Manual Supplement. Product/System Title: Premium Clean Room Monitor. Contents of this manual supplement include:

Similar documents
Manual Supplement. Product/System Title: Static Pressure Controller. Contents of this manual supplement include:

Manual Supplement. Model Number: 8680-N2. Communications Protocol. Contents of this manual supplement include:

PRESSURA ROOM PRESSURE CONTROLLER MODELS 8630-SC 8630-PC

Model 8682-KET Sequenced Offset (Flow Tracking) and Static Pressure Controller with Dual Exhaust Modulation for Temperature Control

PRESSURA ROOM PRESSURE MONITOR MODELS 8630-SM 8630-PM

RPM1600 Series Room Pressure Monitors

TSI Model 8630 PRESSURA Room Pressure Monitor Modbus Communications Application Note LC-106

PRESSURA ROOM PRESSURE MONITOR MODEL RPM10 AND RPM20

PRESSURA ROOM PRESSURE MONITOR MODEL RPM10 AND RPM20

PRESSURA ROOM PRESSURE MONITOR MODEL RPM10 AND RPM20

SUREFLOW ROOM PRESSURE CONTROLLER MODELS BAC

SUREFLOW ADAPTIVE OFFSET CONTROLLER MODELS BAC

PRESSURA ROOM PRESSURE CONTROLLER MODEL RPC30

PRESSURA ROOM PRESSURE CONTROLLER MODEL RPC30

Critical Environments. Model FHC50/FHM10. Fume Hood Controller/Monitor. Operation and Service Manual. P/N , Revision B October 2010

OPERATION & MAINTENANCE MANUAL GUARDIAN SPACE PRESSURE MONITOR WITH REMOTE AUXILLARY ALARM

Analog Room Pressure Monitor RPC Series

HVAC Controls Laboratory. Model EVERWATCH Face Velocity Monitor. Operation and Service Manual. P/N , Revision E October 2002

Product Manual SZ1145

Product Manual SZ1144

MYRIAD TRIPLEX PUMP CONTROLLER INSTRUCTION MANUAL

EVERWATCH FACE VELOCITY MONITOR MODEL 8610

ENERGY LIGHT USER S GUIDE ENERGY LIGHT USER S GUIDE

TV2 Room Pressure Monitor Quick Start Guide

Electro-Sentry. Users Manual

Accuracy by Design Products for the HVAC Professional

TV2 Clean Room Monitor

AD-1272 Advanced Thermal Dispersion Probe Airflow Measuring System

Installation Manual Tracker 221

MODEL SF-10 CONTROL OPERATION AND INSTRUCTION MANUAL

Follett Performance Plus

Barrington Consultants Incorporated

EasyTronic III MANUAL SERVICE

GLD-30 Gas Leak Detector

DIGITAL TEMPERATURE RELAY TR-100

Carbon Monoxide Transmitter

La Marche Manufacturing Company Option 16 Series. Digital Combined Accessory Package. Installation and Operation Manual

T60xDFH-4 and T60xDFH-4+PIR Series Thermostat Controllers with Dehumidification and Occupancy Sensing Capability

prestige Control Application Supplement - TriMax

CAREL IR33+ CONTROLLER

200i/KN2, KN4 Firmware Revision Sheet

SEC 2000 Millenium Infrared Gas Detector

VAV Thermostat Controller Specification and Installation Instructions. Model TRO24T4XYZ1

prestige Control Application Supplement - ACVMax

Modus Model DA General Eastern Low Differential Pressure Alarm Controller

La Marche Manufacturing Company Option 46 Series. Digital Combined Accessory Package. Installation and Operation Manual

Rev B, 9/2/2009. Kodiak Chiller Overview

DC VOLTMETER DCV-10 / 10A / 10C / 10S / 10CS / 11 / 11A / 11C / 11S / 11CS. A4741 / Rev.1

B-40/B-41 Modulating Temperature Controller

MO n : 12JMC rév A

Digital Precise Air Control - DPAC

Electric Duct Heaters. IDHB & IDHC Series

INSTALLATION MANUAL AND OPERATING INSTRUCTIONS

Digital Control Unit- Installation, Operation & Maintenance IMPORTANT INFORMATION

MYRIAD DPC DUPLEX PUMP CONTROLLER INSTRUCTION MANUAL VERSION 3.7

NexSysLink. 2 CAN Display Operation Manual. CAN Instruments Product Family

A36D/TPSD Modbus RTU (Serial) SCADA INTERFACE INSTRUCTIONS

Pump-Up Controller MODEL 4062

Operation 8085C ENGLISH. Customer Support: or Visit our webiste Printed in China

ARGO (Technical Support) 2201 Dwyer Avenue Utica, NY (Corporate Sales) 85 Middle Road

MF-PFA ver 3.x. Micaflex PFA ver 3. Pressure- and Flow transmitter with alarmfunction. Installation- & Operation manual [Dok. id: mi-303gb_180528]

DAP III Zone Master User s Guide


Rev UltraSite User s Guide BCU Supplement

Guide Specification - MasterFormat 2017 Style SECTION FLOW INSTRUMENTS PART 2 PRODUCTS 2.1 SECTION INCLUDES 2.2 ACCEPTABLE MANUFACTURERS

Factory Packaged Controls. MHGRV-X Controller Field Technical Guide

Pump-Down Controller MODEL 4052

Delta P Plus Control

CTT8 TEMPERATURE MONITOR DEVICE

- Data Brochure Universal Reset Module 422

Factory Packaged Controls. MHGRV-X Controller Field Technical Guide

FIRERAY 5000 range USER GUIDE

QD-ENG-68 Controller for Thermoelectric Thermal Management

- Data Brochure Universal Reset Module 423

Series DCT1000DC Dust Collector Timer Controller Specifications Installation and Operating Instructions

IntelliPack : 800 Series

Reciprocating Chiller

Manual# User s Manual. DCU 410/408 Engine Control Unit RP 410 Remote Panel FW 2.3

Electrical. Bi-Metallic Thermal Cutouts. Linear Thermal Cutouts

- Data Brochure Steam Control 279

TECHNICAL MANUAL CVM 3000 C 5030 CV/04-99 GB

OPERATING MANUAL Enertronic Control System 2

- Data Brochure Boiler Control 274

2704 Controller Melt Pressure Controller

Electric Coils. Blower Coils. Product Information

SECTION SEQUENCE OF OPERATIONS FOR HVAC CONTROLS

Temperature Controllers

2604 Controller Melt Pressure Controller

ModSync Sequencing System Installation & Operation Manual. For use with Fulton Steam Boilers.

RSMV Technical Guide

DWYER INSTRUMENTS, INC. P.O. BOX 373 MICHIGAN CITY, INDIANA 46360, U.S.A. Series 670 Hood Monitor. Bulletin AV-670

Advanced Installation and Configuration Instructions

MAINTENANCE & TROUBLESHOOTING GUIDE LEAK ALARM CHANNEL DRY OIL WATER AUX ALARM HIGH LOW CRITICAL WATER TANK LEVEL ALARM MODEL LDE-740 ADVANCE PAPER

Delta P Plus Control

1600 Gas Controller. User s Manual. Industrial Scientific Corporation. Version 3.2 September 1, 2006

SPM-4000-DC GUARDIAN INFINITY SPACE PRESSURIZATION MONITOR AND DUAL CONTROLLER

ExactLogic BACnet Communicating Thermostat EXL01625 Sequence Datasheet Fan Coil with Modulatating H/C and PO-PC H/C

Important Supplementary Manual to the main Ezeio manual. 5. Section 2a: Introducing the 2400 input and output expansion field stations.

CRITICAL ENVIRONMENT MONITOR ALNOR AIRGARD 350 CEM

Construction Electrical

Transcription:

Model Number: Product/System Title: 8630-PM-CRM Premium Clean Room Monitor Contents of this manual supplement include: 1) Sequence of operation 2) Menu structure drawing 3) Description of new software items 4) Deleted software menu item 5) Wiring diagram 6) Access Code Page 1 of 1 Released 4/9/04

Sequence of Operation The Model 8630-PM-CRM monitors room pressure by utilizing a through-the-wall pressure sensor. The Model 8630-PM-CRM features high and low pressure alarms for up to two independent sensors. A minimum supply volume alarm is also present. Additinally, the Model 8630-PM-CRM supports digital communications over an RS-485 network and an analog pressure output. Menu Structure ALARM CONFIGURE CALIBRATION LOW ALARM HIGH ALARM SEC LOW ALM SEC HIGH ALM MIN SUP ALM ALARM RESET AUDIBLE ALM ALARM DELAY MUTE TIMEOUT DISPLAY AVG UNITS ROOM VOLUME 2 SENSOR SENSOR ZERO SENSOR SPAN 2SENSOR ZERO 2SENSOR SPAN SUP 1 ZERO SUP 2 ZERO ELEVATION INTERFACE DIAGNOSTICS PRESSURE FLOW NET PROTOCOL NET ADDRESS OUT SIG PRESS AOUT SENSOR INPUT SENSOR STAT 2 SENS INPUT 2 SENS STAT SUP 1 INPUT SUP 2 INPUT PRES ALM REL SUP ALM REL SENSOR TYPE MAX OUT SIG MAX OUT VAL SUP1 AREA SUP2 AREA SUP1 KFACTOR SUP2 KFACTOR SENSOR TYPE MAX OUT SIG MAX OUT VAL Figure 1: Menu Items - Model 8630-PM-CRM Premium Controller Page 2 of 2 Released 4/9/04

Description of New Software Items The Model 8630-PM-CRM has additional software items. Alarm Menu Menu Item LOW ALARM SEC LOW ALM HIGH ALARM SEC HIGH ALM Description The LOW ALARM and SEC LOW ALARM items set the low pressure alarm set points for the primary and secondary pressure sensor. A low alarm condition occurs when the room pressure falls below or goes in the opposite direction of the low alarm set point. The SEC LOW ALM setpoint is only used when the second sensor is enabled through the CONFIGURE menu. The LOW ALARM and SEC LOW ALM can be set to OFF. The LOW ALARM and SEC LOW ALM have a range from 0 to within 0.005 H 2 O of the pressure SETPOINT. For TSI or BI DIRECT sensor types, the low alarm must be of the same sign (positive or negative) as the pressure SETPOINT. The default value is OFF. The HIGH ALARM and SEC HIGH ALM items set the high pressure alarm set points. A high alarm condition occurs when the room pressure rises above the high alarm set point. The SEC HIGH ALM setpoint is only used when the second sensor is enabled through the CONFIGURE menu. The HIGH ALARM and SEC HIGH ALM can be set to OFF. The HIGH ALARM and SEC HIGH ALM have a range from within 0.005 H 2 O of the pressure SETPOINT to within 0.005 H 2 O of the pressure MAX OUT VAL. For TSI or BI DIRECT sensor types, the high alarm must be of the same sign (positive or negative) as the pressure SETPOINT. The default value is OFF. Page 3 of 3 Released 4/9/04

Calibration Menu Menu Item SUP 1 ZERO SUP 2 ZERO Description The SUP 1 ZERO and SUP 2 ZERO items are used to calibrate the flow station pressure transducers. A zero or no flow setpoint needs to be established prior to using the supply flow measurements (see Calibration section of manual following menu item listing). Diagnostics Menu Menu Item PRESS AOUT Description The PRESS AOUT item is used to vary the analog output from the Model 8630-PM-CRM. When this item is entered, a number will be shown on the display indicating the last analog output value. The value displayed ranges from 0 to 255. The value 255 corresponds to the lowest voltage (current) output and 0 corresponds to the highest voltage (current) output. Pressing the key will decrease the analog output and increase the value displayed. Pressing the key will increase the analog output and decrease the value displayed. The PRESS AOUT function can be used in conjunction with a voltmeter to verify that the analog output is correct. SUP 1 INPUT SUP 2 INPUT PRES ALM REL The SUP 1 INPUT and SUP 2 INPUT items are used to read the flow measurement inputs directly. When these item are entered, the display will indicate the voltage from the proper transducer. The exact voltage displayed is relatively unimportant. It is more important that the voltage changes to indicate the flow station is working properly. The PRES ALM REL item is used to change the state of the pressure alarm relay. When this item is entered, the display will indicate either OPEN or CLOSED. The / keys are used to toggle the state of the relay. The key is used to OPEN the alarm contact. The key is used to CLOSE the alarm contact. When the contact is closed, the pressure alarm relay should be in an alarm condition. Page 4 of 4 Released 4/9/04

SUP ALM REL Pressure Menu Menu Item SENSOR TYPE MAX OUT SIG MAX OUT VAL The SUP ALM REL item is used to change the state of the minimum supply alarm relay. When this item is entered, the display will indicate either OPEN or CLOSED. The / keys are used to toggle the state of the relay. The key is used to OPEN the alarm contact. The key is used to CLOSE the alarm contact. When the contact is closed, the minimum supply alarm relay should be in an alarm condition. Description The SENSOR TYPE item is used to set the type of pressure sensor used to measure the room pressure differential. This item can be set to TSI, UNI DIRECT, or BI DIRECT. The default value is TSI. The MAX OUT SIG item is used to set the maximum pressure output voltage from the transducer used. This item can be set to 5 V or 10 V, with a default value of 10 V. For a TSI pressure sensor, the MAX OUT SIG must be set to 10 V. The MAX OUT VAL item is used to set the maximum pressure reading of the transducer used. This item can be set between 0.1 H2O and 2 H2O, with a default value of 0.2 H2O. For a TSI pressure sensor, the MAX OUT VAL must be set to 0.2 H2O. For a UNI DIRECT pressure sensor, the MAX OUT VAL must be programmed as a positive or negative, depending on the pressure relationship of the space to its reference. For UNI DIRECT sensors, 0 V (or 4 ma in CURRENT mode) corresponds to a pressure differential of 0, and 10 V or (20 ma in CURRENT mode) corresponds to a pressure differential of MAX OUT VAL. For BI DIRECT or TSI sensors, 0 V (or 4 ma in CURRENT mode) corresponds to a pressure differential of -MAX OUT VAL, and 10 V or (20 ma in CURRENT mode) corresponds to a pressure differential of MAX OUT VAL. Page 5 of 5 Released 4/9/04

Flow Menu Menu Item SUP1 AREA SUP2 AREA Description The SUP1 AREA and SUP2 AREA items are used to input the duct sizes for the first and second supply. The duct sizes are needed to compute the air flowing into the room. These items require a flow sensor to be mounted in the proper supply duct. When a duct area is programmed, the display will automatically scroll the actual total supply flow as part of the display scroll sequence. If a zero value is entered, the supply flow value will not scroll on the display. The programmed duct areas can range from 0 to 10 square feet if the PRESSURA displays English units. If the PRESSURA displays metric units, then the duct areas can range from 0 to 0.9500 square meters. The default is 0. SUP1 KFACTOR SUP2 KFACTOR SENSOR TYPE MAX OUT SIG MAX OUT VAL The KFACTOR menu item sets the K factor for the flow probe being used. The flow signal is multiplied by the KFACTOR so that the flow measurement matches the actual flow, usually determined with a pitot tube traverse. The KFACTOR has a minimum value of 0 and a maximum value of 10., with a default of 1. The SENSOR TYPE item is used to select the flow station input signal. PRESSURE is used when flow stations with pressure transducers are installed. LINEAR is selected when a linear output flow station, typically a thermal-based flow station, is installed. The MAX OUT SIG item is used to set the maximum output voltage from the transducer used. This item can be set to 5 V or 10 V, with a default value of 5 V. For a TSI flow station, the MAX OUT SIG must be set to 5 V. The MAX OUT VAL item is used to set the maximum pressure reading of the transducer used, or the maximum velocity of the linear flow station used. For a pressure based measurement, this item can be set between 0.1 H2O and 0.5 H2O, with a default value of 0.5 H2O. For a linear flow station, this item can be set between 0 and 5,000 ft/min. For a TSI flow station, the MAX OUT VAL must be set to 0.5 H2O. Page 6 of 6 Released 4/9/04

Deleted Software Menu Items The following items have been replaced on the 8630-PM-CRM.: ALARM MENU CONFIGURE MENU CALIBRATION MENU INTERFACE MENU DIAGNOSTICS MENU NEG LOW ALARM NEG HIGH ALARM POS LOW ALARM POS HIGH ALARM MIN CFM ALM 2 LOW ALM 2 HIGH ALM ROOM MODE DCT AREA FLOW ZERO OUTPUT RANGE ANALOG OUT KEY INPUT FLOW INPUT LOW ALM RELAY HIGH ALM RELAY Page 7 of 7 Released 4/9/04

Wiring Diagrams Manual Supplement MODEL 8630-CRM WIRING DIAGRAM TSI SENSOR Page 8 of 8 Released 4/9/04

MODEL 8630-CRM - MONITOR WIRING WIRING DIAGRAM DIAGRAM - PRESSURE - XDCR XDCR Page 9 of 9 Released 4/9/04

Access Codes Manual Supplement The 8630-PM-CRM has a single access code for all menus. Each menu has the access code enabled individually; implementing the access code in one menu does not enable the access code in other menus. When an access code is required, pressing the following key sequence will provide access: Key # 1 EMERGENCY 2 MUTE 3 MUTE 4 MENU 5 AUX Page 10 of 10 Released 4/9/04