorz Krajewski Building Research Institute (ITB) So What Are You We Going to Show You? A lot of tables, simplified methods
More informationFigure 1. Structure Used For the Simulations.
OVERVIEW: Vent, Enter, Search (VES) is one of the most talked about tactics in the fire service today. When used correctly, its positive impact can be measured by the lives it saves. The VES method is
More informationF I R E A L A R M R E C O G N I T I O N A N D E X I T C H O I C E I N U N D E R G R O U N D S TAT I O N S
F I R E A L A R M R E C O G N I T I O N A N D E X I T C H O I C E I N U N D E R G R O U N D S TAT I O N S 19 th January 2016 P R E S E N TAT I O N O V E R V I E W 1. Introduce fire alarm and its importance
More informationSmoke Alarm Research at NIST
Smoke Alarm Research at NIST Thomas G. Cleary Fire Research Division National Institute of Standards and Technology Smoke Alarm Summit March 31, 2015 Outline Supporting ANSI/UL 217 268 Task Group on adding
More informationBuilding Description Applicable Codes & Standards Prescriptive Requirements. Performance Based Design
June 15, 2017 Building Description Applicable Codes & Standards Prescriptive Requirements Structural Fire Protection Fire Sprinkler Fire Alarm Means of Egress Performance Based Design 2 3 Semiconductor
More informationLife Safety Report. XYZ Office Building. Denver Colorado. Prepared by: Keith Dix Monday, June 3, 2013
Life Safety Report XYZ Office Building Denver Colorado Figure 1 - XYZ Building West Side Prepared by: Keith Dix Monday, June 3, 2013 Culminating Project FPE 596 California Polytechnic University, San Luis
More informationA New Zealand Case Study Building Design 11 th International Conference on Performance
A New Zealand Case Study Building Design 11 th International Conference on Performance Prof Charles Fleischmann University of Canterbury Dept. Civil and Nat Res Eng. Christchurch, New Zealand Carol Caldwell
More informationand Sprinkler System in Resalat Tunnel of Tehran
CFD Simulation of Water Mist and Sprinkler System in Resalat Tunnel of Tehran Motivation Resalat tunnel is the first road tunnel in Tehran one of most crowded tunnels of Tehran my every day route, home
More informationFire Protection Engineering Culminating Project. Analysis of the Seattle Customer Delivery Center. Prepared by Cynthia Wernet
Fire Protection Engineering Culminating Project Analysis of the Seattle Customer Delivery Center Prepared by Cynthia Wernet California Polytechnic State University at San Luis Obispo June 9, 2016 Cynthia
More informationSmoke Layer Height and Heat Flow through a Door
Smoke Layer Height and Heat Flow through a Door 2018 Smoke Layer Height and Heat Flow through a Door In this tutorial you will simulate a growing fire in the corner of a 5m x 5m room. The room has a 1m
More informationZONE MODEL VERIFICATION BY ELECTRIC HEATER
, Volume 6, Number 4, p.284-290, 2004 ZONE MODEL VERIFICATION BY ELECTRIC HEATER Y.T. Chan Department of Building Services Engineering, The Hong Kong Polytechnic University, Hong Kong, China ABSTRACT Selecting
More information5B-3 6th Asia-Oceania Symposium on Fire Science and Technology 17-20, March, 2004, Daegu, Korea
5B-3 6th Asia-Oceania Symposium on Fire Science and Technology 17-20, March, 2004, Daegu, Korea PRACTICAL APPLICATIONS OF FIRE MODELING IN INDUSTRIAL APPLICATIONS By James M. Dewey, Advisor Risk Management
More informationFire Protection Analysis DCI Data Center Building
Fire Protection Analysis DCI Data Center Building California Polytechnic State University FPE 596 Culminating Experience in Fire Protection Engineering Bryan Hathaway M.S. Fire Protection Engineering -
More informationCHOOSING A FIRE VENTILATION STRATEGY FOR AN UNDERGROUND METRO STATION
- 165 - CHOOSING A FIRE VENTILATION STRATEGY FOR AN UNDERGROUND METRO STATION Wojciech Węgrzyński, Grzegorz Krajewski, Paweł Sulik Fire Research Department, Building Research Institute (ITB), Poland ABSTRACT
More informationA case study for integrated modelling of personnel evacuation with pool fire simulation to increase safety in design for offshore oil and gas projects
A case study for integrated modelling of personnel evacuation with pool fire simulation to increase safety Davood Afshari 1 Richard Welsh 2 Maryam Moghaddas 3 Sara Afsharikia 1 Amir Tavakoli 4 1 Lead Technical
More informationReleasing Systems. Rob Mennie Senior Consultant Gage-Babcock & Associates Ltd.
Releasing Systems Rob Mennie Senior Consultant Gage-Babcock & Associates Ltd. Releasing Systems What is a releasing system? System designed to detect a fire Causes release of an extinguishing system in
More informationA COMPARISON OF FIRE ALARM SYSTEM REQUIREMENTS IN THE US AND UK. James R. Lugar Jr., P.E. Rolf Jensen & Associates, Inc. SFPE 2012 Savannah, GA
A COMPARISON OF FIRE ALARM SYSTEM REQUIREMENTS IN THE US AND UK James R. Lugar Jr., P.E. Rolf Jensen & Associates, Inc. SFPE 2012 Savannah, GA Presentation Objective Compare fire alarm system design methods
More informationFIRE AND LIFE SAFETY ANALYSIS
FIRE AND LIFE SAFETY ANALYSIS AF Child Development Center Standard Design Judy Biddle Acknowledgements Special thanks for support and guidance over that past 2.5 years to: Professor Fred Mowrer Professor
More informationFire Protection as the Underpinning of Good Process Safety Programs
Fire Protection as the Underpinning of Good Process Safety Programs Key Words: fires; protection, fire; building Background James Milke, Ph.D., P.E., Professor and Chair Department of Fire Protection Engineering
More informationANALYSIS OF SMOKE MOVEMENT IN A BUILDING VIA ELEVATOR SHAFTS
ANALYSIS OF SMOKE MOVEMENT IN A BUILDING VIA ELEVATOR SHAFTS Prepared for Smoke Safety Council 6775 SW 111 th Avenue, Suite 10 Beaverton, OR 97008 Prepared by Jesse J. Beitel Alison J. Wakelin Craig L.
More informationFire Protection Engineering
Fire Protection Engineering FPE-596-FINAL REPORT NAME: MICHAEL STEWART DATE: JUNE 6, 2014 Contents Statement of Disclaimer... 5 Acknowledgement... 6 Building Overview & Description... 6 Building Construction
More informationWORKSHEET 2-1 THE MANITOBA RESIDENTIAL OCCUPANCY FIRE RISK INDEX FIRE SAFETY PARAMETER VALUES
1 WORKSHEET 2-1 THE MANITOBA RESIDENTIAL OCCUPANCY FIRE RISK INDEX FIRE SAFETY PARAMETER VALUES TABLE 2.1 CONSTRUCTION OF STRUCTURAL MEMBERS AND FLOOR AND ROOF (1) ASSEMBLIES (Applies to each fire zone)
More informationDEALING WITH FIRE SAFETY
DEALING WITH FIRE SAFETY Personal Care Homes And Assisted Living Facilities Presented by: Harold D. Hicks, P.E., FSFPE Fire Protection Engineer 1 Atlantic Code Consultants 2 Our Objectives Recognize the
More informationBuilding Fire Safety in New York City s Existing Office Buildings
www.goldmancopeland.com Building Fire Safety in New York City s Existing Office Buildings Daniel Colombini, PE, LEED AP Principal, Director of Plumbing/Fire Protection Director of Plumbing and Fire Protection
More information12F052 ADVANCED FLORIDA (MULTIPLE OCCUPANCY BUILDINGS)
11I058 ALLOWABLE HEEIGHTS AND AREAS IN THE INTERNATIONAL BUILDING CODE 12F052 ADVANCED FLORIDA BUILDING CODE (MULTIPLE OCCUPANCY BUILDINGS) www.codeaccess.net 2 AIA HSW LUH S AIA COURSE NUMBER 12F052 FLORIDA
More informationFire and smoke management in a uni-directional road tunnel for a congested traffic condition
Fire and smoke management in a uni-directional road tunnel for a congested traffic condition Y Liu, J Munro Parsons Brinckerhoff Australia B Dandie Thiess Pty Ltd., Australia ABSTRACT Emergency smoke ventilation
More informationMECKLENBURG COUNTY FIRE MARSHAL S OFFICE
Effective Date: 11/01/02 Purpose: MECKLENBURG COUNTY To establish a set of guidelines for performance testing of all newly installed or upgraded fire alarm systems in order to ensure that all devices and
More informationNatural Ventilation A Green Smoke Control Approach
Natural Ventilation A Green Smoke Control Approach Presented By: William Koffel, P.E., FSFPE Adam Graybeal, P.E. Authored by: Erik Anderson, P.E Koffel Associates Background New Engineering, Aviation,
More informationDate: Place: Technical University of Denmark. Knowledge FOr Resilient society
Date: 27-06-2017 Place: Technical University of Denmark Knowledge FOr Resilient society 11B25 Smoke and temperature ACTION 11B04 11B12 fire development 11B01 Evacuation human behaviour building response
More informationPROPOSAL BALLOT DUE BY: Thursday, September 18, 2008
PROPOSAL BALLOT DUE BY: Thursday, September 18, 2008 NFPA 204 SMO-AAA Standard for Smoke and Heat Venting Staff Liaison: Return Completed Ballot To: Jill McGovern E-Mail to jmcgovern@nfpa.org Fax to 617-984-7110
More informationCase Study 1 Underground car park
Case Study 1 Underground car park Dorota Brzezińska 1, Janusz Paliszek 2, Piotr Smardz 2, Renata Ollesz 1, Karol Kaczor 2 1 Lodz University of Technology, GRID - Lodz, INBEPO Wroclaw, Poland 1. Introduction
More informationWORKSHEET 3-1 THE MANITOBA OFFICE OCCUPANCY FIRE RISK INDEX FIRE SAFETY PARAMETER VALUES
1 WORKSHEET 3-1 THE MANITOBA OFFICE OCCUPANCY FIRE RISK INDEX FIRE SAFETY PARAMETER VALUES TABLE 3.1 CONSTRUCTION OF STRUCTURAL MEMBERS AND FLOOR AND ROOF (1) ASSEMBLIES (Applies each fire zone) Building
More information2018 IFC Update. Based on the 2018 International Fire Code, (IFC ) Goal. Objectives. Content
Based on the 2018 International Fire Code, (IFC ) The International Fire Code (IFC ), establishes minimum regulations for fire safety. This handout will identify important changes in the IFC from 2015
More informationFire Safety Strategies for Penthouse Designs
ctbuh.org/papers Title: Authors: Subject: Keywords: Fire Safety Strategies for Penthouse Designs Hadrien Fruton, Fire Engineer, Hoare Lea Karl Wallasch, Associate, Hoare Lea Fire & Safety Fire Safety Residential
More informationFEMA Recommendations for Protection of Curtained Limited Finishing Workstations using UL 1254 Listed Pre engineered Dry Chemical Systems
FEMA Recommendations for Protection of Curtained Limited Finishing Workstations using UL 1254 Listed Pre engineered Dry Chemical Systems FEMA Recommendations are based upon Live Fire Testing of Prep Stations
More informationHigh challenge warehouse case study Summary
High challenge warehouse case study Summary February 19, 2010 Richard Gallagher Michael Gollner Zurich Services Corporation Objectives Review the results of the high challenge warehouse workshop Recognize
More information2. The Group F occupancy has have an a combined occupant load of 500 or more above or below the lowest level of exit discharge.
2. The Group F occupancy has have an a combined occupant load of 500 or more above or below the lowest level of exit discharge. Exception: Manual fire alarm boxes are not required where the building is
More informationEvaluation on Combustion Characteristics of Finishing Materials for Exterior Walls
Journal of Mechanics Engineering and Automation 5 (2015) 465-471 doi: 10.17265/2159-5275/2015.08.007 D DAVID PUBLISHING Evaluation on Combustion Characteristics of Finishing Materials for Exterior Walls
More information2015 SFPE Europe Conference on Fire Safety Engineering
2015 SFPE Europe Conference on Fire Safety Engineering THE FSE APPROACH FOR A HISTORICAL BUILDING IN LIGHT OF THE ITALIAN STANDARDS. Simonetto Sacco Luciano Nigro HUGHES ASSOCIATES EUROPE, srl FIRE SCIENCE
More informationF.R.A.M.E. EVENT NETWORKS used in "FRAME".
EVENT NETWORKS used in "FRAME". In 2004, Dipl. Ing. Trond Maag wrote his doctorates' thesis "Risikobasierte Beurteilung der Personensicherheit von Wohnbauten im Brandfall unter Verwendung von Bayes'schen
More informationJanuary 1, 2014 Mandatory Effective Date
2013 Kentucky Building Code Highlights Winnie Blythe, Technical Advisor Dept. of Housing, Buildings, and Construction winnie.blythe@ky.gov www.dhbc.ky.gov 502-573-0373 January 1, 2014 Mandatory Effective
More informationAnatomy of a Fire. Christopher Crivello, MSFPE, PE. Douglas Nadeau, MSFPE, PE, CFPS, LEED AP
Anatomy of a Fire Douglas Nadeau, MSFPE, PE, CFPS, LEED AP President of RAN Fire Protection Engineering, PC Vice President of truvue Inspection Technology Christopher Crivello, MSFPE, PE Fire Protection
More informationFM Approval Standard For Cavity Walls And Rainscreens
FM4411 - Approval Standard For Cavity Walls And Rainscreens Mark D. Tyrol, P.E. FM Approvals Air Barrier Association of America (ABAA) is a Registered Provider with The American Institute of Architects
More informationThird Runway Project APM Depot Fire Engineering Design. Presented by Ir Wilson Sau-kit TSANG
1 Third Runway Project APM Depot Fire Engineering Design Presented by Ir Wilson Sau-kit TSANG 1 2 Presentation Overview 1. Project Background and Depot Overview 2. Building Information and Challenge for
More informationExplosion Protection Engineering Principles
Handbook of Fire and Explosion Protection Engineering Principles for Oil, Gas, Chemical and Related Facilities Second edition Dennis P. Nolan ELSEVIER AMSTERDAM BOSTON HEIDELBERG LONDON NEW YORK OXFORD
More informationResearch Needs for the Fire Safety Engineering Profession
Research Needs for the Fire Safety Engineering Profession Note: Items highlighted in RED are identified as the highest priority for each thread. Items highlighted in BOLD are identified as the highest
More informationPracticalities and Limitations of Coupling FDS with Evacuation Software
ABSTRACT Practicalities and Limitations of Coupling FDS with Evacuation Software Daniel Rådemar, WSP, Sweden Daniel Blixt, WSP, Sweden Brecht Debrouwere, WSP, Sweden Björn Grybäck Melin, WSP, Sweden Andrew
More informationSelecting appropriate egress strategies
Selecting appropriate egress strategies The selection of an appropriate egress strategy requires a good understing of the building its occupants, the protection measures in place, the expected emergency
More informationWATER MIST FIRE PROTECTION SYSTEMS FOR INDUSTRIAL CABLE TUNNELS AND TURBINE HALLS
WATER MIST FIRE PROTECTION SYSTEMS FOR INDUSTRIAL CABLE TUNNELS AND TURBINE HALLS Jukka Vaari 1, Amit Lior 2 1 2 VTT Technical Research Centre of Finland, Espoo, Finland Marioff Corporation Oy, Vantaa,
More informationRichard B. Alpert, P.E. Senior FPE, Clark Nexsen
Richard B. Alpert, P.E. Senior FPE, Clark Nexsen Clark Nexsen is a Registered Provider with The American Institute of Architects Continuing Education Systems (AIA/CES). Credit(s) earned on completion of
More informationCALIFORNIA POLYTECHNIC SLO
CALIFORNIA POLYTECHNIC SLO FIRE PROTECTION ENGINEERING PROGRAM CULMINATING PROJECT SUMMER 2014 ROCK TOLER Statement of Disclaimer This project report is a result of a class assignment; it has been graded
More informationMOBILE FIRE - RESCUE DEPARTMENT FIRE CODE ADMINISTRATION
MOBILE FIRE - RESCUE DEPARTMENT FIRE CODE ADMINISTRATION Fire Alarm System Plan Review 2009 International Fire Code and 2010 NFPA 72 Date of Review // BLD201 - Project Address: Project Name: _ Professional
More informationThe Physical Environment Portal: Module 5, LS Leadership
The Physical Environment Portal: Module 5, LS.02.01.10 - Leadership Fire Safety: Background Fire safety impacts both the lives of the occupants and the physical structures. In the early 1900 s many buildings
More informationApplying the New Zealand Performance Based Design Fire Framework to Buildings Designed in Accordance with NFPA5000
Applying the New Zealand Performance Based Design Fire Framework to Buildings Designed in Accordance with NFPA5000 Submitted by Chin Hung (Marco) Yip Supervised by Assoc. Professor Charles Fleischmann,
More informationCLOUD CEILINGS: FIRE DYNAMICS AND CODE CONTEXT
Peterson Guadagnolo Consulting Engineers PC CLOUD CEILINGS: FIRE DYNAMICS AND CODE CONTEXT 1 November 7, 2016 AGENDA Introduction New York State Code - Update Ceiling Types Fire Dynamics Compartment Fire
More information3.1 Introduction. 3.1 Introduction
DEPARTMENT OF ARCHITECTURE ABUBAKAR TAFAWA BALEWA UNIVERSITY, BAUCHI ARC 624: ADVANCED BUILDING SERVICES LESSON 3: FIRE DETECTION AND ALARM SYSTEMS IN BUILDINGS 3.1 Introduction 3.1 Introduction 3.2 Conventional
More informationMass Notification and Intelligent Response TM The European Way
Mass Notification and Intelligent Response TM The European Way Infrastructure & Cities, Building Technologies, Innovation & Industry Affairs Peter J. Loeffler Siemens Switzerland Ltd. 2013. All rights
More informationFlorida Building Code Chapter 9 Fire Protection Systems Advanced Course
Florida Building Code 2010 Chapter 9 Fire Protection Systems Advanced Course 1 Introduction This course will cover specific sections of Chapter 9 that relate to fire alarm systems. While many contractors
More informationICC CODE CORNER 2012 IFC Code & Commentary
SECTION 910 SMOKE AND HEAT VENTS 910.1 General. Where required by this code or otherwise installed, smoke and heat vents or mechanical smoke exhaust systems and draft curtains shall conform to the requirements
More informationSUMMARY. Building receiving sprinkler credit: SPRINKLERED. Grade: 68. Percent of Building Sprinklered: 100% Sprinkler Demand Met: 91%
210 N CHURCH ST CHARLOTTE NC 28202-2256 MECKLENBURG COUNTY RISK ID: 32 NC99 040235 ON-SITE SURVEY: 4/1/2009 LAST UPDATE: 4/1/2009 SUMMARY Building receiving sprinkler credit: SPRINKLERED Grade: 68 Percent
More informationSignificant Advancements in Water Based Fire Suppression for Storage Occupancies
Significant Advancements in Water Based Fire Suppression for Storage Occupancies Presented by: James Golinveaux Sr. Fellow Tyco Fire Protection Products Higher Faster - Further How high can we go? Ceiling
More informationTRI-LAKES MONUMENT FIRE PROTECTION DISTRICT
TRI-LAKES MONUMENT FIRE PROTECTION DISTRICT LOCAL AMENDMENTS INTERNATIONAL FIRE CODE 2009 December 5, 2012 1 Chapter 1 Administration Chapter 5 Fire Service Features Chapter 9 Fire Protection Systems Chapter
More informationEQUIVALENT INITIAL FIRE SAFETY ASSESSMENT
EQUIVALENT INITIAL FIRE SAFETY ASSESSMENT 171-181, Baizid Bostami Road Nasirabad I/A, Chittagong Chittagong The Alliance for Bangladesh Worker Safety Page 1/14 Introduction to the Report The following
More informationHow to know if a residential or domestic water mist system is performance compliant to BS 8458:2015?
Plumis White Paper April 2017 How to know if a residential or domestic water mist system is performance compliant to BS 8458:2015? As with the introduction of every new formal product category through
More information