PRODUCTS GUIDE INTEGRATED COMFORT SYSTEMS

Similar documents
SIGMA PRISMA LOW BODY CONCEALED

FAN COIL UNITS LASER / LOW BODY / CONCEALED

UCS UCS/M UCS/H UCS900

DUCTED UNITS EBH EDS INTEGRATED COMFORT SYSTEMS

TECHNICAL MANUAL YEFB HIGH PRESSURE DUCTED UNIT

Blower-YEFB-020-3R-1maxVel

YFCN Fan Coil Unit centrifugal fan

ECM Technology. Technology. Features. Advantages (compared to traditional brushed motors) Power consumption: YFCN versus YFCN-ECM (W/kW)

Conditioning your ambient, maximising your comfort.

DUCTIMAX 2-8 kw. Medium available static pressure ducted hydronic units. Duct unit DUCTIMAX

Conditioning your ambient, maximising your comfort.

QTS SELECTION TECHNICAL BOOKLET

LASER Fan Coil Unit. 2 & 4 pipe system A complete range from 1.1 kw up to 9.9 kw. Thermostats

THIN PROFILE CENTRIFUGAL FAN COIL UNITS SLIM

Fans Air Handling Units Air Distribution Products Fire Safety Air Curtains and Heating Products Water terminals SYSWALL. Wall mounted fan coil units

Carisma Fly Carisma Fly-ECM. Made in. Italy. High Wall Fan Coil. Air Conditioning ENVIRONMENTAL COMFORT

SIMPLICITY FULL MODULARITY?

Also available with the new i-life R-Slim inverter and radiant panel version. Perfect comfort. Silent operation. Real energy savings

Product is subject to and complies with Regulation (UE) N.327/2011. cert. n Fan Coil Unit Cassette SkyStar Jumbo ECM. technical catalogue

SIMPLICITY OR FULL MODULARITY?

SABIANA ENVIRONMENTAL COMFORT. Air Conditioning Futura Fan Coil Units ICIM

System architecture. Air treatment Index

a-life Hydronic terminals Fan-coil for professional applications, with cabinet or built-in version 1,50-7,50 kw <<< BACK INDEX

Fan Coil Range HYDRONIC TERMINALS

COOLROW Close control air conditioners for In-Row installation Cooling Capacity: kw

MORE VALUE TO YOUR WELL-BEING

Carisma Fly. Made in. Italy. Wall-mounted Fan Coil. Air Conditioning ENVIRONMENTAL COMFORT.

technical data Fan coil unit FWB small duct unit

AIR COOLED CHILLERS WITH SCROLL COMPRESSORS AND CENTRIFUGAL FANS

F series close control air conditioners exploit the indirect FREE COOLING system with adiabatic cooling to ensure high system energy savings.

SPECIFICATION GUIDE FLEXAIR. Possibility to add auxiliary heaters: Gas, Electrical Heater, Hot Water Coil Possibility to add Heat Recovery Module

High wall fan coils Climmy FHW/FHW-ECM. Technical Catalogue

AIR COOLED CHILLERS FOR OUTDOOR INSTALLATION WITH INTEGRATED FREE COOLING MULTISCROLL SERIES

> Refrigerant R-410A. Uniflair LE TDER-TUER kW. Energy-saving units with backward-curved fans. Perimeter cooling for medium/large data center

FCX FAN COIL SILENT & EFFICIENT. Floor, ceiling & ducted installation Applicable with VMF management system, Plasmacluster filter option

GPE Kc UNITS FOR 4-PIPE SYSTEMS WITH SCROLL COMPRESSORS. COOLING CAPACITY FROM 77 TO 426 kw - 2 COOLING CIRCUITS. GPE 802 Kc + CF + GP + MV + P1

SkyStar SK. Cassette Fan Coil Unit with Asynchronous Motor

NEXT EVO DXR410A NEXT EVO DX NEW SOFTWARE. rcgroupairconditioning

Next P kw COOLING 5 93 kw HEATING. technicalcatalogue. Heat pump air conditioners with upflow air delivery T_NXTP_0411_GB

WATER COOLED HEAT PUMP VERTICAL UNIT CONSOLE TYPE OR RECESSED

NEW. Wall Controls. Air Conditioning Ceiling Air Conditioning Elegant. Cert. n 0545

UniTrane Ductable Units D-line and B-Line

ELFODuct MP. Technical Bulletin. New generation horizontal and vertical built-in water-source ductable terminal for medium and large systems

4,5 22,5 kw. technicalcatalogue. Air-conditioned server-racks for direct installation into the room T_CLSEVO_0113_GB

KPSW CONSOLE TERMINAL UNIT

HIWARM kw. Air-water system with external and internal BLDC unit. Total heat recovery multi-purpose units HIWARM PLUS

TOTAL HEAT RECOVERY MULTI-PURPOSE HEAT PUMPS

FHE FHE. Dehumidifiers for radiant cooling systems with heat recovery. Versions

SYSEFTYS - SYSHRW THE. Water Source Heat Pumps Range N E W. Water cooled. Refrigerant R407C. from 2.1 to 30.0 kw. from 2.7 to 38.1 kw. models.

SABIANA ENVIRONMENTAL COMFORT. Air Conditioning Ceiling Air Conditioning Elegant

SLS 1202 to With or without total heat recovery. u Air Cooled Screw Chillers. 262 to 916 kw. Engineering Data Manual

BRT C/H Series PACKAGED AIR TO AIR UNITS COOLING / HEATING APPLICATIONS OUTDOOR INSTALLATION. Ver. 1.01

ELFODuct MP. Technical Bulletin. New generation horizontal and vertical built-in water-source ductable terminal for medium and large systems

The integral solution for. Air Handling Units. Technology & Evolution

QUALITAIR PACKAGED SYSTEMS & APPLIED CHILLED WATER PRODUCTS. Fan Coil Units. QCeiling Cassettes. Floor Standing Units

RAS Kp AIR COOLED CHILLERS WITH RECIPROCATING COMPRESSORS AND AXIAL FANS REFRIGERANT R290 LIQUID CHILLERS - AIR COOLED AIR

Evaporadoras Hidrónicas

Technical. Catalogue. NA Version PDWL AECM. LSTAT Series Hydronic EC Ducted Fan Coil

NEW. SkyStar SkyStar ECM. Cassette Fan Coil Units. consumption ECM motors. Low energy. Air Conditioning ENVIRONMENTAL COMFORT

LCP kw. Outdoor monobloc air-water unit. Total heat recovery multi-purpose units LCP PLUS

MULTIPLO PF Multifunction chillers for indoor installation. Cooling Capacity: kw Heating Capacity: kw

EEDEN technical data. Fan coil units FWV-FWL-FWM FWD FWB FWC FWF FWT

COMFORT APPLICATION HYDRONIC TERMINALS ELEGANCE AND DESIGN FOR YOUR RESIDENTIAL COMFORT

BRAN Residential chillers and heat pumps. Reversible unit, air source for outdoor installation 4,81-27,2 kw <<< BACK INDEX.

consumption ECM motors NEW Low energy Cassette Fan Coil Units YHK ECM YHK

CWX 6 - CWX 8 - CWX 10 CASSETTE TYPE TERMINAL UNIT

CASSETTE UNIT. Comfort Circle

The Sabiana. of Fan Coil

RAH Ka AIR COOLED WATER CHILLERS WITH SCREW COMPRESSORS AND AXIAL FANS. COOLING CAPACITY FROM 387 TO 1207 kw 1 AND 2 COOLING CIRCUITS

TECNAIR LV C series Close control air conditioners

AIR COOLED CHILLERS WITH SCROLL COMPRESSORS AND CENTRIFUGAL FANS

COMFORT HYDRONIC TERMINALS

TVR 5G GUIDE SPECS. TVR 5G GUIDE SPECS - JUL.2014 Page 1

Next MTR kw. technicalcatalogue. Air conditioners for Metrology Labs with upflow air delivery T_NXTMTR_0511_GB

> HGA AIR - WATER HEAT PUMPS FOR OUTDOOR INSTALLATION. Available range. Unit description. Options. Accessories

AIR DESIGN WATER ITALIA CARISMA COLLECTION

Specification Data. General:

SkyStar SK-ECM. Cassette Fan Coil Unit with EC Brushless Electronic Motor and Inverter Board

york airside products Tailored air conditioning solutions Introducing the YORK YPRE range of custom air-to-air packaged roof top units

QZB "Standard" comfort fan coil

CWX 3 - CWX 5 CASSETTE TYPE TERMINAL UNIT. Cooling

FAN COIL UNITS. The optimal solution for limited space

Air cooled chillers. Air cooled chillers with brushless oil-free compressors. RAC. Ka Series - 1 or 2 cooling circuits capacity from 300 to 1400 kw

Fan coil units with centrifugal fan. Fan coils with inverter BRUSHLESS motor. Fan coil units with centrifugal fan. Units for air conditioning system

TECNAIR LV C series Close control air conditioners

50CO. Close Control Unit. Wide range of chilled water cabinets. Compact and attractive design. EC motor for energy savings. Auto-adaptive control

CMA TECHNICAL MANUAL CONDENSING UNITS FOR OUTDOOR INSTALLATION O L S A F RA N

next evo cw next evo cw rcgroupairconditioning

CZT CZT. High efficiency air to water heat pumps with E.V.I. compressors E.V.I. HP OTHER VERSIONS ACCESSORIES

KOG LN. Low Noise Chilled Water Cassettes Models 09, 12 & to 6.10kW to 5.10kW. 330 to 920 m3/h

Dehumidification and ventilation for residential, industrial radiant systems and swimming pools

Galletti IWC THE HYDRONIC CASSETTE UNIT PAR EXCELLENCE A guide to choosing Create value to design better

Air Conditioning Carisma CRS High Pressure Fan Coil Units.

Technical Catalogue. Air-Cooled Liquid Chillers with screw compressors Nominal cooling capacity: kw 50 Hz

Elegance and design for your residential comfort

CMA CONDENSING UNITS FOR OUTDOOR INSTALLATION INSTALLATION AND OPERATION MANUAL

Fan Coil Unit 1. BOSCH Climate Fan Coil Unit

Fan coils with Inverter Brushless motor (EC) Universal and floor installation FCZI_U

OMNIA RADIANT FAN COIL WITH RADIANT HEATING PANEL THE FAN COIL FEATURING 3 HEATING MODES

Technical Manual. New Water Cassette. Series BREZZA DOUBLE

Transcription:

PRODUCTS GUIDE INTEGRATED COMFORT SYSTEMS

Founded in Pordenone in 1979, EURAPO has grown and developed as part of the state-of-the-art industrial scenario of North-East Italy. EURAPO is specialized in the production of heating and air conditioning units. The Company has always fostered a serene, well-organised working environment where employee participation is encouraged. Here several decades of invaluable experience are pitted against new human resources and projects, in a constructive exchange of ideas between generations, making EURAPO a young, proactive, creative company. As well as these consolidated qualities, EURAPO products are now available with innovative features: a smart, made in Italy design for the fan coil unit range, ducted units with high performances, from the traditional regulation system to the great potential of Omnibus, the new sophisticate digital system even for BMS systems. EURAPO products are well known for energy efficiency, certified performances, highly resistant materials, great emphasis on safety in order to make installation as simple as possible. Highly customised products designed to meet specific system requirements providing a wide range of different technical and aesthetic solutions. Products are strictly subjected to systematic controls before being introduced onto the market, equipped with accessories and properly wired up. This comprehensive approach has enabled the Company to gain the loyalty of a highly-demanding, prestigious world market, with privileged outlets in Italy and in many countries in Central and Northern Europe. And with new prospects for border-free development.

LABORATORIES LABORATORIES Innovation has always been a key factor for competitiveness: in the current global economy, it allows companies to diversify strategies and products to size new opportunities and to face diversities and peculiarities, which distinguish every single market. In 2013, Eurapo decided to take a very important step in terms of investments, by building, in cooperation with Padua University, brand new technical laboratories, in strict compliance with the applicable regulations and Eurovent standards, in order to achieve the following goals: differentiate the offered products through the continuous and constant research of innovative technical and technological solutions, which follow or anticipate global markets dynamics; improve products quality, efficiency, performances, security and reliability; ensure performances of the offered products by running periodic tests and making analysis on the results; improve the technical support offered to their customers, by providing accurate, reliable and customized solutions with a very short response time; consolidate their presence in an increasingly competitive market; strengthen the engineering and technical relationships with their industrial and business partners. The laboratories, which cover an area of over 400 square meters, can measure aeraulic, acoustic and thermal performances of all Eurapo products, both ducted and non-ducted, and consist of: 4

A CLIMATE CHAMBER, which measures heating and cooling capacities and is able to test units with heating capacities from 0,5 kw to 40 kw (standard conditions: 20 C/50% r.h.) and cooling capacities from 0,5 kw to 30 kw (standard conditions: 27 C/48% r.h.). It has been manufactured in compliance with EN 1397:2001 standards and Eurovent 6/3 standards (Thermal test method for Fan Coil units) and Eurovent 6/11 standards (Thermal test method for Ducted Fan Coil units). Two AERAULIC TUNNELS, a standard one and an enthalpy one, which are sized to ensure a correct measurement of the air flow from 100 m³/h to 6000 m³/h. The two tunnels have been manufactured according to ISO 5801:2007 (and former UNI 10531) and ISO 5221 standards and to Eurovent 6/3 standards (Thermal test method for Fan Coil units) and Eurovent 6/10 standards (Air Flow test method for Ducted Fan Coil units). Two REVERBERATION ROOMS, designed to measure very low sound power levels, with range of frequency between 100Hz and 10000Hz, in accordance with the methods of measurements described in UNI EN ISO 3740:2002, UNI EN ISO 3741:2010 and UNI EN ISO 5135:2003 standards. Each room complies with Eurovent 8/2 standards (Acoustical testing of Fan Coil Units). The two rooms are connected by an air duct in order to run acoustic test on ducted units, in compliance with 8/12 Eurovent standards (Sound test method for Ducted Fan Coil units). The laboratories represent the highest evolution in terms of technological solutions that make them unique in Italy. With the new technical laboratories, research, development and innovation become strongly and increasingly an integral part of the Eurapo corporate mission, to pursue the goal of continuous improvement. 5

kw 0,83 1,50 2,00 2,87 3,52 0 1 2 3 4 5 6 7 8 kw 0,62 1,16 1,64 2,20 3,36 3,58 4,53 5,19 6,57 7,41 Products page FAN COIL UNITS 10 Sphera page FAN COIL UNITS 16 Sigma 0 1 2 3 4 5 6 7 8 page FAN COIL UNITS 24 Prisma page FAN COIL UNITS 32 Low Body page FAN COIL UNITS 40 Concealed kw kw kw 0 0 0,48 0,62 0,62 1,16 1 1 1,48 1,16 1,64 1,74 1,64 2 2 2,20 2,53 2,20 3,36 3,95 3 3,06 3,75 3 3,36 3,58 4 4 4,53 5 5 5,19 6 6 6,57 7 7 7,41 8 8 0 1 2 3 4 5 6 7 8 page DUCTED UNITS 48 EBH kw 2,29 4,47 6,21 8,86 10,42 (50 Pa) 0 1 2 3 4 5 6 7 8 9 10 11 12 6

kw 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 9,50 11,38 13,26 kw 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 kw 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 kw 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 9,50 11,38 13,26 kw 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 12,94 15,47 17,22 20,35 24,80 27,74 33,10 kw 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 32 33 34 7

kw 1,14 1,95 3,44 4,22 5,50 7,19 8,87 (50 Pa) 0 1 2 3 4 5 6 7 8 9 10 11 kw 0 1,39 1,81 1 2 2,52 2,93 3,57 3,86 3 4 4,89 5 6 7 8 kw 1,39 1,81 2,52 2,93 Products page DUCTED UNITS 54 EDS page CASSETTE UNITS 60 UCS600 UCS/M 600 page CASSETTE UNITS 68 UCS/H 600 3,57 3,86 4,89 0 1 2 3 4 5 6 7 8 page CASSETTE UNITS 76 UCS900 kw 3,90 7,62 0 1 2 3 4 5 6 7 8 page 84 EST ENERGY SAVING TECHNOLOGY page BUILDING MANAGEMENT SYSTEM 86 OMNIBUS 8

12,62 16,64 20,88 23,23 25,58 27,96 kw 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 kw 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 kw 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 8,76 9,20 10,15 kw 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 9

SPHERA MODEL, FOR HEATING AND COOLING, 2 AND 4 PIPES, CAPACITY FROM 0,8 kw TO 3,52 kw. mod. ESF mod. ESF LUX SPHERA FANCOIL UNITS mod. ESW mod. ESW LUX Thanks to its elegant and refined design, extremely silent and compact, SPHERA fancoil is suitable for creating comfort and closeness in every style. Smart and versatile, SPHERA fancoil is available for wall or floor installation and can be combined with the newest EURAPO controls: from the traditional mechanical or microprocessor controls to those innovative digital controls, which can be integrated to the Building Automation System. SPHERA fancoil rises from EURAPO well-established experience by word of reliability, competence as well as continuous technical and design research. SPHERA is definitely a revolutionary way to think about a fancoil. 10

TECHNICAL DATA (max speed-est) 20 40 Cooling Total cooling capacity [kw] 2,03 3,46 Air temperature 27 C d.b., 19 C w.b. Water temperature 7/12 C Sensible cooling capacity [kw] 1,69 2,83 Water flow [l/h] 348 594 Pressure drop [kpa] 3,5 11,6 Heating Heating capacity [kw] 2,91 4,60 2 pipes Air temperature 20 C Inlet water temperature 50 C Water flow [l/h] Values as Cooling, accordingly to the EUROVENT Standards and UNI ENV 1397 Norm Pressure drop [kpa] 3,0 10,0 Heating Heating capacity [kw] 5,07 7,81 2 pipes Air temperature 20 C Water temperature 70/60 C Water flow [l/h] 443 667 Pressure drop [kpa] 4,6 12,0 Further data Air flow [m 3 /h] 387 617 Sound power level [db(a)] 56 59 Sound pressure level [db(a)] 46 49 Power input [W] 36 56 Absorbed current [A] 0,33 0,46 Water content [I] (2 pipes) 0,87 1,32 TECHNICAL DATA (max speed-asynchronous) 20 40 Cooling Total cooling capacity [kw] 1,94 3,12 Air temperature 27 C d.b., 19 C w.b. Water temperature 7/12 C Sensible cooling capacity [kw] 1,58 2,48 Water flow [l/h] 333 535 Pressure drop [kpa] 3,3 9,9 Heating Heating capacity [kw] 2,69 4,09 2 pipes Air temperature 20 C Inlet water temperature 50 C Water flow [l/h] Values as Cooling, accordingly to the EUROVENT Standards and UNI ENV 1397 Norm Pressure drop [kpa] 2,8 8,5 Heating Heating capacity [kw] 4,68 6,96 2 pipes Air temperature 20 C Water temperature 70/60 C Water flow [l/h] 428 600 Pressure drop [kpa] 4,6 10,1 Further data Air flow [m 3 /h] 345 511 Sound power level [db(a)] 51 58 Sound pressure level [db(a)] 41 48 Power input [W] 53 85 Absorbed current [A] 0,24 0,38 Water content [I] (2 pipes) 0,87 1,32 11

DIMENSIONS mod. ESF mod. ESW SPHERA FANCOIL UNITS mod. ECV mod. ECH 12

Dimensions (mm) and weights ESF 20 40 A 900 1200 Dimensions (mm) and weights ESW 20 40 A 900 1200 B 540 540 B 540 540 C 190 190 C 190 190 kg 19 27 Water connections 1/2 G F kg 20 29 Water connections 1/2 G F Dimensions (mm) and weights ECV - ECH 20 40 A 843 1143 B 357 357 C 186 186 kg 14 20 Water connections 1/2 G F 13

ACCESSORIES KREL Electric heater EXTRA RAL Special painting DTH2902 Valve and shut off valve PC Condensate pump SPHERA FANCOIL UNITS PPV Vertical back panel EST TECHNOLOGY PPV LUX Vertical back panel PA Air suction plenum PM90 90 air delivery plenum EDCR Remote microprocessor control for brushless motors OBF10 Omnibus card for brushless motors with Modbus ODC736 White Analogue Plus Console on wall for brushless motors ODC735-745 White (ODC735) or black (ODC745) Analogue Plus Console for brushless motors ODC236 White Display Console for brushless motors ODC235-245 White (ODC235) or black (ODC245) Display Console for brushless motors ODC336 White Display Console on wall with humidity sensor for brushless motors ODC335-345 White (ODC335) or black (ODC345) Display Console with humidity sensor for brushless motors 14

STANDARD CONTROLS CBL20 Master & Slave card WS Water sensor TM Minimum water temperature thermostat CSR00 Control panel 3 speeds CMR00 Room temperature thermostat, 3 speeds, S/W switch CER00 Microprocessor control with thermostat, 3 speeds, Auto S/W switch CER20 Microprocessor control with thermostat, Auto speeds, S/W switch OMNIBUS CONTROLS OPF10 Omnibus card for BMS OPF11-OC123 Omnibus card for BMS + Analogue Console OPF11-OC223 Omnibus card for BMS + Display Console OPF11-OC723 Omnibus card for BMS + Analogue Plus Console OPF11-OC523 Omnibus card for BMS + Infrared control OPF11-OC423 Omnibus card for BMS + Manager Console ONF10 Omnibus card not for BMS ONF11-OC123 Omnibus card + Analogue Console ONF11-OC223 Omnibus card + Display Console ONF11-OC723 Omnibus card + Analogue Plus Console ONF11-OC523 Omnibus card + Infrared Console OC136 White Analogue Console on wall OC135-145 White (OC135) or black (OC145) Analogue Console OC736 White Analogue Plus Console on wall OC735-745 White (OC735) or black (OC745) Analogue Plus Console OC236 White Display Console on wall OC235-245 White (OC235) or black (OC245) Display Console OC436 White Manager Console on wall OC435-445 White (OC435) or black (OC445) Manager Console OC336 White Display Console on wall with humidity sensor OC335-345 White (OC335) or black (OC345) Display Console with humidity sensor OC516 White IR Console on wall must be combined with OIR30 OC515-525 White (OC515) or black (525) IR Console must be combined with OIR30 OPF50 Multitask additional card ONET Web server with Ethernet card for TCP/IP protocol OCB20 LON converter OIR30 Infrared remote control OCB30 OTOUCH Touch screen supervision panel 15

Sigma FAN COIL UNIT WITH CASING, FOR HEATING AND COOLING, 2 AND 4 PIPES, CAPACITY FROM 0,62 kw TO 13,26 kw. mod. SV mod. SV/AF SIGMA FANCOIL UNITS mod. SH mod. SH/AF SIGMA fancoil unit, designed by Eurapo, is versatile in different applications, discreet in the lines, reliable in the performances. This fancoil unit, with its harmonic shapes and linearity, can be installed in every kind of environment thanks to its configuration variety: it can be installed directly on the floor, with frontal air intake, or it can stand on the floor with feet, with bottom air intake. The same configuration is available for ceiling installation: rear or bottom air intake. The Sigma housing is manufactured with sheet steel and painted with oven dried epoxy powders, available in all RAL colours; access doors and grilles are made of heat-resistant ABS and can be turned into all four directions. Standard colour is RAL9003, white. One important element is the filter, totally retractable and easily accessible; it is particularly strong, wear and tear resistant, requiring short time for routine maintenance. In order to make Sigma fancoil more complete, Eurapo offers a large range of accessories, from the simple electromechanical regulations and on/off valves to the advanced systems with modulating valves and digital Bus management. Sigma units are also available for District Cooling applications: the water coils are designed with a reduced number of circuits, suitable for functioning with high water temperature difference. 16

TECHNICAL DATA (3 rows, max speed-est) 512 514 516 520 522 524 528 Cooling Total cooling capacity [kw] 1,98 2,56 3,81 5,05 5,81 7,47 9,18 Air temperature 27 C d.b., 19 C w.b. Water temperature 7/12 C Sensible cooling capacity [kw] 1,65 2,12 3,14 4,13 4,80 6,09 7,51 Water flow [l/h] 340 439 654 867 997 1282 1575 Pressure drop [kpa] 9,6 6,5 14,6 16,9 22,2 16,8 31,3 Heating Heating capacity [kw] 2,79 3,69 4,13 6,86 7,97 10,03 12,35 Air temperature 20 C Inlet water temperature 50 C Water flow [l/h] Values as Cooling, accordingly to the EUROVENT Standards and UNI ENV 1397 Norm Pressure drop [kpa] 8,0 5,4 12,7 14,6 19,1 14,9 26,9 Heating Heating capacity [kw] 4,76 6,39 9,17 11,61 13,53 16,91 20,91 Air temperature 20 C Water temperature 70/60 C Water flow [l/h] 392 524 747 946 1102 1379 1731 Pressure drop [kpa] 13,8 7,3 15,8 16,6 22,2 16,4 30,8 Further data Air flow [m 3 /h] 456 575 793 1083 1306 1566 2040 Sound power level [db(a)] 55 59 57 57 62 63 69 Sound pressure level [db(a)] 45 49 57 47 52 53 59 Power input [W] 37 54 45 47 78 92 176 Absorbed current [A] 0,33 0,44 0,37 0,45 0,68 0,83 1,50 Water content [I] (2 pipes) 0,79 1,05 1,31 2,20 2,20 2,84 3,47 To obtain capacities for District Cooling solutions or for conditions different from standard ones, please use the EURAPO selection software. TECHNICAL DATA (3 rows, max speed-asynchronous) 110 112 114 216 218 220 222 224 226 328 Cooling Total cooling capacity [kw] 1,11 1,59 2,14 3,30 3,50 4,44 5,07 6,43 7,25 9,73 Air temperature 27 C d.b., 19 C w.b. Water temperature 7/12 C Sensible cooling capacity [kw] 0,93 1,25 1,90 2,46 3,06 3,53 4,42 5,06 5,70 8,04 Water flow [l/h] 199 281 414 577 614 777 891 1127 1271 1669 Pressure drop [kpa] 3,4 7,1 5,8 14,8 13,6 24,1 28,4 18,8 21,0 34,2 Heating Heating capacity [kw] 1,57 2,16 3,05 4,11 4,95 5,71 7,19 7,83 9,33 12,97 Air temperature 20 C Inlet water temperature 50 C Water flow [l/h] Values as Cooling, accordingly to the EUROVENT Standards and UNI ENV 1397 Norm Pressure drop [kpa] 2,7 6,1 4,8 11,9 12,5 20,0 23,5 15,5 20,5 30,4 Heating Heating capacity [kw] 2,77 3,70 5,25 6,96 8,43 9,64 12,18 13,30 15,82 22,00 Air temperature 20 C Water temperature 70/60 C Water flow [l/h] 246 265 393 524 601 691 835 1116 1303 1638 Pressure drop [kpa] 4,9 7,8 6,4 14,3 15,6 22,4 26,8 18,2 24,3 34,8 Further data Air flow [m 3 /h] 243 321 436 581 712 871 1081 1254 1481 2068 Sound power level [db(a)] 48 50 54 53 55 54 60 60 63 67 Sound pressure level [db(a)] 39 41 44 44 46 44 50 49 53 57 Power input [W] 46 48 57 61 76 90 117 140 162 222 Absorbed current [A] 0,23 0,23 0,26 0,29 0,33 0,38 0,52 0,65 0,65 1,06 Water content [I] (2 pipes) 0,53 0,79 1,05 1,31 1,57 2,20 2,20 2,84 2,84 3,47 To obtain capacities for District Cooling solutions or for conditions different from standard ones, please use the EURAPO selection software. 17

Sigma DIMENSIONS mod. SV and mod. SH SIGMA FANCOIL UNITS mod. SV/AF and mod. SH/AF 18

Dimensions (mm) and weights SV - SV/AF - SH - SH/AF 110 112 114 216 218 220 222 224 226 328 EST - 512 514 516-520 522 524-528 mod. SV A 648 773 898 1023 1148 1273 1273 1523 1523 1773 B 538 538 538 538 538 614 614 614 614 614 SV - SH C 224 224 224 224 224 254 254 254 254 254 kg 18 20 23 28 31 41 44 52 52 58 SV/AF - SH/AF mod. SH C 233 233 233 233 233 263 263 263 263 263 kg 19 21 24 30 32 43 46 54 54 61 Water connections 1/2 G F mod. SV/AF mod. SH/AF 19

Sigma EST TECHNOLOGY EST Brushless motor with inverter EDCL Microprocessor control for brushless motors EDCR Remote microprocessor control for brushless motors OBV10 Omnibus card with Modbus for brushless motors SIGMA FANCOIL UNITS OBV11-ODC211 Omnibus card + Display Console for brushless motors with Modbus ODC236 White Display Console on wall for brushless motors ODC235 White Display Console for brushless motors ODC245 Black Display Console for brushless motors ODC736 White Analogue Plus Console on wall for brushless motors ODC735-745 White (ODC735) or black (ODC736) Analogue Plus Console for brushless motors ODC336 White Display Console on wall with humidity sensor for brushless motors ODC335-345 White (ODC335) or black (ODC345) Display Console with humidity sensor for brushless motors 20

ACCESSORIES BA1 Additional heating coil for 4 pipe system KREL Electric heater H3A2+DT Valves and shut-off valves PC Condensate pump TM Minimum water temperature thermostat CP Set of feet ZL Long socle with feet PPV SIGMA Vertical back panel PPH Horizontal back panel PAE/V Vertical external air intake with manual damper PAE/VM Vertical external air intake with motorized damper PAE/HAF Horizontal external air intake for AF models AFT Anti-frost thermostat EXTRA RAL Special painting KIT 4 PIPES COMPACT Hydraulic kit 21

Sigma STANDARD CONTROLS CSL00 3 fan speed selector CML00 Room thermostat, 3 speeds, S/W switch CEL00 Microprocessor control, with thermostat, 3 speeds, Auto S/W switch CEL10/B Microprocessor control as CEL00, for modulating valves SIGMA FANCOIL UNITS CEL20 Microprocessor control, with thermostat, Auto speeds, Auto S/W switch CBL20 Master & Slave card CEL30/B Microprocessor control as CEL20, for modulating valves CBL30 Master & Slave card for modulating valves CEL31 Microprocessor control as CEL30/B, power supply 24V AS Air sensor CBL10 Transformer 230/24V WS Water sensor TAD10 Room temperature thermostat, S/W switch CSR00 Remote control panel 3 speeds CMR00 Room temperature thermostat, 3 speeds, S/W switch CER00 Microprocessor control with thermostat, 3 speeds, Auto S/W switch CER10/B Microprocessor control as CER00 for modulating valves CER20 Microprocessor control with thermostat, Auto speeds, Auto S/W switch CER30/B Microprocessor control as CER20, for modulating valves CER31 Microprocessor control as CER30/B, power supply 24V 22

OMNIBUS CONTROLS OPV10 Omnibus card for BMS OPV11-OC111 Omnibus card for BMS + Analogue Console OPV11-OC211 Omnibus card for BMS + Display Console OPV11-OC711 Omnibus card for BMS + Analogue Plus Console OPV11-OC411 Omnibus card for BMS + Manager Console OPV11-OC517 Omnibus card for BMS + Infrared Receiver ONV10 Omnibus card not for BMS ONV11-OC111 Omnibus card + Analogue Console ONV11-OC211 Omnibus card + Display Console ONV11-OC711 Omnibus card + Analogue Plus Console ONV11-OC517 Omnibus card + Infrared Receiver OC136 White Analogue Console on wall OC135-145 Analogue Console white (OC135) or black (OC145) OC736 White Analogue Plus Console on wall OC735-745 Analogue Plus Console white (OC735) or black (OC745) OC236 White Display Console on wall OC235-245 Display Console white (OC235) or black (OC245) OC436 White Manager Console on wall OC435-445 Manager Console white (OC435) or black (OC445) OC336 White Display Console on wall with humidity sensor OC335-345 White (OC335) or black (OC345) Display Console with humidity sensor OC516 White IR Console on wall must be combined with OIR30 OC515-525 White (OC515) or black (OC525) IR Console must be combined with OIR30 OIR30 Infrared remote control OPV50 Multitask additional card ONET Web server with Ethernet card for TCP/IP protocol OCB20 LON Converter OCB30 OTOUCH Touch screen supervision panel 23

Prisma FANCOIL UNIT WITH CASING, FOR HEATING AND COOLING (ONLY FOR PV AND PV/AF), 2 AND 4 PIPES, CAPACITY FROM 0,62 kw TO 3,95 kw. mod. PV mod. PV/AF PRISMA FANCOIL UNITS mod. PH mod. PH/AF PRISMA fancoil unit has an original shape. The housing itself is a piece of furniture, it is made of painted metal sheet with side flaps and grilles made of ABS, which are adjustable in all four directions. This fancoil is designed by Eurapo to be compatible with every kind of environment, thanks to its configuration variety: it can be easily installed on the floor, thanks to firm feet, or mounted on the ceiling. In both configurations the air intake can be located on the bottom or front side. One important component is the filter, which is totally retractable but easily accessible; it is particularly strong and wear resistant and needs very short time for routine maintenance. In order to make Prisma fancoil more complete, Eurapo offers a large range of accessories, from the simple electromechanical regulations and on/off valves to the advanced systems with modulating valves and digital Bus management. 24

TECHNICAL DATA (3 rows, max speed-est) 512 514 516 Cooling Total cooling capacity [kw] 1,98 2,56 3,81 Air temperature 27 C d.b., 19 C w.b. Water temperature 7/12 C Sensible cooling capacity [kw] 1,65 2,12 3,14 Water flow [l/h] 340 439 654 Pressure drop [kpa] 9,6 6,5 14,6 Heating Heating capacity [kw] 2,79 3,69 4,13 Air temperature 20 C Inlet water temperature 50 C Water flow [l/h] Pressure drop [kpa] 8,0 5,4 12,7 Values as Cooling, accordingly to the EUROVENT Standards and UNI ENV 1397 Norm Heating Heating capacity [kw] 4,76 6,39 9,17 Air temperature 20 C Water temperature 70/60 C Water flow [l/h] 392 524 747 Pressure drop [kpa] 13,8 7,3 15,8 Further data Air flow [m 3 /h] 456 575 793 Sound power level [db(a)] 55 59 57 Sound pressure level [db(a)] 45 49 57 Power input [W] 37 54 45 Absorbed current [A] 0,33 0,44 0,37 Water content [I] (2 pipes) 0,79 1,05 1,31 TECHNICAL DATA (3 rows, max speed-asynchronous) 110 112 114 216 218 Cooling Total cooling capacity [kw] 1,11 1,59 2,14 3,30 3,50 Air temperature 27 C d.b., 19 C w.b. Water temperature 7/12 C Sensible cooling capacity [kw] 0,93 1,25 1,90 2,46 3,06 Water flow [l/h] 199 281 414 577 614 Pressure drop [kpa] 3,4 7,1 5,8 14,8 13,6 Heating Heating capacity [kw] 1,57 2,16 3,05 4,11 4,95 Air temperature 20 C Inlet water temperature 50 C Water flow [l/h] Values as Cooling, accordingly to the EUROVENT Standards and UNI ENV 1397 Norm Pressure drop [kpa] 2,7 6,1 4,8 11,9 12,5 Heating Heating capacity [kw] 2,77 3,70 5,25 6,96 8,43 Air temperature 20 C Water temperature 70/60 C Water flow [l/h] 246 265 393 524 601 Pressure drop [kpa] 4,9 7,8 6,4 14,3 15,6 Further data Air flow [m 3 /h] 243 321 436 581 712 Sound power level [db(a)] 48 50 54 53 55 Sound pressure level [db(a)] 39 41 44 44 46 Power input [W] 46 48 57 61 76 Absorbed current [A] 0,23 0,23 0,26 0,29 0,33 Water content [I] (2 pipes) 0,53 0,79 1,05 1,31 1,57 25

Prisma DIMENSIONS mod. PV A C B PRISMA FANCOIL UNITS mod. PH/AF 26

Dimensions (mm) and weights PV - PV/AF - PH - PH/AF mod. PV 110 112 114 216 218 EST - 512 514 516 - A 648 773 898 1023 1148 B 560 560 560 560 560 PV - PH C 226 226 226 226 226 kg 17 20 23 27 31 PV/AF - PH/AF mod. PV/AF C 235 235 235 235 235 kg 18 21 24 28 32 Water connections 1/2 G F mod. PH mod. PH/AF 27

Prisma EST TECHNOLOGY EST Brushless motor with inverter EDCL Microprocessor control for brushless motors EDCR Remote microprocessor control for brushless motors OBV10 Omnibus card with Modbus for brushless motors PRISMA FANCOIL UNITS OBV11-ODC211 Omnibus card + Display Console for brushless motors with Modbus ODC236 White Display Console on wall for brushless motors ODC235 White Display Console for brushless motors ODC245 Black Display Console for brushless motors ODC736 White Analogue Plus Console on wall for brushless motors ODC735-745 White (ODC735) or black (ODC745) Analogue Plus Console for brushless motors ODC336 White Display Console on wall with humidity sensor for brushless motors ODC335-345 White (ODC335) or black (ODC345) Display Console with humidity sensor for brushless motors 28

ACCESSORIES BA1 Additional heating coil for 4 pipe system KREL Electric heater H3A2+DT Valves and shut-off valves PC Condensate pump TM Minimum water temperature thermostat CP Set of feet ZL Long socle with feet PPH Horizontal back panel PAE/V Vertical external air intake with manual damper PAE/VM Vertical external air intake with motorized damper PAE/HAF Horizontal external air intake for AF models AFT Antifrost thermostat EXTRA RAL Special painting PPV PRISMA Vertical back panel KIT 4 PIPES COMPACT Hydraulic kit 29

Prisma STANDARD CONTROLS CSL00 3 fan speed selector CML00 Room thermostat, 3 speeds, S/W switch CEL00 Microprocessor control, with thermostat, 3 speeds, Auto S/W switch CEL10/B Microprocessor control as CEL00, for modulating valves PRISMA FANCOIL UNITS CEL20 Microprocessor control, with thermostat, Auto speeds, Auto S/W switch CBL20 Master & Slave card CEL30/B Microprocessor control as CEL20, for modulating valves CBL30 Master & Slave card for modulating valves CEL31 Microprocessor control as CEL30/B, power supply 24V AS Air sensor CBL10 Transformer 230/24V WS Water sensor TAD10 Room temperature thermostat, S/W switch CSR00 Remote control panel 3 speeds CMR00 Room temperature thermostat, 3 speeds, S/W switch CER00 Microprocessor control with thermostat, 3 speeds, Auto S/W switch CER10/B Microprocessor control as CER00 for modulating valves CER20 Microprocessor control with thermostat, Auto speeds, Auto S/W switch CER30/B Microprocessor control as CER20, for modulating valves CER31 Microprocessor control as CER30/B, power supply 24V 30

OMNIBUS CONTROLS OPV10 Omnibus card for BMS OPV11-OC111 Omnibus card for BMS + Analogue Console OPV11-OC211 Omnibus card for BMS + Display Console OPV11-OC711 Omnibus card for BMS + Analogue Plus Console OPV11-OC411 Omnibus card for BMS + Manager Console OPV11-OC517 Omnibus card for BMS + Infrared Receiver ONV10 Omnibus card not for BMS ONV11-OC111 Omnibus card + Analogue Console ONV11-OC211 Omnibus card + Display Console ONV11-OC711 Omnibus card + Analogue Plus Console ONV11-OC517 Omnibus card + Infrared Receiver OC136 White Analogue Console on wall OC135-145 Analogue Console white (OC135) or black (OC145) OC736 White Analogue Plus Console on wall OC735-745 Analogue Plus Console white (OC735) or black (OC745) OC236 White Display Console on wall OC235-245 Display Console white (OC235) or black (OC245) OC436 White Manager Console on wall OC435-445 Manager Console white (OC435) or black (OC445) OC336 White Display Console on wall with humidity sensor OC335-345 White (OC335) or black (OC345) Display Console with humidity sensor OC516 White IR Console on wall must be combined with OIR30 OC515-525 White (OC515) or black (OC525) IR Console must be combined with OIR30 OIR30 Infrared remote control OPV50 Multitask additional card ONET Web server with Ethernet card for TCP/IP protocol OCB20 LON Converter OCB30 OTOUCH Touch screen supervision panel 31

FANCOIL UNIT WITH COMPACT DIMENSIONS, FOR HEATING AND COOLING, 2 AND 4 PIPES, CAPACITY FROM 0,48 kw TO 3,75 kw. LOW BODY FANCOIL UNITS Low Body mod. SVR mod. CVR The LOW BODY fancoils are characterized by a very reduced height (only 427 mm) and they have been designed for installation in small niches. The LOW BODY units present an upper air outlet and a frontal air intake; they can be installed on the floor, on the wall or concealed. The low body fancoils are available in 5 sizes and they are always equipped with an auxiliary drain pan. The inner frame is made of galvanized steel, the housing is manufactured with sheet steel painted with oven dried epoxy powders available in all RAL colours (standard colour is RAL9003), access doors and grilles are made of white coloured heat-resistant ABS and can be turned into all four directions. To complete all models, Eurapo offers a wide range of accessories. 32

TECHNICAL DATA (3 rows, max speed-est) 512 514 516 Cooling Total cooling capacity [kw] 1,47 1,98 2,77 Air temperature 27 C d.b., 19 C w.b. Water temperature 7/12 C Sensible cooling capacity [kw] 1,36 1,75 2,35 Water flow [l/h] 252 340 475 Pressure drop [kpa] 5,3 8,3 6,8 Heating Heating capacity [kw] 2,19 2,87 3,96 Air temperature 20 C Inlet water temperature 50 C Water flow [l/h] Values as Cooling, accordingly to the EUROVENT Standards and UNI ENV 1397 Norm Pressure drop [kpa] 4,6 7,3 5,8 Heating Heating capacity [kw] 3,79 4,90 6,80 Air temperature 20 C Water temperature 70/60 C Water flow [l/h] 308 388 560 Pressure drop [kpa] 6,5 9,1 7,6 Further data Air flow [m 3 /h] 386 494 682 Sound power level [db(a)] 57 60 60 Sound pressure level [db(a)] 47 50 50 Power input [W] 34 46 52 Absorbed current [A] 0,30 0,41 0,44 Water content [I] (2 pipes) 0,62 0,83 1,03 TECHNICAL DATA (3 rows, max speed-asynchronous) 110 112 114 216 218 Cooling Total cooling capacity [kw] 0,98 1,16 1,74 2,53 3,06 Air temperature 27 C d.b., 19 C w.b. Water temperature 7/12 C Sensible cooling capacity [kw] 0,86 1,07 1,49 2,38 2,58 Water flow [l/h] 168 199 299 434 525 Pressure drop [kpa] 2,1 3,0 6,9 5,8 8,9 Heating Heating capacity [kw] 1,36 1,68 2,39 3,44 4,13 Air temperature 20 C Inlet water temperature 50 C Water flow [l/h] Values as Cooling, accordingly to the EUROVENT Standards and UNI ENV 1397 Norm Pressure drop [kpa] 1,7 2,5 5,8 4,9 7,6 Heating Heating capacity [kw] 2,55 2,90 4,07 5,91 7,05 Air temperature 20 C Water temperature 70/60 C Water flow [l/h] 281 239 339 513 600 Pressure drop [kpa] 4,4 3,4 7,2 6,5 9,4 Further data Air flow [m 3 /h] 253 317 432 614 737 Sound power level [db(a)] 51 51 54 55 58 Sound pressure level [db(a)] 41 41 45 45 49 Power input [W] 46 51 57 67 77 Absorbed current [A] 0,22 0,23 0,25 0,29 0,33 Water content [I] (2 pipes) 0,41 0,62 0,83 1,03 1,24 33

Low Body DIMENSIONS mod. CVR LOW BODY FANCOIL UNITS mod. SVR 34

Dimensions (mm) and weights CVR mod. CVR 110 112 114 216 218 EST - 512 514 516 - A 555 680 805 930 1055 B 395 395 395 395 395 C 230 230 230 230 230 kg 9 11 14 16 19 Water connections - 1/2 G F Dimensions (mm) and weights SVR mod. SVR 110 112 114 216 218 EST - 512 514 516 - A 648 773 898 1023 1148 B 430 430 430 430 430 C 254 254 254 254 254 kg 15 17 22 23 26 Water connections - 1/2 G F 35

Low Body EST TECHNOLOGY EST Brushless motor with inverter EDCL Microprocessor control for brushless motors EDCR Remote microprocessor control for brushless motors OBV10 Omnibus card with Modbus for brushless motors LOW BODY FANCOIL UNITS OBV11-ODC211 Omnibus card + Display Console for brushless motors with Modbus ODC236 White Display Console on wall for brushless motors ODC235 White Display Console for brushless motors ODC245 Black Display Console for brushless motors ODC736 White Analogue Plus Console on wall for brushless motors ODC735-745 White (ODC735) or black (ODC745) Analogue Plus Console ODC336 White Display Console on wall with humidity sensor for brushless motors ODC335-345 White (ODC335) or black (ODC345) Display Console with humidity sensor for brushless motors 36

ACCESSORIES BA1 Additional heating coil for 4 pipe system KREL Electric heater H3A2+DT Valves and shut-off valves PC Condensate pump TM Minimum water temperature thermostat PPV LOW BODY Vertical back panel PM Air delivery plenum with collars PM90 90 Air delivery plenum EXTRA RAL Special painting 37

STANDARD CONTROLS Low Body CSL00 3 fan speed selector CML00 Room thermostat, 3 speeds, S/W switch CEL00 Microprocessor control, with thermostat, 3 speeds, Auto S/W switch CEL10/B Microprocessor control as CEL00, for modulating valves LOW BODY FANCOIL UNITS CEL20 Microprocessor control, with thermostat, Auto speeds, Auto S/W switch CBL20 Master & Slave card CEL30/B Microprocessor control as CEL20, for modulating valves CBL30 Master & Slave card for modulating valves CEL31 Microprocessor control as CEL30/B, power supply 24V AS Air sensor CBL10 Transformer 230/24V WS Water sensor TAD10 Room temperature thermostat, S/W switch CSR00 Remote control panel 3 speeds CMR00 Room temperature thermostat, 3 speeds, S/W switch CER00 Microprocessor control with thermostat, 3 speeds, Auto S/W switch CER10/B Microprocessor control as CER00 for modulating valves CER20 Microprocessor control with thermostat, Auto speeds, Auto S/W switch CER30/B Microprocessor control as CER20, for modulating valves CER31 Microprocessor control as CER30/B, power supply 24V 38

OMNIBUS CONTROLS OPV10 Omnibus card for BMS OPV11-OC111 Omnibus card for BMS + Analogue Console OPV11-OC211 Omnibus card for BMS + Display Console OPV11-OC711 Omnibus card for BMS + Analogue Plus Console OPV11-OC411 Omnibus card for BMS + Manager Console OPV11-OC517 Omnibus card for BMS + Infrared Receiver ONV10 Omnibus card not for BMS ONV11-OC111 Omnibus card + Analogue Console ONV11-OC211 Omnibus card + Display Console ONV11-OC711 Omnibus card + Analogue Plus Console ONV11-OC517 Omnibus card + Infrared Receiver OC136 White Analogue Console on wall OC135-145 Analogue Console white (OC135) or black (OC145) OC736 White Analogue Plus Console on wall OC735-745 Analogue Plus Console white (OC735) or black (OC745) OC236 White Display Console on wall OC235-245 Display Console white (OC235) or black (OC245) OC436 White Manager Console on wall OC435-445 Manager Console white (OC435) or black (OC445) OC336 White Display Console on wall with humidity sensor OC335-345 White (OC335) or black (OC345) Display Console with humidity sensor OC516 White IR Console on wall must be combined with OIR30 OC515-525 White (OC515) or black (OC525) IR Console must be combined with OIR30 OIR30 Infrared remote control OPV50 Multitask additional card ONET Web server with Ethernet card for TCP/IP protocol OCB20 LON Converter OCB30 OTOUCH Touch screen supervision panel 39

Concealed FANCOIL UNIT WITHOUT CASING, FOR HEATING AND COOLING, 2 AND 4 PIPES, CAPACITY FROM 0,62 kw TO 13,26 kw. mod. CV mod. CV/AF CONCEALED FANCOIL UNITS mod. CH mod. CH/AF The CONCEALED fancoil is a unit which can be used for ductwork installations: it has very good performances also with medium/long ducts, thanks to its high pressure centrifugal fans; it is silent and can be equipped with a wide range of dedicated accessories. The CONCEALED fancoil is available for vertical installation on the wall (with bottom air intake) or on the floor (with frontal air intake) and horizontal on the ceiling (with back or bottom air intake). This fancoil is the ideal solution for the needs of small spaces and limited sizes that nowadays influences the choice of furniture in homes or offices. Available in 10 sizes, the CONCEALED model is equipped with an electric box containing the terminal board and auxiliary drain pan. The frame is made of galvanized steel and the inner sides are completely lined by an insulating self-extinguishing material. To complete this model Eurapo offers a wide range of accessories. The concealed fancoils are also available for District Cooling applications: the water coils are designed with a reduced number of circuits, suitable for functioning with high water temperature difference. 40

TECHNICAL DATA (3 rows, max speed-est) 512 514 516 520 522 524 528 Cooling Total cooling capacity [kw] 1,98 2,56 3,81 5,05 5,81 7,47 9,18 Air temperature 27 C d.b., 19 C w.b. Water temperature 7/12 C Sensible cooling capacity [kw] 1,65 2,12 3,14 4,13 4,80 6,09 7,51 Water flow [l/h] 340 439 654 867 997 1282 1575 Pressure drop [kpa] 9,6 6,5 14,6 16,9 22,2 16,8 31,3 Heating Heating capacity [kw] 2,79 3,69 4,13 6,86 7,97 10,03 12,35 Air temperature 20 C Inlet water temperature 50 C Water flow [l/h] Values as Cooling, accordingly to the EUROVENT Standards and UNI ENV 1397 Norm Pressure drop [kpa] 8,0 5,4 12,7 14,6 19,1 14,9 26,9 Heating Heating capacity [kw] 4,76 6,39 9,17 11,61 13,53 16,91 20,91 Air temperature 20 C Water temperature 70/60 C Water flow [l/h] 392 524 747 946 1102 1379 1731 Pressure drop [kpa] 13,8 7,3 15,8 16,6 22,2 16,4 30,8 Further data Air flow [m 3 /h] 456 575 793 1083 1306 1566 2040 Sound power level [db(a)] 55 59 57 57 62 63 69 Sound pressure level [db(a)] 45 49 57 47 52 53 59 Power input [W] 37 54 45 47 78 92 176 Absorbed current [A] 0,33 0,44 0,37 0,45 0,68 0,83 1,50 Water content [I] (2 pipes) 0,79 1,05 1,31 2,20 2,20 2,84 3,47 To obtain capacities for District Cooling solutions or for conditions different from standard ones, please use the EURAPO selection software. TECHNICAL DATA (3 rows, max speed-asynchronous) 110 112 114 216 218 220 222 224 226 328 Cooling Total cooling capacity [kw] 1,11 1,59 2,14 3,30 3,50 4,44 5,07 6,43 7,25 9,73 Air temperature 27 C d.b., 19 C w.b. Water temperature 7/12 C Sensible cooling capacity [kw] 0,93 1,25 1,90 2,46 3,06 3,53 4,42 5,06 5,70 8,04 Water flow [l/h] 199 281 414 577 614 777 891 1127 1271 1669 Pressure drop [kpa] 3,4 7,1 5,8 14,8 13,6 24,1 28,4 18,8 21,0 34,2 Heating Heating capacity [kw] 1,57 2,16 3,05 4,11 4,95 5,71 7,19 7,83 9,33 12,97 Air temperature 20 C Inlet water temperature 50 C Water flow [l/h] Values as Cooling, accordingly to the EUROVENT Standards and UNI ENV 1397 Norm Pressure drop [kpa] 2,7 6,1 4,8 11,9 12,5 20,0 23,5 15,5 20,5 30,4 Heating Heating capacity [kw] 2,77 3,70 5,25 6,96 8,43 9,64 12,18 13,30 15,82 22,00 Air temperature 20 C Water temperature 70/60 C Water flow [l/h] 246 265 393 524 601 691 835 1116 1303 1638 Pressure drop [kpa] 4,9 7,8 6,4 14,3 15,6 22,4 26,8 18,2 24,3 34,8 Further data Air flow [m 3 /h] 243 321 436 581 712 871 1081 1254 1481 2068 Sound power level [db(a)] 48 50 54 53 55 54 60 60 63 67 Sound pressure level [db(a)] 39 41 44 44 46 44 50 49 53 57 Power input [W] 46 48 57 61 76 90 117 140 162 222 Absorbed current [A] 0,23 0,23 0,26 0,29 0,33 0,38 0,52 0,65 0,65 1,06 Water content [I] (2 pipes) 0,53 0,79 1,05 1,31 1,57 2,20 2,20 2,84 2,84 3,47 To obtain capacities for District Cooling solutions or for conditions different from standard ones, please use the EURAPO selection software. 41

Concealed DIMENSIONS mod. CV/AF CONCEALED FANCOIL UNITS mod. CH 42

mod. CV Dimensions (mm) and weights CV - CV/AF - CH - CH/AF 110 112 114 216 218 220 222 224 226 328 EST - 512 514 516-520 522 524-528 CV - CH A 555 680 805 930 1055 1180 1180 1430 1430 1680 CV/AF - CH/AF A 574 699 824 949 1074 1199 1199 1449 1449 1699 mod. CV/AF CV - CV/AF - CH - CH/AF B 505 505 505 505 505 581 581 581 581 581 C 215 215 215 215 215 245 245 245 245 245 kg 10 13 16 19 22 29 31 38 38 42 Water connections - 1/2 G F mod. CH mod. CH/AF 43

EST TECHNOLOGY Concealed EST Brushless motor with inverter EDCR Remote microprocessor control for brushless motors OBV10 Omnibus card with Modbus for brushless motors ODC236 White Display Console on wall for brushless motors CONCEALED FANCOIL UNITS ODC235 White Display Console for brushless motors ODC245 Black Display Console for brushless motors ODC736 White Analogue Plus Console on wall for brushless motors ODC735-745 White (ODC735) or black (ODC745) Analogue Plus Console ODC336 White Display Console on wall with humidity sensor for brushless motors ODC335-345 White (ODC335) or black (ODC345) Display Console with humidity sensor for brushless motors 44

ACCESSORIES BA1 Additional heating coil for 4 pipe system BA41 Additional coil for 4R+1R configuration KREL Electric heater H3A2+DT Valve and shut-off valve PC Condensate pump TM Minimum water temperature thermostat CP CONCEALED Set of feet PAE/V Vertical external air intake with manual damper PAE/VM Vertical external air intake with motorized damper PAE/H Horizontal air mixing box with manual damper PAE/HM Horizontal air mixing box with motorized damper PAE/HAF Horizontal air intake for AF models PA Air suction plenum AFT Antifrost thermostat PAS Air suction plenum with round collars PA90 90 air suction plenum RCA Duct fitting PM Air delivery plenum with round collars PM90 90 air delivery plenum KIT 4 PIPES COMPACT Hydraulic kit 45

STANDARD CONTROLS Concealed CBL10 Transformer 230/24V CBL20 Master & Slave card CBL30 Master & Slave card for modulating valve AS Air sensor CONCEALED FANCOIL UNITS WS Water sensor CER00 Microprocessor control with thermostat, 3 speeds, Auto S/W switch TAD10 Room temperature thermostat, S/W switch CER10/B Microprocessor control as CER00 for modulating valves CSR00 Remote control panel 3 speeds CER20 Microprocessor control with thermostat, Auto speeds, Auto S/W switch CMR00 Room temperature thermostat, 3 speeds, S/W switch CER30/B Microprocessor control as CER20, for modulating valves CER31 Microprocessor control as CER30/B, power supply 24V 46

OMNIBUS CONTROLS OPV10 Omnibus card for BMS ONV10 Omnibus card not for BMS OC136 White Analogue Console on wall OC135-145 Analogue Console white (OC135) or black (OC145) OC736 White Analogue Plus Console on wall OC735-745 Analogue Plus Console white (OC735) or black (OC745) OC236 White Display Console on wall OC235-245 Display Console white (OC235) or black (OC245) OC436 White Manager Console on wall OC435-445 Manager Console white (OC435) or black (OC445) OC336 White Display Console on wall with humidity sensor OC335-345 White (OC335) or black (OC345) Display Console with humidity sensor OC516 White IR Console on wall must be combined with OIR30 OC515-525 White (OC515) or black (OC525) IR Console must be combined with OIR30 OIR30 Infrared remote control OPV50 Multitask additional card ONET Web server with Ethernet card for TCP/IP protocol OCB20 LON Converter OCB30 OTOUCH Touch screen supervision panel 47

EBH mod. EBH HIGH PRESSURE DUCTED UNIT, FOR HEATING AND COOLING, 2 AND 4 PIPES, CAPACITY FROM 2,50 kw TO 33,10 kw. DUCTED UNIT EBH high pressure ducted units, thanks to their high pressure fan decks, permit to satisfy every request of heating and cooling applications in big environments, where ducted air distribution is requested. They are suitable for horizontal installation. These are units for COOLING and HEATING applications; they are fed with cold and hot water and used according to their relevant performance features. EBH units are components of cooling and/or heating systems, designed for temperatures up to 100 C. When you want to connect this high pressure unit to a condensing unit in COOLING mode, it must be ordered with a direct expansion coil (optional upon request, except for sizes 060 070). The EBH high pressure ducted units are also available for District Cooling applications: the water coils are designed with a reduced number of circuits, suitable for functioning with high water temperature difference. 48

TECHNICAL DATA (4 rows, with external static pressure of 50 Pa, max speed-est) 020 030 040 050 060 Cooling Total cooling capacity [kw] 7,93 9,50 12,35 16,00 24,51 Air temperature 27 C d.b., 19 C w.b. Water temperature 7/12 C Sensible cooling capacity [kw] 6,12 7,65 10,12 14,32 19,36 Water flow [l/h] 1361 1630 2119 2746 4205 Pressure drop [kpa] 22,9 29,8 31,4 49,3 28,8 Heating Heating capacity [kw] 10,96 13,52 16,94 23,94 36,88 Air temperature 20 C Inlet water temperature 50 C Water flow [l/h] Values as Cooling, accordingly to the EUROVENT Standards and UNI ENV 1397 Norm Pressure drop [kpa] 18,0 27,3 57,6 95,6 30,5 Further data Air flow [m 3 /h] 1430 1981 2712 3772 4306 Sound pressure level [db(a)] 53 51 56 56 69 Power input [W] 185 232 296 617 762 Absorbed current [A] 1,38 1,04 1,32 2,74 3,37 Water content [I] 2,94 2,94 3,78 3,78 6,72 * Pressure level in open field at 1,5 m distance and reverberating time of 0,3 s. In order to select the EBH ducted fancoil with District Cooling coils, please use the EURAPO software for selection. TECHNICAL DATA (4 rows, with external static pressure of 50 Pa, max speed-asynchronous) 020 030 040 050 060 070* Cooling Total cooling capacity [kw] 6,95 9,49 12,17 14,34 23,69 29,07 Air temperature 27 C d.b., 19 C w.b. Water temperature 7/12 C Sensible cooling capacity [kw] 5,30 7,91 10,54 12,81 18,58 23,83 Water flow [l/h] 1192 1628 2088 2460 4064 4988 Pressure drop [kpa] 17,4 31,5 35,6 49,0 27,1 39,4 Heating Heating capacity [kw] 8,68 12,70 16,70 21,26 31,56 41,71 Air temperature 20 C Inlet water temperature 50 C Water flow [l/h] Values as Cooling, accordingly to the EUROVENT Standards and UNI ENV 1397 Norm Pressure drop [kpa] 16,3 28,0 31,7 45,0 23,8 37,6 Further data Air flow [m 3 /h] 1156 2092 2662 3189 4116 5552 Sound power level [db(a)] 64 66 68 70 76 79 Power input [W] 171 338 467 620 956 1701 Absorbed current [A] 0,75 1,55 2,08 2,84 4,47 7,64 Water content [I] 2,94 2,94 3,78 3,78 6,72 6,72 *Performances are out of scope Eurovent FCP. In order to select the EBH ducted fancoil with District Cooling coils, please use the EURAPO software for selection. 49

EBH DIMENSIONS mod. EBH G 350 A B I C 134 F 134 E 21 DUCTED UNITS H 78,2 200 OPTIONAL PLENUM Dimensions [mm] and weights [kg] EBH 91,5 31,5 D 020 030 040 050 060 070 A 990 990 1240 1240 1635 1635 B 902 902 902 902 1160 1160 C 408 408 408 408 518 518 D 927 927 1177 1177 1572 1572 E 366 366 366 366 476 476 F 634 634 634 634 892 892 G 963 963 1213 1213 1608 1608 H 307 307 300 300 311 311 I 404 404 404 404 514 514 Weights 64,3 64,3 79,3 79,3 126,0 126,0 Water connections G 1/2 F G 1/2 F G 1/2 F G 1/2 F G 1 M G 1 M Spigots 3 3 4 4 5 5 50

EST TECHNOLOGY EST Brushless motor with inverter EDCR Remote microprocessor control for brushless motors OBT10 Omnibus card with Modbus for brushless motors ODC236 White Display Console on wall for brushless motors ODC235 White Display Console for brushless motors ODC245 Black Display Console for brushless motors ODC736 White Analogue Plus Console on wall for brushless motors ODC735-745 White (ODC735) or black (ODC745) Analogue Plus Console ODC336 White Display Console on wall with humidity sensor for brushless motors ODC335-345 White (ODC335) or black (ODC345) Display Console with humidity sensor for brushless motors 51

EBH ACCESSORIES BA2 Additional coil 2R BA3 Additional coil 3R KREL Electric heater VALVE Valve kit DUCTED UNITS KPC Condensate pump KPM Air delivery plenum FILTER F5 Special filter KIT 4 PIPES COMPACT Hydraulic kit 52

STANDARD CONTROLS CBL10 Transformer 230/24V CBL20 Master & Slave card CBL30 Master & Slave card for modulating valve CSR00 Control panel 3 speeds CMR00 Room temperature thermostat, 3 speeds, S/W switch CER00 Microprocessor control with thermostat, 3 speeds, Auto S/W switch CER10/B Microprocessor control as CER00 for modulating valves CER20 Microprocessor control with thermostat, Auto speeds, Auto S/W switch CER30/B Microprocessor control as CER20, for modulating valves CER31 Microprocessor control as CER30 and power supply 24V TAD10 Microprocessor control as CER00 for modulating valves AS Air sensor WS Water sensor OMNIBUS CONTROLS OPT10 Omnibus card for BMS ONT10 Omnibus card not for BMS OC136 White Analogue Console on wall OC135-145 Analogue Console white (OC135) or black (OC145) OC736 White Analogue Plus Console on wall OC735-745 Analogue Plus Console white (OC735) or black (OC745) OC236 White Display Console on wall OC235-245 Display Console white (OC235) or black (OC245) OC436 White Manager Console on wall OC435-445 Manager Console white (OC435) or black (OC445) OC336 White Display Console on wall with humidity sensor OC335-345 White (OC335) or black (OC345) Display Console with humidity sensor OC516 White IR Console on wall must be combined with OIR30 OC515-525 White (OC515) or black (OC525) IR Console must be combined with OIR30 OIR30 Infrared remote control OCB30 OTOUCH Touch screen supervision panel OPT50 Multitask additional card ONET Web server with Ethernet card for TCP/IP protocol 53

DUCTED UNITS EDS HIGH PRESSURE DUCTED UNIT, FOR HEATING AND COOLING, DOUBLE SKIN PANELS, 2 PIPES, CAPACITY FROM 1,14 kw TO 27,96 kw. mod. EDS EDS high pressure ducted units, thanks to their high pressure fan decks, permit to satisfy every request of heating and cooling applications in big environments, where ducted air distribution is requested. They are suitable for horizontal installation. The double skin structure is composed by insulated 25 mm thick panels, colour RAL9002, and aluminium supporting frame. These are units for COOLING and HEATING applications and have been designed for temperatures up to 100 C. When you want to connect this high pressure unit to a condensing unit in COOLING mode, it must be ordered with a direct expansion coil (optional upon request, except for sizes 060 070). The EDS high pressure ducted units are also available for District Cooling applications: the water coils are designed with a reduced number of circuits, suitable for functioning with high water temperature difference. 54

TECHNICAL DATA (4 rows, with external static pressure of 50 Pa, max speed-est) 004 008 020 030 040 050 060 Cooling Total cooling capacity [kw] 3,45 5,25 7,49 8,77 9,86 12,21 22,47 Air temperature 27 C d.b., 19 C w.b. Water temperature 7/12 C Sensible cooling capacity [kw] 2,77 4,31 5,70 7,16 8,59 11,50 18,60 Water flow [l/h] 592 901 1285 1505 1692 2095 3855 Pressure drop [kpa] 9,8 7,4 17,8 27,2 29,6 36,8 24,6 Further data Air flow [m 3 /h] 624 1040 1554 2191 2611 3354 4769 Sound pressure level [db(a)]* 41 40 51 53 54 57 65 Power input [W] 60 114 186 279 275 488 870 Absorbed current [A] 0,53 0,95 1,38 1,24 1,23 2,18 3,83 Water content [I] 1,75 2,10 2,94 2,94 3,78 3,78 6,72 *Pressure level in open field at 1,5 m distance and reverberating time of 0,3 s. The EST-EDS ducted unit is available for cooling only. In order to select the EDS ducted fancoil with District Cooling coils, please use the EURAPO software for selection. TECHNICAL DATA (4 rows, with external static pressure of 50 Pa, max speed-asynchronous) 004 006 008 020 030 040 050 060 070 Cooling Total cooling capacity [kw] 2,42 3,26 4,50 6,94 8,79 10,00 11,62 21,02 24,68 Air temperature 27 C d.b., 19 C w.b. Water temperature 7/12 C Sensible cooling capacity [kw] 1,85 2,43 3,57 5,25 7,59 9,12 10,66 17,45 20,93 Water flow [l/h] 416 560 773 1191 1508 1716 1994 3607 4235 Pressure drop [kpa] 5,0 3,0 5,9 15,5 24,8 30,4 36,8 21,8 29,2 Heating Heating capacity [kw] 3,18 4,26 5,50 9,15 12,35 14,72 17,74 29,43 36,91 Air temperature 20 C Inlet water temperature 50 C Water flow [l/h] Values as Cooling, accordingly to the EUROVENT Standards and UNI ENV 1397 Norm Pressure drop [kpa] 3,5 2,7 5,1 9,5 21,6 27,3 33,8 19,2 17,9 Further data Air flow [m 3 /h] 401 596 794 1396 2347 2652 3356 4335 5496 Sound pressure level [db(a)]* 43 39 43 60 55 53 57 62 64 Power input [W] 59 79 97 183 358 406 623 1037 1784 Absorbed current [A] 0,26 0,35 0,42 0,79 1,65 1,79 2,90 4,79 7,85 Water content [I] 1,75 2,10 2,10 2,94 2,94 3,78 3,78 6,72 6,72 *Pressure level in open field at 1,5 m distance and reverberating time of 0,3 s. In order to select the EDS ducted fancoil with District Cooling coils, please use the EURAPO software for selection. 55

EDS DIMENSIONS mod. EDS DUCTED UNITS Dimensions [mm] and weights [kg] EDS 004 006 008 020 030 040 050 060 070 A 882 1007 1007 1132 1132 1382 1382 1777 1777 B 742 867 867 992 992 1242 1242 1637 1637 C 924 1049 1049 1174 1174 1424 1424 1819 1819 D 390 390 390 440 440 440 440 550 550 E 799 924 924 1049 1049 1299 1299 1694 1694 F 250 250 250 300 300 300 300 410 410 G 855 855 855 855 855 855 855 1030 1030 H 306 306 306 357 357 357 357 467 467 I 798 798 798 798 798 798 798 973 973 Weights 52,5 57,5 59,0 68,0 69,5 82,0 83,0 117,5 131,5 Water connections G 3/4 M G 3/4 M G 3/4 M G 3/4 M G 3/4 M G 3/4 M G 3/4 M G 1 M G 1 M 56

EST TECHNOLOGY EST Brushless motor with inverter EDCR Remote microprocessor control for brushless motors OBT10 Omnibus card with Modbus for brushless motors ODC236 White Display Console on wall for brushless motors ODC235 White Display Console for brushless motors ODC245 Black Display Console for brushless motors ODC736 White Analogue Plus Console on wall for brushless motors ODC735-745 White (ODC735) or black (ODC745) Analogue Plus Console ODC336 White Display Console on wall with humidity sensor for brushless motors ODC335-345 White (ODC335) or black (ODC345) Display Console with humidity sensor for brushless motors 57

EDS ACCESSORIES VALVE Valve kit KPC Condensate pump FILTER F5 Special filter KREL Electric heater DUCTED UNITS KPM Air delivery plenum KIT 4 PIPES COMPACT Hydraulic kit 58

STANDARD CONTROLS CBL10 Transformer 230/24V CBL20 Master & Slave card CBL30 Master & Slave card for modulating valve CSR00 Control panel 3 speeds CMR00 Room temperature thermostat, 3 speeds, S/W switch CER00 Microprocessor control with thermostat, 3 speeds, Auto S/W switch CER10/B Microprocessor control as CER00 for modulating valves CER20 Microprocessor control with thermostat, Auto speeds, Auto S/W switch CER30/B Microprocessor control as CER20, for modulating valves CER31 Microprocessor control as CER30 and power supply 24V TAD10 Microprocessor control as CER00 for modulating valves AS Air sensor WS Water sensor OMNIBUS CONTROLS OPT10 Omnibus card for BMS ONT10 Omnibus card not for BMS OC136 White Analogue Console on wall OC135-145 Analogue Console white (OC135) or black (OC145) OC736 White Analogue Plus Console on wall OC735-745 Analogue Plus Console white (OC735) or black (OC745) OC236 White Display Console on wall OC235-245 Display Console white (OC235) or black (OC245) OC436 White Manager Console on wall OC435-445 Manager Console white (OC435) or black (OC445) OC336 White Display Console on wall with humidity sensor OC335-345 White (OC335) or black (OC345) Display Console with humidity sensor OC516 White IR Console on wall must be combined with OIR30 OC515-525 White (OC515) or black (OC525) IR Console must be combined with OIR30 OIR30 Infrared remote control OCB30 OTOUCH Touch screen supervision panel OPT50 Multitask additional card ONET Web server with Ethernet card for TCP/IP protocol 59

UCS600 UCS/M 600 CASSETTE UNITS, FOR HEATING AND COOLING, 2 AND 4 PIPES, CAPACITY FROM 1,39 kw TO 4,89 kw. CASSETTE UNITS EURAPO has designed a new range of hydronic cassette units thanks to the recent investments in the new technical laboratories. The new UCS600 series has been planned in accordance with quality standards that characterize the complete EURAPO production since years and it is distinguished by an increased capacity with a low noise level, by a further improvement in the quality of the components, by a new design of the air intake/air supply grilles that also improves air distribution. Power consumption is reduced by more than 50% in the EST version and thanks to the new production process, UCS600 can deeply penetrate the market with extremely aggressive and competitive prices. Available in 6 models, the UCS600 overall dimensions allow an easy installation in modular false ceilings (600x600), while the hydraulic and electrical connections, located on the same side, facilitate the maintenance operations. The UCS/M 600 presents all the new features of the basic model UCS600 and is characterized by the microdrilled air intake grill and its air diffusion frame entirely realized in painted metal sheet, perfectly adaptable to modular false ceilings. The unit in basic configuration is equipped with a condensate pump, and it is pre-arranged for the connection to an additional air outlet duct and/or to an external air intake. The air intake/outlet grilles are designed in order to avoid that people are directly invested by the air flow (thanks to the Coanda effect), by reaching the maximum levels of comfort. The CASSETTE unit can be managed by the complete range of EURAPO regulators: from the standard electromechanical and microprocessor controls to the digital controls (OMNIBUS), compatible to BMS Systems. 60

TECHNICAL DATA (max speed-est) 2 pipes 4 pipes Cooling Air temperature 27 C d.b., 19 C w.b. Water temperature 7/12 C Heating 2 pipes Air temperature 20 C Inlet water temperature 50 C Heating Air temperature 20 C Water temperature 70/60 C Further data 621 622 641 642 Total cooling capacity [kw] 2,85 4,85 1,87 3,94 Sensible cooling capacity [kw] 2,42 3,64 1,68 3,08 Water flow [l/h] 494 841 327 686 Pressure drop [kpa] 9,2 17,2 7,9 17,0 Heating capacity [kw] 3,66 6,00 - - Water flow [l/h] Values as Cooling, accordingly to the EUROVENT Standards and UNI ENV 1397 Norm Pressure drop [kpa] 7,7 14,9 - - Heating capacity [kw] 6,03 9,81 2,59 3,86 Water flow [l/h] 539 855 222 332 Pressure drop [kpa] 9,2 15,7 8,9 19,6 Air flow [m 3 /h] 605 733 605 733 Sound power level [db(a)] 54 58 54 58 Sound pressure level [db(a)] 45 49 45 49 Power input [W] 27 42 27 43 Absorbed current [A] 0,24 0,38 0,24 0,38 Water content [l] 1,34 2,12 1,34 2,12 (0,3) (0,3) TECHNICAL DATA (max speed-asynchronous) 2 pipes 4 pipes Cooling Air temperature 27 C d.b., 19 C w.b. Water temperature 7/12 C Heating 2 pipes Air temperature 20 C Inlet water temperature 50 C Heating Air temperature 20 C Water temperature 70/60 C Further data 621 622 623 641 642 643 Total cooling capacity [kw] 2,52 3,67 4,72 1,76 3,11 3,88 Sensible cooling capacity [kw] 2,12 2,79 3,70 1,62 2,49 3,24 Water flow [l/h] 444 642 827 311 544 683 Pressure drop [kpa] 7,8 10,9 16,5 7,5 11,2 16,7 Heating capacity [kw] 2,74 4,50 7,00 - - - Water flow [l/h] Values as Cooling, accordingly to the EUROVENT Standards and UNI ENV 1397 Norm Pressure drop [kpa] 7,0 8,5 6,4 - - - Heating capacity [kw] 4,54 7,34 11,44 2,33 3,13 3,83 Water flow [l/h] 486 645 839 201 269 330 Pressure drop [kpa] 8,5 8,7 6,7 7,2 13,1 18,9 Air flow [m 3 /h] 495 495 717 495 495 717 Sound power level [db(a)] 49 49 58 49 49 58 Sound pressure level [db(a)] 40 40 49 40 40 49 Power input [W] 53 52 85 53 52 86 Absorbed current [A] 0,25 0,24 0,36 0,25 0,24 0,38 Water content [l] 1,34 2,12 2,12 1,34 2,12 2,12 (0,3) (0,3) (0,3) 61

UCS600 UCS/M 600 DIMENSIONS UCS 600 Electric box 2 pipe system 1 Water Inlet 3/4 F 2 Water outlet 3/4 F 4 pipe system 1 Inlet cooling water 3/4 F 2 Outlet cooling water 3/4 F 3 Inlet heating water 1/2 F 4 Outlet heating water 1/2 F Condensate drain hose Dimensions (mm) and weights UCS600 A 615 B 312 C 575 D 70 Kg 30 62

UCS/M 600 Electric box 2 pipe system 1 Water Inlet 3/4 F 2 Water outlet 3/4 F 4 pipe system 1 Inlet cooling water 3/4 F 2 Outlet cooling water 3/4 F 3 Inlet heating water 1/2 F 4 Outlet heating water 1/2 F Condensate drain hose Dimensions (mm) and weights UCS/M 600 A 615 B 312 C 575 D 70 Kg 30 63

UCS600 UCS/M 600 EST TECHNOLOGY EST Brushless motor with inverter EDCR Remote microprocessor control for brushless motors OBU10 Omnibus card with Modbus for brushless motors ODC236 White Display Console on wall for brushless motors CASSETTE UNITS ODC235 White Display Console for brushless motors ODC245 Black Display Console for brushless motors ODC336 White Display Console on wall with humidity sensor for brushless motors ODC335 White Display Console with humidity sensor for brushless motors ODC345 Black Display Console with humidity sensor for brushless motors ODC736 White Analogue Plus Console on wall for brushless motors ODC735-745 White (ODC735) or black (ODC745) Analogue Plus Console 64

ACCESSORIES KREL Electric heater VALVES Valves and shut-off valves EXTRA RAL Special painting KIT 4 PIPES COMPACT Hydraulic kit KMC600 Casing (available for UCS/M 600) 65

UCS600 UCS/M 600 STANDARD CONTROLS CSR00 Remote control panel 3 speeds CMR00 Room temperature thermostat, 3 speeds, S/W switch CER00 Microprocessor control with thermostat, 3 speeds, Auto S/W switch CER10/B Microprocessor control as CER00 for modulating valves CER20 Microprocessor control with thermostat, Auto speeds, Auto S/W switch CER30/B Microprocessor control as CER20, for modulating valves CER31 Microprocessor control as CER30/B, power supply 24V TAD10 Room temperature thermostat, S/W switch CASSETTE UNITS AS Air sensor WS Water sensor QEC10 Transformer 230/24V QEC20 Master & Slave card QEC30 Master & Slave card for modulating valve 66

OMNIBUS CONTROLS OPU10 Omnibus card for BMS ONU10 Omnibus card not for BMS OPU11-OC514 Omnibus card for BMS + Infrared Receiver ONU11-OC514 Omnibus card + Infrared Receiver OC136 White Analogue Console on wall OC135-145 White (OC135) or black (OC145) Analogue Console OC736 White Analogue Plus Console on wall OC735-745 White (OC735) or black (OC745) Analogue Plus Console OC236 White Display Console on wall OC235-245 White (OC235) or black (OC245) Display Console OC436 White Manager Console on wall OC435-445 White (OC235) or black (OC245) Manager Console OC516 White IR Console on wall - must be combined with OIR30 OC515-525 Withe (OC515) or black (OC525) IR Console on wall - must be combined with OIR30 OC336 White Display Console on wall with humidity sensor OC335-345 White (OC335) or black (OC345) Display Console on wall with humidity sensor OIR30 Infrared remote control OPU50 Multitask card ONET Web server with Ethernet card for TCP/IP protocol OCB20 LON converter OCB30 OTOUCH Touch Screen supervision panel 67

UCS/H 600 CASSETTE UNIT WITHOUT CONDENSATE PUMP, FOR HEATING AND COOLING, 2 AND 4 PIPES, CAPACITY FROM 1,39 kw TO 4,89 kw. CASSETTE UNITS UCS/H 600 cassette unit has been designed to allow a natural condensate water discharge, for gravity; in this way, condensate pump is not necessary. UCS/H 600 unit is particularly indicated when reduced maintenance operations are required, for safety or sanitary locations (banks, police stations, hospitals, sanitary rooms), or if very low sound levels are tolerated. Similarly to the standard UCS600 models, the grill has been designed to obtain the Coanda effect, that guarantees an uniform and pleasant air diffusion, avoiding that people are directly invested by outgoing air flow. The absence of the condensate pump allows a greater silence, reduced electric consumptions and limited maintenance operations. The accessories range has been implemented with the new antiallergic F7 filter, with a very high filtration capacity, which ensures purification and air quality improvement by filtering pollen particles and powders having dimensions less than 0,4 microns. The F7 filter can be combined with a pressure switch that highlights the filter clogging, warning of the need to replace the filter, in order to keep its characteristics unchanged and to avoid to affect the air flow of the unit. 68

TECHNICAL DATA (max speed-est) 2 pipes 4 pipes Cooling Air temperature 27 C d.b., 19 C w.b. Water temperature 7/12 C Heating 2 pipes Air temperature 20 C Inlet water temperature 50 C Heating Air temperature 20 C Water temperature 70/60 C Further data 621 622 641 642 Total cooling capacity [kw] 2,85 4,85 1,87 3,94 Sensible cooling capacity [kw] 2,42 3,64 1,68 3,08 Water flow [l/h] 494 841 327 686 Pressure drop [kpa] 9,2 17,2 7,9 17,0 Heating capacity [kw] 3,66 6,00 - - Water flow [l/h] Values as Cooling, accordingly to the EUROVENT Standards and UNI ENV 1397 Norm Pressure drop [kpa] 7,7 14,9 - - Heating capacity [kw] 6,03 9,81 2,59 3,86 Water flow [l/h] 539 855 222 332 Pressure drop [kpa] 9,2 15,7 8,9 19,6 Air flow [m 3 /h] 605 733 605 733 Sound power level [db(a)] 54 58 54 58 Sound pressure level [db(a)] 45 49 45 49 Power input [W] 27 42 27 43 Absorbed current [A] 0,24 0,38 0,24 0,38 Water content [l] 1,34 2,12 1,34 2,12 (0,3) (0,3) In order to select the cassette UCS/H in presence of the F7 filter, please use the EURAPO selection software. TECHNICAL DATA (max speed-asynchronous) 2 pipes 4 pipes Cooling Air temperature 27 C d.b., 19 C w.b. Water temperature 7/12 C Heating 2 pipes Air temperature 20 C Inlet water temperature 50 C Heating Air temperature 20 C Water temperature 70/60 C Further data 621 622 623 641 642 643 Total cooling capacity [kw] 2,52 3,67 4,72 1,76 3,11 3,88 Sensible cooling capacity [kw] 2,12 2,79 3,70 1,62 2,49 3,24 Water flow [l/h] 444 642 827 311 544 683 Pressure drop [kpa] 7,8 10,9 16,5 7,5 11,2 16,7 Heating capacity [kw] 2,74 4,50 7,00 - - - Water flow [l/h] Values as Cooling, accordingly to the EUROVENT Standards and UNI ENV 1397 Norm Pressure drop [kpa] 7,0 8,5 6,4 - - - Heating capacity [kw] 4,54 7,34 11,44 2,33 3,13 3,83 Water flow [l/h] 486 645 839 201 269 330 Pressure drop [kpa] 8,5 8,7 6,7 7,2 13,1 18,9 Air flow [m 3 /h] 495 495 717 495 495 717 Sound power level [db(a)] 49 49 58 49 49 58 Sound pressure level [db(a)] 40 40 49 40 40 49 Power input [W] 53 52 85 53 52 86 Absorbed current [A] 0,25 0,24 0,36 0,25 0,24 0,38 Water content [l] 1,34 2,12 2,12 1,34 2,12 2,12 (0,3) (0,3) (0,3) In order to select the cassette UCS/H in presence of the F7 filter, please use the EURAPO selection software. 69

UCS/H 600 DIMENSIONS CASSETTE UNITS Electric box Water drain hose 70

2 pipe system 1 Inlet water 3/4 F 2 Outlet water 3/4 F 4 pipe system 1 Inlet cooling water 3/4 F 2 Outlet cooling water 3/4 F Dimensions (mm) and weights UCS/H 600 A 615 B 507 C 575 D 70 kg 39 3 Inlet heating water 1/2 F 4 Outlet cooling water 1/2 F 71

UCS/H 600 EST TECHNOLOGY EST Brushless motor with inverter EDCR Remote microprocessor control for brushless motors OBU10 Omnibus card with Modbus for brushless motors ODC236 White Display Console on wall for brushless motors CASSETTE UNITS ODC235 White Display Console for brushless motors ODC245 Black Display Console for brushless motors ODC336 White Display Console on wall with humidity sensor for brushless motors ODC335 White Display Console with humidity sensor for brushless motors ODC345 Black Display Console with humidity sensor for brushless motors ODC736 White Analogue Plus Console on wall for brushless motors ODC735-745 White (ODC735) or black (ODC745) Analogue Plus Console 72

ACCESSORIES UCS/HM 600 Metallic grill F7 Filter (UCS/HM 600) Filter with F7 filtration grade Pressure switch (UCS/HM 600) Pressure regulator VALVES Valves and shut-off valves EXTRA RAL Special paintings KIT 4 PIPES COMPACT Hydraulic kit 73

UCS/H 600 STANDARD CONTROLS CSR00 Remote control panel 3 speeds CMR00 Room temperature thermostat, 3 speeds, S/W switch CER00 Microprocessor control with thermostat, 3 speeds, Auto S/W switch CER10/B Microprocessor control as CER00 for modulating valves CER20 Microprocessor control with thermostat, Auto speeds, Auto S/W switch CER30/B Microprocessor control as CER20, for modulating valves CER31 Microprocessor control as CER30/B, power supply 24V TAD10 Room temperature thermostat, S/W switch CASSETTE UNITS AS Air sensor WS Water sensor QEC10 Transformer 230/24V QEC20 Master & Slave card QEC30 Master & Slave card for modulating valve 74

OMNIBUS CONTROLS OPU10 Omnibus card for BMS ONU10 Omnibus card not for BMS OPU11-OC514 Omnibus card for BMS + Infrared Receiver ONU11-OC514 Omnibus card + Infrared Receiver OC136 White Analogue Console on wall OC135-145 White (OC135) or black (OC145) Analogue Console OC736 White Analogue Plus Console on wall OC735-745 White (OC735) or black (OC745) Analogue Plus Console OC236 White Display Console on wall OC235-245 White (OC235) or black (OC245) Display Console OC436 White Manager Console on wall OC435-445 White (OC235) or black (OC245) Manager Console OC516 White IR Console on wall - must be combined with OIR30 OC515-525 Withe (OC515) or black (OC525) IR Console on wall - must be combined with OIR30 OC336 White Display Console on wall with humidity sensor OC335-345 White (OC335) or black (OC345) Display Console on wall with humidity sensor OIR30 Infrared remote control OPU50 Multitask card ONET Web server with Ethernet card for TCP/IP protocol OCB20 LON converter OCB30 OTOUCH Touch screen supervision panel 75

UCS900 CASSETTE UNIT 900X900 mm FOR HEATING AND COOLING, 2 AND 4 PIPES, CAPACITY FROM 3,9 kw TO 10,15 kw CASSETTE UNITS With an innovative, essential and clean design, which fits in every kind of environment, the UCS900 water cassette unit is the result of the stylist research to present an innovative product in terms of performance, low sound level, comfort and regulation flexibility. The aesthetics of this unit is accurate in every detail, planned in accordance with the EURAPO experience, appreciated by architects and designers from all over the world. The UCS900 water cassette unit can be used for heating and cooling applications, it has been designed to fit into modular or not modular false ceilings, in 2 and 4 pipe systems. The 900x900mm dimension of the cassette unit permits to satisfy the cooling demand of ambient having quite big volumes. The UCS900 units in basic configuration are equipped with a condensate pump and they are pre-arranged for the connection to an additional air outlet duct and/or to an external air intake, by using the specific collars, supplied as standard in a kit. The particular shape of the air outlet plenum is designed specifically in order to obtain the Coanda effect, a phenomenon for which the air outlet flow tends to adhere to the ceiling and falls down smoothly, without blowing directly towards people in the room: the optimal solution for an uniform and pleasant air diffusion. The UCS900 cassette unit can be managed by the complete range of EURAPO regulators: from the standard electro-mechanical and microprocessor controls to the digital controls, compatible to BMS Systems. 76

TECHNICAL DATA (max speed-est) 2 pipes 4 pipes Cooling Air temperature 27 C d.b., 19 C w.b. Water temperature 7/12 C Heating 2 pipes Air temperature 20 C Inlet water temperature 50 C Heating Air temperature 20 C Water temperature 70/60 C Further data 922 942 Total cooling capacity [kw] 9,60 8,88 Sensible cooling capacity [kw] 7,10 6,80 Water flow [l/h] 1672 1548 Pressure drop [kpa] 22,5 30,0 Heating capacity [kw] 11,20 - Water flow [l/h] Values as Cooling, accordingly to the EUROVENT Standards and UNI ENV 1397 Norm Pressure drop [kpa] 19,5 - Heating capacity [kw] 20,52 8,74 Water flow [l/h] 1910 752 Pressure drop [kpa] 24,1 39,4 Air flow [m 3 /h] 1454 1454 Sound power level [db(a)] 61 61 Sound pressure level [db(a)] 51 51 Power input [W] 119 119 Absorbed current [A] 0,94 0,94 Water content [l] 4,22 4,26 (0,6) TECHNICAL DATA (max speed-asynchronous) 2 pipes 4 pipes Cooling Air temperature 27 C d.b., 19 C w.b. Water temperature 7/12 C Heating 2 pipes Air temperature 20 C Inlet water temperature 50 C Heating Air temperature 20 C Water temperature 70/60 C Further data 921 922 941 942 Total cooling capacity [kw] 8,63 9,99 7,49 9,04 Sensible cooling capacity [kw] 6,10 7,64 5,98 7,46 Water flow [l/h] 1503 1742 1307 1579 Pressure drop [kpa] 20,1 26,0 23,2 32,0 Heating capacity [kw] 10,40 11,74 - - Water flow [l/h] Values as Cooling, accordingly to the EUROVENT Standards and UNI ENV 1397 Norm Pressure drop [kpa] 18,9 22,0 - - Heating capacity [kw] 17,54 19,82 7,53 8,86 Water flow [l/h] 1609 1873 661 778 Pressure drop [kpa] 20,5 24,0 30,8 40,9 Air flow [m 3 /h] 1240 1588 1240 1558 Sound power level [db(a)] 54 61 54 63 Sound pressure level [db(a)] 44 51 44 53 Power input [W] 129 161 127 161 Absorbed current [A] 0,62 0,78 0,60 0,78 Water content [l] 4,22 4,22 4,26 4,26 (0,6) (0,6) 77

UCS900 DIMENSIONS CASSETTE UNITS Electric box Condensate drain hose 78

2 pipe system 1 Inlet water 3/4 F 2 Outlet water 3/4 F 4 pipe system 1 Inlet cooling water 3/4 F 2 Outlet cooling water 3/4 F Dimensions (mm) and weights UCS900 A 985 B 360 C 820 D 75 kg 45 3 Inlet heating water 1/2 F 4 Outlet heating water 1/2 F 79

UCS900 EST TECHNOLOGY EST Brushless motor with inverter EDCR Remote microprocessor control for brushless motors OBU10 Omnibus card with Modbus for brushless motors ODC236 White Display Console on wall for brushless motors CASSETTE UNITS ODC235 White Display Console for brushless motors ODC245 Black Display Console for brushless motors ODC336 White Display Console on wall with humidity sensor for brushless motors ODC335 White Display Console with humidity sensor for brushless motors ODC345 Black Display Console with humidity sensor for brushless motors ODC736 White Analogue Plus Console on wall for brushless motors ODC735-745 White (ODC735) or black (ODC745) Analogue Plus Console 80

ACCESSORIES KREL Electric heater KIT 4 PIPES COMPACT Hydraulic kit VALVE Valve and shut-off valve EXTRA RAL Special painting 81

UCS900 STANDARD CONTROLS CSR00 Remote control panel 3 speeds CMR00 Room temperature thermostat, 3 speeds, S/W switch CER00 Microprocessor control with thermostat, 3 speeds, Auto S/W switch CER10/B Microprocessor control as CER00 for modulating valves CER20 Microprocessor control with thermostat, Auto speeds, Auto S/W switch CER30/B Microprocessor control as CER20, for modulating valves CER31 Microprocessor control as CER30/B, power supply 24V TAD10 Room temperature thermostat, S/W switch CASSETTE UNITS AS Air sensor WS Water sensor QEC10 Transformer 230/24V QEC20 Master & Slave card QEC30 Master & Slave card for modulating valve 82

OMNIBUS CONTROLS OPU10 Omnibus card for BMS ONU10 Omnibus card not for BMS OPU11-OC514 Omnibus card for BMS + Infrared Receiver ONU11-OC514 Omnibus card + Infrared Receiver OC136 White Analogue Console on wall OC135-145 White (OC135) or black (OC145) Analogue Console OC736 White Analogue Plus Console on wall OC735-745 White (OC735) or black (OC745) Analogue Plus Console OC236 White Display Console on wall OC235-245 White (OC235) or black (OC245) Display Console OC436 White Manager Console on wall OC435-445 White (OC235) or black (OC245) Manager Console OC516 White IR Console on wall - must be combined with OIR30 OC515-525 Withe (OC515) or black (OC525) IR Console on wall - must be combined with OIR30 OC336 White Display Console on wall with humidity sensor OC335-345 White (OC335) or black (OC345) Display Console on wall with humidity sensor OIR30 Infrared remote control OPU50 Multitask card ONET Web server with Ethernet card for TCP/IP protocol OCB20 LON converter OCB30 OTOUCH Touch Screen supervision panel 83

EST EST (Energy Saving Technology) is applied to the EURAPO fan coil units and cassette units. It permits to obtain extremely low electrical absorption and a continuous modulation of the air flow, constantly related to the concrete need of energy in the room. EST technology is composed by a brushless motor combined to a dedicated electronic device (inverter), managed by specific regulators developed by EURAPO. In comparison to the traditional units equipped with asynchronous three-speed-motors, the fan coil and cassette units with brushless motors can obtain a considerable energy saving, by reducing the power consumption up to 70%. 80% 70% W speed 1 60% speed 2 50% speed 3 EST 40% 30% 20% speed 5 speed 6 speed 4 10% 0% m 3 /h m 3 /h 6 5 speed 4 speed 3 speed 2 speed 1 Asynchronous fan coil absorption (W) Energy saving with EST fancoil EST fan coil absorption EST (W) Thanks to the step-less modulation of the fan speeds it is possible to accurately regulate the air volume in a very precise way, in strict relation to the real need of air conditioning in the room. Oscillations in the temperature and relative humidity are reduced at lowest level: a guarantee for the highest comfort in the room. The possibility to reach very low air volumes makes the units extremely quiet at the lowest motor revolutions. EST technology is designed in particular for offices, hospitals, nursing homes and hotels. It is available for the EURAPO range of fan coil units, cassette units and ducted units. The EST technology consists of a brushless motor combined to a dedicated electronic device (inverter), managed by specific regulators. The controller uses a modulating signal with 0-10Vdc tension in order to regulate the fan speed. The brushless electric motor is composed by a rotor having permanent magnets, whose magnetic fields interact with the ones produced by the stator winding. The transfer of current is no longer by mechanical commutation (sliding contacts) but by an electronic commutation system: an electronic controller (inverter) powers the motor s stator and generates rotating magnetic fields, that determine the rotor s speed. 84

For applying the EST technology also to the ducted units, the inverter is provided with DIP SWITCHES that can be also set on site, during start-up of the unit. This high flexibility grants the proper configuration for every kind of installation, by personalization of the Dip Switches accordingly to the pressure drop in the system. Brushless motors develop much less heat than the traditional brushed motors and they have much lower mechanical resistance than the standard asynchronous ones. They offer several advantages, like as higher efficiency, longer lifetime, less need of maintenance. The absence of brushes eliminates also the main source of electromagnetic noise. By giving a 0-10Vdc signal to the inverter, an electronic regulator intervenes by simply managing the fan speed and the rotor s torque in a continuous way, adapting with extreme precision the air volume to the real and punctual requirements in the room. For managing all units equipped with brushless motors, EURAPO developed a new microprocessor control, available both built-in the unit (EDCL) and for remote installation on the wall (EDCR). Also the OMNIBUS digital system has been implemented in order to be combined to the EST technology: the new cards for fan coil units (OBV10) and for cassette units (OBU10) can be connected to the new OMNIBUS consoles, designed for managing fan coil and cassette units with brushless motors. The consoles are available for on-wall installation (ODC236), fitted in the fan coil unit or for built-in the wall installation, on 503 modules (ODC235 white colour and ODC245 black colour). OMNIBUS regulators give the possibility to fully control the fan speed (0-100%) and/or to manually select three fan steps (high, med and low speed): it is actually possible to set in every moment and very easily the three different levels of motor s rotation, in order to fulfil specific thermal or acoustical requirements. FEATURES 0-10Vdc control signal Low mechanical resistance and low overheating Wide range of fan speed regulation, especially at the lowest revolutions Continuous regulation of the fan speeds (0-100%) Possibility to manually set the desired three fan steps (by using OMNIBUS regulators) Available for Sphera, Sigma, Prisma, Low Body, Concealed fancoil units, UCS600, UCS/M 600, UCS/H 600 cassette units, EBH and EDS ducted units ADVANTAGES Energy saving: electrical absorption reduced up to 70% Higher efficiency: possibility to adapt the air volume and the capacities accordingly to the real room loads Higher comfort: reduced oscillation of the temperature and relative humidity in the room Extremely quiet functioning of the unit, thanks to the operation at low revolutions Reduced wearing and higher reliability Longer expected lifetime of the motor 85

OMNIBUS Yet designing and producing air conditioning systems comprising selected, reliable components is not sufficient in itself to guarantee high standards of air-conditioned comfort, these also need to be integrated and harmonised with the intelligence controlling them. OMNIBUS Only the complete synergy between terminal unit performance and heat regulating devices can guarantee optimum results and meet the most modern requirements in comfort management simply and efficiently. The EURAPO-OMNIBUS Digital System is designed to fully regulate the water terminal units (such as fan coil units, water cassette units, high pressure ducted fan coil units and radiant systems) for domestic use, residential buildings and public rooms. This controller permits to be easily programmed by the installing company and configured accordingly to each particular type of system. Elegant design LCD Display Touch screen Humidity sensor Plug & Play connections Weekly, daily and monthly programs Scenarios configuration Compatible with brushless and inverter technology Flexible configuration Service tool available MODBUS RTU: free protocol ETHERNET (TCP/IP) compability LONWORKS compatibility Different access levels to the Building Management System 86

APPLICATIONS Fan coil units Hydronic cassettes Ducted units Radiant systems Dehumidificators Heat recovery units Mechanically controlled ventilation systems (VMC) Chilled beams 87

OMNIBUS COMPONENTS Main card without modbus Main card with modbus Multitask card Analogue Console, for built-in application and remote installation either on wall or concealed on 503 module OMNIBUS Analogue Plus Console, for builtin application and remote installation either on wall or concealed on 503 module Display Console for built-in application and remote installation either on wall or concealed on 503 module Display Console with humidity sensor for remote installation either on wall or concealed on 503 module Infrared Console for installation on the unit, for wall installation or built-in the wall installation, on 503 module Main card with modbus for EST brushless units Display Console, for built-in application and remote installation either on wall or concealed on 503 module, for EST brushless units Display Console with humidity sensor, for remote installation either on wall concealed on 503 module, for EST brushless units Analogue Plus Console, for builtin application and remote installation either on wall or concealed on 503 module, for EST brushless units 88

SUPERVISION FOR SMALL SYSTEMS (recommended up to 10 units) Modbus/RTU protocol Different access levels (user/supervisor/service) Direct configuration of connected units Centralized operations Set-up parameters configuration INPUT/OUTPUT status monitoring Daily and weekly program Alarms management Console Manager FOR MEDIUM SYSTEMS (recommended up to 100 units) Same features as Console Manager, plus... OTOUCH 7 inches touch screen Optional modem for remote management via GSM LAN interface with TCP/IP protocol Suitable for the most common web browsers Remote management via Internet Boiler room management (pumps, boiler, heat pump) Boost function for a period set by the user Scenarios management Multilanguage FOR LARGE SYSTEMS (recommended up to 480 units) WEBSERVER with built-in Ethernet card Modbus/RTU protocol Different access levels (user/supervisor/service) Centralized operations Set-up parameters configuration INPUT/OUTPUT status monitoring Daily, weekly and special events program Suitable for connecting up to 2 lines of 240 units each. Boost function for a period set by the user LAN interface with TCP/IP protocol. Suitable for the most common web browsers. Remote management via Internet. 89

OTOUCH OTOUCH is a control and supervision system developed by Eurapo Laboratories in order to manage residential comfort. This high tech solution is matched with an easy-to-use graphical interface, which has been designed in cooperation with Udine University in order to guarantee an intuitive and simply comfort control. OTOUCH OTOUCH can functionally fully control air condition system devices (such as fan coils units) or radiant system ones (such as hydraulic actuators or dehumidifiers) or even both at the same time, following an innovative idea of control philosophy. Its distinctive feature consists of including monitoring and controlling functions of fan coils units added to capacity of interacting and integrating different HVAC system devices in the same control panel. OTOUCH can control: Cooling and heating units (chillers/boilers) HVAC system pumps Mixing valves (for radiant systems) Thermal zone valves Dehumidifiers Fan coil units 90

The system consists of two different applications: OTOUCH-CLIMA for the management of the air-conditioning system, the time programming, controlling individual instruments or groups, etc. OTOUCH-SERVICE contains the procedure for creating the system and for the maintenance operations Both applications are easily accessible by the most common web browsers: it is possible to fully manage, supervise, start-up and maintain the system by any terminal connected to the network, including smartphones, tablets and PCs. OTouch-Clima Visualization and management of individual units or groups OTouch-Clima Daily or weekly time scheduling OTouch-Service Installation and diagnostic tool on PC OTouch-Service Installation and diagnostic tool on tablet 91

92 NOTES

93

94

All the information contained in this manual cannot be reproduced in any form or electronic/mechanic way, without the permission of Eurapo S.r.l. Programs and technologies are always improving. Therefore descriptions, data and images must be intended as merely indicative and can be modified without any notice.

www.eurovent-certification.com www.certiflash.com novembre 6CG0002-2013 EN1601