Local area fire protection using automatic suppression

Similar documents
Local area fire protection using automatic suppression

Personal Protection Systems (PPS)

New Approaches to Design for Fire Safety - Residential sprinklers, open plan flat layouts and water mist

Standards and third party certification

MistMax Pro; A WaterMist fire skid designed for your UTV or smaller fire fighting vehicle.

How to know if a residential or domestic water mist system is performance compliant to BS 8458:2015?

Application of BS 8489 to the Protection of Generator Enclosures. IWMA, BRE 22 nd March 2017 Dr Tim Nichols CPhys FIFireE

AUTOMATIC FIRE DETECTION AND ALARM SYSTEMS

26 June 2001 *** I:\CIRC\MSC\1007.DOC INTERNATIONAL MARITIME ORGANIZATION 4 ALBERT EMBANKMENT LONDON SE1 7SR

Indicative hoarding fire experiment. Prepared for: London Fire Brigade. 21 May 2014 Client report number

Loss Prevention Standard

GUIDELINES FOR THE APPROVAL OF EQUIVALENT FIXED GAS FIRE-EXTINGUISHING SYSTEMS, AS REFERRED TO IN SOLAS 74, FOR MACHINERY SPACES AND CARGO PUMP-ROOMS

FIRE PROTECTION SYSTEM FOR INDUSTRIAL KITCHENS

FIRE SAFETY AND THE NATIONAL DISABILITY INSURANCE SCHEME

Factors Affecting Efficiency of Water Mist Suppression of Solid Combustible Fires in Open Environment

Loss Prevention Standard

Safer. Smarter. Tyco. I wish I had a flexible FM Approved Water Mist Solution to fit any industrial oil cooker.

DOMESTIC SMOKE ALARMS AND SPRINKLERS. Introduction. Materials and methods. Frank SWANN 1. Legislative impact. Review article

Fire Suppression Systems

Red Book News November 2010

RESOLUTION MSC.265(84) (adopted on 9 May 2008) AMENDMENTS TO THE REVISED GUIDELINES FOR APPROVAL OF SPRINKLER SYSTEMS EQUIVALENT TO THAT REFERRED TO

MistMax Pro; A WaterMist fire skid designed for your UTV or smaller fire fighting vehicle. TM TM

Are we using the wrong design fires for tall building fire strategies, in light of recent full height fires?

Characterising the smoke produced from modern materials and evaluating smoke detectors

Fire and Security Products and Services

Report of fire tests on Li-ion batteries based on condensed aerosol

Fire Suppression. Water-Mist : A Revolutionary Green Technology in. - by Nimit Sheth TALL, SMART, SAFE BUILDINGS FOR SMART CITIES.

BOC FS125 The Fire Extinguishing Solution

Water-mist systems for fire-protection of saunas

The Protection of Machinery Spaces by means of the Local Application of Water Mist. Dr. Tim R. Nichols CPhys FIFireE

Department for Communities and Local Government Research Report:

Fire Protection for Printing Machines with High Pressure Water Mist

Fire Detection and Fire Fighting Testing and Approval on Railway Vehicles

PORTABLE FIRE EXTINGUISHERS. Fire Safety.

Explosion Protection of an Armoured Vehicle Crew Compartment with Water Mist. Andrew Kim and George Crampton

The requirements of BS Watermist Fire System standard and how to demonstrate compliance

fixed dry aerosol fire extinguishing components FirePro Systems Ltd.

K Series - Fire Suppression Systems for the Catering Industry

RIM SEAL SYSTEMS E-BOOK

Fire fighting with fast deployment units. CRISTANINI Spa Via Porton 5, Rivoli Veronese, ITALY

Learning from incidents IFE AGM and Conference 2014 Intelligent Engineering Reducing Risk 25 th and 26 th June 2014 Stratford on Avon

4 June This circular supersedes MSC/Circ.914. *** I:\CIRC\MSC\01\1272.doc

I wish I could protect my business with the most suitable Water Mist solution to fit my needs.

DEALING WITH FIRE SAFETY

Fire Suppression Tests Using a Handheld Water Mist Extinguisher Designed for Spacecraft Applications

CO 2 Fire Extinguishing Systems

Research into multi-sensor detector capabilities and false alarm reduction

The Combustion Process THE FIRE TETRAHEDRON FUEL TEMPERATURE

CAN/ULC-S1001, INTEGRATED SYSTEMS TEST OF FIRE PROTECTION AND LIFE SAFETY SYSTEMS

MAINTENANCE AND INPSECTION OF FIRE PROTECTION SYSTEMS AND APPLIANCES

DSPA DSPA B.V. Product Certificate K86591/07 UK. Non-Pressurized Condensed Aerosol Generators and Components K86591/06 UK

Special solution KS marine. Kitchen protection system KS marine Fire prevention for galleys

REVISED GUIDELINES FOR THE DESIGN AND APPROVAL OF FIXED WATER-BASED FIRE-FIGHTING SYSTEMS FOR RO-RO SPACES AND SPECIAL CATEGORY SPACES

Welcome to Argonite fire protection from Ginge-Kerr

KITCHENShield WCK Kitchen Fire Suppression System. Advanced fire protection systems

Fire safety and the ageing population. René Hagen, professor of Fire Safety Fire Service Academy, Netherlands European Fire Safety Alliance

ODS & SGG Alternatives for the Fire Protection Industry 2018

SPECIFICATION: ECS SERIES CLEAN AGENT FIRE SUPPRESSION SYSTEM

Water Mist-Based Fire Suppression Modelling of an Office Space Scenario

Fire Performance of external thermal insulation for walls of multistorey buildings

HKIE CPD Training Course (II) 23, 25 June and 7, 9 July 2009

This document is a preview generated by EVS

THE IDEAL SOLUTION FOR KITCHENS

International Water Mist Conference, Istanbul October 22-23, 2014 The background and development of the guidelines in IMO Resolution A.

Hazardous Goods Warehouse. VOSSCHEMIE GmbH. Preventive Fire Protection. Case study

Safer.Smarter.Tyco. Watermist fire protection Technology you can trust

Safe, Effective, Environment-friendly

SPECIFICATION: Kidde Engineered Fire Suppression System Designed for use with 3M Novec 1230 Fire Protection

A. NFPA 2001 Standard for Clean Agent Fire Extinguishing Systems 2004 edition.

PROFESSIONAL KITCHEN CLEANING. New Kitchen Ventilation Systems supplied and fitted at competitive rates

Watermist nozzle issues and test methods

ESSEX POLICE, FIRE AND CRIME COMMISSIONER FIRE & RESCUE AUTHORITY Essex County Fire & Rescue Service

FM-200 In-Cabinet Series

Fire suppression systems for server rooms and data centres

STANDARDS FOR ACTIVE FIRE PROTECTION. Stewart Kidd Loss Prevention Consultancy Ltd

Watermist Systems. Versatile, Affordable Water Mist Fire Suppression. your TRUSTED partner in fire safety

Schedule of Accreditation

Ships and marine technology Fireextinguishing. of galley cooking equipment

ISO 6183 INTERNATIONAL STANDARD. Fire protection equipment Carbon dioxide extinguishing systems for use on premises Design and installation

NFPA Marine Fire Protection Codes and Standards An Overview. Guy R. Colonna, P.E. National Fire Protection Association. Quincy, MA USA

Second Revision No. 1-NFPA 17A-2016 [ Section No ] Submitter Information Verification. Committee Statement. 1 of 14 6/22/2016 3:15 PM

Highly Protected Risks in Power Generation Stewart Kidd outlines the issues to consider when installing active fire suppression in power stations THE

SECTION FM-200 FIRE SUPPRESSION SYSTEM

Certificate of Conformity Certificate num. Registration date Version Valid until

Fire Safety in HMOs - Automatic Fire Sprinklers Ian Gough, BAFSA

Proven Fire Fighting Efficiency for Large Transformers with High Pressure Water Mist

Fixed fire protection solutions

Swiftclean and ANSUL. AXA s Commercial Kitchen Fire Safety Service. Ansul is a leading brand of Johnson Controls International PLC

Water Mist v Sprinklers

IMPROVEMENTS OF TEST METHOD FOR WATER MIST SYSTEMS - CEN/TS 14972:2008, ANNEX A.3.

DEPARTMENTAL GUIDELINES CHAPTER 6 TACTICAL OPERATIONS

Loss Prevention Standards

Committee Input No. 9-NFPA [ Global Input ] Supplemental Information. Submitter Information Verification. Committee Statement

LPG ProteK. for commercial kitchens

Can we use knowledge and experience from other sectors to prove Water mist s suitability for land applications? UK Water Mist Seminar 8th March 2016

Based on NFPA 1003: Standard for Airport Fire Fighter Professional Qualifications 2015 Edition

Loss Prevention Standard

LPS 1014 Scheme Requirements for certificated fire detection and alarm system firms. Presented by - Reg Grigg LPCB

Thomasville fire rescue

Real-scale dwelling fire tests with regard to tenability criteria

Transcription:

Local area fire protection using automatic suppression Nigel Firkins Certification Scheme Developer, Fire Suppression Group Fire Research Conference 9 th June 2016 Part of the BRE Trust

Local area protection standards focused on market needs Personal Protection Watermist Systems (LPS 1655) Condensed Aerosol Generators (LPS 1656) Catering Equipment Extinguishing Systems (LPS 1223) Direct local application for small enclosures (LPS XXXX)

Loss Prevention Standards: Help ensure that products meet the needs of users by Setting performance benchmarks Testing both individual component and complete system reliability Review of manufacturers quality systems Design, installation, operation and maintenance Appropriate and repeatable fire test protocols that simulate most onerous extinguishing scenarios Functional requirements such as system monitoring, annunciating and actuation.

Broad stakeholder engagement BRE Global governing body impartiality and conflicts of interest checks BRE Global standing panel Technical oversight Suppression Industry Liaison Group Sector focussed input BAFSA and FIA, Insurers Manufacturers Fire and Rescue Services

Range of applications with common themes Additional to normal fire safety measures Enhanced fire protection -based on risk assessment Dedicated -system specific detection Actuate early in the fire development phase Maximise effect of a limited quantity of agent Localised application

Benefits and challenges Significant reduction in fire damage and therefore risk Ability to be quickly installed and retrofitted Cost effective fire suppression or extinguishment Limited quantity discharged over a limited duration Balance between early and unwanted actuation Need to ensure agent reaches fire in sufficient quantity or concentration

Indicative time/temperature graph

Looking at these four new standards in more detail Personal Protection Watermist Systems (LPS 1655) Condensed Aerosol Generators (LPS 1656) Catering Equipment Extinguishing Systems (LPS 1223) Direct local application for small enclosures (LPS XXXX)

LPS 1655: Typical PPS Installation time: About an hour Resilient power supply: Capable of operating independent of mains power for at least 3 days Detection: Actuate at early stage of fire development Tank: 110 litres of water Active for minimum of 10 mins Flow rate approx. 10 litres/min Protected area approx. 16m² Application rate < 1 litre/m 2 /min

Background to Personal Protection Systems Most fire deaths and injuries occur in people s homes. Vulnerable people most at risk Older people People living alone Mental and/or physical health issues Smokers USA fatal fire data nearly 50% of older people are close to fire when clothing/bedding is ignited LFB fatal fire data 50% of older people were smokers with physical or cognitive impairment. 1/3 in receipt of care package

Discharge area Principle fire risk is within area Defined in installation manual Verified by testing using collection array to define discharge density and pattern Dimension Y Further verification during fire tests

Fuel package Simulate bed or chair Thermocouples Shelf Marine plywood backboard. Timber slats and headboard Polyether foam and polyester/ cotton cover Duvet Pillow Standard ET18 polyether foam Metal frame 12 Polyester duvet & pillow 1000 Polyester/cotton bedding All dimensions in mm.

Fuel package un-suppressed

LPS 1656 (draft): Condensed Aerosol Generators Fast expanding extinguishing aerosol based on potassium compounds Dedicated fire detection system to actuate Manual actuation also possible No persons in area of discharge Compound ignited to release aerosol Initially used as a Halon replacement and also as a lower cost option for risks typically protected by inert gas systems

LPS 1656 (draft): Condensed Aerosol Generators Follows ISO 15779 requirements and methods Fire tests for class B liquid fuel Fire tests for surface burning class A Methods to determine design concentrations Test series for functional reliability Tests to determine service life Tests to determine safe deployment distances

Fire tests to determine class B extinguishing density Defined volume to simulate real world deployment Size of generator determined by design density Heptane cans strategically located to demonstrate extinguishment in all areas

Condensed aerosol generators for room protection Larger generators used for whole room protection Dedicated detection system Normally un-occupied spaces

Fire tests to determine class A extinguishing density Test protocols include: Polymeric fuels Wood cribs Fires are partially shielded Objectives are extinguishment and prevention of re-ignition

LPS 1223: Fixed fire extinguishing systems for catering equipment Designed for protection of catering equipment such as deep fat dryers, other cooking appliances and associated extract systems. A number of high profile fires in fast food outlets, with large impact on business continuity such as: Heathrow T1 60 firefighters over 5 hours to deal with Terminal closed for 10 hours, 45,000 passengers affected M25 services Major site rebuild Many others incidents in retail centers

LPS1223 - Design requirements Protect both the extract system and cooking appliances Automatic and manual actuation Detection of fires in the cooking appliances and within the extract hood Shut-down of the heat source on manual actuation or by detection system. Discharge nozzles shall be protected against ingress of fat deposits. Capable of connection to a fire-bell or other alarm.

LPS1223 Extinguishing Performance Test

LPSxxxx (draft): Direct application extinguishing systems for small enclosures Direct application of low pressure fixed fire extinguishing in small enclosures Automatic and manual actuation Detection by means of heat sensitive pneumatic tube that also delivers extinguishing agent Detect, annunciate and extinguish fire at its source Isolate power to protected enclosure Capable of connection to a fire-bell or other alarm.

Direct local application: Design requirements Protect enclosures up to 2m 2 with up to 10m of pneumatic detection/actuation tube Capability for automatic isolation of power supplies Self monitoring and fault alarm of system pressure. Capability to shut-down extract ventilation Capable of connection to a fire-bell or other alarm.

Fire tests for direct application extinguishing systems for small enclosures Agent extinguishment tests Cabinet perimeter protection Detection tube activation height

Cabinet perimeter tests

Detection height tests for pneumatic nitrogen filled tubing

Lastly all four standards include component testing Primarily tested as a complete system, including detection, actuation and control and indicating arrangements Examination of components and materials Function and operation tests Accelerated ageing using damp/ heat cyclic tests Testing of detection, control and indicating arrangements

Loss Prevention Standards: Help ensure that products meet the needs of users by Setting performance benchmarks Testing both individual component and complete system reliability Review of manufacturers quality systems Design, installation, operation and maintenance Appropriate and repeatable fire test protocols that simulate most onerous extinguishing scenarios Functional requirements such as system monitoring, annunciating and actuation.

Any Questions?

Thank you Nigel Firkins Certification Scheme Developer, Fire Suppression Group T: +44 (0) 1923 664880 E: firkinsn@bre.co.uk W: www.bre.co.uk/fire BRE, Garston, Watford WD25 9XX, UK