C Installation and Operation Manual

Size: px
Start display at page:

Download "C Installation and Operation Manual"

Transcription

1 (Issue 2.02, December 2005)

2 CONTENTS I General... 1 II Features... 1 III Technical Specifications... 1 IV Structure and Operation Principle... 1 V Mounting and Wiring... 2 VI Testing... 3 VII Troubleshooting... 3 VIII Maintenance... 4 IX Cautions... 4

3 I General C-9104 (hereinafter called the detector) detects fire by the ultraviolet produced by material flaming. It's applicable to places easy to occur open fire, fire with intense flame radiation or fire without smoldering stage and places demanding quick response to a fire. Used together with other detectors, it can sense fire in time to avoid losses as much as possible. II Features Applying excellent UV sensor, the detector has the features of high sensitivity, reliable performance, dust-proof, damp-proof and corrosion-proof. III Technical Specifications 1) Operating Voltage: 12VDC ~ 28VDC 2) Operating Current: Standby Current 1.2mA Alarm Current 30mA 3) Sensitivity: Grade 4) Indicator: Red, not lit in normal standby state, constantly lit after alarming. 5) Detection Angle 80 6) Monitoring Area: S=(h tgα)²π=2.21h² h: Height from the detector to the floor, α=40 7) Operating Environment: Temperature: Relative Humidity 95%, non condensing 8) Dimension: Diameter: 103mm, Height: 53.5mm (including the base) Diameter: 100mm, Height: 41mm (excluding the base) 9) Material and Color of Enclosure: ABS, ivory white 10) Weight: 112g 11) Mounting Hole Spacing: 45mm 75mm IV Structure and Operation Principle 1) Structure of the detector is shown in Fig. 1. Page 1

4 Fig. 1 Structure 2) Operation Principle The detector is DC powered, which powers signal processing circuit after voltage stabilization, the UV sensor needs a voltage of about 300V, which is provided after boosted by transformer. When there is ultraviolet light on the sensor, it discharges due to photoelectric effect, and the strength of discharge is in proportion with the intensity of UV light. Signal processing circuit shapes and integrates its output signal, then compares with alarm threshold and outputs alarm signals. The alarming mode of the detector is current output mode; it's shorted out by internal 680Ω after alarming. V Mounting and Wiring Warning: Before installing the detector, disconnect the power from the loop and verify that all bases are securely installed and that the wiring polarity is correct at each base. 1) Before installation, check whether the enclosure and labels complete or not. It can be installed on embedded box as shown in Fig. 2. Wiring Hole Embedded Box Orientation Base Detector Fig. 2 Mounting Page 2

5 C ) Orientation base of the detector is shown in Fig. 3. Fig. 3 Thread the detector wires through the wiring holes of embedded box and orientation base; fix the orientation base on the embedded box. There are four terminals with numbers on the orientation base. "1" and "3" to power supply, "1" is anode and "3" is cathode, "2" to next detector. There are location elements on the detector and the orientation base to ensure there is only one installing position. There are two marks on point A and B of the orientation base, and a mark on point C of the side face of bottom of the detector. When installing, aligning the mark C of the detector to point A of the orientation base, rotate the detector clockwise to point B, then the detector is installed. 3) Wiring: 227 IEC 05 cable with cross section not less than 1.0mm 2. VI Testing Warning: Power up only after all devices are well connected. 1) Test should be made to the detector after installation and after annual maintenance. 2) Put the detector at normal operating state, remove the detector, there should be fault signal on the fire alarm control panel. Ignite ultraviolet light source in front of the detector, fire alarm indicator should be lit, and the control panel should generate alarm signal. 3) After testing, reset the detector through the control panel. Notify the proper authorities the system is back in operation. 4) If a detector fails in testing, clean it as described in VIII Maintenance and test it again. If it still fails, return it for repair. VII Troubleshooting The detector should be installed just before commissioning and kept well before Page 3

6 installation, taken corresponding measures for dust-proof, damp-proof and corrosion-proof. Main fault and solutions are as follows: 1) Reporting Fault: Check wires and fire alarm control panel, then check internal parts of the detector. 2) Nuisance Alarm: Ensure there is no UV light source, then check its sensor and signal processing circuit. VIII Maintenance 1) The detector should be cleaned at least once a year to ensure normal operation of the system. 2) Before cleaning, notify the proper authorities that the system is undergoing maintenance and will temporarily be out of service. Disable the zone or system undergoing maintenance to avoid unwanted alarms. 3) Remove the detector, clean it and installed it again. 4) Test the detector after installed again. IX Cautions The detector should be handled with care wherever it is moved, to avoid collision, squeezing, and friction. The detector is not suitable for the following places. 1) Where flameless fires are expected. 2) Where thick smoke spreads before flames. 3) Places where the "view" of the detector is easy to be obscured. 4) Where the sun can directly or indirectly shine the detector. 5) Where there are strong ultraviolet light source, such as halogen and tungsten. 6) Where there is open flame, welding operation, X rays and arc and spark etc. Page 4

7 GST China Gulf Security Technology Co., Ltd. No. 80, Changjiang East Road, QETDZ, Qinhuangdao, Hebei, P. R. China Tel: +86 (0) Fax: +86 (0) GST UK Global System Technology PLC Enterprise Glade, Bath Lane, Moira, South Derbyshire, England. DE12 6BD Tel: + 44 (0) Fax: + 44 (0) Rigional Office PO Box Unit ZA04 JEBEL ALI Free Zone, Dubai, UAE Tel: +971 (0) Fax: +971 (0) tech.support@gst.uk.com

Installation and Operation Manual

Installation and Operation Manual C90 Rate of Rise and Fixed Temperature Heat (Issue., March 006) C90 Rate of Rise and Fixed Temperature Heat CONTENTS I General... II Features... III Technical Specifications... IV Structure and Operation

More information

C-9105R Conventional Reflective Beam Detector Installation and Operation Manual. (Issue 2.01, February 2006)

C-9105R Conventional Reflective Beam Detector Installation and Operation Manual. (Issue 2.01, February 2006) (Issue 2.01, February 2006) CONTENTS I General... 1 II Features... 1 III Technical Specifications... 1 IV Structure and Operation Principle... 2 V Mounting and Wiring... 4 1. Ambient Conditions for Installation...

More information

I-9105R Intelligent Reflective Beam Detector Installation and Operation Manual. (Issue 2.03 February 2006)

I-9105R Intelligent Reflective Beam Detector Installation and Operation Manual. (Issue 2.03 February 2006) (Issue 2.03 February 2006) CONTENTS I General... 1 II Features... 1 III Technical Specifications... 1 IV Structure and Operation Principle... 2 V Mounting and Wiring... 4 1. Ambient Conditions for Installation...

More information

GST-FT40N Fire Telephone Panel Installation and Operation Manual

GST-FT40N Fire Telephone Panel Installation and Operation Manual Installation and Operation Manual CONTENTS 1 GENERAL...1 2 TECHNICAL SPECIFICATIONS...1 3 PANEL INSTRUCTION...2 3.1 APPEARANCE AND STRUCTURE...2 3.2 THE FRONT SURFACE...2 3.3 THE KEYS...3 3.4 INDICATORS...3

More information

I-9105R Intelligent Reflective Beam Detector Installation and Operation Manual. The Intelligent Solution CONTENTS

I-9105R Intelligent Reflective Beam Detector Installation and Operation Manual. The Intelligent Solution CONTENTS CONTENTS I Overview...1 II Features...1 III Technical Specifications...2 IV Structure and Operation Principle...4 V Mounting and Wiring...6 1. Ambient Conditions for Installation...6 2. Mounting Height

More information

CONTENTS. I Description II Specification III Structure IV Mounting and Wiring V Application VI Troubleshooting...

CONTENTS. I Description II Specification III Structure IV Mounting and Wiring V Application VI Troubleshooting... CONTENTS I Description... 1 II Specification... 1 III Structure... 2 IV Mounting and Wiring... 3 V Application... 7 VI Troubleshooting... 8 VII Maintenance... 8 VIII Cautions... 9 IX Warranty Limited...

More information

CONTENTS Installation Precautions... 1 Chapter 1 Product Introduction... 2 Chapter 2 Technical Specifications... 3

CONTENTS Installation Precautions... 1 Chapter 1 Product Introduction... 2 Chapter 2 Technical Specifications... 3 CONTENTS Installation Precautions... 1 Chapter 1 Product Introduction... 2 Chapter 2 Technical Specifications... 3 2.1 Electrical Specifications... 3 2.2 Communication Loop Parameters... 3 2.3 Dimensions...

More information

FLV 40 UV Flame Detector

FLV 40 UV Flame Detector FLV 40 UV Flame Detector TECHNICAL INSTRUCTIONS FOR INSTALLATION, SETUP ANDMAINTENANCE EDS srl - V. Cà Nova Zampieri 6-37057 S.G.Lupatoto - Verona - Italy - tel +39045547529 - fax. +390458750065 - Mail:

More information

CONTENTS. GST102A/104A/108A/116A Conventional Fire Alarm Control Panel Installation and Operation Manual

CONTENTS. GST102A/104A/108A/116A Conventional Fire Alarm Control Panel Installation and Operation Manual CONTENTS Installation Precautions... 1 EN 54 Information... 2 Chapter 1 Product Overview... 3 1.1 Features... 3 1.2 Technical Specifications... 3 1.2.1 Operating Voltage... 3 1.2.2 Batteries... 3 1.2.3

More information

PRODUCT BULLETIN. Rev. A Monitoring Station offering PN Rev. B as a direct replacement. OVERVIEW / DESCRIPTION

PRODUCT BULLETIN. Rev. A Monitoring Station offering PN Rev. B as a direct replacement. OVERVIEW / DESCRIPTION PRODUCT BULLETIN ISSUE/DATE: March 28, 2008 rev A BULLETIN NUMBER: AQ032808 SUBJECT: Monitoring Station PRODUCT LINE: Aquafine UV Equipment TOPIC: REVISION TO THE 41114-1 MONITORING STATION OVERVIEW /

More information

GST Headquarters. GST Production Base

GST Headquarters. GST Production Base GST Headquarters GST Production Base Company Profile GST, a high tech company, is specialising in R&D, manufacturing, marketing and technical service of Fire Alarm Systems. GST manufactures over 6 million

More information

IR4000. Point Infrared Combustible Gas Detection System. The Reliable and Flexible Safety Solution That s Low Maintenance

IR4000. Point Infrared Combustible Gas Detection System. The Reliable and Flexible Safety Solution That s Low Maintenance IR4000 Point Infrared Combustible Gas Detection System The Reliable and Flexible Safety Solution That s Low Maintenance Multi-Point Gas Detection That s Fast Set-Up, Low Maintenance, Cost-Effective The

More information

CONTENTS. GstDef2.1 Defining Tool User s Manual

CONTENTS. GstDef2.1 Defining Tool User s Manual CONTENTS 1 Overview... 1 2 System Requirement... 1 2.1 Hardware... 1 2.2 Software... 1 3 Installation... 1 4 Download Card... 2 5 User s Guide... 3 5.1 Function Tools... 3 5.1.1 Com Set... 4 5.1.2 Setting

More information

Sitron s CF Line of Flow Switch Monitors

Sitron s CF Line of Flow Switch Monitors Sitron s CF Line of Flow Switch Monitors Models: CF 12AC CF 12DC CF 420 F 420 RCF 420 Introduction Sitron s versatile and intelligent line of Thermal Dispersion Flow Switch Monitors are compact switches,

More information

Safety. Operating instructions UV sensor UVS 10 DANGER WARNING. Contents CAUTION Edition Please read and keep in a safe place

Safety. Operating instructions UV sensor UVS 10 DANGER WARNING. Contents CAUTION Edition Please read and keep in a safe place 8.. Edition 08.0 D GB F NL I E DK S N P GR TR CZ PL RUS H www.docuthek.com Operating instructions UV sensor UVS 0 Translation from the German 008 009 Elster GmbH Contents UV sensor UVS 0......................

More information

IRIS IP65 IRIS UNISCAN APPLICATION MANUAL

IRIS IP65 IRIS UNISCAN APPLICATION MANUAL IRIS IP65 IRIS UNISCAN APPLICATION MANUAL 01/08/05 DESCRIPTION TABLE OF CONTENTS PAGE IRIS - UNISCAN... 1 SPECIFICATION... 1 SUPPLY VOLTAGE: -... 1 OUTPUTS: -... 1 TRANSMISSION: -... 1 CABLE: -... 1 FLAME

More information

Attention Items: I. Brief Introduction

Attention Items: I. Brief Introduction 1 Content Attention Items:... 3 I. Brief Introduction... 3 II. Model Difference... 3 III. Technical Specifications... 4 IV. Detector Structure... 5 V. Network Structure... 5 VI. The Principle and Application

More information

Models TX-KE and TX-KP Toxic Gas Transmitters

Models TX-KE and TX-KP Toxic Gas Transmitters Models TX-KE and TX-KP Toxic Gas Transmitters Instruction Manual PureAire Monitoring Systems, Inc. 557 Capital Dr. Lake Zurich, IL. 60047 Phone: 847-726-6000 Fax: 847-726-6051 Toll-Free: 888-788-8050 www.pureairemonitoring.com

More information

SAFETY MANUAL. X2200 UV, X9800 IR, X5200 UVIR SIL 2 Certified Flame Detectors

SAFETY MANUAL. X2200 UV, X9800 IR, X5200 UVIR SIL 2 Certified Flame Detectors SAFETY MANUAL X2200 UV, X9800 IR, X5200 UVIR SIL 2 Certified Flame Detectors SAFETY-CERTIFIED Flame DETECTORs This manual addresses the specific requirements and recommendations applicable to the proper

More information

D7050DH. Installation Instructions. Multiplex Photoelectric Duct Smoke Detector

D7050DH. Installation Instructions. Multiplex Photoelectric Duct Smoke Detector D700DH EN Installation Instructions Multiplex Photoelectric Duct Smoke Detector D700DH Installation Instructions.0 Description Notices These instructions cover the installation of the D700DH Multiplex

More information

INSTALLATION AND MAINTENANCE INSTRUCTIONS 6500R AND 6500RS REFLECTIVE TYPE PROJECTED BEAM SMOKE DETECTOR

INSTALLATION AND MAINTENANCE INSTRUCTIONS 6500R AND 6500RS REFLECTIVE TYPE PROJECTED BEAM SMOKE DETECTOR INSTALLATION AND MAINTENANCE INSTRUCTIONS 6500R AND 6500RS REFLECTIVE TYPE PROJECTED BEAM SMOKE DETECTOR GENERAL The model 6500R is a conventional long range projected beam smoke detector designed to provide

More information

INSTALLATION AND MAINTENANCE INSTRUCTIONS NFXI-BEAM AND NFXI-BEAM-T REFLECTED TYPE PROJECTED BEAM SMOKE DETECTOR

INSTALLATION AND MAINTENANCE INSTRUCTIONS NFXI-BEAM AND NFXI-BEAM-T REFLECTED TYPE PROJECTED BEAM SMOKE DETECTOR INSTALLATION AND MAINTENANCE INSTRUCTIONS NFXI-BEAM AND NFXI-BEAM-T REFLECTED TYPE PROJECTED BEAM SMOKE DETECTOR GENERAL The model NFXI-BEAM is an addressable long range projected beam smoke detector designed

More information

Fire Detection System: An Overview

Fire Detection System: An Overview Fire Detection System: An Overview Arief Rahman Thanura Process & Control Engineer VICO Indonesia, LLC Member of ISA Introduction Fire accidents had happened all around the world and more concern raised

More information

UV Flame Supervision System

UV Flame Supervision System 7 783 UV Flame Supervision System DETACTOGYR LFE50 Series 02 ISO 9001 The LFE50 is a self-checking UV flame supervision system designed for use with continuously operating burners or for burners running

More information

QRA4.U. Flame Detector. Siemens Building Technologies HVAC Products

QRA4.U. Flame Detector. Siemens Building Technologies HVAC Products 7 711 Flame Detector QRA4.U Flame detector for use with burner controls from for the supervision of gas or oil flames. The QRA4.U and this Data Sheet are intended for use by OEMs which integrate the flame

More information

INSTALLATION AND MAINTENANCE INSTRUCTIONS 6500 AND 6500S REFLECTED TYPE PROJECTED BEAM SMOKE DETECTOR

INSTALLATION AND MAINTENANCE INSTRUCTIONS 6500 AND 6500S REFLECTED TYPE PROJECTED BEAM SMOKE DETECTOR INSTALLATION AND MAINTENANCE INSTRUCTIONS 6500 AND 6500S REFLECTED TYPE PROJECTED BEAM SMOKE DETECTOR GENERAL The model 6500 is an addressable long range projected beam smoke detector designed to provide

More information

INSTALLATION AND MAINTENANCE INSTRUCTIONS 6500R AND 6500RS REFLECTIVE TYPE PROJECTED BEAM SMOKE DETECTOR

INSTALLATION AND MAINTENANCE INSTRUCTIONS 6500R AND 6500RS REFLECTIVE TYPE PROJECTED BEAM SMOKE DETECTOR INSTALLATION AND MAINTENANCE INSTRUCTIONS 00R AND 00RS REFLECTIVE TYPE PROJECTED BEAM SMOKE DETECTOR GENERAL The model 00R is a conventional long range projected beam smoke detector designed to provide

More information

This document is a preview generated by EVS

This document is a preview generated by EVS TECHNICAL SPECIFICATION ISO/TS 7240-29 First edition 2017-06 Fire detection and alarm systems Part 29: Video fire detectors Systèmes de détection et d alarme d incendie Partie 29: Titre manque Reference

More information

Single Doors FIREGUARD Series Use one Master Unit each door or one 2409 Support unit each door. Pairs of Doors

Single Doors FIREGUARD Series Use one Master Unit each door or one 2409 Support unit each door. Pairs of Doors Hinge Edge of Door Hinge Edge of Door Wiring Instructions for the Sargent 0 Series FIREGUARD Combination Door Closer-Holder and Releasing Device with Integral Smoke Detector CAUTION: FAILURE TO INSTALL

More information

FX-PDD Duct Smoke Detector Installation Sheet

FX-PDD Duct Smoke Detector Installation Sheet FX-PDD Duct Smoke Detector Installation Sheet Table 2: LEDs LED Power LED Alarm/active LED Off when the detector is in the alarm state. Flashes intermittently when the detector is in the normal state.

More information

GLD-30 Gas Leak Detector

GLD-30 Gas Leak Detector GLD-30 Gas Leak Detector Installation, Operation & Maintenance General: The Archer Instruments GLD-30 is an ambient air monitor, used to detect the presence of a target gas (or gases) and to alert operators

More information

LEARNING SPECIAL HAZARD DETECTION TYPES

LEARNING SPECIAL HAZARD DETECTION TYPES LEARNING SPECIAL HAZARD DETECTION TYPES JUNE 2013 COPYRIGHT CLIMATEC SPECIAL HAZARDS DETECTION TYPES EXPLAINED STAGE ONE DETECTION - ACTIVE AIR SAMPLING\\INCIPIENT AND IN- VISIBLE SMOKE STAGE AIR SAMPLING

More information

O. Gas boiler. Gaz 6000 W WBN H-E-N/L-S2400. Operating instructions for the end customer (2017/09) en

O. Gas boiler. Gaz 6000 W WBN H-E-N/L-S2400. Operating instructions for the end customer (2017/09) en 8 716 473 216-00.3O Gas boiler WBN 6000-30-H-E-N/L-S2400 Operating instructions for the end customer en 2 Contents Contents 1 Key to symbols and safety instructions................... 2 1.1 Key to symbols..................................

More information

LIGHTING TEF 9980 STATUS LIGHT, MAIN LIGHT & REPEATER LIGHT ZONE 1, ZONE 2 & SAFE AREA USER MANUAL

LIGHTING TEF 9980 STATUS LIGHT, MAIN LIGHT & REPEATER LIGHT ZONE 1, ZONE 2 & SAFE AREA USER MANUAL Subject to change without prior notice TUM7 REV. B.08.08 SAFETY INSTRUCTIONS The TEF 9980 status light may be installed in Zone, or safe area. The Equipment shall not be installed in Zone 0! HANDLE WITH

More information

Arc Fault Protection System D1000

Arc Fault Protection System D1000 Arc Fault Protection System D1000 Improve personnel safety Reduce damage Avoid costly repairs Minimize production downtime www.selco.com Segments & applications In all areas where electrical energy is

More information

D1000 Arc-fault Protection System

D1000 Arc-fault Protection System D1000 Arc-fault Protection System Improve personnel safety Reduce damage and minimize costly repairs Minimize production downtime www.selco.com D1000 Arc-Fault Protection system Efficient protection of

More information

C Note! LGI16... Burner Controls. Building Technologies

C Note! LGI16... Burner Controls. Building Technologies 7 786 Burner Controls LGI16... Burner controls For use on industrial furnaces For burners in continuous operation Without fan control and air pressure supervision Flame supervision - with QR53... / QR55,

More information

LFE50. UV Flame Safeguard. Siemens Building Technologies HVAC Products DETACTOGYR. Series 02

LFE50. UV Flame Safeguard. Siemens Building Technologies HVAC Products DETACTOGYR. Series 02 7 783 ISO 9001 DETACTOGYR Flame Safeguard Series 02 The... together with the QRA50M / QRA51M form a self-checking flame supervision system (DETACTOGYR ) designed for use with continuously operating oil

More information

D2E Duct Smoke Detector

D2E Duct Smoke Detector INSTALLATION AND MAINTENANCE INSTRUCTIONS D2E Duct Smoke Detector Specifications Operating Temperature: 20 to 60 C Storage Temperature: 20 to 60 C Humidity: 0% to 93% Relative Humidity Non-condensing Air

More information

AUR300C. Advanced Ultraviolet Burner Controller

AUR300C. Advanced Ultraviolet Burner Controller No. CP-SS-1807E AUR300C Advanced Ultraviolet Burner Controller Overview The AUR300C is a burner controller with a dynamic selfchecking function and is used in combination with the AUD300C or AUD500C Advanced

More information

Photobeam 5000 ISC-FPB1-W60QS, ISC-FPB1-W120QS, ISC-FPB1-W200QS. en Installation and Operation Guide

Photobeam 5000 ISC-FPB1-W60QS, ISC-FPB1-W120QS, ISC-FPB1-W200QS. en Installation and Operation Guide Photobeam 5000 ISC-FPB-W60QS, ISC-FPB-W20QS, ISC-FPB-W200QS en Installation and Operation Guide Photobeam 5000 Table of Contents en 3 Table of contents Introduction 4. About documentation 4.2 Bosch Security

More information

Safety. Operating instructions UV sensor UVS 5 DANGER. Contents WARNING CAUTION Elster GmbH Edition Please read and keep in a safe place

Safety. Operating instructions UV sensor UVS 5 DANGER. Contents WARNING CAUTION Elster GmbH Edition Please read and keep in a safe place 06 Elster GmbH Edition 0.6 Translation from the German 0556 D F NL I E DK S N P GR TR CZ PL RUS H www.docuthek.com Operating instructions UV sensor UVS 5 Cert. version 0.6 Contents UV sensor UVS 5... Contents...

More information

M5800 Pressure Transducer with Rotatable Display

M5800 Pressure Transducer with Rotatable Display Pressure Transducer with Rotatable Display SPECIFICATIONS Wide Temperature Range Compact Variety of Pressure Ports and customized Electrical Configurations FEATURES CE Compliance Reverse Polarity Protection

More information

Wiring Instructions for the 2900 Series FIREGUARD Combination Door Closer-Holder and Releasing Device with Integral Smoke Detector

Wiring Instructions for the 2900 Series FIREGUARD Combination Door Closer-Holder and Releasing Device with Integral Smoke Detector Wiring Instructions for the 900 Series FIREGUARD Combination Door Closer-Holder and Releasing Device with Integral Smoke Detector CAUTION: FAILURE TO INSTALL OR ADJUST PROPERLY MAY RESULT IN INJURY OR

More information

Why choose Fireray? Why use a Beam Smoke Detector? Product Range.

Why choose Fireray? Why use a Beam Smoke Detector? Product Range. Range Brochure Why use a? Beam smoke detectors are the wide area smoke detection technology of choice, offering both excellent detection and value for money. With a high area of coverage per unit (as high

More information

INSTRUCTION MANUAL PORTABLE FRIDGE/FREEZER. Models: RVX-35 / RVX-45 / RVX-50 RVX-55 / RVX-65 / RVX-75

INSTRUCTION MANUAL PORTABLE FRIDGE/FREEZER. Models: RVX-35 / RVX-45 / RVX-50 RVX-55 / RVX-65 / RVX-75 INSTRUCTION MANUAL PORTABLE FRIDGE/FREEZER Models: RVX-35 / RVX-45 / RVX-50 RVX-55 / RVX-65 / RVX-75 PLEASE READ THIS INSTRUCTION MANUAL CAREFULLY BEFORE CONNECTING AND OPERATING THE APPLIANCE. SAVE IT

More information

IMPORTANT. PLEASE NOTE: The infrared beam path MUST be kept clear of obstructions at all times!

IMPORTANT. PLEASE NOTE: The infrared beam path MUST be kept clear of obstructions at all times! USER GUIDE English IMPORTANT PLEASE NOTE: The infrared beam path MUST be kept clear of obstructions at all times! Failure to comply may result in the Detector initiating a Fire or Fault signal. Contents

More information

Air Specialties Express, 448 S. Main St., P. O. Box , Verona, WI Phone: (877) Fax: (608)

Air Specialties Express, 448 S. Main St., P. O. Box , Verona, WI Phone: (877) Fax: (608) FORM ASX-40021 INSTALLATION, OPERATING AND MAINTENANCE INSTRUCTIONS SM-501 Series Smoke Detectors, Model EXSAC and EXSAD (Ionization), EXSAJ and EXSAK (Photoelectric) Air Specialties Express, 448 S. Main

More information

TX7130. Conventional Reflective Beam Detector Installation and Operation Manual. TANDA UK Technology Copyright 2015, All right reserved.

TX7130. Conventional Reflective Beam Detector Installation and Operation Manual. TANDA UK Technology Copyright 2015, All right reserved. TX7130 Conventional Reflective Beam Detector Installation and Operation Manual Technology Copyright 2015, All right reserved. Product Safety To prevent severe injury and loss of life or property, read

More information

1400 Direct Wire Ionization Smoke Detector

1400 Direct Wire Ionization Smoke Detector INSTALLATION AND MAINTENANCE INSTRUCTIONS 1400 Direct Wire Ionization Smoke Detector A Division of Pittway 3825 Ohio Avenue, St. Charles, Illinois 60174 1800SENSOR2, FAX: 6303776495 Specifications Diameter:

More information

Wiring Instructions. Single Doors 99 Checkmate Series Use one or Master Unit each door or one or Support unit each door

Wiring Instructions. Single Doors 99 Checkmate Series Use one or Master Unit each door or one or Support unit each door CAUTION Hinge Edge of Door Wiring Instructions Checkmate Series with Single Point Hold-Open Combination Door Closer-Holder and Releasing Device with or without Integral Smoke Detector INSTALLER: LEAVE

More information

IFD-E Flame Detector User Manual

IFD-E Flame Detector User Manual IFD-E Flame Detector User Manual 2 Hochiki Europe (UK) Ltd General Description The flame detector is designed for use where open flaming fires may be expected. It responds to the light emitted from flames

More information

Installation Instructions

Installation Instructions 48/50A2,A3,A4,A5020-060, 48/50P2,P3,P4,P5030-100, 48/50N 75 to 105 Ton Return Smoke Detector Accessory Installation Instructions Part No. CRSMKDET002C00 CONTENTS GENERAL........................................

More information

Table of Contents. 1. Mounting Tips... 2

Table of Contents. 1. Mounting Tips... 2 Table of Contents 1. Mounting Tips............................................. 2 1.1. Connections and DIP switch settings................................... 3 1.2. Mounting the Fireray 50/100RV........................................

More information

Open-area Smoke Imaging Detection (OSID)

Open-area Smoke Imaging Detection (OSID) Open-area Smoke Imaging Detection (OSID) OSID Smoke Detection Open-area Smoke Imaging Detection (OSID) by Xtralis is a new innovation in projected beam smoke detection technology. By using advanced dual

More information

Technical Manual for the Alarm Pull Station PH1

Technical Manual for the Alarm Pull Station PH1 Technical Manual for the Alarm Pull Station PH1 Please note that every care has been taken to ensure the accuracy of our technical manual. We do not, however, accept responsibility for damage, loss or

More information

Contents The IET Regulations, BS 7671, and this Guide 1.1 The need for this Electrician s Guide 1.2 The IET Regulations BS 7671

Contents The IET Regulations, BS 7671, and this Guide 1.1 The need for this Electrician s Guide 1.2 The IET Regulations BS 7671 Contents 1 The IET Regulations, BS 7671, and this Guide 1 1.1 The need for this Electrician s Guide 1 1.2 The IET Regulations BS 7671 2 1.2.1 International basis 2 1.2.2 The Seventeenth Edition 3 1.2.3

More information

Reflective Optical Beam Smoke Detector User Guide

Reflective Optical Beam Smoke Detector User Guide Reflective Optical Beam Smoke Detector User Guide 1. Installation IMPORTANT NOTE: The infrared beam path MUST be kept clear of obstructions at all times! Failure to comply may result in the system initiating

More information

M5800 Pressure Transducer with Rotatable Display

M5800 Pressure Transducer with Rotatable Display Pressure Transducer with Rotatable Display SPECIFICATIONS Wide Temperature Range Compact Variety of Pressure Ports and customized Electrical Configurations Optional Stainless Steel Snubber CE Compliant

More information

LAE10 LFE10. Use. Series 02

LAE10 LFE10. Use. Series 02 ISO 00 Flame Safeguards 7 7 LAE L Series 02 Supplementary data sheets 772 and 773 Flame safeguards for burners with intermittent operation. For safety reasons - self-test of flame supervision circuit,

More information

General Routing Interface

General Routing Interface General Routing Interface Features The General Routing Interface Card is an optional module to provide Fire and Fault Routing Outputs compliant with BSEN54-2: 1998 Clauses 7.9 and 8.9 and BS5839-1: 2002.

More information

University of Pennsylvania. Environmental Health and Radiation Safety (EHRS) X-ray Diffraction User Guide

University of Pennsylvania. Environmental Health and Radiation Safety (EHRS) X-ray Diffraction User Guide University of Pennsylvania Environmental Health and Radiation Safety (EHRS) X-ray Diffraction User Guide (Reviewed: September 2012) I. INTRODUCTION II. III. IV. PA DEPARTMENT OF ENVIRONENTAL PROTECTION

More information

Model 3300 Technical Support and Installation Manual

Model 3300 Technical Support and Installation Manual Model 3300 Technical Support and Installation Manual Manual # T15011 Document Revision: A1 1. OVERVIEW 1 2. BASIC OPERATION 1 2.1 General 1 2.2 Field-of-View 2 2.3 Range 2 2.4 Environment 2 2.5 Configuration

More information

Flame detector. The QRA4.U is for use with the following types of burner control:

Flame detector. The QRA4.U is for use with the following types of burner control: 7 711 Flame detector QRA4.U UV flame detector for use with burner controls from Siemens for the supervision of gas or oil flames. The QRA4.U and this Data Sheet are intended for use by OEMs which integrate

More information

E-PDD Duct Smoke Detector Installation Sheet

E-PDD Duct Smoke Detector Installation Sheet E-PDD Duct Smoke Installation Sheet E-PDD operation The duct smoke detector's primary purpose is to provide early warning of an impending fire and shut down the HVAC unit in order to prevent smoke from

More information

Global Water Instrumentation, Inc.

Global Water Instrumentation, Inc. Instrumentation, Inc. 11390 Amalgam Way Gold River, CA 95670 T: 800-876-1172 Int l: (916) 638-3429, F: (916) 638-3270 High Water Alarm WA400-DC WA400-AC WA400-BU WA400-FS WA400-AL 10/23/06 P/N: 01-527

More information

TX7110. Intelligent Heat Detector Installation and Operation Manual. TANDA UK Technology Copyright 2015, All right reserved.

TX7110. Intelligent Heat Detector Installation and Operation Manual. TANDA UK Technology Copyright 2015, All right reserved. TX7110 Intelligent Heat Detector Installation and Operation Manual Technology Copyright 2015, All right reserved. Product Safety To prevent severe injury and loss of life or property, read the instruction

More information

Open-area Smoke Imaging Detector. Engineering Specification

Open-area Smoke Imaging Detector. Engineering Specification Open-area Smoke Imaging Detector 15273_02 October 2011 Table of Contents 1. Scope... 3 2. System Information... 3 2.1 General... 3 2.2 Approvals... 3 2.3 Codes, Standards or Regulations... 3 2.4 System

More information

IFD-E Flame Detector User Manual

IFD-E Flame Detector User Manual IFD-E Flame Detector User Manual 2 Hochiki Europe (UK) Ltd General Description The flame detector is designed for use where open flaming fires may be expected. It responds to the light emitted from flames

More information

SAFETY CERTIFIED MODEL FP-700 COMBUSTIBLE GAS DETECTOR

SAFETY CERTIFIED MODEL FP-700 COMBUSTIBLE GAS DETECTOR SAFETY MANUAL SIL 2 Certified Model FP-700 Combustible Hydrocarbon Gas Sensor Version 2.0 1 SAFETY CERTIFIED MODEL FP-700 COMBUSTIBLE GAS DETECTOR This manual addresses the specific requirements and recommendations

More information

UNITIZED ULTRAVIOLET FIRE DETECTOR

UNITIZED ULTRAVIOLET FIRE DETECTOR MODEL #: UVU-140-A & UVU-140-AR UNITIZED ULTRAVIOLET FIRE DETECTOR REVISED: DECEMBER, 1999 REV. uvu140a-aroct99.wpd WARRANTY POLICY Net Safety Monitoring Inc. products are carefully designed and manufactured

More information

Installation and Operation Manual

Installation and Operation Manual [Please read this installation & operation manual before install and use this Installation and Operation Manual Address: 8-701,Dongfangming Industry Zone, Dabao Road., Baoan, Shenzhen, China-518101 Page

More information

Safety Photo Beam UL MONITORED DEVICE

Safety Photo Beam UL MONITORED DEVICE IRB-HB Safety Photo Beam UL325-2010 MONITORED DEVICE Operating Instructions CAUTIONS AND WARNINGS This product is an accessory or part of a system. Always read and follow the manufacturer s instructions

More information

Schedule of Accreditation issued by United Kingdom Accreditation Service 2 Pine Trees, Chertsey Lane, Staines-upon-Thames, TW18 3HR, UK

Schedule of Accreditation issued by United Kingdom Accreditation Service 2 Pine Trees, Chertsey Lane, Staines-upon-Thames, TW18 3HR, UK 2 Pine Trees, Chertsey Lane, Staines-upon-Thames, TW18 3HR, UK 17065:2012 to provide product conformity certification Newport Business Park New Port Road Ellesmere Port CH65 4LZ United Kingdom Contact:

More information

Instruction Manual EVA-S6 Base

Instruction Manual EVA-S6 Base Instruction Manual EVA-S6 Base Sounder Base NITTAN COMPANY, LIMITED 1-54-5 SASAZUKA, SHIBUYA-KU, TOKYO 151-8535, JAPAN http://www.nittan.com Before Installation Please read these instructions carefully

More information

Users Manual. Gas wall hung Boiler condensing Buderus /S. Please read thoroughly before operating the unit

Users Manual. Gas wall hung Boiler condensing Buderus /S. Please read thoroughly before operating the unit 7215 3200-02/2006 GB (EN) For the user Users Manual Gas wall hung Boiler condensing Buderus 500-24/S Please read thoroughly before operating the unit Introduction Please read these instructions and follow

More information

Motorised Infrared Optical Beam Smoke Detector. User Guide

Motorised Infrared Optical Beam Smoke Detector. User Guide Motorised Infrared Optical Beam Smoke Detector User Guide EN 1. General Information 50cm 50cm 8-100m Ensure clear line of sight from Detector to Reflector Mount on solid surfaces (structural wall or girder)

More information

DH200PL Intelligent Air Duct Smoke Detector with Extended Air Speed Range

DH200PL Intelligent Air Duct Smoke Detector with Extended Air Speed Range INSTALLATION AND MAINTENANCE INSTRUCTIONS DH200PL Intelligent Air Duct Smoke Detector with Extended Air Speed Range 3825 Ohio Avenue, St. Charles, Illinois 60174 800-736/7672, FAX: 630-377-6495 Before

More information

E-17 Flammable Gas Detection and Alarm System

E-17 Flammable Gas Detection and Alarm System Guideline No.E-17 (201705) E-17 Flammable Gas Detection and Alarm System Issued date: May 9, 2017 China Classification Society Foreword This Guideline is a part of CCS Rules, which contains technical requirements,

More information

DT1101A / DT1102A / DO110xA Automatic fire detectors

DT1101A / DT1102A / DO110xA Automatic fire detectors DT1101A / DT1102A / DO110xA Automatic fire detectors collective/synoline600 AlgoRex Synova High degree of reliability and stability Compatible with all control units with collective/synoline600 detector

More information

SERIES VAC Microprocessor-Based Direct Spark Ignition Control with Inducer Blower Relay FEATURES APPLICATIONS SPECIFICATIONS DESCRIPTION

SERIES VAC Microprocessor-Based Direct Spark Ignition Control with Inducer Blower Relay FEATURES APPLICATIONS SPECIFICATIONS DESCRIPTION R SERIES 35-61 24 VAC Microprocessor-Based Direct Spark Ignition Control with Inducer Blower Relay F-35-61 August 2015 FEATURES Safe start with DETECT-A-FLAME flame sensing technology Custom pre-purge

More information

FLAME115 INFRARED HEATER SERVICE MANUAL INDEX FIRE 115 WARNING

FLAME115 INFRARED HEATER SERVICE MANUAL INDEX FIRE 115 WARNING FLAME115 INFRARED HEATER SERVICE MANUAL INDEX 1. CONTROLS AND COMPONENTS 2. FLAME CONTROL CYCLES 3. MAINTENANCE SCHEDULE 4. TROUBLESHOOTING GUIDE 5. REPAIR PROCEDURES 1. FAN MOTOR ASSEMBLY 2. FUEL FILTER

More information

Free swing slide-channel door closer TS 99 DORMA. in Contur Design

Free swing slide-channel door closer TS 99 DORMA. in Contur Design Free swing slide-channel door closer DOA TS in Contur Design reddot design award winner 00 DOA TS Free swing slide channel door closer For easy use of fire and smoke check doors combined with safe closing

More information

Isco 3700ZR Sampler. Manual Set

Isco 3700ZR Sampler. Manual Set Isco 3700ZR Sampler Manual Set Assembly #60-2744-045 Copyright 2001. All rights reserved, Teledyne Isco Revision D, December 14, 2012 This set of manuals supports the Isco 3700ZR Refrigerated Sampler.

More information

Conventional Fire Alarm System 2014 V1.2

Conventional Fire Alarm System 2014 V1.2 Conventional Fire Alarm System 2014 V1.2 Product Overview Control Panel 2 Conventional Fire Panel GST102A 2 zone Fire panel GST104A 4 zone Fire panel GST108A 8 zone Fire panel GST116A 16 zone Fire Panel

More information

Dräger Polytron Pulsar 2 Detection of flammable gases and vapours

Dräger Polytron Pulsar 2 Detection of flammable gases and vapours Dräger Polytron Pulsar 2 Detection of flammable gases and vapours The Dräger Polytron Pulsar 2 is the latest infrared technology in open path gas detection. Equipped with all the same functions as the standard

More information

Flame Detection Jon Sarfas

Flame Detection Jon Sarfas Flame Detection Jon Sarfas Agenda Introduction Detection Principles FL4000H MSIR Flame Detector Flame Test Lamp Installation Best Practice Features & Benefits Applications Introduction Primary objectives:

More information

7XG3130 ReyArc30 Optical Arc Fault Sensor Energy Management

7XG3130 ReyArc30 Optical Arc Fault Sensor Energy Management Reyrolle Protection Devices 7XG3130 ReyArc30 Optical Arc Fault Sensor Energy Management 7XG3130 - RA30 Optical Arc Fault Sensor Features Compact rugged design One or two optical detectors High speed arc

More information

Motorised Infrared Optical Beam Smoke Detector. User Guide

Motorised Infrared Optical Beam Smoke Detector. User Guide Motorised Infrared Optical Beam Smoke Detector User Guide EN 1. General Information 50cm 50cm 8-100m Ensure clear line of sight from Detector to Reflector Mount on solid surfaces (structural wall or girder)

More information

LFE50. UV Flame Safeguard. Building Technologies Division DETACTOGYR

LFE50. UV Flame Safeguard. Building Technologies Division DETACTOGYR 7 783 DETACTOGYR Flame Safeguard The... together with the QRA50M / QRA51M form a self-checking flame supervision system (DETACTOGYR ) designed for use with continuously operating oil or gas burners or

More information

Model DRD-AS Conventional Infrared Flame Detector User Manual Ver. 1.0

Model DRD-AS Conventional Infrared Flame Detector User Manual Ver. 1.0 Model DRD-AS Conventional Infrared Flame Detector User Manual Ver. 1.0 Page 1 of 11 DRD-AS Flame Detector User Manual Table of Contents 1.1 Description... 3 1.2 Alarm Response Modes... 3 1.3 IR Detection

More information

Indirect gas-fired air heater

Indirect gas-fired air heater Indirect gas-fired air heater SERIES HD INSTALLATION AND SERVICE MANUAL MANUFACTURED BY : BROTHERS LIMITED WARNING Improper installation, modification, adjustment or maintenance may cause damage, injury

More information

Field Start-Up Sheet Direct Fired Gas Equipment

Field Start-Up Sheet Direct Fired Gas Equipment Customer: Sales Representative: Model Number: Serial Number: Field Start-Up Sheet Direct Fired Gas Equipment ***Please Print*** INITIAL INSPECTION I. Installer Responsibilities 1. Remote Panel: All interconnecting

More information

ALK-V PHOTOELECTRIC SMOKE SENSOR

ALK-V PHOTOELECTRIC SMOKE SENSOR ALK-V PHOTOELECTRIC SMOKE SENSOR APPLICATION The HOCHIKI America ALK-V Photoelectric Smoke Sensor is particularly suited to detecting optically dense smoke typical of fires involving materials such as

More information

Guide To Troubleshooting INEFFICIENT COOLING FANS

Guide To Troubleshooting INEFFICIENT COOLING FANS Guide To Troubleshooting INEFFICIENT COOLING FANS TABLE OF CONTENTS Introduction Enclosure Cooling Basics Key Attributes of Enclosure Cooling Symptoms of Poor Enclosure Cooling Typical Cooling Fan Problems

More information

Flame Safeguards LFE10. Building Technologies HVAC Products

Flame Safeguards LFE10. Building Technologies HVAC Products 7 71 Flame Safeguards LAE LFE Flame safeguards for burners with intermittent operation The LAE is used for the supervision and indication of oil flames The LFE is used for the supervision and indication

More information

POINTEK CLS 100 OINTEK CLS 100 CAPACITANCE LIQUIDS/SOLIDS. Instruction Manual March 2001

POINTEK CLS 100 OINTEK CLS 100 CAPACITANCE LIQUIDS/SOLIDS. Instruction Manual March 2001 POINTEK CLS 100 CAPACITANCE LIQUIDS/SOLIDS Instruction Manual March 2001 OINTEK CLS 100 Safety Guidelines Warning notices must be observed to ensure personal safety as well as that of others, and to protect

More information

Flame detector. Building Technologies Division Infrastructure & Cities Sector

Flame detector. Building Technologies Division Infrastructure & Cities Sector 7 711 Flame detector QRA4 UV flame detector for use with burner controls from Siemens for the supervision of gas or oil flames. The QRA4... and this Data Sheet are intended for use by OEMs which integrate

More information

Photovoltaic Cables EN H1Z2Z2-K

Photovoltaic Cables EN H1Z2Z2-K Photovoltaic Cables EN 50618 H1Z2Z2-K COMPANY PROFILE Caledonian, established in 1978, offers one of the most complete lines of fiber and copper cabling system solutions with over hundreds of different

More information

FLAME SENSOR FS-2000E

FLAME SENSOR FS-2000E FLAME SENSOR FS-2000E We appreciate your purchase of a TAKEX flame sensor. Please read this instruction manual carefully for correct and effective use. This sensor is designed to detect flames and to initiate

More information