Reflective Beam Smoke Detector

Similar documents
PHOTOELECTRIC REFLECTIVE BEAM DETECTOR MODEL SRA-ET. Mounting Guidelines

PHOTO-ELECTRIC BEAM DETECTOR MODEL SPB-ET INSTALLATION PROCEDURE

ALK-V PHOTOELECTRIC SMOKE SENSOR

INSTALLATION AND MAINTENANCE INSTRUCTIONS 6500R AND 6500RS REFLECTIVE TYPE PROJECTED BEAM SMOKE DETECTOR

INSTALLATION AND MAINTENANCE INSTRUCTIONS 6500R AND 6500RS REFLECTIVE TYPE PROJECTED BEAM SMOKE DETECTOR

Installation and Operation Manual

INSTALLATION AND MAINTENANCE INSTRUCTIONS NFXI-BEAM AND NFXI-BEAM-T REFLECTED TYPE PROJECTED BEAM SMOKE DETECTOR

TX7130. Conventional Reflective Beam Detector Installation and Operation Manual. TANDA UK Technology Copyright 2015, All right reserved.

INSTALLATION AND MAINTENANCE INSTRUCTIONS 6500 AND 6500S REFLECTED TYPE PROJECTED BEAM SMOKE DETECTOR

FIRERAY 2000 EExd Hazardous Area Smoke Detector Installation Guide

MR300 OPTICAL SMOKE DETECTOR RANGE PRODUCT APPLICATION & DESIGN INFORMATION

Reflective Optical Beam Smoke Detector User Guide

IFD-E Flame Detector User Manual

Fireray Application and. Installation Guide FEATURES. Range metres. 12V to 24V dc operation. Selectable alarm thresholds

Line Smoke Detector LRMX

IFD-E Flame Detector User Manual

EVC-P CONVENTIONAL PHOTOELECTRIC SMOKE DETECTOR. instruction manual. evolution EVC-P Conventional Photoelectric Smoke Detector

Model DRD-AS Conventional Infrared Flame Detector User Manual Ver. 1.0

MODEL 6200 ANALOGUE ADDRESSABLE OPTICAL BEAM SMOKE DETECTOR

FIRERAY 5000 range USER GUIDE

IMPORTANT. PLEASE NOTE: The infrared beam path MUST be kept clear of obstructions at all times!

Installation, Operating and Maintenance Manual

ED820-24V MODEL INSTRUCTION MANUAL. fire DETECTOR

PNC 1000 SERIES 2, 4, 8 Zone Fire Alarm Control Panel

Open-area Smoke Imaging Detection (OSID)

Motorised Infrared Optical Beam Smoke Detector. User Guide

E-PDD Duct Smoke Detector Installation Sheet

Motorised Infrared Optical Beam Smoke Detector. User Guide

5000 INSTALLATION GUIDE

SANDOR QUAD/ESA. Double beam. POLITEC s.r.l. Installation And commissioning manual

APPLICATION NOTE. Document Type. Application Note. Document Title. Date January Version DS0167/Iss 2. ESP Technical Summary

TITLE SLIDE. FIRERAY2000 EExd OPTICAL BEAM SMOKE DETECTOR. Doc. No: Copyright Fire Fighting Enterprises Ltd.

PHOTOELECTRIC DUAL BEAM DETECTOR R4222 RECEIVER INDICATORS 1

Open-area Smoke Imaging Detection (OSID)

Apollo Intelligent Auto Aligning Beam Detector. User Guide

Instructions AutroFlame IR Flame Detector BG-201/BG-21

Series 65 Product Guide MAN 3036

MINERVA S200Plus. Fire Detection. Triple Waveband Infra-Red Flame Detection. Features: Minerva S200PLUS

Optical Smoke Detector Heat Detector Manual Call Point Output Unit Isolator

English. Series. Installation and Use Manual

HART XL High Sensitivity Smoke Detection

Movement Detector GJD 300

S200Plus Triple Infra Red Flame Detector Triple Waveband Infra-Red Flame Detection

English. Italiano. Português. Françias. Español

l High precision, computer-designed parabolic optical system,. Dual element pyro-electric sensor.

D-Tect 2 GJD300 Quad PIR Movement Detector

Ceiling PIR HS presence detector 1-10V, low temperature. PIR Sensor. IR Receiver. Light Level Sensor. Status LEDs. IR Receiver

Conventional Smoke Detectors KFAPO

FR-A180 FR-A360. Occupancy detector. Use

FEC400 Series. Installation Manual

D-TECT Introduction. Connecting the Unit. Quick Installation. Multi Beam Alignment & Masking. Mounting the Unit

C-9105R Conventional Reflective Beam Detector Installation and Operation Manual. (Issue 2.01, February 2006)

FIRE DETECTOR TYPE ED816 ZONE 5 ZONE 4 ZONE 6 ZONE 7 FIRE FIRE FIRE FIRE FAULT FAULT FAULT FAULT DISABLED DISABLED DISABLED DISABLED OFF OFF OFF OFF

Open-area Smoke Imaging Detector. Engineering Specification

Table of Contents. Page Quick Set-up Instructions 1. Theory of Operation 2. Specifications 3. TM 1003W Controls and Connections 4

INFRARED MODULATED BARRIERS

DI601AM Outdoor PIR/AM Detector Installation Sheet

AX-100TFR/AX-200 TFR INTRODUCTION 1-1 BEFORE YOUR OPERATION BATTERY OPERATED PHOTOELECTRIC DETECTOR. Warning FEATURES. Caution. Warning.

This training course discusses the correct use of Infrared (IR) Optical Beam Smoke Detectors for the protection of lives, equipment and property.

Motion Detectors. Whatever the application, there s a Paradox motion detector that will suit your needs and surpass your expectations.

DS9370-BEL. Installation Instructions TriTech Ceiling Mount PIR/Microwave Intrusion Detector

Elite. GJD022 /GJD023 35m External PIR. Multi Beam Lens Data

TITLE SLIDE FIRERAY50/100R OPTICAL BEAM SMOKE DETECTOR. Doc. No: Copyright Fire Fighting Enterprises Ltd.

Passive Infrared Motion Detector 5420/90P. Installation Instructions

INTELLIGENT FIRE TECHNOLOGY. Twinflex and Multipoint V3. User Guide (TO BE RETAINED BY USER) Issue 3

SERIES 65 ENGINEERING PRODUCT GUIDE

BEAM355A, BEAM355SA Single-ended Reflected Type Projected Beam Smoke Detector

TX7100. Intelligent Addressable Optical Smoke Detector Installation and Operation Manual. TANDA UK Technology Copyright 2015, All right reserved.

SAFETY MANUAL. FL4000H and FL4000 Multi-Spectral Infrared Flame Detectors

DD205RF/TX Detector Installation Sheet

BEAM355, BEAM355S Single-ended Reflected Type Projected Beam Smoke Detector

D-TECT Dual Tech. GJD360 Triple Technology External Detector

PHOTOELECTRIC BEAM SENSOR PR-11BE : OUTDOOR 3.3 to 36ft. (1 to 11m) : INDOOR 3.3 to 49ft. (1 to 15m)

TrueAlarm Smoke Detectors

LaserFOCUS VLF-250 Engineering Specification

Intelligent addressable fire alarm control panel

LC1 & 2. Fire Alarm Panel 6\VWHPLQVWDOODWLRQRSHUDWLQJ PDLQWHQDQFH LQVWUXFWLRQV

D-TECT 2 IP. GJD230 IP Motion Detector

Ceiling PIR HS presence detector. Product Guide. Overview. Features

Description. Optex Incorporated

BT1 SINGLE ZONE FIRE ALARM SYSTEM OPERATORS MANUAL

EFBW series - BiWire Ultra control panel

D-TECT 3 IP. GJD260 IP Motion Detector

I-9105R Intelligent Reflective Beam Detector Installation and Operation Manual. The Intelligent Solution CONTENTS

Occupancy Sensor LS Descriptions. Product Profile. Technical Specifications

I-9105R Intelligent Reflective Beam Detector Installation and Operation Manual. (Issue 2.03 February 2006)

Evolution Analogue Addressable Fire System

FTEN1, FTEN2, & FTEN4 1, 2 & 4 ZONE FIRE DETECTION AND ALARM CONTROL PANELS

OPTICAL SMOKE DETECTOR Model: SPD-KADET

A Guide To BS Understanding the selection, spacing and siting of detectors

Installation Instruction Manual ILS-S

Fact File 66. Guide to Beam Smoke Detectors

Zerio Plus EDA-R6000 Radio Combined Optical Smoke Detector and Sounder Installation Instructions

Advanced DIGITAL Wired PIR Motion Detector

Conventional Fire Detection

Operating Instructions

Installation and user manual for the BiWire / Conventional Repeater Panel

TrueAlarm Analog Sensing

End To End Optical Beam Smoke Detector. Additional Information

Analogue addressable devices

Transcription:

Reflective Beam Smoke Detector SRA-ET Features! 5-30m range! Small flat reflector! Powered directly from the zone! Full line continuity options! Automatic compensation! Approved by LPCB & VdS Description Model SRA-ET is a reflective beam smoke detector consisting of an emitter/receiver unit and reflector plate that works over a distance of 5-30m, providing a maximum coverage of 450m 2. The detector is powered directly from the zone, so no auxiliary power supplies are required, so when the zone is reset the detector is reset automatically. The SRA-ET can also be interfaced onto Hochiki s ESP systems by using a CHQ-MZ Mini Zone Monitor or a CHQ-Z Dual Zone Monitor. The SRA-ET comes complete with a Reflector and Termination Module which fits directly on to a standard U.K. dual back box, this allows the detector be surface or flush mounted. Line continuity options can be selected on the termination module and these are based on the Schottky or Zener diode method. The SRA-ET is not solar blind so care should be taken when installing the detector as false alarms may occur. In areas affected by sunlight the Hochiki SPB-ET Beam Detector should be employed. Specification Ordering Code SRA-ET Operating Voltage 15-30Vd.c. Quiescent Current (typ) 350µA Maximum Current In Alarm 50mA Operation Range (m) 5-30 Sensitivity 30% Operating Temperature Range -10 C to +50 C Storage Temperature Range -30 C to +70 C Maximum Humidity 95%RH - Non condensing (at 40 C) Colour / Case Material Ivory White / ABS Weight (g) / Dimensions (mm) (SRA-ET) 700 / H152 x W122 x D80 (Reflector) 50 / H190 x W190 x D3 Line Continuity Options (Interface Kit) Schottky/Zener Approvals LPCB BS5839 Part 5 / pren54 Part 12 VdS pren54 Part 12

PHOTOELECTRIC REFLECTIVE BEAM DETECTOR MODEL SRA-ET Installation Instructions

Contents 1. Overview...3 1.1. General Description...3 1.2. Detection principle...3 2. Installing the detector...4 2.1. Siting...4 2.2. Installation...5 2.3. Opening the detector cover...5 2.4. Field wiring & line continuity...6 2.5. Reflector - Installation Procedure...8 2.6. Adjustment & Calibration procedure...8 2.7 Testing the SRA-ET...10 3. Maintenance...11 3.1. General...11 3.2. Visual check...11 3.3. Operation checks...11 3.4. Precautions for insulation resistance checking... 11 3.5. Re-initialisation after cleaning or re-adjustment...11 4. Summary of the SRA-ET's functions...12 4.1. Alarm signal output and indicator lamp...12 4.2. Fault signal output and indicator lamp...12 4.3. Indication of normal operation...12 4.4. Total obscuration of the beam...12 4.5. Automatic compensation for change of SRA-ET's signal strength...13 5. Specification...14 6. Troubleshooting... 15 6.1. Monitor LED fails to flash...15 6.2. Fire signal continues after reset...15 6.3. Fault signal cannot be reset...15 6.4. Beam detector generates a fire but panel does not register the condition...16 6.5. Beam detector generates a fault but panel does not register the condition...16 7. Installation guide lines...17 7.1. General installation conditions...17 7.2. Installation in Saw-tooth type ceilings...18 7.3. Installation in circular type ceilings...18 7.4. Installation in sloped ceilings...19 7.5. Installation in a monitor roof...19 7.6. Installation in corridors or aisles...20 7.7. Installation precautions...21 7.8. Smoke patterns appropriate to the consideration of beam detector installation...22 Page 2 2-3-0-365/ISS3/OCT99

1. Overview 1.1. General Description The Photoelectric reflective beam detector consists of the SRA-ET unit and a reflector, which face each other at a distance of between 5 and 30 metres. In the event of fire the smoke generated will decrease the amount of near infrared light incident on the SRA-ET, this decrease is electronically interpreted to identify the occurrence of fire. An important feature of the detector is that it monitors the protected space linearly. This enables the detector to identify a fire before it spreads, even when the smoke is scattered over a large area. The fire detection sensitivity is factory set at 30% beam obscuration and cannot be altered. 1.2. Detection principle A near infrared-pulsed beam generated by the SRA-ET and is reflected back to the unit, where it is converted into an electrical signal. This signal is then amplified and applied via an A/D converter to a microprocessor. The normal state signal (the initial beam data) once stored in the microprocessor is used as a reference for comparison with subsequent beam signals. When there is sufficient difference between actual beam strength and stored reference data to indicate the occurrence of a fire, then a fire signal is produced. The microprocessor also provides compensation for a change in received signal value with time, caused by contamination of the optics or slight alignment changes. The processed signal is adjusted at a rate of ±1% towards the reference data every 20 minutes. When the limit of compensation is reached the microprocessor will automatically produce a fault signal. Note: To meet with current standards if the SRA-ET is totally obscured then a fire condition will be generated. 2-3-0-365/ISS3/OCT99 Page 3

2. Installing the detector 2.1. Siting Select a suitable position for the installation of both SRA-ET and reflector, such that there are no visible obstructions between them. Remember that the beam detector works on the principle of reduction of light between the SRA-ET and reflector. If there is any possibility of an object remaining within the beam for a few seconds then the siting of the detector is unsuitable. For mounting either the SRA-ET or reflector it is important to establish that the mounting place such as the wall is solid and that the beam detector alignment will be rigid. The wall may appear to be solid, but may be subject to twisting or other changes when the temperature outside the building varies greatly during one day, for instance on cold, frosty days. The installer must ensure that the beam will not be subject to misalignment due to changes in the building itself. The spacing and siting in specific types of locations is covered in section 7. The beam detector must not be installed in the following locations:! Where the ceiling height is greater than 40m! A roof top or place where open air circulates! Where the distance between top and bottom of the space is less than 0.5m! Where objects such as ceiling beams or girders are within 75cm of the beam axis! In locations where a large amount of dust, fine powder or water vapour is present! In locations such as kitchens where smoke occurs normally! In locations which are exposed to extremely high temperatures! Where access to the beam detector is impossible for maintenance purposes! Where the rigid fixing of either the SRA-ET or reflector is impossible! Where access to the beam detector to align and set is impossible! Where there is not a clear line of site between the Receiver and Reflector/Emitter Warning: The SRA-ET is not solar blind, therefore the SRA-ET or reflector should not be installed where they can be subjected to direct or reflected sunlight, i.e. via adjacent walls and reflective surfaces. It is recommended that in these locations or where the beam detector may be surrounded by glass, the SPB-ET Beam Detector should be fitted. Page 4 2-3-0-365/ISS3/OCT99

2.2. Installation Please check that the beam detector contains the following components so installation can be carried out.! 1 SRA-ET! 1 Reflector (enclosed in packaging)! 1 Mask! 1 Installation manual! 2 Fixing screws! 1 SRA-ET mounting plate (termination module PCB on the back) The termination module is designed to facilitate the installation of the SRA-ET beam detector to fire cables using a standard surface/flush dual gang installation box or the Hochiki SRA-ET Back Box. The module also provides three types of fault monitoring configurations, simple beam reset and remote fire indication. 2.3. Opening the detector cover Removal of the detector can be achieved by unscrewing the outer cover locking screw and pulling the cover forward and then lifting the cover off of the locating slots at the top of the fixing plate, the cover is then retained by a anti-drop cable. The fixing plate screws should then be loosened (Figure 4-1 & Figure 4-3) and the beam assembly can then be removed. Figure 1 - opening the detector housing 2-3-0-365/ISS3/OCT99 Page 5

2.4. Field wiring & line continuity The connection of this unit requires the use of a dual gang installation box, either flush mount or surface mount or the Hochiki SRA-ET Back Box. Suggested types are MK897 ALM surface mount, MK862 ZIC flush mount, but any equivalent type is usable providing that it has a minimum depth of 25mm. This item should be firmly fixed to the wall or other suitable mounting point first. With reference to the wiring diagram Figure 2 & Figure 3 ensure that the field wiring is terminated into the dual gang installation box. The Termination Module can be configured to provide correct operation for three different types of zone fault indication, which provide the same fault detection functions as Hochiki's conventional detector bases when the detector heads are removed. The configuration is achieved using jumpers at the top of the termination PCB ( refer to figure 3 ) and the selection should be made according to the type of fire alarm control panel being used. If the SRA-ET is being used with the CHQ-MZ/Z then the jumpers need to be set to the normal mode. Normal:- No line continuity option (zone is open circuit during fault). Jumpers LK1, LK4 & LK6 ARE MADE, all other jumpers are removed. Zener:- Line continuity using a Zener clamp (produces detector removal fault at the control panel). Jumpers LK2 & LK5 ARE MADE, all other jumpers are removed. (For Protector Alarms Panels). Schottky:- Line continuity using a Schottky diode (produces detector removal fault at the control panel). Jumpers LK1, LK3, LK4 & LK6 ARE MADE, all other jumpers are removed. Note: The Termination Module is factory configured for Schottky diode line continuity. If in doubt check the correct line continuity for the control panel. Warning: When the Zener option is used it must be connected to a control panel, which is able to use this type of option. If connected either to an unsuitable panel or a 24V-power supply the interface could be damaged due to over-current. Figure 2 - Termination module wiring diagram Page 6 2-3-0-365/ISS3/OCT99

Figure 3 Cable Termination 8 way grey connector Unplug the 8 way grey connector from the end of the Termination PCB (Figure 4-4). Install the wires into the correct position and secure by the terminal screw (Figure 3). Ensure the grey connector is facing upwards and that the cables are insulated and neatly located into the base of the installation box. Plug the grey connector back into the PCB then connect the pre-wired ribbon cable assembly to the socket on the back plate (Figure 4-2), the back plate should then be screwed to the back box. Fix the beam assembly to this by fitting the locating slots under the fixing screws (4-1) and pushing the beam up until the locating tabs can be dropped into the back plate (4-3). The top fixing screws should then be tightened, and the cover fitted to the beam detector once the adjustment and calibration procedure has been completed (see section 2.6). Figure 4 Termination module assembly 4-4 4-2 4-3 4-1 2-3-0-365/ISS3/OCT99 Page 7

2.5. Reflector - Installation Procedure Reflector to wall mounting: The reflector should be mounted using the 5mm fixing holes onto a flat surface with suitable screws, care should be taken not to over tighten these screws as this could damage or distort the reflector. Figure 5 Reflector with mask Figure 6 Reflector without mask 50mm x 50mm reflector Reflector mask If the SRA-ET is being used over a distance of 5m-15m then the mask should be fitted to the reflector (Figure 5). From distances of 15m-30m then the mask must not be fitted to the reflector (Figure 6). 2.6. Adjustment & Calibration procedure The adjustment procedure should be carried out by powering up the SRA-ET and setting the switch to calibrate; at this time the yellow LED will start to flash. Then, using the sight holes and alignment adjustment screws, the detector should be adjusted so the reflector can be seen in the centre of the sight hole. If the reflector is being used with the mask then the detector must be adjusted until the black dot on the reflector is in the centre of the site hole. Page 8 2-3-0-365/ISS3/OCT99

Alignment with mask Alignment without mask Horizontal adjustment Vertical adjustment When setting the SRA-ET up the set up switch must be set to calibrate, once alignment is completed as above then the switch must be returned to the normal position. - Normal - Calibrate Indication LED s The set up switch should now be set to the normal position, at this time the yellow and green operating LED s will be flashing this should last for one minute as the detector automatically adjusts. When this has been completed the yellow LED will extinguish and the green LED will continue to flash. If the adjustment isn t completed satisfactorily then the yellow LED will flash on its own. The cover should now be fitted and operation tests should now be carried out as described in section 2.7. The SRA-ET has three LED s mounted underneath the unit, these are yellow, green and red and are illuminated depending on the current state of the SRA-ET. Please find below a table showing the various states of the SRA-ET and which LED s will be illuminated. LED 1 LED 2 LED 3 SRA-ET state Green Yellow Red Beam in set up mode Operating satisfactorily Beam in fault or calibration Beam in Fire See Note 1 See Note 1! - LED Flashing (once every 3 secs)! - LED illuminated Note 1: The Green and Yellow LED may flash depending on the zone voltage in alarm. 2-3-0-365/ISS3/OCT99 Page 9

2.7 Testing the SRA-ET The reflector is marked with graduations between 1 and 9, which equates from 10% through to 90%. The SRA-ET can be tested by obscuring 60% of the reflector (Figure 7) with a material that is non reflective and impervious to infra red light, it will then take 11 to 16 seconds for the beam detector to go into a fire condition. A non-operation test can be carried out by obscuring 40% of the reflector (Figure 8). Figure 7 ~ Operation test Note: - As shown above, up to graduation number 6 is obscured Figure 8 ~ Non-operation test Note: - As shown above, up to graduation number 4 is obscured Page 10 2-3-0-365/ISS3/OCT99

3. Maintenance 3.1. General The detector contains an automatic compensation function, which allows the detector to operate correctly even when the amount of signal reaching the SRA-ET has changed (the compensation rate is ±1%/20 mins). This means that minor changes due to contamination and beam alignment will not affect the sensitivity of the detector. There is of course a limit that the detector can compensate for and this is -50% and +50% of the initial setting. In order to maintain proper performance the detector should be checked every six months. 3.2. Visual check Check the condition of both the reflector and SRA-ET for physical damage or any other condition that might impair proper operation. Ensure that both the SRA-ET and reflector are still firmly secured to the wall or other fixing point. If necessary clean the lens cover or reflector with a damp soft cloth. Washing liquid, alcohol or detergent must not be used. 3.3. Operation checks Perform the sensitivity check function as defined in section 2.7. 3.4. Precautions for insulation resistance checking If the wiring to a beam detector is to be tested for insulation resistance using a high voltage tester such as a Megger, the wiring to the beam detector must be disconnected from the detector by disconnecting the white terminal connector from the PCB. 3.5. Re-initialisation after cleaning or re-adjustment Because the beam detector contains sophisticated processing algorithms to take account of fluctuations in the beam intensity and alignment, if during routine maintenance the beam detector lenses have been cleaned or re-aligned then it will be necessary to make the detector read and store its initial value. This can be achieved by moving the set up switch to the calibration position for 10 seconds and then moving it back to the normal position. 2-3-0-365/ISS3/OCT99 Page 11

4. Summary of the SRA-ET's functions 4.1. Alarm signal output and indicator lamp When the beam is obscured by an amount that exceeds the sensitivity setting of the detector then a fire signal is produced lighting the red LED on the SRA-ET. It should be noted that the SRA-ET has a sophisticated processing and analysing circuit and therefore a fire will not occur immediately the obscuration exceeds the sensitivity value, but will take typically 11 to 16 seconds to produce the fire signal. The fire decision is based on an averaging technique and therefore the time to fire alarm will vary depending on the level of obscuration and the sensitivity setting. 4.2. Fault signal output and indicator lamp 4.2.1. General The beam detector may produce a fault condition for one of many different reasons, which will depend on whether the detector has just been set up or is in normal operation, when this occurs the yellow fault LED on the SRA-ET will be illuminated and flash. 4.2.2. After adjustment/re-initialisation The beam detector will produce a fault after or during adjustment for one of the following reasons:! The set up switch was left in the calibrate position! The signal strength is too high or too low. 4.2.3. During normal operation The beam detector will produce a fault during normal operation for one of the following reasons:! The limit of contamination has been reached. The detector is only able to compensate for contamination or alignment change up to a certain point 4.3. Indication of normal operation When the SRA-ET has been set up correctly then the green LED mounted underneath the case will flash every 3 seconds to confirm that the detector is operating satisfactorily. 4.4. Total obscuration of the beam If the beam detector is totally obscured, the green LED will continue flash and the red fire LED will illuminate, a fire signal will then be produced at the fire alarm panel. Page 12 2-3-0-365/ISS3/OCT99

4.5. Automatic compensation for change of SRA-ET's signal strength From the time that the beam detector is initialised, the signal at the SRA-ET is checked every 20 minutes for variation and will be altered by ±1% back towards the original stored value. The beam detector will store the initialisation value, when the set up switch is moved from calibrate to normal. 2-3-0-365/ISS3/OCT99 Page 13

5. Specification Installation Environment Indoor use only Principle of Operation Light beam obscuration (near infra-red) Rated voltage 24V (nominal) Operating voltage range 15.0 ~ 30V dc Peak surge voltage 42V Current in alarm 50mA Quiescent current 350µA Compensation method 1% every 20 mins. towards initial value Compensation limits +50% to -50% of the initial value Fire condition Red fire LED on SRA-ET illuminated & 470 ohm across zone Fault condition Yellow fire LED on SRA-ET flashes Monitor condition Set up condition: Both green and yellow LED's flash Normal operation: Green LED flashes Monitor condition flash repetition time 1 per 3 seconds Minimum time needed to reset from fire 100msec Minimum time needed before beam can reset after fire produced 3 seconds Operating temperature range -10 C to 50 C Maximum humidity 95% R.H. non-condensing Beam length 5m to 30m Sensitivity 30% obscuration Size Reflector: 190mm x 190mm x 3mm SRA-ET: 152mm x 122mm x 80mm Weight (without termination module) Reflector: 50g. SRA-ET: 700g Colour White Ivory (Black lens) Housing material ABS resin Reflector material Expanded Polyvinyl Chloride Reflector sheet Aluminium metallic acrylic film Mounting Wall mounting Reflector mounting angle +/- 10 Connection method Termination module: screw terminals Wiring method Termination module: 2 wires for zone Approval Body LPCB Page 14 2-3-0-365/ISS3/OCT99

6. Troubleshooting The following conditions relate to the SRA-ET itself. 6.1. Monitor LED fails to flash The monitor LED should flash every 3 seconds. If it does not the reason may be as follows:! Zone voltage to the SRA-ET less than 15V! SRA-ET is damaged! Ensure that the SRA-ET has been powered for more than 60 seconds and that the power at the SRA-ET is greater than 15V. 6.2. Fire signal continues after reset When a fire has occurred there may be certain circumstances that will prevent the beam detector from resetting. These are:! There is an obstruction of the optical path between reflector and SRA-ET. Ensure there is no obstruction.! The optical axis has been altered suddenly. The beam will need re-alignment.! Insufficient time between fire and reset. At least 3 seconds are required before resetting the beam after the fire signal has occurred. 6.3. Fault signal cannot be reset 6.3.1. Fault only If a fault has been generated without any obvious reason, it has occurred due to one of the following reasons:! Contamination limit has been exceeded (light received has changed by more than 50%)! Beam detector is defective or removed from interface PCB 2-3-0-365/ISS3/OCT99 Page 15

6.4. Beam detector generates a fire but panel does not register the condition! The zone is incorrectly wired to the beam detector. The wiring must be done in accordance with the relevant wiring diagram! The control panel is incompatible with the interface PCB! The interface PCB is defective! The interface fault monitoring jumpers have been incorrectly set. Verify the fault monitoring function of the control panel! Panel does not use 470 ohms to detect a fire condition 6.5. Beam detector generates a fault but panel does not register the condition! The zone is incorrectly wired to the beam detector. The wiring must be done in accordance with the relevant wiring diagram. Page 16 2-3-0-365/ISS3/OCT99

7. Installation guide lines The Hochiki SRA-ET beam detector must be installed according to the requirements laid out in National or local standards. The following guidelines for installation are provided to give information in certain installation conditions where no advice or regulations are provided by the relevant standard. 7.1. General installation conditions The diagram in Figure 9 relates to the typical installation condition i.e. in a long straight area and details the siting positions of the beam detector: Figure 9 General installation conditions. H=ceiling height l1=side wall distance P=distance between optical axes h=mounting height l2=back wall distance L=distance between Reflector/SRA-ET If H 15m then use beam detectors at locations 1 and 2 If H > 15m then beam detectors should be mounted at locations 1, 2, 3, 4 and 5 For Detectors at 1 and 2 For detectors at 3, 4 and 5 h 0.8H h' = H/2 l1 7m l1 5m l2 1m P 14m P' 5m L = 5m to 30m L = 5m to 30m 2-3-0-365/ISS3/OCT99 Page 17

7.2. Installation in Saw-tooth type ceilings In installations where there is a saw-tooth shape to the ceiling the detectors should be mounted with the axis either in condition A or condition B according to Figure 10. If the height of the ceiling 'a' is greater than 0.2'H' do not install with the axis according to line B. Figure 10 Installation in saw-tooth shaped roofs 7.3. Installation in circular type ceilings The installation in a cylindrical or circular roofed building should be in accordance with Figure 11. In the case of the cylindrical roof position A or B for the detector's axis is acceptable. Figure 11 Installation in circular shaped ceilings Page 18 2-3-0-365/ISS3/OCT99

7.4. Installation in sloped ceilings The installation for a sloped type roof or ceiling will be as shown in Figure 12. Either position A or B is acceptable for installation of the SRA-ET. Figure 12 Installation under a sloped ceiling 7.5. Installation in a monitor roof The installation for a monitor roof should be performed as in Figure 13. The detector's installation height should be 0.8H or higher. If there is ventilation in the top part of the roof then the detector must be placed below the opening. The detector should be installed in accordance with the following height restriction: Figure 13 Installation in a monitor roof H-a > h 0.8H 2-3-0-365/ISS3/OCT99 Page 19

7.6. Installation in corridors or aisles 7.6.1. Closed corridor When the detector is installed in a corridor with a closed corner it is possible to use just one detector as shown in Figure 14 providing that the distance L is less than 7.5m. Figure 14 Installation in a closed corridor 7.6.2. Corridor with open adjoining aisle When the detector is installed in a corridor with an area adjoining which is open as shown in Figure 15, it is necessary to consider the adjoining area as a separate detection area. Figure 15 Installation in an open corridor Page 20 2-3-0-365/ISS3/OCT99

7.6.3. Corridor with corners When the detector is installed in a corridor with a bend and an aisle as shown in Figure 16 it will be necessary to use at least 2 beam detectors to cover the corridors. If the distance P is greater than 15m then another beam detector will need to be installed at point C. Figure 16 Installation in a corridor with corners 7.7. Installation precautions The following precautions are necessary when installing beam detectors: -! In a room where an air inlet is positioned in the ceiling the beam detector should be placed near to the air inlet.! Select an appropriate installation place where the detector is unaffected by air being drawn into a ventilated opening.! The distance between the SRA-ET and the wall immediately behind the SRA-ET should be less than 7.5m.! If more than one detector is installed they must be positioned in such a manner that they cannot affect each other s operation.! The detector should be positioned such that a shutter or hanging wall will not affect it.! The detector should be positioned such that it will be unaffected by moving objects.! The detector should not be installed in a rooftop or place where open air circulates.! The detector should be installed where the distance between top and bottom of the space is greater than 0.5m.! The monitoring distance between the reflector and SRA-ET is 5m to 30m and the maximum distance of coverage between the line of the beam is 7.5m.! If there is a probability of people walking in the area of the beam then the beam detector should be installed at least 2.7m from the floor.! The beam detector should not be installed at a height greater than 25m unless the fire detection system is connected directly to the fire brigade or via a central station and rapid 2-3-0-365/ISS3/OCT99 Page 21

attendance by the fire brigade is possible. In any case the maximum installation height is 40m. 7.8. Smoke patterns appropriate to the consideration of beam detector installation Figure 17 Typical smoke patterns Hochiki Europe (UK) Ltd. reserves the right to alter the specification of its products from time to time without notice. Although every effort has been made to ensure the accuracy of the information contained within this document it is not warranted or represented by Hochiki Europe (UK) Ltd. to be a complete and up-to-date description. Please check our web site for the latest version of this document. Page 22 2-3-0-365/ISS3/OCT99

2.4. Field wiring & line continuity The connection of this unit requires the use of a dual gang installation box, either flush mount or surface mount or the Hochiki SRA-ET Back Box. Suggested types are MK897 ALM surface mount, MK862 ZIC flush mount, but any equivalent type is usable providing that it has a minimum depth of 25mm. This item should be firmly fixed to the wall or other suitable mounting point first. With reference to the wiring diagram Figure 2 & Figure 3 ensure that the field wiring is terminated into the dual gang installation box. The Termination Module can be configured to provide correct operation for three different types of zone fault indication, which provide the same fault detection functions as Hochiki's conventional detector bases when the detector heads are removed. The configuration is achieved using jumpers at the top of the termination PCB ( refer to figure 3 ) and the selection should be made according to the type of fire alarm control panel being used. If the SRA-ET is being used with the CHQ-MZ/Z then the jumpers need to be set to the normal mode. Normal:- No line continuity option (zone is open circuit during fault). Jumpers LK1, LK4 & LK6 ARE MADE, all other jumpers are removed. Zener:- Line continuity using a Zener clamp (produces detector removal fault at the control panel). Jumpers LK2 & LK5 ARE MADE, all other jumpers are removed. Schottky:- Line continuity using a Schottky diode (produces detector removal fault at the control panel). Jumpers LK1, LK3, LK4 & LK6 ARE MADE, all other jumpers are removed. Note: The Termination Module is factory configured for Schottky diode line continuity. If in doubt check the correct line continuity for the control panel. Warning: When the Zener option is used it must be connected to a control panel, which is able to use this type of option. If connected either to an unsuitable panel or a 24V-power supply the interface could be damaged due to over-current. Figure 2 - Termination module wiring diagram