Single Doors FIREGUARD Series Use one Master Unit each door or one 2409 Support unit each door. Pairs of Doors

Similar documents
Wiring Instructions. Single Doors 99 Checkmate Series Use one or Master Unit each door or one or Support unit each door

Wiring Instructions (01-09)

Wiring Instructions for the 2900 Series FIREGUARD Combination Door Closer-Holder and Releasing Device with Integral Smoke Detector

MODEL /4" Conduit. (By others) Terminal Strips Companion unit (without electronics) not shown. Approximate Preload

8600 EMR SERIES. INSPK NO Rev.06/ INS NO. GENERAL DESCRIPTION

TS93 EMR WITH SMOKE DETECTOR

1400 Direct Wire Ionization Smoke Detector

7200 Series. Electromechanical Closer/Holder Releasing Devices

Installation Instructions

FireNET FN-LCD-S Serial Annunciator Installation and Operation Manual

2408/2900. Fire Guard. SARGENT Manufacturing Company 2004, 2007 All rights reserved

2408/2900. Fire Guard

INSTALLATION AND MAINTENANCE

2409/2900. Fire Guard

EHT/EHTD. Electromechanical Closer-Holder Release Devices

RELEASE DEVICES RELEASE DEVICE-WPS MODELS A/B INSTALLATION MANUAL U.L. LISTED CANADIAN LISTED CSFM: :100 GENERAL DESCRIPTION:

DETECTOR TEST LOG. Detector Identification Information DHX-501 INTELLIGENT AIR DUCT SMOKE DETECTOR HOUSING INSTALLATION AND MAINTENANCE INSTRUCTIONS

RELEASE DEVICE CONTROLS

MODEL B2 INSTALLATION MANUAL

FIREFLY II PLUS RELEASE DEVICES INSTALLATION MANUAL

DH500ACDC Intelligent Air Duct Smoke Detector Housing

DH400 Air Duct Smoke Detector

SOLID STATE SECURITIES, INC. THE "SS90" SERIES RELEASE DEVICES MADE IN THE U.S.A. SS90-WPS MODEL A/B INSTALLATION MANUAL

Installation Guide for AL600ULM. Multi-Output Access Control Power Supply Charger. Rev

D285DH. Installation Instructions Photoelectric Duct Smoke Detector

Multi-Output Access Control Power Supply Charger VDC or 24VDC VDC or 3 24VDC.

THE "SS90" SERIES RELEASE DEVICES MODEL B2 INSTALLATION MANUAL

Firefly II Multi Voltage RELEASE DEVICES. Firefly II & IIB-MV INSTALLATION MANUAL

Addressable Detectors & Bases

DH100ACDCI Ionization Air Duct Smoke Detector

D350RPL INTELLIGENT PHOTOELECTRONIC DUCT SMOKE DETECTOR WITH EXTENDED AIR SPEED RANGE INSTALLATION AND MAINTENANCE INSTRUCTIONS

Installation Guide for AL300ULM. Multi-Output Access Control Power Supply Charger

THE "SS90" SERIES RELEASE DEVICES MADE IN THE U.S.A. MODELS A/B INSTALLATION MANUAL

DH100ACDCI Ionization Air Duct Smoke Detector

MADE IN THE U.S.A. ADVANCE FIRE CONTROL MODEL LM21-AFC MANUAL RELEASE DEVICES TEST WEEKLY TO ASSURE PROPER OPERATION OF RELEASE DEVICE/CONTROL PANEL

4100U City and Relay Cards Installation Instructions

E-PDD Duct Smoke Detector Installation Sheet

Air Specialties Express, 448 S. Main St., P. O. Box , Verona, WI Phone: (877) Fax: (608)

ACSI AO ELECTRIC LATCH RETRACTION CONTROLLER INSTALLATION INSTRUCTIONS I.D. 1089, REV. F

An ASSA ABLOY Group brand Series. Electromechanical Closer-Holder Releasing Device

D350PL INTELLIGENT PHOTOELECTRONIC DUCT SMOKE DETECTOR WITH EXTENDED AIR SPEED RANGE INSTALLATION AND MAINTENANCE INSTRUCTIONS

Installation Instructions

"SS90" SERIES CONTROLS MODEL C INSTALLATION MANUAL

Installation Guide for AL400ULM. Multi-Output Access Control Power Supply Charger

Multi-Output Access Control Power Supply Chargers VDC or 24VDC VDC or 4 24VDC.

DH100ACDCLP Air Duct Smoke Detector with Extended Air Speed Range

DH200RPL Intelligent Air Duct Smoke Detector with Extended Air Speed Range

MADE IN THE U.S.A. MODELS A/B INSTALLATION MANUAL

Duct smoke housings, 4-wire D341/D341P and D342/D342P

D7050DH. Installation Instructions. Multiplex Photoelectric Duct Smoke Detector

TECHNICAL DATA OBSOLETE

ISIMET Series Shop Controller

Operator: Save these instructions for future use!

Model 17A00 Expansion Enclosure

ELECTRONIC FLAME SUPERVISION MULTI-BURNER

TECHNICAL DATA SHEET CONVENTIONAL FIRE ALARM SYSTEMS Conventional Fire Alarm Control Panel

TRN100BPT, TRN100BP, and TRN100BPC Air Duct Smoke Detector with Extended Air Speed Range

Smoke Alarm User s Manual

Model PAD-3 Distributed Power Module NAC Expander Installation, Operation, and Maintenance Manual

DH100ACDCLPX Air Duct Smoke Detector with Extended Air Speed Range

RF280THS. Installation Instructions Wireless (RF) Photoelectric Smoke Detectors

TraceTek Sensing Module Installation, Operation and Maintenance Instructions DESCRIPTION SPECIFICATIONS APPROVALS TYPE NM

Analog Room Pressure Monitor RPC Series

MANUAL RESET ALARM RELEASE

DH200PL Intelligent Air Duct Smoke Detector with Extended Air Speed Range

120 VOLT POTENTIAL PRESENT. MAKE SURE POWER INPUT TO UNIT IS TURNED OFF DURING INSTALLATION AND WIRING PROCEDURE.

Installation Guide for models:

Air Specialties Express, 448 S. Main St., P. O. Box , Verona, WI Phone: (877) Fax: (608)

APS-300 SERIES DUAL VOLTAGE UL 294 LISTED ACCESS CONTROL POWER SUPPLIES

TECHNICAL DATA. Humidity: 85% Relative Humidity (non-condensing) at 90 F (32 C) maximum.

Models NFPA 1221-A, NFPA 1221-B Public Safety DAS Annunciator Panel. Revision E 61117

Series. Access Power Controllers. Installation Guide

Installation Guide for models:

Energy Manager INSTALLATION INSTRUCTIONS. Keep these instructions with the boiler at all times for future reference

Operator: Save these instructions for future use!

CommStat 4. Controller for Redundant Telecom HVAC Systems PRODUCT DATA SHEET. Features and Benefits

CommStat 4 Controller

Cookson Company 1901 South Litchfield Road Goodyear, AZ Phone:

MANUAL RESET ALARM RELEASE BOX

F I R E G A R D D C EXTENDED PERFORMANCE RELEASE DEVICE SAFE A N D SECURE

DH200PL Intelligent Air Duct Smoke Detector with Extended Air Speed Range

Installing the Cisco ONS FAP-4 Fuse Alarm Panel

ISIMET Utility Controller

DH500 Intelligent Air Duct Smoke Detector Housing

50A Integrated Furnace Control

WARNING. Installation Tip: Try out this unit before installing onto a fire door system. Test and learn the release INTRODUCTION

PS1240x Series Dual Voltage Access Control Power Supply Systems Operating and Installation Instructions Rev D.01

DH100LP Air Duct Smoke Detector with Extended Air Speed Range

FX-PDD Duct Smoke Detector Installation Sheet

CommStat 6. Controller for Redundant HVAC Systems PRODUCT DATA SHEET

MASTER JOCKEY PUMP CONTROLLER. Model JPCE INSTRUCTION MANUAL. C 2018 Master Control Systems, Inc

End To End Optical Beam Smoke Detector. Additional Information

IDP-Zone-6 Six Zone Interface Module

TA-12. Tabbing System USER'S GUIDE

PO Box 827 Hawley, MN (218) Fax (218)

PRODUCT OVERVIEW SM-501 AT-A-GLANCE

- 4 12VDC or 24VDC VDC or 24VDC - Eight (8) Fused Outputs - Eight (8) PTC Outputs. Installing Company: Service Rep.

MANUAL RESET ALARM RELEASE

Electric Release Panel Wiring Tips

Macurco HD-11 Hydrogen Gas Detector

Transcription:

Hinge Edge of Door Hinge Edge of Door Wiring Instructions for the Sargent 0 Series FIREGUARD Combination Door Closer-Holder and Releasing Device with Integral Smoke Detector CAUTION: FAILURE TO INSTALL OR ADJUST PROPERLY MAY RESULT IN INJURY OR DAMAGE. For assistance, contact SARGENT at 00-0-WIRE () or www.sargentlock.com INSTALLER: LEAVE INSTRUCTIONS WITH BUILDING OWNER Single Doors FIREGUARD Series Use one -0 Master Unit each door or one 0 Support unit each door Pairs of Doors Power Track Series Use one -0 Master Unit and one 0 Support Unit for each door leaf (VDC 0 Support Unit must be used with -0 Master Unit) -0 Master Unit shown VDC 0 Support Unit shown Hinge Edge of Door VDC 0 Support Unit shown -0 Master Unit shown. Disconnect all power before beginning installation to prevent electrical shock and equipment damage.. Installer must be a trained, experienced service person. CAUTION:. All wiring must comply with applicable local electrical codes, ordinances, and regulations.. Maximum wire size is AWG.. These units are not to be used in limited open area applications. REQUIREMENT: Power input to unit must be of the same voltage as that listed on the product label: VDC for systems where the power input to both the integral smoke detector and the door holder solenoid is supplied from the same circuit (see Pages and thru of these instructions). Copyright 0, Sargent Manufacturing Company, an ASSA ABLOY Group express written permission of Sargent Manufacturing Company is prohibited. A00 (0/)

Smoke Detector Connection Board Red LED / Reset Switch Opening for Concealed Wiring 0VAC -0 Master Unit shown Board Test Switch Power Input Opening for Surface Wiring Power Inputs Test Switch Connection! 0VAC 0 Support Unit shown WARNING: These fire protection devices require correct wiring to function. It is the responsibility of the purchaser to provide qualified correct wiring installation. SARGENT accepts no responsibility for incorrect wiring. Devices wired incorrectly may be damaged and this is not covered under warranty. Life safety devices require correct positioning and appropriate selection for the required task. It is the responsibility of the purchaser to select appropriate hardware and provide professional installation. It is the responsibility of the purchaser to insure that NFPA and other applicable fire codes are met. Door release devices function properly only if the door is free to close and is installed correctly. SARGENT accepts no responsibility for incorrect installation of its equipment. Smoke detectors will not work without power. AC or DC powered smoke detectors will not work if the power supply is cut off for any reason. All high voltage wiring should be undertaken by a qualified professional licensed electrician. It is the responsibility of the purchaser to insure that installation meets all applicable local and national electrical codes. A detector may not detect a fire developing on another level of a building. For this reason, detectors should be located on every level of the building. Smoke detectors will not sense fires which start where smoke does not reach the detectors. Smoke from fires in chimneys, in walls, on roofs, or on the other side of a closed door may not reach the smoke detector and activate it. Smoke detectors cannot last forever. Smoke detectors contain electronic parts. Even though detectors are made to last over 0 years, any of these parts could fail at any time. Therefore, test your smoke detector system per NFPA Chapter 0 at least semiannually. Clean and take care of your smoke detectors regularly. Refer to Page of these instructions for Smoke Detector Cleaning and Testing. Taking care of the fire detection system you have installed will maintain the reliability of the system. Smoke detectors have sensing limitations. Photoelectric detectors sense smoldering fires better than flaming fires. Ionization detectors offer a broad range of fire-sensing capability, but they are better at detecting fast, flaming fires than slow smoldering fires. Because fires develop in different ways, and are often unpredictable in their growth, neither type of detector is always best, and a given detector may not always provide warning of a fire. In general, detectors cannot be expected to provide warning for fires resulting from inadequate fire protection practices, violent explosions, escaping gas, improper storage of flammable liquids like cleaning solvents, other safety hazards, or arson. Smoke detectors used in high air velocity conditions may fail to alarm due to dilution of smoke densities created by such frequent and rapid air exchanges. Additionally, high air velocity environments may create increased dust contamination, demanding more frequent maintenance. Copyright 0, Sargent Manufacturing Company, an ASSA ABLOY Group express written permission of Sargent Manufacturing Company is prohibited. A00 (0/)

Smoke Detector Operation and Application The closer/holder unit includes a -wire, photoelectric type smoke detector. It provides: smoke detection, door holder latch control, N.O. alarm contact, N.C. supervisory contact and interconnection to other smoke detectors. Field option: one form C auxiliary contact (cut jumper wire between and ). Smoke Detector Terminal Inputs and Outputs V input power is applied to terminals and from the circuit board. The red LED flashes every seconds. Terminals and provide a normally open (alarm) contact. This contact closes when smoke is detected. The red LED illuminates continuously. Terminals and provide a normally closed supervisory (trouble) contact. This contact opens when power is lost to the detector circuitry. The red LED stops flashing and does not illuminate. Terminals and, if used, provide rectified, unfiltered VDC power to an additional door holder solenoid. In an alarm condition, power is removed and the door closes. Terminals and, if used, provide rectified, unfiltered VDC power to auxiliary devices when the detector alarms. Terminal 0 is VDC Positive output. It is continuous, rectified, unfiltered VDC power used for remote detector interconnect applications. Terminals,, and 0 may be field configured to a dry form contact by cutting jumper between terminals and. Terminal 0 is Common, is N.C. and is N.O. If this is done, Aux+ is lost; latch power must be supplied by a separate source Terminals and provide interconnections to other detectors (see diagram on Page ). Up to five smoke detectors may be interconnected. When a single detector alarms, terminal goes high and all interconnected smoke detectors will release their doors. The unit that initiated the alarm will have its LED on. The LED on the other interconnected units will flash as normal. Refer to Interconnection Wiring Diagram for connections. CONNECTION LIST FUNCTION TERMINAL VDC input, Alarm Contacts, Latch Latch Aux Aux Interconnect Interconnect SOLENOID Trouble contacts, +VDC output (unfiltered) 0 NOTE: Terminals,, and are same point Detector Specifications: Type: Photo-Electric Smoke Detector complies with UL and UL standards. Power Requirements: VDC +/- 0%. Max / Min Voltage Normal Sensitivity:. +/-.0% / FT.. VAC Max VAC Contact Ratings:. VAC Min Alarm and / or accessories (Resistive Load):. VDC Max.0 Amps Max @ VDC VDC. VDC Min 0. Amps Max @ 0VAC VAC Max Trouble Contact (Resistive Load): 0 VAC 0. Amps Max @ VDC 0 VAC Min 0 Current - Detector 0.0 A Standby 0.0 A Alarm 0.0 A Standby 0.0 A Alarm 0.0 A Standby 0.0 A Alarm LED / Reset Copyright 0, Sargent Manufacturing Company, an ASSA ABLOY Group express written permission of Sargent Manufacturing Company is prohibited. A00 (0/)

Fuse PTOV (V / /A) V AC/DC INPUT CIRCUIT BOARD (shown with -pin jumper for nondetectored units) TEST SWITCH V AC/DC POWER INPUT -PIN JUMPER SOLENOID CONNECTION TWO PIN JUMPER WIRE Support Unit Single Station Wiring Diagram (VAC/DC Input) 0V AC INPUT CIRCUIT BOARD (shown with Wiring Harness detectored units) Fuse PTOV (V / /A) TEST SWITCH 0V AC POWER INPUT SOLENOID CONNECTION TWO PIN JUMPER WIRE WIRING HARNESS SEE PAGES - FOR ADDITIONAL WIRING OPTIONS Support Unit Single Station Wiring Diagram (0VAC Input) VAC/DC Board -Pin 0VAC Board -Pin SOL SOL Master Unit Single Station Wiring Diagram (VAC/DC Input) VAC/DC Board SOL Smoke Detector 0 Master Unit Single Station Wiring Diagram (0VAC Input) 0VAC Board SOL Smoke Detector 0 All wiring diagrams are shown with circuits energized in stand by mode. Once alarmed, detector remains in alarm until reset by turning the reset switch on the detector. Refer to ANSI NFPA for recommended smoke detector applications. Environmental limits: 00 F( C); % relative humidity; not for use where high concentrations of corrosive vapors exist. Do not install where air velocity exceeds 0 ft. per minute. Copyright 0, Sargent Manufacturing Company, an ASSA ABLOY Group express written permission of Sargent Manufacturing Company is prohibited. A00 (0/)

Checking Procedures: Turn the power to the unit On. Red LED light should illuminate at second intervals. Open the door to the hold open point. The door should hold open. Manually pull door out of hold open and release. The door should close. Open the door to the hold open position. Press the Test / Reset Switch button on the power supply board. Door should close. Press the Test / Reset Switch button again. Open the door to the hold open position. Inducing smoke into the smoke detector chamber assembly will bring the unit into alarm. The red LED will be continuously illuminated and the door will close. After clearing the smoke chamber, reset the unit as described below. Resetting Instructions: Remote Reset: Cycle main power by turning the facility main power supply OFF then ON. NOTE: If there are other units connected to the same power supply, those doors will close. They will have to be reopened returning them to the hold open position. Local Reset: Insert a small flat head screwdriver through the cover and into the slotted light tube on the smoke detector as shown. Turn screwdriver slightly (about / turn) clockwise until hitting stop and hold for seconds until the Red LED turns OFF. WARNING: Do not force past the stop. Doing so may damage the smoke detector. Once the detector is reset and the smoke has cleared, the detector s Red LED should flash once every seconds. The door(s) should hold open now. Maintenance of Smoke Detectors: It is recommended to clean smoke detectors at least every six months. The frequency of cleaning will depend upon local ambient conditions. The smoke detector in this door closer-holder has been enhanced with a feature that detects when a smoke-sensing chamber requires cleaning due to dirt and dust. The need for cleaning is indicated by the flashing of the Red LED once per second. Normal Supervisory Operation - Red LED flashes once every seconds. Dirty Chamber needs cleaning - Red LED flashes once every second. Smoke Detection - Red LED is continuously illuminated. To clean the smoke detector assembly, follow these instructions: (NOTE: Before servicing the system, notify the proper authorities that the smoke detector system is undergoing maintenance and will be temporarily out of service. Disable the zone undergoing maintenance to prevent unwanted alarms.) Remove detector cover and screen assembly using a standard screwdriver. Turn the screwdriver in the cover slot to loosen the cover and carefully rock the cover back and forth until it snaps out of place. See slot location below. Inspect chamber for particles and dust. Vacuum the screen, cover, and photo chamber. Then use clean, compressed air to loosen and blow out any remaining debris. Before reassembling the detector, be sure all parts are free of dust and debris. Slot for screwdriver to remove cover RP Test Point RP Test Point Cover and Screen Chamber Replace cover and screen, aligning cover snaps. Press cover onto chamber until it snaps into place. Measure and record the test voltage at test points RP and RP (see below).if the smoke detector is operating normally and was cleaned effectively, the test voltage will be greater than.0vdc and less than.vdc. The test voltage will increase with dust accumulation in the smoke sensing chamber. A difference in test voltages over time will provide and indication of dust accumulation. Enable the system and inform proper authorities that system is operational. Copyright 0, Sargent Manufacturing Company, an ASSA ABLOY Group express written permission of Sargent Manufacturing Company is prohibited. A00 (0/)

MASTER WIRING DIAGRAM FOR -WIRE (CLASS A) SYSTEM WITH ALARM PANEL MONITORING The alarm circuit monitors if smoke is detected The detector trouble circuit monitors if power is lost to the detector. VDC Output Board VDC @ 0.A Max. P P V AC/DC or 0V AC Input (MPS0 or equiv.) 0 VDC Alarm Alarm Panel EOL Res Trouble VDC Output V DC @ 0.A Max. Board P P V AC/DC or 0V AC Input (MPS0 or equiv.) 0 VDC V DC @ 0.A Max. VDC Output Board P P V AC/DC or 0V AC Input (MPS0 or equiv.) 0 VDC Notes: End of Line (EOL) resistor determined and supplied by others. Terminal numbers shown correspond to position numbers of terminal strips on detector. Additional units may be added as required based on this schematic. See electrical data sheet. Do not overload circuits. All wiring connections use standard wiring practice conforming to local wiring codes. Copyright 0, Sargent Manufacturing Company, an ASSA ABLOY Group express written permission of Sargent Manufacturing Company is prohibited. A00 (0/)

MASTER WIRING DIAGRAM FOR -WIRE (CLASS B) SYSTEM WITH ALARM PANEL MONITORING The alarm circuit and trouble circuit monitor if smoke is detected VDC Output VDC @ 0.A Max. Board P P V AC/DC or 0V AC Input (MPS0 or equiv.) 0 VDC UL Listed Fire Alarm Panel Alarm & Trouble To Terminal 0 & On Additional Units or To EOL Resister on Last Unit VDC @ 0.A Max. VDC Output Board P P V AC/DC or 0V AC Input (MPS0 or equiv.) 0 VDC Notes: End of Line (EOL) resistor determined and supplied by others. Terminal numbers shown correspond to position numbers of terminal strips on detector. Additional units may be added as required based on this schematic. See electrical data sheet. Do not overload circuits. All wiring connections use standard wiring practice conforming to local wiring codes. Copyright 0, Sargent Manufacturing Company, an ASSA ABLOY Group express written permission of Sargent Manufacturing Company is prohibited. A00 (0/)

Wiring Diagram for -0 to 0/-0 To 0/-0 Unit - v ONLY Field Wiring Provided by Others -0 Unit -0v or v Input Nut or Splice Connector (Provided) To Interconnection Wiring Diagram # # # # 0 Notes: Five Detectors Maximum. Use Terminals and to wire detectors in parallel (see #,#, and #). Use Terminal 0 to signal remote detectors with relay contact only (see # and #). # Remote Detector C Relay N.O. Copyright 0, Sargent Manufacturing Company, an ASSA ABLOY Group express written permission of Sargent Manufacturing Company is prohibited. A00 (0/)