User s Manual. Model VJRK IM 77J01R21-01E 1. CAUTIONARY NOTES FOR SAFE USE OF THE PRODUCT 4. MODEL AND SUFFIX CODES 5.

Similar documents
User's Manual. Model VJQ8 Pulse to Analog Converter. (Multi-function) MODEL AND SUFFIX CODES CAUTIONARY NOTES FOR SAFE USE OF THE PRODUCT

IM 77J01H07-01E 1st Edition Nov th Edition Feb Fixed code 0 Always 0

IM 77J01A07-01E 1st Edition Nov th Edition Feb Fixed code 0 Always 0. Output-2 signal

User s. Manual) Model VJUK Limit Alarm for Universal Input

User s. Manual) Model VJS7 Potentiometer Converter (Multi-function) (Isolated Single-output and Isolated Dualoutput

General Specifications

Series Temperature Controller Instruction Sheet

Warning Caution INSTRUCTION MANUAL DIN RAIL MOUNTING TYPE INDICATING CONTROLLER

Instruction manual Temperature Controller KT7

AE500 Instruction Manual

DIGITAL INDICATOR JIR-301-M

Digital Panel Meter K3TL. Ordering Information. Low-cost, High-quality Digital Thermometer with Built-in Microcomputer. Accessories (Order Separately)

Analog Room Pressure Monitor RPC Series

Advanced Ultraviolet Burner Controller

General Specifications

General Specifications

Model SDAU (Style R) Digital Alarm Unit

ST Wiring diagram. Product description. Four-stage controller. Order number

Buzzer Unit. TAN-5000 Series. Operating Manual

enproteko.com Specifications Ratings Item voltage to 24 VAC 5/6 Hz 24 VAC 5/6 Hz or 24 VDC Allowable voltage Characteristics 85% to 11% of power suppl

AUR300C, AUR350C. Advanced Ultraviolet Burner Controller

General Specifications

Smart Transmitter/ Gas Detector Head

Indoor Oxygen Monitor OX-600 Operating Manual

Series Digital Controller Instruction Sheet

ISOLATOR SGI SGIW INSTRUCTION MANUAL

Non-contact voltage (for SSR drive): V DC DC current: 4 to 20mA DC Thermocouple: K, J, E Input. RTD: Pt100, JPt100

DIGITAL INDICATING CONTROLLER FCS-23A INSTRUCTION MANUAL

ST Wiring diagram. Product description. Standard temperature controller. Order number

Tempco PCT-3000 Series Temperature Control Console with Relay Output for Heating or Cooling Applications

General Specifications

REFRIGERATED BATH CIRCULATOR. Instruction Manual. Covers model : LRBC-13C / LRBC-22C. Please read this manual carefully before using the instrument

DIGITAL INDICATOR DI25

General Specifications

Instruction manual for DIN rail mounting type indicating controller DCL-33A

Ceiling Mount Temperature Sensor

INSTRUCTION MANUAL FOR MICROCOMPUTER BASED TEMPERATURE INDICATING CONTROLLER GCD-200, GCR-200

SA-3841 User Manuel. 1U 4 Fans Unit with Thermostat Sensor. Version 1.1 Copyright All Rights Reserved

INSTRUCTION MANUAL FOR MICROCOMPUTER BASED TEMPERATURE INDICATING CONTROLLER JCD-13A, JCR-13A

Tempco Part Number PCT30006 Temperature Control Enclosure with Relay Output for Tote Tank Heating Applications

Furnace Gas Monitor SD Operating Manual (PT2-163)

SA100. General Description. Features. Temperature Controller SA100. Corresponding to Various Applications. Simple Mounting on DIN Rail

ST710-KHJV.03. Wiring diagram. Product description. Temperature controller. Order number

S304 and S305 Dust Emission Monitors. User Manual. Distributor

No.THD51E To prevent accidents arising from the use of this product, please ensure the operator using it receives this manual.

CB103/CB403/CB PRODUCT CHECK 2. MOUNTING - * - / /Y INSTRUCTION MANUAL WARNING. 2.1 Mounting Cautions CAUTION RKC INSTRUMENT INC.

Smart transmitter/ Gas Detector Head SD-1. Operating Manual (PT2-160)

MICRO CONTROLLER S Z SERIES

Three-phase Thyristor Unit. 200 V AC Type THW-A1. Instruction Manual IMR02R01-E1 RKC INSTRUMENT INC.

OX100, OX102. Limiting-current type Oxygen Analyzer OX100, OX102. Bulletin 11M10A01-03E

TEMPERATURE CONTROL MODULE MODEL R3-TC2

47LV BEFORE USE... POINTS OF CAUTION INSTRUCTION MANUAL DC INPUT DIGITAL PANEL METER MODEL. (4 1/2 digit, LED display type)

SA200. General Description. Features. Temperature Controller SA200. Self-Tuning Algorithm. Close Vertical or Horizontal Mounting

JIR-301-M No.JIR31E To prevent accidents arising from the misuse of this instrument, please ensure the operator receives this manual.

Instruction Manual August sitrans CU 02

PSE-369A. KL4000 SERIES 100mm chart DOT-PRINTING TYPE HYBRID RECORDER

Smart Transmitter/Gas Detector Head SD-1GH. Operating Manual (PT2-169)

Model 144H. Product Data Sheet , Rev DB February Content

Indoor Carbon Monoxide Monitor EC-600. Operating Manual. Part Number: Revision: P1 Released: 3/22/17

Smart Transmitter/Gas Detector Head SD-1DGH. Operating Manual (PT2-170)

ARTIFICIAL INTELLIGENCE TEMPERATURE CONTROLLER

SA100L. General Description. Features. Temperature Limit Controller SA100L. Simple Mounting on DIN Rail. Over/Under Temperature Protection

Temperature Controller SA100. Initial Setting Manual IMR01J03-E1 RKC INSTRUMENT INC.

MODEL: 47LT. Digital Panel Meters 47 Series. [3] DISPLAY COLOR R: Red YR: Orange G: Green BG: Bluegreen B: Blue W: White. [4] POWER INPUT AC Power

OX100/OX102. Limiting-current type Oxygen Analyzer. Bulletin 11M10A01-03E

WIO200 Water In Oil measuring instrument

Digital Panel Meters 47 Series. DC INPUT DIGITAL PANEL METER (4 1/2 digit, LED display type) Model: 47LV OPERATING MANUAL

DIN RAIL MOUNTED INDICATING CONTOLLER DCL-33A INSTRUCTION MANUAL

Table of Contents 1. OVERVIEW SYSTEM LAYOUT SPECIFICATIONS FUNCTION... 11

DC200 Digital Dispenser Operating Manual

DCL-33A No.DCL31E To prevent accidents arising from the misuse of this controller, please ensure the operator receives this manual.

PSE-367C. AL4000 SERIES 100mm chart MULTI-POINT TYPE HYBRID MEMORY RECORDER

CN4800 Series CONTROLLER

MICROJET RECORDER (180mm)

GCS-300 No.GCS31E

AUR300C. Advanced Ultraviolet Burner Controller

YS1310 Indicator with Alarm Operation Guide

JIR-301-M No.JIR31E To prevent accidents arising from the misuse of this instrument, please ensure the operator receives this manual.

Operating Manual TR600

General Specifications

INSTRUCTION MANUAL. Laboratory Equipment Pty Ltd Ph: Fax:

User s Manual. YTA110, YTA310, YTA320, and YTA710 Temperature Transmitters. Manual Change No

DIGITAL METERS Large Display Temperature Meters Instruction Manual

General Specifications

MICROJET RECORDER (24-CHANNEL 180mm)

Important Supplementary Manual to the main Ezeio manual. 5. Section 2a: Introducing the 2400 input and output expansion field stations.

Universal controller for panel mounting Models CS6S, CS6H, CS6L

INSTALLATION INSTRUCTIONS

User s Manual YTA610 and YTA710 NEPSI Certification

Toll Free: Tel: Fax:

PLC INTERFACE UNIT CIT-200 INSTRUCTION MANUAL

Constant climate chamber with humidity

DESCRIPTIVE AND INSTALLATION INSTRUCTION MANUAL FOR MODEL AH1000, BH1000, AND EH1000 SERIES ANNUNCIATORS

Three-phase Thyristor Unit. 400 V AC Type THW-A4. Instruction Manual IMR02R02-E2 RKC INSTRUMENT INC.

SCHMIDT LED Measured Value Display MD Instructions for Use

Dusty / Dusty Ex Low-Cost Broken Bag Detection

Pump-Down Controller MODEL 4052

General Specifications

Furnace Gas Detector Head GD-A2400. Operating Manual (PT2-162)

TEMPERATURE CONTROLLER

Transcription:

User s Manual Model VJRK Limit Alarm (RTD for RTD Input Input Type) IM J01R21-01E 1. CAUTIONARY NOTES FOR SAFE USE OF THE PRODUCT This user s manual should be carefully read before installing and operating the product. The following symbol is used on the product and in this manual to eusure safe use. This symbol is displayed on the product when it is necessary to refer to the user s manual for information on personnel and instrument safety. This symbol is displayed in the user s manual to indicate precautions for avoiding danger to the operator, such as an electric shock. The following symbols are used only in this manual. IMPORTANT Indicates that operating the hardware or software in a particular manner may cause damage or result in a system failure. NOTE Draws attention to essential information for understanding the operations and/or functions of the product. 2. CHECKING THE PRODUCT SPECIFICATIONS AND THE CONTENTS OF THE PACKAGE (1) Model and Specifications Check Check that the model and specifications indicated on the nameplate attached to the side face of the main unit are as ordered. (2) Contents of the Package Check that the package contains the following items: VJRK: 1 User s manual (this manual: IM J01R21-01E): 1 Accessories: Tag number label: 1 sheet Range label: 1 sheet 3. GENERAL This plug-in type Limit Alarm for RTD input receives RTD signal. Each parameter setting can be changed using a PC (VJ PC-based Parameters Setting Tool) or the Handy Terminal (JHT200 ).. MODEL AND SUFFIX CODES VJRK-0 2 - T 0 0/ VJRK-0 - T00/ Model Model Number of outputs Number 2: 2 outputs of outputs 2: 2 outputs 6: 100-20 V AC/DC (Operating range: to 26 V) : 1-30 V DC (Operating range: 12 to 36 V) 6: 100-20 V AC/DC (Operating range: to 26 V) : Input 1-30 signal V DC (Operating range: 12 to 36 V) 1: Pt100 (ITS-0) Input 2: JPt100 signal (JIS') 1: 3: Pt100 Pt0 (JIS'1) (ITS-0) 2: : JPt100 (JIS') (IPTS-6) 3: Output Pt0 (JIS'1) signal : T: Pt100 Alarm (IPTS-6) output (2 points of relay contacts) Output Optional signal specification T: lank: Alarm With output socket (2 points of relay contacts) /SN: Without socket /DF: Fahrenheit display function Optional specification lank: With socket /SN: Without socket. MOUNTING METHODS.1 Wall Mounting Loosen the main unit-fixing screw to disconnect the main unit from the socket. Next, anchor the socket onto the wall with screws. Then, plug the main unit into the socket and secure the main unit with the main unit-fixing screw. Main unit-fixing screw Main unit <Mounting Dimensions> ±0.3 2. or more 22±0.2 Socket Unit: mm 2-M or 2-ø. or more Mounting screws Hole for main unit-fixing screw Keep this manual in a safe place. Fig..1 Network Solutions usiness Divisiion 2--32, Naka-cho Musashino-shi, Tokyo 10-0 Japan Phone: +1-22-2-1 Facsimile: +1-22-2-63 +1-22-2-661 IM J01R21-01E 1st 2nd Edition: : Aug. Nov. 201 2006 (YK)

2.2 DIN Rail Mounting Locate the VJRK so that the DIN rail fits into the upper part of the DIN-rail groove at the rear of the socket, and fasten the socket using the slide lock at the lower part of the socket. DIN rail Fig..2 (Rear of the socket) DIN rail Slide lock Push Fit into here DIN rail.3 Using a Duct Wiring duct should be installed at least 30 mm away from the top and bottom faces of the main unit. 6. INSTALLATION LOCATIONS Avoid the following environments for installation locations: Areas with vibrations, corrosive gases, dust, water, oil, solvents, direct sunlight, radiation, a strong electric field, and/or a strong magnetic field. If there is any risk of a surge being induced into the power line and/or signal lines due to lightning or other factors, a dedicated lightning arrester should be used as protection for both the product and a field-installed device.. EXTERNAL WIRING WARNING To avoid the risk of an electric shock, turn off the power supply and use a tester or similar device to ensure that no power is supplied to a cable to be connected, before carring out wiring work. Wiring should be connected to the terminals on the socket of the VJRK. The terminals for external connections are of M3 screws. Use crimp-on lugs for connections to the terminals. It is recommended that signal wires have a nominal cross-sectional area of 0. mm 2 or thicker, while the power cable has a nominal cross-sectional area of 1.2 mm 2 or thicker. Input signal A 1 3 L+ 10 6 3 2 1 11 10 Alarm-2 output ALM2 (NO) 2 COM Alarm-1 output ALM1 (NO) IMPORTANT Use of the product ignoring the specifications may cause overheating or damage. efore turning on the power, ensure the following: (a) voltage and input signal value applied to the product should meet the required specifications. (b) The external wiring to the terminals and wiring to ground are as specifications. Do not operate the product in the presence of flammable or explosive gases or vapors. To do so is highly dangerous. The product is sensitive to static electricity; exercise care in operating it. efore you operate the product, touch a nearby metal part to discharge static electricity. If an inductance (L) load such as auxiliary relays or solenoid valves is used, always insert a spark killer for diminishing sparks, such as a CR filter or a diode in parallel with the inductance load. Otherwise a malfunction or relay failure may occur. Refer to the following guidelines for a capacitor and resistor: Capacitor : 0. to 1 F with respect to a contact current of 1 A Resistor: 0. to 1 Ω with respect to a contact voltage of 1 V The power line and input/output signal lines should be installed away from noisegenerating sources. Otherwise accuracy cannot be guaranteed. The grounding resistance must be 100 Ω (JIS Class D grounding). The length and thickness of the grounding cable should be as short and thick as possible. Directly connect the lead from the ground terminal (terminal no. ) of the product to the ground. Do not carry out daisychained inter-ground terminal wiring.. DESCRIPTION OF FRONT PANEL AND CONNECTION OF SETTING TOOLS.1 Front Panel The communications connector on the front panel is used for setting up parameters using a PC (VJ PC-based Parameters Setting Tool) or the Handy Terminal (JHT200). The alarm indicator lamps for alarm 1 and alarm 2 light up if an alarm occurs. Communication connector Alarm indicator lamp (for alarm 1) Alarm indicator lamp (for alarm 2) ALM1 ALM2 N 11 GND COM Fig..1 Front Panel All Rights Reserved. Copyright 1, Yokogawa M&C Corporation IM J01R21-01E 2nd 1st Edition: : 2006.0.1-00

3.2 Connecting the Setting Tools Connect the modular jack conversion adapter (E6WH) to the JUXTA communication cable with -pin connector (F12EE) and then connect this adapter to the communication connector of JUXTA. JUXTA communication cable with -pin connector (F12EE) [Comes with VJ and JHT200] JHT200 Handy Terminal Modular jack conversion adapter (E6WH) [Comes with VJ] Dedicated adapter (EHA) [Comes with VJ] Dedicated cable (E6WK) PC with the [Comes with VJ] VJ installed Fig..2 Connecting the Setting Tools Note: The modular jack conversion adapter does not come with the JHT200 Handy Terminal. It is sold separately.. SETTING PARAMETERS Set the parameters using a PC (VJ PC-based Parameters Setting Tool) or the Handy Terminal (JHT200). Refer to the list of parameters in this manual and the user s manual for VJ PC-based Parameters Setting Tool (IM J01J-01E) or JHT200 Handy Terminal (IM JF1-02E)..1 Settings Related to Input.1.1 Input Type and Temperature Unit Select the RTD type to use from among Pt100-0, Pt100-6, JPt100 and Pt0 in D0: RTD TYPE. Pt100-0: ITS-0 (R 0 =100 Ω, R 100 /R 0 =1.31) Pt100-6: IPTS-6 (R 0 =100 Ω, R 100 /R 0 =1.30) JPt100: JIS (R 0 =100 Ω, R 100 /R 0 =1.316) Pt0: JIS 1 Select the temperature unit to use in D1: UNIT..1.2 Input Hard Range Select the input hard range from among AUTO, HIGH and MIDDLE in D1: SELECT RANGE. AUTO: Sets the most appropriate input hard range automatically with respect to the input range to be set. HIGH: For a span of 130 Ω or more in an input range of 0 to 20 Ω based on the reference resistane table MIDDLE: For a span of 3. Ω or more in an input range of 0 to 16 Ω based on the reference resistane table NOTE.1.3 Input Range Set the 0% value of input range in D22: INPUT1 L_RANGE and the 100% value of input range in D23: INPUT1 H_RANGE numerically within the specified range. Input type Operation guaranteed range ( C) Pt100 (ITS-0) Pt100 (IPTS-6) JPt100 (JIS') Pt0 (JIS'1) 200 to 660 200 to 660 200 to 10 200 to 6.1. urnout Select the direction of burnout action from among UP, DOWN and OFF in D30: URN OUT..1. Wiring Resistance Correction When an error occurs due to the influence of the input wiring resistance, the wiring resistance can be corrected automatically. Apply a stable input as shown below and select EX- ECUTE in P01: WIRING R. The correction is also required when the direction of burnout action is changed from UP (DOWN) to DOWN (UP) or the wiring for input is changed. Short-circuit at the cable end. VJRK VJ or JHT200.2 Settings Related to Alarm Output.2.1 Alarm Setpoint Set the alarm setpoints of alarm 1 and alarm 2 in E01: SET POINT1 and E02: SET POINT2 numerically. Setting range: 0 to 100% of input range Setting resolution: 0.1 C.2.2 Direction of Alarm Action Select the direction of alarm-1 action and that of alarm-2 action from among HIGH ALM (high-limit alarm) and LOW ALM (low-limit alarm) in E0: ALM1 ACTION and E06: ALM2 AC- TION. To activate alarm status when input signal alarm setpoint, select HIGH ALM. To activate alarm status when input signal alarm setpoint, select LOW ALM..2.3 Hysteresis Set the alarm-1 and alarm-2 hysteresis in E0: HYSTER- ESIS1 and E0: HYSTERESIS2. Hysteresis is a value added to the alarm setpoint in order for an alarm status to be released (to normal) after the alarm status has been activated. The alarm status will be released in the following conditions, depending on the direction of alarm action. * When HIGH ALM (high-limit alarm) is set: Alarm is released when input signal < (alarm setpoint - hysteresis). * When LOW ALM (low-limit alarm) is set: Alarm is released when input signal > (alarm setpoint + hysteresis). Setting range: 0 to 100% of input range Setting resolution: 0.1 C The conditions for the input hard range (HIGH and MIDDLE) are specified for operations within the range of accuracy rating. The input range may be set to a range not meeting these conditions, but take note of accuracy limitations. Similar accuracy limitations exist even when AUTO is selected. For more information on acuracy limitations, see the general specifications of VJRK (GS J01R21-01E). IM J01R21-01E 2nd 1st Edition: : 2006.0.1-00

.2. Alarm ON Delay and Alarm OFF Delay Set the alarm-1 and alarm-2 ON delays in E11: ON DELAY1 and E12: ON DELAY2 and then alarm-1 and alarm-2 OFF delays in E13: OFF DELAY1 and E1: OFF DELAY2. An alarm ON delay is the condition monitoring time from the establishment of alarm conditions to its output; an alarm OFF delay is the condition monitoring time from the establishment of return-to-normal conditions to its output. Setting range: 0 to seconds Setting resolution: 1 second (However, about 0.2 second is to be added to the set time to prevent wrong operation.) For example, when an alarm ON delay is set to 1 second, alarm output is generated if alarm status continues for 1 second or more after the input value exceeds the alarm setpoint. Further, when an alarm OFF delay is set to 2 seconds, alarm output is released if normal condition continues for 2 seconds or more after the input value has returned to normal from the alarm status..2. Direction of Relay Action Select the direction of relay energizing in alarm-1 normal condition and alarm-2 normal condition from among NRM DE-ENERGIZED (de-energized under normal condition) and NRM ENERGIZED (energized under normal condition) in E1: RL1 ACTION and E16: RL2 ACTION and set them. 10. DESCRIPTION OF ALARM ACTIONS This chapter describes examples of alarm actions under the following conditions. Item Alarm 1 Alarm 2 Parameter Setpoint Parameter Setpoint Direction of alarm action E0 : ALM1 ACTION High-limit alarm E06 : ALM2 ACTION Low-limit alarm Alarm setting E01 : SET POINT1 0% E02 : SET POINT2 1% Hysteresis E0 : HYSTERESIS1 10% E0 : HYSTERESIS2 % Alarm ON delay E11 : ON DELAY1 1 sec E12 : ON DELAY2 3 sec Alarm OFF delay E13 : OFF DELAY1 2 sec E1 : OFF DELAY2 sec Description of alarm actions The alarm is output if the condition where the input value is 0% or more of highlimit alarm continues for 1 second or more. After the alarm is output, when the condition where the input value is less than 0% of high-limit alarm continues for 2 seconds or more, the status returns to normal. The alarm is output if the condition where the input value is 1% or less of low-limit alarm continues for 3 seconds or more. After the alarm is output, when the condition where the input value is more than 20% of the low-limit alarm continues for seconds or more, the status returns to normal. [%] 100 Alarm conditions Alarm conditions High-limit alarm ON Normal conditions [1] [2] Normal conditions High-limit alarm OFF [1]: Alarm status does not continue for more than 1 second after the alarm conditions are at alarm 1. [2]: Normal status does not continue for more than 2 seconds after the normal conditions are at alarm 1. [3]: Alarm status does not continue for more than 3 seconds after the alarm conditions are at alarm 2. []: Normal status does not continue for more than seconds after the normal conditions are at alarm 2. 0 Alarm-1 setpoint (0%) Alarm-1 hysteresis (10%) 60 0 20 1 1 sec 2 sec Alarm-1 ON delay Alarm-1 OFF delay Alarm-2 hysteresis (%) Alarm-2 setpoint (1%) Alarm conditions Alarm conditions Alarm-2 ON delay Low-limit alarm ON Normal conditions Normal conditions Alarm-2 OFF delay [3] 3 sec [] sec Low-limit alarm OFF 0 Elapsed time 1 sec Alarm-1 action Normal Alarm Normal Alarm-2 action Normal Alarm Normal All Rights Reserved. Copyright 1, Yokogawa M&C Corporation IM J01R21-01E 2nd 1st Edition: : 2006.0.1-00

11. LIST OF PARAMETERS No. Item Display 01 Model MODEL 02 Tag No. TAG NO 03 Self-check result SELF CHK Display items A Display 1 DISPLAY1 A01 Input value INPUT1 A0 Output value 1 OUTPUT1 (*1) A0 Alarm-1 status ALM1 STATUS A0 Alarm-2 status ALM2 STATUS A Status STATUS (*2) A6 Rev No. REV NO A Menu Rev MENU REV A60 Self-check result SELF CHK Setting items (*3) D Setting (I/O) SET(I/O) D01 Tag no.1 TAG NO.1 D02 Tag no.2 TAG NO.2 D03 Comment 1 COMMENT1 D0 Comment 2 COMMENT2 D0 Input sensor type SENSOR TYPE (*1) D0 RTD type RTD TYPE D1 Unit UNIT D1 Input hard range selection SELECT RANGE D22 Input low range INPUT1 L_RANGE D23 Input high range INPUT1 H_RANGE D30 urnout URN OUT D3 Direction of output-1 action OUT1 DR (*1) D60 Self-check result SELF CHK Adjusting items (*3) P Adjustment ADJUST1 P01 Wiring resistance correction WIRING R P02 Zero adjustment of input 1 ZERO ADJ1 P03 Span adjustment of input 1 SPAN ADJ1 P12 0% adjustment of output 1 OUT1 0% (*1) P13 100% adjustment of output 1 OUT1 100% (*1) P60 Self-check result SELF CHK No. Item Display Display 2 DISPLAY2 01 Input value INPUT1 0 Output value 1 OUTPUT1 (*1) 0 Alarm-1 status ALM1 STATUS 0 Alarm-2 status ALM2 STATUS 60 Self-check result SELF CHK E Setting (alarm output) SET(ALM) E01 Alarm-1 setting SET POINT1 E02 Alarm-2 setting SET POINT2 E0 Direction of alarm-1 action ALM1 ACTION E06 Direction of alarm-2 action ALM2 ACTION E0 Alarm-1 hysteresis HYSTERESIS1 E0 Alarm-2 hysteresis HYSTERESIS2 E11 Alarm-1 ON delay setting ON DELAY1 E12 Alarm-2 ON delay setting ON DELAY2 E13 Alarm-1 OFF delay setting OFF DELAY1 E1 Alarm-2 OFF delay setting OFF DELAY2 E1 Direction of alarm-1 relay action RL1 ACTION E16 Direction of alarm-2 relay action RL2 ACTION E60 Self-check result SELF CHK Test items (*3) Q Test TEST Q02 Forced output 1 OUT1 TEST (*1) Q0 Forced output (alarm 1) ALM1 TEST Q0 Forced output (alarm 2) ALM2 TEST Q60 Self-check result SELF CHK *1 : The indications and settings of the parameters are not available. *2 : The status is displayed for service personnel to see history records. *3 : To call the parameter setting items D, E, P and Q using the JHT200 Handy Terminal, execute the following operation: Press F1 ENTER keys. D, E, P or Q key enters above. IMPORTANT Do not change the settings of the items marked (*1) in the List of Parameters above after the delivery of the product. Doing so may result in a malfunction or a system failure. IM J01R21-01E 1st 2nd Edition: : 2006.0.1-00

6 12. MAINTENANCE The product enters the operable status as soon as the power is turned on, but requires 10 to 1 minutes of warm-up to meet the performance requirements. 12.1 Calibration Apparatus Calibrator (Yokogawa Meters & Instruments CA1 or equivalent): 1 Setting tool for adjustment (Refer to.2 Connecting the Setting Tools in this manual.) 12.2 Calibration Procedure (1) Connect the instruments as shown in Fig.12.1 and Fig..2. (2) Produce the input signal equivalent to 0% of the input range from the calibrator to the product. Then, read the input value of Display items, A01: INPUT1 using the VJ or JHT200 and check that the input value is within the rated accuracy range. Take the same procedure for the input signal equivalent to 2, 0, and 100% of the input range and check that the input values are within the rated accuracy range. For alarm output, check the relay action by the alarm indicator lamp or resistance of output terminals. If the input values are out of the rated accuracy range, adjust the input signal level referring to the user s manual for VJ PC-based Parameters Setting Tool (IM J01J-01E) or for JHT200 Handy Terminal (IM JF1-02E). Input Calibrator A 1 3 6 3 2 1 Alarm-2 output 2 ALM2 (NO) COM Calibrator L+ 10 N 11 11 10 Alarm-1 output ALM1 (NO) COM Calibrator GND Fig. 12.1 All Rights Reserved. Copyright 1, Yokogawa M&C Corporation IM J01R21-01E 2nd 1st Edition: : 2006.0.1-00