General Routing Interface

Size: px
Start display at page:

Download "General Routing Interface"

Transcription

1 General Routing Interface Features The General Routing Interface Card is an optional module to provide Fire and Fault Routing Outputs compliant with BSEN54-2: 1998 Clauses 7.9 and 8.9 and BS5839-1: Two Fire Routing Outputs are provided for differentiation between Call Point (MCP) and Automatic Detector (AFD) Fire Alarm Signals if required. Outputs are monitored for open and short circuit wiring conditions in both the quiescent (off) and active (on) modes with fault conditions indicated on the panel (CIE) display / LED Indicators. Outputs are compatible with a wide range of routing equipment coil impedances (1kΩ to 5kΩ). Simple to install and configure. Circuitry is prepared ready for Confirmation inputs in accordance with the EN54-2:1997 +A1:2006 Clause The operation and functions described in this manual are available from Software Version onwards.

2 Specifications & Ordering: Models, Sales Order Parts: Mxp-032 Mxp-032F General Routing Interface General Routing Interface (fitted) Applications / Limitations: EN54-2 compliant routing interfaces providing monitored outputs to fire alarm and fault routing circuits. Circuits are monitored for open and short circuit conditions in both the normal and active mode in compliance with EN54-2 and BS5839-1: 2002 Clause a. The outputs will drive relay coils with impedances of between 1kΩ and 5kΩ. Compatibility: Can be used with Mx-4200, Mx-4400 and Mx-4800 control panels programmed with Version software (or later) and fitted with base card hardware revision levels 10 ( Mx-4400) and 09 ( Mx- 4200) or later. Compatible with the PC Configuration Tool from version 4.19 or later. Requires installation of the Mxp-031 Peripheral Bus Interface Adaptor card in the panel. Item Output Circuit Specification Fire & Fault Outputs Input Circuit Specification (Future Option) Operating Voltage Panel Loading, standby, AC Mains Fail (fault output off) Panel Loading, quiescent state (fault output on) Panel Loading, ALL inputs and outputs active On-board Indications Specification Details 24VDC Active, 5VDC Monitor 1.0mA monitor mode nominal, 5.0mA 25.0mA active (energised) mode depending on coil impendence, 40.0mA maximum short circuit current 4x Monitored Input EOL 10KΩ, Operating Resistor 470Ω 24V DC [Range 19-28V] from panel Auxiliary Supply Output 43mA 45mA +24mA (1KΩ coil), +5mA (5KΩ coil) 48mA, +72mA (1KΩ coils), +15mA (5KΩ coils) 6x LED Indicators for Outputs Active, Communications and Microprocessor Heartbeat Operating Temperature 0 C to 50 C Approvals EN54-2:1997 +A1:2006 As our policy is one of constant product improvement the right is therefore reserved to modify product specifications without prior notice

3 Table of Contents Page 1. INTRODUCTION INSTALLING THE CARD IN THE PANEL... 4 A. MOUNTING THE CARD... 4 B. WIRING... 4 C. EOL JUMPER INSTALLING THE CARD IN AN EXTERNAL ENCLOSURE FIELD WIRING CONNECTIONS... 5 A. OUTPUT WIRING... 5 B. INPUT WIRING CONFIGURATION Introduction Outputs to Routing Equipment Clauses 7.9 and 8.9. The Routing Interface Card provides monitored outputs in accordance with EN54-2 for connection to: - Fire Routing Equipment (Item E) and - Fault Routing Equipment (Item J). Two fire routing outputs are provided. These can be independently programmed with different cause and effect rules. They can, for example, be programmed to signal MCP (Call Point) and AFD (Automatic Fire Detection) conditions respectively. When Fire Routing is disabled at the panel, both outputs are disabled. Also provided for future options is provision for confirmation / fault inputs. Details of these are provided below but are not currently supported by the panel. The panel will indicate activated, disabled and fault conditions for each output using a combination of the LED Indicators (Function 1, 2 & 3 for Fire Alarm Output) and the Alphanumeric Display. The panel will indicate a fault condition if it fails to establish communications (or loses communications) with the General Routing Interface Card. 3

4 J1 EOL SELECT 2. Installing the Card in the Panel a. Mounting the Card J1 EOL SELECT The card is fitted to the chassis using 4x M3 screws. Refer to the diagram opposite. Screws marked * must be securely fixed to provide an earth connection for EMC purposes. * Routing Interface TB4 J1 * M3 Fixing Screws Base Card TB2 Communications TB3 DC SUPPLY b. Wiring Cables are provided for internal connection of a local 24V DC supply and communications connections. Connect the DC Supply from the AUX output (TB2 on the base card) to the connections on TB4 observing polarities (V+ to 24V and 0V to 0V). Mounting Position for the Routing Interface Card A B 24V 0V TB4 Routing Interface Connect the communications cable between TB3 on the Base Card to the connections on TB4 so that 'A' is connected to 'A' and 'B' to 'B'. Route the wiring as shown in the diagram above. TB2 Base Card TB3 To Batteries 0V V+ AUX B A B A c. EOL Jumper OUT IN If the card is mounted in the panel, ensure that the EOL jumper (J1) is set to the OUT position. OUT IN OUT IN If the card is mounted external to the panel and is the last (furthest) unit on the link then set the EOL Jumper (J1) to the IN position. 3. Installing the card in an External Enclosure Alternatively, the card may be mounted in a separate enclosure such as Mxm-044. This may be required if a modem / 8x relay output / sounder splitter card option is installed in the panel. In this case, the enclosure should be located not greater than 10M from the control panel (and must be within the same room) with the wiring run in rigid metal conduit. All wiring should be in 18AWG cable minimum. See above for connections. Communications cable must be twisted-pair type. Use the right hand A+B connections on TB3. Set Jumper J1 as described above. 4

5 4. Field Wiring Connections The Routing Interface can be used to output monitored signals to Fire Alarm Routing Equipment and to Fault Routing Equipment. Each function comprises of an output circuit (and optional confirmation input future option). Each circuit is monitored for open circuit and short circuit wiring conditions in both the activated and quiescent states. The outputs can be connected to a remote relay coil with a resistance of 1KΩ to 5KΩ. A suppression diode must be connected across the coil observe connection polarities. The Fault Output is normally energised during the quiescent condition it will de-energise on any fault or on total loss of power. NB: These circuits are classed as Safety Extra Low Voltage (SELV) circuits. Route away from mains wiring Not Currently Used Power + Data OUT IN OUT IN OUT IN1 IN2 FIRE 1 FIRE 2 FAULT Routing Interface Typical Arrangement a. Output Wiring Connect the output wiring to the + and - terminals. Use cables of appropriate size for the voltage and loading required. All cables should be to the same voltage and insulation specification appropriate to the intended application. Maximum cable impedance = 100Ω. Refer to diagram above for typical arrangement the wiring to the relay coil in the remote equipment. Refer to the specification section for the maximum and minimum compatible coil impedances. If an output is not used connect a 4.7KΩ EOL resistor across the relevant terminals. b. Input Wiring FUTURE OPTION The fire alarm outputs each have an associated input for a confirmation signal to indicate that the output signal has reached the receiving centre. IN1 & IN2 are additional inputs. A 10kΩ E.O.L resistor should be placed across any unused input terminals. 10K ¼W The monitored inputs circuits should be wired as per the diagram opposite. 470R ¼W Volt free contact The 470Ω (operating) resistor and 10kΩ (E.O.L) resistor arrangement should be made adjacent to the switch contacts to ensure that correct fault monitoring of the total circuit (including the wiring) between the input contact and the General Routing Interface unit is maintained. + SWITCH INPUT 'n' 5

6 5. Configuration To configure the panel for monitored fire and fault routing, select the SETUP option from the COMMISSION menus and scroll down to the following display. [Setup] TRACE LOGGING MODE : STANDARD DETECTOR BLINKING : NONE EARTH MONITORING : FIRE/FAULT ROUTING : x More> To enable the operation of the General Routing Interface, press the button to cycle through the options and select the MONITORED option. X MONITORED NOT MONITORED No Fire / Fault Routing Fire / Fault Routing uses the General Routing Interface Card Fire / Fault Routing uses the base card volt-free relay outputs As soon as the MONITORED option is selected, the panel will try to establish communications with the General Routing Interface Card. If connection cannot be established then a fault condition will be indicated. By default, the outputs are configured to use Output Groups 199 (Fire) and 200 (Fault). These can be adjusted or can be assigned to alternative output groups as required for the application. Refer to the Panel Installation and Commissioning Manual for general information on output group programming. 6

7 USER NOTES

8 Doc Number: Revision: 02A Advanced Electronics Ltd Moorland Way, Cramlington, Northumberland, NE23 1WE UK Tel: +44 (0) Fax: +44 (0) Web:

4100S. The operation and functions described in this manual are available from Software Version 4100S onwards.

4100S. The operation and functions described in this manual are available from Software Version 4100S onwards. 4100S The operation and functions described in this manual are available from Software Version 4100S-023-013 onwards. Specifications: Item Specification Details Enclosure Steel IP30 Dimensions H x W x

More information

Product Data Sheet. Remote Terminals. Features:

Product Data Sheet. Remote Terminals. Features: Remote Terminals Product Data Sheet Features: Based around two core products, the Mx- 4010 Remote Display Terminal (RDT) and the fully functional Mx-4020 Remote Control Terminal (RCT). Both remote terminals

More information

The EN54 Part 2 & 4 Fire System

The EN54 Part 2 & 4 Fire System Scope of work: To design, supply, install and commission an Analogue Addressable Fire Alarm Control System in accordance with the details specified herein and in accordance with supplied drawings The EN54

More information

Fire Alarm Panels. Product Manual.

Fire Alarm Panels. Product Manual. Fire Alarm Panels Product Manual The operation and functions described in this manual are available from Software Version 5000-050-04 onwards. Specifications: Item Specification Details Part Number: Mx-5100

More information

PNC 1000 SERIES 2, 4, 8 Zone Fire Alarm Control Panel

PNC 1000 SERIES 2, 4, 8 Zone Fire Alarm Control Panel PNC 1000 SERIES 2, 4, 8 Zone Fire Alarm Control Panel INSTALLATION, OPERATION AND MAINTENANCE MANUAL Version: CN-PM-1000.VER1.1-12/2012 EN54 INFORMATION In accordance with EN 54-2 clause 13.7, the maximum

More information

4100U City and Relay Cards Installation Instructions

4100U City and Relay Cards Installation Instructions 4100U City and Relay Cards Installation Instructions Introduction This publication describes the installation procedure for the following: 4100-6031/6032 City Circuit Cards 4100-6033 Alarm Relay Card Inspecting

More information

Reliably Advanced Extinguishing Control

Reliably Advanced Extinguishing Control Reliably Advanced Extinguishing Control The Best Choice for Asset Protection What suppression and extinguishant control panel would you choose to protect the literary collection of an entire nation? 47

More information

Reliably Advanced Extinguishing Control

Reliably Advanced Extinguishing Control Reliably Advanced Extinguishing Control 14 years. 60 countries. Still Advanced. We re the same people, with the same commitment to excellence and customer satisfaction and now we have a brand that reflects

More information

Installation, Operating and Maintenance Manual

Installation, Operating and Maintenance Manual STATUS ZONES CONTROLS FIRE FAULT DISABLED FIRE 1 2 3 4 5 6 7 8 TEST FAULT DISABLED 1 5 BUZZER SILENCE RESET 1 2 TEST 2 6 LAMP TEST 3 SUPPLY 3 7 SYSTEM FAULT 4 8 SOUNDERS ACTIVATE/ SILENCE 4 FAULTS INSTRUCTIONS

More information

The EN54 Part 2 and 4 Fire System

The EN54 Part 2 and 4 Fire System Scope of work: To design, supply, install and commission a Fire Alarm Control System in accordance with the details specified herein and in accordance with supplied drawings The EN54 Part 2 and 4 Fire

More information

5000 Series Rack Panels

5000 Series Rack Panels 5000 Series Rack Panels The operation and functions described in this manual are available from Software Version Mx5000-050-04 onwards. Specifications & Ordering: Models, Sales Order Parts: Mx-5101xR Panel

More information

1 INTRODUCTION NOTICE WARNINGS AND CAUTIONS NATIONAL APPROVALS EMC COMPATIBILITY UNPACKING...

1 INTRODUCTION NOTICE WARNINGS AND CAUTIONS NATIONAL APPROVALS EMC COMPATIBILITY UNPACKING... ZXA / ZXE FIRE ALARM CONTROL PANEL MORLEY-IAS Table of Contents 1 INTRODUCTION...1 1.1 NOTICE... 1 1.2 WARNINGS AND CAUTIONS... 1 1.3 NATIONAL APPROVALS... 2 1.4 EMC COMPATIBILITY... 2 2 UNPACKING...3

More information

Intelligent Single Loop Fire Alarm Control Panel

Intelligent Single Loop Fire Alarm Control Panel Intelligent Single Loop Fire Alarm Control Panel The CAX-CTL-1L Intelligent Single Loop Fire Alarm Control Panel is a member of the industry leading Axis AX Series Intelligent Fre Alarm Control Panels

More information

FIREBETA EXTINGUISHING CONTROL PANEL (ECP)

FIREBETA EXTINGUISHING CONTROL PANEL (ECP) F I R E D E T E C T I O N A N D C O N T R O L FIREBETA EXTINGUISHING CONTROL PANEL (ECP) Three versions: 2 areas of detection and 1 area extinguishing 4 areas of detection and 1 area extinguishing 4 areas

More information

1 INTRODUCTION NOTICE WARNINGS AND CAUTIONS NATIONAL APPROVALS EN54 INFORMATION UNPACKING...

1 INTRODUCTION NOTICE WARNINGS AND CAUTIONS NATIONAL APPROVALS EN54 INFORMATION UNPACKING... ZX Fire Alarm Control Panels MORLEY-IAS Table of Contents 1 INTRODUCTION...1 1.1 NOTICE...1 1.2 WARNINGS AND CAUTIONS...1 1.3 NATIONAL APPROVALS...2 1.4 EN54 INFORMATION...2 2 UNPACKING...4 3 INSTALLATION...5

More information

Application, Installation, Operation & Maintenance Manual

Application, Installation, Operation & Maintenance Manual APPROVED BY:JBJ PRESCIENT III FIRE ALARM & GAS EXTINGUISHING CONTROL PANEL Application, Installation, Operation & Maintenance Manual PAGE 1 of 43 CONTENTS 1. INTRODUCTION... 3 2. GENERAL DESCRIPTION...

More information

Intelligent 2 & 4 Loop Fire Alarm Control Panels

Intelligent 2 & 4 Loop Fire Alarm Control Panels Intelligent 2 & 4 Loop Fire Alarm Control Panels Advanced has combined the latest technology with many years of fire experience, to create the Axis AX Series Intelligent Fire Alarm Control Panels. The

More information

1X-F Series Installation Manual

1X-F Series Installation Manual 1X-F Series Installation Manual P/N 501-415003-1-31 REV 03.10 ISS 13NOV13 Copyright Trademarks and patents Manufacturer Version Certification European Union directives Contact information 2013 UTC Fire

More information

Conventional Fire Alarm System 2014 V1.2

Conventional Fire Alarm System 2014 V1.2 Conventional Fire Alarm System 2014 V1.2 Product Overview Control Panel 2 Conventional Fire Panel GST102A 2 zone Fire panel GST104A 4 zone Fire panel GST108A 8 zone Fire panel GST116A 16 zone Fire Panel

More information

Installation and user manual for the CF5000, MF5000 and FXP5000 range of fire panels

Installation and user manual for the CF5000, MF5000 and FXP5000 range of fire panels CF5000, MF5000 and FXP5000 Installation and user manual for the CF5000, MF5000 and FXP5000 range of fire panels 16 zone panels Contents PANEL INSTALLATION...3 Installation...3 PANEL WIRING... 3 Mains power

More information

Interface Modules for SENTRI

Interface Modules for SENTRI EQUIPMENT INTERFACED Data and Installation Interface s for SENTRI Low voltage (LV) / SEN-INT-INPUT 1- Interface (low voltage) SEN-INT-OUTPUT 1- & 1- Interface (low voltage) SEN-INT-4IO # 4- / Interface

More information

System 800 Addressable Fire Detection & Alarm System

System 800 Addressable Fire Detection & Alarm System SECTION 5: page 1 Section 5: System 800 Addressable Fire Detection & Alarm System SECTION 5: page 3 10 reasons to specify 800 1 Plug and Play A user friendly panel not requiring special software tools

More information

Touch 10. The operation and functions described in this manual are available from Software Version onwards.

Touch 10. The operation and functions described in this manual are available from Software Version onwards. Touch 1 The operation and functions described in this manual are available from Software Version 5-53-1 onwards. Specifications: Item Specification Details Part Number: Touch-1 Touch-1/FT Enclosure Steel

More information

The EN54 Part 2, 4 and 13 Fire System

The EN54 Part 2, 4 and 13 Fire System Scope of work: To design, supply, install and commission an Analogue Addressable Fire Alarm Control System in accordance with the details specified herein and in accordance with supplied drawings The EN54

More information

Control Panel Engineering and Commissioning Manual (TO BE RETAINED BY THE COMMISSIONING ENGINEER)

Control Panel Engineering and Commissioning Manual (TO BE RETAINED BY THE COMMISSIONING ENGINEER) Fire Detection & Alarm System Control Panel (Suitable for TWINFLEX pro control panels from V2.00) Control Panel Engineering and Commissioning Manual (TO BE RETAINED BY THE COMMISSIONING ENGINEER) 26-0959

More information

BT1 SINGLE ZONE FIRE ALARM SYSTEM OPERATORS MANUAL

BT1 SINGLE ZONE FIRE ALARM SYSTEM OPERATORS MANUAL BT1 SINGLE ZONE FIRE ALARM SYSTEM OPERATORS MANUAL 26 Aug 2015 V1.8 Page 1 SECTION CONTENTS PAGE NO. 1.0 SYSTEMS DESCRIPTION 1.1 General descriptions 2 1.2 Master Alarm PCB 2 1.3 Zone Display Board 2 1.4

More information

3500 CONVENTIONAL FIRE ALARM CONTROL PANEL

3500 CONVENTIONAL FIRE ALARM CONTROL PANEL 3500 CONVENTIONAL FIRE ALARM CONTROL PANEL INSTALLATION AND COMMISSIONING MANUAL Protec Fire Detection PLC, Protec House, Churchill Way, Nelson, Lancashire, BB9 6RT. Telephone: +44 (0) 1282 717171 Fax:

More information

Document No Issue 4 product manual

Document No Issue 4 product manual DX Document No. 997-147-000-4 Issue 4 product manual MORLEY-IAS Dimension Series Table of Contents 1 INTRODUCTION... 7 1.1 NOTICE... 7 1.2 MODELS... 7 1.3 WARNINGS AND CAUTIONS... 9 1.4 NATIONAL APPROVALS...

More information

Intelligent Security & Fire Ltd

Intelligent Security & Fire Ltd full installation, commissioning and operating manuals can be downloaded from www.haes-systems.co.uk combined addressable / conventional fire alarm control panel User Guide Approved Document No. MFBU-04

More information

Booster Power Supply Manual

Booster Power Supply Manual Supply Manual DEVELOPED BY COPYRIGHT NOTICE General Signal Building Systems Corporation 6411 Parkland Drive Sarasota, FL 34243 (941) 739-4300 Copyright 1999 General Signal Building Systems Corporation

More information

Addressable NAC Output Module D327A

Addressable NAC Output Module D327A Installation Instructions Notice Addressable NAC Output Module D327A These instructions cover the installation of the D327A Addressable NAC Output Module in an analog system controlled by a Bosch D8024,

More information

Remote NAC Power Supply D7038

Remote NAC Power Supply D7038 Operation and Installation Guide Remote NAC Power Supply D7038 D7038 REMOTE NAC POWER SUPPLY Page 2 2005 Bosch Security Systems Contents Contents 1.0 Overview...5 1.1 Module Control...5 1.1.1 Option Bus

More information

Advanced FireAlarm Panel 1-4Loop

Advanced FireAlarm Panel 1-4Loop Advanced FireAlarm Panel 1-4Loop Advanced Technologies Advanced Electronics Ltd IP Gateway Monitoring and interrogation via the internet Password protected multiple user permissions Event notification

More information

ACSI AO ELECTRIC LATCH RETRACTION CONTROLLER INSTALLATION INSTRUCTIONS I.D. 1089, REV. F

ACSI AO ELECTRIC LATCH RETRACTION CONTROLLER INSTALLATION INSTRUCTIONS I.D. 1089, REV. F II 1400-2 ACSI 1406-04-AO ELECTRIC LATCH RETRACTION CONTROLLER INSTALLATION INSTRUCTIONS I.D. 1089, REV. F INSTALLATION Transformer Model BE31763001 by Basler Electric, Transformer Model 2010028 by Galaxy

More information

Excel-EN Conventional Fire Control Panel

Excel-EN Conventional Fire Control Panel Available as 2, 4, 6, 8,10 or 12 zones Approved to EN54-2 & 4 Modular expansion zone cards Programmable relays and outputs Optional additional sounder circuits Optional additional programmable outputs

More information

LED Driver Module. These instructions contain procedures to follow in order to avoid personal injury and damage to equipment.

LED Driver Module. These instructions contain procedures to follow in order to avoid personal injury and damage to equipment. LED Driver Module Installation Guide 1.0 Notice These instructions are for installing Radionics LED Driver Module in a fire alarm system controlled by Radionics D8024 or D10024 Fire Alarm Control Panels

More information

OPERATION AND INSTALLATION MANUAL

OPERATION AND INSTALLATION MANUAL EX+Plus 2 ZONE, 1AREA EXTINGUISHANT CONTROL PANEL OPERATION AND INSTALLATION MANUAL INTRODUCTION The Premier EX Plus is a 2 zone, single area panel for controlling the release of extinguishing gases in

More information

Vocia VACIE. Reference Guide

Vocia VACIE. Reference Guide Vocia VACIE Reference Guide Document Revision 1.2.3, August 2015 Biamp Systems 9300 SW Gemini Drive Beaverton, Oregon 97008, U.S.A. (503) 641-7287 www.biamp.com INTRODUCTION... 3 SECTION 1... 4 VACIE CONFIGURATION...

More information

VACIE REFERENCE GUIDE REVISION 1.2.6

VACIE REFERENCE GUIDE REVISION 1.2.6 VACIE REFERENCE GUIDE REVISION 1.2.6 November 2016 INTRODUCTION... 3 SECTION 1... 4 VACIE CONFIGURATION... 4 Communications... 4 Vocia VACIE Devices... 4 Vocia Support devices:... 5 Power Supply and Network

More information

Conventional & Twin-wire Fire System

Conventional & Twin-wire Fire System Conventional & Twin-wire Fire System Advanced Customer Service At Advanced we re not just famous for our fire systems. Our Advanced360 customer support, service and technical training are widely acknowledged

More information

Installation and user manual for the FX range of fire panels. 1, 2, 4 and 8 zone panels

Installation and user manual for the FX range of fire panels. 1, 2, 4 and 8 zone panels Installation and user manual for the FX range of fire panels 1, 2, 4 and 8 zone panels Contents Panel installation 3 Panel connections 3 Wiring connection drawings 4 Panel facilities 6 Installation check

More information

Saffire User & Installation Manual. IMPORTANT This manual should be left with the panel after installation.

Saffire User & Installation Manual. IMPORTANT This manual should be left with the panel after installation. Saffire+ 8-12 User & Installation Manual IMPORTANT This manual should be left with the panel after installation. We reserve the right to change product specifications without prior notice. Copyright VRC

More information

FEC403EN Installation Manual

FEC403EN Installation Manual FEC403EN Installation Manual P/N 10-4101-501-2FC1-01 ISS 22JAN15 Copyright Trademarks and patents Manufacturer 2015 UTC Fire & Security. All rights reserved. The FEC403EN name and logo are trademarks of

More information

Harrington Signal HS-3100/3200 Fire Alarm Control Unit

Harrington Signal HS-3100/3200 Fire Alarm Control Unit HARRINGTON SIGNAL INC. FIRE ALARM Harrington Signal HS-3100/3200 Fire Alarm Control Unit Installation Manual Revision 2 January 2009 Document # LT-2000HAR Table of Contents 1.0 Technical Information...

More information

IDP-Zone-6 Six Zone Interface Module

IDP-Zone-6 Six Zone Interface Module INSTALLATION AND MAINTENANCE INSTRUCTIONS IDP-Zone-6 Six Zone Interface Module BEFORE INSTALLING If the modules will be installed in an existing operational system, inform the operator and local authority

More information

Product Manual SZ1145

Product Manual SZ1145 Product Manual SZ114 General Purpose Monitor Communicating Controls Description The SZ114 is a microprocessor-based monitoring and alarm interface designed to monitor up to four 1000 Ω platinum temperature

More information

FIREFORCE 8 NOTIFICATION APPLIANCE CIRCUIT EXPANDER INSTALLATION & OPERATION MANUAL

FIREFORCE 8 NOTIFICATION APPLIANCE CIRCUIT EXPANDER INSTALLATION & OPERATION MANUAL FIREFORCE 8 NOTIFICATION APPLIANCE CIRCUIT EXPANDER INSTALLATION & OPERATION MANUAL THE GAMEWELL COMPANY PN: 71981 60 PLEASANT STREET ISSUE A ASHLAND, MA 01721 3/22/2001 This page intentionally blank ii

More information

TECHNICAL DATA SHEET CONVENTIONAL FIRE ALARM SYSTEMS Conventional Fire Alarm Control Panel

TECHNICAL DATA SHEET CONVENTIONAL FIRE ALARM SYSTEMS Conventional Fire Alarm Control Panel CVENTIAL ALARM S Features: Description: The LF-CP Series Fire Alarm Control Panel is manufactured based on advanced technology while maintaining high quality during assembly. It is of solid state circuitry

More information

User Manual. Security Systems Security System L208

User Manual. Security Systems Security System L208 User Manual Security Systems Security System L208 a Contents This hand book is a technical instruction document for the installation, commissioning and operation of the L208 intrusion alarm security system.

More information

1200-HCM DIN RAIL MOUNTING FIRE SYSTEM MODULE Fire Detection & Extinguishant Control A R T PATOL LIMITED SUPPLY FAULT SOUNDER

1200-HCM DIN RAIL MOUNTING FIRE SYSTEM MODULE Fire Detection & Extinguishant Control A R T PATOL LIMITED SUPPLY FAULT SOUNDER Application The unit is primarily intended for use where there is a requirement to integrate a limited fire protection function into a larger control equipment scheme, or in specialist applications where

More information

PERTRONIC INDUSTRIES LTD F4-RMAX Installation Note

PERTRONIC INDUSTRIES LTD F4-RMAX Installation Note Product Overview: The Pertronic F4 Remote LED Mimic / Aux Relay Module F4-RMAX is an optional extra for the Pertronic F4 conventional 4-zone fire alarm panel. This board enables the fire alarm panel to

More information

FTEN1, FTEN2, & FTEN4 1, 2 & 4 ZONE FIRE DETECTION AND ALARM CONTROL PANELS

FTEN1, FTEN2, & FTEN4 1, 2 & 4 ZONE FIRE DETECTION AND ALARM CONTROL PANELS QUICK USER GUIDE FOR, 2 & 4 ZONE PANELS INDICATORS COLOUR INDICATION MON FAULT Yellow On when a fault condition has occurred, or if no other fault Led is on, this indicates 24v auxiliary fuse failure.

More information

INDEX 1- Introduction The Control Pane...7l 4.1- The Control Panel 1 and 2 Loops The Control Panel 4 and 8 Loops...

INDEX 1- Introduction The Control Pane...7l 4.1- The Control Panel 1 and 2 Loops The Control Panel 4 and 8 Loops... GUIDE MANUAL INDEX 1- Introduction...5...5...6 4- The Control Pane...7l 4.1- The Control Panel 1 and 2 Loops...7 4.2- The Control Panel 4 and 8 Loops...9 5- Installation Guide...10 5.1- Pre-Installation

More information

ANNUNCIATOR FIXED MODULE

ANNUNCIATOR FIXED MODULE 12 Clintonville Road Northford, CT 06472 Phone: 203-484-7161 Fax: 203-484-7118 THE ANNUNCIATOR FIXED MODULE Installation Manual for the AFM-16ATF and AFM-32AF Annunciator Modules Document # 15970 3/27/95

More information

Models NFPA 1221-A, NFPA 1221-B Public Safety DAS Annunciator Panel. Revision E 61117

Models NFPA 1221-A, NFPA 1221-B Public Safety DAS Annunciator Panel. Revision E 61117 Models NFPA 1221-A, NFPA 1221-B Public Safety DAS Annunciator Panel Revision E 61117 CAUTION: (Read This First) This panel has been designed to make it nearly bullet proof to mistakes made when wiring

More information

Product Manual SZ1144

Product Manual SZ1144 Product Manual SZ1144 Refrigeration Temperature Monitor Communicating Controls Description The SZ1144 is a microprocessor-based monitoring and alarm interface designed to monitor up to four 1000 Ω platinum

More information

Fire Control Panel FS5100

Fire Control Panel FS5100 Fire Control Panel FS5100 INSTRUCTION MANUAL Revision 6/02.11 Contents 1. Introduction... 5 2. Terminology... 5 3. Function... 7 4. Technical data... 7 4.1. Modules... 7 4.1.1. Type of modules... 7 4.1.2.

More information

Document No Issue 02 operation & installation manual. ZXr-A ZXr-P

Document No Issue 02 operation & installation manual. ZXr-A ZXr-P ZXr-A ZXr-P Document No. 996-144 Issue 02 operation & installation manual MORLEY-IAS ZXr-A / ZXr-P Repeaters Table of Contents 1 INTRODUCTION... 3 1.1 NOTICE... 3 1.2 WARNINGS AND CAUTIONS... 3 1.3 NATIONAL

More information

LifeAlarm Fire Alarm Control Panels

LifeAlarm Fire Alarm Control Panels LifeAlarm Fire Alarm Control Panels UL, ULC Approved* Features Control panel operator convenience features: Wide viewing angle 2 x 20 (40 character) alphanumeric LCD and dedicated LEDs provide convenient

More information

ED820-24V MODEL INSTRUCTION MANUAL. fire DETECTOR

ED820-24V MODEL INSTRUCTION MANUAL. fire DETECTOR ED820 24V MODEL fire DETECTOR INSTRUCTION MANUAL Address: Enigma House, Enigma Business Park, Malvern, Worcestershire, WR14 1GD Tel: 44 (0)1684 891500 Fax: 44 (0)1684 891600 Email: sales@electronicdevices.co.uk

More information

Fire-Cryer. Plus Application Guide APPLICATION GUIDE FIRE EXIT VIMPEX. Shaping Alarm Technology

Fire-Cryer. Plus Application Guide APPLICATION GUIDE FIRE EXIT VIMPEX. Shaping Alarm Technology Fire-Cryer Plus Application Guide APPLICATION GUIDE FIRE EXIT VIMPEX Shaping Alarm Technology Fire-Cryer Plus The Fire-Cryer range of voice sounders was first introduced to the market by Vimpex in 1999.

More information

RMS/RPX Reader. User Manual

RMS/RPX Reader. User Manual RMS/RPX Reader User Manual Copyright Disclaimer Trademarks and patents Intended use FCC compliance Copyright 2005, GE Security Inc. All rights reserved. This document may not be copied or otherwise reproduced,

More information

MODUL-R FIRE ALARM CONTROL PANELS. MR-2900/MR-2920 Addressable Fire Alarm Control Panels MEA. Features. Description

MODUL-R FIRE ALARM CONTROL PANELS. MR-2900/MR-2920 Addressable Fire Alarm Control Panels MEA. Features. Description MODUL-R FIRE ALARM CONTROL PANELS MR-2900/MR-2920 Addressable Fire Alarm Control Panels Description MR-2900 Fire Alarm Control Panel The MR-2900 fire alarm system control unit is the heart of a sophisticated

More information

ZXe INTELLIGENT MULTI PROTOCOL FIRE ALARM CONTROL PANEL

ZXe INTELLIGENT MULTI PROTOCOL FIRE ALARM CONTROL PANEL ZXe INTELLIGENT MULTI PROTOCOL FIRE ALARM CONTROL PANEL PRODUCT Specification FEATURES Designed To Meet The Requirements Of EN54 Expandable From 1 To 5 Loops As Standard A Variety Of Networking Options

More information

Application Guide 001

Application Guide 001 Application Guide 001 Morley-IAS by Honeywell ZXSe Fire Panel BS7273-4 Category A Contents: Application note information: 2 Basic BS7273-4 Category A compliant C&E example 2 Zoned BS7273-4 Category A compliant

More information

SIMPLICITY CO CARBON MONOXIDE DETECTION & VENTILATION PANEL

SIMPLICITY CO CARBON MONOXIDE DETECTION & VENTILATION PANEL SIMPLICITY CO CARBON MONOXIDE DETECTION & VENTILATION PANEL USER MANUAL 1 Table of Contents 1 SAFETY INFORMATION...3 1.1 SAFETY PRECAUTIONS DURING NORMAL OPERATION OF PANEL...3 1.3 BATTERY INFORMATION...3

More information

Technical Data Sheet

Technical Data Sheet Mx-1000 Series Technical Data Sheet Application Guide for Mx-1002, Mx-1004, Mx-1008, Mx-1016 & Mx-1032 Conventional Fire Alarm Control Panels And Mx-1108, Mx-1116 & Mx-1132 Repeater Panels Document Number:

More information

Notification Appliance Circuit Module

Notification Appliance Circuit Module Notification Appliance Circuit Module D192G en Installation guide Notification Appliance Circuit Module Notices en 3 1 Notices These instructions cover the installation of the D192G Notification Appliance

More information

Touch Screen 1 loop Addressable Fire Alarm Panel

Touch Screen 1 loop Addressable Fire Alarm Panel evolution 1 Touch Screen 1 loop Addressable Fire Alarm Panel The evolution 1 control panel offers complete compatibility with the award winning range of Nittan evolution detection and alarm devices and

More information

Fire Safety. Installation Instructions Model SMB-2 Main Control Board OPERATION INSTALLATION

Fire Safety. Installation Instructions Model SMB-2 Main Control Board OPERATION INSTALLATION Fire Safety Installation Instructions Model SMB- Main Control Board OPERATION The SIEMENS Model SMB- board in each MXL-IQ System controls operations and monitors input device identity, network communication,

More information

NFS Supra / VSN-2Plus / ESS-2Plus Conventional Fire Alarm Control Panel. Installation and Operating Manual

NFS Supra / VSN-2Plus / ESS-2Plus Conventional Fire Alarm Control Panel. Installation and Operating Manual / VSN-2Plus / ESS-2Plus Conventional Fire Alarm Control Panel Installation and Operating Manual HLSI-MN-025-I v.05 April 2015 Note: This manual is valid for the following control panel models: NFS-Supra

More information

FIREPRO INSTALLATION MANUAL FIRE ALARM CONTROL PANEL INSTALLATION MANUAL. Approved Document No. GLT Issue: 1. 8 Author: NRPJ Date: 7/ 3/201 4

FIREPRO INSTALLATION MANUAL FIRE ALARM CONTROL PANEL INSTALLATION MANUAL. Approved Document No. GLT Issue: 1. 8 Author: NRPJ Date: 7/ 3/201 4 FIRE ALARM CONTROL PANEL INSTALLATION MANUAL Approved Document No. GLT -201-7-3 Issue: 1. 8 Author: NRPJ Date: 7/ 3/201 4 CONTENTS 1. INTRODUCTION... 1.1 HANDLING THE PCBS... 1.2 USING THIS MANUAL... 1.3

More information

KT-100 Door Controller

KT-100 Door Controller WARNING: This manual contains information on limitations regarding product use and function and information on the limitations as to liability of the manufacturer. The entire manual should be carefully

More information

CONTENTS. GST102A/104A/108A/116A Conventional Fire Alarm Control Panel Installation and Operation Manual

CONTENTS. GST102A/104A/108A/116A Conventional Fire Alarm Control Panel Installation and Operation Manual CONTENTS Installation Precautions... 1 EN 54 Information... 2 Chapter 1 Product Overview... 3 1.1 Features... 3 1.2 Technical Specifications... 3 1.2.1 Operating Voltage... 3 1.2.2 Batteries... 3 1.2.3

More information

INPUT / OUTPUT MINI MODULES

INPUT / OUTPUT MINI MODULES INPUT / OUTPUT MINI MODULES APPLICATION The Addressable Control and Monitor mini modules are the latest technology for a loop powered module. Installed on the same loop with other devices such as detectors

More information

Control Panel Engineering and Commissioning Manual (TO BE RETAINED BY THE COMMISSIONING ENGINEER)

Control Panel Engineering and Commissioning Manual (TO BE RETAINED BY THE COMMISSIONING ENGINEER) Fire Detection & Alarm System Control Panel V3 (Suitable for Quadnet control panels from V2.00) Control Panel Engineering and Commissioning Manual (TO BE RETAINED BY THE COMMISSIONING ENGINEER) 26-0582

More information

TECHNICAL DATA OBSOLETE

TECHNICAL DATA OBSOLETE Deluge Devices 270a 1. PRODUCT NAME VIKING PAR-3 Available since 1991 2. MANUFACTURED FOR: THE VIKING CORPORATION 210 N. Industrial Park Road Hastings, Michigan 49058 U.S.A. Telephone: (269) 945-9501 (877)

More information

ISOMETER IRDH375. Insulation monitoring device for unearthed AC, AC/DC and DC systems (IT systems)

ISOMETER IRDH375. Insulation monitoring device for unearthed AC, AC/DC and DC systems (IT systems) Insulation monitoring device for unearthed AC, AC/DC and DC systems (IT systems) IRDH375_D00124_01_D_XXEN/07.2018 Insulation monitoring device for unearthed AC, AC/DC and DC systems (IT systems) Product

More information

UNC100 Integra Manual

UNC100 Integra Manual UNC100 Integra Manual New Generation Building Security July 30, 2014 V1.2 Copyright Notice Copyright 1995-2014 by All rights reserved Worldwide. Printed in Canada. This publication has been provided pursuant

More information

SC-6 Six Supervised Control Module

SC-6 Six Supervised Control Module INSTALLATION AND MAINTENANCE INSTRUCTIONS SC-6 Six Supervised Control Module SPECIFICATIONS Normal Operating Voltage: Stand-By Current: Alarm Current: Temperature Range: Humidity: Dimensions: Accessories:

More information

Product Catalogue. Intelligent Control Equipment for Life Safety. Issue 1

Product Catalogue. Intelligent Control Equipment for Life Safety.   Issue 1 Product Catalogue Intelligent Control Equipment for Life Safety Mx-Range Issue 1 Fire Detection Gas Extinguishing Hearing Impaired Alarms Disabled Refuge Alarms www.advel.co.uk CONTENTS 1 2 Introduction

More information

BS-100 DYFI. Installation handbook. Protecting environment, life and property... P-BS100/DCE

BS-100 DYFI. Installation handbook.  Protecting environment, life and property... P-BS100/DCE BS-100 DYFI Protecting environment, life and property... P-BS100/DCE P-BS100/DCE/Doc/961023 2 Autronica Fire and Security AS Contents Please observe! This handbook contains installation instructions for

More information

ACSI MODEL 1410 POWER SUPPLY INSTALLATION INSTRUCTIONS

ACSI MODEL 1410 POWER SUPPLY INSTALLATION INSTRUCTIONS II 1400-3 ACSI MODEL 1410 POWER SUPPLY INSTALLATION INSTRUCTIONS Features: For use with doors or groups of doors that must interlock with each other to regulate control of accessing one area from another,

More information

INFINITY 8 INSTALLATION MANUAL FIRE ALARM CONTROL PANEL INSTALLATION MANUAL

INFINITY 8 INSTALLATION MANUAL FIRE ALARM CONTROL PANEL INSTALLATION MANUAL FIRE ALARM CONTROL PANEL INSTALLATION MANUAL Approved Document No. GLT-201-7-1 CONTENTS 1. INTRODUCTION... 1.1 HANDLING THE PCBS... 1.2 USING THIS MANUAL... 1.3 ABOUT THE INFINITY FIRE ALARM CONTROL PANEL

More information

Multiplex Eight Input Remote Modules

Multiplex Eight Input Remote Modules Multiplex Eight Input Remote Modules 1.0 Introduction These instructions cover the installation of the D7042/D7042B Eight Input Remote Modules in a fire system supervised by an FPD-7024 Fire Alarm Control

More information

GE Security. FP1200, FP2000 and KSA1200 series fire panels, repeaters and emulators Interconnection and wiring

GE Security. FP1200, FP2000 and KSA1200 series fire panels, repeaters and emulators Interconnection and wiring GE Security FP1200, FP2000 and KSA1200 series fire panels, repeaters and emulators Interconnection and wiring Version v2-2 / September 2005 Aritech and Kilsen are GE Security brands. http://www.geindustrial.com/ge-interlogix/emea

More information

Installation and user manual for the BiWire / Conventional Repeater Panel

Installation and user manual for the BiWire / Conventional Repeater Panel Panel EFBWCV-REPEATER Contents Introduction.... 3 Purpose... 3 The Panel.... 3 Indication Equipment (IE).... 3 Power Supply Equipment (PSE).... 4 System Wiring.... 5 Status Indications.... 5 Repeater I/O....

More information

DS7465i. Installation Instructions. Input/Output Module

DS7465i. Installation Instructions. Input/Output Module DS7465i EN Installation Instructions Input/Output Module DS7465i Installation Instructions.0 Introduction EN 2.0 Introduction The DS7465i Input/Output Module operates with compatible multiplex systems.

More information

Fire Extinguishing Control Panel INSTRUCTION MANUAL. Revision 8/ Instruction Manual Page 1 Revision 8/01.17 of 63

Fire Extinguishing Control Panel INSTRUCTION MANUAL. Revision 8/ Instruction Manual Page 1 Revision 8/01.17 of 63 Fire Extinguishing Control Panel FS5200Е INSTRUCTION MANUAL Revision 8/01.17 Instruction Manual Page 1 1. 2. 3. 4. 4.1. 4.2. 4.2.1. 4.2.2. 4.2.3. 4.2.4. 4.2.5. 4.2.6. 4.2.7. 4.2.8. 4.2.9. 4.2.10. 4.2.11.

More information

Interface and EOL Modules 8

Interface and EOL Modules 8 Interface and EOL Modules Interface Modules Series 420 25 Interface Modules Series 100 291 EOL Modules 293 254 Interface and EOL Modules Interface Modules Series 420 Interface Modules Serie 420 Interface

More information

PS6 SERIES. Installation PS6 SERIES. Power Supplies c/w Fire Panel Interface, EOL Trigger and Standby Power Option

PS6 SERIES. Installation PS6 SERIES. Power Supplies c/w Fire Panel Interface, EOL Trigger and Standby Power Option Installation PS6 SERIES Power Supplies PS6 SERIES Power Supplies c/w Fire Panel Interface, EOL Trigger and Standby Power Option Installation and Specifications Manual ISDPS6_SERIES 08121590 PCN15016 R05/15GR

More information

SPECIFICATION: AlarmLine TM INTELLIGENT LINEAR HEAT DETECTION

SPECIFICATION: AlarmLine TM INTELLIGENT LINEAR HEAT DETECTION 1. GENERAL SPECIFICATION 1.1 The contractor shall provide an Intelligent AlarmLine Linear Heat Detection System to perform the following functionality: A. Fire Alarm, Supervisory and Trouble-Event Initiation

More information

Conventional Fire Detection

Conventional Fire Detection SECTI 4: page 1 Section 4: Conventional Fire Detection Contents System Architecture Control Panel Automatic & Manual Detection Manual Call Points Smoke Detectors Heat Detectors Beam Smoke Detectors Duct

More information

Public Safety DAS Annunciator Panel

Public Safety DAS Annunciator Panel Public Safety DAS Annunciator Panel 120 VAC Models: 1221-A, 1221-B, 1221-C Revision D 91117 48 VDC Models: 1221-A-48, 1221-B-48, 1221-C-48 24 VDC Models: 1221A-24, 1221-B-24, 1221-C-24 CAUTION: (Read This

More information

AU MX Digital Loop Card Installation Instructions

AU MX Digital Loop Card Installation Instructions 4100-6077AU MX Digital Loop Card Installation Instructions Cautions and Warnings READ AND SAVE THESE INSTRUCTIONS - Follow the instructions in this installation manual. These instructions must be followed

More information

EXTINGUISHING AGENT RELEASE MODULE

EXTINGUISHING AGENT RELEASE MODULE EXTINGUISHING AGENT RELEASE MODULE Operation, Installation & Programming Manual Revision 3.00 Distributors For: 18-20 Brookhollow Ave telephone 02 8850 2888 www.firesense.com.au Baulkham Hills NSW 2153

More information

MMF Six Zone Interface Module

MMF Six Zone Interface Module Installation and Maintenance Instructions I56-900-005 MMF-0-6 Six Zone Interface Module SPECIFICATIONS Normal Operating Voltage: 5- VDC Stand-By Current: ma Alarm Current: 40 ma (assumes all six LEDs solid

More information

FEC400 Series. Installation Manual

FEC400 Series. Installation Manual FEC400 Series Conventional microprocessor controlled fire detection and alarm panels with extinguishing control Installation Manual Version 2.3 / August 2004 Aritech is a GE Interlogix brand. http://www.geindustrial.com/ge-interlogix/emea

More information

An introduction to... Sigma

An introduction to... Sigma An introduction to... Sigma XT+ Sigma XT+ Overview The Sigma XT+ 21000 series are the latest additions to the Sigma family of control equipment from Kentec Electronics Limited. The Sigma XT+ range combines

More information

CZ-6A Six Zone Interface Module

CZ-6A Six Zone Interface Module INSTALLATION AND MAINTENANCE INSTRUCTIONS CZ-6A Six Zone Interface Module 658 Kitimat Rd. Unit #6 Mississauga, Ontario L5N T5-800-SENSOR, FAX: 905-8-077 www.systemsensor.ca SPECIFICATIONS Normal Operating

More information