7XG3130 ReyArc30 Optical Arc Fault Sensor Energy Management

Similar documents
7XG3120 ReyArc20 Arc Fault Monitor Relay Energy Management

1S20 User Guide. Arc Fault Monitor. Advanced Protection Devices. relay monitoring systems pty ltd. User Guide. Test Manual

1S26 User Guide. Arc Fault Monitor + Integrated Current Check Relay. Advanced Protection Devices. relay monitoring systems pty ltd.

1S25. Arc Fault Monitor 4 Zones, 8 Sensors. Features. Introduction. ARC Fault Protection

7PG17 - XR Intertripping, Interposing, Supervision and Special Purpose Relays. Answers for Infrastructure & Cities.

Reyrolle Protection Devices. 7PG26 DAD High Impedance Current Relay. Answers for energy

l High precision, computer-designed parabolic optical system,. Dual element pyro-electric sensor.

Arc Fault Protection System D1000

D1000 Arc-fault Protection System

INSTRUCTION MANUAL (ATEX/IECEx/SIL2) BExBG05D-SIL Flameproof Xenon SIL 2 Beacons For use in Flammable Gas and Dust Atmospheres

MINERVA S200Plus. Fire Detection. Triple Waveband Infra-Red Flame Detection. Features: Minerva S200PLUS

S200Plus Triple Infra Red Flame Detector Triple Waveband Infra-Red Flame Detection

Multi-Spectral, Digital, Infrared Electro-Optical. FSC Model No. s. Unitized, Two Stage, Quick Response Flame Detectors.

APPLICATION NOTE. Applying pressure sensing in arc flash protection applications with air magnetic circuit breakers

COMPACT FLAME CONTROLLER CFC 1000

ADPRO PRO Series by Xtralis

Elite. GJD022 /GJD023 35m External PIR. Multi Beam Lens Data

Installation Instructions Azatrax Dual Infrared Model Train Detector MRD2 'Turnout' Edition

Interface and EOL Modules 8

Index Arc Guard Systems. Arc Guard Systems. Arc Guard Systems Industrial Automation Supply - Tel:

Class 1 laser beam sensor safe for your eyes

Sensing light curtain as per DIN 18650/EN 16005

Sitron s CF Line of Flow Switch Monitors

COMPACT FLAME CONTROLLER CFC 2000

D-TECT Introduction. Connecting the Unit. Quick Installation. Multi Beam Alignment & Masking. Mounting the Unit

EFBW series - BiWire Ultra control panel

Sensing light curtain as per DIN 18650/EN 16005

Movement Detector GJD 300

Retroreflective sensor with polarization filter

Class 1 laser beam sensor safe for your eyes

MPAD-C 12-24V. Ceiling microwave presence/absence detector 12-24V AC/DC. Product Guide. Overview. Features

Mounting bezel Retaining spring. Detects movement within the detection range, allowing load control in response to changes in room occupancy.

PGR-8800 TECHNICAL FAQ

Dräger Flame 2100 Flame Detection

Intelligent addressable fire alarm control panel

M2500 Engine Controller Installation Manual

Signaling Devices. Acoustic Signaling Devices 298. Optical Signaling Devices 309. Bosch Security Systems B.V.

Flame Safeguards LFE10. Building Technologies HVAC Products

Sita200plus. 200detectors. Single loop analogue addressable System

D-Tect 2 GJD300 Quad PIR Movement Detector

ACC-25/50ZST. Zoned System Voice with Telephone Evacuation Control Panel

i-con Switchgear Condition Monitoring HV Switchgear Integrated Substation Condition Monitoring ISCM Answers for Infrastructure & Cities.

Ceiling PIR HS presence detector. Product Guide. Overview. Features

LAE10 LFE10. Use. Series 02

DF1151-Ex Infrared flame detector

WLS-T25 Solar Powered Low Intensity Duty & Stand-by Aviation Obstruction Light

Class 1 laser beam sensor safe for your eyes

COMPACT FLAME CONTROLLER CFC 200 (Formerly 8.XX)

DF1101-Ex Infrared flame detector

Active Infrared Multi Beam Sensors

RC801/803/ B 16E1 Fiber-Optic Multiplexer (Rev. M) User Manual. Raisecom Technology Co., Ltd. (04/2005)

General Routing Interface

SEL Arc-Flash Solutions

Optical Smoke Detector Heat Detector Manual Call Point Output Unit Isolator

VAMP 121. Arc protection unit. User manual

Devices for Special Applications

Twin Photobeam Detectors Manual

Advantages / Characteristics

1S25 User Guide. Arc Fault Monitor. Advanced Protection Devices. relay monitoring systems pty ltd. User Guide

VAMP 120 & 121. Arc flash detection units. Product picture

Ceiling Microwave presence/absence detector 12-24V AC/DC

Conventional Fire Detection

Long-Range Barrier Sensors

Maxim3 TM Series IP66. LED Vapor Tight - Waterproof Key Features

Model 3300 Technical Support and Installation Manual

Basic Vehicle Fire Protection Manual

Sensors and Detectors

SENSOR SOLUTIONS FOR DOORS

17 TH APRIL 2017 Switch Board Monitoring Protecting Switchboard. Courtesy of ABB. Paul Lee

Water Leak Detector - Four Zone with open/short-circuit detection. Product overview

NO (SPST-NO) 10 A Internal installations Particularly suited for wall mounting

Flame Safeguards LFE10. Building Technologies HVAC Products

MODEL FPT-130 SINGLE POINT FREEZE PROTECTION HEAT TRACE CONTROL

MWS3A-PRM. Ceiling microwave presence/absence detector. Product Guide. Overview. Features

Requirements of EN 1838: illuminance of 5 lx for safety equipment

UV Flame Supervision System

GS100-ATEX. Hazardous Areas Infra-Red Beam PULSE MODULATED ACTIVE INFRA-RED BEAM FOR HAZARDOUS AREAS ZONE 1 OR ZONE 2 GENERAL

Conventional Smoke Detectors KFAPO

LPCMPIRM65 & LPCMPIRDSI65

LFE50. UV Flame Safeguard. Building Technologies Division DETACTOGYR

2 General Application Photoelectric Sensors

Bravo II. High Performance Multi-Purpose Speaker

AQ 100 Series. Arc Flash Protection System

Leuze electronic. Dimensioned drawing. Electrical connection. Accessories: 150m ISO 9001

SEL Arc-Flash Solutions

Active Infrared Multi Beam Sensors. R Series

MWS6-PRM. Ceiling microwave presence/absence detector. Product Guide. Overview. Features

Dräger Flame 2500 Flame Detection

Ceiling Microwave presence detector - DALI / DSI 12-24V AC/DC. Microwave Sensor. IR Receiver. Light Level Sensor. Status LEDs.

HOA1888 Series. Infrared Assemblies Wide Gap Transmissive Sensor. MICRO SWITCH Sensing and Control

XUX0AKSAM12 photo-electric sensor - XUX - multi - Sn 0..40m VDC - M12

II SL. Installation Guide. VOLTEX IMS64-2 Dual output indoor flush mount PIR motion detector IMS64-2

Integrated PIR detectors

Danfoss gas detection units

Extreme High-Intensity Sensors Thru-Beam and Fiberoptic Penetrates Many Packaging Materials for Content Verification

Model 5610 Infra-red Transit Heat Sensor

Instruction manual for the Infrared Point Type Flame Detector

culus and CE Marked for all applicable directives Operating Environment Operating Temperature [C (F)]

Pipe Freeze Protection Control SCFP-CO-F130 Installation and Operation Manual

FAAST. Fire Alarm Aspirating Sensing Technology

Transcription:

Reyrolle Protection Devices 7XG3130 ReyArc30 Optical Arc Fault Sensor Energy Management

7XG3130 - RA30 Optical Arc Fault Sensor Features Compact rugged design One or two optical detectors High speed arc detection Heavy duty 6m termination cable Optional 20m & screened cables Simple flush cable panel mounting outside or inside switchgear compartment Integrated sensor circuit supervision Very low sensitivity to ambient light levels to avoid nuisance tripping even in direct sunlight Sealed module for harsh environments Metal reinforced mounting shield comes as standard Description The RA30(ReyArc30) is an optical sensor that responds to the flash of light emitted during the incidence of an arcing fault. Onset of the light flash & detection by the RA30 occurs in a few ms. Each arc fault sensor consists of one or two silicon PIN photo diode light detectors mounted on a circuit board together with the associated detection circuit (Figures 1 & 2). The detector monitors a wide space angle. A broad spectral response in the visible region is provided as depicted in figure 5. Sensitivity of the arc sensor has been set to a low level to reduce the possibility of mal operation under high ambient lighting conditions. This is made possible due the high intensity of light emitted under arc fault conditions. Additional security can be incorporated by way of a current check stage. In standby mode the RA30 sensor presents a high resistance to the 12V DC control signal provided by the Arc Fault Monitor. This allows a small circulating current to flow for continuous supervision of the RA30 connection circuit. When an arc is detected, the resistance presented by the RA30 drops to a level where the current flow increases to approximately 20mA. This increased current flow is instantaneously detected by the Arc Fault Monitor & its trip output contacts closed. Refer to the RA20 Arc Fault Monitor Catalogue sheet for further details. Single detector package Figure 1 depicts the RA30 with a single optical detector. Note the window where the active part of the detector is positioned to. This permits convenient mounting on the outside of the panel with the detector window protruding through a hole in the panel. Application Arc fault protection is a technique employed for the fast clearance of arcing faults on busbars & within metal clad switchgear & associated cable boxes. The arc is detected using an optical sensor & the signal input to a protection device which also monitors the load current on the system. A trip signal can be achieved in less than 10ms using arc detection. While the high intensity flash caused by an electrical arc will be reflected within the metal clad switchgear, it is recommended that one or more sensors be mounted in each enclosed switchgear compartment. For busbar protection applications multiple sensors are required to achieve adequate coverage along the length of the bar. A sensor version with two optical detectors looking in opposite directions is available for this purpose (Refer figure 3 for generic layout). Figure 1: Siemens Protection Devices Limited 2

Dual detector package Figure 2 depicts the RA30 with dual optical detectors. The two optical detectors face in opposite directions to provide arc detection coverage in both directions. This version is particularly useful when mounted in a bus chamber or barrier between adjacent switchgear chambers. The main benefits are reduced cost compared to two separate sensors & use of only one input channel on the RA20 Arc Fault Monitor. Detector Characteristics Optical sensitivity ~10,000 Lux* for white light at normal incidence to the detector window(s) as depicted in figure 4: Light Source Rear Detector RA30 [B] Dual detectors models only Front Detector RA30 [A] Light Source Figure 2: Detector range A detection range along the 100% relative sensitivity curve shown in figure 3 is approximately 3m. Single detector versions therefore need to be placed at a maximum spacing of 5-6m. The dual detector versions may be placed at a maximum spacing of 8-10m to provide adequate detection overlap. In switchgear the light caused by the arc is reflected from the walls & therefore, the mounting of the sensor is not critical. While the high intensity flash caused by an electrical arc will be reflected within the metal clad switchgear, it is recommended that one or more sensors be mounted in each enclosed switchgear compartment. Figure 4: For the RA30 single detector version the front detector only is fitted. In this configuration the RA30 will be insensitive to white light incident on the rear surface of the case up to a level of 200,000 Lux. As the illuminace of diffuse ambient sunlight falls in the range 5,000 to 10,000 Lux, this will not normally be sufficient to trigger the RA30 sensor. The luminous intensity from the sun at noon at the equator however is ~100,000 Lux which will be sufficient to trigger the RA30 sensor so measures should be made to avoid this situation. Direct sunlight incident on the rear of the RA30 single sensor model will not cause it to pick up. This attribute provides a significant safety margin to avoid nuisance tripping when the option of mounting the sensor externally on switchgear as depicted in figure 6 is employed. Detector directional characteristics Detector sensitivity falls to ~40% of the nominal level at inclination angles up to 70 degrees from the normal for white light. Detector spectral response 100% Figure 3: Relative Sensitivity 90% 80% 70% 60% 50% 600 700 800 900 1,000 1,100 1,200 Wavelength (nm) Figure 5: Arc detector spectral response * Due to the relatively high sensitivity of the detector to IR wavelengths the type of light source employed for sensitivity testing will have a major effect on the results obtained. Sensitivity testing should therefore be conducted using a 50-75W halogen lamp with an integrated aluminum reflector. Siemens Protection Devices Limited 3

Mounting Options Flush panel mounting The RA30 is suitable for flush panel mounting in a number of configurations. Flush mount reinforcing plate 2 x M4 self threading mounting screws (Supplied) Dual detector version The dual detector version can be panel mounted to monitor two adjacent switchgear compartments simultaneously. This feature can be used to reduce the total cost for sensors or to increase the monitoring coverage for each RA20 Arc Fault Monitor unit. protruding through compartment divider into adjacent switchgear chamber window facing away from compartment divider Internal partition between switchgear compartments Figure 6: RA30 shown mounted on the outside of a switchgear panel Detector oriented to look through a hole into the switchgear protruding through hole in panel 2 x M4 self threading mounting screws (Supplied) Figure 9: RA30 shown mounted on the inside of a switchgear panel. This configuration combines the functions described in Figures 6 & 7 with the application of a single dual detector arc fault sensor Switchgear panel Sealed cable stress relief Figure 7: RA30 shown mounted on the inside of a switchgear panel Detector oriented to look out into the switchgear compartment Flush mounting reinforcing plate When mounting the RA30 on the outside of a switchgear cubicle as depicted in figure 6, the hole required in the panel may degrade the short circuit rating. If this is considered to be an issue then a reinforcing plate may be fitted over the RA30 as depicted below. The Reinforcing plate comes as standard with the RA30. facing away from panel 2 x M4 self threading mounting screws (Supplied) Figure 8: Flush mount reinforcing plate 1.2mm zinc plated mild steel Siemens Protection Devices Limited 4

Panel mount cut out detail Hole in panel to allow detector to look into switchgear chamber Figure 10: Flush mounting detail Right angle mounting off a surface A right angle mounting bracket may be fabricated using the panel cut out detail in figure 10. Single & dual detector models may be mounted in this manner as depicted below. Single optical detector Dual optical detector window facing away from right angle mounting bracket CRO trace showing nominal operation time of the trip contacts at 7ms. First contact touch at 6.25ms and fully closed by 7.25ms. Operation in <10ms is considered acceptable as current check relay operate time is ~25ms. Minimum Arc duration The minimum arc flash duration required to guarantee operation of the Arc Fault Monitors output contacts is 1.25ms. Auxiliary supply Voltage from RA20 Arc Fault Monitor: Power consumption: Casing Rugged moulded construction to IP51. 12V DC <2.5mA Right angle mounting bracket Temperature range Operating: Storage: Sensor Connections -5 to +55 o C -25 to +75 o C Figure 11: Right angle mounting off a surface mount off floor or walls within switchgear / busbar chamber Technical Data Arc fault protection scheme Refer to the ReyArc20/23/24 Technical Catelogue sheets for further details. Arc protection scheme operate time Arc fault trip contacts guaranteed to pick up in less than 10ms including bounce. Typical operate time is 7ms. The RA30 is supplied with a 6m two core connection cable as standard. Two core multi strand wire (2x16/0.2mm), is supplied stripped & pre tinned at the RA20 connection end. The standard 6m cable may be cut down to the desired length & crimp ring lugs fitted for termination. The RA30 connections are not polarity sensitive. Reversal of the wires on the arc monitor terminals has no effect on the performance of the RA30 or arc detection system. The cable is factory fitted to the RA30 Arc Fault Sensor using a stress relief molding to provide a sealed & durable connection interface. The cable employs thick inner & outer insulation layers to avoid damage during installation. For connection over longer distances shielded cable is recommended. For distances over 20m, 24/0.2 mm cable should be employed. Additional RA30 cable length Screened arc sensor cables may be increased by wiring additional series twisted pair SCREENED cable provided it does not exceed 5 ohms and 30nF loop impedance. Siemens Protection Devices Limited 5

Dimensions Order Code Serial No. Optional second optical detector looks forward through front label window Figure 16: RA30 Arc fault Sensor dimensions Siemens Protection Devices Limited 6

Ordering Information Product description Variants Order No. 7 X G 3 1 3 0-0 0-0 A A 0 Reyarc Arc Fault Protection Category Components Arc Protection 3 1 Device RA30 Arc Sensor 3 0 Arc Detectors Single detector (Through Hole) 1 Dual detector 2 B Cabling 6m unshielded A 6m shielded B 20m shielded C Reinforcing plate (single sensors only) Required A Not Required B Siemens Protection Devices Limited 7

Published by and copyright 2016: Siemens Protection Devices Limited P.O. Box 8 North Farm Road Hebburn Tyne & Wear NE31 1TZ United Kingdom Phone: +44 (0)191 401 7901 Fax: +44 (0)191 401 5575 E-mail: marketing.spdl.gb@siemens.com EMEA-C10068-00-76GB March 2016 For enquires please contact our Customer Support Center Phone: +49 180/524 8437 (24hrs) Fax: +49 180/524 24 71 E-mail: support.ic@siemens.com www.siemens.com/protection Subject to change without notice, Printed in the UK. www. siemens.com/energy Siemens Protection Devices Limited 8