CFFWA4P-12-1-U Chilled/Hot Water Universal Mount Fan Coil (4-Pipe) 4-Pipe Heat / Cool Fan Coil 36,000 BTUH

Similar documents
CFFWA4P-16-1-U Chilled/Hot Water Universal Mount Fan Coil (4-Pipe) 4-Pipe Heat / Cool Fan Coil 48,000 BTUH

CFFWA4P-08-1-U Chilled/Hot Water Universal Mount Fan Coil (4-Pipe) 4-Pipe Heat / Cool Fan Coil 24,000 BTUH

MHNCCW (4-Pipe) Chilled/Hot Water Ceiling Concealed 208/230V 4-Pipe Heating & Cooling Fan Coil 12,000 BTUH

MHCFC4W Chilled/Hot Water Cassette Fan Coil

MHCFC4W Chilled/Hot Water Cassette Fan Coil

MHCFC4W Chilled/Hot Water Cassette Fan Coil

MHCCW Chilled Water Ceiling Concealed With 5kW Electric Heat 2-Pipe Heat / Cool Fan Coil 30,000 BTUH

MHCCW Chilled Water Ceiling Concealed Without Electric Heat 2-Pipe Heat / Cool Fan Coil 18,000 BTUH

MH1WC4W-06-1-B Chilled/Hot Water 1-Way Cassette Fan Coil

MHWW-24-H-1 Chilled/Hot Water Hi-Wall Fan Coil 2-Pipe Heat / Cool Fan Coil 24,000 BTUH

MHWW-09-H-1 Chilled/Hot Water Hi-Wall Fan Coil 2-Pipe Heat / Cool Fan Coil 9,000 BTUH

CWA4 Chilled & Hot Water Fan Coil

MHNCCX DX with Hot Water Heat Ceiling Concealed 4-Pipe Heat / Cool Fan Coil 12,000-36,000 BTUH

CWA2 Chilled Water Fan Coil With or Without Electric Heat 2-Pipe Heat / Cool Fan Coil 18,000-60,000 BTUH

MAC-060HE-01-L High Efficiency Air-Cooled Chiller Air-Cooled Chillers for Global Residential and Light Commercial Micro Climates Rev 1.

MAC-120HE-03 Air-Cooled Chiller

MAC-036HE-02-L High Efficiency Air-Cooled Chiller Air-Cooled Chillers for Global Residential and Light Commercial Micro Climates Rev 1.

MAC-048HE-01-L High Efficiency Air-Cooled Chiller Air-Cooled Chillers for Global Residential and Light Commercial Micro Climates Rev 1.

MAC N-407 Air-Cooled Chiller

MACH N-407 Heat Pump Air-Cooled Chiller

Commercial High-Efficiency Condensing Units

FCC Fan-Coil Units High-Performance, Vertical

engineering guide FH Fan-Coil Units Low-Profile, Horizontal

SKYPAK II, 3 Ton Series, gives you a

TECHNICAL GUIDE DESCRIPTION SPLIT-SYSTEM AIR-COOLED CONDENSING UNITS MODELS: HF-07 FEATURES B-0703

FLD = Furnished by Trane U.S. Inc. / Installed by Equipment Submittal Page 3 of 13

Product Specifications. Vertical Floor Consoles By First Co.

catalog CDV Fan-Coil Units High-Performance, Vertical

Commercial High-Efficiency Condensing Units

SKYPAK II, 3 Ton Series, gives you a

Q-TEC QC-Series Chilled Water Air Conditioner

Product Specifications NEW OPTION AVAILABLE: AUTOSPEED 24V CONTROL PACKAGE

High Ambient / High Efficiency Series. R - 410a. 50Hz. Ducted Split Air Conditioners (5.0 kw kw)

TECHNICAL GUIDE DESCRIPTION SPLIT-SYSTEM AIR-COOLED CONDENSING UNITS. HA300, HB360, HB480 & HB thru 50 NOMINAL TONS (50 Hz)

McQuay Suite Type N Top Mounted Hydronic Heat Incremental Packaged Terminal Air Conditioners C:

C13-Series Engineering Guide

TECHNICAL GUIDE LISTED. SPLIT-SYSTEM AIR CONDITIONERS 10 SEER R22 60Hz MODELS: AC036X10(3,4) THRU 060 (3 THRU 5 NOMINAL TONS, 3 PH) DESCRIPTION

SpaceKeeper Console (SKC)

Compact, Self-Contained unit that offer low installation cost plus dependable performance.

100 TON AIR-COOLED SCROLL PACKAGED. Call us today! (800) SPECIFICATIONS GENERAL DIMENSIONS ELECTRICAL DATA ADDITIONAL INFORMATION

Q-Tec TM QC-Series Chilled Water Air Conditioner

TECHNICAL GUIDE LISTED. SPLIT-SYSTEM AIR CONDITIONERS 10 SEER R22 60Hz MODELS: H*BA-(T,W)036 THRU 076 (3 THRU 6.3 NOMINAL TONS, 3 PH) DESCRIPTION

SKYPAK II Heating & Cooling Self Contained Packages

Product Specifications NEW OPTION AVAILABLE: AUTOSPEED 24V CONTROL PACKAGE

PAJ3. Product Specifications

TECHNICAL GUIDE. Description SPLIT-SYSTEM AIR-COOLED CONDENSING UNITS YD360, 480 & THRU 50 NOMINAL TONS YTG-B-0811

Concealed Ducted Split Series R-407C MBH

60 TON AIR-COOLED CHILLER. Call us today! (800) PA-ACCTR-60 GENERAL DIMENSIONS ELECTRICAL DATA 60 TON AIR-COOLED CHILLER FEATURES

CATALOG. SKYPAK Self-Contained Heating/Cooling Units

GUIDE SPECIFICATIONS AQUARIUS ii

Unit Data - RCA 051 RATED IN ACCORDANCE TO AHRI STANDARD

CHS. Product Specifications COMMERCIAL SPLIT SYSTEMS HEAT PUMP UNITS R 410A, 6 10 TONS BUILT TO LAST, EASY TO INSTALL AND SERVICE

VERTICAL FAN COIL UNITS

Rooftop Units 60HZ. PACKAGED HEAT PUMPS 13HPP / rhp13 PRODUCT SPECIFICATIONS 13 HPP 36 A P - 1 A RHP 13 A 36 T - 1 A MODEL NUMBER IDENTIFICATION

MERIT Series R-410A - Upflow / Horizontal

FALCON Rooftop Units ACPSE 50/60Hz Cooling Capacity : 36 to 1388 MBH (11 to 407 kw) Heating Capacity : 40 to 1298 MBH (12 to 380 kw)

TECHNICAL SPECIFICATIONS

VertiCool Aurora Engineering Guide

FF1DNA, FF1DNE FAN COIL UNITS. Sizes 018, 024, 030. Form No. PDS FF1D.18.3 FEATURES FF1D

MERIT SERIES Up Flow / Horizontal

UP to 14.5 SEER, PACKAGE AIR CONDITIONER UNIT, 2 to 5 TONS 208/230 Volt, 1 phase, 60 Hz REFRIGERATION CIRCUIT

GTIP60 ISO GT Series, Inch Pounds - 60 Hz GT (iso) Spec Guide Drawings Spec Sheets Low Temp Heating P/T Charts

ENGINEERING GUIDE. Water-Cooled Self-Contained Units C-Series, Vertical

Advance Product Data. Features/Benefits. 42WKN Hydronic Fan Coil Units

General Description. Operation

Ruud Standard Efficiency Air Handler

Series PIN. New Construction or Renovation. Application Flexible Quiet Comfort Damage Protection

MERIT Series R-410A - Upflow / Horizontal

Incremental Comfort Conditioners

TECHNICAL GUIDE MODELS: H5CE090, H3CE120 & H1CE /2, 10, & 12-1/2 NOMINAL TONS EER DESCRIPTION

Rheem Standard Efficiency Air Handler

AIR HANDLERS AIR HANDLERS

SeasonMaker ThinLine Fan-coil Units

Presents PANTONE COOL GRAY 10 C PANTONE 3155 C

JOB NAME: LOCATION: PURCHASER: ENGINEER: SUBMITTED TO: FOR: REFERENCE [ ] APPROVAL [ ] CONSTRUCTION [ ] SUBMITTED BY: DATE:

Portable Vertical Air-Conditioning and Heating Systems

Call us today! (800)

Ruud Standard Efficiency Air Handler

Call us today! (800)

Call us today! (800)

K*ES120 DESCRIPTION TECHNICAL GUIDE SPLIT-SYSTEM EVAPORATOR BLOWERS 10 NOMINAL TONS EER 8.5 ACCESSORIES FIELD INSTALLED TABLE 1: ARI RATINGS*

HIGH EFFICIENCY AIR HANDLER

technical guide Water-Cooled Self-Contained Units

Technical Guide SUNLINE 2000 DESCRIPTION ACCESSORIES FIELD INSTALLED SPLIT-SYSTEM EVAPORATOR BLOWER K4EU NOMINAL TONS (WORLD 50 HZ)

Rheem Air Handlers. RHML- Series X-13 (ECM) Motor

Presents PANTONE COOL GRAY 10 C PANTONE 3155 C

Ruud Air Handler. RF1T- Series X-13 (ECM) Motor Efficiencies up to 16 SEER. RF1P- Series PSC Motor Efficiencies up to 14.5 SEER

PRODUCT SPECIFICATIONS 2YCC3048A1120A /1/ /

Indoor Air Handlers with Compressors MVS and MVW

Product Data. Features/Benefits. 50TJ S Side Discharge Single-Package Rooftop Units 50/60 Hz 15 to 30 Nominal Tons

SPLIT SYSTEM HEAT PUMP 1½ 5 TON HERITAGE 13 MODELS 2A6H A American Standard Heating & Air Conditioning

WH1T SERIES Constant Torque Motor (ECM) Efficiencies up to 14 SEER. FORM NO. H REV. 1 Supersedes Form No. G Rev. 3

Submittal Data Performance Data Electrical Data

4YCC3048A3096A /3/ /

2YCC3060A1120A /1/ / YCC3060A1096A /1/ /

ICE AIR LLC. Draw1 REV. - PERFORMANCE DATA 117/133 COOLING CAPACITY CORRECTION FACTORS HEATING CAPACITY CORRECTION FACTORS

Rheem Air Handler. RF1T- Series X-13 (ECM) Motor Efficiencies up to 16 SEER. RF1P- Series PSC Motor Efficiencies up to 14.5 SEER

2 shp 13 lc 1 36 t - 1 a

Rheem High Efficiency Air Handler

TECHNICAL GUIDE GENERAL SPECIFICATIONS COMMERCIAL SPLIT-SYSTEM COOLING UNITS FOUR PIPE SYSTEM OUTDOOR UNIT: INDOOR UNIT:

Transcription:

CFFWA4P-12-1-U Chilled/Hot Water Universal Mount Fan Coil (4-Pipe) 4-Pipe Heat / Cool Fan Coil 36,000 BTUH Rev. 1.3

HVAC Guide Specifications Chilled and Hot Water Universal Mount Fan Coil 4-Pipe Nominal Size: 36,000 BTUH Multiaqua Model Number: CFFWA4P-12-1-U Part 1-General 1.01 System Description Multiaqua Chilled Water Fan Coils are manufactured with galvanized steel and high impact molded polymers. 1.02 Quality Assurance A. Certified in accordance with U.L. Standard 95, latest version (U.S.A.) B. Manufactured in a facility registered to ISO 9002, Manufacturing Quality Standard. C. Fully electrically tested at the factory. D. Damage resistant packaging. 1.03 Delivery, Storage and Handling A. Packaged and readied for shipment from the factory. B. Controls shall be capable of withstanding 150 F storage temperatures in the control compartment. C. Stored and handled per manufacturer s recommendations. Part 2-Product 2.01 Equipment A. General: 1. Unit shall be a factory assembled and tested chilled and hot water fan coil. 2. Shall be assembled with high quality. 3. Contained with the unit shall be all factory wiring, piping, associated controls. B. Unit Cabinet: 1. Composed of galvanized steel with baked polyester powder and high impact polymers. 2. Coil Compartment shall be internally insulated to ensure quiet operation. C. Fan Motors: 1. Shall be available in 208/230-1-50/60 VAC. 2. Fan motors shall be three speed, direct drive, and PSC type. 3. Totally enclosed. 4. Internal overload protected. 5. Unit shall contain a swing motor to distribute the discharge air. D. Blower Wheels: 1. Blower wheels are double entry and dynamically balanced. E. Water Coils: 1. Manufactured with water coils containing 3/8 copper tubing mechanically bonded to aluminum fins. 2. Coils shall be factory tested to 350 psig. 3. Maximum inlet water temperature 180 F 4. Primary coil and Secondary coil connections are opposite ends and are non reversible. 5. Pressure independent flow control required on both coils to not exceed max flow for each coil. i. Consult primary coil and secondary coil data for proper sizing F. Drain Pan: 1. All drain pans shall be coated on both the interior and exterior with baked polyester powder to resist corrosion. 2. The exterior of all drain pans shall be insulated with closed cell insulation to prevent condensation. 3. Pans shall contain drain tubing that is accessible from the back, bottom and side of the unit. G. Filters: 1. Unit shall contain washable filters. 2

Part 3-Controls and Safeties 3.01 Controls A. Fan coils shall be completely factory wired and tested. B. Unit shall include a terminal block that is capable of incorporating a field supplied 24 VAC thermostat. C. Controls shall be capable of incorporating a field supplied three speed fan speed switch and or thermostat. 3.02 Safeties: A. Fan coil shall contain a field renewable fuse on the secondary voltage side of the transformer. B. Fan coil shall contain a non renewable thermal protector on the primary voltage side of the transformer. Part 4-Operating Characteristics: 4.01 Electrical Requirements A. Electrical shall include a terminal block for both high voltage and low voltage. B. Electrical power supply shall be rated to withstand 120 F operating ambient temperatures. Part 5- Definitions: 5.01 Abbreviations A. = Cubic Feet per Minute B. DB = Dry Bulb Temperature C. EWT = Entering Water Temperature D. GPM = US Gallons Per Minute E. MBH = BTU X 1000 F. SC = Sensible Cooling G. TC = Total Cooling = Sensible + Latent H. WB = Wet Bulb Temperature I. WPD = Water Pressure Drop in feet of head J. db = Decibel Level K. m = Meter L. In = Inches M. FP I= Fins per Inch N. OD = Outside Diameter O. ID = Inside Diameter P. MCA = Minimum Circuit Amps Q. MOP = Maximum Over current Protection R. LBS = Pounds U.S. 5.02 Measurements A. All measurements with regard to length, width, and height shall be in inches. 3 Rev. 1.2

208/230-1-50/60 CFFWA4P-12-1-U Product Specifications Physical Data Model Number Height (in) Length (in) Depth (in) Weight (lbs.) Primary Coil Rows FPI Water Inlet / Outlet OD (in) Secondary Coil Rows FPI Water Inlet/ Outlet OD (in) Drain Connection ID (in) CFFWA4P-12-1-U 11.3 76.7 28.3 132.3 3-14.750 1/14.750 1 tube All dimensions rounded up to nearest tenth of an inch. All dimensions are as the unit is horizontal/ceiling mounted. Electrical Data Model Number High Speed Volts/ Phase/ Hertz Fan Motor (Qty) Watts Fan Motor Full Load Ampacity Fuse or HACR Circuit Breaker Per Circuit MCA MOP CFFWA4P-12-1-U 1100 (2)177 2.3 2.59 3.0 4

CFFWA4P-12-1-U Chilled Water Performance Data CFFWA4P-12-01-U COOLING CAPACITIES (Primary Coil) EWT GPM ENTERING AIR TEMPERATURE (F) ( F) 80 D.B. / 67 W.B. TC 29634 4.0 SC 23053 WPD 5.2 TC 33507 5.0 SC 24791 1100* 42 WPD 7.8 TC 36503 6.0 SC 26153 WPD 11.0 TC 38832 7.0 SC 27263 WPD 14.6 *High Speed CFFWA4P-12-01-U COOLING CAPACITIES (Primary Coil) EWT GPM ENTERING AIR TEMPERATURE (F) ( F) 80 D.B. / 67 W.B. TC 26675 4.0 SC 21914 WPD 5.1 TC 29878 5.0 SC 23390 1100* 45 WPD 7.8 TC 32575 6.0 SC 24579 WPD 10.9 TC 34620 7.0 SC 25595 WPD 14.6 *High Speed Recommended minimum flow rate for the primary coil at > 2 fps is 3.5 gpm Recommended maximum flow rate for the primary coil at < 6 fps is 9.75 gpm 5

CFFWA4P-12-1-U Hot Water Performance Data This heating performance data is at dry bulb temperature indicated / wet bulb temperature not considered (Primary Coil) 50 1100 4.0 4.8 30813 38575 46377 54212 62073 69954 77850 85757 93672 101590 5.0 7.3 32524 40716 48948 57211 65499 73807 82129 90463 98804 107149 6.0 10.2 33725 42217 50745 59303 67884 76483 85097 93721 102353 110989 7.0 13.6 34611 43321 52065 60836 69630 78440 87264 96097 104938 113784 (Primary Coil) 60 1100 4.0 4.8 23231 30969 38750 46565 54408 62274 70156 78051 85954 93863 5.0 7.3 24498 32667 40877 49121 57391 65683 73992 82313 90643 98978 6.0 10.2 25388 33857 42364 50903 59467 68051 76651 85264 93885 102512 7.0 13.5 26045 34733 43456 52209 60986 69782 78593 87416 96246 105083 (Primary Coil) 70 1100 4.0 4.8 15627 23343 31103 38900 46727 54577 62446 70329 78222 86121 5.0 7.2 16456 24602 32791 41015 49269 57546 65840 74149 82468 90795 6.0 10.2 17038 25483 33970 42490 51038 59607 68194 76795 85405 94023 7.0 13.5 17467 26132 34836 43572 52333 61115 69913 78724 87544 96372 (Primary Coil) 80 1100 4.0 4.8 8003 15698 23439 31219 39031 46867 54723 62595 70478 78369 5.0 7.2 8397 16522 24691 32898 41136 49398 57680 65977 74286 82604 6.0 10.1 8674 17099 25566 34069 42600 51156 59730 68319 76920 85529 7.0 13.5 8879 17523 26208 34927 43673 52441 61227 70027 78838 87657 Heating at ANSI/AHRI 440 with addendum 1, 6.3.2 Table 1 as follows: CFFWA4P-12-01-U HOT WATER CAPACITY (Primary Coil) ENTERING AIR TEMPERATURE GPM ENTERING WATER TEMPERATURE 140F 70F DB / 60F WB 4.0 54913 5.0 57936 6.0 60039 7.0 61579 6

CFFWA4P-12-1-U Chilled Water Performance Data CFFWA4P-12-01-U COOLING CAPACITIES (Secondary Coil) EWT GPM ENTERING AIR TEMPERATURE (F) ( F) 80 D.B. / 67 W.B. TC 13176 4.0 SC 11777 WPD 2.7 TC 15059 5.0 SC 12668 1100* 42 WPD 4.2 TC 16572 6.0 SC 13366 WPD 5.9 TC 17799 7.0 SC 13926 WPD 7.9 *High Speed CFFWA4P-12-01-U COOLING CAPACITIES (Secondary Coil) EWT GPM ENTERING AIR TEMPERATURE (F) ( F) 80 D.B. / 67 W.B. TC 11816 4.0 SC 10901 WPD 2.7 TC 13270 5.0 SC 12009 1100* 45 WPD 4.2 TC 14634 6.0 SC 12642 WPD 5.9 TC 15720 7.0 SC 13141 WPD 7.9 *High Speed Recommended minimum flow rate for the secondary coil at > 2 fps is 3.5 gpm Recommended maximum flow rate for the secondary coil at < 6 fps is 9.75 gpm 7

CFFWA4P-12-1-U Hot Water Performance Data This heating performance data is at dry bulb temperature indicated / wet bulb temperature not considered (Secondary Coil) 50 1100 4.0 2.6 16434 20528 24666 28841 33045 37275 41525 45793 50073 54365 5.0 4.0 17199 21478 25798 30151 34532 38936 43358 47795 52245 56705 6.0 5.6 17760 22174 26624 31105 35612 40139 44684 49242 53812 58390 7.0 7.5 18191 22706 27255 31833 36434 41054 45690 50339 54998 59665 (Secondary Coil) 60 1100 4.0 2.6 12510 16577 20690 24842 29026 33236 37469 41721 45987 50266 5.0 4.0 13076 17329 21625 25957 30318 34704 39110 43533 47969 52417 6.0 5.6 13491 17880 22308 26769 31257 35768 40297 44842 49399 53967 7.0 7.5 13810 18302 22830 27388 31972 36577 41199 45835 50482 55139 (Secondary Coil) 70 1100 4.0 2.6 8574 12614 16703 20833 24997 29189 33405 37641 41894 46160 5.0 3.9 8943 13171 17444 21755 26097 30465 34856 39264 43688 48124 6.0 5.6 9214 13579 17985 22426 26897 31391 35906 40437 44982 49539 7.0 7.5 9423 13891 18399 22939 27506 32095 36703 41327 45963 50609 (Secondary Coil) 80 1100 4.0 2.6 4626 8641 12707 16815 20959 25134 29334 33556 37795 42049 5.0 3.9 4801 9005 13255 17546 21869 26221 30596 34991 39402 43826 6.0 5.6 4930 9271 13656 18078 22531 27010 31510 36028 40562 45107 7.0 7.5 5029 9475 13963 18484 23035 27609 32204 36815 41441 46077 Heating at ANSI/AHRI 440 with addendum 1, 6.3.2 Table 1 as follows: CFFWA4P-12-01-U HOT WATER CAPACITY (Secondary Coil) ENTERING AIR TEMPERATURE GPM ENTERING WATER TEMPERATURE 140F 70F DB / 60F WB 4.0 29276 5.0 30561 6.0 31494 7.0 32203 8

CFFWA4P-12-1-U Chilled Water Performance Data CFFWA4P-12-01-U COOLING CAPACITIES (Both Coils) EWT GPM ENTERING AIR TEMPERATURE (F) ( F) 80 D.B. / 67 W.B. TC 41491 8.0 SC 29357 WPD 6.4 TC 45688 10.0 SC 31189 1100* 42 WPD 9.8 TC 48510 12.0 SC 32461 WPD 13.9 TC 51157 14.0 SC 33730 WPD 18.7 *High Speed CFFWA4P-12-01-U COOLING CAPACITIES (Both Coils) EWT GPM ENTERING AIR TEMPERATURE (F) ( F) 80 D.B. / 67 W.B. TC 36982 8.0 SC 27546 WPD 6.4 TC 40646 10.0 SC 29133 1100* 45 WPD 9.8 TC 43470 12.0 SC 30344 WPD 13.8 TC 45470 14.0 SC 31227 WPD 18.6 *High Speed Pressure independent flow control required on both coils to not exceed max flow for each coil Consult primary coil and secondary coil data for proper sizing Recommended minimum flow rate for both coils piped in parallel at > 2fps is 6.75 gpm Recommended minimum flow rate for both coils piped in parallel at < 6fps is 19.5 gpm 9

CFFWA4P-12-1-U Hot Water Performance Data This heating performance data is at dry bulb temperature indicated / wet bulb temperature not considered (Both Coils) 50 1100 8.0 6.1 38501 48265 58080 67938 77830 87750 97693 107654 117628 127614 10.0 9.3 39604 49626 59692 69794 79926 90082 100257 110448 120650 130863 12.0 13.2 40326 50513 60738 70994 81277 91580 101899 112233 122576 132928 14.0 17.8 40838 51139 61474 71838 82224 92628 103047 113478 123918 134365 (Both Coils) 60 1100 8.0 6.1 28949 38680 48465 58295 68163 78061 87983 97926 107884 117855 10.0 9.3 29764 39756 49795 59873 69984 80120 90278 100453 110641 120841 12.0 13.2 30298 40458 50659 60894 71158 81444 91748 102067 112399 122740 14.0 17.7 30677 40954 51268 61612 71981 82370 92776 103194 113623 124061 (Both Coils) 70 1100 8.0 6.1 19380 29078 38833 48637 58480 68356 78259 88184 98126 108083 10.0 9.3 19911 29874 39886 49941 60029 70146 80287 90446 100620 110807 12.0 13.2 20260 30393 40570 50784 61028 71297 81586 91892 102210 112540 14.0 17.7 20507 30760 41052 51378 61729 72103 82494 92901 103319 113746 (Both Coils) 80 1100 8.0 6.1 9796 19462 29190 38968 48788 58643 68527 78465 88362 98304 10.0 9.3 10048 19982 29969 40001 50069 60167 70290 80434 90595 100769 12.0 13.2 10214 20321 30476 40669 50894 61146 71420 81712 92019 102338 14.0 17.7 10331 20561 30833 41139 51474 61833 72211 82605 93012 103430 Heating at ANSI/AHRI 440 with addendum 1, 6.3.2 Table 1 as follows: CFFWA4P-12-01-U HOT WATER CAPACITY (Both Coils) ENTERING AIR TEMPERATURE GPM ENTERING WATER TEMPERATURE 140F 70F DB / 60F WB 8.0 68960 10.0 70808 12.0 71999 14.0 72834 10

CFFWA4P-12-01-U Data MODEL # Fan Speed CFFWA4P-12-01-U L 925 M 975 H 1100 Wattage @ High Speed 292 11

CFFWA4P-12-01-U Dimensional Drawing 12