Two Stage Indirect/Direct Evaporative Cooling

Similar documents
INTERNATIONAL JOURNAL OF APPLIED ENGINEERING RESEARCH, DINDIGUL Volume 1, No 4, 2011

PERFORMANCE EVALUATION OF TWO STAGE AIR COOLER IN DIFFERENT SPEED

Keywords : Evaporative cooling, Saturation efficiency, Cooling capacity, Cooling pad, Cellulose, Aspen, Coconut coir. IJSER

ME Mechanical Engineering Systems Laboratory. Experiment 3 - Mass and Energy Balances in Psychrometric Processes

ME 410 MECHANICAL ENGINEERING SYSTEMS LABORATORY MASS & ENERGY BALANCES IN PSYCHROMETRIC PROCESSES EXPERIMENT 3

Theoretical Performance Analysis Of Direct Evaporative Cooler In Hot And Dry Climates

s. Properties for R134a are as follows : Saturated R-134a Superheated R-134a

Reducing energy consumption of airconditioning systems in moderate climates by applying indirect evaporative cooling

Design and Development of Combined Direct and Indirect Evaporative Cooling System

ME 410 MECHA ICAL E GI EERI G SYSTEMS LABORATORY

Investigation of an evaporative air cooler using solar energy under Algerian climate

Experimental study of air evaporative cooling process using microporous membranes

Design Procedure for a Liquid Dessicant and Evaporative Cooling Assisted 100% Outdoor Air System

TECHNICAL NOTE ON EVAPORATIVE COOLING. Renato Lazzarin, President of the IIR s Commission E1

EXPERIMENTAL INVESTIGATION OF COMPARISION OF AIR COOLED AND WATER COOLED CONDENSER ATTACHED WITH COOLING TOWER

SIDDHARTH GROUP OF INSTITUTIONS :: PUTTUR Siddharth Nagar, Narayanavanam Road AUTONOMOUS QUESTION BANK (DESCRIPTIVE) UNIT I

Feasibility of a Liquid Desiccant Application in an Evaporative. Cooling Assisted 100% Outdoor Air System

Impact of Multi-Stage Liquid Desiccant Dehumidification in a Desiccant and Evaporative Cooling-Assisted Air Conditioning System

AND AIR-CONDITIONING. Dr Ali Jawarneh Department of Mechanical Engineering Hashemite University

EXPERIMENTAL INVESTIGATION OF DIRECT EVAPORATIVE COOLER WITH HEMP AND ABACA COOLING PAD MATERIAL

Performance Optimization of the Evaporative Condenser Design

Chapter 14 GAS VAPOR MIXTURES AND AIR-CONDITIONING

Modified Air Cooler with Split Cooling Unit

Dynamic performance of a novel dew point air conditioning for the UK buildings

A review on Efficient Technique of Air-Conditioning Rajesh Kumar, Pravesh Mishra, Ram Raja

4th International Conference on Sensors, Measurement and Intelligent Materials (ICSMIM 2015)

Performance Comparison of Ejector Expansion Refrigeration Cycle with Throttled Expansion Cycle Using R-170 as Refrigerant

UNIT 1 AIR CONDITIONING 1. Write the various psychometric processes? Explain any four processes with neat sketches?

EXPERIMENTAL STUDY OF CENTRIFUGAL HUMIDIFIER FITTED IN AN INDUSTRIAL SHED LOCATED IN TROPICAL CLIMATES

Scholars Research Library

Analysis of Constant Pressure and Constant Area Mixing Ejector Expansion Refrigeration System using R-1270 as Refrigerant

System-CoolAC. Bharatividyapeeth College of Engineering, Deekshant Bharti Scholar, New Delhi, India

Experimental investigation of Hybrid Nanofluid on wickless heat pipe heat exchanger thermal performance

SIMULATION ANALYSIS ON THE FRESH AIR HANDLING UNIT WITH LIQUID DESICCANT TOTAL HEAT RECOVERY

S.A. Klein and G.F. Nellis Cambridge University Press, 2011

Development of a Psychrometric Test Chamber. Michael J. Swedish. Associate Professor Mechanical Engineering Department Milwaukee School of Engineering

Recent Advances in Energy, Environment and Economic Development

Applied Thermal Engineering

PERFORMANCE OF SOLID DESICCANT COOLING WITH SOLAR ENERGY IN HOT AND HUMID CLIMATE

Subscripts 1-4 States of the given system Comp Compressor Cond Condenser E Evaporator vol Volumetric G Gas L Liquid

Institute of Aeronautical Engineering (Autonomous) Dundigal, Hyderabad B.Tech (III II SEM) MECHANICAL ENGINEERING

Comfort and health-indoor air quality

Oxyvap Evaporative Cooling Applications

Thermodynamics II Chapter 6 Mixtures & Psychrometry

Article Energy Saving Benefits of Adiabatic Humidification in the Air Conditioning Systems of Semiconductor Cleanrooms

R07. Answer any FIVE Questions All Questions carry equal marks *****

Effect of Operating Parameters on the Performance of Direct Evaporative Cooler

EVAPORATIVE AIR-COOLING EQUIPMENT

Green Practices Of Air Conditioning For Major Capital Cities Of India Using Advanced Evaporative Cooling

Performance Of The Dehumidification Cycle Of A 3-Fluid Liquid Desiccant Membrane Air-Conditioning System

Technical college/ Baghdad 4th Year Week No. :- 11. The objectives of this lesson are to: Introduction:

An Experimental Analysis of Direct Evaporative Cooler by Changing its Cooling Pads

Evaporative Cooling in a Hot-Dry Climate

AN ENVIRONMENT FRIENDLY COOLING OPTION

Numerical study of heat pipe application in heat recovery systems


R10. IV B.Tech I Semester Regular/Supplementary Examinations, Nov/Dec REFRIGERATION & AIR-CONDITIONING (Mechanical Engineering)

Week 4. Gas-vapor mixtures Air conditioning processes. ME 300 Thermodynamics II 1

Mechanical Engineering Laboratory

Chapter 14, Problem 27.

For an ideal gas mixture, Dalton s law states that the sum of the partial pressures of the individual components is equal to the total pressure.

HVAC (Heating, Ventilating, and Air Conditioning)

Performance investigation of Air-conditioning system using ejector as expansion device

Greenhouse Temperature Management

PERFORMANCE IMPROVEMENT OF SPLIT AIR CONDITIONER USING EVAPORATIVE COOLING METHOD IN THE CLIMATIC CONDITION OF GUWAHATI, ASSAM

Available online Journal of Scientific and Engineering Research, 2018, 5(11): Research Article

Available online at Energy Procedia 6 (2011) MEDGREEN 2011-LB

Heat pump and energy recovery systems

Psychrometrics. Outline. Psychrometrics. What is psychrometrics? Psychrometrics in daily life and food industry Psychrometric chart

MECHANICAL ENGINEERING THERMAL AND FLUID SYSTEMS STUDY PROBLEMS

Comparison Simulation between Ventilation and Recirculation of Solar Desiccant Cooling System by TRNSYS in Hot and Humid Area

Review on Waste Heat Recovery Techniques in Air Conditioning Application

Dhulapally, Secunderabad Subject: REFRIGERATION AND AIR CONDITIONING QUESTION BANK

Evaporative Cooling Applicability in the Middle East

9. ENERGY PERFORMANCE ASSESSMENT OF HVAC SYSTEMS

International Journal of Informative & Futuristic Research ISSN (Online):

ANALYSIS OF DESICCANT COOLING SYSTEM

ENERGY SAVING IN A DOMESTIC SPLIT-TYPE AIR CONDITIONER WITH EVAPORATIVE COOLING SYSTEMS

Feasibility of Controlling Heat and Enthalpy Wheel Effectiveness to Achieve Optimal Closed DOAS Operation

Review of Energy Efficient Cooling Techniques Based on Various Evaporative Cooling Systems

Performance analysis of ejector refrigeration system with environment friendly refrigerant driven by exhaust emission of automobile

Experimental Study of Direct Contact Condensation of Steam on Water Droplets

International Journal of Engineering Research (IJOER) [Vol-1, Issue-3, June- 2015]

Impact of indirect evaporative air cooler type on the performance of desiccant systems

Design of Divided Condensers for Desiccant Wheel-Assisted Separate Sensible and Latent Cooling AC Systems

Energy Consumption Reduction of AHU using Heat Pipe as Dehumidifier

INTRODUCTION HVAC BASICS AND HVAC SYSTEM EFFICIENCY IMPROVEMENT SECTION O 4/19/2012

Experimental Analysis and Performance Comparison between Evaporative Cooling System and Air Conditioning System

Experimental Study on Match for Indoor and Outdoor Heat Exchanger of Residential Airconditioner

ANALYSIS OF VAPOUR COMPRESSION REFRIGERATION (VCR) BASED AIR CONDITIONING (AC) SYSTEM FOR HOT AND DRY CLIMATIC CONDITIONS IN OMAN

DESIGN AND FABRICATION OF AN EVAPORATIVE COOLING SYSTEM. Md. Rakibuzzaman 1,* and M. A. Wazed 2. Chittagong-4349, Bangladesh 1,*

PDHonline Course A127 (4 PDH) Evaporative Cooling. Instructor: George E. Thomas, PE. PDH Online PDH Center

3. (a) Explain the working of a rotary screw compressor. [10] (b) How the capacity control is achieved in refrigerant compressor?

Heat Recovery Units. Heat Recovery 1

Thermodynamic analysis of air cycle refrigeration system for Chinese train air conditioning

USE OF DOE-2 TO EVALUATE EVAPORATIVE COOLING IN TEXAS CORRECTIONAL FACILITIES

Performance of an Improved Household Refrigerator/Freezer

INDIRECT EVAPORATIVE COOLING A PAST REVIEW

THE ANALYSIS AND EXPERIMENTAL INVESTIGATION OF HEAT PUMP SYSTEM USING THERMOBANK AND COS EJECTOR CYCLE

Enhancement of COP in Vapour Compression Refrigeration System

Transcription:

Two Stage Indirect/Direct Evaporative Cooling Abstract The performance of two-stage indirect/direct evaporative cooling system is experimentally investigated. For this purpose, a two-stage evaporative cooling experimental setup consisting of an indirect evaporative cooling stage (IEC) followed by a direct evaporative cooling stage (DEC) was designed, constructed and tested. Two air simulators are provided to simulate outdoor design condition in primary and secondary air streams. To achieve comfort conditions and power saving the system has been investigated with related excess water consumption. Considering the evaporative comfort zone, this system can provide comfort condition in a vast region where direct evaporative system alone is not able to provide summer comfort condition. More than 60% power saving could be achieved by this system in comparison with mechanical vapor compression systems and 55% increase in water consumption with respect to direct evaporative cooling systems. This system can complete the gap between direct evaporative cooling systems and mechanical vapor compression systems as an energy efficient and environmentally clean alternate. I. INTRODUCTION Evaporativecoolingisanenvironmentallyfriendlyand energyefficientmethodforcoolingbuildingsinhotand dryregions.indiaasamulti-climatecountrydemandsav arietyofcoolingsystemstoachieveoptimizedenergyco nsumption,reduceemission,andprovidesummercomf ortcondition.manytypesofnaturalandpassivemethod swereusedforcoolingbuildings.allofthesemethodsh avebeenworkedbasedonnatural ventilation.windtowerandshapeofbuildingarethema inelementsinthesetraditionalcoolingmethods,which deviateandconveyoutsideairtobuildings. Two principle methods of evaporative cooling are commonly used, the direct (DEC) and the indirect one (IEC).DEC is the simplest, oldest, and the most widespread form of evaporative air conditioning. This system typically uses a fan to draw hot outdoor air into a porous wetted medium. The water absorbs heat as it evaporates from the porous wetting medium, and the air thus leaves the DEC at a lower temperature.in fact, dry bulb temperature of the air reduces as it is moistened in thisadiabatic saturation process. The principle underlying DEC is the conversion of sensible heat to latent heat. The wetted medium could be a porous wetted pad consisting of fibers, cellulose papers or a spray of water. Abhishek Sharma 1, Hemant Darokar 2 ME (Heat Power) student 1, Assistant Professor 2 abtau56@gmail.com 1, hemantdarokar@rediffmail.com 2 A. DIRECT EVAPORATIVE COOLING In direct evaporative cooling sensible heat energy evaporates some water, and reduced the air s dry bulb temperature. Greater the differences in dry bulb and wet bulb temperatures; better is the cooling effect to the space and the temperature of saturated moist air is achieved almost near the wet bulb temperatures. Fig. 1. DIRECT EVAPORATIVE COOLING Direct evaporative cooling, commonly used for residential, commercial, and industrial systems, cools the air by evaporation of water to increase the moisture content of the air. In industrial system mainly uses cellulose pads as evaporative medium. A standard residential system uses evaporative media of shredded aspen fibers, typically 1 to 2 inches thick. These systems have an effectiveness of 55 to 70 percent. When hot and dry air blows through wet medium, the water gets saturated and evaporates. This evaporation of water provides cooling effects. The effectiveness of evaporative cooling system is defined by the types of evaporative media used and it also depends on its thickness. Effectiveness is determined by the performance of evaporative cooling system. It is defined by following equation: 41 ε = Tdb SAT Tdb Twb (1) Where Td b is the outdoor dry-bulb temperature, Tw b is the outdoor wet-bulb temperature and ЅАТ is the supply air temperature leaving the evaporative cooler. Evaporative cooling system design is directly affected by dry bulb, wet bulb temperature, and relative humidity. The main restriction of direct evaporative cooling is air moisture content present in the air. Evaporative cooling systems are of increasing

choice because of their lower energy consumption compared to any other refrigerated system, first simplicity in design, low initial cost, and ease of installation, operation, and maintenance. It does not use refrigerants such as chlorofluorocarbons (CFCs), which may cause harmful effects on the human health and the environment. Another attractive feature of evaporative system is that most air contaminants such as dust, dirt, bacteria, and other impurities are washed out in the re-circulated water. When the water evaporates, only pure water is released and air circulation fan supplies 100% fresh and cooled air to the space. 1) ACTIVE DIRECT EVAPORATIVE COOLING SYSTEM The active direct evaporative coolers are electricity-driven systems, however, it use a fraction of power for air and water circulation. So, it is considered much less energy intensive than other traditional cooling technologies, with energy saving up to 90%. A typical direct evaporative cooler comprises of evaporative media (wettable and porous Pads), fan blows air through the wetted medium, water tank, recirculation pump and water distribution system. The direct evaporative cooling is an adiabatic cooling process, i.e. the total enthalpy of the air is constant throughout the process. The water absorbs the sensible heat from the supply air and evaporates causing the air temperature decreases and its humidity to increase Theoretically, the supply air could be cooled to 100% effectiveness, but in such process a wet-bulb effectiveness of 70%-80% only is achievable because of short contact time between the two fluids, insufficient wettability of the pads and due to the fact that the circulated water and the supply air will reach an equilibrium point that is equal to the wet-bulb temperature of the supply air. Eventually the system would not be able to cool down the incoming air lower than its wet-bulb temperature. The wet-bulb effectiveness could reach range between 70-95% in most current commercial DEC coolers and mainly as a function of the type and thickness of evaporative media, working climate, and supply air flow-rate. According to ASHRAE Handbook-HVAC Systems and Equipment (2008) active DEC could be divided according to types of wet media into: Random media DEC, Rigid media DEC and Remote media DEC as shown in figure 2. Fig. 2. TYPES OF DEC SYSTEM PADS 2) PASSIVE DIRECT EVAPORATIVE COOLING Passive cooling techniques use natural phenomena, energies, and heat sinks for cooling buildings without the use of mechanical apparatus consume electrical energy. However, small fans and pumps could be required. Passive DEC is relied on the climate which means the techniques applied for hot and humid regions are different from those for hot and arid areas. This technology is able to reduce indoor air temperature by about 9. The main types of passive direct evaporative cooling building integrated systems are: (a) The Mashrabiya required fan power, the high effectiveness extends 42 (b) Wind Towers (c) Roof-Pound B. INDIRECT EVAPORATIVE COOLING SYSTEM In indirect evaporative cooling systems heat and mass transfer takes place and uses an air to air heat exchanger to remove heat from the primary air stream without addition of moisture by means of cooled secondary stream evaporative. During the heating season, an indirect system s heat exchanger can preheat outside air if exhaust air is used as the secondary air stream. In one configuration, hot dry outside air is passed through a series of horizontal tubes that are wetted on the outside. A secondary air stream blows over the outside of the coils and exhausts the warm, moist air to the outdoors. The outside air is cooled without adding moisture as it passes through the tubes. Indirect evaporative cooling typically has an effectiveness of 60-80%. In indirect evaporative process air moisture content stays constant during temperature decreasing. Due to less energy losses in indirect evaporative cooling process; it results in less effective than direct evaporative, because energy needed in vaporization is taken from the same environment. Indirect evaporative cooling systems takes advantage of evaporative cooling effects, but cools without raising indoor humidity. As cooling of the primary air stream takes place by heat transfer across the heat exchanger walls without the mixing of the two air streams, the primary air stream becomes cooler without an increase in its humidity. While the greater number of air passes increases the pressure drop and the

the geographic range where the indirect evaporative cooler can fully meet the cooling demand. In some applications, the greater temperature difference between the secondary and primary air is that the secondary air temperature is lower than the dew-point temperature of the primary air and results dehumidification of the primary air in this cooling process i.e. condensation from primary air, especially in hot and wet climates. Fig. 3. INDIRECT EVAPORATIVE COOLING The effectiveness of indirect evaporative cooling can be expressed as: ε = t1 t2 t1 twb 1 (2) ε = indirect evaporative cooling effectiveness, % t1 = dry bulb temperature of entering primary air C t2 = dry bulb temperature of leaving primary air, C twb1= wet bulb temperature of entering secondary air, C Direct Evaporative Cooling system (DEC) and Indirect Evaporative Cooling system (IEC) are two main groups in evaporative cooling systems. In hot and humid or temperate and humid regions where the DEC and IEC systems do not provide comfort condition, mechanical vapor compression cooling systems are used. Some advantages of evaporative cooling systems in comparison with mechanical vapor compression systems are as following: (a) Reduction in input power and input current. (b) Using water as the working fluid which is environmentally friendly (c) Elimination of CFC gases which are harmful to ozone layer (d) Ability to induce fresh air into the room. (e) Base price is low. Also, some disadvantages of evaporative cooling systems are as following: (a) Water supply restrictions in an area where there is scarcity of water. (c) Due to supply of humid air in the room, the air within the room will get saturated. (d) Evaporative cooling systems need more frequent maintenance. (e) Ductwork is required in Evaporative cooling systems. In both the above cases of Direct evaporative cooler (DEC) and Indirect evaporative cooler (IEC) the minimum temperature to which air can be cooled theoretically is the wet bulb temperature (WBT) of the incoming air. Therefore a combination of above two systems called indirect-direct two stage evaporative cooling is used to improve the performance of the whole system. Such a system reduces the dry bulb temperature (DBT) of incoming air in a heat exchanger before it passes to the direct stage. Such a system can ultimately reduce the temperature of the incoming air below its WBT. C. INDIRECT DIRECT EVAPORATIVE COOLING SYSTEM Two-stage indirect/direct evaporative coolers as shown in Figure 4 can cool air to lower temperatures than are attainable with direct ( one-stage ) evaporative coolers, and add less moisture to the indoor air. In these coolers, a first-stage indirect evaporative cooler lowers both the dry bulb temperature (DBT) and wet bulb temperature (WBT) of the incoming air. After leaving the indirect stage, the supply air passes through a second stage direct evaporative cooler. Figure 5 shows the cooling process on a psychrometric chart. First-stage cooling follows a line of constant humidity ratio as no moisture is added to the primary airstream; the second stage follows the WBT line at the condition of the air leaving the first stage. Fig. 4. INDIRECT DIRECT EVAPORATIVE COOLING (b) Evaporative cooling systems will have little or no cooling effect in a moist environment. 43

Fig. 5. INDIRECT DIRECT EVAPORATIVE COOLING PROCESS Different researchers have made the effort to improve the performance of these systems by changes in design, process and materials. G. Heidarinejad 2009 experimentally investigated the cooling performance of two stage indirect/direct evaporative cooling system in various simulated climatic conditions in Iran. They used plastic wet surface heat exchanger as an IEC unit and 15 cm thick cellulose pad for a DEC unit. They obtained an effectiveness of IEC unit in the range of 55 % 61 % and effectiveness of IEC/DEC unit in the range of 108 % 111 %. They also reported 55 % more water consumption than DEC unit and power consumption as 33 % of mechanical cooling systems. Jain 2007 developed and tested a two stage evaporative cooler to improve the efficiency by using wooden shave as the packing material. Room return air was evaporatively cooled and used in a heat exchanger to cool the incoming dry air. The effectiveness ranged from 1.1 to 1.2 and this cooler could achieve favourable temperature and relative humidity conditions for storage of tomatoes for 14 days. Camargo 2005 developed a mathematical model for a DEC and presented their experimental results of the tests using rigid cellulose media with wetted surface area of 370 m2/m3. The effectiveness relation derived in terms of heat transfer coefficient, mass flow rate of air, wetted surface area and humid specific heat is useful in predicting the performance of different pad materials. They concluded that the effectiveness is higher at higher dry bulb temperature and lower air speeds. El Dessouky 2004 carried out theoretical and experimental study on small scale evaporative cooling unit using structured packing material of high density polythene with wetted surface area of 420 m2/m3. They used a combination of DEC and IEC and concluded that the efficiency of IEC unit is less than DEC but a combination of both can reduce the temperature of incoming air below its WBT. Maheshwari2001 compared the power requirements of an IEC unit with conventional packaged air conditioner. They concluded that the best performance of IEC unit coincides with the hour of maximum cooling capacity and peak power demand of conventional unit and it offers maximum reduction in cooling capacity and peak power demand. El Dessouky1996 used the concept of pre cooling the air before DEC without using cooling tower. Structured, sheathy leaf and natural fiber packing was used as cooling media with varying thickness and flow of water. They observed that effectiveness increased with packing thickness and flow rate of water to IEC. Structured packing showed higher effectiveness than sheathy leaf and natural fiber. Dowdy and Karbash 1987 tested rigid impregnated cellulose media experimentally to determine heat and mass transfer coefficients for evaporative cooling process. They used the sample of rigid cellulose media having wetted surface area of 350 m2/m3 with thickness 305 mm and obtained saturation efficiency between 90 to 94 %. II. EXPERIMENTAL SETUP To evaluate performance of IEC/DEC system and in order to investigate effect of operational parameters, an experimental setup was designed and constructed as shown in Fig. 6. Test setup consists of four major modules: 1) A primary air simulator including a centrifugal fan provided with a frequency inverter to adjust flow rate, electrical heating elements, and electrical humidifier. This module adjusts flow rate, temperature, and relative humidity in primary air stream. A straighter was installed to achieve airflow uniformity. 2) Secondary air simulator is similar to primary air simulator in secondary air stream. 3) IEC/DEC unit including a polycarbonate wet surface heat exchanger as IEC unit, a cellulose pad as DEC unit, a water circulating pump and two flow meters and two valves to control water flow rate of indirect and direct evaporative systems. Water is distributed over indirect and direct systems using proper spray nozzles. 4) Control panel for setting steady-state temperature and relative humidity and flow rate of primary and secondary air. As shown in Fig. 6, temperature and relative humidity (RH) are measured in the following positions: a) Air temperature and RH before the IEC unit in primary andsecondary flows. 44

b) Air temperature after the IEC unit in primary flow. c) Air temperature and RH after the IEC unit in secondary flow. d) Air temperature and RH after the DEC unit. III. EXPERIMENTAL PROCEDURE In Indirect evaporative cooler, hot and dry secondary air enters the heat exchanger from the bottom duct. Water flowingalong the polycarbonate plates in downward direction gets evaporated due to heat of air and takes heat from air as well as plates. As a result the temperature of plates is reduced. Warm and humid secondary air is discharged through the upper duct on the same side. The primary air enters the indirect evaporative cooler horizontally from the primary air simulator due to suction of air in primary fan. The cooling effect produced in secondary channels is transferred to the primary air flowing through the alternate channels and thus primary air gets cooled. The primary air travels in horizontal direction through the IEC and enters the DEC on the opposite side. In direct evaporative cooler, primary air comes in contact with wetted pad surface. Water on the pad surface getsevaporated by taking heat from incoming air. Thus the temperature of primary air is reduced in two stages first in IEC and then in DEC. IV. INDICATIVE PARAMETERS A. WET BULB & DEW POINT EFFECTIVENESS Wet-bulb effectiveness is a parameter describing the extent of the approach of the outlet product air temperature of the IEC against the wet-bulb temperature of the inlet working air, and can be written as: ε wb = t p,db,in t p,db,out t p,db,in tp,wb,in (3) Dew point effectiveness is another parameter used for this purpose and defined as the ratio of the temperature difference between the inlet and outlet product air to the difference between the inlet product air s dry bulb and inlet working air s dew point temperature. This reflects the extent of the approach of the outlet product air temperature against the dew point temperature of the inlet working air related to the IEC, shown as follows: ε dp = t p,db,in t p,dh,out t p,db,in t p,db,in (4) Fig. 6. EXPERIMENTAL SETUP B. EVAPORATIVE COOLER EFFIECIENCY RATIO ECER, defined as the ratio of the cooling delivery volume to electrical power related to the IEC, is measured on the condition of intake air dry/wet bulb temperature of 32.8/ 20.6 1ºC and room air temperature of 26.7 1ºC. This could be expressed in the following equation: ECER = ρ f c f [t room C. COOLING CAPACITY t p,db,in t p,wb,in )]V p,out /W(5) The cooling capacity refers to the enthalpy change of the product air when travelling across the dry channels of the IEC heat exchanger, and is expressed as follows: Q total = ρ f V p,out (i p,db,in i p,db,out )(6) Since the air is cooled at the constant moisture contentduring the dry channels of the IEC exchanger, theenthalpy change of the air could be represented by the temperature reduction of the air during its dry channel flow path. For this reason, the above equation could be rewritten as: Q = c f ρ f V p,out (t p,db,in t p,db,out )(7) D. ENERGY EFFICIENCY Energy efficiency, known as coefficient of performance (COP), is the ratio of the cooling capacity of the IEC to the power consumption of the system. This term can be mathematically expressed as: η = Q = c f ρ f V p,out (t p,db,in t p,db,out (8) W W If this figure is multiplied by a unit conversion factor of 3.413, the COP is then converted into the energy efficiency ratio (EER). E. WATER EVAPORATION RATE The water evaporation rate of an IEC system depends upon a number of its operational parameters, e.g., the inlet air temperature/humidity, airflow rate, treated cooling load, as well as the swellas system s cooling effectiveness. Theoreticallyspeaking, the water evaporation rate is equal to the volume of the moisture increase in the working air during its indirect cooling operation and could be expressed as: 45

V w = V s,out ρ s,f ρ w (W s,out W s,in )(9) F. SECONDARY TO PRIMARY AIR RATIO In an IEC system, the secondary air, known as the working air is used to cool the primary (i.e., product) air. Ratio of the secondary to primary air-flow is an important measure effecting on the cooling performance of the system. It is claimed that the ratio of the secondary to primary air is usually in the range 0.3 1.0 and during operation, increasing the value of this ratio will lead to increase of the cooling effectiveness. However, this increase will also lead to reduced supply air volume and thus the overall cooling capacity of the system may fall. There will be an optimised figure on the ratio that will enable the maximised cooling capacity of the system and adequate cooling effectiveness. This figure will be determined using the dedicated computer programme under a given geometrical and operational conditions. G. PRESSURE LOSS Pressure loss refers to static pressure drop of the air when passing across the dry and wet channels of an IEC heat exchanger. H. AIR FLOW RATE Air flow rate refers to air volume flow rate across the IEC heat exchanger channels including dry and wet channels. The air flow rate is usually measured by the unit of m 3 /s orm 3. V. CONCLUSION The results obtained from experimental two-stage indirect/direct evaporative cooling system shows that, this system has high potential to provide comfort conditions in regions where at present standalone direct evaporative coolers cannot provide comfort conditions. Also in regions with higher wet bulb temperatures, this system can be used instead of mechanical vapor compression systems, which results decrease in electrical energy consumption. Despite wide variety of climatic conditions, it is found that IEC effectiveness varies between 55 and 61% and IEC/DEC effectiveness over a range of 108 111%. The average water consumption of two-stage evaporative cooling system is 55%more than direct evaporative cooling system and power consumption is33% of mechanical vapour compression cooling systems, so this cooling system can be used in various climatic conditions as an environmentally clean and energy efficient system. REFERENCE [1] Heidarinejad G, Heidarinejad M, Delfani S, Esmaeelian J. Feasibility of usingvarious kinds of cooling systems in a multi-climates country. Energy andbuildings 2008; 40:1946 53. [2] Heidarinejad G, Bozorgmehr M. Modeling, evaluation and application potential of two stage indirect/direct evaporativeair coolers. In: Proceedings of the 6th international energy conversion engineering conference (IECEC), Cleveland, Ohio, July 28 30, 2008; AIAA 2008 5690. [3] El-DessoukyH, Ettouney H, Al-Zeefari A. Performance analyses of two-stageevaporative coolers. Chemical Engineering Journal 2004; 102:255 66. [4] Jain D. Development and testing of two-stage evaporative cooler. Building and Environment 2006; 42:2549 54 [5] ASTM D3464-96. Standard test method for average velocity in a duct usinga thermal anemometer; 2007. [6] Dr.C.R.Patil, K.G.Hirde, P.R.M.I.T. &R., Badnera. The Concept of Indirect Evaporative cooling, International Journal of Engineering Science and Innovative Technology (IJESIT)Volume 2, Issue 5, September 2013. [7] Shahab Moshari, Ghassem Heidarinejad, Aida Fathipour. Numerical investigation of wet-bulb effectiveness and water consumption in one-and two-stage indirect evaporative coolers. Energy Conversion and Management 108 (2016) 309 321. [8] Kulkarni.R.K, Rajput S.P.S, Performance evaluation of two stage indirect/direct evaporative cooler withalternative shapes and cooling media in direct stage. International Journal of Engineering Research, Dindigulvolume 1, no 4, 2011. 46