PDD-FT-3. Fire Panel Interface With EOL Trigger. Installation and Specifications Manual

Similar documents
PS6 SERIES. Installation PS6 SERIES. Power Supplies c/w Fire Panel Interface, EOL Trigger and Standby Power Option

PDD-8PCI. Power Distribution Board With Supervised Interface. Installation and Specifications Manual

APS-300 SERIES DUAL VOLTAGE UL 294 LISTED ACCESS CONTROL POWER SUPPLIES

10-175UL INSTALLATION. Power Supply UL. Access Control Power Supply/Charger. Installation and Specifications Manual

1 Description. 2 Specifications. HP600ULM Access Control Power Supply/Charger with Power Distribution Controller PN 52393:A 1/05/06 ECN

RPSMLR2 RPSMLR2BB. Panic Device Power Controller Installation Guide LISTED. Rev

Installation Guide for AL300ULM. Multi-Output Access Control Power Supply Charger

Installation Guide for AL400ULM. Multi-Output Access Control Power Supply Charger

Multi-Output Access Control Power Supply Chargers VDC or 24VDC VDC or 4 24VDC.

Installation Guide for AL600ULM. Multi-Output Access Control Power Supply Charger. Rev

AL600ULADA. NAC Power Extender. Installation Guide

Multi-Output Access Control Power Supply Charger VDC or 24VDC VDC or 3 24VDC.

Installation Guide for models:

Series. Access Power Controllers. Installation Guide

SP-1000X. Panic Device Power Controller Installation Guide. Rev

Installation Guide for models:

AL802ULADA. NAC Power Extender. Installation Guide. (See Application Guide for additional information) Rev

- 4 12VDC or 24VDC VDC or 24VDC - Eight (8) Fused Outputs - Eight (8) PTC Outputs. Installing Company: Service Rep.

AL400ULACM AL600ULACM - 4 amp - 12VDC or 6 amp. - Fused Outputs - Fused Outputs

Installation Guide for AL800UL-ADA. NAC Power Extender. Rev

ACSI Series 1550K-MD and 1550-MD Motor Drive Electric Latch Retraction

AL800ULADA. NAC Power Extender. Installation Guide

Securitron Magnalock Corporation S. 51 st St., Ste. 102 Phoenix, AZ Phone: (800) MAGLOCK

For a red enclosure add an R suffix to the part # e.g. eflow4na8dr. Altronix Corp th St. Brooklyn, NY. Installing Company: Service Rep.

ACM8 & ACM8CB. Access Power Controllers Installation Guide. - Fused Outputs - Fused Outputs. - PTC Outputs - PTC Outputs. Models Include: Rev.

FIREFORCE 8 NOTIFICATION APPLIANCE CIRCUIT EXPANDER INSTALLATION & OPERATION MANUAL

Cookson Company 1901 South Litchfield Road Goodyear, AZ Phone:

Multiplex Eight Input Remote Modules

F I R E G A R D D C EXTENDED PERFORMANCE RELEASE DEVICE SAFE A N D SECURE

For a red enclosure add an R suffix to the part # e.g. eflow4na8r. Altronix Corp th St. Brooklyn, NY. Installing Company: Service Rep.

MODEL B2 INSTALLATION MANUAL

ACSI AO ELECTRIC LATCH RETRACTION CONTROLLER INSTALLATION INSTRUCTIONS I.D. 1089, REV. F

GENERAL STANDARD FEATURES. ISO-9001 Engineering and Manufacturing Quality System Certified to International Standard ISO-9001 PATENT PENDING

Model PAD-3 Distributed Power Module NAC Expander Installation, Operation, and Maintenance Manual

FireNET Plus Wiring Instructions

Remote NAC Power Supply D7038

TECHNICAL DATA OBSOLETE

This wiring diagram describes circuit connections for all models of the Series Quaestor-SZU Releasing Fire Control

Access Power Controllers with Power Supplies

July 14, 1999 DF C-100.

Installation, Operating and Maintenance Manual

ACM4 Series UL Listed Sub-Assembly Access Power Controllers

June 10, 2002 DF C S2424

FIREFLY II PLUS RELEASE DEVICES INSTALLATION MANUAL

Booster Power Supply Manual

FMR Installation Instructions. Addressable Fire System Controller

Stopper Station Series Push Button Models SS2xx2, SS2xx5, SS2xx9

TECHNICAL DATA. multi-hazard. model vfr400. Release Control Panel 290a. January 16, 2014

MADE IN THE U.S.A. ADVANCE FIRE CONTROL MODEL LM21-AFC MANUAL RELEASE DEVICES TEST WEEKLY TO ASSURE PROPER OPERATION OF RELEASE DEVICE/CONTROL PANEL

Addressable NAC Output Module D327A

THE "SS90" SERIES RELEASE DEVICES MODEL B2 INSTALLATION MANUAL

4100U City and Relay Cards Installation Instructions

Duct smoke housings, 4-wire D341/D341P and D342/D342P

DT8050A DUAL TEC Motion Sensor with Anti-Mask - Installation Instructions

ACM8 Series UL Listed Sub-Assembly Access Power Controllers. Installation Guide. ACM8 - Eight (8) Fuse Protected Outputs

Notification Appliance Circuit Module

Excel-EN Conventional Fire Control Panel

M O D E L S F I R E G A R D M C V ADVANCE FIRE CONTROL RELEASE DEVICE

Model 17A00 Expansion Enclosure

RELEASE DEVICES RELEASE DEVICE-WPS MODELS A/B INSTALLATION MANUAL U.L. LISTED CANADIAN LISTED CSFM: :100 GENERAL DESCRIPTION:

Installation Instructions. PS902 Power Supply. These instructions cover the following parts: PS902 Power Supply Specifi cations:

Firefly II Multi Voltage RELEASE DEVICES. Firefly II & IIB-MV INSTALLATION MANUAL

Application, Installation, Operation & Maintenance Manual

LiftMaster 300 Windsor Drive Oak Brook, IL LiftMaster.com

Specification/ Data Sheet

PNC 1000 SERIES 2, 4, 8 Zone Fire Alarm Control Panel

# amp # amp 12/24 VDC POWER SUPPLY INSTALLATION MANUAL. 4202/4MA, Rev. E 0804

AL802ULADA. NAC Power Extender. Installation Guide. (See Application Guide for additional information)

FCPS-24F FIRE ALARM FIELD CHARGER/POWER SUPPLY FOR FIRE PROTECTION/SIGNALING SERVICE FCPS-24F/FCPS-24FE. Field Charger/Power Supply

RELEASE DEVICE CONTROLS

APPLICATION NOTES. Stone Technologies Corporation Westrock Dr. #4 Austin, Texas OUT + + IN - + IN - + IN - + IN -

General Routing Interface

SOLID STATE SECURITIES, INC. THE "SS90" SERIES RELEASE DEVICES MADE IN THE U.S.A. SS90-WPS MODEL A/B INSTALLATION MANUAL

MR-2602 Two Zone Fire Alarm Control Panel

MADE IN THE U.S.A. MODELS A/B INSTALLATION MANUAL

Cautions and Warnings. Introduction 4009 NAC POWER EXTENDER

THE "SS90" SERIES RELEASE DEVICES MADE IN THE U.S.A. MODELS A/B INSTALLATION MANUAL

TECHNICAL DATA. Humidity: 85% Relative Humidity (non-condensing) at 90 F (32 C) maximum.

POWERPATH PS-8 (105531) PS-8E (100263) PS-6 (105530) PS-6E (100262)

IDP-Zone-6 Six Zone Interface Module

Operation and Installation Guide. Fire Alarm Control Panel

"SS90" SERIES CONTROLS MODEL C INSTALLATION MANUAL

KT-100 Door Controller

D326A/D334A/D339A. Installation Instructions. Point Contact Modules

TECHNICAL DATA SHEET CONVENTIONAL FIRE ALARM SYSTEMS Conventional Fire Alarm Control Panel

Illuminated Stopper Station Push Button

Duct smoke housing, 2-wire D340/D340P

WARNING. Installation Tip: Try out this unit before installing onto a fire door system. Test and learn the release INTRODUCTION

AL1002ULADA. NAC Power Extender. Installation Guide. (See Application Guide for additional information) Rev X

F220-B6PS/M. Installation Guide. Addressable Detector Bases

INSTALLATION GUIDE XR5FC AND XR5SL COMMERCIAL FIRE PANELS

BT1 SINGLE ZONE FIRE ALARM SYSTEM OPERATORS MANUAL

Wiring Instructions. Single Doors 99 Checkmate Series Use one or Master Unit each door or one or Support unit each door

Rack Mount Series Installation Guide

Models NFPA 1221-A, NFPA 1221-B Public Safety DAS Annunciator Panel. Revision E 61117

IP Access FACP Adapters. Installation Guide. Entrada2DMK - IP Access FACP Adapter Kit. Kit Includes: Entrada2DMR - IP Access FACP Receiver

M O D E L S FIREGARD BV EXTENDED PERFORMANCE RELEASE DEVICE

AL1042ULADA. NAC Power Extender. Installation Guide (See Application Guide for additional information) Rev

Public Safety DAS Annunciator Panel

Stopper II Heated Enclosure

Transcription:

Installation -3-3 Fire Panel Interface With EOL Trigger Installation and Specifications Manual ISPSFPD-3 PCN16045 R12/17GR 2017 Rutherford Controls Int l dormakaba Group www.rutherfordcontrols.com Phone: 1.800.265.6630 Fax: 1.800.482.9795 E-mail: sales@rutherfordcontrols.com

Details The -3 board is a fire panel control interface. This board can be used to control DC output based on a fire alarm control panel. Two outputs switch state on alarm. Features Non Latching or Latching mode Universal 12VDC or 24VDC Operation Reverse polarity protected Normally ON & Normally OFF Output Output LED s indicate condition Outputs can be Triggered with: 1) N/O or N/C Switch with Supervised End of Line Resistor (EOL) 2) N/C Switch with () over ride 3) N/C Switch with (-IN) auxiliary 4) Ground on any trigger input when () Jumper is enabled Form C DPDT Relay Indicates Trigger Status 3 Amp Transfer Relay Contacts Auto or manual reset by jumper selection Installation Instructions 1. Mount the -3 board in a suitable location in close proximity to the power supply. Note: a) Ground fault detection will only work if conductive stand offs are used and power supply enclosure is properly grounded. b) As this device can be used to power multiple devices ensure that all wiring is of an appropriate gauge for the devices being installed. c) This RCI board is for use in a controlled indoor environment. The -3 and all devices connected to or powered through the -3 shall be installed within the same continuous building structure. Installation must be in accordance with local building and fire codes. Check with Authority Having Jurisdiction (AHJ) for details prior to installing. d) All power limited wiring must be a minimum of.25 from non-power limited wiring. e) Maximum torque of 7 in*lb for black input and output terminals. 2. Connect INPUT terminals to output of DC supply, paying close attention to polarity of DC output from power supply. 3. Connect devices to be powered to output terminals of -3 control board, paying close attention to polarity requirements. Minimum 22AWG and maximum distance of 6170ft. for field wiring. 4. Set jumpers (,,, and ) as required for proper installation. 2

5. Connect fire alarm control panel to EOL input terminals, ensure the 2.2K resistor is installed at the terminals in the fire alarm panel. a) See fire alarm control panel installation and operation manual for details about signaling requirements. b) Fig s 2-6 in this installation guide will provide details on wiring to the fire alarm control panel. 6. Connect any required monitoring equipment to the trigger relays using appropriate cabling. 7. This unit is to be powered from a 10 Series RCI Power Supply or a UL listed power supply. 8. Apply power to power supply to activate control board and test all connected devices. Specifications For UL listed power supply UL 294 6e and ULC S319 Class 1 Access Control System Unit Access Control Levels: Endurance: Level 4 Line Security: Level 1 Power Standby: Level 1 Destructive Attack: Level 1 Input Input Voltage: 12 or 24VDC ± 10% Typical Current Draw with no Output Load: 10mA @ 12VDC 15mA @ 24VDC Output Output Relay Rating: 3A Monitor Inputs EOL (End of Line) Trigger: Trigger at + or 50% of 2.2K Trigger Trigger Reset Input Ground Fault Trigger (see note 1a) Monitor Outputs Trigger Relay Rating: 1A DPDT Environmental Use in a controlled indoor environment Warning: Improper wiring connections may result in damage to this product. Mise en garde: Un mauvais raccordement des câbles risque d endommager ce produit. 3

Description of -3 Connections See Fig. 1 Input Power -INPUT+ : 2 position terminal block with self clamping screws will accept multiple 12AWG wires Universal input. Output Power Two, 2 position terminal blocks. Self clamping screws will accept multiple 12AWG wires. -N/ON+ are normally ON output power. This output is ON when the -3 is not triggered. -N/OFF+ is normally OFF. This output is ON when this unit is triggered. The transfer relay is rated at 3 Amps. Power LED s A red led above each output indicates which output is active. Input Trigger EOL* 2 position terminal block Will accept 12AWG wire. This input must see the 2.2K ohm end of line resistor to be in the normal set condition. A change in resistance of ± 50% will cause the trigger relays to drop out in the Triggered mode. This change in resistance is caused by the supervised wire between the EOL at the fire panel and the -3 being shorted or opened. The EOL supervises the pair of wires. Input Trigger * 2 position terminal block - Will accept 12AWG wire. This pair is normally closed and can be connected to an override switch. When is open, unit will trigger. Input Trigger -IN* 2 position terminal block - Will accept 12AWG wire. This pair is normally closed and can be connected to an auxiliary device. When -IN is open, unit will trigger. Reset 2 Position Terminal Block* 2 position terminal block - Will accept 12AWG wire. When this pair is shorted, input triggers do not latch. If pair is open, the input triggers will latch until alarm is corrected and RESET is momentary closed to reset trigger. *Minimum 22AWG and maximum distance of 6170ft for field wiring. Jumpers - - Jumpers are used to activate (remote) features as required. Jumpers This jumper is used to enable ground supervision or the inputs. If the jumper is connected to both headers, and the mounting hole adjacent to jumper is connected to earth ground, a ground on any of the input triggers will cause a trigger. Trigger Status Terminal block Two, 3 position terminal blocks - Will accept 12AWG wire. Form C DPDT relay with a 1 Amp rating will indicate the condition of trigger. C and are normally open in the normal energize not triggered state. C and are normally closed in the normal energized not triggered state. These contacts may be used to provide feedback to the FACP or other auxilary devices. 4

Fig. 1 - -3 Connections DC Input Ground Fault Jumper Reset Input End Of Line Trigger Output Override Input - IN Output Led's Auxilary Input - N/ON + - N/OFF + Normally "On" Output Normally "Off" Output Application Diagrams - IN Fig. 2 - Fire Panel Connections for Non-Latching Automatic Reset Operation This application illustrates how to connect the -3 to a power supply for main input as well as a fire alarm control panel. If wired in this manner, outputs will change state only as long as the fire alarm relay is active. When the fire alarm resets the -3 outputs will also reset. 5

- IN Fig. 3 - Fire Panel Connections for Latching Release with N/O Manual Reset This application illustrates how to connect the -3 to a power supply for main input as well as a fire alarm control panel. If wired in this manner, outputs will change state whenever the fire alarm relay activates and remain latched in the triggered state until reset by activating the N/O switch. Note: Remove jumper for manual reset operation. Remarque: Retirez la bretelle pour effectuer une réinitialisation manuelle. - IN - IN Fig. 4 - Connections for Non-Latching release reset using multiple -3 boards This application illustrates how to connect the -3 to a power supply for main input as well as a fire alarm control panel. If wired in this manner, outputs will change state only as long as the fire alarm relay is active. When the fire alarm resets the -3 outputs will also reset. Connecting the EOL input of one board to the trigger relay of the next board as shown will allow for override and reset of multiple boards. Note: The jumper must be left in place on all boards for automatic reset operation. Remarque: La bretelle doit être laissée en place sur tous les panneaux pour effectuer une réinitialisation automatique. 6

- IN - IN Fig. 5 - Connections for latching release with N/O manual reset using multiple -3 boards (Master & Slave) This application illustrates how to connect the -3 to a power supply for main input as well as a fire alarm control panel. If wired in this manner, outputs will change state whenever the fire alarm relay activates and remain latched in the triggered state until Master is reset by activating the N/O switch. Connecting the EOL input of one board to the trigger relay of the next board as shown will allow for reset of multiple boards. Note: The jumper must be left in place on all slave boards except the one that is directly connected to the fire alarm (Master), reset, and switches. Remarque: La bretelle doit être laissée en place sur tous les panneaux asservis, sauf celui qui set directement connecté à l alarme de feu (d exploitation), situé près des boutons de réinitialisation et d annulation. Fig. 6 - Fire Panel Connections for Latching Trigger with N/O Manual Reset and N/C override with Battery Backup Power limited AC SEE TE 4. N/O MANUAL RESET - IN SEE TE 6. GROUND FAULT JUMPER POWER SUPPLY INTER-CONNECT. RESET EOL L N G AC Fail DC - N/ON + - N/OFF + This application illustrates how to connect Power limited SEE TE 3. SEE TE 5. the -3 to an RCI AC FAIL CIRCUIT ONLY REQUIRED WITH BATTERY BACKUP. Power Supply for main TE: input, AC failure as well 1) DISCONNECT AC INPUT PRIOR TO SERVICING. 2) ALL POWER LIMITED CIRCUITS TO HAVE A MINIMUM Non-power limited SPACING OF.25" FROM N-POWER LIMITED CIRCUITS. as a fire alarm control BATTERY TES 3-6 REFER TO ONLY 3) FOR MANUAL OVER-RIDE REMOVE JUMPER "" AND INSTALL N/C SWITCH. panel. If wired in this 4) FOR MANUAL RESET REMOVE JUMPER "" AND INSTALL A N/O SWITCH. 5) FOR -IN REMOVE JUMPER "" manner, trigger outputs AND INSTALL A N/C CIRCUIT. 6) JUMPER IS FOR GROUND FAULT DETECTION ON ENABLES GROUND FAULT, REMOVED DISABLES will change state whenever the fire alarm, or GROUND FAULT. AC failure relays activate. The -3 outputs will remain in the triggered state until both relays have been reset and the N/O manual reset is triggered. Note: Ensure jumpers for,, and IN are removed to allow terminals to operate correctly. Remarque: Assurez-vous que les bretelles, et IN sont retirées afin de permettre aux terminaux de fonctionner correctement. 7 N/C MANUAL OVER-RIDE

-3 Troubleshooting Guide Problem No DC output from terminals. Trigger is active and will not reset. Trouble output relay is de-energized. (Relay terminals are labeled shown in the Normal, energized, no trouble condition. Relays are energized when no trouble is detected.) Solution - Check AC Power. - Check Power Supply for voltage output. - Check devices connected to outputs for a short circuit. (PTC s may require short to be removed for several minutes before automatically resetting). - Check trigger jumpers. Output LED should be lit if output is active. - Check for proper wiring connections on trigger connections. - Ensure that 2.2K resistor is installed at End of Line position in the wiring. - Check devices connected to outputs for a short circuit. (PTC s may require short to be removed for several minutes before automatically resetting.) Notes For Technical Support: 1.800.265.6630 WWW.RUTHERFORDCONTROLS.COM