Performance Based Design: Fire Alarm Visual Notification Appliances - Mathematical Guide. Ernesto Vega Jánica, EE, MSc, MEng

Size: px
Start display at page:

Download "Performance Based Design: Fire Alarm Visual Notification Appliances - Mathematical Guide. Ernesto Vega Jánica, EE, MSc, MEng"

Transcription

1 Performance Based Design: Fire Alarm Visual Notification Appliances - Mathematical Guide Ernesto Vega Jánica, EE, MSc, MEng 1

2 Performance Based Design Introduction Change on Philosophy Prescriptive Codes Vs Performance Based Design 2

3 Strobe Calculations Pros & Cons $ Financial Company R&D TM Project Owner Marketing Technical End-User 3

4 Engineer Design Brief What is Our Goal? Room Configurations & Applicable Rules 25% Performance Criteria NFPA 72 Vs UL 1971 Critical Design Assumptions 20% Design Features Method of Evaluation Mathematical Guide & Modeling Reference Model Examples 15% 15% 15% 10% 4

5 Performance Based Design What is Our Goal? The Strobe Calculator intends to Satisfy provisions of the NFPA 72 and the UL 1971 for building room configurations not listed on the NFPA 72, 2010* Tables (a) and (b) *NFPA recently released the NFPA 72, 2013 Edition, but the 2010 edition still referenced in the latest editions of model building codes such as the IBC 5

6 Performance Based Design Room Configurations NFPA 72, 2010 Tables (a) and (b) as Prescriptive Code Points to UL 1971 as the PBD guideline Rule of Thumb: Designs shall provide a minimum of lumens/ft 2 ( lumens/m 2 ) of illumination at any point 6

7 Performance Based Design Applicable Rules The American with Disabilities Act, ADA The National Fire Alarm Code NFPA 72 The American National Standards Institute, ANSI A117.1 UL Standard 1971, Signaling Devices for the Hearing Impaired 7

8 Prescriptive Code Strobe Coverage for Irregular Areas 10 a1=30 x30 900ft 2 15cd A=680 ft cd Strobe 22 a2=20 x20 400ft 2 a1=30 x30 900ft 2 30cd 8

9 Performance Based Design Performance Criteria Minimum requirements are listed by ADAAG, NFPA 72 & UL 1971: lumens/ft 2 ( lumens/m 2 ) of illumination at any point and, Vertical, Horizontal and Polar Output as per UL

10 Angular Derating Factor Performance Criteria 0 α 90 Angle Vertical α (Deg) Output (%) UL 1971 Minimum Vertical Output, Wall Mounted 10

11 Angular Derating Factor Performance Criteria α 0 Angle Horizontal α (Deg) Output (%) UL 1971 Minimum Horizontal Output, Wall Mounted 11

12 Angular Derating Factor Performance Criteria α 0 Angle α (Deg) Polar Output (%) UL 1971 Minimum Polar Output, Ceiling Mounted 12

13 Performance Based Design NFPA 72 (Prescriptive) Vs UL 1971 (PBD: Strobe Calculations) MINIMUM REQUIRED LIGHT OUTPUT [cd] Maximum Room Size Wall Mount as per NFPA (cd) Wall Mount as per UL (cd) Maximum Ceiling Height Ceiling Mount as per NFPA (cd) Ceiling Mount as per UL (cd) 20 x ,20,30 15, 30, 55 15, 30, x ,20,30 30, 45, 75 75, 75, x ,20,30 60, 75, 95 75, 75, x ,20,30 95, 95, , 110, x OVER ,20,30 150, 150, , 177,

14 Performance Based Design NFPA 72 Add Value! Wall Mounted Strobes Vs UL 1971 New Scenarios no listed in NFPA 72 MINIMUM REQUIRED LIGHT OUTPUT [cd] Maximum Wall Mount as Wall Mount as Room Size per NFPA (cd) per UL (cd) 10 x10 NA (15) x15 NA (15) x10 NA (15) x x30 NA (34) x x35 NA (60) x x44 NA (75) x50 NA (94) x

15 Performance Based Design NFPA 72 Vs UL 1971 New Scenarios! New Savings! Ceiling Mounted Strobes Maximum Room Size MINIMUM REQUIRED LIGHT OUTPUT [cd] Maximum Ceiling Height Ceiling Mount as per NFPA (cd) Add Value! Ceiling Mount as per UL (cd) 10 x10 10,12,15 15, 30, 30 15, 15, x15 10,12,25 15, 30, 55 15, 15, x20 10,20,30 15, 30, 55 15, 30, x20 12,18,24 15, 30, 55 15, 30, x25 12,18,24 45, 45, 75 30, 30, x30 10,20,30 30, 45, 75 75, 75, x40 10,20,30 60, 75, 95 75, 75, x44 12,24,30 75, 95, 95 75, 75, x50 10,20,30 95, 95, , 110, x60 10,20,30 150, 150, , 177,

16 Performance Based Design Critical Design Assumptions Inverse Square Law Vertical, Horizontal & Polar distribution as per UL 1971 Distance from Strobe to most remote point Add Value! 16

17 Inverse Square law Keep it Simple! P = I / D 2 P2 P = Illuminance (lumens/ft 2 ) P1 I = Effective Intensity (candela) Strobe (Source) D1 D2 D = Distance (ft) 17

18 Prescriptive Code Design Features 6 In rooms with Low Ceilings Middle of Lens Sect ADA NFPA 72 Sync more than 2 Strobes in a field view Sect (4) Sect Sect NFPA 72,

19 Strobe Calculations Method of Evaluation Scenarios Not Listed in prescriptive tables Wall Mounted: Horizontal & Vertical Outputs Ceiling Mounted: Polar Outputs The Strobe Calculator will recommend the next commercially available strobe Equivalent Facilitation Letter 15cd 30cd 75cd 110cd 177cd Add Value! 19

20 Strobe Calculations Code Compliance Facilitation Letter Department of Community Affairs -DCA- Authority Having Jurisdiction -AHJ- Explain Evaluation Procedure & Results Add Value! 20

21 Performance Based Design Model Interface Strobe Location: Wall Ceiling Room Dimensions: h = x = y = x=wide Recommended Strobe: 75cd y=deep h=height 21

22 Performance Based Design Model Examples Super extra Outlet Mall 44 x44 Ceilings at 12 AFF NFPA 72 Prescriptive 80cd Strobe A=1600 SqFt 40 x40 Performance Based Design 75cd Strobe A=1936 SqFt 22

23 Performance Based Design Model Examples Super extra Outlet Mall ACHIEVE 14% SAVINGS $ 80,000 Over 300 Stores Sports Food Movies Home Retail $ 8,500 $ 15,000 $ 22,000 $ 21,000 $ 13,500 23

24 Equivalent Facilitation Letter 24

25 Performance Based Design Model Examples Add Value! What about existing buildings? Existing Strobes not in compliance with proper coverage? Limited Wire, Circuit Runs and Power Supplies? Landmark or Sensitive Areas or Buildings? What would be the Maximum Coverage if...? 25

26 Performance Based Design Where do we see more add Value? MINIMUM REQUIRED LIGHT OUTPUT [cd] Maximum Room Size Maximum Ceiling Height Ceiling Mount as per NFPA (cd) Ceiling Mount as per UL (cd) New Scenarios! New Savings! Ceiling Mounted Strobes 10 x10 10,12,15 15, 30, 30 15, 15, x15 10,12,25 15, 30, 55 15, 15, x20 10,20,30 15, 30, 55 15, 30, x20 12,18,24 15, 30, 55 15, 30, x25 12,18,24 45, 45, 75 30, 30, x30 10,20,30 30, 45, 75 75, 75, x40 10,20,30 60, 75, 95 75, 75, x44 12,24,30 75, 95, 95 75, 75, x50 10,20,30 95, 95, , 110, x60 10,20,30 150, 150, , 177, 177 Discard non-commercially available ( ) 26

27 any? 27

28 Ernesto Vega Jánica. EE, MSc, MEng any? 28

29 Thank You! References ADAAG Visible Notification Sections and 2,2 Equivalent Facilitation NFPA 72, National Fire Alarm Code, 1999, 2002, 2007, 2010 & 2013 Editions UL Standard for Safety 1971, Signaling Devices for the Hearing Impaired SFPE Handbook of Fire Protection Engineering, 3rd Edition SFPE Engineering Guide to Performance-Based Fire Protection, 2nd Edition Credits Dr. James Milke. University of Maryland Rolf Jensen & Associates. New York City 29

11:00 to 12:00 Secrets to achieving code-compliant strobe installations. Ralph Coco, Potter Canada Paul Jewett, Mircom Group of Companies

11:00 to 12:00 Secrets to achieving code-compliant strobe installations. Ralph Coco, Potter Canada Paul Jewett, Mircom Group of Companies 11:00 to 12:00 Secrets to achieving code-compliant strobe installations. Ralph Coco, Potter Canada Paul Jewett, Mircom Group of Companies Visible Signals Agenda 1. Physics 2. Installation Considerations

More information

COSTCO, SAN FRANCISCO A PRESCRIPTIVE AND PERFORMANCE BASED ANALYSIS OF FIRE PROTECTION SYSTEMS AND DESIGN

COSTCO, SAN FRANCISCO A PRESCRIPTIVE AND PERFORMANCE BASED ANALYSIS OF FIRE PROTECTION SYSTEMS AND DESIGN COSTCO, SAN FRANCISCO A PRESCRIPTIVE AND PERFORMANCE BASED ANALYSIS OF FIRE PROTECTION SYSTEMS AND DESIGN Presented by Ian Levine June, 2016 Photo courtesy of Google Maps PRESENTATION OVERVIEW BUILDING

More information

TrueAlert Multi-Candela Notification Appliances

TrueAlert Multi-Candela Notification Appliances UL, ULC Approved* TrueAlert Multi-Candela Notification Appliances Non-Addressable Visible Only Amber Lens Strobes for Emergency Communications Features Visible only (V/O) 24 VDC wall mount notification

More information

MULTI-PHASED FIRE ALARM AND MASS NOTIFICATION SYSTEM UPGRADES: The Authority Having Jurisdiction (AHJ) and Proper Planning

MULTI-PHASED FIRE ALARM AND MASS NOTIFICATION SYSTEM UPGRADES: The Authority Having Jurisdiction (AHJ) and Proper Planning CAMPUS FIRE SAFETY CODE TALK Campus Fire Safety e-newzone MULTI-PHASED FIRE ALARM AND MASS NOTIFICATION SYSTEM UPGRADES: The Authority Having Jurisdiction (AHJ) and Proper Planning By Ernesto Vega Janica,

More information

A COMPARISON OF FIRE ALARM SYSTEM REQUIREMENTS IN THE US AND UK. James R. Lugar Jr., P.E. Rolf Jensen & Associates, Inc. SFPE 2012 Savannah, GA

A COMPARISON OF FIRE ALARM SYSTEM REQUIREMENTS IN THE US AND UK. James R. Lugar Jr., P.E. Rolf Jensen & Associates, Inc. SFPE 2012 Savannah, GA A COMPARISON OF FIRE ALARM SYSTEM REQUIREMENTS IN THE US AND UK James R. Lugar Jr., P.E. Rolf Jensen & Associates, Inc. SFPE 2012 Savannah, GA Presentation Objective Compare fire alarm system design methods

More information

08 Series Notification Appliances AS / AH & AS Audible Strobe Appliances and AH Audibles Application: Indoor / Outdoor

08 Series Notification Appliances AS / AH & AS Audible Strobe Appliances and AH Audibles Application: Indoor / Outdoor s Data Sheet Fire Safety & Security Products 08 Series Notification Appliances AS / AH & AS Audible Strobe Appliances and AH Audibles Application: Indoor / Outdoor AS-MC-CW AS-MC-R AH-W AH-R Product Overview

More information

Horn/Strobe Compliance Reference Guide

Horn/Strobe Compliance Reference Guide Horn/Strobe Compliance Reference Guide Table of Contents INTRODUCTION...1 WHAT IS THE COVERAGE AND ENFORCEMENT OF THE ADA?...2 WHAT IS THE ADAAG?...3 WHAT IS PUBLIC MODE VS. PRIVATE MODE OPERATION?...4

More information

TrueAlert Multi-Candela Notification Appliances

TrueAlert Multi-Candela Notification Appliances TrueAlert Multi-Candela Notification Appliances UL, ULC, CSFM Listed; FM Approved* Features 24 VDC high intensity notification appliance common features: Xenon strobe with intensity selectable as 135,

More information

s Notification Appliances

s Notification Appliances s Notification Appliances Data Sheet Fire Safety Products AS & AH Audible Horn Strobe / Audible Horn Appliances Application: Indoor / Outdoor AS-MC-CW AS-MC-R AH-R AH-W Product Overview Fast installation

More information

1 Watt Supervised Self-Amplified Strobe Speakers Round Flush Grille with 75cd Strobe

1 Watt Supervised Self-Amplified Strobe Speakers Round Flush Grille with 75cd Strobe 273 Branchport Avenue Long Branch, N.J. 07740 (800) 631-2148 Thank you for using our products. www.wheelockinc.com INSTALLATION INSTRUCTIONS SUPERVISED SELF-AMPLIFIED STROBE SPEAKERS Use this product according

More information

Fire Alarm System Fundamentals Presented By: Shamim Rashid-Sumar, Vice President Middle East Operations Rolf Jensen and Associates, Inc.

Fire Alarm System Fundamentals Presented By: Shamim Rashid-Sumar, Vice President Middle East Operations Rolf Jensen and Associates, Inc. Fire Alarm System Fundamentals Presented By: Shamim Rashid-Sumar, Vice President Middle East Operations Rolf Jensen and Associates, Inc. (RJA) Overview Understanding the Codes Fire Alarm Systems (Manual

More information

By: Russell Bainbridge March 18th, 2016 FPE 596

By: Russell Bainbridge March 18th, 2016 FPE 596 By: Russell Bainbridge March 18th, 2016 FPE 596 Egress Analysis and Design California Polytechnic State University's Engineering IV building Fire Detection, Alarm and Communication Systems A warehouse

More information

Speakers and Speaker Strobes

Speakers and Speaker Strobes Kingfisher Company, inc. Speakers and Speaker Strobes Features: Approvals include: UL Standard 1971, UL Standard 1480, New York City (MEA), California State Fire Marshall (CSFM), Factory Mutual (FM), and

More information

SELECT-A-HORN/STROBE SERIES

SELECT-A-HORN/STROBE SERIES SELECT-A-HORN/STROBE SERIES Features Description Mircom s Select-A-Strobe/Horn Series is designed to comply with the Americans with Disability Act (ADA) and meet UL standard 1971 requirements for emergency

More information

TrueAlert Notification Appliances

TrueAlert Notification Appliances TrueAlert Notification Appliances UL Listed; FM, CSFM and MEA (NYC) Approved* Non-Addressable Audible/Visible Notification Appliances with SmartSync Operation of Strobes and Horns Features Wall mount audible/visible

More information

Genesis Low Frequency (520 Hz) Horn-Strobe Installation Sheet

Genesis Low Frequency (520 Hz) Horn-Strobe Installation Sheet Genesis Low Frequency (520 Hz) Horn-Strobe Installation Sheet Table 1: Models Description Low frequency (520 Hz) horn, white housing, no FIRE marking, standard output clear strobe light Low frequency (520

More information

MNEC NFPA 72 WHITE PAPER

MNEC NFPA 72 WHITE PAPER MNEC NFPA 72 WHITE PAPER In 2010, the National Fire Protection Assocation (NFPA), significantly changed their code # 72 (National Fire Alarm Code) and has forever improved the importance of communicating

More information

WARNING WARNING. Installation Instructions for 116DEXSTC-FJ AdaptaBeacon Fire Alarm Strobe Lights for Use in Hazardous Locations.

WARNING WARNING. Installation Instructions for 116DEXSTC-FJ AdaptaBeacon Fire Alarm Strobe Lights for Use in Hazardous Locations. Cheshire, CT 064 3-699-30 (Ph) 3-699-3365 (Cust. Serv. Fax) 3-699-78 (Tech. Serv. Fax) Installation Instructions for 116DEXSTC-FJ AdaptaBeacon Fire Alarm Strobe Lights for Use in Hazardous Locations STANCHION

More information

FIRE ALARM SYSTEMS & 780 CMR. Dave LeBlanc, PE, FSFPE March 17, 2015

FIRE ALARM SYSTEMS & 780 CMR. Dave LeBlanc, PE, FSFPE March 17, 2015 FIRE ALARM SYSTEMS & 780 CMR Dave LeBlanc, PE, FSFPE March 17, 2015 BIOGRAPHY David J. LeBlanc, PE, FSFPE BS EE & MS FPE - WPI 23 Years PE Technical Committee Member NFPA72 - National Fire Alarm Code NFPA3

More information

Field Configurable Horns and Strobes

Field Configurable Horns and Strobes Vigilant Catalog Strobes, Horns, Bells, Chimes Field Configurable Horns and Strobes Genesis Series MNEC appliances available with clear or amber lenses. Pending Overview The Genesis line of fire alarm

More information

Changes in NFPA

Changes in NFPA Changes in NFPA 72-2002 2002 Oregon Fire Code Committee November 25, 2003 Michael B. Baker, SET Automatic Fire Alarm Association MikeBaker@afaa.org 2003 Michael B. Baker 1 Table of Contents 1. Administration

More information

Wheelock RSS & RSSP Series

Wheelock RSS & RSSP Series Wheelock RSS & RSSP Series Single- and Multi-Candela Strobes and Strobe Plates DF-51780:A G-520 General Wheelock s patented Series RSS Strobe Appliances and Series RSSP Strobe Plates have lower current

More information

SpectrAlert Advance. Field-Selectable Mass Notification Devices. Description. An ISO Company SIGNALING. MEA Approved E

SpectrAlert Advance. Field-Selectable Mass Notification Devices. Description. An ISO Company SIGNALING. MEA Approved E SpectrAlert Advance Description System Sensor SpectrAlert Advance offers a variety of devices designed for mass notification, including plain devices for non-fire applications, amber lens strobes and speaker

More information

MEMORANDUM. Technical Committee on Notification Appliances for Fire Alarm and Signaling Systems

MEMORANDUM. Technical Committee on Notification Appliances for Fire Alarm and Signaling Systems National Fire Protection Association 1 Batterymarch Park, Quincy, MA 02169-7471 Phone: 617-770-3000 Fax: 617-770-0700 www.nfpa.org MEMORANDUM TO: FROM: Technical Committee on Notification Appliances for

More information

'08 Series Notification A liances

'08 Series Notification A liances SIEMENS Data Sheet Fire Safety & Security Products '08 Series Notification A liances AS I AH & AS - Audible Strobe Appliances and AH Audibles AS-MC-CW AS-MC-R AH-W AH-R Product Overview - Fast installation

More information

American Fire Sprinkler Association. An Introduction to the IBC and IFC

American Fire Sprinkler Association. An Introduction to the IBC and IFC American Fire Sprinkler Association Presents An Introduction to the IBC and IFC October 13, 2005 Speaker Roland Huggins, P.E. Vice President of Engineering and Technical Services American Fire Sprinkler

More information

PHOTOLUMINESCENT EXIT SIGNS EVALUATED AND TESTED TO UL924

PHOTOLUMINESCENT EXIT SIGNS EVALUATED AND TESTED TO UL924 PHOTOLUMINESCENT EXIT SIGNS EVALUATED AND TESTED TO UL924 90.8924R-2-F-B 90.8924G-2-F-B EverGlow manufactures aluminum exit signs and architectural frames. These signs are evaluated and tested to UL924.

More information

Page 1 of 16 FLASH PUSLE WIDTH EFFECTIVENESS IN NOTIFICATION APPLIANCES

Page 1 of 16 FLASH PUSLE WIDTH EFFECTIVENESS IN NOTIFICATION APPLIANCES Page 1 of 16 FLASH PUSLE WIDTH EFFECTIVENESS IN NOTIFICATION APPLIANCES Ken Savage TYCO Safety Products January 25, 2011 Page 2 of 16 ABSTRACT Today s fire alarm system notification equipment standards

More information

TrueAlert Non-Addressable, Multi-Candela Notification Appliances Installation Instructions

TrueAlert Non-Addressable, Multi-Candela Notification Appliances Installation Instructions TrueAlert NonAddressable, MultiCandela Notification Appliances Installation Instructions PRODUCT IDENTIFICATION REFERENCE (See Page 4 for Detailed Product Specifications) Type Mount Model Color Operation

More information

Installation Instructions for 116DEGEX-FJ-(R) AdaptaBeacon Fire Alarm Strobe Lights for Use in Hazardous Locations

Installation Instructions for 116DEGEX-FJ-(R) AdaptaBeacon Fire Alarm Strobe Lights for Use in Hazardous Locations Installation Instructions for 116DEGEX-FJ-(R) AdaptaBeacon Fire Alarm Strobe Lights for Use in Hazardous Locations CEILING 116EX-C 3/ CONDUIT ENTRIES PENDANT 116EX-P 3/ CONDUIT ENTRY 116EX-C (WALL MOUNTED)

More information

Florida Building Code 2010

Florida Building Code 2010 Introduction Florida Building Code 2010 Chapter 9 Fire Protection Systems This course will cover specific sections of Chapter 9 that relate to fire alarm systems. While many contractors are familiar with

More information

Field Configurable Horns and Strobes

Field Configurable Horns and Strobes EDWARDS Catalog u Strobes, Horns, Bells, Chimes LIFE SAFETY & INCIDENT MANAGEMENT Field Configurable Horns and Strobes Genesis Series ECS/MNS appliances available with clear or amber lenses. S218, S5389,

More information

Minimum Standards for Engineers Practicing Fire Protection Engineering in the State of Oklahoma September 14, 2016

Minimum Standards for Engineers Practicing Fire Protection Engineering in the State of Oklahoma September 14, 2016 1. Introduction The intent of this document is to establish minimum standards for the practice of fire protection engineering within the State of Oklahoma as conducted by licensed professional engineers.

More information

TrueAlert ES Addressable Notification Appliances

TrueAlert ES Addressable Notification Appliances UL, ULC, CSFM Listed; FM Approved* TrueAlert ES Addressable Notification Appliances Visible Notification Appliances, Wall Mount Multi-Candela Strobes, Model Series 49VO Features Individually addressed

More information

L-Series, Indoor Strobes and Horn Strobes

L-Series, Indoor Strobes and Horn Strobes Notification Appliances L-Series, Indoor Strobes and Horn Strobes Indoor Selectable-Output Strobes/Horn Strobes for Ceiling Applications General The L-Series audible visible notification products offer

More information

Use this product according to this instruction manual. Please keep this instruction manual for future reference.

Use this product according to this instruction manual. Please keep this instruction manual for future reference. 273 Branchport Avenue Thank you for using our products. Long Branch, NJ 07740 (800) 631-2148 INSTALLATION INSTRUCTIONS www.cooperwheelock.com E50 MULTI-CANDELA SPEAKER STROBES GENERAL: Use this product

More information

Florida Building Code Chapter 9 Fire Protection Systems Advanced Course

Florida Building Code Chapter 9 Fire Protection Systems Advanced Course Florida Building Code 2010 Chapter 9 Fire Protection Systems Advanced Course 1 Introduction This course will cover specific sections of Chapter 9 that relate to fire alarm systems. While many contractors

More information

MEA. SpectrAlert Series Horns, Strobes, and Horn/Strobes GENERAL

MEA. SpectrAlert Series Horns, Strobes, and Horn/Strobes GENERAL March 30, 2000 Section: Audio/Visual Devices G-250 SpectrAlert Series Horns, Strobes, and Horn/Strobes GENERAL System Sensor SpectrAlert Series strobes, horns, and combination horn/strobes are UL listed

More information

Committee Input No NFPA [ Global Input ] Submitter Information Verification. Committee Statement. 1 of /20/ :02 AM

Committee Input No NFPA [ Global Input ] Submitter Information Verification. Committee Statement. 1 of /20/ :02 AM 1 of 213 10/20/2016 11:02 AM Committee Input No. 2505-NFPA 72-2016 [ Global Input ] Change the term visible to visual where appropriate Submitter Information Verification Submitter Full Name: SIG-NAS Organization:

More information

Will Clay Spring 2014

Will Clay Spring 2014 Will Clay Spring 2014 1. Project Overview 2. Prescriptive Requirements 3. Existing Requirements 4. Performance Evaluation 5. Conclusions RJA-Houston since 2010 Hired as FP/LS consultants by architect in

More information

Fire Protection System and Life Safety Evaluation of Building X. Anthony W. Sublett

Fire Protection System and Life Safety Evaluation of Building X. Anthony W. Sublett Fire Protection System and Life Safety Evaluation of Building X Presented by Anthony W. Sublett Culminating Project Master of Science in Fire Protection Engineering California Polytechnic State University

More information

L-Series, Emergency Communication Devices

L-Series, Emergency Communication Devices Notification Appliances L-Series, Emergency Communication Devices Description The L-Series Emergency Communications devices and accessories combine application versatility with all of the same time-saving

More information

CLOUD CEILINGS: FIRE DYNAMICS AND CODE CONTEXT

CLOUD CEILINGS: FIRE DYNAMICS AND CODE CONTEXT Peterson Guadagnolo Consulting Engineers PC CLOUD CEILINGS: FIRE DYNAMICS AND CODE CONTEXT 1 November 7, 2016 AGENDA Introduction New York State Code - Update Ceiling Types Fire Dynamics Compartment Fire

More information

STATE FIRE MARSHAL S REQUIRED FIRE PROTECTION SYSTEMS NARRATIVE REPORT

STATE FIRE MARSHAL S REQUIRED FIRE PROTECTION SYSTEMS NARRATIVE REPORT STATE FIRE MARSHAL S REQUIRED FIRE PROTECTION SYSTEMS NARRATIVE REPORT The interaction of fire protection systems can be extremely complex. The detection of a fire in a building by an automatic device

More information

Proposed Changes to NFPA

Proposed Changes to NFPA 2017 NFPA Conference & Expo Proposed Changes to NFPA 72-2019 Presented by: Daniel O Connor (SIG-IDS), Jensen Hughes Robert Schifiliti (SIG-NAS), R.P. Schifiliti Associates William Koffel (SIG-ECS), Koffel

More information

CSH24CH. Colored Light Strobe/Horn Series High Candela. Description. Features. Ceiling/Wall Mount Patent Pending. Ordering Information

CSH24CH. Colored Light Strobe/Horn Series High Candela. Description. Features. Ceiling/Wall Mount Patent Pending. Ordering Information OF FIRE CS24C Colored Light Strobe/orn Series igh Candela Ceiling/Wall Mount Patent Pending Description AMSECO's UL listed Colored Light Strobe CS24C series is designed to provide audible and visual signals

More information

TrueAlert Addressable Notification Appliances

TrueAlert Addressable Notification Appliances UL, ULC, CSFM Listed, FM Approved TrueAlert Addressable Notification Appliances Audible/Visible Notification Appliances, Wall Mount Multi-Candela Horn/Strobe, Model Series 49AV Features Individually addressed

More information

Signature Series Auto-Sync Output Module (CC1S)

Signature Series Auto-Sync Output Module (CC1S) Signature Series Auto-Sync Output Module (CC1S) Product description Mounting The Signature Series can be mounted in a North American 2-1/2 in (64 mm) deep 2-gang box or a standard 4 in square box 1-1/2

More information

SANTA ROSA FIRE DEPARTMENT FIRE PREVENTION BUREAU PLAN REVIEW CHECKLIST FIRE ALARM SYSTEM INSTALLATION

SANTA ROSA FIRE DEPARTMENT FIRE PREVENTION BUREAU PLAN REVIEW CHECKLIST FIRE ALARM SYSTEM INSTALLATION July 1, 2010 SANTA ROSA FIRE DEPARTMENT FIRE PREVENTION BUREAU PLAN REVIEW CHECKLIST FIRE ALARM SYSTEM INSTALLATION Address: Permit #: Inspector: Date: Status: Inspector: Date: Status: A-Approved; AC-Approved

More information

TrueAlert Addressable Notification Appliances

TrueAlert Addressable Notification Appliances UL, ULC Listed* TrueAlert Addressable Notification Appliances Audible/Visible Notification Appliances; Multi-Tone Horn/Strobe with 520 Hz Output Features Individually addressed and controlled multi-tone

More information

Fire Alarm Wiring. Circuit types, styles and limitations

Fire Alarm Wiring. Circuit types, styles and limitations Fire Alarm Wiring Circuit types, styles and limitations What we will cover Types Classes Notification Appliance Circuits (NAC) Initiating Device Circuits (IDC) Signaling Line Circuits (SLC) Class A, B,

More information

RESIDENTIAL SPRINKLER INSTALLATION GUIDE

RESIDENTIAL SPRINKLER INSTALLATION GUIDE RESIDENTIAL SPRINKLER INSTALLATION GUIDE 4077 AIR PARK DRIVE STANDISH, MICHIGAN 48658 PHONE 989-846-4583 800-248-0278 FAX 989-846-9231 www.globesprinkler.com A-15 GLOBE RESIDENTIAL SPRINKLER GUIDE DESCR.,

More information

Standard for the Installation of Carbon Monoxide (CO) Detection and Warning Equipment

Standard for the Installation of Carbon Monoxide (CO) Detection and Warning Equipment NFPA 720 2015 Summary Standard for the Installation of Carbon Monoxide (CO) Detection and Warning Equipment TM, 7Oct14 CODE: Title, Standard, not Code Consistent with recent trend at NFPA, this document

More information

Frequently Asked Questions

Frequently Asked Questions Frequently Asked Questions For Life Safety System Designers, Building Owners, and Installers P/N 85000-0395 Introduction Provisions in NFPA 72 (The National Fire Alarm and Signaling Code) now require low

More information

Virtual Compartment: An Alternative Approach to Means of Egress Design in Airport Pedestrian Tunnel

Virtual Compartment: An Alternative Approach to Means of Egress Design in Airport Pedestrian Tunnel Virtual : An Alternative Approach to Means of Egress Design in Airport Pedestrian Tunnel Xiaolei Chen, PhD California State University, Los Angeles, United States Ning (Frank) Wang, P.E. Jensen Hughes,

More information

L-Series, Indoor Strobes and Horn Strobes

L-Series, Indoor Strobes and Horn Strobes Notification Appliances L-Series, Indoor Strobes and Horn Strobes Indoor Selectable-Output Horns, Strobes and Horn Strobes for Wall Applications General The L-Series audible visible notification products

More information

Genesis LED G1 Series

Genesis LED G1 Series EDWARDS Catalog u Strobes, Horns, Bells, Chimes LIFE SAFETY INCIDENT MANAGEMENT Genesis LED G1 Series Compact Notification Devices S218, S5389 7125-1657:0506 7135-1657:0502 Overview Genesis LED G1 Series

More information

LIFESAVER MODEL SL240 REMOTE VISUAL SIGNALLING DEVICE (STROBE LIGHT)

LIFESAVER MODEL SL240 REMOTE VISUAL SIGNALLING DEVICE (STROBE LIGHT) LIFESAVER MODEL SL240 REMOTE VISUAL SIGNALLING DEVICE (STROBE LIGHT) USER MANUAL AUSTRALIAN ELECTRICAL AUTHORITY CS96313V IMPORTANT! READ ALL INSTRUCTIONS BEFORE INSTALLATION AND LEAVE THIS MANUAL FOR

More information

CONVENTIONAL AUDIBLE VISUAL

CONVENTIONAL AUDIBLE VISUAL Fast Installation, Safe Evacuation CONVENTIONAL AUDIBLE VISUAL www.kac.co.uk Setting the Standard with ENscape EN54-23 and how it affects you EN54-23 is a new European standard for Visual Alarm Devices

More information

Project Scenario Summary Report http://fusion.deltacollege.edu/code/planning/project/editfpu/scenariorpt.asp?id=2629&ce... Page 1 of 1 11/7/2017 California Community Colleges Project Scenario Summary 2019

More information

SECTION FIRE ALARM SYSTEMS

SECTION FIRE ALARM SYSTEMS SECTION 28 3100 PART 1 -GENERAL 1.01 RELATED DOCUMENTS Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 1 Specification Sections, apply to this

More information

First Revision No. 82-NFPA [ Section No ] Submitter Information Verification. Committee Statement. 2 of /21/2013 1:03 PM

First Revision No. 82-NFPA [ Section No ] Submitter Information Verification. Committee Statement. 2 of /21/2013 1:03 PM 2 of 326 11/21/2013 1:03 PM First Revision No. 82-NFPA 72-2013 [ Section No. 2.3.4 ] 2.3.4 ISO Publications. International Organization for Standardization, 1, ch. de la Voie-Creuse, Case postale 56, CH-1211

More information

Table OUT OF SERVICE. Building Fire Video 1/15/ Inspection, testing and maintenance. Standards Further Referenced by FCNYS

Table OUT OF SERVICE. Building Fire Video 1/15/ Inspection, testing and maintenance. Standards Further Referenced by FCNYS 901.6 Inspection, testing and maintenance. Fire detection, alarm and extinguishing systems shall be maintained in an operative condition at all times, and shall be replaced or repaired where defective.

More information

Fire Protection as the Underpinning of Good Process Safety Programs

Fire Protection as the Underpinning of Good Process Safety Programs Fire Protection as the Underpinning of Good Process Safety Programs Key Words: fires; protection, fire; building Background James Milke, Ph.D., P.E., Professor and Chair Department of Fire Protection Engineering

More information

SPECIFICATION: ECS SERIES CLEAN AGENT FIRE SUPPRESSION SYSTEM

SPECIFICATION: ECS SERIES CLEAN AGENT FIRE SUPPRESSION SYSTEM 1. GENERAL SPECIFICATION 1.1. A total flooding, FM-200 fire suppression system, super-pressurized with dry nitrogen shall be installed to meet a minimum design concentration of %, by volume in all designated

More information

Center for Life Safety Education

Center for Life Safety Education Center for Life Safety Education Fire Sprinklers 101 Introduction, Building Codes, and Water Supplies Reprinted with permission from NFPA 13, Installation of Sprinkler Systems, Copyright 2007, National

More information

Human Factors - Egress Analysis for High Hazard Occupancies. Presented by: Michael J. Klemenz, PE, SFPE

Human Factors - Egress Analysis for High Hazard Occupancies. Presented by: Michael J. Klemenz, PE, SFPE Human Factors - Egress Analysis for High Hazard Occupancies Presented by: Michael J. Klemenz, PE, SFPE Group H Other SFPE presenters today discussed issues relevant to Group H This presentation addresses

More information

Notifier by Honeywell: Non-Addressable Audible & Visual Alarm Devices. Approved to EN54-3/EN54-23

Notifier by Honeywell: Non-Addressable Audible & Visual Alarm Devices. Approved to EN54-3/EN54-23 Notifier by Honeywell: Non-Addressable Audible & Visual Alarm Devices Approved to EN54-3/EN54-23 Setting the Standard EN54-23 and how it affects you EN54-23 is a new European standard for Visual Alarm

More information

SECTION : FIRE ALARM & DETECTION SYSTEMS

SECTION : FIRE ALARM & DETECTION SYSTEMS SECTION 28 31 10: FIRE ALARM & DETECTION SYSTEMS 1. GENERAL A. This section applies to fire detection/alarm system and carbon monoxide system components and equipment installed during new construction

More information

Fire Alarm System Fundamentals

Fire Alarm System Fundamentals Fire Alarm System Fundamentals Mircom is the largest and oldest privately owned fire alarm and life safety manufacturer in North America and 5th largest overall with 50 years of industry experience. Mircom

More information

A. NFPA 2001 Standard for Clean Agent Fire Extinguishing Systems 2004 edition.

A. NFPA 2001 Standard for Clean Agent Fire Extinguishing Systems 2004 edition. 1. GENERAL SPECIFICATION 1.1 A total flooding, FM-200 fire suppression system, super-pressurized with dry nitrogen shall be installed to meet a minimum design concentration of %, by volume in all designated

More information

MOBILE FIRE - RESCUE DEPARTMENT FIRE CODE ADMINISTRATION

MOBILE FIRE - RESCUE DEPARTMENT FIRE CODE ADMINISTRATION MOBILE FIRE - RESCUE DEPARTMENT FIRE CODE ADMINISTRATION Fire Alarm System Plan Review 2009 International Fire Code and 2010 NFPA 72 Date of Review // BLD201 - Project Address: Project Name: _ Professional

More information

SPECIFICATION: Kidde Engineered Fire Suppression System Designed for use with 3M Novec 1230 Fire Protection

SPECIFICATION: Kidde Engineered Fire Suppression System Designed for use with 3M Novec 1230 Fire Protection 1. GENERAL SPECIFICATION 1.1 A total flooding, Novec 1230 fluid, fire suppression system, super-pressurized with dry nitrogen shall be installed to meet a minimum design concentration of %, by volume in

More information

NFPA Siemens Industry, Inc. All rights reserved. usa.siemens.com/infrastructure-cities

NFPA Siemens Industry, Inc. All rights reserved. usa.siemens.com/infrastructure-cities Fire Alarm and Signaling Code Overview NFPA 72-2010 usa.siemens.com/infrastructure-cities Siemens Building Technologies, Inc. is a Registered Provider with The American Institute of Architects Continuing

More information

AMENDMENT NO.: III INVITATION FOR BID NO.: GPA FOR

AMENDMENT NO.: III INVITATION FOR BID NO.: GPA FOR January 26, 2018 AMENDMENT NO.: III TO INVITATION FOR BID NO.: GPA-022-18 FOR PHYSICAL SECURITY AND ACCESS CONTROL SYSTEM (ACS) REPAIR AND UPGRADE AT VARIOUS GPA LOCATIONS Prospective Bidders are hereby

More information

2. HVAC and smoke control systems; fire, smoke, and combination fire/smoke dampers. 5. Central control and monitoring system.

2. HVAC and smoke control systems; fire, smoke, and combination fire/smoke dampers. 5. Central control and monitoring system. PART 1 GENERAL 1.01 Scope of Standard A. This Standard is intended to assure that fire detection/alarm systems at The University of Texas at Austin provide the highest level of fire safety possible.. This

More information

PROPOSED CODE CHANGES FOR REVIEW BY THE FIRE CODE ACTION COMMITTEE

PROPOSED CODE CHANGES FOR REVIEW BY THE FIRE CODE ACTION COMMITTEE PROPOSED CODE CHANGES FOR REVIEW BY THE FIRE CODE ACTION COMMITTEE Developed by the Midwestern Regional Work Group CONTENTS Item 15 Limited area sprinkler systems Item 20 Scope of IFC Ch 7 Item 21 Fire-resistance-rated

More information

3.1 Introduction. 3.1 Introduction

3.1 Introduction. 3.1 Introduction DEPARTMENT OF ARCHITECTURE ABUBAKAR TAFAWA BALEWA UNIVERSITY, BAUCHI ARC 624: ADVANCED BUILDING SERVICES LESSON 3: FIRE DETECTION AND ALARM SYSTEMS IN BUILDINGS 3.1 Introduction 3.1 Introduction 3.2 Conventional

More information

University Design Standard Fire Alarm Systems

University Design Standard Fire Alarm Systems 1.0 Overview University Design Standard Fire Alarm Systems This document provides Virginia Tech s standards for the design and installation of fire alarm systems and equipment in new construction, retrofit

More information

ACM8 Series UL Listed Sub-Assembly Access Power Controllers. Installation Guide. ACM8 - Eight (8) Fuse Protected Outputs

ACM8 Series UL Listed Sub-Assembly Access Power Controllers. Installation Guide. ACM8 - Eight (8) Fuse Protected Outputs ACM8 Series UL Listed Sub-Assembly Access Power Controllers Installation Guide Models Include: ACM8 - Eight (8) Fuse Protected Outputs ACM8CB - Eight (8) PTC Protected Outputs Rev. 042811 More than just

More information

Life safety notification

Life safety notification LED Wheelock Exceder LED3 Life safety notification Meeting the latest codes with increased energy-efficiency in a compact design Wheelock Exceder LED3 Compliant, compatible, compact, and energy efficient

More information

Circulation Report for SIG-TMS Comments Document # 72

Circulation Report for SIG-TMS Comments Document # 72 1 72-12 Eligible To Vote:28 Affirmative: 24 : 0 Abstain: 0 : 4 3.3.x Deficiency (New) (Log # 209 ) 72-13 Eligible To Vote:28 Affirmative: 24 : 0 Abstain: 0 : 4 3.3.x Deficiency (New) (Log # 234 ) 72-15

More information

*15cd models are Listed at 15cd and meet 75cd on axis

*15cd models are Listed at 15cd and meet 75cd on axis 273 Branchport Avenue Long Branch, NJ 07740 Thank you for using our products. (800) 631-2148 INSTALLATION INSTRUCTIONS www.wheelockinc.com MULTITONE STROBE APPLIANCES Use this product according to this

More information

Sinorix Engineered Fire Suppression Systems For use with Novec TM 1230 Fire Protection Fluid and HFC-227ea

Sinorix Engineered Fire Suppression Systems For use with Novec TM 1230 Fire Protection Fluid and HFC-227ea s Data Sheet Fire Safety Products Sinorix Engineered Fire Suppression Systems For use with Novec TM 1230 Fire Protection Fluid and HFC-227ea ARCHITECT AND ENGINEER SPECIFICATIONS System Overview Sinorix

More information

Fire Safety in Tall Building: Performance-Based Solutions. Chris Jelenewicz, P.E., FSFPE

Fire Safety in Tall Building: Performance-Based Solutions. Chris Jelenewicz, P.E., FSFPE Fire Safety in Tall Building: Performance-Based Solutions Chris Jelenewicz, P.E., FSFPE Kingdom Tower -- Jeddah Central Park Tower Philadelphia, PA One Meridian Plaza February 23, 1991 SFPE/ICC Guide

More information

Required vs. Non-required Fire Protection Systems. Dan Austin Chief Fire Code Consultant/State Fire Protection Engineer

Required vs. Non-required Fire Protection Systems. Dan Austin Chief Fire Code Consultant/State Fire Protection Engineer Required vs. Non-required Fire Protection Systems Dan Austin Chief Fire Code Consultant/State Fire Protection Engineer What are we going to cover? What makes a system required? What to do when a non-required

More information

Design Considerations of LED based Visible Notification Appliance SUPDET 2015

Design Considerations of LED based Visible Notification Appliance SUPDET 2015 Design Considerations of LED based Visible Notification Appliance SUPDET 2015 LED Applications Indoor/Outdoor Video Wall TV/Monitor backlighting Automatic Lighting General Lighting Can LED use in Visible

More information

NGV MAINTENANCE FACILITIES Code Related Modifications For NGVs In Existing Maintenance Facilities

NGV MAINTENANCE FACILITIES Code Related Modifications For NGVs In Existing Maintenance Facilities DELAWARE VALLEY REGIONAL PLANNING COMMISSION NGV MAINTENANCE FACILITIES Code Related Modifications For NGVs In Existing Maintenance Facilities Steve Arnold, P.E. - Engineering Vice President Brian Bogar,

More information

Open to Below: A Discussion of Allowed Floor Openings. Jay A. Ierardi, Ph.D., P.E., LEED AP. Kevin S. Hastings, P.E., LEED AP

Open to Below: A Discussion of Allowed Floor Openings. Jay A. Ierardi, Ph.D., P.E., LEED AP. Kevin S. Hastings, P.E., LEED AP Open to Below: A Discussion of Allowed Floor Openings Kevin S. Hastings, P.E., LEED AP Jay A. Ierardi, Ph.D., P.E., LEED AP R.W. Sullivan Engineering (617) 523-8227, Fax (617) 523-8016 http://www.rwsullivan.com

More information

RESIDENTIAL SPRINKLER INSTALLATION GUIDE

RESIDENTIAL SPRINKLER INSTALLATION GUIDE RESIDENTIAL SPRINKLER INSTALLATION GUIDE 4077 AIR PARK DRIVE STANDISH, MICHIGAN 48658 PHONE 989-846-4583 800-248-0278 FAX 989-846-9231 www.globesprinkler.com AUGUST 2014 A-15 GLOBE RESIDENTIAL SPRINKLER

More information

SECTION FM-200 FIRE SUPPRESSION SYSTEM

SECTION FM-200 FIRE SUPPRESSION SYSTEM SECTION 15360 FM-200 FIRE SUPPRESSION SYSTEM 1. GENERAL SPECIFICATION 1.1 A total flooding, ADS FM-200 fire suppression system with separate nitrogen storage used for a propellant shall be installed to

More information

APPENDIX C REGULATORY AGENCIES AND INDUSTRY STANDARDS 1.0 APPLICABLE GOVERNMENT CODES AND REGULATIONS

APPENDIX C REGULATORY AGENCIES AND INDUSTRY STANDARDS 1.0 APPLICABLE GOVERNMENT CODES AND REGULATIONS REGULATORY AGENCIES AND INDUSTRY STANDARDS 1.0 APPLICABLE GOVERNMENT CODES AND REGULATIONS All improvements of the facilities within the jurisdiction of the PCJPB shall be in strict conformance with government

More information

FIRE ALARM AND DETECTION SYSTEMS

FIRE ALARM AND DETECTION SYSTEMS 283100 FIRE ALARM AND DETECTION SYSTEMS PART 1: GENERAL 1.01 QUALITY ASSURANCE A. The integrated fire alarm system including all equipment, components, and accessories shall be UL listed for the purpose

More information

STUDY AND TEST MATERIAL FOR THE. FA2 and FA4 ASSESSMENTS. (Fire Alarm On-Site and Business Cert. Holder) June 14, 2017

STUDY AND TEST MATERIAL FOR THE. FA2 and FA4 ASSESSMENTS. (Fire Alarm On-Site and Business Cert. Holder) June 14, 2017 STUDY AND TEST MATERIAL FOR THE FA2 and FA4 ASSESSMENTS (Fire Alarm On-Site and Business Cert. Holder) June 14, 2017 This document contains sample questions to help participants study for the FA2 and FA4

More information

Objectives. To review updated IBC and fire test requirements when designing for life safety.

Objectives. To review updated IBC and fire test requirements when designing for life safety. Objectives To review updated IBC and fire test requirements when designing for life safety. To understand the relationship of fire safety and human impact safety. To clarify the difference between fire

More information

Fire Safety Evaluation of Existing Manufactured Educational Building Covered by Section 423 of the Florida Building Code

Fire Safety Evaluation of Existing Manufactured Educational Building Covered by Section 423 of the Florida Building Code Walker Engineering, Inc. 833 Rockingham Road Birmingham Alabama 35235-2625 205-854-0160 205-854-0160 (Fax) Fire Safety Evaluation of Existing Manufactured Educational Building Covered by Section 423 of

More information

Challenges of Fire Protection Upgrades in Existing Libraries. Campus Fire Safety Forum

Challenges of Fire Protection Upgrades in Existing Libraries. Campus Fire Safety Forum Challenges of Fire Protection Upgrades in Existing Libraries Campus Fire Safety Forum November 6, 2013 Presentation Overview Code Requirements Goals of Fire Protection Systems Life Safety Property Protection

More information

SEM7800 Series. Magnets

SEM7800 Series. Magnets Magnets The Sentronic SEM 7800 are heavy duty, electrically controlled door holding magnets. Magnets are fail safe and hold until the current is interrupted. A manual door closer is used to control and

More information

Battery Design Considerations

Battery Design Considerations Battery Design Considerations For general safety, and New York requirements Victoria Carey March 18, 2019 1 SAFER, SMARTER, GREENER DNV GL in Brief 155 350 14,000 2 DNV GL Energy Storage Expertise FEASIBILITY

More information

26 of 128 9/23/2014 9:25 AM

26 of 128 9/23/2014 9:25 AM 26 of 128 9/23/2014 9:25 AM Second Revision No. 105-NFPA 72-2014 [ Global Comment ] Revise the Annex F figures that include a smoke detector symbol (hexagon with a whisp of smoke) so that the new smoke

More information