Project: Customer: Engineer: Pump Manufacturer: Technical Data Submittal Document Model VPS + VPU Pressure Limiting (VFD) with Soft Start Bypass with Automatic Transfer Switch Contents: Data Sheets Dimensional Data Wiring Schematics Field Connections Note: The drawings included in this package are for controllers covered under our standard offering. Actual AS BUILT drawings may differ from what is shown in this package.
with Automatic Transfer Switch From Transfer Switch* 1R CR6 CR8 CR7 1R 4R 4R CR6 CR7 CR8 2R 3R FU1 SSS1 2R 3R LR1 VFD1 POWER MODULE Standard, Listings and Certifications Built to NFPA 20 Underwriters Laboratory (UL) New York City UL218 - Fire Pump Controllers UL 1008 - Automatic power transfer switches for fire pump controllers Accepted for use in the City of New York by the Department of Buildings Enclosure Protection Rating Standard: NEMA 2 (IP31) Optional NEMA 12 NEMA 3 NEMA 3R IP54 Accessories Bottom entry gland plate Lifting lugs Keylock handle Paint Specifications Red RAL3002 Powder coating Glossy textured finish Shortcircuit Withstand Rating 200V to 208V 60Hz 220V to 240V 60Hz 380V to 416V 50 Hz / 60Hz 440V to 480V 60Hz 600V 60Hz HP Standard 100kA Optional 150kA Standard 50kA Optional 100kA 5-60 5-60 5-300 5-400 n/a n/a n/a n/a n/a 5-500 *Please see Disconnecting Means details on page 3. 2
with Automatic Transfer Switch Ambient Temperature Rating Operating Modes Surge Suppression Disconnecting Means Service Entrance Rating Standard: 5 C to 40 C / 41 F to 104 F The controller shall have the capability of running the pump motor in the following three (3) modes via a speed mode selector switch: Variable mode: Upon an automatic or manual start, the controller shall start the pump through the variable frequency drive (VFD) and instantly regulate the motor speed in reference to the discharge pressure Preset mode: Upon an automatic or manual start, the controller shall start the pump through the variable frequency drive (VFD) and run the pump motor at a pre-determined speed. This pre-determined speed shall be adjustable on the variable frequency drive (VFD) itself Bypass mode: Upon an automatic or manual start, the controller shall start the pump through the reduced voltage soft start bypass circuit. Surge arrestor rated to suppress surges above line voltage Isolating switch and circuit breaker assembly: - Door interlocked in the ON position - Isolating switch rated not less than 115% of motor full load current - Circuit breaker continuous rating not less than 115% of motor full load current - Overcurrent sensing non-thermal type, magnetic only - Instantaneous trip setting of not more than 20 times the motor full load current Common flange mounted operating handle Suitable as service entrance equipment Emergency Start Handle Flange mounted Pull and latch activation Integrated limit switch Across the line start (direct on line) Locked Rotor Protector Operate shunt trip to open circuit breaker Factory set at 600% of motor full load current Trip between 8 and 20 seconds Electrical Readings Pressure Readings Pressure and Event recorder Pressure Sensing Voltage phase to phase (normal power) Amperage of each phase when motor is running Continuous system pressure display Cut-in and Cut-out pressure settings Pressure readings with date stamp Event recording with date stamp The recorder will register and keep in memory pressure fluctuations over time that have occurred over the previous seven (7) days and events, alarms, general system information that have occurred over the previous fifteen (15) Information is retrievable through DB9 communication port accessible without having to open the controller door. Pressure transducers (2) for reading of discharge pressure Pressure sensing line connection (1/2 Female NPT) Rated for 0-600PSI working pressure Externally mounted with protective cover 3
Audible Alarm Visual Indications Alarm buzzer power available power available position position Technical Data with Automatic Transfer Switch Individual phase-to-phase voltage indication + Hz frequency (normal power) Individual phase current indication Pressure indication Elapsed run time Visual & Audible Alarms Visual only loss Motor run Phase reversal Phase unbalance Visual and Audible Overcurrent Undercurrent Fail to start Audible only Fault SSS (soft-start) Phase loss L1 Phase loss L2 Phase loss L3 Low System pressure Pressure transducer problem By-pass mode VFD Failure Undervoltage Overvoltage Locked rotor System trouble Remote Alarm Contacts DPDT-8A-250V.AC available Phase loss loss Overvoltage Undervoltage Phase unbalance Common motor trouble Overcurrent Undercurrent Fail to start Pressure transducer problem Phase reversal Bypass mode VFD Failure Motor run ***Can only be used if approved by the AHJ 4
Operator Interface Operation Technical Data with Automatic Transfer Switch Micro-processor based Accessible without opening main door Voltage and current indication Pressure settings and system pressure indication 15 day pressure and 15 day event Automatic Start Manual Start Stopping Timers Actuation Mode Start on pressure drop Start pushbutton Remote start from manual device Manual with Stop pushbutton Automatic after expiration of minimum run timer *** Field Adjustable & Visual Countdown Visual Indication Minimum run timer ***(off delay) Sequential start timer (on delay) Periodic test timer Pressure Automatic Non-automatic 5
with Automatic Transfer Switch Automatic Transfer Switch Surge Suppression Disconnecting Means Locked Rotor Protector Visual Indications Visual and Audible Alarms Surge arrestor rated to suppress surges above line voltage Isolating switch and circuit breaker assembly: - Door interlocked in the ON position - Isolating switch rated not less than 115% of motor full load current - Circuit breaker continuous rating not less than 115% of motor full load current - Overcurrent sensing non-thermal type, magnetic only - Instantaneous trip setting of not more than 20 times the motor full load current Common flange mounted operating handle Operate shunt trip to open circuit breaker Factory set at 600% of motor full load current Trip between 8 and 20 seconds (emergency) isolating switch in the OFF position (emergency) voltage phase to phase + frequency Transfer switch in normal or alternate position Isolating switch in OFF position Electrically operated and mechanically held in the normal or alternate position Provision for manual operation Remote Alarm Contacts SPDT-8A-250VAC Isolating switch in the OFF position Transfer switch in normal position Transfer switch in alternate (emergency) position Time Delays Momentary normal power outage override (factory set at 4 sec) (emergency) power available delay (factory set at 1 sec) Retransfer to normal (factory set at 5 min) Generator cooldown (factory set at 5 min) Voltage Sensing Transfer to alternate (normal power dropout) 85% of nominal Phase reversal transfer to alternate Retransfer to normal (normal power pickup) 90% of nominal Audible Alarm (AIS Open) Alarm buzzer Generator Start Connection SPDT-8A-250V.AC 6
with Automatic Transfer Switch A06B A07B A9 A10 A11 B11 B11B B19A B19B C1 C4 C7 C10 C14 C15 C18 C19 C21 C22 C23 C24 Cx Lockout Circuit from other VPx Interlock Circuit from other VPx Low zone pump control function Medium zone pump control function High zone pump control function Built in alarm panel (120V.AC supervisory power) providing indication for: Audible alarm & silence pushbutton for motor run, phase reversal, loss of phase. Pilot lights for loss of phase & supervisory power available Built in alarm panel same as B11 but 220-240VAC supervisory power High motor temperature c/w thermoster relay and alarm contacts (DPDT) High motor temperature c/w PT100 relay and alarm contacts (DPDT) Extra motor run alarm contact (DPDT) Periodic test alarm contact (DPDT) Low pump room temperature alarm contact (DPDT) Low water reservoir level alarm contact (DPDT) Pump on demand / automatic start alarm contact (DPDT) Pump fail to start alarm contact (DPDT) High water reservoir level c/w visual indication and alarm contact (DPDT) Emergency start alarm contact (DPDT) Deluge valve start alarm contact (DPDT) Remote automatic start alarm contact (DPDT) Remote manual start alarm contact (DPDT) High pump room temperature alarm contact (DPDT) Additional visual and alarm contact (Specify function) (DPDT) Note: Options chosen from this page are not electrically represented on the wiring schematics in this submittal package. D1 D1A D13 D14 D14A D14B D15 D24 D26 D26A D27 D27A D28 D37 E1 E2 E3 F2 F2A F2B F6 F10 Low suction pressure transducer for fresh water rated at 0-300PSI with visual indication and alarm contact Low suction pressure transducer for sea water rated at 0-300PSI with visual indication and alarm contact High withstand rating for (normal power section) 208V to 480V = 150kA 600V = 100kA Anti-condensation heater & thermostat Anti-condensation heater & humidistat Anti-condensation heater & thermostat & humidistat Tropicalization Audible Alarm Modbus with RTU frame format and RS485 connection Modbus TCP / IP provision Motor heater connection (external single phase power source and heater on/off contact) Motor heater connection (internal single phase power source and heater on/off contact) Customized drawing set Window kit for operator interface Permanent load shedding contacts Temporary pump motor start period load shedding contacts Temporary & permanent load shedding contacts Anti condensation heater & thermostat (alternate power section) Anti condensation heater & humidistat (alternate power section) Anti condensation heater & thermostat & humidistat (alternate power section) High withstand rating for (model GPU only) : 208V to 480V=150kA 600V=100kA IP55 assembly 7
with Automatic Transfer Switch L01 L02 L03 Other language and English (bilingual) French Spanish Additional Options: Note: Options chosen from this page are not electrically represented on the wiring schematics in this submittal package. 8
Operator Interface Technical Data with Automatic Transfer Switch Current / Time Pressure L1-L2 L2-L3 L3-L1 V. / Hz V. / Hz A. / Hr Available Position Phase Reversal Low System Pressure Altern. Available Position Isolating Switch in Off Position System Trouble Cut-out Cut-in Reset Test Print Paper Feed Trouble Legend : P : Pump Starting Failure O : Overcurrent Problem U : Undercurrent Problem T : Pressure Transducer Problem 9