Service Requirements SEMI- ANNUAL ANNUALLY OTHER REF. REQUIREMENT

Similar documents
ADDENDUM #1 ITB# Fire Protection Maintenance Services Responses to Clarification Questions 10/06/2015

NFPA CODE TESTING & INSPECTION. Requirements & Recommendations for. Licensed Florida Hospitals, Ambulatory Surgery Centers,

MAINTENANCE AND TESTING OF FIRE SPRINKLER SYSTEMS

2-SUPPRESSION REQUIREMENTS - CODE REQUIRED INSPECTIONS TEST Page 1 of 7

Annual Report of Inspection, Testing & Maintenance of Automatic Sprinkler System

Global Property. SEMIANNUAL FIRE PROTECTION EQUIPMENT INSPECTION REPORT Date of Inspection Location:

False Sense of Security???

Black Diamond Fire Department Building Owner s Responsibilities for Fire Safety Equipment

Winnipeg Fire Department Fire Prevention Branch

FIRE EXTINGUSIHER INSPECTION, MAINTENANCE, AND TESTING PROCEDURES

System Test Report CLEAN AGENT

Southaven Fire Department Fire Marshal s Office 8710 Northwest Drive Southaven, Mississippi Phone: Fax:

MAINTENANCE AND INPSECTION OF FIRE PROTECTION SYSTEMS AND APPLIANCES

Global Property. QUARTERLY FIRE PROTECTION EQUIPMENT INSPECTION REPORT Date of Inspection Location:

Chapter 4: Fire Protection Systems

New Construction Fire Inspection Process

Self Inspection Program

LIFE SAFETY TRAINING Nebraska Health Care Association Chris Moran November 1, 2017

WHEA FSE inspections.

Quick Guide for Fire Sprinkler Inspection Requirements Key Deficiencies with NFPA References NFPA & NFPA 13/

Skilled Healthcare Documentation Requirements Life Safety and Fire Protection

Florida Building Code Chapter 9 Fire Protection Systems Advanced Course

Revised March 2015 Fire Alarm Systems Verification. Schedule I(A) Services. *Manditory Site visit required*

ClassNK Technical Information No. TEC-0970 For any questions about the above, please contact: NIPPON KAIJI KYOKAI (ClassNK) Survey Department, Adminis

Florida Building Code 2010

MAINTENANCE AND SERVICE OF AUTOMATIC FIRE EXTINGUISHING SYSTEMS

FIVE YEAR AUTOMATIC FIRE EXTINGUISHING SYSTEMS CERTIFICATION REPORT

Government of Bermuda Bermuda Shipping and Maritime Authority BERMUDA SHIPPING NOTICE

GUILFORD COUNTY SCHOOLS

Inspection of Fire Sprinkler Systems. NFPA 25, Inspection, Testing & Maintenance of Water Based Fire Protection Systems

FIRE SAFETY SYSTEMS MAINTENANCE INFORMATION

Life Safety Code NFPA 10 NFPA 13 NFPA 25 NFPA 72 NFPA 90A NFPA 110 NFPA 99 THE 2012 EDITION OF THE LIFE SAFETY CODE HOSPITAL EDITION SESSION #7

DISTRICT OF SECHELT. Inspection and Testing of Fire Protection Equipment Bylaw No. 397, 2002

OPTIONAL INFORMATION PORTABLE FIRE EXTINGUISHERS SELF INSPECTION CHECKLIST

Module 3. Water-Based Suppression Systems (WBSS) Part II: Highlights of Code Requirements

USAutomatic Sprinkler Corporation

HIGH-RISE RETROFIT ORDINANCES - NO and NO

Oxnard Fire Department 360 W. Second Street Oxnard, CA (805) Fax (805)

EC 5.10 FIRE PREVENTION MANAGEMENT

OWNER'S SERVICE MANUAL NO INSPECTION, MAINTENANCE AND RECHARGE

THÔNG BÁO KỸ THUẬT TÀU BIỂN TECHNICAL INFORMATION ON SEA-GOING SHIPS

Other EC and LS documents may be requested by surveyors, as needed, throughout the survey.

Subchapter 7. General Industry Safety Orders Group 27. Fire Protection Article 157. Portable Fire Extinguishers. Return to index New query

Montgomery County Government Building and Codes Department 350 Pageant Lane, Suite 309 Clarksville, TN 37040

Fight or Flee? Extinguisher Basics Extinguisher Use Extinguisher Placement and Spacing Hydrostatic Testing OSHA Requirements Test Your Knowledge

Inspection Report Nursing Home Life Safety Code Section 4 - Annual Fire Alarm Testing and Maintenance. For

Checklist For Life Safety

Committee Input No. 9-NFPA [ Global Input ] Supplemental Information. Submitter Information Verification. Committee Statement

Inspection and Testing of Water-Based Systems

SPRINKLER SYSTEM DRY WET

DEPARTMENT OF LICENSING AND REGULATORY AFFAIRS DIRECTOR S OFFICE GENERAL INDUSTRY SAFETY STANDARDS PART 8. PORTABLE FIRE EXTINGUISHERS

FIRE PROTECTION SYSTEMS

EXHIBIT D ATTACHMENT G - UNIT PRICING DMS-14/15-039B - SIMPLEXGRINNELL, LP FIRE SPRINKLER SYSTEM INSPECTIONS YEARS 1-5

PURPLE K POWDER EXTINGUISHERS INSTALLATION, OPERATION, MAINTENANCE AND RECHARGE MANUAL

Iranian Classification Society Convention and Legislation Department Code: Tech Contents

FIRE SAFETY MAINTENANCE INFORMATION for Agricultural Livestock Structures

SECTION WET-PIPE SPRINKLER SYSTEMS EASY RISER CHECK VALVE

BMA INFORMATION BULLETIN No. 97 FIRE FIGHTING EQUIPMENT

SECTION SPRINKLER SYSTEMS

HOW COMMERCIAL FIRE PROTECTION SPRINKLER SYSTEMS REALLY OPERATE

Fire Safety Plan (Single-Stage Fire Alarm System) (Small Establishment):

MINOOKA FIRE PROTECTION DISTRICT Fire Prevention Bureau Fire Inspector Rodney Bradberry Plan Review

Box-in-Box Cold Storage Fire Protection Options

APPENDIX H (DESIGN SUBMISSION CRITERIA)

Understanding, Applying and Enforcing NFPA 25. James D. Lake NFSA Director of Training

9/15/ Cantara Lane Vista, CA (760)

FIRE SAFETY PLAN. BUILDING NAME: Pathobiology / AHL BUILDING NUMBER: 089. DATE: 15-August-10 FPO #2

Attachment 1. to ClassNK Technical Information No.TEC-0764 Malta Maritime Authority Date Revised 28 August 2008 Page 1 of 10 This Administration Requi

Revision May All designs must be submitted to FM Global for review and approval prior to issuing such for bids.

CITY OF MADISON FIRE DEPARTMENT (MFD) FIRE PROTECTION SYSTEM PLANS

Slide 2 NFPA 25: 2017

Government of Bermuda Department of Maritime Administration BERMUDA SHIPPING NOTICE

YORK COUNTY DEPARTMENT OF FIRE SAFETY BUILDING PLAN REVIEW REQUIREMENTS

UNIVERSITY OF MISSOURI Fire Protection System Design 2016 Q1

Sheetz Inc. Fire Protection Service Guidelines

Fire Protection Systems Operation and Maintenance 3 PDH / 3 CE Hours

PORTABLE FIRE EXTINGUISHERS

Attachment 1. to ClassNK Technical Information No. TEC-1077 Isle of Man Ship Registry Manx Shipping Notice SOLAS II-2 The Maintenance and inspection o

MARINE CIRCULAR MC-7/2011/1

CHAPTER 61G15-32 RESPONSIBILITY RULES OF PROFESSIONAL ENGINEERS CONCERNING THE DESIGN OF FIRE PROTECTION SYSTEMS

SPECIFICATION: CARBON DIOXIDE ENGINEERED FIRE SUPPRESSION SYSTEM

AMENDMENTS TO THE BUILDING AND FIRE CODE FOR THE CITY AND COUNTY OF DENVER

Owner/Operator Guide for Successful Sprinkler and Fire Pump Systems

Contren Learning Series Apprenticeship Training Program for Fire Sprinkler Fitters

MINOOKA FIRE PROTECTION DISTRICT Fire Prevention Bureau Fire Inspector Rodney Bradberry

Fire Safety Plan (Single-Stage Fire Alarm System):

Annual Water-Based Fire Protection Systems Inspection

International Fire Code 2006 Requirements for Construction Plan Reviews of Commercial and Multi-Family Structures

SECTION DRY PIPE SPRINKLER SYSTEMS MODEL F SERIES DRY VALVE

FIRE SAFETY PLAN. Building Name. Address. Prepared By. Date Prepared. Page 1 of 36

Fire Sprinkler Plan Submittal Form

Residential Fire Sprinkler Inspection

PLAN REVIEW CHECKLIST

UBC Technical Guidelines Section Edition Fire Protection General Requirements Page 1 of 6

FIRE PROTECTION SYSTEMS

Port of St Helens SIA Aircraft Hanger Scappoose, OR

SANTA ROSA FIRE DEPARTMENT FIRE PREVENTION BUREAU STANDARD

FIRE PROTECTION SYSTEMS

El Reno Fire Department Fire Alarm Plan Review Worksheet

WHEELED STORED PRESSURE

Transcription:

58 Fire protection equipment requires care and maintenance at scheduled intervals to assure it will operate properly and safely when needed. Only personnel who are trained and qualified to maintain the equipment described below should do these services. The following outlines the service requirements of the equipment described in this catalog. These requirements are minimum as contained in the National Fire Codes published by the National Fire Protection Association. Contact one of our sales and service professionals for more information on your specific service needs. EQUIPMENT TYPE MONTHLY QUARTERLY SEMI- LY OTHER REF. REQUIREMENT CHAPTER-1 Clean Agent Systems System System Test Weigh Cylinders Room Integrity Carbon Dioxide Systems System System Test Weigh Cylinders Halon 1301 Systems System Hose Room Integrity NFPA 2001 4-1.1 At least annually, all systems shall be thoroughly inspected and tested for proper operation by competent personnel.discharge tests are not required. 4-1.1 (Same as above). 4-1.3 At least semiannually, the agent quantity and pressure of refillable containers shall be checked. 4-2.1 U.S.Department of Transportation (DOT), Canadian Transport Commission (CTC), or similar design clean agent containers shall not be recharged without retesting if more than 5 years have elapsed since the date of the last test and inspection. 4-3.2.1 All hose shall be tested every 5 years. 4-4 At least every 12 months, the enclosure protected by the clean agent shall be thoroughly inspected to determine if penetrations or other changes have occurred that could adversely affect agent leakage or change volume of hazard or both. NFPA 12 1-11.1 At least every 30 days, an inspection shall be conducted to assess the system s operational condition. 1-11.3.2 The following shall be verified by competent personnel at least annually using available documentation required in 1-7.2.6. 1-11.3.5 At least semiannually, all high-pressure cylinders shall be weighed and 1-9.5.1 the date of the last hydrostatic test noted (see 1-9.5.1). High-pressure cylinders used in fire-extinguishing systems shall not be recharged without a hydrostatic test (and remarking) if more than 5 years have elapsed from the date of the last test.cylinders continuously in service without discharging shall be permitted to be retained in service for a maximum of 12 years from the date of the last hydrostatic test.at the end of 12 years, they shall be discharged and retested before being returned to service. 1-11.2.1 All system hose including those used as flexible connectors shall be tested every 5 years in accordance with 1-11.2. NFPA 12A 4-1.1 At least semiannually, all systems shall be thoroughly inspected, tested, and documented for proper operation by trained competent personnel. Tests shall be in accordance with the appropriate NFPA or Canadian standards. 4-2.1 DOT, CTC,or similar design Halon 1301 cylinders shall not be recharged without a retest if more than five years have elapsed since the date of the last test and inspection. 4-3 All system hoses shall be examined annually for damage. 4-3.2 All hoses shall be tested every 5 years in accordance with 4-3.1. 4-4 At least every 6 months the halon-protected enclosure shall be thoroughly inspected to determine if penetrations or other changes have occurred that could adversely affect halon leakage.

CHAPTER 1 Dry Chemical Systems Agent Examination Agent Replacement Wet Chemical Systems Agent Replacement Fire Alarm & Detection Systems Visual Control Panels Batteries Remote Annunciators Initiating Devices Air Sampling Duct Detectors Electromechanical Releasing Devices Suppression System Switches Manual Pull Stations Heat Detectors Radiant Energy Fire Detectors Smoke Detectors Supervisory Signal Devices Waterflow Devices Alarm Notification Appliances Interface Equipment Digital Alarm Communication Equipment Control Panels Batteries Remote Annunciators Initiating Devices Air Sampling Duct Detectors Electromechanical Releasing Devices Suppression System Switches Manual Pull Stations Heat Detectors Radiant Energy Fire Detectors Smoke Detectors Supervisory Signal Devices Tamper Switches Waterflow Devices Alarm Notification Appliances Interface Equipment Digital Alarm Communication Equipment 59 LY OTHER REF. REQUIREMENT NFPA 17 9-3.1 At least semiannually, maintenance shall be conducted in accordance 9-5a. with the manufacturer s listed installation and maintenance manual. The following parts of dry chemical extinguishing systems shall be 9-5c. years:a.dry Chemical Containers. The following parts of dry chemical extinguishing systems shall be subjected to a hydrostatic pressure test at intervals not exceeding 12 years:c.hose Assemblies. 9-3.1d. 9-5.2 Examination of the dry chemical (if there is evidence of caking, the dry chemical shall be discarded and the system shall be recharged in accordance with the manufacturer s instructions). Dry chemical agent removed from the containers prior to hydrostatic testing shall be discarded. NFPA 17 5-3.1.1 At least semiannually, maintenance shall be conducted in accordance with the manufacturer s listed installation and maintenance manual. 5-5a. The following parts of wet chemical extinguishing systems shall be years:a.wet Chemical Containers. 5-5c. The following parts of wet chemical extinguishing systems shall be years:c.hose Assemblies. 5-5.2 Wet chemical agent removed from the containers prior to hydrostatic testing shall be discarded. NFPA 72 7-3.1 Visual inspection shall be performed in accordance with the schedules in Section 7-3 or more often if required by the authority having jurisdiction.the visual inspection shall be made to ensure that there are no changes that affect equipment performance. 7-3.2 shall be performed in accordance with the schedules in Chapter 7 or more often if required by the authority having jurisdiction.if automatic testing is performed at least weekly by a remotely monitored fire alarm control unit specifically listed for the application, the manual testing frequency shall be permitted to be extended to annual.table 7-3.2 shall apply.

60 CHAPTER-5 CHAPTER-4 CHAPTER-2 Fire Extinguishers 6-year Hydrostatic Test Pressurized Water Wetting Agent(s) AFFF Foam FFFP Foam Carbon Dioxide (CO 2 ) Dry Chemical(s) Halogenated Agent(s) Hose Conductivity Fire Hose Hose Couplings Gaskets & Seals Nozzles Re-rack Hose Hydrostatic Test Fire Department Connections Pressure Reducing and Relief Valves Sprinkler Systems Hose Connections Hose Racks Fire Pump Casing Relief Valves Fire Pump Pressure Relief Valves Sprinkler Systems Gauges - Dry, PreAction & Deluge Gauges - Wet Pipe Systems Alarm Devices Hydraulic Nameplate LY OTHER REF. REQUIREMENT 4-3.1 Fire extinguishers shall be inspected when initially placed in service and thereafter at approximately 30 day intervals. 4-4.1 Fire extinguishers shall be subjected to maintenance at intervals of not more than 1 year, at the time of hydrostatic test, or when specifically indicated by an inspection. 4-4.3 Every 6 years, stored-pressure fire extinguishers that require a 12-year hydrostatic test shall be emptied and subjected to the applicable maintenance procedures. 5-2 Refer to Table 5-2. 12 Years 12 Years 4-4.1.2 A conductivity test shall be conducted annually on all carbon dioxide hose assemblies. NFPA 1962 NFPA 10 2-4.1 The hose shall be service-tested as specified in Section 5-4 within 90 days prior to being placed in service for the first time and at least annually. 4-2.1 Couplings shall be kept in serviceable condition.after each use, and during each hose service test, they shall be visually inspected... 4-3.1 The thread gasket in couplings and nozzles shall be inspected for presence, tight fit, and lack of deterioration.if defective, it shall be replaced with a new gasket. 4-1.2 All nozzles shall be inspected after each use and at least annually. 2-3.3 In-service hose shall be unracked, unreeled, or unrolled and physically inspected as specified in Section 2-5 at least annually.hose shall be reracked, rereeled, or rerolled so that any folds do not occur at the same position on the hose. 2-3.2 In-service hose designed for occupant use only shall be removed and service-tested as specified in Chapter 5 at intervals not exceeding 5 years after installation and every 3 years thereafter. 9-7.1 Fire department connections shall be inspected quarterly. 9-5.1 Sprinkler pressure reducing control valves shall be inspected and tested as described in 9-5.1.1 and 9-5.1.2. 9-5.1.1 All valves shall be inspected quarterly. 9-5.2.1 All valves shall be inspected quarterly. 9-5.3.1 All valves shall be inspected quarterly. 9-5.5.1 All circulation relief valves shall be inspected weekly. 9-5.5.2 All pressure relief valves shall be inspected weekly. 2-2.4.2 Gauges on dry, preaction, and deluge systems shall be inspected weekly to ensure that normal air and water pressures are being maintained. 2-2.4.1 Gauges on wet pipe sprinkler systems shall be inspected monthly to ensure that they are in good condition and that normal water supply pressure is being maintained.. 2-2.6 Alarm devices shall be inspected quarterly to verify that they are free of physical damage. 2-2.7 The hydraulic nameplate, if provided, shall be inspected quarterly to verify that it is attached securely to the sprinkler riser and is legible.

CHAPTER-5 Buildings Hangers/Bracing Pipe & Fittings Sprinkler Heads Spare Sprinkler Heads Valves (All Types) Alarm Devices Main Drain Antifreeze Solution Gauges Sprinkler Heads Sprinkler Heads - Extra High Temp Sprinkler Heads - Fast Response Valves (All Types) Obstruction Investigation 61 LY OTHER REF. REQUIREMENT 2-2.5 Annually, prior to the onset of freezing weather, buildings with wet pipe systems shall be inspected to verify that windows, skylights, doors, ventilators, other openings and closures, blind spaces, unused attics, stair towers, roof houses, and low spaces under buildings do not expose water-filled sprinkler piping to freezing and to verify that adequate heat [minimum 40 F (4.4 C)] is available. 2-2.3 Sprinkler pipe hangers and seismic braces shall be inspected annually from the floor level. 2-2.2 Sprinkler pipe and fittings shall be inspected annually from the floor level. 2-2.1.1 Sprinklers shall be inspected from the floor level annually. 2-2.1.3 The supply of spare sprinklers shall be inspected annually... 2-3.2 Waterflow alarm devices including, but not limited to, mechanical water motor gongs, vane-type waterflow devices, and pressure switches that provide audible or visual signals shall be tested quarterly. 2-3.4 The freezing point of solutions in antifreeze shall be tested annually by measuring the specific gravity with a hydrometer or refractometer and adjusting the solutions if necessary. 2-3.2 Gauges shall be replaced every 5 years or tested every 5 years by comparison with a calibrated gauge.gauges not accurate to within 3 percent of the full scale shall be recalibrated or replaced. 2-3.1.1 Where sprinklers have been in service for 50 years, they shall be replaced or representative samples from one or more sample areas shall be submitted to a recognized testing laboratory acceptable to the authority having jurisdiction for field service testing.test procedures shall be repeated at 10-year intervals. 2-3.1.1 Exception No.3*:Representative samples of solder type sprinklers with a temperature classification of extra high [325 F (163 C)] or greater that are exposed to semicontinuous to continuous maximum allowable ambient temperature conditions shall be tested at 5-year intervals. 2-3.1.1 Exception No.2:Sprinklers manufactured using fast response elements that have been in service for 20 years shall be tested.they shall be retested at 10-year intervals. 10-2.2 Systems shall be examined internally for obstructions where conditions exist that could cause obstructed piping.if the condition has not been corrected or the condition is one that could result in obstruction of piping despite any previous flushing procedures that have been performed, the system shall be examined internally for obstructions every 5 years. Valves Alarm Valves Check Valves Backflow Prevention Assemblies 9-3.3.1 All valves shall be inspected weekly. 9-4.1.1 Alarm valves shall be externally inspected monthly. 9-4.2.1 Valves shall be inspected internally every 5 years to verify that all components operate properly, move freely, and are in good condition. 9-4.3.1.3 The interior of the preaction or deluge valve and the condition of detection devices shall be inspected annually when the trip test is conducted. 9-4.4.1.4 The interior of the dry pipe valve shall be inspected annually when the trip test is conducted. 9-6.1.2 All backflow preventers installed in fire protection system piping shall be tested annually...

62 CHAPTER-8 CHAPTER-7 CHAPTER-6 CHAPTER-5 Valves Main Drain Waterflow Alarm Backflow Prevention Assemblies Home Safety Equipment Single Station Smoke Detectors Battery Replacement Emergency Lighting Annual Test Exit Signs/Lighting Visual Annual Test LY OTHER REF. REQUIREMENT 9-2.6 A main drain test shall be conducted quarterly at each waterbased fire protection system riser to determine whether there has been a change in the condition of the water supply piping and control valves. 9-2.7 All waterflow alarms shall be tested quarterly in accordance with the manufacturer s instructions. 9-3.4.1 Each control valve shall be operated annually through its full range and returned to its normal position. 9-4.3.2.2 Each deluge or preaction valve shall be trip tested annually at full flow in warm weather and in accordance with the manufacturer s instructions. 9-4.4.2.1 Each dry pipe valve shall be trip tested annually during warm weather. 9-6.2.1 All backflow preventers installed in fire protection system piping shall be tested annually... 9-3.5 The operating stems of outside screw and yoke valves shall be lubricated annually. 9-4.3.3.2 During the annual trip test, the interior of the preaction or deluge valve shall be cleaned thoroughly and the parts replaced or repaired as necessary. 9-4.4.3.2 During the annual trip test, the interior of the dry pipe valve shall be cleaned thoroughly and parts replaced or repaired as necessary. NFPA 72 2-6.2.1 Test single station detector monthly. Replace battery annually. NFPA 101 7-9.3 A functional test shall be conducted on every required emergency lighting system at 30-day intervals for not less than 30 seconds. 7-9.3 An annual test shall be conducted on every required batterypowered emergency lighting system for not less than 1 1 /2 hours. Equipment shall be fully operational for the duration of the test. NFPA 101 7-10.9.1 Exit signs shall be visually inspected for operation of the illumination sources at intervals not to exceed 30 days. 7-10.9.2 Exit signs connected to or provided with a battery-operated emergency illumination source, where required in 7.10.4, shall be tested and maintained in accordance with 7.9.3. National Fire Code Standards Referenced: NFPA 2001 - Clean Agent Fire Extinguishing Systems NFPA 12 - Carbon Dioxide Extinguishing Systems NFPA 12A - Halon 1301 Fire Extinguishing Systems NFPA 17 - Dry Chemical Extinguishing Systems NFPA 17A - Wet Chemical Extinguishing Systems NFPA 72 - National Fire Alarm Code NFPA 10 - Portable Fire Extinguishers NFPA 1962 - Care, Use and Service of Fire Hose including Connections and Nozzles - Water-Based Fire Protection Systems NFPA 101 - Safety to Life from Fire in Building and Structures Reprinted with permission. Copyright 2000, National Fire Protection Association, Quincy, MA 02269. This reprinted material is not the complete and official position of the National Fire Protection Association on the referenced subject which is represented only by the standard in its entirety.