Data sheet Danfoss gas detection Controller unit The gas detection Controller Unit is used for a centralized monitoring and warning of hazardous gas concentrations. The input signals for the controller are collected from the local gas detection units of the types Basic, Premium and Heavy Duty via S85 Fieldbus or Analog communication. In total 96 gas detection sensors can be handled via Fieldbus + via Analog directly on the controller (+8 additional possible if expansion modules added). The Controller Unit comes with alarm relays available for external looped alarm devices. Additional relays and sensor wiring loops is possible by adding Expansion modules to the controller. Each local gas detection unit is assigned a unique address in the Controller and by continuous communication with the individual GDU s the Controller reacts on alarm signals from the local GDU. The parameter setting and the actual state of each local GDU can be read in the Controller display. Features For connection of up to 96 sensors via fieldbus + via Analog (when 7 expansion modules added) Easy configuration via intuitive user-interface; helps simplify operator handling and minimize risk of operational setting errors Simple commissioning by standard parameter configuration Flexible connection to local gas detection units by either Analog or S85 fieldbus communications Fieldbus wiring: Wire length up to 900 meters (95 ft.) per segment. relays for external alarm device circuits Up to 7 Expansion modules possible; allows additional 7 segments with a total of 700 meters (6 ft.) wiring and a total of relays for alarm device circuits. Automatic self-diagnostics to ensure correct communication and operation for communication error 6 menu languages Password protected settings allowing authorized access only Service alerts on display Conformity to EN 5055- Enables regulatory compliance with EN 78:06, ISO 59:0, AI758805en-0000 DKCI.PD.S00.G.0
Contents Page Features... Specifications... Electrical connection... Fieldbus loop...5 Ordering...6 AI758805en-0000 DKCI.PD.S00.G.0
Specifications Electrical Power supply V DC ± 0 % Power consumption ( V DC) W, 50 ma Analog input () to 0 ma, overload and short-circuit- protected, input resistance 00 Ω Tension for external analog transmitter V DC (same as power supply), max. 00 ma / per sensor Analog output () configurable for each input Proportional, overload and short-circuit- protected, charge 500 Ω - 0 ma = measuring range.0 < ma = underrange >0. ma = overrange.0 ma = fault Alarm relay () 50 V AC, 5 A, potential-free, change-over (SPDT) Fault relay () 50 V AC, 5 A, potential-free, normally open contact (SPST) Visualization LCD Status LED () Operation Menu language (selectable) Interface fieldbus Transceiver Gases Digital and analog sensors for toxic, combustible & refrigerant gases Environmental Humidity Working temperature Storage temperature Two lines, 6 characters each, illuminated Operation fault st alarm nd alarm 6 push-buttons German, English, Dutch, USA, French, Swedish S 85 / 900 Baud 5 95 % H non-condensing -5 C to +0 C ( F to 0 F) 0 C to +0 C ( F to 0 F) Physical Enclosure Plastic housing ABS Colour AL 705 Protection class IP 0 Weight 0. kg (0.8 lb.) Packaging volumes Ca.. l Mounting Top DIN rail mounting, installation in distribution box Dimensions (Controller unit) (W x H x D) 06 x 0 x 6 mm (. x. x. in.) Dimensions (Controller Solution) (W x H x D) 98 x 0 x 0 mm (.7 x 6.5 x 5.5 in.) Wire connection: Power supply... Output... Screw type terminal:.5 mm ( AWG) x spring type terminal: min. 0.5 mm, max..5 mm ( to 6 AWG) Input... Spring type: min. 0.5 mm, max..5 mm ( to 6 AWG) Guidelines EMC Directive 0/0/EU Low voltage directive 0/5/EU CE EN 5055-, EN 507 Interface ModBus TU S 85 Function Transmission of current and average values, alarm and relay status, and analog output states in MODBus TU S 85 protocol to external devices AI758805en-0000 DKCI.PD.S00.G.0
Electrical connection Fault A 06 A 0 A 0 A 0 X 5 X_Bus X_Bus X 5 6 X 7 8 9 0 5 D D D D D F Digital output Controller unit Danfoss 8H_0-08 Power/ Main Bus X0 + - Main Bus_A A Main Bus_B B X < Power Field Bus Analog input < X Field Bus_A A Field Bus_B B AI_0 AI_0 AI_0 AI_0 Analog output AO_0 AO_0 DI_0 Digital input DI_0 DI_0 DI_0 5 6 7 8 9 0 Main Bus_A A Main Bus_B B A J5 port available on the controller. Field Bus_A A Field Bus_B B B -0 ma -0 ma -0 ma -0 ma AP 0 AP 0 AP 0 AP 0 AI758805en-0000 DKCI.PD.S00.G.0
Fieldbus loop Each GD controller can handle up to 96 sensors and handle any mix of individual Gas detection units of the types Basic, Premium and Heavy Duty. The max. recommended loop wire length is 900 meter (95 ft) per segment. With additional segments (and additional controller expansion modules) the max recommended loop wire length is 700 meter (6 ft). The controller and the last GDU in each segment must be provided with a resistor of 560 Ohm. A Umin of 6 V DC must be secured at any spot in the loop. Below figure shows how to make proper connections between the controller and each GDU. Controller Unit unit 560 GDU Addr. 05 GDU Addr. 0 Danfoss 8H9_0-08 0 V DC V DC BUS_B BUS_A 0 V DC V DC GDU Addr. 0 GDU Addr. 0 GDU Addr. 0 U min = 6 V DC Wire length max. 900 meter (95 ft) per segment. Wire length max. 900 meter (95 ft) per segment. More More segments segments with with additional additional expansion expansion modules modules max. 700 max. meter 700 (6 meter (6 ft). ft). Additional power power limitations limitations must must be calculated. be calculated. IGHT Controller unit = Terminating resistor 560 560 Ohm Ohm = GDU (Basic, Premium and/or and/or Heavy Heavy Duty) Duty) Controller unit WONG Danfoss 8H_0-08 AI758805en-0000 DKCI.PD.S00.G.0 5
Ordering Description Code number Controller unit Controller solution (controller + enclosure) Controller solution Uptime Warning module (wire break monitoring module) Controller expansion module Gateway for controller 8H6 8H6 8H67 8H6 8H6 8H68 Controller solution Controller unit placed in an enclosure ready to be connected to a power source. A separate UPS for the controller is available. Gateway for controller The gateway is an addition to the controller and used for communicating via Modbus TCP/IP. Warning module (wire break monitoring module) The warning module is used for monitoring the circuiting to the warning/alarm devices on a centrally controlled gas detection system. Wire breaks or wire interruptions in the alarm device loop will be reported to the central control. Controller expansion module The gas detection Controller Expansion module is used for expansion of the cable coverage in terms of number of loops and the total wire length. Each Controller Unit can handle up to 7 Expansion modules allowing additional 7 segments with a total of 700 meters (6 ft.) wiring and a total of relays for alarm device circuits. AI758805en-0000 DKCI.PD.S00.G.0 6