DYCU-3 AEROSOL FIRE EXTINGUISHER CONTROL UNIT OPERATION MANUAL

Similar documents
1200-HCM DIN RAIL MOUNTING FIRE SYSTEM MODULE Fire Detection & Extinguishant Control A R T PATOL LIMITED SUPPLY FAULT SOUNDER

Excel-EN Conventional Fire Control Panel

System 800 Addressable Fire Detection & Alarm System

USER MANUAL COMBINED FIRE & EXTINGUISHING CONTROL PANEL COMPLIES WITH BS EN PART 1 & EN54 PARTS 2 & 4

Intelligent Security & Fire Ltd

Installation and user manual for the FX range of fire panels. 1, 2, 4 and 8 zone panels

TECHNICAL DATA SHEET CONVENTIONAL FIRE ALARM SYSTEMS Conventional Fire Alarm Control Panel

PAT E N T System 88. COMPLIES WITH Singapore Standard : SS CP10 : 2005 British Standard : BS EN54-2 : 1998 BS EN54-4 : 1998 REV.00

Application, Installation, Operation & Maintenance Manual

EXTINGUISHING AGENT RELEASE MODULE

Sigma. K1000 Series 1, 2, 4 & 6 Zone Fire Control Panels. Operation and Maintenance Manual. Man-1048 Issue 05 October 2009

Specification/ Data Sheet

USER MANUAL & MAINTENANCE GUIDE OG OO

The EN54 Part 2 and 4 Fire System

Installation and user manual for the CF5000, MF5000 and FXP5000 range of fire panels

PREMIER EX8 INSTALLATION MANUAL COMBINED FIRE & EXTINGUISHING CONTROL PANEL COMPLIES WITH BS EN PART 1 & EN54 PARTS 2 & 4 INSTALLATION MANUAL

General Routing Interface

MINERVA MX. 800 Series Ancillary Equipment

OPERATION AND INSTALLATION MANUAL

FIREBETA EXTINGUISHING CONTROL PANEL (ECP)

FIRE ALARM CONTROL PANEL. COMPLIES WITH EN54 part 2 & part 4 MEETS THE FUNCTIONAL REQUIREMENT OF BS:EN 5839 part 1 INSTALLATION MANUAL

The system is expanded via the RCC network with each RCC capable of passing information to and from up to 31 detection or output devices.

EX8. Instruction Manual: COMBINED FIRE & EXTINGUISHING CONTROL PANEL COMPLIES WITH BS EN PART 1 AND EN54 PARTS 2 & 4

This wiring diagram describes circuit connections for all models of the Series Quaestor-SZU Releasing Fire Control

SYSTEM MANUAL FT1-SB. Single Zone Fire Alarm System

SIMPLICITY CO CARBON MONOXIDE DETECTION & VENTILATION PANEL

BT1 SINGLE ZONE FIRE ALARM SYSTEM OPERATORS MANUAL

MODEL B2 INSTALLATION MANUAL

Model 17A00 Expansion Enclosure

Power Supply / Battery Charger Units, incorporating load switching relays for Smoke Dispersal, Bell Booster or other uses

AL802ULADA. NAC Power Extender. Installation Guide. (See Application Guide for additional information) Rev

AL600ULADA. NAC Power Extender. Installation Guide

GRUNDFOS INSTRUCTIONS LCD 108. Installation and operating instructions

FEC400 Series. Installation Manual

Installation, Operating and Maintenance Manual

ZIOU/230 - MAINS IO INSTRUCTION MANUAL

Conventional Fire Alarm System 2014 V1.2

Matrix2000. User Guide - CPD Advanced Analog Fire Alarm Control Panel 4 24 Zones. Version: 2.0 Revision: 1

Electric Release Panel Wiring Tips

Syncro AS. Analogue Addressable Fire Control Panel. User Manual

SECURIT 700L PLUS ENGINEERING MANUAL

Intelligent Security & Fire Ltd

Installation Guide for AL600ULM. Multi-Output Access Control Power Supply Charger. Rev

ED820-24V MODEL INSTRUCTION MANUAL. fire DETECTOR

FIREPRO INSTALLATION MANUAL FIRE ALARM CONTROL PANEL INSTALLATION MANUAL. Approved Document No. GLT Issue: 1. 8 Author: NRPJ Date: 7/ 3/201 4

Installation Guide for AL300ULM. Multi-Output Access Control Power Supply Charger

User Operation Manual

MO144. Operators Guide. Universal Timer Module

Fire-Cryer. Plus Application Guide APPLICATION GUIDE FIRE EXIT VIMPEX. Shaping Alarm Technology

IT AFEM. Table of Contents. Error! Table not allowed in footnote, endnote, header, footer, comment, or text box.

THE "SS90" SERIES RELEASE DEVICES MODEL B2 INSTALLATION MANUAL

PERTRONIC INDUSTRIES LTD F4-RMAX Installation Note

Installation Guide for AL800UL-ADA. NAC Power Extender. Rev

Technical Manual. Level Alarm Unit CARLA & WIDS

3200 NON-ADDRESSABLE FIRE ALARM CONTROL PANEL

FTEN1, FTEN2, & FTEN4 1, 2 & 4 ZONE FIRE DETECTION AND ALARM CONTROL PANELS

Installation Manual Premier 412/816/832. Issue 10

FIRE ALARM CONTROL EQUIPMENT. Addendum October 2006 Instructions for new style EN54-4 Power supply unit module

AL800ULADA. NAC Power Extender. Installation Guide

FC330A-ECO Auto-addressing analogue 1-Loop fire detection panel

FIREFLY II PLUS RELEASE DEVICES INSTALLATION MANUAL

EC-P Zone Intruder Alarm System

Honeywell Air Sampling Devices Data Sheet

user manual Document No , Revision 03 November 2015

An introduction to... Sigma

ACSI AO ELECTRIC LATCH RETRACTION CONTROLLER INSTALLATION INSTRUCTIONS I.D. 1089, REV. F

MR-2602 Two Zone Fire Alarm Control Panel

Commercial and Light Industrial Fire Alarm Control Panel

Control/Communicator Installation Manual

3500 CONVENTIONAL FIRE ALARM CONTROL PANEL

MADE IN THE U.S.A. ADVANCE FIRE CONTROL MODEL LM21-AFC MANUAL RELEASE DEVICES TEST WEEKLY TO ASSURE PROPER OPERATION OF RELEASE DEVICE/CONTROL PANEL

Release Control Fire Alarm Systems

INFINITY 8 INSTALLATION MANUAL FIRE ALARM CONTROL PANEL INSTALLATION MANUAL

IGD.CO.UK

EVO192 v3.0 Fire and Burglary What s New

Reliably Advanced Extinguishing Control

Intelligent addressable fire alarm control panel

Prem1er EVACS16. Installation Manual VOICE ALARM CONTROL PANEL 4 16 ZONES

ACSI MODEL 1410 POWER SUPPLY INSTALLATION INSTRUCTIONS

ZSC100 Gas Detection and Alarm System Controller

Gasflag. Single Channel Control Panel Alarm Only Apparatus. Installation, operating and maintenance instructions, M07225.

CHECKFIRE 110 DETECTION AND ACTUATION SYSTEM

PNC 1000 SERIES 2, 4, 8 Zone Fire Alarm Control Panel

Why Hart XL Aspirating Smoke Detection?

AL802ULADA. NAC Power Extender. Installation Guide. (See Application Guide for additional information)

SOUNDER CONTROL MODULE SCM-AS4

3500 CONVENTIONAL FIRE ALARM CONTROL PANEL

CommStat 6. Controller for Redundant HVAC Systems PRODUCT DATA SHEET

U ser's Guide PC6010

FC330A-ECO1 Auto-addressing analogue 1-Loop fire detection panel

DAP III Zone Master User s Guide

TECHNICAL DATA OBSOLETE

FIRE DETECTOR TYPE ED816 ZONE 5 ZONE 4 ZONE 6 ZONE 7 FIRE FIRE FIRE FIRE FAULT FAULT FAULT FAULT DISABLED DISABLED DISABLED DISABLED OFF OFF OFF OFF

CONVENTIONAL FIRE ALARM CONTROL UNITS. MR-2300 SERIES Fire Alarm Control Units MEA

Reliably Advanced Extinguishing Control

SALES SUPPORT DOCUMENT

Hydrosense. Vimpex Limited. Star Lane. Great Wakering. Essex SS3 0PJ. Tel: +44 (0) Fax +44 (0)

DUAL MONITORED INPUT/OUTPUT UNIT BN-305-2

Installation Instructions. PS902 Power Supply. These instructions cover the following parts: PS902 Power Supply Specifi cations:

2G & 3G GSM Door Contact Alarm

Transcription:

DYCU-3 AEROSOL FIRE EXTINGUISHER CONTROL UNIT OPERATION MANUAL DOC: GLT.MAN-136 1

INDEX INTRODUCTION 3 CONNECTIONS 4 OPERATION 5 LINKING 6 TECHNICAL INFO 7 DOC: GLT.MAN-136 2

INTRODUCTION The Dynameco Aerosol Generator canister is a low cost fire suppression module, that comes in 3 sizes:- Dynameco 200 protects an area of 2 m 2 Dynameco 300 protects an area of 3 m 2 Dynameco 2000 protects an area of 20 m 2 When triggered the canister generated a fine potassium dust that binds with free radicals produced by the fire, causing the physical chain reaction to stop, thus extinguishing the fire. These canisters are electrically triggered, so need to be connected to a control unit. The DYCU-3 is a low cost unit designed to trigger 3 canisters from a single module, either by the manual operation of a switch (call point or mushroom push button switch), or by the relay output of an automatic fire detector. Examples of automatic fire detector include:- Smoke detector & relay base Flame Detector Aspirating smoke detector Heat detection cable Standard fire alarm panel As the Canister requires a large current to operate (around 1 Amp), the DYCU-3 triggers the 3 canisters sequentially, so that only a 1 amp PSU is required. DOC: GLT.MAN-136 3

CONNECTIONS The DYCU-3 has the following connections:- LABEL 24V IN OUT1 OUT2 OUT3 ALARM 24V OUT CALL REMOTE HOLD DESCRIPTION Connection from 24V PSU to run the unit (With battery back up) Connection to first Dynameco Canister Connection to second Dynameco Canister Connection to third Dynameco Canister 24V output. Energises when unit triggered Connection to power external Detector (100mA max) Manual Triggering input (eg Call point) Automatic triggering input (EG flame detector) Extinguishing Hold Input. Stops all triggering signals to canisters NOTE: The CALL, REMOTE & HOLD signals have 2 connection places. Either connection can be used as these are in parallel. The extra connection is used for linking units together. DOC: GLT.MAN-136 4

OPERATION. The DYCU-3 can be triggered in one of 2 ways:- MANUAL TRIGGERING (CALL CONNECTION) If a normally open connection to the CALL input closes (EG call point pressed), the unit will wait for about half a second to verify the signal. It will then operate it`s INTERNAL BUZZER. It will then operate it`s ALARM output. This can be used to drive a local sounder, or to signal to monitoring equipment. It will then operate Canister OUTPUT 1. (this will operate the Dynameco canister connected to this output). After about 0.5 second, it will turn off this output, and then turn on OUTPUT 2. (to trigger a second canister) After about 0.5 second, it will turn off OUTPUT 2, and then turn on OUTPUT 3. (to trigger a third canister). After another 0.5 second, the unit will turn off OUTPUT 3. It will continue with it`s internal buzzer operating, and its alarm output operating, until the Triggering signal is reset. AUTOMATIC TRIGGERING (REMOTE CONNECTION) For the automatic triggering, there is an option to delay the output signals by 10 seconds. This gives an opportunity to investigate the cause of the alarm and HOLD the system if necessary. This is done by setting jumper 1. With the jumper OFF there will be no delay, and the operation sequence will be exactly the same as for manual triggering With the jumper ON there will be a 10 second delay between the unit operating it`s ALARM, and operating canister output 1. The unit then follows the same sequence. HOLD The unit has a hold input. This is used to inhibit the extinguishing outputs from operating. It stops both Automatic & manual Triggering. DOC: GLT.MAN-136 5

LINKING The DYCU-3 contains dual connections for each of the 3 input signals (CALL, REMOTE, HOLD) These allow units to be daisy-chained together. Either 1, 2, or all 3 signals can be linked. Whatever is more appropriate for type of system being designed. Controller 1 Controller 2 In the above example, the yellow call point would trigger the canisters on both controller 1 & controller 2, but an automatic trigger would only operate canisters on that specific controller. Note that if the HOLD signal is linked, all extinguishing on the linked system will be halted. DOC: GLT.MAN-136 6

TECHNICAL INFORMATION ENCLOSURE OPERATING TEMPERATURE MAX HUMIDITY IP RATING SIZE WEIGHT 0 o C to 50 o C 95% RH Non Condensing IP43 234 x 165 x 80mm 200g ELECTRICAL MODEL DYCU-3 PART NO 83-005 SUPPLY VOLTAGE 24V DC POWER UP CURRENT 1A STANDBY CURRENT 20mA ACTIVE CURRENT 50mA + 1A for Canister (Sequenced) INPUTS MANUAL TRIGGER AUTO- TRIGGER HOLD OUTPUT OUTPUTS 3 X CANISTER TRIG. AUX 24V ALARM 24V INTERNAL BUZZER LED INDICATION (OPTION) INTERLINK MANUAL TRIGGER AUTO- TRIGGER HOLD OUTPUT DOC: GLT.MAN-136 7