FIRE PROTECTION. 1. Vertical fire pumps shall not be used at the University.

Similar documents
1.1 Refer to Section for General Mechanical Requirements. 1.3 Refer to Section for Pipe and Equipment Identification Requirements.

C. All components of the systems described shall meet the requirements as stated herein and shall be approved by the Architect and Consultant.

CubeSmart Gulf Breeze Storage AUTOMATIC FIRE SPRINKLER SYSTEM

THE JAMES RUSHTON EARLY LEARNING AND FAMILY SUCCESS CENTER #2616 ISSUE FOR CONSTRUCTION

SECTION WET PIPE FIRE PROTECTION SPRINKLER SYSTEM

West District Library Section Campeau Drive, Ottawa SPRINKLER SYSTEMS City of Ottawa Project No. CR Page 1 of 8

SECTION WET-PIPE SPRINKLER SYSTEMS

FIRE SUPPRESSION SPRINKLER SYSTEM

B. Related Sections: The following Sections contain requirements that relate to this Section.

University of Houston Master Construction Specifications Insert Project Name SECTION DRY-PIPE FIRE SPRINKLER SYSTEM PART 1 - GENERAL

Division 21: FIRE SUPRESSION WET-PIPE SPRINKLER PROTECTION SYSTEM. The Academy Sept Table of Contents 1 Division 21

SECTION FIRE-SUPPRESSION STANDPIPES

SECTION FIRE PROTECTION. A. Examine all conditions as they exist at the project, prior to submitting a bid for the work of this section

COBB COUNTY SCHOOLS /S&A % BID DOCUMENTS 2/18/11 SECTION SPRINKLER SYSTEM

MLA Architects Pierz Public Schools ISD #484 Healy High School Multi-Purpose & Choir Additions Pioneer Elementary School Class Room Addition Pierz, MN

A. This section includes design and performance information for fire protection and suppression systems.

1.2 CODES AND REGULATIONS A. Sprinkler system design, equipment, materials, devices, and installation shall conform to the following:

SECTION DRY-PIPE SPRINKLER SYSTEMS

SPRINKLERS TABLE OF CONTENTS

B. Product Data: Provide manufacturers catalogue information. Indicate valve data and ratings.

SECTION WET AUTOMATIC FIRE SPRINKLER SYSTEMS

NORTHWESTERN UNIVERSITY PROJECT NAME JOB # ISSUED: 03/29/2017

DIVISION 21: FIRE SUPPRESSION WATER BASED FIRE SUPRESSION SYSTEMS

Gas Station & C Store SECTION CWM Job No

A. Section includes wet-pipe sprinkler system, system design, installation, and certification.

SECTION WET-PIPE SPRINKLER SYSTEMS EASY RISER CHECK VALVE

NORTHWESTERN UNIVERSITY PROJECT NAME JOB # ISSUED: 03/29/2017

WET AUTOMATIC FIRE SPRINKLER SYSTEMS

A. Hydraulic calculations shall be prepared in accordance with Chapter 23 of NFPA 13 with the following exceptions:

SECTION DRY PIPE SPRINKLER SYSTEMS MODEL G SERIES DRY VALVE

SECTION DRY PIPE SPRINKLER SYSTEMS MODEL F SERIES DRY VALVE

SECTION WET-PIPE SPRINKLER SYSTEMS

SECTION SPRINKLER SYSTEMS

DARTMOUTH COLLEGE DESIGN November 15, 2007 & CONSTRUCTION GUIDELINES

DIVISION 21 FIRE SUPPRESSION SECTION FIRE PROTECTION SPECIALTIES

Revision May All designs must be submitted to FM Global for review and approval prior to issuing such for bids.

ADDENDUM NO. 3 March 19, 2018

Environmental Health & Safety

DIVISION 21 - FIRE SUPPRESSION

DIVISION 21 - FIRE SUPPRESSION

UNIVERSITY OF MISSOURI Fire Protection System Design 2016 Q1

SECTION AUTOMATIC SPRINKLER PIPING

SECTION DRY-PIPE SPRINKLER SYSTEMS

A. Standard-Pressure Piping System Component: Listed for 175-psig minimum working pressure.

WET-PIPE SPRINKLER SYSTEMS

SECTION WET FIRE SPRINKLER SYSTEMS

UC Santa Cruz Campus Design Guide. Includes the following sections: None DESIGN REQUIREMENTS

2. Welding Materials and Procedures shall conform to the ASME Code.

SECTION FIRE-SUPPRESSION SYSTEMS

B. The sprinkler system shall be designed to meet the more stringent of the requirements of NFPA 13 and FM Global requirements.

North Hanover Township School District North Hanover Township, New Jersey

TABLE OF CONTENTS

B. Section Identification for Fire Suppression Piping and Equipment.

SECTION PREACTION SPRINKLER SYSTEMS

Mercury Plastics New Building February TABLE OF CONTENTS

DIVISION 21: FIRE SUPPRESSION

B. Galvanized-Steel-Sheet Sleeves: inch minimum thickness; round tube closed with welded longitudinal joint.

Port of St Helens SIA Aircraft Hanger Scappoose, OR

EL DORADO COUNTY REGIONAL FIRE PROTECTION STANDARD

Design and Construction Standards SECTION FIRE SUPPRESSION

DIVISION 21 FIRE SUPPRESSION FIRE SUPRESSION

SECTION FIRE SUPRESSION

UMC El Paso Far East Clinic and Neighborhood Healthcare Center West Issue for Construction Page Project No and April 13, 2015

A. This Section includes the following fire-suppression piping inside the building:

ADDENDUM #3 DATE: August 8, 2018 Page 1 of 1. The Curators of the University of Missouri

PART 1 - GENERAL SECTION FIRE PROTECTION BASIC MATERIALS AND METHODS

SECTION WET-PIPE SPRINKLER SYSTEMS

SECTION FIRE SUPPRESSION SYSTEMS

UBC Technical Guidelines Section Edition Fire Protection General Requirements Page 1 of 6

SECTION FIRE PROTECTION

A. All Fire Suppression System design and installation shall comply with the most current and adopted version of NFPA 13.

New Rigby Elementary School February TABLE OF CONTENTS

SECTION SPRINKLER SYSTEMS

SECTION ADDENDUM NO. 1 FIRE SPRINKLER SYSTEM

SECTION WET-PIPE FIRE SUPPRESSION SPRINKLERS

SECTION DRY-PIPE FIRE-SUPPRESSION SPRINKLERS

SECTION FIRE PROTECTION

SECTION DRY-PIPE SPRINKLER SYSTEMS

Model MBEC-14. Extended Coverage Ordinary & Extra Hazard Horizontal Sidewall Sprinklers for Metal Building Applications. Model MBEC-14 (SIN R6932)

Facility Fire-Suppression Water-Service Piping

SECTION KITCHEN HOOD AND DUCT FIRE SUPPRESSION SYSTEM

KITCHEN HOOD AND DUCT FIRE SUPPRESSION SYSTEM

UNIFIED FACILITIES GUIDE SPECIFICATIONS

SECTION FIRE-SUPPRESSION PIPING

SECTION WATER BASED FIRE SUPPRESSION SYSTEMS

SECTION FIRE PROTECTION SYSTEMS

Addendum No. 2 to the Contract Documents

PHYSICAL FACILITIES. 1 General. 2 Related Requirements. 5 Quality Assurance. 3 Wiring. 4 Submittals

Model F1 Residential Sprinklers for Design Density of.10 gpm/ft 2

Council Bluffs, Iowa Division TOC 1 TABLE OF CONTENTS DIVISION 21 FIRE SUPPRESSION

Kenworth Sales Co. - North Las Vegas, Nevada November TABLE OF CONTENTS

Lucy s Pizza 100% CD Specification 06/22/2018

DIVISION 21: FIRE SUPPRESSION

SECTION COMMON WORK RESULTS FOR FIRE SUPPRESSION

END OF SECTION

TABLE OF CONTENTS DIVISION 21- FIRE SUPPRESSION PAGES SECTION WATER BASED FIRE PROTECTION SYSTEMS... 5

Wayne State University WSU Project No Chatsworth Tower Apts. Misc. Bldg. Upgrades DSD Project No

DESIGN AND CONSTRUCTION STANDARDS SPECIFICATION GUIDELINES

UNIVERSITY SERVICES ANNEX James Madison University Harrisonburg, Virginia State Project Code: Architect s Project Number:

Additional Bulletins applicable to all F1RES LL Sprinklers Wall Wetting - Bulletin 007 Design and Installation - Bulletin 140

Transcription:

15500 - FIRE PROTECTION PART I DESIGN GUIDELINES A. General 1. Vertical fire pumps shall not be used at the University. 2. coupling piping shall be permitted for sprinkler and standpipe systems only. B. Working Plans for Sprinkler Work 1. The specifications shall require the contractor to submit complete, coordinated working plans, prior to the commencement of any work, and to submit and obtain all approvals from agencies having jurisdiction including the New York City Department of Buildings, Fire Department, Underwriters' Laboratories and Factory Mutual. 2. Working plans shall include the following information: a. Name and address of Owner. b. Name and address of the Architect, Engineers and Contractor. c. Location of project. d. Symbol list and abbreviations for entire fire protection system. e. North Arrow. f. Drawing scale (1/8" = 1'-0" minimum) g. Plans of all floors showing partitions, exits, beams, chutes, lights, unit heaters, diffusers, registers, ducts over four feet wide and ceiling heights. h. Riser diagram of entire system indicating all alarms, valves, tamper switches, floor control assemblies, air compressors, Siamese connections, mains, risers, source of water supply, quantity of sprinklers in each fire area on each floor, water pressure at each floor and height of each floor. i. Location, name, type, temperature rating and model of sprinkler heads. j. Structural beams and penetrations. k. Source of water supply, service size, static and residual pressure of street main(s), flow at residual pressure, and whether dead end or loop, and location of fire hydrants. l. Number of sprinklers on each riser, floor and each room and total in the building, including location and size of risers, mains, branches and most remote area. m. Cutting lengths of pipe. n. Water flow alarms. o. Type of hangers, inserts and sleeves. p. Inspector's test connections, drain pipes and test pipes. q. Crosses, riser nipples and sizes. r. Provisions for flushing. s. Location of Fire Command Station. t. Siamese locations. u. Valve locations. v. Hydraulic calculations of entire system including branches, mains and cross-mains performed by a licensed professional engineer. w. Fire pump, jockey pump and related appurtenances. x. Indicate all fire standpipe valve stations, cabinets, piping, valves, Siamese, test connections, roof manifold and all related appurtenances. 15500-1 May 2009

C. SPRINKLER DESIGN CRITERIA 1. All areas of the building shall be provided with automatic sprinklers. In general, wet sprinkler systems shall be designed. Pre-action sprinkler systems shall be considered in areas where an accidental discharge or water leak cannot be tolerated. Areas include computer rooms, library rare books storage areas, etc. 2. Where sprinklers are installed in areas subject to freezing (loading docks, etc.) dry systems shall be considered. 3. Sprinkler pipe shall not be Schedule 10, even if allowed by Code. Schedule 40 shall be the minimum allowable. 4. The sprinkler system shall be hydraulically designed in accordance with local Code requirements unless required otherwise by the Insurance Underwriter. The maximum pipe velocity permitted in the piping system is 20 feet per second. D. GROOVED COUPLING PIPING 1. Malleable and/or ductile iron couplings shall conform to ASTM A-47 and ASTM A-536 respectively complete with gasket, bolts and nuts approved for fire protection service. 2. Provide galvanized couplings for galvanized piping systems. E. MATERIALS FOR PIPE SERVICE MATERIAL SCHEDULE DESIGNATION Fire Standpipe Below Ground Sprinkler Below Ground C-151 & C-104 C-151 & C-104 Fire Standpipe Above Ground Black Steel 40 ASTM A-120 Sprinkler Above Ground Black Steel 40 ASTM A-120 Drain Above Ground Galvanized Steel 40 ASTM A-120 Sprinkler Tank Fill Line Galvanized Steel 40 ASTM A-120 Air Lines Copper or Galvanized Steel Type L 40 ASTM B-88 ASTM A-120 15500-2 May 2009

F. MATERIALS FOR FITTINGS SERVICE MATERIAL WEIGHT TYPE Fire Standpipe Below Ground Sprinkler Below Ground Fire Standpipe Above Ground Sprinkler Above Ground Drain Above Ground Air Lines Cast Iron, Malleable, Ductile, Cast St Cast Iron, Malleable Iron Galvanized Cast Iron Wrought Copper Galvanized Malleable 250, 300 500, 800 1000 250 WOG 125 125 Screwed, Flanged & Coupling Screwed, Flanged & Coupling Screwed & Soldered Screwed G. HOSE STATIONS 1. Hose stations shall be provided so that all areas of the building are within twenty feet of the end of the hose nozzle with the hose in an extended position. Hose length shall not exceed 125 feet. H. FIRE EXTINGUISHERS 1. Fire extinguishers shall be installed in each fire hose cabinet. Provide wall hung fire extinguisher in Equipment Rooms, Electrical Switchgear and Service Rooms, Elevator Equipment Rooms and other areas as required by the Fire Department or Code. I. SIAMESE CONNECTION 1. Siamese connections shall be provided as described in the New York City Building Code. The specifications must state that the threads shall conform to the New York City Fire Department requirements. 2. Siamese escutcheon shall be lettered "Standpipe", "Auto Spkr", "Combination Standpipe and Auto Spkr", "Dry Spkr", etc. and shall be provided with red, green, yellow, and green caps respectively. 3. Finish of siamese assembly including escutcheon, caps and chain shall be polish chrome plated. J. FIRE PUMP TEST STATION 1. Adjacent to the fire pump location, provide three saddle racks, three single jacket cotton rubber lined fire hoses with 2-1/2" brass couplings attached. Fire hose size shall be 2-1/2" and length of each section shall be 50 feet. Also furnish 15500-3 May 2009

three 2-1/2" x 15" red enameled nozzles and three 2-1/2" malleable iron spanners with chains and twelve washers. K. AUTOMATIC BALL DRIP 1. Each siamese and fire pump test connection shall have an automatic ball drip with discharge to a slop sink or floor drain. L. TAMPER SWITCHES 1. All control valves shall be provided with a tamper switch to detect and indicate when a valve has been closed M. WATER FLOW ALARMS 1. Provide adjustable water flow alarms to detect water flow in each fire zone. Whenever a water flow alarm is installed in the piping system, an approved control valve shall be provided upstream of the alarm indicator. N. SPRINKLER HEADS 1. All sprinkler heads will be UL listed, Factory Mutual and New York City BS&A approved. In general, sprinklers shall have a 1/2 inch orifice and ordinary temperature rating (160-165 F) except where required to prevent false sprinkler discharge. 2. Sprinkler heads in unfinished areas without hung ceilings will be all bronze upright or/pendent type. 3. The type of sprinkler head in hung ceilings (recessed, semi-recessed or pendent) will be coordinated with the Architect. 4. Sprinkler heads for a dry system installed in areas without hung ceilings shall be cast brass closed fusible link up-right sprinkler head type. In hung ceiling areas use dry pendant type sprinkler heads. 5. Sprinkler heads for a concealed sidewall installation (recessed or concealed) shall be coordinated with the Architect. 6. In loading dock areas, freight elevator lobbies and similar areas where heads are subject to damage, provide a sprinkler guard with a red enamel finish for pendent and upright sprinkler heads. 7. Provide six (6) spare heads of each type used on project. Include removal tool. O. VALVES 1. Valves for Fire Standpipe and Sprinkler Systems shall be iron body bronze mounted OS&Y solid wedge gate valves with rising stem. All valves shall be stamped with manufacturer name and working pressure of the valve. A valved by-pass around valves six inches and larger shall be provided. 2. Valves shall be provided with properly lettered valve signs indicating the section or portion of the system that is controlled. 3. Check valves except pump discharge shall be UL and FM approved. All valves 15500-4 May 2009

shall be stamped with manufacturers name and working pressure. 4. Check valves on pump discharge shall be flanged flat type UL and FM and BS&A approved. 5. Globe and angle valves shall be UL, FM approved. 6. Valves below ground or floor levels shall be UL, FM and listed. 7. Indicator post for below ground or floor levels shall be UL, FM and listed. 8. Curb valves box shall be three-piece screw type extension box with "Water" indexed cover. 9. Sprinkler branch piping subjected to pressures exceeding 175 psi connecting to a fire standpipe, combined fire protection or sprinkler riser shall be provided with an automatic pressure control valve. The valve shall be UL, FM and BS&A approved. A shutoff valve shall be provided upstream of the pressure control valve. P. ACCESS LADDERS 1. Where valves are located 7 feet or higher above the finished floor, a permanent steel ladder shall be provided. In mechanical rooms and similar areas, a wheel and chain shall be provided. Q. ACCESS DOORS 1. Access doors are required in finished walls, ceilings, partitions, etc., for access to all valves, flow indicators, flushing connections, etc., concealed behind finished construction. R. FLUSHING AND TESTING 1. All sections of the piping system shall be thoroughly flushed at flow rates. 2. All sections of the piping system will be hydrostatically tested at not less than 200 psi for two hours at the building service or siamese. Test pressures shall be maintained by a small capacity pump to minimize water damage in the event of a break. 3. The sprinkler system must be tested in accordance with the requirements of the Building Code of the City of New York. 4. The fire standpipe system must be tested in accordance with the requirements of the Building Code of the City of New York. 5. With the entire system under normal operating pressure, each control valve shall be opened and closed to demonstrate proper operation. 6. All tests shall be performed in the presence of the University's representative, and all authorities having jurisdiction. END OF SECTION 15500-5 May 2009