Natural Ventilation A Green Smoke Control Approach

Size: px
Start display at page:

Download "Natural Ventilation A Green Smoke Control Approach"

Transcription

1

2 Natural Ventilation A Green Smoke Control Approach Presented By: William Koffel, P.E., FSFPE Adam Graybeal, P.E. Authored by: Erik Anderson, P.E Koffel Associates

3 Background New Engineering, Aviation, Computer & Mathematical Sciences Building (EACMS), University of Maryland Eastern Shore in Princess Anne, Maryland Construction completed early 2016

4 Design Intent Designed per: 2012 International Building Code (IBC) 2012 Life Safety Code (LSC) Amendments per State of Maryland and UM

5 Building Information Building Structure: Three (3) stories each approximately 15 ft (4.6m) 3-story atrium extends from the Ground Level up to a clearstory above the 3rd floor for an approximate height of 55 ft (16.8m).

6

7 EACMS Third Floor Plan

8 EACMS Fire Model Geometry

9 Design Approach Natural Smoke Exhaust System in Lieu of Mechanical Smoke Control System Used algebraic equations first (NFPA 92 and 204) Fire Dynamics Simulator (FDS) used to further evaluate anticipated conditions within atrium.

10 Design Approach Smoke exhausted from top of Atrium Tenable conditions maintained from the bottom of the atrium to 6 ft (1.8m) above the highest walking surface. Four (4) Design Fire Scenarios Axisymmetric and Spill Plume

11 Ground Level Center Fire Location

12 Ground Level - Underneath Stairs

13 Ground Level Axisymmetric Plume

14 Second Floor Opening in South Hallway

15 Design Fire Scenarios Constant 5 Megawatt (MW) for each fire Each fire scenario was modeled with: No wind, 30 mph (48 kmph) wind, 60 mph (96 kmph) wind. Directional wind Sensitivity analysis

16 Tenability Criteria Visibility was evaluated to be maintained for a period of at least 20 minutes. Minimum visibility distance of 30 ft (9.1 m)was cited as the threshold above which egress is impeded through the smoke layer.

17 Tenability Criteria Maximum temperature criteria: Maximum temperatures of 169 F (76 C) during egress Maximum temperature of 392 F (200 C)

18 Unique Design Considerations Awning Type Smoke Exhaust Windows Venting Locations and Size based on calculations methods from NFPA 204, Smoke and Heat Venting, 2012 Edition.

19

20 EACMS Fire Model Geometry

21 Unique Design Considerations Make-up air is provided by two sets of 6 ft x 8 ft (1.8 m x 2.4 m) double doors at each of the four entrances. Additional air from two extra vents by both of the East and West entrances.

22

23 Unique Design Considerations Actual venting area: 48 windows along the clearstory Each vent is 4.5 ft x 4.5 ft (1.4 m x 1.4 m) Total of 972 square feet (90 sq m) of actual venting Effective venting area = 340 sq ft (31.5 sq m)

24 Exhaust Activation Method Beam detection along the roof Sprinkler activation Manual means

25 Modeling Results No Wind *Activation time may be due to placement of sprinkler in relation to fire. **In the same model, another sprinkler activated after 89 seconds ***Sprinklers located on the 3 rd Floor in the South Hall

26 Normal Stack Effect Results *Sprinklers located on the 3 rd Floor in the South Hall

27 Reverse Stack Effect Results *Sprinklers located on the 3 rd Floor in the South Hall

28 Lessons Learned Natural ventilation can be used in lieu of mechanical smoke control for some building configurations. Decision to use natural ventilation must be done early in the design process. Design team buy-in. Allow time to coordinate system requirements with AHJ and make the appropriate architectural changes needed. Effect on building design and layout.

29 Lessons Learned NFPA 92 and 204 calcs provide a good estimate. Wind and stack effect significantly impact venting capability. LARGE vent openings are required. Remember the details: Window actuators (how far open?) Venting coefficient Automatic make-up air approach Listed smoke control panel/controls

30 Lessons Learned Sensitivity analysis required for model input variables such as vent arrangement, grid size, beam detection locations, and sprinkler activation temperature alter results. AHJ must ensure variables used are clearly indicated in any submitted fire modeling report.

31 Natural Ventilation A Green Smoke Control Approach Presented By: William Koffel, P.E., FSFPE Adam Graybeal, P.E. Authored by: Erik Anderson, P.E. Koffel Associates

Open to Below: A Discussion of Allowed Floor Openings. Jay A. Ierardi, Ph.D., P.E., LEED AP. Kevin S. Hastings, P.E., LEED AP

Open to Below: A Discussion of Allowed Floor Openings. Jay A. Ierardi, Ph.D., P.E., LEED AP. Kevin S. Hastings, P.E., LEED AP Open to Below: A Discussion of Allowed Floor Openings Kevin S. Hastings, P.E., LEED AP Jay A. Ierardi, Ph.D., P.E., LEED AP R.W. Sullivan Engineering (617) 523-8227, Fax (617) 523-8016 http://www.rwsullivan.com

More information

NFPA 45 NFPA 211 NFPA 1600

NFPA 45 NFPA 211 NFPA 1600 NFPA 45 NFPA 211 NFPA 1600 Prepared by: William E. Koffel, P.E., FSFPE Expertly Engineering Safety From Fire 1 Objectives Overview of the NFPA process Understand the scope and application of NFPA 45, NFPA

More information

Considerations in the Design of Smoke Management Systems for Atriums

Considerations in the Design of Smoke Management Systems for Atriums Construction Technology Update No. 48 Considerations in the Design of Smoke Management Systems for Atriums by G.D. Lougheed This Update discusses the use of an engineered approach to the design of smoke

More information

Statue of Liberty: A Risk Analysis

Statue of Liberty: A Risk Analysis Statue of Liberty: A Risk Analysis Bruce Campbell, FSFPE VP DOE Services National Park Service Agenda Overview of Project Scope Evaluation Steps Task 1 Code Analysis Task 2 Fire Modeling Task 3 Egress

More information

ICC CODE CORNER 2012 IFC Code & Commentary

ICC CODE CORNER 2012 IFC Code & Commentary SECTION 909 SMOKE CONTROL SYSTEMS 909.1 Scope and purpose. This section applies to mechanical or passive smoke control systems when they are required for new buildings or portions thereof by provisions

More information

Changes to NFPA 101A 2013 Edition for Health Care Facilities

Changes to NFPA 101A 2013 Edition for Health Care Facilities 2017 NFPA Conference & Expo Changes to NFPA 101A 2013 Edition for Health Care Facilities Presented by: William Koffel, P.E, FSFPE Lennon Peake, P.E. Koffel Associates Koffel Associates President Manager

More information

ANALYSIS OF SMOKE MOVEMENT IN A BUILDING VIA ELEVATOR SHAFTS

ANALYSIS OF SMOKE MOVEMENT IN A BUILDING VIA ELEVATOR SHAFTS ANALYSIS OF SMOKE MOVEMENT IN A BUILDING VIA ELEVATOR SHAFTS Prepared for Smoke Safety Council 6775 SW 111 th Avenue, Suite 10 Beaverton, OR 97008 Prepared by Jesse J. Beitel Alison J. Wakelin Craig L.

More information

Tunnel Fire Dynamics and Evacuation Simulations

Tunnel Fire Dynamics and Evacuation Simulations Tunnel Fire Dynamics and Evacuation Simulations James Priest, PhD & James Niehoff DGS-SEE Seminar on Fire Protection for Physics Research Facilities 7 & 8 October 2015 Introduction (Background) Presentation

More information

Smoke Management in High-Rise Structures

Smoke Management in High-Rise Structures Smoke Management in High-Rise Structures Most modern building codes define a high-rise structure as a building greater than 75 feet in height from the lowest level of fire department vehicle access to

More information

Life Safety Damper Installation ASHRAE St Louis Chapter Feb. 9,2015. Peter McDonnell, PE, LEED AP BD+C McClure Engineering

Life Safety Damper Installation ASHRAE St Louis Chapter Feb. 9,2015. Peter McDonnell, PE, LEED AP BD+C McClure Engineering Life Safety Damper Installation ASHRAE St Louis Chapter Feb. 9,2015 Peter McDonnell, PE, LEED AP BD+C McClure Engineering UL DAMPER TEST STANDARDS UL 555 - FIRE DAMPERS UL555S SMOKE DAMPERS UL555C CEILING

More information

Human Factors - Egress Analysis for High Hazard Occupancies. Presented by: Michael J. Klemenz, PE, SFPE

Human Factors - Egress Analysis for High Hazard Occupancies. Presented by: Michael J. Klemenz, PE, SFPE Human Factors - Egress Analysis for High Hazard Occupancies Presented by: Michael J. Klemenz, PE, SFPE Group H Other SFPE presenters today discussed issues relevant to Group H This presentation addresses

More information

Computer Simulation Investigation on the Effect of Channelled and Unchannelled Screens on Smoke Contamination in Atriums Upper Balconies

Computer Simulation Investigation on the Effect of Channelled and Unchannelled Screens on Smoke Contamination in Atriums Upper Balconies MATEC Web of Conferences 13, 27 (214) DOI: 1.151/ matecconf/ 21413 27 C Owned by the authors, published by EDP Sciences, 214 Computer Simulation Investigation on the Effect of Channelled and Unchannelled

More information

Chapter 17, Initiating Devices

Chapter 17, Initiating Devices Chapter 17, Initiating Devices Summary. Chapter 17 was Chapter 5 in NFPA 72-2007. The term authority having jurisdiction is replaced in some sections by the term other governing laws, codes, or standards.

More information

COSTCO, SAN FRANCISCO A PRESCRIPTIVE AND PERFORMANCE BASED ANALYSIS OF FIRE PROTECTION SYSTEMS AND DESIGN

COSTCO, SAN FRANCISCO A PRESCRIPTIVE AND PERFORMANCE BASED ANALYSIS OF FIRE PROTECTION SYSTEMS AND DESIGN COSTCO, SAN FRANCISCO A PRESCRIPTIVE AND PERFORMANCE BASED ANALYSIS OF FIRE PROTECTION SYSTEMS AND DESIGN Presented by Ian Levine June, 2016 Photo courtesy of Google Maps PRESENTATION OVERVIEW BUILDING

More information

2012 International Fire Code Significant Changes. IFC Background. Purpose IBC and 2012 NFPA 101 Significant Means of Egress Changes

2012 International Fire Code Significant Changes. IFC Background. Purpose IBC and 2012 NFPA 101 Significant Means of Egress Changes 2012 International Fire Code Significant Changes Andrew M. Schneider, P.E. Senior Fire Protection Engineer aschneider@koffel.com Koffel Associates, Inc. www.koffel.com Expertly Engineering Safety From

More information

Numerical investigation on the effect of channelled and unchannelled screens on smoke contamination in atriums upper balconies with open upstand

Numerical investigation on the effect of channelled and unchannelled screens on smoke contamination in atriums upper balconies with open upstand Numerical investigation on the effect of channelled and unchannelled screens on smoke contamination in atriums upper balconies with open upstand Mohammed Mutafi 1, Mohammad Nasif 1*, William Pao 1 and

More information

Richard B. Alpert, P.E. Senior FPE, Clark Nexsen

Richard B. Alpert, P.E. Senior FPE, Clark Nexsen Richard B. Alpert, P.E. Senior FPE, Clark Nexsen Clark Nexsen is a Registered Provider with The American Institute of Architects Continuing Education Systems (AIA/CES). Credit(s) earned on completion of

More information

ICC CODE CORNER 2012 IFC Code & Commentary

ICC CODE CORNER 2012 IFC Code & Commentary SECTION 910 SMOKE AND HEAT VENTS 910.1 General. Where required by this code or otherwise installed, smoke and heat vents or mechanical smoke exhaust systems and draft curtains shall conform to the requirements

More information

FIRE ALARM SYSTEMS & 780 CMR. Dave LeBlanc, PE, FSFPE March 17, 2015

FIRE ALARM SYSTEMS & 780 CMR. Dave LeBlanc, PE, FSFPE March 17, 2015 FIRE ALARM SYSTEMS & 780 CMR Dave LeBlanc, PE, FSFPE March 17, 2015 BIOGRAPHY David J. LeBlanc, PE, FSFPE BS EE & MS FPE - WPI 23 Years PE Technical Committee Member NFPA72 - National Fire Alarm Code NFPA3

More information

Virtual Compartment: An Alternative Approach to Means of Egress Design in Airport Pedestrian Tunnel

Virtual Compartment: An Alternative Approach to Means of Egress Design in Airport Pedestrian Tunnel Virtual : An Alternative Approach to Means of Egress Design in Airport Pedestrian Tunnel Xiaolei Chen, PhD California State University, Los Angeles, United States Ning (Frank) Wang, P.E. Jensen Hughes,

More information

PROPOSAL BALLOT DUE BY: Thursday, September 18, 2008

PROPOSAL BALLOT DUE BY: Thursday, September 18, 2008 PROPOSAL BALLOT DUE BY: Thursday, September 18, 2008 NFPA 204 SMO-AAA Standard for Smoke and Heat Venting Staff Liaison: Return Completed Ballot To: Jill McGovern E-Mail to jmcgovern@nfpa.org Fax to 617-984-7110

More information

Table EXIT ACCESS TRAVEL DISTANCE a OCCUPANCY SYSTEM SYSTEM. A, E, F-1, I-1, M, b,d R, S-1. B c. F-2, S-2, U c

Table EXIT ACCESS TRAVEL DISTANCE a OCCUPANCY SYSTEM SYSTEM. A, E, F-1, I-1, M, b,d R, S-1. B c. F-2, S-2, U c Table 1015.1 EXIT ACCESS TRAVEL DISTANCE a WITHOUT SPRINKLER WITH SPRINKLER OCCUPANCY SYSTEM SYSTEM A, E, F-1, I-1, M, 200 250 b,d R, S-1 B 200 300 c F-2, S-2, U 300 400 c No Change to Other Entries in

More information

Case Study 1 Underground Car Park

Case Study 1 Underground Car Park Case Study 1 Underground Car Park Dorota Brzezińska 1, Janusz Paliszek 2, Piotr Smardz 2, Renata Ollesz 1, Karol Kaczor 2 1 Lodz University of Technology, GRID - Lodz, 2 INBEPO Wroclaw, Poland Building

More information

Figure 1. Structure Used For the Simulations.

Figure 1. Structure Used For the Simulations. OVERVIEW: Vent, Enter, Search (VES) is one of the most talked about tactics in the fire service today. When used correctly, its positive impact can be measured by the lives it saves. The VES method is

More information

Fire Protection Analysis DCI Data Center Building

Fire Protection Analysis DCI Data Center Building Fire Protection Analysis DCI Data Center Building California Polytechnic State University FPE 596 Culminating Experience in Fire Protection Engineering Bryan Hathaway M.S. Fire Protection Engineering -

More information

Not-So-Dead Air Space

Not-So-Dead Air Space Fire Alarm Notebook by Dean K. Wilson. P.E. Page 1 Not-So-Dead Air Space by Dean K. Wilson, P.E. Question: As the Authority Having Jurisdiction for my township, I have just received plans for a new fire

More information

Fire Hazard Analysis of Technical Area 53 Building 1

Fire Hazard Analysis of Technical Area 53 Building 1 Fire Hazard Analysis of Technical Area 53 Building 1 June 11, 2015 LA-UR-15-23589 Slide 1 Introduction Brett Noakes Los Alamos National Laboratory Los Alamos, New Mexico Slide 2 Outline Background of the

More information

Will Clay Spring 2014

Will Clay Spring 2014 Will Clay Spring 2014 1. Project Overview 2. Prescriptive Requirements 3. Existing Requirements 4. Performance Evaluation 5. Conclusions RJA-Houston since 2010 Hired as FP/LS consultants by architect in

More information

Shut Down The Fan: A Reprise by Dean K. Wilson, P.E.

Shut Down The Fan: A Reprise by Dean K. Wilson, P.E. Fire Alarm Notebook by Dean K. Wilson. P.E. Page 1 Shut Down The Fan: A Reprise by Dean K. Wilson, P.E. Question: My grandfather passed away last summer. He had spent many years as a fire fighter. Among

More information

WHITE PLAINS SMOKE CONTROL CODE PART 1. GENERAL REQUIREMENTS

WHITE PLAINS SMOKE CONTROL CODE PART 1. GENERAL REQUIREMENTS WHITE PLAINS SMOKE CONTROL CODE a. Application of Code. PART 1. GENERAL REQUIREMENTS The following uniform standards and procedures shall apply to the design, installation and testing of new smoke purge

More information

Maintaining Building and Fire Safety During Active Assailant Events and Other Terrorist Events

Maintaining Building and Fire Safety During Active Assailant Events and Other Terrorist Events Position Statement Maintaining Building and Fire Safety During Active Assailant Events and Other Terrorist Events Maintaining school safety in light of recent terrorist events is challenging for everyone,

More information

El Reno Fire Department Fire Alarm Plan Review Worksheet

El Reno Fire Department Fire Alarm Plan Review Worksheet El Reno Fire Department Fire Alarm Plan Review Worksheet This Fire Alarm Plan Review Checklist is provided as a guide to assist with your Fire Alarm Plan Review Submittal requirements. Please contact us

More information

Common Building Code Misinterpretations

Common Building Code Misinterpretations Common Building Code Misinterpretations Presented by: Ron Melucci, P.E. Technical Manager, FP Division Engineering Planning and Management, Inc. rbm@epm inc.com www.epm inc.com 508 875 2121 Engineering

More information

Narrative Reports As Regulated by 780 CMR, Section 903.0

Narrative Reports As Regulated by 780 CMR, Section 903.0 EXHIBIT 20 Narrative Reports As Regulated by 780 CMR, Section 903.0 903.1.1 - FIRE PROTECTION CONSTRUCTION DOCUMENTS a. Basis (methodology) of design for the protection of the occupancy and hazard for

More information

SMOKE MANAGEMENT AND EGRESS ANALYSIS OF A SPORTS ARENA USING THE PERFORMANCE-BASED DESIGN

SMOKE MANAGEMENT AND EGRESS ANALYSIS OF A SPORTS ARENA USING THE PERFORMANCE-BASED DESIGN , Volume 4, Number 2, p.73-83, 2003 SMOKE MANAGEMENT AND EGRESS ANALYSIS OF A SPORTS ARENA USING THE PERFORMANCE-BASED DESIGN K.H. Yang and C.S. Yang Mechanical Engineering Department, National Sun Yat-Sen

More information

CAN/ULC-S1001, INTEGRATED SYSTEMS TESTING OF FIRE PROTECTION & LIFE SAFETY SYSTEMS Simon Crosby, LEL, CET, CFPS October 21, 2015

CAN/ULC-S1001, INTEGRATED SYSTEMS TESTING OF FIRE PROTECTION & LIFE SAFETY SYSTEMS Simon Crosby, LEL, CET, CFPS October 21, 2015 CAN/ULC-S1001, INTEGRATED SYSTEMS TESTING OF FIRE PROTECTION & LIFE SAFETY SYSTEMS Simon Crosby, LEL, CET, CFPS October 21, 2015 Fire Commissioning in Canadian Codes and Standards BACKGROUND Why Commissioning?

More information

FIRE/SMOKE BARRIER FUNDAMENTALS

FIRE/SMOKE BARRIER FUNDAMENTALS FIRE/SMOKE BARRIER FUNDAMENTALS William E. Koffel, P.E., FSFPE President Koffel Associates, Inc. www.koffel.com wkoffel@koffel.com Expertly Engineering Safety From Fire OBJECTIVE Identify the different

More information

FIRE AND SAFETY PROJECT REVIEW REPORT

FIRE AND SAFETY PROJECT REVIEW REPORT 1. A001 2. A001 3. A001 4. D102/103 5. A102/103 *VA enforces/applies the National Fire Protection Association (NFPA) 101 (current edition is 2015) and not the International Building Code (IBC). Ideally

More information

CLOUD CEILINGS: FIRE DYNAMICS AND CODE CONTEXT

CLOUD CEILINGS: FIRE DYNAMICS AND CODE CONTEXT Peterson Guadagnolo Consulting Engineers PC CLOUD CEILINGS: FIRE DYNAMICS AND CODE CONTEXT 1 November 7, 2016 AGENDA Introduction New York State Code - Update Ceiling Types Fire Dynamics Compartment Fire

More information

Recent BRANZFIRE enhancements and validation

Recent BRANZFIRE enhancements and validation Recent BRANZFIRE enhancements and validation Michael Spearpoint University of Canterbury Summary BRANZFIRE is a multi-compartment fire zone model that has been under development since 1996 predominately

More information

Smoke Layer Height and Heat Flow through a Door

Smoke Layer Height and Heat Flow through a Door Smoke Layer Height and Heat Flow through a Door 2018 Smoke Layer Height and Heat Flow through a Door In this tutorial you will simulate a growing fire in the corner of a 5m x 5m room. The room has a 1m

More information

The Residences at Christina Landing Wilmington, DE

The Residences at Christina Landing Wilmington, DE 5.0 FIRE PROTECTION EXISTING CONDITIONS 5.1 Project Specific Fire Protection Data Codes, Regulations, and Standards Building Officials and Code administrators (BOCA) National Building Code [1996] with

More information

SMOKE CONTROL: ISSUES / APPROACHES. Smoke, Not Flame

SMOKE CONTROL: ISSUES / APPROACHES. Smoke, Not Flame SMOKE CONTROL: ISSUES / APPROACHES Ball State Architecture ENVIRONMENTAL SYSTEMS 2 Grondzik 1 Smoke, Not Flame The most significant cause of death in building fires is smoke, which accounted for 73% of

More information

Evaluation of the NFPA 72 Spacing Requirements for Waffle Ceilings

Evaluation of the NFPA 72 Spacing Requirements for Waffle Ceilings Evaluation of the NFPA 72 Spacing Requirements for Waffle Ceilings Stephen M. Olenick 1, Richard J. Roby, Douglas J. Carpenter, and Adam Goodman Combustion Science & Engineering, Inc. 8940 Old Annapolis

More information

An Overview to Designing Smoke-Control Systems

An Overview to Designing Smoke-Control Systems The following article was published in ASHRAE Journal, June, 2002. Copyright 2002 American Society of Heating, Refrigerating and Air- Conditioning Engineers, Inc. It is presented for educational purposes

More information

Case Study of Underground Car Park. Team Japan

Case Study of Underground Car Park. Team Japan 11th Conference on Performance Based Codes and Fire Safety Design Methods Case Study of Underground Car Park Team Japan We focused on the characteristics of the fire behavior of car fire. Car fire is not

More information

1. Revise , from what was done by Second Revision SR-95 (Annual 2014 revision cycle NFPA 101 Second Draft), to read as follows:

1. Revise , from what was done by Second Revision SR-95 (Annual 2014 revision cycle NFPA 101 Second Draft), to read as follows: NFPA 101 -Proposed 2015 Edition Life Safety Code TIA Log No. 1130 Reference: 12.4.1, 13.4.1, A.12.4.1, and A.13.4.1 Comment Closing Date: April 18, 2014 Submitter: Jeffrey Tubbs, Arup and Michael DiMascio,

More information

SPRINKLER PROTECTION OF COMBUSTIBLE CONCEALLED SPACES WITH LESS THAN 6 BETWEEN OPPOSITE FACES IN CAVITY.

SPRINKLER PROTECTION OF COMBUSTIBLE CONCEALLED SPACES WITH LESS THAN 6 BETWEEN OPPOSITE FACES IN CAVITY. STATE OF LOUISIANA DEPARTMENT OF PUBLIC SAFETY AND CORRECTIONS OFFICE OF STATE FIRE MARSHAL CODE ENFORCEMENT AND BUILDING SAFETY 8181 INDEPENDENCE BOULEVARD, BATON ROUGE, LA 70806 800-256-5452 225-925-4920

More information

TENABILITY CRITERIA IN UNIQUE SITUATIONS AND ATYPICAL BUILDINGS

TENABILITY CRITERIA IN UNIQUE SITUATIONS AND ATYPICAL BUILDINGS TENABILITY CRITERIA IN UNIQUE SITUATIONS AND ATYPICAL BUILDINGS Arthur H. Gager III, PE and Gary Dominguez 1 Jensen Hughes agager@jensenhughes.com 2 Jensen Hughes gdominguez@jensehughes.com Abstract. FDS

More information

Report on First Revisions with Statement June 2014 NFPA 101

Report on First Revisions with Statement June 2014 NFPA 101 101 FR7040 SAF-MER (36.1.1.4) 36.1.1.4 The provisions of this chapter shall apply to life safety requirements for all new mercantile buildings. Specific requirements shall apply to suboccupancy groups,

More information

American Fire Sprinkler Association. An Introduction to the IBC and IFC

American Fire Sprinkler Association. An Introduction to the IBC and IFC American Fire Sprinkler Association Presents An Introduction to the IBC and IFC October 13, 2005 Speaker Roland Huggins, P.E. Vice President of Engineering and Technical Services American Fire Sprinkler

More information

Case Study 2 (Production and Storage Buildings) - Spain

Case Study 2 (Production and Storage Buildings) - Spain Case Study 2 (Production and Storage Buildings) - Spain OBJECTIVE Developed by the SFPE Spanish Chapter Editor: Jimmy Jönsson, JVVA Fire & Risk The objective of this case study is to show how a project

More information

CAN/ULC-S INTEGRATED SYSTEMS TESTING OF FIRE PROTECTION AND LIFE SAFETY SYSTEMS

CAN/ULC-S INTEGRATED SYSTEMS TESTING OF FIRE PROTECTION AND LIFE SAFETY SYSTEMS 2013 Randal Brown & Associates Engineering Ltd. 1 RANDAL BROWN & ASSOCIATES ENGINEERING LTD. CONSULTING ENGINEERS LIFE SAFETY & FIRE PROTECTION 105 6 LANSING SQUARE TORONTO, ONTARIO CAN/ULC-S1001-11 INTEGRATED

More information

Fire Safety Evaluation of Existing Manufactured Educational Building Covered by Section 423 of the Florida Building Code

Fire Safety Evaluation of Existing Manufactured Educational Building Covered by Section 423 of the Florida Building Code Walker Engineering, Inc. 833 Rockingham Road Birmingham Alabama 35235-2625 205-854-0160 205-854-0160 (Fax) Fire Safety Evaluation of Existing Manufactured Educational Building Covered by Section 423 of

More information

Minimum Standards for Engineers Practicing Fire Protection Engineering in the State of Oklahoma September 14, 2016

Minimum Standards for Engineers Practicing Fire Protection Engineering in the State of Oklahoma September 14, 2016 1. Introduction The intent of this document is to establish minimum standards for the practice of fire protection engineering within the State of Oklahoma as conducted by licensed professional engineers.

More information

UNIVERSITY OF MISSOURI Fire Protection System Design 2016 Q1

UNIVERSITY OF MISSOURI Fire Protection System Design 2016 Q1 GENERAL: 1. All fire protection systems shall be installed in accordance with the International Fire Code and applicable NFPA standards. This guideline provides additional requirements for the design and

More information

Fire and smoke management in a uni-directional road tunnel for a congested traffic condition

Fire and smoke management in a uni-directional road tunnel for a congested traffic condition Fire and smoke management in a uni-directional road tunnel for a congested traffic condition Y Liu, J Munro Parsons Brinckerhoff Australia B Dandie Thiess Pty Ltd., Australia ABSTRACT Emergency smoke ventilation

More information

CAN/ULC S Integrated Systems Testing of Fire Protection and Life Safety Systems and Fire Protection Commissioning

CAN/ULC S Integrated Systems Testing of Fire Protection and Life Safety Systems and Fire Protection Commissioning CAN/ULC S1001-11 Integrated Systems Testing of Fire Protection and Life Safety Systems and Fire Protection Commissioning Presentation To: Canadian Fire Alarm Association (CFAA) National Capital Region

More information

Building Description Applicable Codes & Standards Prescriptive Requirements. Performance Based Design

Building Description Applicable Codes & Standards Prescriptive Requirements. Performance Based Design June 15, 2017 Building Description Applicable Codes & Standards Prescriptive Requirements Structural Fire Protection Fire Sprinkler Fire Alarm Means of Egress Performance Based Design 2 3 Semiconductor

More information

Fire Protection System and Life Safety Evaluation. Building X. Anthony W. Sublett. Culminating Project

Fire Protection System and Life Safety Evaluation. Building X. Anthony W. Sublett. Culminating Project Fire Protection System and Life Safety Evaluation Of Building X By Anthony W. Sublett Culminating Project Presented to the Faculty of the Graduate School of California Polytechnic State University in Partial

More information

Building & Fire Code Academy. Building Better With Our Greatest Resource Education. Welcome!

Building & Fire Code Academy. Building Better With Our Greatest Resource Education. Welcome! Building & Fire Code Academy Building Better With Our Greatest Resource Education Welcome! Understanding the Sprinkler System Design Alternatives in the 2015 International Why inspect, test and maintain?

More information

Taming the Health Care Building Codes NFPA vs. The International and Chicago Building Codes JENSEN & HALSTEAD LTD.

Taming the Health Care Building Codes NFPA vs. The International and Chicago Building Codes JENSEN & HALSTEAD LTD. Taming the Health Care Building Codes NFPA vs. The International and Chicago Building Codes Comparing the Codes: NFPA 101 Life Safety Code (2000) (NFPA) International Building Code (2012) (IBC) Chicago

More information

PLAN REVIEW SUBMITTAL GUIDE

PLAN REVIEW SUBMITTAL GUIDE PLAN REVIEW SUBMITTAL GUIDE Plans, specifications and other construction documentation for the initial plan review should be as complete as possible at the time of submittal. Use this convenient guide

More information

Module 7. Control of Smoke & Highlights of Code Requirements

Module 7. Control of Smoke & Highlights of Code Requirements Module 7 Control of Smoke & Highlights of Code Requirements 1 Module 7 Overview This module will cover: 1. The requirements of smoke control in the Ohio Building Code Section 909 2. The differences between

More information

FIRE PROTECTION AND SAFETY ANALYSIS FOR AN OFFICE HIGH RISE BUILDING. Fabio Mazza June 2016

FIRE PROTECTION AND SAFETY ANALYSIS FOR AN OFFICE HIGH RISE BUILDING. Fabio Mazza June 2016 FIRE PROTECTION AND SAFETY ANALYSIS FOR AN OFFICE HIGH RISE BUILDING Fabio Mazza June 2016 Introduction Codes & Standards Building description Performance based design Prescriptive based design Structural

More information

NFPA 101, 2012 EDITION IMPACT ON NEW AND EXISTING HEALTH CARE FACILITIES

NFPA 101, 2012 EDITION IMPACT ON NEW AND EXISTING HEALTH CARE FACILITIES NFPA 101, 2012 EDITION IMPACT ON NEW AND EXISTING HEALTH CARE FACILITIES Sharon S. Gilyeat, P.E., Principal Koffel Associates, Inc. www.koffel.com sgilyeat@koffel.com Expertly Engineering Safety From Fire

More information

CAN/ULC-S1001, INTEGRATED SYSTEMS TEST OF FIRE PROTECTION AND LIFE SAFETY SYSTEMS

CAN/ULC-S1001, INTEGRATED SYSTEMS TEST OF FIRE PROTECTION AND LIFE SAFETY SYSTEMS RANDAL BROWN & ASSOCIATES ENGINEERING LTD. CONSULTING ENGINEERS LIFE SAFETY & FIRE PROTECTION 105 6 LANSING SQUARE TORONTO, ONTARIO CAN/ULC-S1001, INTEGRATED SYSTEMS TEST OF FIRE PROTECTION AND LIFE SAFETY

More information

VIRTUAL FIRES via COMPUTERS

VIRTUAL FIRES via COMPUTERS VIRTUAL FIRES via COMPUTERS Robert N. Meroney Wind Engineering Software Wind Engineering and Fluids Laboratory Civil and Environmental Engineering Colorado State University, Fort Collins, CO Paper prepared

More information

Module 3. Water-Based Suppression Systems (WBSS) Part II: Highlights of Code Requirements

Module 3. Water-Based Suppression Systems (WBSS) Part II: Highlights of Code Requirements Module 3 Water-Based Suppression Systems (WBSS) Part II: Highlights of Code Requirements 1 WATER-BASED SUPPRESSION SYSTEMS-PART TWO This module covers: 1. Ohio Building Code requirements and when and why

More information

Construction Warehouse. FPE 596 Culminating Experience In Fire Protection Engineering Final Project (Spring 2014) By Ben Johnson

Construction Warehouse. FPE 596 Culminating Experience In Fire Protection Engineering Final Project (Spring 2014) By Ben Johnson Construction Warehouse FPE 596 Culminating Experience In Fire Protection Engineering Final Project (Spring 2014) By Ben Johnson 1 Statement of Disclaimer This project report is a result of a class assignment;

More information

Construction Innovation Center Building 186

Construction Innovation Center Building 186 Construction Innovation Center Building 186 FPE 596 Professors Presented Culminating Experience in Fire Protection Engineering Christopher Pascual & Frederick W. Mowrer Christopher Torres Objective / Overview

More information

By: Russell Bainbridge March 18th, 2016 FPE 596

By: Russell Bainbridge March 18th, 2016 FPE 596 By: Russell Bainbridge March 18th, 2016 FPE 596 Egress Analysis and Design California Polytechnic State University's Engineering IV building Fire Detection, Alarm and Communication Systems A warehouse

More information

Fire Research and Education at the University of Maryland

Fire Research and Education at the University of Maryland Fire Research and Education at the University of Maryland J. G. Quintiere Department of Fire Protection Engineering March 7,8 2005 2nd Int. Symp. 21st Century Center of Excellence Program History of FPE

More information

Stairwell Pressurization Systems

Stairwell Pressurization Systems Course No: M05-022 Credit: 5 PDH A. Bhatia Continuing Education and Development, Inc. 9 Greyridge Farm Court Stony Point, NY 10980 P: (877) 322-5800 F: (877) 322-4774 info@cedengineering.com Introduction

More information

Prepared for: Professor Frederick W. Mowrer, PhD, P.E. Professor Christopher Pascual, PhD, P.E

Prepared for: Professor Frederick W. Mowrer, PhD, P.E. Professor Christopher Pascual, PhD, P.E Fire and Life Safety Analysis of The Production Facility (PF) - 870 Sandia National Laboratories, Albuquerque, New Mexico USA November 3, 2017 FPE596 Culminating Final Project Report By Nolan J. Baker,

More information

D. The work addressed in this section consists of a fire protection system, which may include coordination with one or more of the following:

D. The work addressed in this section consists of a fire protection system, which may include coordination with one or more of the following: PART 1 GENERAL 1.01 Scope of Standard A. This standard provides general requirements of Sam Houston State University for the design and construction of standpipe systems to include combination standpipe

More information

NUMERICAL STUDIES ON BARE CABIN FIRES WITH OPERATION OF SMOKE EXTRACTION SYSTEM

NUMERICAL STUDIES ON BARE CABIN FIRES WITH OPERATION OF SMOKE EXTRACTION SYSTEM , Volume 11, Number 2, p.43-48, 2012 NUMERICAL STUDIES ON BARE CABIN FIRES WITH OPERATION OF SMOKE EXTRACTION SYSTEM Q. Kui Institute of Building Fire Research, China Academy of Building Research, Beijing,

More information

REVIEW OF TECHNICAL STANDARDS AND CALCULATION METHODS FOR DIMENSIONING OF SMOKE AND HEAT CONTROL SYSTEMS IN CASE OF FIRE IN UNDERGROUND CAR PARKS

REVIEW OF TECHNICAL STANDARDS AND CALCULATION METHODS FOR DIMENSIONING OF SMOKE AND HEAT CONTROL SYSTEMS IN CASE OF FIRE IN UNDERGROUND CAR PARKS REVIEW OF TECHNICAL STANDARDS AND CALCULATION METHODS FOR DIMENSIONING OF SMOKE AND HEAT CONTROL SYSTEMS IN CASE OF FIRE IN UNDERGROUND CAR PARKS Nikola TANASIĆ, Tomislav SIMONOVIĆ, Miloš IVOŠEVIĆ, Branislav

More information

Culminating Project. Fire Protection and Life Safety Engineering Analysis. Cal Poly. Center for Science and Mathematics. Fire Protection Engineering

Culminating Project. Fire Protection and Life Safety Engineering Analysis. Cal Poly. Center for Science and Mathematics. Fire Protection Engineering Culminating Project Fire Protection and Life Safety Engineering Analysis Fire Protection Engineering California Polytechnic State University Center for Science and Mathematics Cal Poly San Luis Obispo,

More information

ISO/TR TECHNICAL REPORT. Fire-safety engineering Technical information on methods for evaluating behaviour and movement of people

ISO/TR TECHNICAL REPORT. Fire-safety engineering Technical information on methods for evaluating behaviour and movement of people TECHNICAL REPORT ISO/TR 16738 First edition 2009-08-01 Fire-safety engineering Technical information on methods for evaluating behaviour and movement of people Ingénierie de la sécurité incendie Informations

More information

(h) Pesticide Application.

(h) Pesticide Application. Fire Code Cannabis Amendment Section 13.20.066 is added to the Marysville Municipal Code to read in its entirety as follows: 13.20.066 Cannabis Growing, Processing, or Extraction Facilities (a) Application.

More information

2015 SFPE Europe Conference on Fire Safety Engineering

2015 SFPE Europe Conference on Fire Safety Engineering 2015 SFPE Europe Conference on Fire Safety Engineering THE FSE APPROACH FOR A HISTORICAL BUILDING IN LIGHT OF THE ITALIAN STANDARDS. Simonetto Sacco Luciano Nigro HUGHES ASSOCIATES EUROPE, srl FIRE SCIENCE

More information

MOBILE FIRE - RESCUE DEPARTMENT FIRE CODE ADMINISTRATION

MOBILE FIRE - RESCUE DEPARTMENT FIRE CODE ADMINISTRATION MOBILE FIRE - RESCUE DEPARTMENT FIRE CODE ADMINISTRATION Fire Alarm System Plan Review 2009 International Fire Code and 2010 NFPA 72 Date of Review // BLD201 - Project Address: Project Name: _ Professional

More information

Moreno Valley Fire Department Fire Prevention Bureau. New and Existing Fire Alarm & Signaling Systems Guideline

Moreno Valley Fire Department Fire Prevention Bureau. New and Existing Fire Alarm & Signaling Systems Guideline Moreno Valley Fire Department Guideline Approved and Authorized By: Adria Reinertson, Fire Marshal Issued: May 8, 2017 Alarm & Signaling Systems PURPOSE Fire alarm and signaling systems are designed to

More information

Edward K. Budnick Hughes Associates, Inc. Wheaton, Maryland, U.S.A SUMMARY. that is entrained or otherwise mixed into the mass.

Edward K. Budnick Hughes Associates, Inc. Wheaton, Maryland, U.S.A SUMMARY. that is entrained or otherwise mixed into the mass. THE CAPABILITIES OF SMOKE CONTROL: FUNDAMENTALS AND ZONE SMOKE CONTROL John H. Klote Center for Fire Research National Institute of Standards and Technology Gaithersburg, Maryland, U.S.A. 20899 Edward

More information

Fire safety engineering applied to high-rise building facades

Fire safety engineering applied to high-rise building facades MATEC Web of Conferences 46, 04002 (2016) DOI: 10.1051/matecconf/20164604002 C Owned by the authors, published by EDP Sciences, 2016 Fire safety engineering applied to high-rise building facades Samuele

More information

Advantages and Disadvantages of Fire Modelling

Advantages and Disadvantages of Fire Modelling Advantages and Disadvantages of Fire Modelling Dr Guillermo Rein School of Engineering University of Edinburgh & Imperial College London Dr Guillermo Rein 9 May 2012 Chief Fire Officers Association Annual

More information

2009 International Fire Code Errata. SECOND PRINTING (Posted April 6, 2010)

2009 International Fire Code Errata. SECOND PRINTING (Posted April 6, 2010) CHAPTER 1 SCOPE AND ADMINISTRATION 102.7 Referenced codes and standards. The codes and standards referenced in this code shall be those that are listed in Chapter 45 47 and such codes and standards shall

More information

Application of the New Italian Fire Safety Code (D.M. 3 agosto 2015) to Case Study 3 Mall. Enrico Danzi Luca Fiorentini Luca Marmo Vincenzo Puccia

Application of the New Italian Fire Safety Code (D.M. 3 agosto 2015) to Case Study 3 Mall. Enrico Danzi Luca Fiorentini Luca Marmo Vincenzo Puccia Application of the New Italian Fire Safety Code (D.M. 3 agosto 2015) to Case Study 3 Mall Enrico Danzi Luca Fiorentini Luca Marmo Vincenzo Puccia A Challenging Application for the New Italian Fire Code

More information

CHOOSING A FIRE VENTILATION STRATEGY FOR AN UNDERGROUND METRO STATION

CHOOSING A FIRE VENTILATION STRATEGY FOR AN UNDERGROUND METRO STATION - 165 - CHOOSING A FIRE VENTILATION STRATEGY FOR AN UNDERGROUND METRO STATION Wojciech Węgrzyński, Grzegorz Krajewski, Paweł Sulik Fire Research Department, Building Research Institute (ITB), Poland ABSTRACT

More information

CODE TECHNOLOGIES COMMITTEE NURSING CARE FACILITIES WORK GROUP APPROVED CODE CHANGE DRAFTS CODE GROUP B

CODE TECHNOLOGIES COMMITTEE NURSING CARE FACILITIES WORK GROUP APPROVED CODE CHANGE DRAFTS CODE GROUP B CODE TECHNOLOGIES COMMITTEE NURSING CARE FACILITIES WORK GROUP APPROVED CODE CHANGE DRAFTS CODE GROUP B This report includes 3 code change proposal from the CTC Nursing Care Facilities Coordination committee

More information

GUIDELINES FOR INSPECTING GROUND BASED SPARKLING DEVICE (GBSD) RETAIL SALES FACILITIES

GUIDELINES FOR INSPECTING GROUND BASED SPARKLING DEVICE (GBSD) RETAIL SALES FACILITIES OFFICE OF THE FIRE MARSHAL Worcester County GOVERNMENT CENTER - ONE WEST MARKET STREET - ROOM 1003 SNOW HILL, MARYLAND 21863-1194 TEL: 410-632-5666 FAX: 410-632-5664 GUIDELINES FOR INSPECTING GROUND BASED

More information

ADMINISTRATIVE BULLETIN

ADMINISTRATIVE BULLETIN ADMINISTRATIVE BULLETIN NO. AB-047 DATE: SUBJECT: TITLE: Smoke Control Systems Specific Submittal Criteria for Reports, Special Inspections and Final Acceptance Testing of Smoke Control Systems. PURPOSE:

More information

Ball State Architecture ENVIRONMENTAL SYSTEMS 2 Grondzik 1. Smoke, Not Flame

Ball State Architecture ENVIRONMENTAL SYSTEMS 2 Grondzik 1. Smoke, Not Flame SMOKE CONTROL Ball State Architecture ENVIRONMENTAL SYSTEMS 2 Grondzik 1 Smoke, Not Flame The most significant cause of death in building fires is smoke, which accounted for 73% of fire-related deaths

More information

Emergency Ventilation System Design - Preliminary Report Shishir Gupta

Emergency Ventilation System Design - Preliminary Report Shishir Gupta Emergency Ventilation System Design - Preliminary Report Shishir Gupta (shishir@mechartes.com), Abstract The existing stations and tunnels of Metro Railway, Kolkata are not equipped with effective emergency

More information

US Based Codes/Standards in International Design Jeffrey E. Harper, P.E., FSFPE 13 September 2017

US Based Codes/Standards in International Design Jeffrey E. Harper, P.E., FSFPE 13 September 2017 US Based Codes/Standards in International Design Jeffrey E. Harper, P.E., FSFPE 13 September 2017 Acknowledgements/Credits JENSEN HUGHES would like to thank all our clients worldwide for your trust and

More information

and Sprinkler System in Resalat Tunnel of Tehran

and Sprinkler System in Resalat Tunnel of Tehran CFD Simulation of Water Mist and Sprinkler System in Resalat Tunnel of Tehran Motivation Resalat tunnel is the first road tunnel in Tehran one of most crowded tunnels of Tehran my every day route, home

More information

5B-3 6th Asia-Oceania Symposium on Fire Science and Technology 17-20, March, 2004, Daegu, Korea

5B-3 6th Asia-Oceania Symposium on Fire Science and Technology 17-20, March, 2004, Daegu, Korea 5B-3 6th Asia-Oceania Symposium on Fire Science and Technology 17-20, March, 2004, Daegu, Korea PRACTICAL APPLICATIONS OF FIRE MODELING IN INDUSTRIAL APPLICATIONS By James M. Dewey, Advisor Risk Management

More information

National Fire Protection Association. 1 Batterymarch Park, Quincy, MA Phone: Fax:

National Fire Protection Association. 1 Batterymarch Park, Quincy, MA Phone: Fax: National Fire Protection Association 1 Batterymarch Park, Quincy, MA 02169-7471 Phone: 617-770-3000 Fax: 617-770-0700 www.nfpa.org M E M O R A N D U M TO: FROM: NFPA Technical Committee on Mercantile and

More information

JOINT COMMISSION PREPAREDNESS / STATEMENT OF CONDITIONS DRAWINGS WSSHE SOUTHWEST CHAPTER NOVEMBER 19, 2015

JOINT COMMISSION PREPAREDNESS / STATEMENT OF CONDITIONS DRAWINGS WSSHE SOUTHWEST CHAPTER NOVEMBER 19, 2015 JOINT COMMISSION PREPAREDNESS / STATEMENT OF CONDITIONS DRAWINGS WSSHE SOUTHWEST CHAPTER NOVEMBER 19, 2015 AGENDA INTRODUCTION OF PRESENTERS SOC VS. FIRE & LIFE SAFETY DRAWINGS HAZARDOUS AREAS VS. INCIDENTAL

More information