Model GPW + GPU Full Service Reduced Voltage Wye-delta Closed Electric Fire Pump Controller with Automatic Power Transfer Switch
|
|
- Kristina Conley
- 6 years ago
- Views:
Transcription
1 Project: ustomer: Engineer: Pump Manufacturer: Technical Data Submittal Document Model GPW + GPU Full Service Reduced Wye-delta losed Electric Fire Pump ontroller with Automatic Transfer Switch ontents: Data Sheets Dimensional Data Wiring Schematics Field onnections Note: The drawings included in this package are for controllers covered under our standard offering. Actual AS BUILT drawings may differ from what is shown in this package. March 07
2 Technical Data Model GPW + GPU Electric Fire Pump ontroller with Automatic Transfer Switch From Automatic Transfer Switch* 3L R4 R5 S(LB) S M(LB) M(LB) 3L3 3L 3L R3A R3A M M S M M T3 T T T5 T4 T6 M S S Across-the line starting 3L Line current % of full load 0 Locked rotor current Wye delta starting Transition current losed transition Full load current S RES RES RES Percent of motor speed (%) Starting Method: Reduced Wye-delta closed Typical Applied at Start: 00% Inrush urrent: 33% of normal load current Starting Torque: 33% Motor Type: Wye-delta No. of ontactors: at 58%, at 33% of motor FL Min. ampacity of motor conductors: 6 at 5% x 58% of FL Standard, Listings, Approvals and ertifications Enclosure Built to NFPA 0 (latest edition) UL8 - Fire Pump ontrollers Underwriters Laboratory (UL) UL Automatic power transfer switches for fire pump controllers SA. No. 4 Industrial ontrol Equipment FM Global lass 3/33 New York ity Accepted for use in the ity of New York by the Department of Buildings Seismic ertification See page 7 for details Optional E Mark Various EN, IE & EE directives and standards Protection Rating Standard: NEMA (IP3) Optional NEMA NEMA 3 NEMA 3R NEMA 4 Accessories Bottom entry gland plate Lifting Lugs Keylock handle NEMA 4X-304 sst painted NEMA 4X-304 sst brushed finish NEMA 4X-36 sst painted NEMA 4X-36 sst brushed finish Paint Specifications Red RAL300 Powder coating Glossy textured finish IP54 IP55 IP65 IP66 *Please see Disconnecting Means details on page 3. March 07
3 Technical Data Model GPW + GPU Electric Fire Pump ontroller with Automatic Transfer Switch Shortcircuit Withstand Rating 00V to 08V 60Hz Normal Alternate 0V to 40V 60Hz Normal Alternate 380V to 46V 50 Hz / 60Hz Normal Alternate 440V to 480V 60Hz Normal Alternate 575V to V 60Hz Normal Alternate (kw) Standard 00kA Optional 50kA 5-50 (3.7-0) 5-00 (3.7-47) (3.7-0) ( ) n/a Standard 50kA 00 (47) 50 (84) (57-335) 500 (373) Optional 00kA n/a n/a n/a n/a ( ) Ambient Temperature Rating Standard: 5 to 40 / 4 F to 04 F Optional: 5 to 55 / 4 F to 3 F Surge Suppression Disconnecting Means Service Entrance Rating Surge arrestor rated to suppress surges above line voltage Isolating switch and circuit breaker assembly: - Door interlocked in the ON position - Isolating switch rated not less than 5% of motor full load current - ircuit breaker continuous rating not less than 5% of motor full load current - Overcurrent sensing non-thermal type, magnetic only - Instantaneous trip setting of not more than 0 times the motor full load current ommon flange mounted operating handle Suitable as service entrance equipment Emergency Start Handle Flange mounted Pull and latch activation Integrated limit switch Across the line start (direct on line) Locked Rotor Protector Operate shunt trip to open circuit breaker Factory set at % of motor full load current Trip between 8 and 0 seconds Electrical Readings Pressure Readings Pressure and Event recorder Pressure Sensing phase to phase (normal power) Amperage of each phase when motor is running ontinuous system pressure display ut-in and ut-out pressure settings Pressure readings with date stamp Event recording with date stamp Under regular maintained operation, events are stored in memory for the life of the controller. Data viewable on operator interface display screen Downloadable by USB port to external memory device Pressure transducer and run test solenoid valve assembly for fresh water application Pressure sensing line connection / Female NPT Drain connection 3/8 Rated for 0-500PSI working pressure (standard display at 0-300PSI) Externally mounted with protective cover March 07 3
4 Technical Data Model GPW + GPU Electric Fire Pump ontroller with Automatic Transfer Switch Audible Alarm Visual Indications 4 alarm bell - 85 db at 0ft. (3m) available Motor run Periodic test Manual start Deluge valve start Remote automatic start Remote manual start Emergency start Pump on demand/automatic start Low discharge pressure Pump room temperature (ºF or º) Lockout Visual & Audible Alarms Visual only Pump room alarm Pump on demand Motor trouble Loss Phase reversal Phase unbalance Phase loss L Phase loss L Phase loss L3 Low pump room temperature Weekly Test cut-in not reached ontrol voltage not healthy Overcurrent Undercurrent Undervoltage Overvoltage Invalid ut-in Service required Visual and Audible Locked rotor current Fail to start Low water level Low suction pressure Remote Alarm ontacts DPDT-8A-50V.A available Phase reversal Motor run ommon pump room alarm (field re-assignable)** Overvoltage Undervoltage Phase unbalance Low pump room temperature High Pump room temperature ommon motor trouble (field re-assignable)** Overcurrent Fail to start Undercurrent Ground fault Free (field programmable)** **Tornatech reserves the right to use any of these three alarm points for special specific application requirements. March 07 4
5 Technical Data Model GPW + GPU Electric Fire Pump ontroller with Automatic Transfer Switch ViZiTouch V Operator Interface ommunication Protocol apability Operation Embedded microcomputer with software PL logic 7.0 color touch screen (HMI technology) Upgradable software Multi-language Protocol: Modbus onnection type: Shielded female connector RJ45 Frame Format: TP/IP Addresses: See bulletin MOD-GPx Start on pressure drop Automatic Start Remote start signal from automatic device Start pushbutton Run test pushbutton Manual Start Deluge valve start Remote start from manual device Manual with Stop pushbutton Stopping Automatic after expiration of minimum run timer *** Timers Actuation Mode Field Adjustable & Visual ountdown Visual Indication Minimum run timer ***(off delay) Sequential start timer (on delay) Periodic test timer Pressure Non-pressure Automatic Non-automatic ***an only be used if approved by the AHJ March 07 5
6 Technical Data Model GPW + GPU Electric Fire Pump ontroller with Automatic Transfer Switch Automatic Transfer Switch Surge Suppression Disconnecting Means Locked Rotor Protector Visual Indications Visual Alarms Surge arrestor rated to suppress surges above line voltage Isolating switch and circuit breaker assembly: - Door interlocked in the ON position - Isolating switch rated not less than 5% of motor full load current - ircuit breaker continuous rating not less than 5% of motor full load current - Overcurrent sensing non-thermal type, magnetic only - Instantaneous trip setting of not more than 0 times the motor full load current ommon flange mounted operating handle Operate shunt trip to open circuit breaker Factory set at % of motor full load current Trip between 8 and 0 seconds Alternate (emergency) isolating switch in the OFF position Alternate (emergency) voltage phase to phase Transfer switch in normal position Transition timers Transfer switch trouble Alternate power phase reversal Alternate isolating switch open/tripped Alternate circuit breaker open/tripped Alternate side locked rotor current Transfer switch test pushbutton Bypass for re-transfer and generator shutdown Electrically operated and mechanically held in the normal or alternate position Provision for manual operation Remote Alarm ontacts SPDT-8A-50VA Isolating switch in the OFF position Transfer switch in normal position Transfer switch in alternate (emergency) position Time Delays Momentary normal power outage override (factory set at 3 sec - field adjustable to 3 sec) Alternate (emergency) power available delay (factory set at 3 sec - field adjustable to 3 sec) Transfer trouble delay (factory set at 0 sec - field adjustable to 60 sec) Retransfer to normal (factory set at 5 min - field adjustable to 0 min) Generator cooldown (factory set at 5 min - field adjustable to 0 min) Sensing Transfer to alternate (normal power dropout) 85% of nominal - field adjustable 0 to 00% Phase reversal transfer to alternate Retransfer to normal (normal power pickup) 90% of nominal - field adjustable 0 to 00% Audible Alarm (AIS Open) 4 alarm bell - 85 db at 0ft. (3m) Generator Start onnection SPDT-8A-50V.A March 07 6
7 Technical Data Model GPW + GPU Electric Fire Pump ontroller with Automatic Transfer Switch Seismic ertification Seismic ertification ompany Mounting details Seismic Information TRU ompliance, LL A Tobalski Watkins Affiliate TWEI Project No.: 504 Rigid base and wall mounting Building ode IB 05, B 06 Test riteria I- ES A56 Seismic Parameters SDS z/h I P A FLX-H A RIG-H A FLX-V A RIG-V ASE 7-0 hapter RRS for Nonstructural omponents Testing Spectral Response Acceleration (g) Frequency, f (Hz) Horiz. Level Vert. Level Notes: omponents are tested in accordance with I-ES A56, IB 05 & B 06. OSD Special Seismic ertification Preapproval (OSP) March 07 7
8 Technical Data Model GPW + GPU Electric Fire Pump ontroller with Automatic Transfer Switch A4 A8 Flow switch provision Foam pump application w/o pressure transducer and run test solenoid valve. 8 9 High water reservoir level c/w visual indication and alarm contact (DPDT) Emergency start alarm contact (DPDT) A9 Low zone pump control function 0 Manual start alarm contact (DPDT) A0 Middle zone pump control function Deluge valve start alarm contact (DPDT) A High zone pump control function Remote automatic start alarm contact (DPDT) A3 A6 B BB B9A B9B B Non-pressure actuated controller w/o pressure transducer and run test solenoid valve Lockout/interlock circuit from equipment installed inside the pump room Built in alarm panel (0V.A supervisory power) providing indication for: Audible alarm & silence pushbutton for motor run, phase reversal, loss of phase. Pilot lights for loss of phase & supervisory power available Built in alarm panel same as B but 0-40VA supervisory power High motor temperature c/w thermoster relay and alarm contacts (DPDT) High motor temperature c/w PT00 relay and alarm contacts (DPDT) Ground fault alarm detection c/w visual indication and alarm contact (DPDT) Extra motor run alarm contact (DPDT) Periodic test alarm contact (DPDT) Low discharge pressure alarm contact (DPDT) Low pump room temperature alarm contact (DPDT) Low water reservoir level alarm contact (DPDT) High electric motor temperature alarm contact (DPDT) High electric motor vibration c/w visual indication and alarm contact (DPDT) Pump on demand / automatic start alarm contact (DPDT) Pump fail to start alarm contact (DPDT) ontrol voltage healthy alarm contact (DPDT) Flow meter valve loop open c/w visual indication and alarm contact (DPDT) x D DA D5 D5D D0 D3 D4 D4A D4B D5 D8 D6 D7 D7A Remote manual start alarm contact (DPDT) High pump room temperature alarm contact (DPDT) Second set of standard alarm contacts (DPDT) (Typical for city of Los Angeles and Denver) Additional visual and alarm contact (Specify function) (DPDT) Low suction pressure transducer for fresh water rated at 0-300PSI with visual indication and alarm contact Low suction pressure transducer for sea water rated at 0-300PSI with visual indication and alarm contact Pressure transducer and run test solenoid valve for fresh water rated for 0-500PSI (for factory calibration purposes only) Pressure transducer and run test solenoid valve for sea water rated for 0-500PSI Omit mounting feet (when applicable) High withstand rating for (normal power section) 08V to 480V = 50kA V = 00kA Anti-condensation heater & thermostat Anti-condensation heater & humidistat Anti-condensation heater & thermostat & humidistat Tropicalization E Mark with factory certificate Modbus with RTU frame format and RS485 connection Motor heater connection (external single phase power source and heater on/off contact) Motor heater connection (internal single phase power source and heater on/off contact) Note: Options chosen from this page are not electrically represented on the wiring schematics in this submittal package. March 07 8
9 Technical Data Model GPW + GPU Electric Fire Pump ontroller with Automatic Transfer Switch D8 ustomized drawing set L0 Other language and English (bilingual) D34A D36 D36A E E E3 F FA FB F6 Field programmable I/O board - 5 Input / 5 output Redundant pressure transducer for fresh water rated for 0-500PSI Redundant pressure transducer for sea water rated for 0-500PSI Permanent load shedding contacts Temporary pump motor start period load shedding contacts Temporary & permanent load shedding contacts Anti condensation heater & thermostat (alternate power section) Anti condensation heater & humidistat (alternate power section) Anti condensation heater & thermostat & humidistat (alternate power section) High withstand rating for (model GPU only) : 08V to 480V=50kA V=00kA L0 L03 L04 L05 L06 L07 L08 L09 L0 L L L3 L4 L5 French Spanish German Italian Polish Romanian Hungarian Slovak roatian zech Portuguese Dutch Russian Turkish L6 Swedish L7 Bulgarian L8 Thai L9 Indonesian L0 Slovenian L Danish L Greek L3 Arabic L4 Hebrew L5 hinese Additional Options: Note: Options chosen from this page are not electrically represented on the wiring schematics in this submittal package. March 07 9
10 Technical Data Model GPW + GPU Electric Fire Pump ontroller with Automatic Transfer Switch ViZiTouch V Operator Interface PMS 95 PMS 36 Noir Home olor touch screen - Onscreen menu HOME page ALARM page ONFIGURATION page HISTORY page SERVIE page MANUAL page LANGUAGES page 3 - Screen protector 4 - LED (3 colors) 5 - START button 6 - STOP button 7 - TRANSFER SWITH TEST button 8 - RUN TEST button 9 - USB port March 07 0
11 Electric Fire Pump ontroller With Automatic Transfer Switch Dimensions Model:GPR/GPS/GPW +GPU Built to the latest edition of the NFPA 0 standard 53 3/8" [354] 5 3/8" [33] /" [] Ø7/8" [Ø3] X 7 3/4" [45] 4" [356] 50" [70] 48 /" [3] Ø3/8" [Ø0] X4 See Notes 55 /8" [400] 48" [0] 54" [37] 5 7/8" [38] 0 7/8" [530] 7 5/8" [70] 7 3/4" [450] " [5] Adjustable Feet Sensing Line onnection - / " F.NPT Drain - 3/8 " M.TUBE Ø/" [Ø3] X4 54" [37] 5" [3] 7" [78] 7" [78] " [5] 8" [04] 9 5/8" [43] Normal and Motor Leads Entrance 7" [78] Emergency Entrance " [305] / Table /4" [3] 3 /" [89] 4" [0] 4" [60] " [5] Min Max opyright Notes: Drawing for information only. Manufacturer reserves the right to modify this drawing without notice. ontact manufacturer for "As Built" drawing. - Standard NEMA: NEMA - Standard paint : textured red RAL All dimensions are in inches [millimeters]. - enter of ViZiTouch screen: 47-5/8" [08] from Bottom. - Bottom conduit entrance through removable gland plate recommended. - Use watertight conduit and connector only. - Protect equipment against drilling chips. - Door swing equal to door width. - Seismic mounting to be rigid wall and base only. NY Dpt of Building Approved REV. DESRIPTION DD/MM/YY 0. First issue 6//6 DL Drawing number GPX-DI7 /E Tornatech Inc. All right reserved. This drawing and the information contained or depicted herein are the sole property of Tornatech Inc. opies are communicated to the recipient in strict confidence and may not be retransmitted, published, reproduced, copied or used in any manner, including as the basis for the manufacture or sale of any products, without the express prior written consent of Tornatech Inc. Projection
12 Electric Fire Pump ontroller Reduced / Wye-Delta (losed Transition) With Automatic Transfer Switch Wiring schematic IS Remote Manual Start Lockout Remote Automatic Start Deluge Valve Water Reservoir Low SA L3 L L B ST 4 Motor Run Available Phase Reversal Pump Room Alarm Motor Trouble (Field Programmable) J* J* L3 L L N N N N N N IN IN IN3 IN4 IN5 IN6 IN7 See GPU Drawing N J5 J40 TB J4 TB N J37 TB3 N J39 TB4 N J4 TB5 N J55 TB6 N J4 J5 J6 J7 J54 J46 J43 J45 J44 J47 J0 J8 3L + AI4 - + AI3 - + AI - + AI - LS DOWN AB SV ST 4V in 4V out 4VA R4 UP Red White Red R5 LS- LS- SV- SV L3 3L 3L S 8 0 M(LB) R3A 4 8 S(LB) M(LB) R3A 3 9 See GPU Drawing Brown Blue X 4VA X XTR H H LS ** PT - + AB SV M M S S 4 3L 3L 3L3 3L 3L To J-J3-J4 T White T Model:GPW+GPU Built to the latest edition of the NFPA 0 standard 3L White T3 White To J76 M** S S M** RES RES RES VMB I/O IN8 J36 R4 J38 R5 N N R4- R4- R5- R5- LS** R5 R4 LS- R3A * Remove jumper to use this feature ** ontact closes when emergency start is in "ON" position opyright 07 EB J76 L J53 J4 J3 J GF L3 L L3 L L L3 3L 3L NY Dpt of Building Approved To T-T-T3 To 3L-3L-3L3 REV. DESRIPTION DD/MM/YY Removed (fail safe) text from Available relay 0/0/7 0 First issue 0//6 Drawing for information only. Manufacturer reserves the right to modify this drawing without notice. ontact manufacturer for "As Built" drawing. Drawing number GPW-WS60 /E Tornatech Inc. All right reserved. This drawing and the information contained or depicted herein are the sole property of Tornatech Inc. opies are communicated to the recipient in strict confidence and may not be retransmitted, published, reproduced, copied or used in any manner, including as the basis for the manufacture or sale of any products, without the express prior written consent of Tornatech Inc. DL Legend M-M ontactors S-S AB B R T EB IS J LS PT RES SA ST SV VMB XTR ontactors Alarm Bell ircuit Breaker ontrol Relay urrent Transformer Electric I/O Board Isolating Switch Jumper Limit Switch Pressure Transducer Primary Resistor Surge Arrester Shunt Trip Solenoid Valve ViZiTouch Main Board Transformer
13 Automatic Transfer Switch For Electric Fire Pump ontroller Wiring schematic Model: GPU Built to the latest edition of the NFPA 0 standard AIS Red Brown J46-0 J46-9 N Brown J46- LSA3 LSA4 AB J46-8 Yellow J46- Orange J50-4 N Brown J50- Yellow LSE LSE Red J50-5 J50-3 J50- E3 E E E3 E E 3L3 3L 3L Normal / Alternate to Fire Pump Section SA ST LSA Orange J46-6 Brown Red N J46-3 LSA Yellow J46-7 J46-5 J46-4 MA Normal from Fire Pump Section L3 L L E3 E E L3 L L Red Orange J49-4 N Brown J49- Yellow LSN LSN J49-5 J49-3 J49- Legend Shown in normal position AB AIS J LSA LSE ircuit Breaker Isolating Switch Jumper Limit Switch Limit Switch LSN MA SA ST TSB Limit Switch Linear Motor Actuator Surge Arrester Shunt Trip Transfer Switch I/O Board XTR Transformer J45 J38 J53 J47 J58 J7 AST 4V in 4V out 4VA 4VA A E3 XTR X H 4VA X H XTR3 X H 4VA X H N N N N A Pos. N Pos. AB GEN J39 J50 J49 J46 LSE LSE LSN LSN LSA3 LSA LSA LSA4 5 N 5 N 0 N N Red Orange Brown Yellow Red Orange Brown Yellow Red Brown Orange Orange Brown Red Yellow Yellow To LSE-LSE To LSN-LSN To LSA-LSA To LSA3-LSA4 J6 A E E J55 LN LN J4 J5 A E E J5 M+ M- White opyright 06 TSB J4 J3 J N3 N N L3 L L L L NY Dpt of Building Approved REV. DESRIPTION DD/MM/YY 0 First issue 0//6 Drawing number GPU-WS /E Tornatech Inc. All right reserved. This drawing and the information contained or depicted herein are the sole property of Tornatech Inc. opies are communicated to the recipient in strict confidence and may not be retransmitted, published, reproduced, copied or used in any manner, including as the basis for the manufacture or sale of any products, without the express prior written consent of Tornatech Inc. TSB J54 J0 J8 LE LE UP DOWN J3 See GPX Drawing Drawing for information only. Manufacturer reserves the right to modify this drawing without notice. ontact manufacturer for "As Built" drawing. DL
14 Electric Fire Pump ontroller Model: GPX Terminal Diagram and Sizing for Isolating Switch Terminals Bonding Ground 3 Phases Incoming Built to the latest edition of the NFPA 0 standard Notes: - For proper wire sizing, refer to NFPA70 and NE (USA) or E (anada) or local code. - ontroller suitable for service entrance in USA. 3 - For more accurate motor connections refer to motor manufacturer or motor nameplate. 4 - ontroller is phase sensitive. Incoming lines must be connected in AB sequence. L L L3 IS OPPER ONDUTORS for Isolating Switch (IS). Field Wiring According to (AWG or MM). Terminals L - L - L3 5 " (7 mm) 8 " (03 mm) x (3 to /0) x ( to /0) x (/0 to 50) x (4/0 to 50) 0 to 40 x (3 to /0) x ( to 50) x (/0 to 50) 380 to 46 x (3 to /0) x (3 to /0) x (3 to /0) " (305 mm) 6 " (406 mm) x (300 to 500) x (500) x (4/0 to 500) x (50 to 500) x (400 to ) 0 to 40 x (50 to 500) x (350 to 500) x (3/0 to 500) x (4/0 to 500) x (350 to 500) x (500 to ) 380 to 46 x (/0 to 50) x (50) x (300 to 500) x (3/0 to 50) x (4/0 to 500) x (400 to ) x (400 to 500) x (500 to ) x () x ( to 50) x (/0 to 50) x (4/0 to 50) x (350 to 500) x (3/0 to 50) x (4/0 to 500) x (350 to 500) x (400 to ) x (500 to ) x (3 to /0) x ( to 50) x (/0 to 50) x (50 to 500) x (350 to 500) x (3/0 to 50) x (4/0 to 500) x (50 to 500) x (350 to 500) 5 " (7 mm) 8 " (03 mm) " (305 mm) ALUMINUM ONDUTORS for Isolating Switch (IS). Field Wiring According to (AWG or MM). Terminals L - L - L3 5 " (7 mm) 8 " (03 mm) 0 " (54 mm) x (3 to /0) x ( to /0) 0 to 40 x (3 to /0) x ( to /0) x (/0) x (4/0 to 50) x ( to /0) x (/0 to 50) x (4/0 to 50) x (300) ** or x (50) 90 * x (50) 380 to 46 x ( to /0) x ( to /0) x (/0) x ( to /0) x ( to /0) x ( to /0) " (305 mm) 6 " (406 mm) 08 0 to to x (400 to 500) x (350 to 500) x (/0 to 50) x ( to /0) x(500) 90 or x(4/0 to 50) ** x (500) x (50) x (/0 to 50) x (50 to 500) x (350) ** N/A ** x (50) x (350 to 500) x (400 to 500) x (300) ** or x (50) 90 * x (4/0 to 50) x () x (500) x (4/0 to 50) x (500) x (350 to 500) x () 90 * x (50) x (500) x (4/0 to 50) 5 " (7 mm) 8 " (03 mm) " (305 mm) x (400 to 500) x (500) x (350 to 500) x (500 to ) x (400 to 500) x () 90 * x () 90 * x (500) x (400 to 500) x () x () 90 * x (500) * For standard enclosure, use 90 aluminium wire. onsult Factory for Use of onductors Rated Lower than 90. ** onsult Factory NY Dpt of Building Approved REV. DESRIPTION Drawing for information only. Manufacturer reserves the right to modify this drawing without notice. ontact manufacturer for "As Built" drawing. DD/MM/YY General Revision (added AL coverage) 0/07/7 Drawing number GPX-TD60 / /E 0 First issue 6/03/7 DL opyright 07 Tornatech Inc. All right reserved. This drawing and the information contained or depicted herein are the sole property of Tornatech Inc. opies are communicated to the recipient in strict confidence and may not be retransmitted, published, reproduced, copied or used in any manner, including as the basis for the manufacture or sale of any products, without the express prior written consent of Tornatech Inc.
15 Electric Fire Pump ontroller Model: GPX Terminal Diagram and Sizing For GPP,GPY & GPW Built to the latest edition of the NFPA 0 standard M Motor Terminals M M M Notes: - For proper wire sizing, refer to NFPA70 and NE (USA) or E (anada) or local code. - ontroller suitable for service entrance in USA. 3 - For more accurate motor connections refer to motor manufacturer or motor nameplate. 4 - ontroller is phase sensitive. Incoming lines must be connected in AB sequence. T7 T8 T9 T T T3 T6 T4 T5 T T T3 M Model : GPP M Models : GPW & GPY OPPER ONDUTORS for Motor onnection (M-M). Field Wiring According to (AWG or MM). Terminals T-T-T3-T4-T5-T6-T7-T8-T x (4 to 0) x (6 to ) x (4 to /0) x ( to 3/0) x ( to /0) 0 to 40 x (4 to 0) x (6 to ) x (4 to /0) x (3 to /0) x ( to /0) 380 to 46 x (4 to 0) x (4 to 0) x (4 to 0) x (6 to ) x (6 to ) x (4 to 0) x (4 to 0) x (4 to 0) x (0 to ) x (6 to ) x (6 to ) x (4 to 0) x (4 to 0) x (4 to 0) x (4 to 0) x (0 to ) x (/0 to 3/0) x (3/0) x (50 to 300) x (/0 to 300) x (3/0 to 350) 0 to 40 x (/0 to /0) x (3/0) x (4/0 to 300) x (300) x (/0 to 300) x (4/0 to 350) 380 to 46 x (4 to /0) x ( to /0) x (/0 to /0) x (/0 to 3/0) x (4/0 to 300) x (300) x (/0 to 300) x (3/0 to 300) x (4/0 to 350) x (4/0 to 350) x (4 to /0) x (3 to /0) x ( to /0) x (/0 to 3/0) x (/0 to 3/0) x (4/0 to 300) x (300) x (/0 to 300) x (/0 to 300) x (3/0 to 350) x (4/0 to 350) x (6 to ) x (4 to /0) x (3 to /0) x ( to 3/0) x (/0 to 3/0) x (/0 to 3/0) x (4/0 to 300) x (50 to 300) x (300) x (/0 to 300) x (/0 to 300) ALUMINUM ONDUTORS for ontactor (M-M). Field Wiring According to (AWG or MM). Terminals T-T-T3-T4-T5-T6-T7-T8-T x (6 to ) x (4 to ) x ( to /0) x (/0 to 3/0) x (/0) 0 to 40 x (6 to ) x ( to /0) x ( to /0) x (/0 to /0) 380 to 46 x (6 to ) x (4 to ) x (3 to /0) x (6 to ) x (4 to ) x (6 to ) x (3/0) onsult Factory x (300) 90 * x (3/0 to 300) x (50 to 350) 0 to 40 x (/0) 90 * onsult Factory x (300) x (300) 90 * x (4/0 to 300) x (300 to 350) 380 to 46 x ( to /0) x (/0 to /0) x (/0 to /0) x (3/0) 90 * x (300) x (300) 90 * x (4/0 to 300) x (50 to 300) x (300 to 350) x (300 to 350) x (3 to /0) x ( to /0) x (/0) 90 * x (/0 to 3/0) x (3/0) 90 * x (300) x (300) 90 * x (3/0 to 300) x (4/0 to 300) x (50 to 350) x (300 to 350) x (4 to ) x (3 to /0) x ( to /0) x (/0 to 3/0) x (3/0) x (3/0) 90 * x (300) x (300) 90 * onsult Factory x (3/0 to 300) x (4/0 to 300) opyright 07 * For standard enclosure, use 90 aluminium wire. onsult Factory for Use of onductors Rated Lower than 90. NY Dpt of Building Approved REV. DESRIPTION Drawing for information only. Manufacturer reserves the right to modify this drawing without notice. ontact manufacturer for "As Built" drawing. DD/MM/YY General Revision (added AL coverage) 0/07/7 First issue 6/03/7 Drawing number GPX-TD60 / /E 0 DL Tornatech Inc. All right reserved. This drawing and the information contained or depicted herein are the sole property of Tornatech Inc. opies are communicated to the recipient in strict confidence and may not be retransmitted, published, reproduced, copied or used in any manner, including as the basis for the manufacture or sale of any products, without the express prior written consent of Tornatech Inc.
16 Electric Fire Pump ontroller Model: GPX Terminal Diagram and Sizing ontrol Terminals (EB) Terminals Wire Size: 4 - AWG 0.5 Nm Built to the latest edition of the NFPA 0 standard Remote Alarm Terminals (EB) Terminals Wire Size: 4 - AWG 0.5 Nm Remote Manual Start lose to start pump IN J5 Motor Run loses to alarm loses to alarm N N J40 TB Lockout lose to block start IN J5 Available loses to alarm loses to alarm N N J4 TB Remote Automatic Start Open to start pump J* IN3 J5 Phase Reversal loses to alarm loses to alarm N N J37 TB3 Deluge Valve Open to start pump J* IN4 J5 Pump Room Alarm ** loses to alarm loses to alarm N N J39 TB4 Alarm Inputs (EB) Terminals Wire Size: 4 - AWG 0.5 Nm Motor Trouble ** loses to alarm loses to alarm N N J4 TB5 Water Reservoir Low lose to signal alarm IN5 J5 (Field Programmable ***) loses to alarm loses to alarm N N J55 TB6 Network onnection (VMB) Shielded Female onnector RJ45 Modbus TP/IP I/O * Remove jumper to use this feature ** Re-assignable *** Not available on GPS models opyright 07 NY Dpt of Building Approved REV. DESRIPTION DD/MM/YY General Revision (added AL coverage) 0/07/7 0 First issue 6/03/7 Drawing for information only. Manufacturer reserves the right to modify this drawing without notice. ontact manufacturer for "As Built" drawing. Drawing number GPX-TD603 /E Tornatech Inc. All right reserved. This drawing and the information contained or depicted herein are the sole property of Tornatech Inc. opies are communicated to the recipient in strict confidence and may not be retransmitted, published, reproduced, copied or used in any manner, including as the basis for the manufacture or sale of any products, without the express prior written consent of Tornatech Inc. DL
17 Automatic Transfer Switch For Electric Fire Pump ontroller Terminal Diagram and Sizing Terminals Model: GPU Built to the latest edition of the NFPA 0 standard Bonding Ground 3 Phases Incoming Notes: - ontroller is phase sensitive. Incoming lines must be connected in AB sequence. AL AL AL3 AIS OPPER ONDUTORS for Isolating Switch (AIS). Field Wiring According to (AWG or MM). Terminals AL - AL - AL3 5 " (7 mm) 8 " (03 mm) x (3 to /0) x ( to /0) x (/0 to 50) x (4/0 to 50) 0 to 40 x (3 to /0) x ( to 50) x (/0 to 50) 380 to 46 x (3 to /0) x (3 to /0) x (3 to /0) " (305 mm) 6 " (406 mm) x (300 to 500) x (500) x (4/0 to 500) x (50 to 500) x (400 to ) 0 to 40 x (50 to 500) x (350 to 500) x (3/0 to 500) x (4/0 to 500) x (350 to 500) x (500 to ) 380 to 46 x (/0 to 50) x (50) x (300 to 500) x (3/0 to 50) x (4/0 to 500) x (400 to ) x (400 to 500) x (500 to ) x () x ( to 50) x (/0 to 50) x (4/0 to 50) x (350 to 500) x (3/0 to 50) x (4/0 to 500) x (350 to 500) x (400 to ) x (500 to ) x (3 to /0) x ( to 50) x (/0 to 50) x (50 to 500) x (350 to 500) x (3/0 to 50) x (4/0 to 500) x (50 to 500) x (350 to 500) 5 " (7 mm) 8 " (03 mm) " (305 mm) ALUMINUM ONDUTORS for Isolating Switch (AIS). Field Wiring According to (AWG or MM). Terminals AL - AL - AL3 5 " (7 mm) 8 " (03 mm) 0 " (54 mm) x (3 to /0) x ( to /0) 0 to 40 x (3 to /0) x ( to /0) x (/0) x (4/0 to 50) x ( to /0) x (/0 to 50) x (4/0 to 50) x (300) ** or x (50) 90 * x (50) 380 to 46 x ( to /0) x ( to /0) x (/0) x ( to /0) x ( to /0) x ( to /0) " (305 mm) 6 " (406 mm) 08 0 to to x (400 to 500) x (350 to 500) x (/0 to 50) x ( to /0) x(500) 90 or x(4/0 to 50) ** x (500) x (50) x (/0 to 50) x (50 to 500) x (350) ** N/A ** x (50) x (350 to 500) x (400 to 500) x (300) ** or x (50) 90 * x (4/0 to 50) x () x (500) x (4/0 to 50) x (500) x (350 to 500) x () 90 * x (50) x (500) x (4/0 to 50) 5 " (7 mm) 8 " (03 mm) " (305 mm) x (400 to 500) x (500) x (350 to 500) x (500 to ) x (400 to 500) x () 90 * x () 90 * x (500) x (400 to 500) x () x () 90 * x (500) opyright 07 * For standard enclosure, use 90 aluminium wire. onsult Factory for Use of onductors Rated Lower than 90. ** onsult Factory NY Dpt of Building Approved REV. DESRIPTION DD/MM/YY General Revision (added AL coverage) 0/07/7 Added terminal ratings 0/05/7 0 First issue 0//6 Drawing for information only. Manufacturer reserves the right to modify this drawing without notice. ontact manufacturer for "As Built" drawing. Drawing number GPU-TD / /E Tornatech Inc. All right reserved. This drawing and the information contained or depicted herein are the sole property of Tornatech Inc. opies are communicated to the recipient in strict confidence and may not be retransmitted, published, reproduced, copied or used in any manner, including as the basis for the manufacture or sale of any products, without the express prior written consent of Tornatech Inc. DL
18 Automatic Transfer Switch For Electric Fire Pump ontroller Terminal Diagram and Sizing Model: GPU Built to the latest edition of the NFPA 0 standard Remote Alarm Terminals (TSB) Terminals Wire Size: 4 - AWG 0.5 Nm Tr. Sw. in alternate position Tr. Sw. in normal position AB in OFF or tripped Generator Set Opens when Tr. Sw. is in alternate position Opens when Tr. Sw. is in normal position loses when AB is in OFF or tripped ontrol Terminals (TSB) Terminals Wire Size: 4 - AWG 0.5 Nm Opens to start generator loses when Tr. Sw. in Alternate Position loses when Tr. Sw. in Normal Position Opens when AB is in OFF or Tripped loses to start generator N N N N A Pos. N Pos. AB GEN J39 J39 opyright 07 NY Dpt of Building Approved REV. DESRIPTION DD/MM/YY General Revision (added AL coverage) 0/07/7 Added terminal ratings 0/05/7 0 First issue 0//6 Drawing for information only. Manufacturer reserves the right to modify this drawing without notice. ontact manufacturer for "As Built" drawing. Drawing number GPU-TD / /E Tornatech Inc. All right reserved. This drawing and the information contained or depicted herein are the sole property of Tornatech Inc. opies are communicated to the recipient in strict confidence and may not be retransmitted, published, reproduced, copied or used in any manner, including as the basis for the manufacture or sale of any products, without the express prior written consent of Tornatech Inc. DL
Model GPP Full Service Reduced Voltage Part Winding Electric Fire Pump Controller
Project: ustomer: Engineer: Pump Manufacturer: Technical Data Submittal Documents Model GPP Full Service Reduced Part Winding Electric Fire Pump ontroller ontents: Data Sheets Dimensional Data Wiring Schematics
More informationModel GPW Full Service Reduced Voltage Wye-delta Closed Electric Fire Pump Controller
Project: ustomer: Engineer: Pump Manufacturer: Technical Data Submittal Documents Model GPW Full Service Reduced Wye-delta losed Electric Fire Pump ontroller ontents: Data Sheets Dimensional Data Wiring
More informationModel GPY + GPU Full Service Reduced Voltage Wye-delta Open Electric Fire Pump Controller with Automatic Power Transfer Switch
Project: ustomer: Engineer: Pump Manufacturer: Technical Data Submittal Document Model GPY + GPU Full Service Reduced Wye-delta Open Electric Fire Pump ontroller with Automatic Transfer Switch ontents:
More informationModel GPA Full Service Full Voltage Across the Line Start Electric Fire Pump Controller
Project: ustomer: Engineer: Pump Manufacturer: Technical Data Submittal Documents Model GPA Full Service Full Across the Line Start Electric Fire Pump ontroller ontents: Data Sheets Dimensional Data Wiring
More informationModel GPS + GPU Full Service Reduced Voltage Soft Start Soft Stop Electric Fire Pump Controller with Automatic Power Transfer Switch
Project: ustomer: Engineer: Pump Manufacturer: Technical Data Submittal Document Model GPS + GPU Full Service Reduced Soft Start Soft Stop Electric Fire Pump ontroller with Automatic Transfer Switch ontents:
More informationModel GPS Full Service Reduced Voltage Soft Start Soft Stop Electric Fire Pump Controller
Project: ustomer: Engineer: Pump Manufacturer: Technical Data Submittal Documents Model GPS Full Service Reduced Soft Start Soft Stop Electric Fire Pump ontroller ontents: Data Sheets Dimensional Data
More informationModel GPS + GPU Full Service Reduced Voltage Soft Start Soft Stop Electric Fire Pump Controller with Automatic Power Transfer Switch
Project: ustomer: Engineer: Pump Manufacturer: Technical Data Submittal Document Model GPS + GPU Full Service Reduced Soft Start Soft Stop Electric Fire Pump ontroller with Automatic Transfer Switch ontents:
More informationProject: Customer: Engineer: Pump Manufacturer: Model GPY + GPU. with Automatic Power Transfer Switch
Project: Customer: Engineer: Pump Manufacturer: Model GPY + GPU with Automatic Power Transfer Switch Contents: NOTE: The drawings included in this package are for controllers covered under our standard
More informationTechnical Data Submittal Document
Project: Customer: Engineer: Pump Manufacturer: Technical Data Submittal Document Model GPL + GLU Limted Service Full Voltage Across the Line Start Electric Fire Pump Controller Contents: Data Sheets Dimensional
More informationDrawing Submittal Package
Project: Customer: Engineer: Pump Manufacturer: Drawing Submittal Package Model GPL + GLU Limited Service Full Voltage Across the Line Start Electric Pump Controller with Automatic Power Transfer Switch
More informationDrawing Submittal Package
Project: Customer: Engineer: Pump Manufacturer: Drawing Submittal Package Model GPL + GLU Limited Service Full Voltage Across the Line Start Electric Pump Controller with Automatic Power Transfer Switch
More informationModel VPS + VPU Pressure Limiting (VFD) Electric Fire Pump Controller with Soft Start Bypass with Automatic Power Transfer Switch
Project: Customer: Engineer: Pump Manufacturer: Technical Data Submittal Document Model VPS + VPU Pressure Limiting (VFD) with Soft Start Bypass with Automatic Transfer Switch Contents: Data Sheets Dimensional
More informationModel VPS Pressure Limiting (VFD) Electric Fire Pump Controller with Soft Start Bypass
Project: Customer: Engineer: Pump Manufacturer: Submittal Document Model VPS Pressure Limiting (VFD) with Soft Start Bypass Contents: Data Sheets Dimensional Data Wiring Schematics Field Connections Note:
More informationModel GPD Diesel Engine Driven Fire Pump Controller
Project: ustomer: Engineer: Pump Manufacturer: Submittal Document Model GPD Diesel Engine Driven Fire Pump ontroller ontents: Data Sheets Dimensional Data Wiring Schematics Field onnections Note: The drawings
More informationTechnical Data Submittal Documents
Project: Customer: Engineer: Pump Manufacturer: Technical Data Submittal Documents Model PD - FM Diesel Engine Driven Fire Pump Controller Contents: Data Sheets Dimensional Data Wiring Schematics Field
More informationTechnical Data Submittal Documents
Project: Customer: Engineer: Pump Manufacturer: Technical Data Submittal Documents Model PD Diesel Engine Driven Fire Pump Controller Contents: Data Sheets Dimensional Data Wiring Schematics Field Connections
More informationTechnical Data Submittal Document
Project: ustomer: ngineer: Pump Manufacturer: Technical ata Submittal ocument Model JP2 cross the Line Start Jockey Pump ontroller ontents: ata Sheets imensional ata Wiring Schematics ield onnections Note:
More informationTechnical Data Submittal Document
Project: ustomer: ngineer: Pump Manufacturer: Technical ata Submittal ocument Model JP3 cross the Line Start Jockey Pump ontroller ontents: ata Sheets imensional ata Wiring Schematics ield onnections Note:
More informationOptions for Diesel Fire Pump Controllers
Options for Diesel Fire Pump Controllers 2015-2016 This document describes our standard options. Please consult factory for any additional options / features / modifications if required. Modifications
More informationLMR Electric Fire Pump Controllers Features
1-1 Printer / Recorder The industrial grade thermal printer is housed in a rugged steel enclosure within the controller. The on/off switch, feed and reset buttons are front accessible. A bi-color status
More informationFD30 Full Voltage - Across the Line July 2011
Must Be Installed Per Applicable Code and Manufacturers Recommendations Electric Fire Pump Controllers Features 1-1 FD30 Full Voltage - Across the Line July 2011 Power I/O Board Transformers Incoming line
More informationCustomer Connection Terminals Connection terminals for external customer connections, are located at the top of the Power I/O board.
Must Be Installed Per Applicable Code and Manufacturers Recommendations Electric Fire Pump Controllers Features 1-1 FD80 Reduced Voltage - Wye Delta (Star-Delta) Closed Transition Power I/O Board Transformers
More informationFT60 Reduced Voltage - Autotransformer
1-1 Product Description The Automatic Transfer Switch Option may be added to any FD type Fire Pump Controller whenever automatic transfer from normal to alternate power is required. The automatic Transfer
More informationLMR Electric Fire Pump Controllers Features
1-1 Printer / Recorder The industrial grade thermal printer is housed in a rugged steel enclosure within the controller. The on/off switch, feed and reset buttons are front accessible. A bi-color status
More informationFT40 Reduced Voltage - Part Winding. Electrically and Mechanically
LMR PLUS Electric Fire Pump Controllers with Transfer Switch Features FT40 Reduced Voltage - Part Winding 1-1 January 2012 Product Description The Automatic Transfer Switch Option may be added to any FD
More informationFT20 Full Voltage - Limited Service. Electrically and Mechanically
LMR PLUS Electric Fire Pump Controllers with Transfer Switch FT20 Full Voltage - Limited Service 1-1 May 2014 Product Description The Automatic Transfer Switch Option may be added to any FD type Fire Pump
More informationFDF Foam Pump Controllers Features
FDF100 Diesel Engine Foam Pump Controllers 1-1 Product Description The FDF Series of Foam Pump Controllers are designed for use with foam concentrate injection, foam transfer and water mist systems for
More informationFire Pump Controllers Medium Voltage Controllers
Fire Pump Controllers Medium Voltage Controllers Medium Voltage Controllers 1.5 Medium Voltage Fire Pump Controllers FDM Medium Voltage... Part Number / Options Selection Guide... Product Specifications
More informationTransfer Switch Features
1-1 Product Description The Automatic Transfer Option may be added to any FD type Fire Pump Controller whenever automatic transfer from normal to alternate power is required. The automatic Transfer and
More informationSoft Start Series MP700 Solid State, Reduced Voltage
Metron Fire Pump Controls and Accessories Soft Start Series MP700 Solid State, Reduced Voltage Metron Fire Pump Controllers conform to the latest requirements of National Fire Protection Association s
More informationFire Pump Controllers Foam (Additive) Controllers
Fire Pump Controllers Foam (Additive) Controllers Diesel Additive (Foam) Pump Controllers 1.4 Foam (Additive) Fire Pump Controllers FDF20 Foam (Additive) - Limited Service... FDF30 Foam (Additive) - Across-the-Line...
More informationWITH POWER TRANSFER SWITCH STANDARD SUBMITTAL PACKAGE
WITH POWER TRANSFER SWITCH STANDARD SUBMITTAL PACKAGE SBP1000-61 FTA1000 Full Voltage Starting Electric Fire Pump Controllers Product Description Description Firetrol FTA1000 Full Voltage Fire Pump Controllers
More informationDIESEL Engine Fire Pump Controllers Features. FD120 Diesel Engine Controllers
DIESEL Engine Fire Pump Controllers Features FD120 Diesel Engine Controllers 1-1 March 2013 Diesel Product Description The DIESEL Plus Fire Pump Controllers from Eaton Corporation are designed to control
More informationAcross-the-Line SERIES MP300 Combined Manual and Automatic
Across-the-Line SERIES MP300 Combined Manual and Automatic Metron Fire Pump Controllers conform to the latest requirements of National Fire Protection Association s Standard for Centrifugal Fire Pumps
More informationDIESEL Engine Fire Pump Controllers Features
1-1 Product Description The FD100 Diesel Engine Controller is designed to control and monitor 12 or 24 volt, diesel fire pump engines. All models are listed by UL and ULC, and approved by Factory Mutual
More informationTransfer Switch Features
1-1 Product Description The Automatic Transfer Switch Option may be added to any FD type Fire Pump Controller whenever automatic transfer from normal to alternate power is required. The automatic Transfer
More informationINSTALLATION AND MAINTENANCE MANUAL FOR ELECTRIC FIRE PUMP CONTROLLERS MODEL GPX
INSTALLATION AND MAINTENANCE MANUAL FOR ELECTRIC FIRE PUMP CONTROLLERS MODEL GPX 1 Table of Contents 1. Introduction 2. Installation 3. Main Features 4. Home 5. Alarms 6. Configuration 7. History 8. Service
More informationFDJ SERIES Jockey Pump Controllers Features
1-1 NEMA 2 Enclosures Enclosures have an oven baked powder paint finish and are supplied with NEMA 2 rating, unless otherwise ordered. Available options include: NEMA 1, 3R,, X, 12. Note: NEMA, X enclosures
More informationVariable Frequency Drive SERIES MP800 VFD
Metron Fire Pump Controls and Accessories Variable Frequency Drive SERIES MP800 VFD Metron Fire Pump Controllers conform to the latest requirements of National Fire Protection Association s Standard for
More informationSECTION AUTOMATIC TRANSFER SWITCHES
PART 1 - GENERAL 1.1 DESCRIPTION SECTION 26 36 23 SPEC WRITER NOTE: Use this section only for NCA projects. Delete between //--// if not applicable to project. Also, delete any other item or paragraph
More informationSECTION Fire Pumps
SECTION 21 30 00 Fire Pumps PART 1 GENERAL 1.1 WORK INCLUDED A. Furnish, install and test a motor-driven fire pump, jockey pump, and controllers in the space provided and as shown in the contract drawings.
More informationMASTER PRESSRE MAINTANENCE CONTROLLER. Models PMCE INSTRUCTION MANUAL. C 2018 Master Control Systems, Inc
MASTER PRESSRE MAINTANENCE CONTROLLER Models PMCE INSTRUCTION MANUAL C 2018 Master Control Systems, Inc TABLE OF CONTENTS Important Safety Information. Page 3 General Description and Installation.. Page
More informationPHYSICAL FACILITIES Consultant s Handbook Specifications Division 21 Fire Suppression 3000 Fire Pumps
Note: The A/E must choose all design values in brackets below before using in project specifications 1 General 1.1 Provide UL listed and FM approved fire pump complete with pump, driver, controller and
More informationMASTER JOCKEY PUMP CONTROLLER. Model JPCE INSTRUCTION MANUAL. C 2018 Master Control Systems, Inc
MASTER JOCKEY PUMP CONTROLLER Model JPCE INSTRUCTION MANUAL C 2018 Master Control Systems, Inc TABLE OF CONTENTS Important Safety Information. Page 3 General Description and Installation.. Page 4 Model
More informationDIESEL Engine Fire Pump Controllers Features
September 007 DIESEL Engine Fire Pump Controllers Features FD0 Diesel Engine Controllers 1-1 Printer / Recorder The industrial grade thermal printer is housed in a rugged steel enclosure within the controller.
More informationPART GENERAL 1.01 SECTION INCLUDES
Specification Number: 26 24 16.06 Product Name: Emergency Lighting Control NQ Circuit Panelboards: 240 Vac, 48 Vdc Maximum SECTION 26 24 16.06 Emergency Lighting Control NQ Circuit Panelboards: 240 Vac,
More informationMicroprocessor Based Wye-Delta Reduced Current Type Starting
Metron Fire Pump Controls and Accessories NEW Microprocessor Based Wye-Delta Reduced Current Type Starting PRODUCT PILOT SERIES MPT430TS (Open Transition) - MPT435TS (Closed Transition) ONLY 32 WIDE WITH
More informationEATON LMR Plus Electric Fire Pump Controllers
O & M Manual IM05805020K EATON LMR Plus Description Page 1. INTRODUCTION... 3 2. INSTALLATION AND ELECTRICAL CONNECTIONS... 3 3. HARDWARE DESCRIPTION... 4 4. OPERATION...7 5. PROGRAMMING... 8 6. HISTORY,
More informationVACUUM BREAKER MEDIUM VOLTAGE AUTOMATIC TRANSFER SWITCHES
Part One General 1.01 Scope A. It is the intent of this specification to provide a medium voltage automatic transfer system. B. All components, testing and services specified and required for a complete
More information1.1 REFERENCES.1 American National Standards Institute/National Fire Protection Association (ANSI/NFPA).1 ANSI/NFPA 20, Centrifugal Fire Pumps.
Issued 2006/08/01 Section 13920 Packaged Fire Pumps and Controllers Page 1 of 7 PART 1 GENERAL 1.1 REFERENCES.1 American National Standards Institute/National Fire Protection Association (ANSI/NFPA).1
More informationSECTION FIRE PUMPS 1.00 PART 1 & GENERAL Description of Work. A. Provide pumps for fire suppression Section Includes
SECTION 210200 Formatted 1.00 PART 1 & GENERAL 1.01 Description of Work A. Provide pumps for fire suppression. 1.02 Section Includes A. Single Stage, Double Suction, 8100 Series Horizontal Splitcase Fire
More informationCONTENTS AUTOMATIC TRANSFER SWITCHES
CONTENTS AUTOMATIC TRANSFER SWITCHES PART 1 GENERAL 1.1 Related Documents 1.2 Summary 1.3 References 1.4 Quality Assurance 1.5 Submittals 1.6 Delivery, Storage and Handling 1.7 Instructions And Training
More informationFire Pump Controller. For Electric Motor Driven Fire Pumps. Wye Delta Reduced Current Types
Fire Pump Controller For Electric Motor Driven Fire Pumps Wye Delta Reduced Current Types Series MP430 and Series MP435 Combined Manual and Automatic Metron Fire Pump Controllers conform to the latest
More informationPS914 Power Supply. 900-KL Keylock (optional) Page BB Battery Backup (optional) Page 3
F1! DANGER 44487056 These instructions cover the following parts: PS914 Power Supply Installation Instructions! DANGER: To avoid risk of electric shock, turn off A power before installing or servicing
More informationSECTION AUTOMATIC TRANSFER SWITCHES
PART 1 - GENERAL 1.1 DESCRIPTION SECTION 26 36 23 This section specifies the furnishing, complete installation, and connection of automatic transfer switches. 1.2 RELATED WORK A. Section 14 21 00, ELECTRIC
More informationPILOT SERIES MPT700TS
Metron Fire Pump Controls and Accessories Microprocessor Based Soft Start/Stop Solid State Reduced Voltage NEW PRODUCT PILOT SERIES MPT700TS ONLY 32 WIDE WITH ATS Available in Across-The-Line, Soft Start,
More informationSECTION P01 LIGHTING AND APPLIANCE PANELBOARDS - A-SERIES
PART 1 GENERAL A. The requirements of the Contract, Division 1, and Division 16 apply to work in this Section. 1.01 SECTION INCLUDES A. Lighting and appliance panelboards 1.02 RELATED SECTIONS A. 16475,
More informationCommercial and Light Industrial Fire Alarm Control Panel
FireSystem 2000 Commercial and Light Industrial Fire Alarm Control Panel Features Easily expandable. All new plug-in board design Two supervised audible circuits Lamp and system trouble circuit test Ground
More informationSECTION AUTOMATIC TRANSFER SWITCHES
SECTION 26 36 23 AUTOMATIC TRANSFER SWITCHES PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. General provisions of the Contract, including General and Supplementary Conditions and Division 01 Specification Sections,
More informationSECTION AUTOMATIC TRANSFER SWITCHES PART 1 - GENERAL
SECTION 16400 AUTOMATIC TRANSFER SWITCHES 1.01 RELATED DOCUMENTS PART 1 - GENERAL A. Drawings and general provisions of Contract, including General Conditions and Division 1 Specification sections, apply
More informationSA100L. General Description. Features. Temperature Limit Controller SA100L. Simple Mounting on DIN Rail. Over/Under Temperature Protection
SA00 SA00 SA00 SA00 Temperature Limit ontroller SA00L FM APPROVED SA00L General Description The SA00L is a FM approved high limit or low limit controllers. The SA00 is a socket mounting type temperature
More informationTotalPac 3 Deluge, Electric release Self-contained system
(Optional) DESRIPTION This TOTALPA 3 integrated fire protection system by FireFlex Systems Inc. consists of a deluge system trim totally preassembled, pre-wired and factory tested. All electrical and mechanical
More informationP.C. Simonton & Associates, Inc. Consulting Engineers. Paul C. Simonton
P.C. Simonton & Associates, Inc. Consulting Engineers 309 North Main Street 1050 Parkside Commons Post Office Box 649 Suite 101 Hinesville, Georgia 31310 Greensboro, Georgia 30642 Addendum No. One Date:
More informationNotes: Warrick Series 67 Intrinsically Safe Multi-Function Control Installation and Operation Bulletin
Notes: Warrick Series 67 Intrinsically Safe Multi-Function ontrol Installation and Operation Bulletin Form 670 Sheet P/N 100501-1 Rev. F Table of ontents Page 3 Page Page 5 Page 6 Page 7 Page 8 Page 9
More informationUltraLITE Model ELU Centralized Emergency Lighting Inverter 4.2 KW- 5 KW
12/23/16 Rev 9 UltraLITE Model ELU General Specification 4.2 KW to 5 KW UltraLITE Model ELU Centralized Emergency Lighting Inverter 4.2 KW- 5 KW 1.0 General General Specification This specification describes
More informationSCC Inc. Master Panel. Specifications. Document No. TS 2010 February 11, Product Description. Sample Specification
February 11, 2019 Master Panel Product Description The Master Panel shall provide lead/lag control and time based, automatic rotation of up to eight (8) boilers, when used in conjunction with LMV3 or LMV5
More informationSpecification/ Data Sheet
Specification/ Data Sheet TRITON RP Agent Release Control Panel FEATURES Agent Release Control Panel designed specifically for suppression release operation with: Four initiating device circuits (IDCs)
More informationRAYCHEM NGC-30 COMPONENTS
PANEL MOUNTED ELECTRONIC MULTI-CIRCUIT HEAT-TRACING CONTROL, MONITORING AND POWER DISTRIBUTION SYSTEM PRODUCT OVERVIEW CABLE DUCT Card Rack Modules TERMINAL STRIP PLINTH MAIN SWITCH 800 mm USER INTERFACE
More information7800 SERIES RM7888A Relay Module
7800 SERIES RM7888A Relay Module SPECIFICATION DATA FEATURES APPLICATION The Honeywell RM7888A Relay Module is a microprocessor-based integrated burner control for industrial process semi-automatically
More informationA. This Section includes transfer switches rated 600 V and less, including the following:
SECTION 16415 - TRANSFER SWITCHES PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 1 Specification
More informationInstallation Operation Maintenance
Installation Operation Maintenance RTAF SE/HE/XE/HSS/HSE Air-cooled Helical-rotary chillers 300-1600 kw Sintesis chillers are part of the Ingersoll Rand EcoWise portfolio of products that are designed
More informationPANEL MOUNTED ELECTRONIC MULTI-CIRCUIT HEAT-TRACING CONTROL, MONITORING AND POWER DISTRIBUTION SYSTEM mm. 100 mm
PANEL MOUNTED ELECTRONIC MULTI-CIRCUIT HEAT-TRACING CONTROL, MONITORING AND POWER DISTRIBUTION SYSTEM Card Rack Modules CABLE DUCT MAIN SWITCH 800 mm USER INTERFACE TERMINAL PRODUCT OVERVIEW The nvent
More informationRA889A Switching Relay
Switching Relay FEATURES PRODUT DATA High load switching capability. Troubleshooting LED. Push-to-test button. Replaceable transformer fuse. Long-life D relay drive control technology. Relay for use with
More informationGE Security. FP1200, FP2000 and KSA1200 series fire panels, repeaters and emulators Interconnection and wiring
GE Security FP1200, FP2000 and KSA1200 series fire panels, repeaters and emulators Interconnection and wiring Version v2-2 / September 2005 Aritech and Kilsen are GE Security brands. http://www.geindustrial.com/ge-interlogix/emea
More informationTECHNICAL DATA. multi-hazard. model vfr400. Release Control Panel 290a. January 16, 2014
January 16, 2014 Release Control Panel 290a 1. Description The Viking VFR400 is a microprocessor based releasing control panel for use on preaction, deluge, Surefire, Firecycle multicycle sprinkler systems,
More informationINSTALLATION/OPERATING INSTRUCTIONS SEQUENCING PANELS
R INSTALLATI/OPERATING INSTRUTIS SEQUENING PANELS SEQ-6, SEQ-6P and SEQ-12 Panels to Sequence up to 12 Individual Stages with Lead-Lag and Manual Override apabilities TENTS SEQ FUNTI HART... 2 DIP SWITH
More informationFireSystem 2000 Commercial and Light Industrial Fire Alarm Control Panel
PROTECTOWIRE FireSystems Features Easily expandable Two supervised audible circuits Lamp and system trouble circuit test Ground fault detection Initiating device circuit (IDC) alarm test Monitors up to
More informationDatasheet. Dry-pipe Vacuum Sprinkler System, Electric Release Self contained unit. Features. FIREFLEX VACTEC description
FIREFLEX VACTEC description This FIREFLEX VACTEC integrated fire protection system consists of a vacuum system trim totally pre-assembled, prewired and factory tested. All electrical and mechanical components
More information232xt Wiring Diagrams and Specifications SPECIFICATIONS: REV 1.01
232xt Wiring Diagrams and Specifications Voltage Selection Settings 1 2 3 Wire Xtreme Pad color to color to the wires on Programmer (Red to Red, ect.) ( / Yellow ) Position 12-24VA 15-24VD P5* Position
More information7EF/7HF/7EC/7ES Temperature Controllers
7EF/7HF/7E/7ES Temperature ontrollers Dual 4 Digit LED Display Universal Input (6 T/, RTD, mv, V, ma) Autotuning NEMA 4X 100 to 240 Vac Switching Power Supply Algorithms for Heat or Heat/ool ontrol 2 Independent
More informationMPT Electric Fire Pump Controller
Setup and Operating Instructions MPT Electric Fire Pump Controller This manual provides general information, installation, operation, maintenance, and system setup information for Metron MPT Electric Fire
More informationNGC-40 PANEL MOUNTED ADVANCED MODULAR HEAT-TRACING CONTROL SYSTEM HTC HTC3
NGC-40 PANEL MOUNTED ADVANCED MODULAR HEAT-TRACING CONTROL SYSTEM Local configuration and monitoring with Raychem Touch 1500 touch screen display PRODUCT OVERVIEW The Raychem NGC-40 is a multipoint electronic
More informationPressure Transducers Ultrahigh-Purity
www.swagelok.com Pressure Transducers Ultrahigh-Purity PTU Series Single-end, flow-through, and modular surface-mount models Positive pressure ranges to 5000 psi, 400 bar, and 40 MPa; compound pressure
More informationLatch key safety limit switches Technical data
Latch key safety Safety General Data Standards IE 6047-1, IE 6047-5-1, EN 6047-1, EN 6047-5-1, UL 508, and SA 22-2 No. 14 ertifications - Approvals UL and SA Air temperature near the device during operation
More informationDatasheet. Vacuum Double-interlock Preaction System, Electric Release Self contained unit. Features. FIREFLEX VACTEC description
FIREFLEX VACTEC description This FIREFLEX VACTEC integrated fire protection system consists of a vacuum system trim totally pre-assembled, prewired and factory tested. All electrical and mechanical components
More informationDESCRIPTION. 42 mm. 125 mm
RMM2-DI TRACE-HEATING REMOTE MONITORING MODULE FOR DIGITAL INPUTS DESCRIPTION 125 mm 60 mm The Remote Monitoring Module for Digital Inputs (RMM2-DI) provides the capability for the Raychem NGC controller
More informationMODEL GPT-130 SINGLE POINT HEAT TRACE CONTROL THERMOSTAT
TRACON MODEL GPT-130 SINGLE POINT HEAT TRACE CONTROL THERMOSTAT TABLE OF CONTENTS GPT 130 Overview... 2 Installation... 3 Power Source and Load Connection... 4 Temperature Sensor Installation... 5 Panel
More information7800 SERIES RM7840E,G,L,M; EC7840L Relay Module
7800 SERIES RM7840E,G,L,M; EC7840L Relay Module SPECIFICATION DATA Valve Proving features including: VPS test time When (Never, Before, After, Split or Both) FEATURES APPLICATION The Honeywell RM7840 is
More informationCONsOlIDATOR 4 & 8. MulTI- C h ANNEl CONTROllERs. ConsoliDator 4 Model PD940 ConsoliDator 4 Features. ConsoliDator 8 Features.
CONsOlIDATOR 4 & 8 MulTI- C h ANNEl CONTROllERs ConsoliDator 4 Model PD940 ConsoliDator 4 Features Four 4-20 Four 4-20 Outputs ConsoliDator 8 Features Eight 4-20 Two 4-20 Outputs Common Features Four Pulse
More informationPolyGard Single Point Controller SPC-X3-20XX for refrigerant gases and vapours
PolyGard Single Point Controller SPC-X3-20XX for refrigerant gases and vapours DESCRIPTION Gas measuring, monitoring and warning controller based on state-of-the-art micro-technology with integrated sensor
More information1.1 Remote Annunciator Controller (RAC) using the one ATC-300+ connected via RS-485 network.
Remote Annunciator Controller (RAC) Instruction Sheet for Automatic Transfer Switches (ATS) Revision: 01 IB01602085E 1.1 Remote Annunciator Controller (RAC) using the one ATC-300+ connected via RS-485
More informationWiring Diagrams. 9AB4-12 Air-Cooled Remote Condenser INDEX OPERATING SEQUENCE ACCESSORIES LEGEND AND NOTES FOR FIG. 1-6
9AB4-12 Air-ooled Remote ondenser Wiring Diagrams INDEX UNIT 9AB DRAWING TYPE DRAWING NUMBER FIG. NO. 4,6 Label Diagram 9AB6-10816 1 8,12 Label Diagram 9AB12-10816 2 AESSORIES OMPONENT PART NO. FIG. NO.
More informationUC700 EMERGENCY TRANSFER SYSTEM SPECIFIER S HANDBOOK. 40 Dale Street West Babylon, NY Ph: Fx:
UC700 EMERGENCY TRANSFER SYSTEM SPECIFIER S HANDBOOK 40 Dale Street West Babylon, NY 11704 Ph: 631-753-9550 Fx: 631-753-9560 www.unionconnector.com Emergency Automatic Transfer System STANDARD SPECIFICATIONS
More informationFireShield Plus. GE Security. EST Life Safety & Communications Conventional Small Building Solutions. Conventional Fire Alarm Control Panels
GE Security EST Life Safety & ommunications onventional Small Building Solutions Overview The FireShield Plus fire alarm family consists of 3, 5 and 10 zone conventional fire alarm s, an integrated DAT/Dialer,
More informationICM 275. Replacement Description
IM 275 Fan ontrol enter Replacement Description The IM275 Gas Furnace ontrol enter is a new generation control for the replacement market. The IM275 Gas Furnace ontrol enter is designed to function similarly
More informationGas Controller Module GC-06
Page 1 Oct. 2015/2 Measuring, warning and controlling module for toxic, combustible and refrigerant gases and vapours. The gas controller series GC-06 is designed in accordance with the standard EN 50545-1.
More informationFTA550 JOCKEY PUMP CONTROLLERS
FTA550 JOCKEY PUMP CONTROLLERS STANDARD SUBMITTAL PACKAGE SBP550E (A) FTA550E XG Jockey Pump Controllers Product Description Failed to start indication Main switch not in Auto alarm Pressure recording
More informationFTA550F JOCKEY PUMP CONTROLLERS STANDARD SUBMITTAL PACKAGE
FTA550F JOCKEY PUMP CONTROLLERS STANDARD SUBMITTAL PACKAGE SBP550F (A) FTA550F XG Jockey Pump Controllers Product Description Description Firetrol FTA550F XG Jockey Pump Controllers are intended for use
More informationConventional Fire Alarm Systems
Kidde atalog u Small Building Fire Alarm Solutions Technology that saves lives onventional Fire Alarm Systems FX-10RD, FX-10R, FX-5RD, FX-5R OA 6230 Overview Kidde brand conventional fire alarm systems
More information7800 SERIES RM7888A Relay Module
7800 SERIES RM7888A Relay Module FEATURES SPECIFICATION DATA APPLICATION The Honeywell RM7888A Relay Module is a microprocessor-based integrated burner control for industrial process semi-automatically
More information