M.200
SPLIT SYSTEM CONDENSING UNIT SCHEDULE MARK SERVICE MODEL NO. COOLING DIMENSIONS ELECTRICAL REMARKS CAPACITY AMBIENT DB REFRIGERANT LENGTH WIDTH HEIGHT WEIGHT VOLT/PHASE MCA MOP (MBH) (DEG F) (IN) (IN) (IN) (LBS) CU-1 AHU-1 J10YCC00 110.2 95 R-410A 59 32 50 499 480/3 23.5 30 1, 2, 3 NOTES: 1. MANUFACTURER IS JCI. ACCEPTABLE ALTERNATES: CARRIER, LENNOX, TRANE. 2. PROVIDE WITH 14" ROOF CURB AND REFRIGERATION LINE SET. ELECTRIC HEATING COIL SCHEDULE DIMENSIONS ELECTRICAL MARK SERVICE MODEL NO. REMARKS WIDTH HEIGHT STAGES AMP POWER VOLT PHASE (IN) (IN) (KW) EHC-1 AHU-1 IDHC 30 16 15 1 18 480 3 1, 2 NOTES: 1. MANUFACTURER IS GREENHECK. ACCEPTABLE ALTERNATES: INDEECO. 2. PROVIDE WITH 24V DC CONTROLS. SEE M.400 FOR TEMPERATURE CONTROLS. INTAKE, RELIEF AND EXHAUST HOOD SCHEDULE MARK SERVICE MODEL NO. CURB SIZE AIRFLOW WEIGHT REMARKS HEIGHT (LBS) LENGTH WIDTH NECK SIZE QUANTITY STATIC (IN) (IN) (IN) (IN) (CFM) PRESSURE (IN WG) IH-1 INTAKE FGI 14 72 53 42x30 4000 0.05 131 1, 2 S-2 RELIEF FGR 14 60 42 42x30 3900 0.048 107 1, 2 S-3 EXHAUST FGR 14 24 18 8x8 200 0.049 37 1, 2 NOTES: 1. MANUFACTURER IS GREENHECK. ACCEPTABLE ALTERNATES: PENN, COOK. 2. PROVIDE WITH GRAVITY BACKDRAFT DAMPER AND BIRD SCREEN. AIR HANDLING UNIT SCHEDULE MARK SERVICE MODEL NO. SUPPLY FAN COOLING HEATING WEIGHT ELECTRICAL REMARKS (LBS) TOTAL OUTSIDE ESP POWER CAPACITY TYPE EAT LAT COMPRESSOR VOLT/PHASE FLA MCA MOP AIRFLOW AIRFLOW (IN WC) (HP) (DB/WB) (DB/WB) TOTAL SENSIBLE (CFM) (CFM) (MBH) (MBH) AHU-1 RETAIL, STORAGE AMI-H10 4000 1300 0.5 3 118.3 87 DX 80/67 60.4/57.7 CU-1 EHC-1 1168 480/3 3.9 4.83 15 1, 2, 3, 4, 5, 6 NOTES: 1. MANUFACTURER IS JCI. ACCEPTABLE ALTERNATES: CARRIER, LENNOX, TRANE. 2. UNIT ARRANGEMENT BACK-TO-FRONT: MEDIUM INLET PLENUM W/ 30% PRE-FILTERS (TOP INLET); MERV 14 CART. FILTERS; SMALL ACCESS; FAN AND COIL COMBINATION (TOP OUTLET) 3. PROVIDE ONE (1) COMPLETE SET OF EXTRA FILTERS AND BELTS. 4. PROVIDE ECONOMIZER FAULT DETECTION AS PER CEC 2013 SECT. 120.2. 5. PROVIDED WITH SMOKE DETECTOR AND AUTOMATIC SHUT DOWN CONTROLS AS PER CMC 608.1 6. PROVIDE TEMPERATURE CONTROLS AS PER M4.00. FAN SCHEDULE MARK SERVICE MODEL NO. FAN TYPE DIMENSIONS WEIGHT NOISE ELECTRICAL REMARKS (LBS) (SONE) TOTAL ESP FAN RPM MOTOR LxW HEIGHT VOLT/PHASE FLA AIRFLOW (IN WC) (IN) (IN) BRAKE RATED RPM (CFM) (HP) (HP) RF-1 AHU-1 BSQ-160HP 4000 0.75 2132 2.28 3 1750 INLINE 26x26 26 184 19.6 460/3 4.8 1 EF-1 TOILET RM SP-A200 100 0.64 900 -- 46.2 W -- CEILING MTD 14x12 11 24 4 115/1 0.4 1 103 EF-2 TOILET RM 102 SP-A200 100 0.64 900 -- 46.2 W -- CEILING MTD 14x12 11 24 4 115/1 0.4 1 NOTES: 1. MANUFACTURER IS GREENHECK. ACCEPTABLE ALTERNATES: PENN, COOK. GRILLE REGISTER AND DIFFUSER SCHEDULE MARK SERVICE MODEL NO. MOUNTING SIZE FINISH REMARKS TYPE LENGTH WIDTH NECK SIZE (IN) (IN) (IN) S-1 SUPPLY RCD DUCT 27 DIA -- SEE DWGS WHITE S-2 SUPPLY 510 DUCT 14 10 SEE DWGS WHITE S-3 SUPPLY 520 DUCT 18 16 SEE DWGS WHITE R-1 RETURN 530 CEILING 46 18 SEE DWGS WHITE R-2 RETURN 530 CEILING 20 16 SEE DWGS WHITE NOTES: 1. MANUFACTURER IS PRICE. ACCEPTABLE ALTERNATE: TITUS. M.200
M.300
M.400
E.100
PLUMBING FIXTURE SCHEDULE CONNECTION MODEL MARK FIXTURE TYPE PLUMBING DESCRIPTION CFW HW SAN CW W&V DF-1 DRINKING 1/2" 3" 1-1/2" ELKAY 8.0 GPH, 370 WATTS, 4.0 FLA, ADA COMPLIANT FOUNTAIN EZSTL8C LAV-1 LAVATORY 1/2" 1/2" 3" 1-1/2" AMERICAN STANDARD LUCERNE 0355.015 WC WATER CLOSET 3/4" 4" AMERICAN STANDARD CADET 2462.100 WCO WALL CLEANOUT 3" ZURN Z1441 WH-1 WATER HEATER 3/8" AO SMITH 3/8" MT004120T WALL-HUNG, VITREOUS CHINA WITH FRONT OVERFLOW, FAUCET HOLES (4" APART), AND SELF DRAINING BACKSPLASH. PROVIDE GRID DRAIN (2411.015), FAUCET (5500.175), AERATER, WALL SUPPLY VALVES, ESCUTEONS, CARRIER, P-TRAP AND INSULATION KIT. LAVATORY AND ALL LISTED ACCESSORIES SHALL BE ADA COMPATABLE (MODEL NUMBERS LISTED ARE AMERICAN STANDARD). ELONGATED BOWL WITH TANK, 1.1 GPF, SUPPLY WITH 1/4 TURN STOPS & WHITE OPEN FRONT SEAT (BEMIS 9400CT). CAST IRON BODY WITH ABS PLUG, ROUND 5" STAINLESS STEEL COVER. ELECTRIC, TANKLESS TYPE WATER HEATER, 0.3 GPM ACTIVATION, 3.5 KW INPUT, 29 A, 120V/1PH, 48 DEG F TEMP RISE @ 0.5 GPM. P.100
E.110
2 E120 SALES FLOOR LIGHTING CONTROL NTS 1 E120 STOCK ROOM LIGHTING CONTROL NTS E.120
SYMBOL LEGEND GENERAL NOTES ABBREVIATIONS E.200
E.210
1 E220 RISER DIAGRAM NTS E.220
E.230
4,554.4 E.300
E.310
4,890 E.320
10/23/2015 10/23/2015 10/23/2015 SPACE 320 SOUTHLAND MALL, HAYWARD, CA. 10/23/2015 10/23/2015 E.330
SPACE 320 SOUTHLAND MALL HAYWARD, CA 10/23/2015 7,711 S.F. #1074 NEW MALL, NEWARK, CA 10/23/2015 320 SOUTHLAND MALL, HAYWARD, CA 9-15-2015 LP-L 80.2 41.1 LP-L 80.2 41.1 320 SOUTHLAND MALL, HAYWARD, CA 10/23/2015 320 SOUTHLAND MALL, HAYWARD, CA 10/23/2015 320 SOUTHLAND MALL, HAYWARD, CA 10/23/2015 E.340