A COMPARISON OF FIRE ALARM SYSTEM REQUIREMENTS IN THE US AND UK. James R. Lugar Jr., P.E. Rolf Jensen & Associates, Inc. SFPE 2012 Savannah, GA

Size: px
Start display at page:

Download "A COMPARISON OF FIRE ALARM SYSTEM REQUIREMENTS IN THE US AND UK. James R. Lugar Jr., P.E. Rolf Jensen & Associates, Inc. SFPE 2012 Savannah, GA"

Transcription

1 A COMPARISON OF FIRE ALARM SYSTEM REQUIREMENTS IN THE US AND UK James R. Lugar Jr., P.E. Rolf Jensen & Associates, Inc. SFPE 2012 Savannah, GA

2 Presentation Objective Compare fire alarm system design methods and products commonly used in North America and Europe This discussion will focus on requirements in the United States and the United Kingdom US discussion limited to model codes, current editions as published UK discussion limited to the scope of the Building Regulations for England and Wales (for buildings other than dwellings)

3 Presentation Overview This presentation will answer the following questions: How does legislation impact fire alarm design? What are common fire alarm design practices? What are common fire alarm system components? How is the fire service summoned?

4 Terminology Differences United States Fire alarm control unit (FACU) Manual fire alarm box Horn or speaker; strobe) Central Station United Kingdom Control and Indicating Equipment (CIE) Manual call point Bell, sounder or speaker; beacon Alarm receiving centre Note: Some are also functional differences, which will be discussed later

5 Legislation - US Law State or local law adopts building and fire codes Int l Code Council and Natl. Fire Prot. Assoc. (NFPA) Code Int l Bldg. Code or NFPA 101 define level NFPA 72, Natl. Fire Alarm & Signaling Code Std. NFPA 72 ref. other standards for products Ex.: UL 864 control units, UL 1971 visible signals

6 Legislation - UK Law Building Regulations England and Wales Provide appropriate provisions for early warning of fire Guide BS 5839 Fire Detection and Fire Alarm Systems for Bldgs. Part 1: Code of Practice Provides Recommendations Implement BAFE Compliance / LPS 1014 Company BS EN 54 Fire Detection and Fire Alarm Systems

7 Differences in Approach, Generalized Generally favors active fire protection, and provides mostly prescriptive requirements to establish the minimum requirements to safeguard public health, safety, and welfare. Generally favors passive fire protection and provides recommended practices to comply with requirements. For Means of warning and escape, The building shall be designed and constructed so that there are appropriate provisions for the early warning of fire, and appropriate means of escape in case of fire from the building to a place of safety outside the building capable of being safely and effectively used at all material times. Neither document is intended to restrict alternate methods that provide a level of safety that is equivalent to the minimum requirements.

8 What Level of System? - US Level of alarm is prescriptive based on inherent hazards of occupancy classification, building height, contents, etc. In general detectors are used sparingly fire detection is primarily via sprinkler water flow signals Fire alarm system is designed, installed, inspected, tested, and maintained per NFPA 72.

9 What Level of System? - UK Type L: Protection of Life Type P: Property Protection Type M: Manual BS Fire Detection Levels L1: Installed throughout the protected building L2: Installed only in defined parts of the building L3: Designed for early warning to permit occupant escape L4: Installed for protection of escape routes L5: Installed in specific areas per fire safety objectives P1: Installed throughout the protected building P2: Installed only in defined parts of the building Manual alarms only no detection provided

10 Product Approvals United States Regulations and model codes require compliance with NFPA 72 and applicable standards, with ANSI/UL standards usually cited as examples Conformity can be demonstrated by listing of the product by a Nationally Recognized Testing Laboratory (NRTL) as complying with that standard Some states require State Fire Marshal approval (based on NRTL report) in order to permit products to be disallowed should local problems emerge (ex California) United Kingdom Regulations require compliance with ISO, CEN, or national standards (in that order) Example BS EN 54 Conformity can be demonstrated by the CE mark authorized by any Notified Body within the EU CE mark must be accepted in any EU member country regardless of the testing organization National testing lab marks signifying compliance with national standards may only be recognized in that country (ex VdS in Germany)

11 Manual Alarm Initiation United States Manual fire alarm box (pull station) Usually required but can be omitted in some sprinklered occupancies (with one at an attended location) United Kingdom Manual Call Point (break glass) Primary component of fire alarm system required in Type L and M installations (optional Type P)

12 Detection Zones BS Detectors (and call points) are required to be zoned to direct responders to the fire Zone indication provided at the CIE Also applicable to addressable systems Recommendations provided for: General zoning Maximum floor area Search distance No similar requirements provided in US codes.

13 Alarm Notification - US Minimum and maximum audibility levels throughout per NFPA 72 Intelligible speech (voice alarm systems) Accessibility guidelines require visible notification via strobes in all public or common use areas

14 Visible Notification - US NFPA 72 provides specific requirements for: Flash rates and synchronization Mounting locations and heights Spacing based on strobe intensity in candelas (cd) Wall mounted Ceiling mounted Wall-mounted Ceiling-mounted

15 Alarm Notification - UK Audible sounders Provided for Types L and M, optional Type P Typical 65dBA min or 5dBA above ambient; limited areas 60dBA; 75dBA sleeping areas Voice can be used, esp. for staged evacuations Above: Examples of sounders from Tyco

16 Visual Alarm Signals - UK Used to supplement audible where deemed ineffective Red color preferred; mount above 2.1m (82.7 in.) Can be used for hearing impaired tactile devices more common Tyco beacon Tyco beacon integral with sensor (for sleeping area)

17 Fire Alarm System Wiring Both NFPA 72 and BS include provisions for protection of circuits and redundancy based on the inherent hazard, such as: Separation of circuit types and routing for redundancy Fire-resistance of wiring for staged evacuations Adequate support of system wiring

18 System Wiring, Continued United States Wire types can include plenum, riser, or circuit integrity (rated) Protection is part prescriptive and part designer s discretion. NFPA 72 defines: Circuit classes based on redundancy 3 levels of survivability Ex.: 2 hr. fire resistance required for selective evacuations United Kingdom Fire alarm wiring is standard fire resistance or enhanced fire resistance Enhanced fire resistance is recommended for multiple conditions including unsprinklered buildings with staged evacuations or unsprinklered high-rise buildings

19 Summoning the Fire Service United States The fire alarm system is required to automatically transmit signals: common methods include Central Station Proprietary Station NFPA 72 includes specific transmission requirements Occupants can also call, but monitoring is generally mandatory United Kingdom The primary method is by public emergency call system Alarm receiving centres (ARCs) can be used for Type L and M when warranted ARCs are used for Type P (property protection)

20 Any Questions? Thanks for your participation! Contact Information: James R. Lugar Jr., P.E. Rolf Jensen & Associates, Inc Peachtree Rd. NE Suite 550 Atlanta, GA (404)

Fire Alarm System Fundamentals

Fire Alarm System Fundamentals Fire Alarm System Fundamentals Mircom is the largest and oldest privately owned fire alarm and life safety manufacturer in North America and 5th largest overall with 50 years of industry experience. Mircom

More information

3.1 Introduction. 3.1 Introduction

3.1 Introduction. 3.1 Introduction DEPARTMENT OF ARCHITECTURE ABUBAKAR TAFAWA BALEWA UNIVERSITY, BAUCHI ARC 624: ADVANCED BUILDING SERVICES LESSON 3: FIRE DETECTION AND ALARM SYSTEMS IN BUILDINGS 3.1 Introduction 3.1 Introduction 3.2 Conventional

More information

FIRE ALARM SYSTEMS & 780 CMR. Dave LeBlanc, PE, FSFPE March 17, 2015

FIRE ALARM SYSTEMS & 780 CMR. Dave LeBlanc, PE, FSFPE March 17, 2015 FIRE ALARM SYSTEMS & 780 CMR Dave LeBlanc, PE, FSFPE March 17, 2015 BIOGRAPHY David J. LeBlanc, PE, FSFPE BS EE & MS FPE - WPI 23 Years PE Technical Committee Member NFPA72 - National Fire Alarm Code NFPA3

More information

SANTA CLARA COUNTY Winchester Blvd., Los Gatos, CA (408) (408) (fax)

SANTA CLARA COUNTY Winchester Blvd., Los Gatos, CA (408) (408) (fax) FIRE DEPARTMENT SANTA CLARA COUNTY 14700 Winchester Blvd., Los Gatos, CA. 95032-1818 (408) 378-4010 (408) 378-9342 (fax) www.sccfd.org STANDARD DETAILS & SPECIFICATIONS Spec No C-4 Rev. Date 03/10/10 SUBJECT:

More information

Frequently Asked Questions

Frequently Asked Questions Frequently Asked Questions For Life Safety System Designers, Building Owners, and Installers P/N 85000-0395 Introduction Provisions in NFPA 72 (The National Fire Alarm and Signaling Code) now require low

More information

NFPA Siemens Industry, Inc. All rights reserved. usa.siemens.com/infrastructure-cities

NFPA Siemens Industry, Inc. All rights reserved. usa.siemens.com/infrastructure-cities Fire Alarm and Signaling Code Overview NFPA 72-2010 usa.siemens.com/infrastructure-cities Siemens Building Technologies, Inc. is a Registered Provider with The American Institute of Architects Continuing

More information

SANTA ROSA FIRE DEPARTMENT FIRE PREVENTION BUREAU PLAN REVIEW CHECKLIST FIRE ALARM SYSTEM INSTALLATION

SANTA ROSA FIRE DEPARTMENT FIRE PREVENTION BUREAU PLAN REVIEW CHECKLIST FIRE ALARM SYSTEM INSTALLATION July 1, 2010 SANTA ROSA FIRE DEPARTMENT FIRE PREVENTION BUREAU PLAN REVIEW CHECKLIST FIRE ALARM SYSTEM INSTALLATION Address: Permit #: Inspector: Date: Status: Inspector: Date: Status: A-Approved; AC-Approved

More information

Automatic Fire Alarm Association Webinar On Inspection, Testing, And Maintenance Of Fire Alarm Systems

Automatic Fire Alarm Association Webinar On Inspection, Testing, And Maintenance Of Fire Alarm Systems Automatic Fire Alarm Association Webinar On Inspection, Testing, And Maintenance Of Fire Alarm Systems Your Presenter: Merton Bunker, PE Inspections and tests are intended to reduce or limit: Loss of life

More information

Changes in NFPA

Changes in NFPA Changes in NFPA 72-2002 2002 Oregon Fire Code Committee November 25, 2003 Michael B. Baker, SET Automatic Fire Alarm Association MikeBaker@afaa.org 2003 Michael B. Baker 1 Table of Contents 1. Administration

More information

CHAPTER 61G15-32 RESPONSIBILITY RULES OF PROFESSIONAL ENGINEERS CONCERNING THE DESIGN OF FIRE PROTECTION SYSTEMS

CHAPTER 61G15-32 RESPONSIBILITY RULES OF PROFESSIONAL ENGINEERS CONCERNING THE DESIGN OF FIRE PROTECTION SYSTEMS CHAPTER 61G15-32 RESPONSIBILITY RULES OF PROFESSIONAL ENGINEERS CONCERNING THE DESIGN OF FIRE PROTECTION SYSTEMS 61G15-32.001 61G15-32.002 61G15-32.003 61G15-32.004 61G15-32.005 61G15-32.006 61G15-32.007

More information

2. The Group F occupancy has have an a combined occupant load of 500 or more above or below the lowest level of exit discharge.

2. The Group F occupancy has have an a combined occupant load of 500 or more above or below the lowest level of exit discharge. 2. The Group F occupancy has have an a combined occupant load of 500 or more above or below the lowest level of exit discharge. Exception: Manual fire alarm boxes are not required where the building is

More information

A Guide To BS Understanding the selection, spacing and siting of detectors

A Guide To BS Understanding the selection, spacing and siting of detectors World Class Leaders in Fire Detection Since 1918 A Guide To BS5839-12017 Understanding the selection, spacing and siting of detectors Welcome to A Guide to BS5839 Part 1 : 2017 from HOCHIKI EUROPE (UK)

More information

British Columbia Building Code 2006 Division B Part 3 Fire Protection, Occupant Safety and Accessibility Section 3.2 Building Fire Safety

British Columbia Building Code 2006 Division B Part 3 Fire Protection, Occupant Safety and Accessibility Section 3.2 Building Fire Safety Div B 3.2.1.1.(4), (5) & (6) Exceptions in Determining Building Height BCBC1998-3.2.1.1.(4), (5) & (7) replace (harmonize with NBC) - NBC 2005 has significant revisions to provisions for mezzanines. These

More information

FIRE SAFETY REQUIREMENTS FOR PRE RESIDENTIAL BUILDINGS OF THREE OR MORE STORIES (DOROTHY MAE ORDINANCE - NO. 158,963)

FIRE SAFETY REQUIREMENTS FOR PRE RESIDENTIAL BUILDINGS OF THREE OR MORE STORIES (DOROTHY MAE ORDINANCE - NO. 158,963) INFORMATION BULLETIN / PUBLIC - MECHANICAL CODE REFERENCE NO.: LAMC 91.8604 Effective: 6-20-84 DOCUMENT NO. P/MC 2002-005 Revised: 6-15-00 Previously Issued As: MGD #74 FIRE SAFETY REQUIREMENTS FOR PRE-

More information

NFPA 72 Code Changes vs 2013

NFPA 72 Code Changes vs 2013 NFPA 72 Code Changes - 2010 vs 2013 AFAA-NE Westborough, MA February 7, 2018 Richard Roux NFPA 72 National Fire Alarm and Signaling Code Overview and 2013 Changes NFPA 72 1993 Edition Aug 20, 1993 1996

More information

University Design Standard Fire Alarm Systems

University Design Standard Fire Alarm Systems 1.0 Overview University Design Standard Fire Alarm Systems This document provides Virginia Tech s standards for the design and installation of fire alarm systems and equipment in new construction, retrofit

More information

EN54 Part 23 Made Easy CPD PRESENTED BY SIMON ADAMS GENT BY HONEYWELL

EN54 Part 23 Made Easy CPD PRESENTED BY SIMON ADAMS GENT BY HONEYWELL EN54 Part 23 Made Easy CPD PRESENTED BY SIMON ADAMS GENT BY HONEYWELL EN54 Part 23 Intent Standardise output levels from Visual Alarm Devices Improve designs & safety through ensuring enough light is generated

More information

SECTION 907 FIRE ALARM AND DETECTION SYSTEMS

SECTION 907 FIRE ALARM AND DETECTION SYSTEMS SECTION 907 FIRE ALARM AND DETECTION SYSTEMS 907.1 General. This section covers the application, installation, performance and maintenance of fire alarm systems and their components in new and existing

More information

Moreno Valley Fire Department Fire Prevention Bureau. New and Existing Fire Alarm & Signaling Systems Guideline

Moreno Valley Fire Department Fire Prevention Bureau. New and Existing Fire Alarm & Signaling Systems Guideline Moreno Valley Fire Department Guideline Approved and Authorized By: Adria Reinertson, Fire Marshal Issued: May 8, 2017 Alarm & Signaling Systems PURPOSE Fire alarm and signaling systems are designed to

More information

1. Floor above/floor below notification. 2. Private alarm notification. 3. Not Used 4. Voice alarm notification. 5. Not Used.

1. Floor above/floor below notification. 2. Private alarm notification. 3. Not Used 4. Voice alarm notification. 5. Not Used. PART 1 GENERAL 1.01 Scope of Standard A. This Standard is intended to assure that fire alarm and signaling systems at Sam Houston State University provide the highest level of life safety possible. This

More information

The Use of Public Address System to Improve Tunnel Safety - Current Practices. Lim Hock Tay

The Use of Public Address System to Improve Tunnel Safety - Current Practices. Lim Hock Tay The Use of Public Address System to Improve Tunnel Safety - Current Practices Lim Hock Tay Content 1 Introduction 2 3 Overview of Survey Responses Discussion 4 Conclusion PIARC International Conference

More information

MOBILE FIRE - RESCUE DEPARTMENT FIRE CODE ADMINISTRATION

MOBILE FIRE - RESCUE DEPARTMENT FIRE CODE ADMINISTRATION MOBILE FIRE - RESCUE DEPARTMENT FIRE CODE ADMINISTRATION Fire Alarm System Plan Review 2009 International Fire Code and 2010 NFPA 72 Date of Review // BLD201 - Project Address: Project Name: _ Professional

More information

ALARM SYSTEMS AND EVACUATION PLANS SELF INSPECTION CHECKLIST

ALARM SYSTEMS AND EVACUATION PLANS SELF INSPECTION CHECKLIST OPTIONAL INFORMATION Name of School: Date of Inspection: Vocational Program/Course/Room: Signature of Inspector: ALARM SYSTEMS AND EVACUATION PLANS Guidelines: This checklist covers regulations issued

More information

Florida Building Code Chapter 9 Fire Protection Systems Advanced Course

Florida Building Code Chapter 9 Fire Protection Systems Advanced Course Florida Building Code 2010 Chapter 9 Fire Protection Systems Advanced Course 1 Introduction This course will cover specific sections of Chapter 9 that relate to fire alarm systems. While many contractors

More information

MECKLENBURG COUNTY FIRE MARSHAL S OFFICE

MECKLENBURG COUNTY FIRE MARSHAL S OFFICE Effective Date: 11/01/02 Purpose: MECKLENBURG COUNTY To establish a set of guidelines for performance testing of all newly installed or upgraded fire alarm systems in order to ensure that all devices and

More information

Performance Based Design: Fire Alarm Visual Notification Appliances - Mathematical Guide. Ernesto Vega Jánica, EE, MSc, MEng

Performance Based Design: Fire Alarm Visual Notification Appliances - Mathematical Guide. Ernesto Vega Jánica, EE, MSc, MEng Performance Based Design: Fire Alarm Visual Notification Appliances - Mathematical Guide Ernesto Vega Jánica, EE, MSc, MEng 1 Performance Based Design Introduction Change on Philosophy 1999-2002-2007-2010-2013

More information

FIRE & LIFE SAFTEY STANDARD

FIRE & LIFE SAFTEY STANDARD Title: Effective Date: 01/01/14 Revised Date: 1/1/14 Code References: Title 16, Chapter 16.16 of the Roseville Municipal Code, NFPA 72 Note: This standard is a summary of Fire Department clarifications

More information

Recent Revisions and Proposed Key Changes to Fire Code

Recent Revisions and Proposed Key Changes to Fire Code Recent Revisions and Proposed Key Changes to Fire Code 2014 CFAA Presentation Kim Bailey - Office of the Fire Marshal and Emergency Management New Section 9.7 Buildings with a Care Occupancy or Retirement

More information

COSTCO, SAN FRANCISCO A PRESCRIPTIVE AND PERFORMANCE BASED ANALYSIS OF FIRE PROTECTION SYSTEMS AND DESIGN

COSTCO, SAN FRANCISCO A PRESCRIPTIVE AND PERFORMANCE BASED ANALYSIS OF FIRE PROTECTION SYSTEMS AND DESIGN COSTCO, SAN FRANCISCO A PRESCRIPTIVE AND PERFORMANCE BASED ANALYSIS OF FIRE PROTECTION SYSTEMS AND DESIGN Presented by Ian Levine June, 2016 Photo courtesy of Google Maps PRESENTATION OVERVIEW BUILDING

More information

08 Series Notification Appliances AS / AH & AS Audible Strobe Appliances and AH Audibles Application: Indoor / Outdoor

08 Series Notification Appliances AS / AH & AS Audible Strobe Appliances and AH Audibles Application: Indoor / Outdoor s Data Sheet Fire Safety & Security Products 08 Series Notification Appliances AS / AH & AS Audible Strobe Appliances and AH Audibles Application: Indoor / Outdoor AS-MC-CW AS-MC-R AH-W AH-R Product Overview

More information

SECTION DIGITAL, ADDRESSABLE FIRE-ALARM SYSTEM

SECTION DIGITAL, ADDRESSABLE FIRE-ALARM SYSTEM SECTION 283111 - DIGITAL, ADDRESSABLE FIRE-ALARM SYSTEM PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division

More information

2004 AUSTRALIAN STANDARDS UPDATE

2004 AUSTRALIAN STANDARDS UPDATE 2004 AUSTRALIAN STANDARDS UPDATE PREPARED by Peter Parsons Chairman of SAI FP-002 Chairman of ISO TC 21/SC 3 TSP Strategic Product Management Kjell Jawerth Chairman FPA Aust. TC/2 Member SAI FP-002 TSP

More information

Fact File 75. Published Document PD CEN/TS 54-32:2015 Fire detection and fire alarm systems

Fact File 75. Published Document PD CEN/TS 54-32:2015 Fire detection and fire alarm systems Fact File 75 Published Document PD CEN/TS 54-32:2015 Fire detection and fire alarm systems Published Document PD CEN/TS 54-32:2015 Fire detection and fire alarm systems INTRODUCTION... 3 BACKGROUND...

More information

EL DORADO COUNTY REGIONAL FIRE PROTECTION STANDARD

EL DORADO COUNTY REGIONAL FIRE PROTECTION STANDARD EL DORADO COUNTY REGIONAL FIRE PROTECTION STANDARD Installation of Residential Fire Sprinkler Systems STANDARD #C-002 EFFECTIVE 03-19-2009 PURPOSE: To ensure that sprinkler plans submitted for review contain

More information

Fire Alarm Wiring. Circuit types, styles and limitations

Fire Alarm Wiring. Circuit types, styles and limitations Fire Alarm Wiring Circuit types, styles and limitations What we will cover Types Classes Notification Appliance Circuits (NAC) Initiating Device Circuits (IDC) Signaling Line Circuits (SLC) Class A, B,

More information

Rancho Cucamonga Fire Protection District Prevention Bureau Standard

Rancho Cucamonga Fire Protection District Prevention Bureau Standard Rancho Cucamonga Fire Protection District Prevention Bureau Standard Title: Fire Alarm and Monitoring Systems Standard # 9-3 Effective: May 2002 Number of Pages: 7 Updated: December 2016 for consistency

More information

Intelligent Security & Fire Ltd

Intelligent Security & Fire Ltd THE NANO SYSTEM The revolutionary analogue addressable control panel Nano, the revolutionary control panel from Gent Nano is the latest fire detection control panel from Gent by Honeywell. It s a single

More information

American Fire Sprinkler Association. An Introduction to the IBC and IFC

American Fire Sprinkler Association. An Introduction to the IBC and IFC American Fire Sprinkler Association Presents An Introduction to the IBC and IFC October 13, 2005 Speaker Roland Huggins, P.E. Vice President of Engineering and Technical Services American Fire Sprinkler

More information

12/14/2013. Fire alarm and emergency power SPRINKLER HEAD

12/14/2013. Fire alarm and emergency power SPRINKLER HEAD Fire alarm and emergency power SPRINKLER HEAD 1 Alert signal Alarm signal Fire detector Heat detector Smoke detector Smoke alarm 1. Detector locations 1. Fire detector locations (3.2.4.11) 2. Smoke detector

More information

THIS ORDINANCE ONLY AFFECTS EXISTING FIRE ALARM SYSTEMS.

THIS ORDINANCE ONLY AFFECTS EXISTING FIRE ALARM SYSTEMS. THIS ORDINANCE ONLY AFFECTS EXISTING FIRE ALARM SYSTEMS. IF YOU RECEIVED A NOTICE BY MAIL AND YOU DO NOT CURRENTLY HAVE A FIRE ALARM INSTALLED IN YOUR BUILDING, YOU MAY DISREGARD THE NOTICE. Dear Building

More information

Life safety notification

Life safety notification LED Wheelock Exceder LED3 Life safety notification Meeting the latest codes with increased energy-efficiency in a compact design Wheelock Exceder LED3 Compliant, compatible, compact, and energy efficient

More information

2018 NICET Code Transition Changes

2018 NICET Code Transition Changes 2018 NICET Code Transition Changes NICET will be transitioning to newer codes accepted in their exams in mid-october 2018, specifically: NFPA 72 2016 NFPA 70 2014 IBC 2015 NFPA 101 2015 Here are some changes

More information

MNEC NFPA 72 WHITE PAPER

MNEC NFPA 72 WHITE PAPER MNEC NFPA 72 WHITE PAPER In 2010, the National Fire Protection Assocation (NFPA), significantly changed their code # 72 (National Fire Alarm Code) and has forever improved the importance of communicating

More information

Fire Alarm System Fundamentals Presented By: Shamim Rashid-Sumar, Vice President Middle East Operations Rolf Jensen and Associates, Inc.

Fire Alarm System Fundamentals Presented By: Shamim Rashid-Sumar, Vice President Middle East Operations Rolf Jensen and Associates, Inc. Fire Alarm System Fundamentals Presented By: Shamim Rashid-Sumar, Vice President Middle East Operations Rolf Jensen and Associates, Inc. (RJA) Overview Understanding the Codes Fire Alarm Systems (Manual

More information

Notifier by Honeywell: Non-Addressable Audible & Visual Alarm Devices. Approved to EN54-3/EN54-23

Notifier by Honeywell: Non-Addressable Audible & Visual Alarm Devices. Approved to EN54-3/EN54-23 Notifier by Honeywell: Non-Addressable Audible & Visual Alarm Devices Approved to EN54-3/EN54-23 Setting the Standard EN54-23 and how it affects you EN54-23 is a new European standard for Visual Alarm

More information

Minimum Standards for Engineers Practicing Fire Protection Engineering in the State of Oklahoma September 14, 2016

Minimum Standards for Engineers Practicing Fire Protection Engineering in the State of Oklahoma September 14, 2016 1. Introduction The intent of this document is to establish minimum standards for the practice of fire protection engineering within the State of Oklahoma as conducted by licensed professional engineers.

More information

By: Russell Bainbridge March 18th, 2016 FPE 596

By: Russell Bainbridge March 18th, 2016 FPE 596 By: Russell Bainbridge March 18th, 2016 FPE 596 Egress Analysis and Design California Polytechnic State University's Engineering IV building Fire Detection, Alarm and Communication Systems A warehouse

More information

TrueAlert Non-Addressable, Multi-Candela Notification Appliances Installation Instructions

TrueAlert Non-Addressable, Multi-Candela Notification Appliances Installation Instructions TrueAlert NonAddressable, MultiCandela Notification Appliances Installation Instructions PRODUCT IDENTIFICATION REFERENCE (See Page 4 for Detailed Product Specifications) Type Mount Model Color Operation

More information

BS 5839: Part THE CHANGES

BS 5839: Part THE CHANGES BS 5839: Part 1 2013 THE CHANGES INTRODUCTION This document has been created to summarise the main changes that have been made to the BS 5839 Part 1 2013. This data is correct at the time of publication

More information

Florida Building Code 2010

Florida Building Code 2010 Introduction Florida Building Code 2010 Chapter 9 Fire Protection Systems This course will cover specific sections of Chapter 9 that relate to fire alarm systems. While many contractors are familiar with

More information

SECTION : FIRE ALARM & DETECTION SYSTEMS

SECTION : FIRE ALARM & DETECTION SYSTEMS SECTION 28 31 10: FIRE ALARM & DETECTION SYSTEMS 1. GENERAL A. This section applies to fire detection/alarm system and carbon monoxide system components and equipment installed during new construction

More information

1 Exam Prep Fire Alarm Signaling Systems Tabs and Highlights

1 Exam Prep Fire Alarm Signaling Systems Tabs and Highlights 1 Exam Prep Fire Alarm Signaling Systems Tabs and Highlights These 1 Exam Prep Highlights are based on the Fire Alarm Signaling Systems, 4th Edition. Each Tabs sheet has five rows of tabs. Start with the

More information

Proposed Changes to NFPA

Proposed Changes to NFPA 2017 NFPA Conference & Expo Proposed Changes to NFPA 72-2019 Presented by: Manuelita David (SIG-FUN), Jensen Hughes Warren Olsen (SIG-SSS), Fire Safety Consultants, Inc. Merton Bunker (SIG-AAC), EYP Architecture

More information

FIRE ALARM AUDIBILITY IN EXISTING RESIDENTIAL OCCUPANCIES. 1 of 7 11/12/ :26 PM

FIRE ALARM AUDIBILITY IN EXISTING RESIDENTIAL OCCUPANCIES. 1 of 7 11/12/ :26 PM 1 of 7 11/12/2009 10:26 PM Skip Navigation Central Site Contact Us Site Map Français OFM HOME ABOUT THE OFM FIRE SERVICE FIRE PROTECTION FIRE SAFETY & PUBLIC EDUCATION LEGISLATION PUBLICATIONS RESOURCES

More information

El Reno Fire Department Fire Alarm Plan Review Worksheet

El Reno Fire Department Fire Alarm Plan Review Worksheet El Reno Fire Department Fire Alarm Plan Review Worksheet This Fire Alarm Plan Review Checklist is provided as a guide to assist with your Fire Alarm Plan Review Submittal requirements. Please contact us

More information

Fire Alarm, Water Flow Alarm & Signaling Systems

Fire Alarm, Water Flow Alarm & Signaling Systems Orange County Fire Authority Community Risk Reduction 1 Fire Authority Road, Building A, Irvine, CA 92602 www.ocfa.org 714-573-6100 Fire Alarm, Water Flow Alarm & Signaling Systems Guideline D-03 Serving

More information

Visual Alarm Devices. Presented prepared by Chris Orr

Visual Alarm Devices. Presented prepared by Chris Orr Visual Alarm Devices Presented prepared by Chris Orr Visual Alarm Devices The new standard AS7240.23 is based on EN54-23/ISO 7240.23 New Clause 3.22 (b) (xvi)&(xvii) introduces the requirements for VADs

More information

Signature Series Auto-Sync Output Module (CC1S)

Signature Series Auto-Sync Output Module (CC1S) Signature Series Auto-Sync Output Module (CC1S) Product description Mounting The Signature Series can be mounted in a North American 2-1/2 in (64 mm) deep 2-gang box or a standard 4 in square box 1-1/2

More information

Surviving Survivability A User s Guide to Survivable Fire Alarm Circuits Larry D. Rietz, SET 23 May 2018

Surviving Survivability A User s Guide to Survivable Fire Alarm Circuits Larry D. Rietz, SET 23 May 2018 Surviving Survivability A User s Guide to Survivable Fire Alarm Circuits Larry D. Rietz, SET 23 May 2018 Automatic FireAlarm Association SURVIVING SURVIVABILITY - A USER S GUIDE TO Larry D. Rietz, SET

More information

HIGH-RISE RETROFIT ORDINANCES - NO and NO

HIGH-RISE RETROFIT ORDINANCES - NO and NO INFORMATION BULLETIN / PUBLIC - BUILDING CODE REFERENCE NO.: LAMC 91.8604 Effective: 9-06-90 DOCUMENT NO. P/BC 2002-054 Revised: 4-15-03 Previously Issued As: MGD 88 HIGH-RISE RETROFIT ORDINANCES - NO.

More information

Second Revision No. 104-NFPA [ Section No ] Submitter Information Verification. Committee Statement

Second Revision No. 104-NFPA [ Section No ] Submitter Information Verification. Committee Statement of 1 9/22/2014 1:38 PM Second Revision No. 104-NFPA 72-2014 [ Section No. 3.3.3 ] 3.3.3 Accessible, Readily (Readily Accessible). Capable of being reached quickly for operation, renewal, or inspections

More information

MAINTENANCE OF FIRE PROTECTION DEVICES WITHIN RESIDENTIAL SUITES OF MULTI-FAMILY BUILDINGS

MAINTENANCE OF FIRE PROTECTION DEVICES WITHIN RESIDENTIAL SUITES OF MULTI-FAMILY BUILDINGS FIRE CODE BULLETIN December 2004 97 FCB 018 (R1) Page 1 of 5 BACKGROUND: MAINTENANCE OF FIRE PROTECTION DEVICES WITHIN RESIDENTIAL SUITES OF MULTI-FAMILY BUILDINGS Fire protection service companies are

More information

COUNTY OF KINGS KINGS COUNTY JAIL EXPANSION PHASE III

COUNTY OF KINGS KINGS COUNTY JAIL EXPANSION PHASE III SECTION 28 3111 - DIGITAL ADDRESSABLE FIRE ALARM SYSTEM PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. General provisions of the Contract, including General and Supplementary Conditions and Division 1 Specification

More information

CAFAA S 22 nd ANNUAL STATE AGENCY FORUM 09/28/17

CAFAA S 22 nd ANNUAL STATE AGENCY FORUM 09/28/17 STEVE SCHWARTZ (Consolidated Fire Protection) Q-01 NFPA 72 Chapter 18 Section 18.4.2.4, The standard evacuation signal shall be synchronized within a notification zone. We have been taught that a floor

More information

Emergency Voice Communication Systems

Emergency Voice Communication Systems We have made it easy for you to find a PDF Ebooks without any digging. And by having access to our ebooks online or by storing it on your computer, you have convenient answers with emergency voice communication

More information

Committee Input No NFPA [ Global Input ] Submitter Information Verification. Committee Statement. 1 of /20/ :02 AM

Committee Input No NFPA [ Global Input ] Submitter Information Verification. Committee Statement. 1 of /20/ :02 AM 1 of 213 10/20/2016 11:02 AM Committee Input No. 2505-NFPA 72-2016 [ Global Input ] Change the term visible to visual where appropriate Submitter Information Verification Submitter Full Name: SIG-NAS Organization:

More information

Addressing Sound Masking Requirements in the National Fire Alarm and Signaling Code and UL Standards

Addressing Sound Masking Requirements in the National Fire Alarm and Signaling Code and UL Standards Addressing Sound Masking Requirements in the National Fire Alarm and Signaling Code and UL Standards Wayne D. Moore, P.E., CFPS, SET Vice President JENSEN HUGHES 117 Metro Center Boulevard, Suite 1002

More information

Chapter 2: Definitions

Chapter 2: Definitions FLORIDA BUILDING CODE Existing Buildings 6 TH Edition (2017) Code Changes based on the document provided by DBPR - 2014 and 6th Edition (2017) Florida Building Code Comparison JUMP TO CHAPTER (click chapter

More information

Hospital Fire Alarm Systems Recurring Misapplications and Misused Requirements

Hospital Fire Alarm Systems Recurring Misapplications and Misused Requirements Hospital Fire Alarm Systems Recurring Misapplications and Misused Requirements Wayne D. Moore, P.E., CFPS Vice President, Jensen Hughes October 8, 2018 Hospital Fire Alarm Systems Recurring Misapplications

More information

STANDARDS UPDATE NOTICE (SUN) ISSUED: February 5, 2018

STANDARDS UPDATE NOTICE (SUN) ISSUED: February 5, 2018 STANDARDS UPDATE NOTICE (SUN) ISSUED: February 5, 2018 STANDARD INFORMATION Standard Number: NFPA 72 Standard Name: National Fire Alarm and Signaling Code Standard Edition and Issue Date: 2016 Edition

More information

5123: information. The graphic plan shall include, but may not be limited to: (a) A primary and secondary means of exit from each floor;

5123: information. The graphic plan shall include, but may not be limited to: (a) A primary and secondary means of exit from each floor; ACTION: Original DATE: 09/30/2005 1:17 PM 5123:2-3-11 Fire safety and emergency response plans. (A) Purpose The purpose of this rule is to ensure the safety of individuals residing in residential facilities

More information

Changes to NFPA 101A 2013 Edition for Health Care Facilities

Changes to NFPA 101A 2013 Edition for Health Care Facilities 2017 NFPA Conference & Expo Changes to NFPA 101A 2013 Edition for Health Care Facilities Presented by: William Koffel, P.E, FSFPE Lennon Peake, P.E. Koffel Associates Koffel Associates President Manager

More information

PROTECTED PROPERTY. City: State: Zip Code: ALARM SERVICE COMPANY. City: State: Zip Code: COMMENTS AND CLARIFICATIONS ALARM SYSTEM DESCRIPTION

PROTECTED PROPERTY. City: State: Zip Code: ALARM SERVICE COMPANY. City: State: Zip Code: COMMENTS AND CLARIFICATIONS ALARM SYSTEM DESCRIPTION Underwriters Laboratories Inc. FIRE ALARM SYSTEM PRE-INSPECTION DATA SHEETS PLEASE RETURN COMPLETED FORMS TO UL PRIOR TO INSPECTION PROTECTED PROPERTY City: State: Zip Code: ALARM SERVICE COMPANY File

More information

MODULE 8. Tying the Systems Together: Emergency Control Functions and Interfaces

MODULE 8. Tying the Systems Together: Emergency Control Functions and Interfaces MODULE 8 Tying the Systems Together: Emergency Control Functions and Interfaces 1 OVERVIEW OF MODULE 8 In this module we will: Describe all components, their arrangements and how the systems work Describe

More information

The 2013 National Fire Alarm and Signaling Code

The 2013 National Fire Alarm and Signaling Code ARE YOU A MEMBER OF AFAA? WHY SHOULD YOU BE A MEMBER BECAUSE YOUR BUSINESS IS IMPORTANT James Mongeau The 2013 National Fire Alarm and Signaling Code 1 NFPA 72 Organization Be*er organiza2on Easier to

More information

FIRE ALARM AUDIBILITY IN EXISTING RESIDENTIAL OCCUPANCIES

FIRE ALARM AUDIBILITY IN EXISTING RESIDENTIAL OCCUPANCIES FIRE ALARM AUDIBILITY IN EXISTING RESIDENTIAL OCCUPANCIES Office of the Fire Marshal and Emergency Management Preface This guideline updates TG-02-1998 published in June 1998. Portions of the guideline

More information

Riverside County Fire Department Office of the Fire Marshal Market St., Ste. 150, Riverside, CA Ph. (951) Fax (951)

Riverside County Fire Department Office of the Fire Marshal Market St., Ste. 150, Riverside, CA Ph. (951) Fax (951) Riverside County Fire Department Office of the Fire Marshal 2300 Market St., Ste. 150, Riverside, CA 92501 Ph. (951) 955-4777 Fax (951) 955-4886 Guideline Title: Residentially Based Care Facilities Group

More information

CONVENTIONAL AUDIBLE VISUAL

CONVENTIONAL AUDIBLE VISUAL Fast Installation, Safe Evacuation CONVENTIONAL AUDIBLE VISUAL www.kac.co.uk Setting the Standard with ENscape EN54-23 and how it affects you EN54-23 is a new European standard for Visual Alarm Devices

More information

CFAA Technical Seminar Ontario Building Code Updates to 2015

CFAA Technical Seminar Ontario Building Code Updates to 2015 CFAA Technical Seminar Ontario Building Code Updates to 2015 October 28, 2015 2015 Fire Alarm Updates Ontario Building Code Glenn Somerton P.Eng. Senior Code Specialist Morrison Hershfield Limited gsomerton@morrisonhershfield.com

More information

TrueAlert Multi-Candela Notification Appliances

TrueAlert Multi-Candela Notification Appliances TrueAlert Multi-Candela Notification Appliances UL, ULC, CSFM Listed; FM Approved* Features 24 VDC high intensity notification appliance common features: Xenon strobe with intensity selectable as 135,

More information

SOUTH AFRICAN NATIONAL STANDARD

SOUTH AFRICAN NATIONAL STANDARD ISBN 978-0-626-19281-5 SOUTH AFRICAN NATIONAL STANDARD Fire detection and alarm systems for buildings System design, installation and servicing Published by Standards South Africa 1 dr lategan road groenkloof

More information

Applying Performance-based Fire Alarm System Design Part 4

Applying Performance-based Fire Alarm System Design Part 4 Fire Alarm Notebook by Dean K. Wilson. P.E. Page 1 Applying Performance-based Fire Alarm System Design Part 4 by Dean K. Wilson, P.E. Over the course of the last four issues I have continued to discuss

More information

Standard for the Installation of Carbon Monoxide (CO) Detection and Warning Equipment

Standard for the Installation of Carbon Monoxide (CO) Detection and Warning Equipment NFPA 720 2015 Summary Standard for the Installation of Carbon Monoxide (CO) Detection and Warning Equipment TM, 7Oct14 CODE: Title, Standard, not Code Consistent with recent trend at NFPA, this document

More information

Carbon Monoxide Detection in Buildings Frequently Asked Questions

Carbon Monoxide Detection in Buildings Frequently Asked Questions What is carbon monoxide? Carbon Monoxide Detection in Buildings Frequently Asked Questions Carbon monoxide (CO) is a colorless, odorless, tasteless, poisonous gas that is produced by the incomplete burning

More information

UNOFFICIAL COPY OF SENATE BILL 735 A BILL ENTITLED

UNOFFICIAL COPY OF SENATE BILL 735 A BILL ENTITLED UNOFFICIAL COPY OF SENATE BILL 735 E4 5lr1315 By: Senator Grosfeld Introduced and read first time: February 4, 2005 Assigned to: Judicial Proceedings 1 AN ACT concerning A BILL ENTITLED 2 Public Safety

More information

AVAILABLE TO DOWNLOAD ON THE APOLLO APP. Pocket guide to. Fire Alarm Systems Design BS Standard

AVAILABLE TO DOWNLOAD ON THE APOLLO APP. Pocket guide to. Fire Alarm Systems Design BS Standard Pocket guide to Fire Alarm Systems Design BS 5839-1 Standard AVAILABLE TO DOWNLOAD ON THE APOLLO APP The Regulatory Reform (Fire Safety) Order (FSO) became law on 1 October 2006 Legally you must comply!

More information

INSPECTION AND TESTING FORM

INSPECTION AND TESTING FORM INSPECTION AND TESTING FORM Date: Time: SERVICE ORGANIZATION Name: Address: Representative: License No.: MONITORING ENTITY Contact: Monitoring Account Ref. No.: TYPE TRANSMISSION McCulloh Multiplex Digital

More information

Fire Alarm Systems Design. incorporating Amendment No.2. a guide to BS5839. Part1:2002

Fire Alarm Systems Design. incorporating Amendment No.2. a guide to BS5839. Part1:2002 a guide to Fire Alarm Systems Design BS5839 Part1:2002 incorporating Amendment No.2 The Regulatory Reform (Fire Safety) Order (RRO) became law on 1 October 2006 Legally you must comply! What is the RRO?

More information

ELEVATORS. Integration of Codes between Fire Alarm, Sprinklers, and Elevators 12/5/2017

ELEVATORS. Integration of Codes between Fire Alarm, Sprinklers, and Elevators 12/5/2017 12/5/2017 1 ELEVATORS Integration of Codes between Fire Alarm, Sprinklers, and Elevators Encore Electric Inc. Prepared By John McGovern and Jeffrey Engelstad 12/5/2017 Encore Electric Inc. 2 Agenda Basics

More information

NFPA 101, 2012 EDITION IMPACT ON NEW AND EXISTING HEALTH CARE FACILITIES

NFPA 101, 2012 EDITION IMPACT ON NEW AND EXISTING HEALTH CARE FACILITIES NFPA 101, 2012 EDITION IMPACT ON NEW AND EXISTING HEALTH CARE FACILITIES Sharon S. Gilyeat, P.E., Principal Koffel Associates, Inc. www.koffel.com sgilyeat@koffel.com Expertly Engineering Safety From Fire

More information

Overview of Fire Alarm Provisions Based on the 2012 IBC, IFC and NFPA 72, 2013 Edition

Overview of Fire Alarm Provisions Based on the 2012 IBC, IFC and NFPA 72, 2013 Edition Accreditation Overview of Fire Alarm Provisions Based on the 2012 IBC, IFC and NFPA 72, 2013 Primarily based on Section 907 Portions of Section 903 and 909 are included. Portions of Chapter 10 are included.

More information

The EN54 Part 2 and 4 Fire System

The EN54 Part 2 and 4 Fire System Scope of work: To design, supply, install and commission a Fire Alarm Control System in accordance with the details specified herein and in accordance with supplied drawings The EN54 Part 2 and 4 Fire

More information

Interbases. Sinteso FDSB221, FDSB228, FDSB229

Interbases. Sinteso FDSB221, FDSB228, FDSB229 Sinteso Interbases FDSB221, FDSB228, FDSB229 Sounder interbase, sounder beacon interbase, sounder interbase with supplementary optical indication for the automatically addressable detector bus FDnet Addressed

More information

109-B Concord Drive Casselberry, FL DynaFire.com INSPECTION AND TESTING FORM PER NFPA 72. Owner s Address: Owner's Phone Number:

109-B Concord Drive Casselberry, FL DynaFire.com INSPECTION AND TESTING FORM PER NFPA 72. Owner s Address: Owner's Phone Number: 109-B Concord Drive Casselberry, FL 32707 407.830.6500 DynaFire.com INSPECTION AND TESTING FORM PER NFPA 72 Pg 1 of 4 Equity One 11180600 Owner/Representative: WO#: _Customer#: 1550 NE Miami Garden Dr

More information

s Notification Appliances

s Notification Appliances s Notification Appliances Data Sheet Fire Safety Products AS & AH Audible Horn Strobe / Audible Horn Appliances Application: Indoor / Outdoor AS-MC-CW AS-MC-R AH-R AH-W Product Overview Fast installation

More information

SOCIETY OF FIRE PROTECTION ENGINEERS POSITION STATEMENT P THE ENGINEER AND THE TECHNICIAN DESIGNING FIRE PROTECTION SYSTEMS.

SOCIETY OF FIRE PROTECTION ENGINEERS POSITION STATEMENT P THE ENGINEER AND THE TECHNICIAN DESIGNING FIRE PROTECTION SYSTEMS. SOCIETY OF FIRE PROTECTION ENGINEERS POSITION STATEMENT P-01-05 THE ENGINEER AND THE TECHNICIAN DESIGNING FIRE PROTECTION SYSTEMS October, 2005 Society of Fire Protection Engineers - 1 - Position Statement

More information

Overview of Standards for CO Detection Products

Overview of Standards for CO Detection Products Overview of Standards for CO Detection Products Rev 1.1 1 General Overview... 3 2 Application and Installation Codes & Standards... 3 3 Product Standards... 4 4 Certified and Listed Products (Conforms

More information

ISO INTERNATIONAL STANDARD

ISO INTERNATIONAL STANDARD INTERNATIONAL STANDARD ISO 7240-19 First edition 2007-08-15 Fire detection and alarm systems Part 19: Design, installation, commissioning and service of sound systems for emergency purposes Systèmes de

More information

Construction Innovation Center Building 186

Construction Innovation Center Building 186 Construction Innovation Center Building 186 FPE 596 Professors Presented Culminating Experience in Fire Protection Engineering Christopher Pascual & Frederick W. Mowrer Christopher Torres Objective / Overview

More information

Evacuate everyone Sonos Pulse & Nexus Pulse

Evacuate everyone Sonos Pulse & Nexus Pulse Evacuate everyone Sonos Pulse & Nexus Pulse Available through distribution: www.discountfiresupplies.co.uk Tel: 01792 452 700 EN54-23 Fire Beacons In a fire, everyone matters. Sonos Pulse and Nexus Pulse

More information