1 Project: ustomer: Engineer: Pump Manufacturer: Technical Data Submittal Document Model GPY + GPU Full Service Reduced Wye-delta Open Electric Fire Pump ontroller with Automatic Transfer Switch ontents: Data Sheets Dimensional Data Wiring Schematics Field onnections Note: The drawings included in this package are for controllers covered under our standard offering. Actual AS BUILT drawings may differ from what is shown in this package. March 08

2 Technical Data Model GPY + GPU Electric Fire Pump ontroller with Automatic Transfer Switch From Automatic Transfer Switch* 3L R4 R5 R5 S M 3L3 3L 3L M M S M M S T3 T T T5 T4 T6 M 3L Line current % of full load Starting Method: Reduced Wye-delta open 0 Typical Applied at Start: 00% Inrush urrent: 33% of normal load current Starting Torque: 33% Motor Type: Wye-delta No. of ontactors: at 58%, at 33% of motor FL Min. ampacity of motor conductors: 6 at 5% x 58% of FL Across-the line starting Locked rotor current Wye delta starting Transition current Percent of motor speed (%) Open transition Full load current Standard, Listings, Approvals and ertifications Enclosure Built to NFPA 0 (latest edition) UL8 - Fire Pump ontrollers Underwriters Laboratory (UL) UL Automatic power transfer switches for fire pump controllers SA. No. 4 Industrial ontrol Equipment FM Global lass 3/33 New York ity Accepted for use in the ity of New York by the Department of Buildings Seismic ertification See page 7 for details Optional E Mark Various EN, IE & EE directives and standards Protection Rating Standard: NEMA (IP3) Optional NEMA NEMA 3 NEMA 3R NEMA 4 Accessories Bottom entry gland plate Lifting Lugs Keylock handle NEMA 4X-304 sst painted NEMA 4X-304 sst brushed finish NEMA 4X-36 sst painted NEMA 4X-36 sst brushed finish Paint Specifications Red RAL300 Powder coating Glossy textured finish IP54 IP55 IP65 IP66 *Please see Disconnecting Means details on page 3. March 08

3 Technical Data Model GPY + GPU Electric Fire Pump ontroller with Automatic Transfer Switch Shortcircuit Withstand Rating 00V to 08V 60Hz Normal Alternate 0V to 40V 60Hz Normal Alternate 380V to 46V 50 Hz / 60Hz Normal Alternate 440V to 480V 60Hz Normal Alternate 575V to V 60Hz Normal Alternate (kw) Standard 00kA Optional 50kA 5-50 (3.7-0) 5-00 (3.7-47) (3.7-0) ( ) n/a Standard 50kA 00 (47) 50 (84) (57-335) 500 (373) Optional 00kA n/a n/a n/a n/a ( ) Ambient Temperature Rating Surge Suppression Disconnecting Means Service Entrance Rating Standard: Optional: 5 to 40 / 4 F to 04 F 5 to 55 / 4 F to 3 F ontrollers built in Dubai, UAE (Tornatech FZE) are supplied standard with 55 rating. Surge arrestor rated to suppress surges above line voltage Isolating switch and circuit breaker assembly: - Door interlocked in the ON position - Isolating switch rated not less than 5% of motor full load current - ircuit breaker continuous rating not less than 5% of motor full load current - Overcurrent sensing non-thermal type, magnetic only - Instantaneous trip setting of not more than 0 times the motor full load current ommon flange mounted operating handle Suitable as service entrance equipment Emergency Start Handle Flange mounted Pull and latch activation Integrated limit switch Across the line start (direct on line) Locked Rotor Protector Operate shunt trip to open circuit breaker Factory set at % of motor full load current Trip between 8 and 0 seconds Electrical Readings Pressure Readings Pressure and Event recorder Pressure Sensing phase to phase (normal power) Amperage of each phase when motor is running ontinuous system pressure display ut-in and ut-out pressure settings Pressure readings with date stamp Event recording with date stamp Under regular maintained operation, events are stored in memory for the life of the controller. Data viewable on operator interface display screen Downloadable by USB port to external memory device Pressure transducer and run test solenoid valve assembly for fresh water application Pressure sensing line connection / Female NPT Drain connection 3/8 Rated for 0-500PSI working pressure (standard display at 0-300PSI) Externally mounted with protective cover March 08 3

4 Technical Data Model GPY + GPU Electric Fire Pump ontroller with Automatic Transfer Switch Audible Alarm Visual Indications 4 alarm bell - 85 db at 0ft. (3m) available Motor run Periodic test Manual start Deluge valve start Remote automatic start Remote manual start Emergency start Pump on demand/automatic start Low discharge pressure Pump room temperature (ºF or º) Lockout Visual & Audible Alarms Visual only Pump room alarm Pump on demand Motor trouble Loss Phase reversal Phase unbalance Phase loss L Phase loss L Phase loss L3 Low pump room temperature Weekly Test cut-in not reached ontrol voltage not healthy Overcurrent Undercurrent Undervoltage Overvoltage Invalid ut-in Service required Visual and Audible Locked rotor current Fail to start Low water level Low suction pressure Remote Alarm ontacts DPDT-8A-50V.A available Phase reversal Motor run ommon pump room alarm (field re-assignable)** Overvoltage Undervoltage Phase unbalance Low pump room temperature High Pump room temperature ommon motor trouble (field re-assignable)** Overcurrent Fail to start Undercurrent Ground fault Free (field programmable)** **Tornatech reserves the right to use any of these three alarm points for special specific application requirements. March 08 4

5 Technical Data Model GPY + GPU Electric Fire Pump ontroller with Automatic Transfer Switch ViZiTouch V Operator Interface ommunication Protocol apability Operation Embedded microcomputer with software PL logic 7.0 color touch screen (HMI technology) Upgradable software Multi-language Protocol: Modbus onnection type: Shielded female connector RJ45 Frame Format: TP/IP Addresses: See bulletin MOD-GPx Start on pressure drop Automatic Start Remote start signal from automatic device Start pushbutton Run test pushbutton Manual Start Deluge valve start Remote start from manual device Manual with Stop pushbutton Stopping Automatic after expiration of minimum run timer *** Timers Actuation Mode Field Adjustable & Visual ountdown Visual Indication Minimum run timer ***(off delay) Sequential start timer (on delay) Periodic test timer Pressure Non-pressure Automatic Non-automatic ***an only be used if approved by the AHJ March 08 5

6 Technical Data Model GPY + GPU Electric Fire Pump ontroller with Automatic Transfer Switch Automatic Transfer Switch Surge Suppression Disconnecting Means Locked Rotor Protector Visual Indications Visual Alarms Surge arrestor rated to suppress surges above line voltage Isolating switch and circuit breaker assembly: - Door interlocked in the ON position - Isolating switch rated not less than 5% of motor full load current - ircuit breaker continuous rating not less than 5% of motor full load current - Overcurrent sensing non-thermal type, magnetic only - Instantaneous trip setting of not more than 0 times the motor full load current ommon flange mounted operating handle Operate shunt trip to open circuit breaker Factory set at % of motor full load current Trip between 8 and 0 seconds Alternate (emergency) isolating switch in the OFF position Alternate (emergency) voltage phase to phase Transfer switch in normal position Transition timers Transfer switch trouble Alternate power phase reversal Alternate isolating switch open/tripped Alternate circuit breaker open/tripped Alternate side locked rotor current Transfer switch test pushbutton Bypass for re-transfer and generator shutdown Electrically operated and mechanically held in the normal or alternate position Provision for manual operation Remote Alarm ontacts SPDT-8A-50VA Isolating switch in the OFF position Transfer switch in normal position Transfer switch in alternate (emergency) position Time Delays Momentary normal power outage override (factory set at 3 sec - field adjustable to 3 sec) Alternate (emergency) power available delay (factory set at 3 sec - field adjustable to 3 sec) Transfer trouble delay (factory set at 0 sec - field adjustable to 60 sec) Retransfer to normal (factory set at 5 min - field adjustable to 0 min) Generator cooldown (factory set at 5 min - field adjustable to 0 min) Sensing Transfer to alternate (normal power dropout) 85% of nominal - field adjustable 0 to 00% Phase reversal transfer to alternate Retransfer to normal (normal power pickup) 90% of nominal - field adjustable 0 to 00% Audible Alarm (AIS Open) 4 alarm bell - 85 db at 0ft. (3m) Generator Start onnection SPDT-8A-50V.A March 08 6

7 Technical Data Model GPY + GPU Electric Fire Pump ontroller with Automatic Transfer Switch Seismic ertification Seismic ertification ompany Mounting details Seismic Information TRU ompliance, LL A Tobalski Watkins Affiliate TWEI Project No.: 504 Rigid base and wall mounting Building ode IB 05, B 06 Test riteria I- ES A56 Seismic Parameters SDS z/h I P A FLX-H A RIG-H A FLX-V A RIG-V ASE 7-0 hapter RRS for Nonstructural omponents Testing Spectral Response Acceleration (g) Frequency, f (Hz) Horiz. Level Vert. Level Notes: omponents are tested in accordance with I-ES A56, IB 05 & B 06. OSD Special Seismic ertification Preapproval (OSP) March 08 7

8 Technical Data Model GPY + GPU Electric Fire Pump ontroller with Automatic Transfer Switch A4 A8 Flow switch provision Foam pump application w/o pressure transducer and run test solenoid valve. 8 9 High water reservoir level c/w visual indication and alarm contact (DPDT) Emergency start alarm contact (DPDT) A9 Low zone pump control function 0 Manual start alarm contact (DPDT) A0 Middle zone pump control function Deluge valve start alarm contact (DPDT) A High zone pump control function Remote automatic start alarm contact (DPDT) A3 A6 B BB B9A B9B B Non-pressure actuated controller w/o pressure transducer and run test solenoid valve Lockout/interlock circuit from equipment installed inside the pump room Built in alarm panel (0V.A supervisory power) providing indication for: Audible alarm & silence pushbutton for motor run, phase reversal, loss of phase. Pilot lights for loss of phase & supervisory power available Built in alarm panel same as B but 0-40VA supervisory power High motor temperature c/w thermoster relay and alarm contacts (DPDT) High motor temperature c/w PT00 relay and alarm contacts (DPDT) Ground fault alarm detection c/w visual indication and alarm contact (DPDT) Extra motor run alarm contact (DPDT) Periodic test alarm contact (DPDT) Low discharge pressure alarm contact (DPDT) Low pump room temperature alarm contact (DPDT) Low water reservoir level alarm contact (DPDT) High electric motor temperature alarm contact (DPDT) High electric motor vibration c/w visual indication and alarm contact (DPDT) Pump on demand / automatic start alarm contact (DPDT) Pump fail to start alarm contact (DPDT) ontrol voltage healthy alarm contact (DPDT) Flow meter valve loop open c/w visual indication and alarm contact (DPDT) x D DA D5 D5D D0 D3 D4 D4A D4B D5 D8 D6 D7 D7A Remote manual start alarm contact (DPDT) High pump room temperature alarm contact (DPDT) Second set of standard alarm contacts (DPDT) (Typical for city of Los Angeles and Denver) Additional visual and alarm contact (Specify function) (DPDT) Low suction pressure transducer for fresh water rated at 0-300PSI with visual indication and alarm contact Low suction pressure transducer for sea water rated at 0-300PSI with visual indication and alarm contact Pressure transducer and run test solenoid valve for fresh water rated for 0-500PSI (for factory calibration purposes only) Pressure transducer and run test solenoid valve for sea water rated for 0-500PSI Omit mounting feet (when applicable) High withstand rating for (normal power section) 08V to 480V = 50kA V = 00kA Anti-condensation heater & thermostat Anti-condensation heater & humidistat Anti-condensation heater & thermostat & humidistat Tropicalization E Mark with factory certificate Modbus with RTU frame format and RS485 connection Motor heater connection (external single phase power source and heater on/off contact) Motor heater connection (internal single phase power source and heater on/off contact) Note: Options chosen from this page are not electrically represented on the wiring schematics in this submittal package. March 08 8

9 Technical Data Model GPY + GPU Electric Fire Pump ontroller with Automatic Transfer Switch D8 ustomized drawing set L0 Other language and English (bilingual) D34A D36 D36A E E E3 F FA FB F6 Field programmable I/O board - 5 Input / 5 output Redundant pressure transducer for fresh water rated for 0-500PSI Redundant pressure transducer for sea water rated for 0-500PSI Permanent load shedding contacts Temporary pump motor start period load shedding contacts Temporary & permanent load shedding contacts Anti condensation heater & thermostat (alternate power section) Anti condensation heater & humidistat (alternate power section) Anti condensation heater & thermostat & humidistat (alternate power section) High withstand rating for (model GPU only) : 08V to 480V=50kA V=00kA L0 L03 L04 L05 L06 L07 L08 L09 L0 L L L3 L4 L5 French Spanish German Italian Polish Romanian Hungarian Slovak roatian zech Portuguese Dutch Russian Turkish L6 Swedish L7 Bulgarian L8 Thai L9 Indonesian L0 Slovenian L Danish L Greek L3 Arabic L4 Hebrew L5 hinese Additional Options: Note: Options chosen from this page are not electrically represented on the wiring schematics in this submittal package. March 08 9

10 Technical Data Model GPY + GPU Electric Fire Pump ontroller with Automatic Transfer Switch ViZiTouch V Operator Interface PMS 95 PMS 36 Noir Home olor touch screen - Onscreen menu HOME page ALARM page ONFIGURATION page HISTORY page SERVIE page MANUAL page LANGUAGES page 3 - Screen protector 4 - LED (3 colors) 5 - START button 6 - STOP button 7 - TRANSFER SWITH TEST button 8 - RUN TEST button 9 - USB port March 08 0

11 Electric Fire Pump ontroller With Automatic Transfer Switch Dimensions Model:GPA/GPP/GPY +GPU Built to the latest edition of the NFPA 0 standard 39 /4" [998] 38 3/8" [976] /" [] 5 7/8" [403] 36" [94] Ø7/8" [Ø3] X " [305] 34 /" [876] Ø3/8" [Ø0] X4 36" [94] See Notes 37 /4" [946] 38 /4" [97] 30" [763] 7 3/4" [703] " [560] 7" [78] 5" [7] 5" [7] " [305] Sensing Line onnection - / " F.NPT Drain - 3/8 " M.TUBE 7 5/8" [448] 3 5/8" [346] Ø/" [Ø3] X3 8 /8" [08] 7" [78] Normal and Motor Leads Entrance Emergency Entrance 6" [5] / Table /4" [3] 7" [78] 6" [5] 9" [483] /" [63] " [5] 3" [76] 4" [0] Min Max opyright Notes: Drawing for information only. Manufacturer reserves the right to modify this drawing without notice. ontact manufacturer for "As Built" drawing. - Standard NEMA: NEMA - Standard paint : textured red RAL All dimensions are in inches [millimeters]. - enter of ViZiTouch screen: 9-5/8" [75] from bottom (no feet). - Bottom conduit entrance through removable gland plate recommended. - Use watertight conduit and connector only. - Protect equipment against drilling chips. - Door swing equal to door width. - Seismic mounting to be rigid wall and base only. NY Dpt of Building Approved REV. DESRIPTION DD/MM/YY. Valve hange //7 0. First issue 6//6 DL Drawing number GPX-DI6 /E Tornatech Inc. All right reserved. This drawing and the information contained or depicted herein are the sole property of Tornatech Inc. opies are communicated to the recipient in strict confidence and may not be retransmitted, published, reproduced, copied or used in any manner, including as the basis for the manufacture or sale of any products, without the express prior written consent of Tornatech Inc. Projection

12 Electric Fire Pump ontroller Reduced / Wye-Delta (Open Transition) With Automatic Transfer Switch Wiring schematic IS SA L3 L L B ST 4 L3 L L See GPU Drawing 3L R4 R5 R5 7 S 8 0 M 9 3L3 3L 3L M M S Model: GPY+GPU Built to the latest edition of the NFPA 0 standard T3 M** T T White White White 3L L L To J-J3-J4 To J76 M** S Motor Run N N J40 TB J4 + AI4-3L Available N N J4 TB J5 + AI3 - Phase Reversal Pump Room Alarm Motor Trouble N N N N N N J37 TB3 J39 TB4 J4 TB5 J6 J7 J54 + AI - + AI - LS Red White LS- LS- LS ** PT (Field Programmable) Remote Manual Start Lockout N IN IN N J55 TB6 J46 J43 J0 J8 DOWN AB SV UP Red SV- SV- See GPU Drawing Brown Blue - + AB SV VMB Remote Automatic Start Deluge Valve J* J* IN3 IN4 J5 J45 ST 4 I/O Water Reservoir Low IN5 IN6 IN7 J44 J47 4V in 4V out 4VA 3 X 4VA X XTR H H 3L 3L IN8 J36 R4 N R4- R4- R4 J38 R5 N R5- R5- R5 * Remove jumper to use this feature ** ontact closes when emergency start is in "ON" position opyright 07 EB J76 L J53 J4 J3 J GF L3 L L3 L L L3 3L 3L NY Dpt of Building Approved To T-T-T3 To 3L-3L-3L3 REV. DESRIPTION DD/MM/YY Removed (fail safe) text from Available relay 0/0/7 0 First issue 0//6 Drawing for information only. Manufacturer reserves the right to modify this drawing without notice. ontact manufacturer for "As Built" drawing. Drawing number GPY-WS60 /E Tornatech Inc. All right reserved. This drawing and the information contained or depicted herein are the sole property of Tornatech Inc. opies are communicated to the recipient in strict confidence and may not be retransmitted, published, reproduced, copied or used in any manner, including as the basis for the manufacture or sale of any products, without the express prior written consent of Tornatech Inc. DL Legend M-M ontactors S AB B R T EB IS J LS PT SA ST SV VMB XTR ontactor Alarm Bell ircuit Breaker ontrol Relay urrent Transformer Electric I/O Board Isolating Switch Jumper Limit Switch Pressure Transducer Surge Arrester Shunt Trip Solenoid Valve ViZiTouch Main Board Transformer

13 Automatic Transfer Switch For Electric Fire Pump ontroller Wiring schematic Model: GPU Built to the latest edition of the NFPA 0 standard R AIS J46- LSA3 Red Brown J46-0 J46-9 N Orange LSA4 AB Yellow J46-8 J R trl Off II I O ONTROL Orange J46-6 Brown Red N J46-3 LSA LSA SA Yellow E3 E E J46-7 J46-5 J46-4 ST E3 E E R XTR4 H X 40VA H X Tornatech Tr. Sw Position II MA 3L3 3L 3L Normal / Alternate to Fire Pump Section Normal from Fire Pump Section opyright 08 TSB J45 J38 J53 J47 J58 J7 J6 J5 J4 J3 J AST 4V in 4V out 4VA 4VA A3 A A N3 N N E3 E E E E L3 L L L L X 4VA X XTR X 4VA X H H L3 L L XTR3 H H E3 E E NY Dpt of Building Approved L3 L L REV. R DESRIPTION DD/MM/YY 0 First issue /0/8 Drawing number GPU-WS60 /E Tornatech Inc. All right reserved. This drawing and the information contained or depicted herein are the sole property of Tornatech Inc. opies are communicated to the recipient in strict confidence and may not be retransmitted, published, reproduced, copied or used in any manner, including as the basis for the manufacture or sale of any products, without the express prior written consent of Tornatech Inc. N N N N TSB A Pos. N Pos. AB GEN Orange Yellow White J39 Position I N Position II N J50 J49 J46 J55 J5 J54 LSE LSE LSN LSN LSA3 LSA LSA LSA4 J0 J8 Position I Shown in normal position Brown Red N N N N LN LN M+ M- LE LE UP DOWN Yellow Brown White White Red Orange Red Red Brown Orange Orange Brown Red Yellow Yellow J4 White OUTPUTS ATyS avail. II I O J3 63A 64A 4 White Red To LSA-LSA R See GPX Drawing A+ A- AB AIS R J LSA LSE LSN MA SA ST TM TSB XTR R DL To LSA3-LSA4 Drawing for information only. Manufacturer reserves the right to modify this drawing without notice. ontact manufacturer for "As Built" drawing. A- A+ Legend ircuit Breaker Isolating Switch ontactor Jumper Limit Switch Limit Switch Limit Switch Linear Motor Actuator Surge Arrester Shunt Trip Timer Transfer Switch I/O Board Transformer

14 Electric Fire Pump ontroller Model: GPX Terminal Diagram and Sizing for Isolating Switch Terminals Bonding Ground 3 Phases Incoming Built to the latest edition of the NFPA 0 standard Notes: - For proper wire sizing, refer to NFPA70 and NE (USA) or E (anada) or local code. - ontroller suitable for service entrance in USA. 3 - For more accurate motor connections refer to motor manufacturer or motor nameplate. 4 - ontroller is phase sensitive. Incoming lines must be connected in AB sequence. L L L3 IS OPPER ONDUTORS for Isolating Switch (IS). Field Wiring According to (AWG or MM). Terminals L - L - L3 5 " (7 mm) 8 " (03 mm) x (3 to /0) x ( to /0) x (/0 to 50) x (3/0 to 50) x (4/0 to 50) 0 to 40 x (3 to /0) x ( to 50) x (/0 to 50) x (3/0 to 50) 380 to 46 x (3 to /0) x (3 to /0) x (3 to /0) " (305 mm) 6 " (406 mm) x (300 to 500) x (500) x (4/0 to 500) x (50 to 500) x (400 to ) 0 to 40 x (50 to 500) x (350 to 500) x (3/0 to 500) x (4/0 to 500) x (350 to 500) x (500 to ) 380 to 46 x (/0 to 50) x (3/0 to 50) x (50) x (300 to 500) x (3/0 to 50) x (4/0 to 500) x (400 to ) x (400 to 500) x (500 to ) x () x ( to 50) x (/0 to 50) x (3/0 to 50) x (4/0 to 50) x (350 to 500) x (3/0 to 50) x (4/0 to 500) x (350 to 500) x (400 to ) x (500 to ) x (3 to /0) x ( to 50) x (/0 to 50) x (3/0 to 50) x (50 to 500) x (350 to 500) x (3/0 to 50) x (4/0 to 500) x (50 to 500) x (350 to 500) 5 " (7 mm) 8 " (03 mm) " (305 mm) ALUMINUM ONDUTORS for Isolating Switch (IS). Field Wiring According to (AWG or MM). Terminals L - L - L3 5 " (7 mm) 8 " (03 mm) 0 " (54 mm) x (3 to /0) x ( to /0) 0 to 40 x (3 to /0) x ( to /0) x (/0) x (3/0 to 50) x (4/0 to 50) x ( to /0) x (/0 to 50) x (4/0 to 50) x (300) ** or x (50) 90 * x (50) 380 to 46 x ( to /0) x ( to /0) x (/0) x ( to /0) x ( to /0) x ( to /0) " (305 mm) 6 " (406 mm) 08 0 to to x (400 to 500) x (350 to 500) x (3/0 to 50) x (/0 to 50) x ( to /0) x(500) 90 or x(4/0 to 50) ** x (500) x (50) x (3/0 to 50) x (/0 to 50) x (50 to 500) x (350) ** N/A ** x (50) x (3/0 to 50) x (350 to 500) x (400 to 500) x (300) ** or x (50) 90 * x (4/0 to 50) x () x (500) x (4/0 to 50) x (500) x (350 to 500) x () 90 * x (50) x (500) x (4/0 to 50) 5 " (7 mm) 8 " (03 mm) " (305 mm) x (400 to 500) x (500) x (350 to 500) x (500 to ) x (400 to 500) x () 90 * x () 90 * x (500) x (400 to 500) x () x () 90 * x (500) * For standard enclosure, use 90 aluminium wire. onsult Factory for Use of onductors Rated Lower than 90. ** onsult Factory NY Dpt of Building Approved REV. DESRIPTION Drawing for information only. Manufacturer reserves the right to modify this drawing without notice. ontact manufacturer for "As Built" drawing. DD/MM/YY General Revision (added AL coverage) 0/07/7 Drawing number GPX-TD60 / /E 0 First issue 6/03/7 DL opyright 07 Tornatech Inc. All right reserved. This drawing and the information contained or depicted herein are the sole property of Tornatech Inc. opies are communicated to the recipient in strict confidence and may not be retransmitted, published, reproduced, copied or used in any manner, including as the basis for the manufacture or sale of any products, without the express prior written consent of Tornatech Inc.

15 Electric Fire Pump ontroller Model: GPX Terminal Diagram and Sizing For GPP,GPY & GPW Built to the latest edition of the NFPA 0 standard M Motor Terminals M M M Notes: - For proper wire sizing, refer to NFPA70 and NE (USA) or E (anada) or local code. - ontroller suitable for service entrance in USA. 3 - For more accurate motor connections refer to motor manufacturer or motor nameplate. 4 - ontroller is phase sensitive. Incoming lines must be connected in AB sequence. T7 T8 T9 T T T3 T6 T4 T5 T T T3 M Model : GPP M Models : GPW & GPY OPPER ONDUTORS for Motor onnection (M-M). Field Wiring According to (AWG or MM). Terminals T-T-T3-T4-T5-T6-T7-T8-T x (4 to 0) x (0) x (8 to ) x (8 to ) x (6 to ) x (4 to /0) x ( to 3/0) x ( to /0) 0 to 40 x (4 to 0) x (0) x (8 to ) x (8 to ) x (6 to ) x (4 to /0) x (3 to /0) x ( to /0) 380 to 46 x (4 to 0) x (4 to 0) x (4 to 0) x (0) x (0) x (8 to ) x (6 to ) x (6 to ) x (4 to 0) x (4 to 0) x (4 to 0) x (0) x (0 to ) x (8 to ) x (6 to ) x (6 to ) x (4 to 0) x (4 to 0) x (4 to 0) x (4 to 0) x (0) x (0 to ) x (8 to ) x (8 to ) x (/0 to 3/0) x (3/0) x (50 to 300) x (/0 to 300) x (3/0 to 350) 0 to 40 x (/0 to /0) x (3/0) x (4/0 to 300) x (300) x (/0 to 300) x (4/0 to 350) 380 to 46 x (4 to /0) x ( to /0) x (/0 to /0) x (/0 to 3/0) x (4/0 to 300) x (300) x (/0 to 300) x (3/0 to 300) x (4/0 to 350) x (4/0 to 350) x (4 to /0) x (3 to /0) x ( to /0) x (/0 to 3/0) x (/0 to 3/0) x (4/0 to 300) x (300) x (/0 to 300) x (/0 to 300) x (3/0 to 350) x (4/0 to 350) x (6 to ) x (4 to /0) x (3 to /0) x ( to 3/0) x (/0 to 3/0) x (/0 to 3/0) x (4/0 to 300) x (50 to 300) x (300) x (/0 to 300) x (/0 to 300) ALUMINUM ONDUTORS for ontactor (M-M). Field Wiring According to (AWG or MM). Terminals T-T-T3-T4-T5-T6-T7-T8-T x (0) x (0) x (8 to ) x (6 to ) x (4 to ) x ( to /0) x (/0 to 3/0) x (/0) 0 to 40 x (0) x (0) x (8 to ) x (8 to ) x (6 to ) x ( to /0) x ( to /0) x (/0 to /0) 380 to 46 x (0) x (0) x (8 to ) x (8 to ) x (6 to ) x (4 to ) x (3 to /0) x (0) x (0) x (8 to ) x (8 to ) x (6 to ) x (4 to ) x (0) x (0) x (0) x (8 to ) x (8 to ) x (6 to ) x (3/0) onsult Factory x (300) 90 * x (3/0 to 300) x (50 to 350) 0 to 40 x (/0) 90 * onsult Factory x (300) x (300) 90 * x (4/0 to 300) x (300 to 350) 380 to 46 x ( to /0) x (/0 to /0) x (/0 to /0) x (3/0) 90 * x (300) x (300) 90 * x (4/0 to 300) x (50 to 300) x (300 to 350) x (300 to 350) x (3 to /0) x ( to /0) x (/0) 90 * x (/0 to 3/0) x (3/0) 90 * x (300) x (300) 90 * x (3/0 to 300) x (4/0 to 300) x (50 to 350) x (300 to 350) x (4 to ) x (3 to /0) x ( to /0) x (/0 to 3/0) x (3/0) x (3/0) 90 * x (300) x (300) 90 * onsult Factory x (3/0 to 300) x (4/0 to 300) opyright 07 * For standard enclosure, use 90 aluminium wire. onsult Factory for Use of onductors Rated Lower than 90. NY Dpt of Building Approved REV. DESRIPTION Drawing for information only. Manufacturer reserves the right to modify this drawing without notice. ontact manufacturer for "As Built" drawing. DD/MM/YY General Revision (added AL coverage) 0/07/7 First issue 6/03/7 Drawing number GPX-TD60 / /E 0 DL Tornatech Inc. All right reserved. This drawing and the information contained or depicted herein are the sole property of Tornatech Inc. opies are communicated to the recipient in strict confidence and may not be retransmitted, published, reproduced, copied or used in any manner, including as the basis for the manufacture or sale of any products, without the express prior written consent of Tornatech Inc.

16 Electric Fire Pump ontroller Model: GPX Terminal Diagram and Sizing ontrol Terminals (EB) Terminals Wire Size: 4 - AWG 0.5 Nm Built to the latest edition of the NFPA 0 standard Remote Alarm Terminals (EB) Terminals Wire Size: 4 - AWG 0.5 Nm Remote Manual Start lose to start pump IN J5 Motor Run loses to alarm loses to alarm N N J40 TB Lockout lose to block start IN J5 Available loses to alarm loses to alarm N N J4 TB Remote Automatic Start Open to start pump J* IN3 J5 Phase Reversal loses to alarm loses to alarm N N J37 TB3 Deluge Valve Open to start pump J* IN4 J5 Pump Room Alarm ** loses to alarm loses to alarm N N J39 TB4 Alarm Inputs (EB) Terminals Wire Size: 4 - AWG 0.5 Nm Motor Trouble ** loses to alarm loses to alarm N N J4 TB5 Water Reservoir Low lose to signal alarm IN5 J5 (Field Programmable ***) loses to alarm loses to alarm N N J55 TB6 Network onnection (VMB) Shielded Female onnector RJ45 Modbus TP/IP I/O * Remove jumper to use this feature ** Re-assignable *** Not available on GPS models opyright 07 NY Dpt of Building Approved REV. DESRIPTION DD/MM/YY General Revision (added AL coverage) 0/07/7 0 First issue 6/03/7 Drawing for information only. Manufacturer reserves the right to modify this drawing without notice. ontact manufacturer for "As Built" drawing. Drawing number GPX-TD603 /E Tornatech Inc. All right reserved. This drawing and the information contained or depicted herein are the sole property of Tornatech Inc. opies are communicated to the recipient in strict confidence and may not be retransmitted, published, reproduced, copied or used in any manner, including as the basis for the manufacture or sale of any products, without the express prior written consent of Tornatech Inc. DL

17 Automatic Transfer Switch For Electric Fire Pump ontroller Terminal Diagram and Sizing Terminals Model: GPU Built to the latest edition of the NFPA 0 standard Bonding Ground 3 Phases Incoming Notes: - ontroller is phase sensitive. Incoming lines must be connected in AB sequence. AL AL AL3 AIS OPPER ONDUTORS for Isolating Switch (AIS). Field Wiring According to (AWG or MM). Terminals AL - AL - AL3 5 " (7 mm) 8 " (03 mm) x (3 to /0) x ( to /0) x (/0 to 50) x (3/0 to 50) x (4/0 to 50) 0 to 40 x (3 to /0) x ( to 50) x (/0 to 50) x (3/0 to 50) 380 to 46 x (3 to /0) x (3 to /0) x (3 to /0) " (305 mm) 6 " (406 mm) x (300 to 500) x (500) x (4/0 to 500) x (50 to 500) x (400 to ) 0 to 40 x (50 to 500) x (350 to 500) x (3/0 to 500) x (4/0 to 500) x (350 to 500) x (500 to ) 380 to 46 x (/0 to 50) x (3/0 to 50) x (50) x (300 to 500) x (3/0 to 50) x (4/0 to 500) x (400 to ) x (400 to 500) x (500 to ) x () x ( to 50) x (/0 to 50) x (3/0 to 50) x (4/0 to 50) x (350 to 500) x (3/0 to 50) x (4/0 to 500) x (350 to 500) x (400 to ) x (500 to ) x (3 to /0) x ( to 50) x (/0 to 50) x (3/0 to 50) x (50 to 500) x (350 to 500) x (3/0 to 50) x (4/0 to 500) x (50 to 500) x (350 to 500) 5 " (7 mm) 8 " (03 mm) " (305 mm) ALUMINUM ONDUTORS for Isolating Switch (AIS). Field Wiring According to (AWG or MM). Terminals AL - AL - AL3 5 " (7 mm) 8 " (03 mm) 0 " (54 mm) x (3 to /0) x ( to /0) 0 to 40 x (3 to /0) x ( to /0) x (/0) x (3/0 to 50) x (4/0 to 50) x ( to /0) x (/0 to 50) x (4/0 to 50) x (300) ** or x (50) 90 * x (50) 380 to 46 x ( to /0) x ( to /0) x (/0) x ( to /0) x ( to /0) x ( to /0) " (305 mm) 6 " (406 mm) 08 0 to to x (400 to 500) x (350 to 500) x (3/0 to 50) x (/0 to 50) x ( to /0) x(500) 90 or x(4/0 to 50) ** x (500) x (50) x (3/0 to 50) x (/0 to 50) x (50 to 500) x (350) ** N/A ** x (50) x (3/0 to 50) x (350 to 500) x (400 to 500) x (300) ** or x (50) 90 * x (4/0 to 50) x () x (500) x (4/0 to 50) x (500) x (350 to 500) x () 90 * x (50) x (500) x (4/0 to 50) 5 " (7 mm) 8 " (03 mm) " (305 mm) x (400 to 500) x (500) x (350 to 500) x (500 to ) x (400 to 500) x () 90 * x () 90 * x (500) x (400 to 500) x () x () 90 * x (500) opyright 07 * For standard enclosure, use 90 aluminium wire. onsult Factory for Use of onductors Rated Lower than 90. ** onsult Factory NY Dpt of Building Approved REV. DESRIPTION DD/MM/YY General Revision (added AL coverage) 0/07/7 Added terminal ratings 0/05/7 0 First issue 0//6 Drawing for information only. Manufacturer reserves the right to modify this drawing without notice. ontact manufacturer for "As Built" drawing. Drawing number GPU-TD / /E Tornatech Inc. All right reserved. This drawing and the information contained or depicted herein are the sole property of Tornatech Inc. opies are communicated to the recipient in strict confidence and may not be retransmitted, published, reproduced, copied or used in any manner, including as the basis for the manufacture or sale of any products, without the express prior written consent of Tornatech Inc. DL

18 Automatic Transfer Switch For Electric Fire Pump ontroller Terminal Diagram and Sizing Model: GPU Built to the latest edition of the NFPA 0 standard Remote Alarm Terminals (TSB) Terminals Wire Size: 4 - AWG 0.5 Nm Tr. Sw. in alternate position Tr. Sw. in normal position AB in OFF or tripped Generator Set Opens when Tr. Sw. is in alternate position Opens when Tr. Sw. is in normal position loses when AB is in OFF or tripped ontrol Terminals (TSB) Terminals Wire Size: 4 - AWG 0.5 Nm Opens to start generator loses when Tr. Sw. in Alternate Position loses when Tr. Sw. in Normal Position Opens when AB is in OFF or Tripped loses to start generator N N N N A Pos. N Pos. AB GEN J39 J39 opyright 07 NY Dpt of Building Approved REV. DESRIPTION DD/MM/YY General Revision (added AL coverage) 0/07/7 Added terminal ratings 0/05/7 0 First issue 0//6 Drawing for information only. Manufacturer reserves the right to modify this drawing without notice. ontact manufacturer for "As Built" drawing. Drawing number GPU-TD / /E Tornatech Inc. All right reserved. This drawing and the information contained or depicted herein are the sole property of Tornatech Inc. opies are communicated to the recipient in strict confidence and may not be retransmitted, published, reproduced, copied or used in any manner, including as the basis for the manufacture or sale of any products, without the express prior written consent of Tornatech Inc. DL

Model GPP Full Service Reduced Voltage Part Winding Electric Fire Pump Controller

Model GPP Full Service Reduced Voltage Part Winding Electric Fire Pump Controller Project: ustomer: Engineer: Pump Manufacturer: Technical Data Submittal Documents Model GPP Full Service Reduced Part Winding Electric Fire Pump ontroller ontents: Data Sheets Dimensional Data Wiring Schematics

More information

Model GPW Full Service Reduced Voltage Wye-delta Closed Electric Fire Pump Controller

Model GPW Full Service Reduced Voltage Wye-delta Closed Electric Fire Pump Controller Project: ustomer: Engineer: Pump Manufacturer: Technical Data Submittal Documents Model GPW Full Service Reduced Wye-delta losed Electric Fire Pump ontroller ontents: Data Sheets Dimensional Data Wiring

More information

Model GPA Full Service Full Voltage Across the Line Start Electric Fire Pump Controller

Model GPA Full Service Full Voltage Across the Line Start Electric Fire Pump Controller Project: ustomer: Engineer: Pump Manufacturer: Technical Data Submittal Documents Model GPA Full Service Full Across the Line Start Electric Fire Pump ontroller ontents: Data Sheets Dimensional Data Wiring

More information

Model GPW + GPU Full Service Reduced Voltage Wye-delta Closed Electric Fire Pump Controller with Automatic Power Transfer Switch

Model GPW + GPU Full Service Reduced Voltage Wye-delta Closed Electric Fire Pump Controller with Automatic Power Transfer Switch Project: ustomer: Engineer: Pump Manufacturer: Technical Data Submittal Document Model GPW + GPU Full Service Reduced Wye-delta losed Electric Fire Pump ontroller with Automatic Transfer Switch ontents:

More information

Model GPS Full Service Reduced Voltage Soft Start Soft Stop Electric Fire Pump Controller

Model GPS Full Service Reduced Voltage Soft Start Soft Stop Electric Fire Pump Controller Project: ustomer: Engineer: Pump Manufacturer: Technical Data Submittal Documents Model GPS Full Service Reduced Soft Start Soft Stop Electric Fire Pump ontroller ontents: Data Sheets Dimensional Data

More information

Model GPS + GPU Full Service Reduced Voltage Soft Start Soft Stop Electric Fire Pump Controller with Automatic Power Transfer Switch

Model GPS + GPU Full Service Reduced Voltage Soft Start Soft Stop Electric Fire Pump Controller with Automatic Power Transfer Switch Project: ustomer: Engineer: Pump Manufacturer: Technical Data Submittal Document Model GPS + GPU Full Service Reduced Soft Start Soft Stop Electric Fire Pump ontroller with Automatic Transfer Switch ontents:

More information

Model GPS + GPU Full Service Reduced Voltage Soft Start Soft Stop Electric Fire Pump Controller with Automatic Power Transfer Switch

Model GPS + GPU Full Service Reduced Voltage Soft Start Soft Stop Electric Fire Pump Controller with Automatic Power Transfer Switch Project: ustomer: Engineer: Pump Manufacturer: Technical Data Submittal Document Model GPS + GPU Full Service Reduced Soft Start Soft Stop Electric Fire Pump ontroller with Automatic Transfer Switch ontents:

More information

Project: Customer: Engineer: Pump Manufacturer: Model GPY + GPU. with Automatic Power Transfer Switch

Project: Customer: Engineer: Pump Manufacturer: Model GPY + GPU. with Automatic Power Transfer Switch Project: Customer: Engineer: Pump Manufacturer: Model GPY + GPU with Automatic Power Transfer Switch Contents: NOTE: The drawings included in this package are for controllers covered under our standard

More information

Technical Data Submittal Document

Technical Data Submittal Document Project: Customer: Engineer: Pump Manufacturer: Technical Data Submittal Document Model GPL + GLU Limted Service Full Voltage Across the Line Start Electric Fire Pump Controller Contents: Data Sheets Dimensional

More information

Drawing Submittal Package

Drawing Submittal Package Project: Customer: Engineer: Pump Manufacturer: Drawing Submittal Package Model GPL + GLU Limited Service Full Voltage Across the Line Start Electric Pump Controller with Automatic Power Transfer Switch

More information

Drawing Submittal Package

Drawing Submittal Package Project: Customer: Engineer: Pump Manufacturer: Drawing Submittal Package Model GPL + GLU Limited Service Full Voltage Across the Line Start Electric Pump Controller with Automatic Power Transfer Switch

More information

Model VPS + VPU Pressure Limiting (VFD) Electric Fire Pump Controller with Soft Start Bypass with Automatic Power Transfer Switch

Model VPS + VPU Pressure Limiting (VFD) Electric Fire Pump Controller with Soft Start Bypass with Automatic Power Transfer Switch Project: Customer: Engineer: Pump Manufacturer: Technical Data Submittal Document Model VPS + VPU Pressure Limiting (VFD) with Soft Start Bypass with Automatic Transfer Switch Contents: Data Sheets Dimensional

More information

Model VPS Pressure Limiting (VFD) Electric Fire Pump Controller with Soft Start Bypass

Model VPS Pressure Limiting (VFD) Electric Fire Pump Controller with Soft Start Bypass Project: Customer: Engineer: Pump Manufacturer: Submittal Document Model VPS Pressure Limiting (VFD) with Soft Start Bypass Contents: Data Sheets Dimensional Data Wiring Schematics Field Connections Note:

More information

Model GPD Diesel Engine Driven Fire Pump Controller

Model GPD Diesel Engine Driven Fire Pump Controller Project: ustomer: Engineer: Pump Manufacturer: Submittal Document Model GPD Diesel Engine Driven Fire Pump ontroller ontents: Data Sheets Dimensional Data Wiring Schematics Field onnections Note: The drawings

More information

Technical Data Submittal Documents

Technical Data Submittal Documents Project: Customer: Engineer: Pump Manufacturer: Technical Data Submittal Documents Model PD - FM Diesel Engine Driven Fire Pump Controller Contents: Data Sheets Dimensional Data Wiring Schematics Field

More information

Technical Data Submittal Documents

Technical Data Submittal Documents Project: Customer: Engineer: Pump Manufacturer: Technical Data Submittal Documents Model PD Diesel Engine Driven Fire Pump Controller Contents: Data Sheets Dimensional Data Wiring Schematics Field Connections

More information

Technical Data Submittal Document

Technical Data Submittal Document Project: ustomer: ngineer: Pump Manufacturer: Technical ata Submittal ocument Model JP2 cross the Line Start Jockey Pump ontroller ontents: ata Sheets imensional ata Wiring Schematics ield onnections Note:

More information

Technical Data Submittal Document

Technical Data Submittal Document Project: ustomer: ngineer: Pump Manufacturer: Technical ata Submittal ocument Model JP3 cross the Line Start Jockey Pump ontroller ontents: ata Sheets imensional ata Wiring Schematics ield onnections Note:

More information

Options for Diesel Fire Pump Controllers

Options for Diesel Fire Pump Controllers Options for Diesel Fire Pump Controllers 2015-2016 This document describes our standard options. Please consult factory for any additional options / features / modifications if required. Modifications

More information

LMR Electric Fire Pump Controllers Features

LMR Electric Fire Pump Controllers Features 1-1 Printer / Recorder The industrial grade thermal printer is housed in a rugged steel enclosure within the controller. The on/off switch, feed and reset buttons are front accessible. A bi-color status

More information

FD30 Full Voltage - Across the Line July 2011

FD30 Full Voltage - Across the Line July 2011 Must Be Installed Per Applicable Code and Manufacturers Recommendations Electric Fire Pump Controllers Features 1-1 FD30 Full Voltage - Across the Line July 2011 Power I/O Board Transformers Incoming line

More information

Customer Connection Terminals Connection terminals for external customer connections, are located at the top of the Power I/O board.

Customer Connection Terminals Connection terminals for external customer connections, are located at the top of the Power I/O board. Must Be Installed Per Applicable Code and Manufacturers Recommendations Electric Fire Pump Controllers Features 1-1 FD80 Reduced Voltage - Wye Delta (Star-Delta) Closed Transition Power I/O Board Transformers

More information

LMR Electric Fire Pump Controllers Features

LMR Electric Fire Pump Controllers Features 1-1 Printer / Recorder The industrial grade thermal printer is housed in a rugged steel enclosure within the controller. The on/off switch, feed and reset buttons are front accessible. A bi-color status

More information

FT60 Reduced Voltage - Autotransformer

FT60 Reduced Voltage - Autotransformer 1-1 Product Description The Automatic Transfer Switch Option may be added to any FD type Fire Pump Controller whenever automatic transfer from normal to alternate power is required. The automatic Transfer

More information

FT40 Reduced Voltage - Part Winding. Electrically and Mechanically

FT40 Reduced Voltage - Part Winding. Electrically and Mechanically LMR PLUS Electric Fire Pump Controllers with Transfer Switch Features FT40 Reduced Voltage - Part Winding 1-1 January 2012 Product Description The Automatic Transfer Switch Option may be added to any FD

More information

FDF Foam Pump Controllers Features

FDF Foam Pump Controllers Features FDF100 Diesel Engine Foam Pump Controllers 1-1 Product Description The FDF Series of Foam Pump Controllers are designed for use with foam concentrate injection, foam transfer and water mist systems for

More information

FT20 Full Voltage - Limited Service. Electrically and Mechanically

FT20 Full Voltage - Limited Service. Electrically and Mechanically LMR PLUS Electric Fire Pump Controllers with Transfer Switch FT20 Full Voltage - Limited Service 1-1 May 2014 Product Description The Automatic Transfer Switch Option may be added to any FD type Fire Pump

More information

Fire Pump Controllers Medium Voltage Controllers

Fire Pump Controllers Medium Voltage Controllers Fire Pump Controllers Medium Voltage Controllers Medium Voltage Controllers 1.5 Medium Voltage Fire Pump Controllers FDM Medium Voltage... Part Number / Options Selection Guide... Product Specifications

More information

Transfer Switch Features

Transfer Switch Features 1-1 Product Description The Automatic Transfer Option may be added to any FD type Fire Pump Controller whenever automatic transfer from normal to alternate power is required. The automatic Transfer and

More information

Soft Start Series MP700 Solid State, Reduced Voltage

Soft Start Series MP700 Solid State, Reduced Voltage Metron Fire Pump Controls and Accessories Soft Start Series MP700 Solid State, Reduced Voltage Metron Fire Pump Controllers conform to the latest requirements of National Fire Protection Association s

More information

Fire Pump Controllers Foam (Additive) Controllers

Fire Pump Controllers Foam (Additive) Controllers Fire Pump Controllers Foam (Additive) Controllers Diesel Additive (Foam) Pump Controllers 1.4 Foam (Additive) Fire Pump Controllers FDF20 Foam (Additive) - Limited Service... FDF30 Foam (Additive) - Across-the-Line...

More information

WITH POWER TRANSFER SWITCH STANDARD SUBMITTAL PACKAGE

WITH POWER TRANSFER SWITCH STANDARD SUBMITTAL PACKAGE WITH POWER TRANSFER SWITCH STANDARD SUBMITTAL PACKAGE SBP1000-61 FTA1000 Full Voltage Starting Electric Fire Pump Controllers Product Description Description Firetrol FTA1000 Full Voltage Fire Pump Controllers

More information

DIESEL Engine Fire Pump Controllers Features. FD120 Diesel Engine Controllers

DIESEL Engine Fire Pump Controllers Features. FD120 Diesel Engine Controllers DIESEL Engine Fire Pump Controllers Features FD120 Diesel Engine Controllers 1-1 March 2013 Diesel Product Description The DIESEL Plus Fire Pump Controllers from Eaton Corporation are designed to control

More information

Across-the-Line SERIES MP300 Combined Manual and Automatic

Across-the-Line SERIES MP300 Combined Manual and Automatic Across-the-Line SERIES MP300 Combined Manual and Automatic Metron Fire Pump Controllers conform to the latest requirements of National Fire Protection Association s Standard for Centrifugal Fire Pumps

More information

Transfer Switch Features

Transfer Switch Features 1-1 Product Description The Automatic Transfer Switch Option may be added to any FD type Fire Pump Controller whenever automatic transfer from normal to alternate power is required. The automatic Transfer

More information

DIESEL Engine Fire Pump Controllers Features

DIESEL Engine Fire Pump Controllers Features 1-1 Product Description The FD100 Diesel Engine Controller is designed to control and monitor 12 or 24 volt, diesel fire pump engines. All models are listed by UL and ULC, and approved by Factory Mutual

More information

INSTALLATION AND MAINTENANCE MANUAL FOR ELECTRIC FIRE PUMP CONTROLLERS MODEL GPX

INSTALLATION AND MAINTENANCE MANUAL FOR ELECTRIC FIRE PUMP CONTROLLERS MODEL GPX INSTALLATION AND MAINTENANCE MANUAL FOR ELECTRIC FIRE PUMP CONTROLLERS MODEL GPX 1 Table of Contents 1. Introduction 2. Installation 3. Main Features 4. Home 5. Alarms 6. Configuration 7. History 8. Service

More information

FDJ SERIES Jockey Pump Controllers Features

FDJ SERIES Jockey Pump Controllers Features 1-1 NEMA 2 Enclosures Enclosures have an oven baked powder paint finish and are supplied with NEMA 2 rating, unless otherwise ordered. Available options include: NEMA 1, 3R,, X, 12. Note: NEMA, X enclosures

More information

Variable Frequency Drive SERIES MP800 VFD

Variable Frequency Drive SERIES MP800 VFD Metron Fire Pump Controls and Accessories Variable Frequency Drive SERIES MP800 VFD Metron Fire Pump Controllers conform to the latest requirements of National Fire Protection Association s Standard for

More information

SECTION AUTOMATIC TRANSFER SWITCHES

SECTION AUTOMATIC TRANSFER SWITCHES PART 1 - GENERAL 1.1 DESCRIPTION SECTION 26 36 23 SPEC WRITER NOTE: Use this section only for NCA projects. Delete between //--// if not applicable to project. Also, delete any other item or paragraph

More information

SECTION Fire Pumps

SECTION Fire Pumps SECTION 21 30 00 Fire Pumps PART 1 GENERAL 1.1 WORK INCLUDED A. Furnish, install and test a motor-driven fire pump, jockey pump, and controllers in the space provided and as shown in the contract drawings.

More information

MASTER PRESSRE MAINTANENCE CONTROLLER. Models PMCE INSTRUCTION MANUAL. C 2018 Master Control Systems, Inc

MASTER PRESSRE MAINTANENCE CONTROLLER. Models PMCE INSTRUCTION MANUAL. C 2018 Master Control Systems, Inc MASTER PRESSRE MAINTANENCE CONTROLLER Models PMCE INSTRUCTION MANUAL C 2018 Master Control Systems, Inc TABLE OF CONTENTS Important Safety Information. Page 3 General Description and Installation.. Page

More information

PHYSICAL FACILITIES Consultant s Handbook Specifications Division 21 Fire Suppression 3000 Fire Pumps

PHYSICAL FACILITIES Consultant s Handbook Specifications Division 21 Fire Suppression 3000 Fire Pumps Note: The A/E must choose all design values in brackets below before using in project specifications 1 General 1.1 Provide UL listed and FM approved fire pump complete with pump, driver, controller and

More information

MASTER JOCKEY PUMP CONTROLLER. Model JPCE INSTRUCTION MANUAL. C 2018 Master Control Systems, Inc

MASTER JOCKEY PUMP CONTROLLER. Model JPCE INSTRUCTION MANUAL. C 2018 Master Control Systems, Inc MASTER JOCKEY PUMP CONTROLLER Model JPCE INSTRUCTION MANUAL C 2018 Master Control Systems, Inc TABLE OF CONTENTS Important Safety Information. Page 3 General Description and Installation.. Page 4 Model

More information

DIESEL Engine Fire Pump Controllers Features

DIESEL Engine Fire Pump Controllers Features September 007 DIESEL Engine Fire Pump Controllers Features FD0 Diesel Engine Controllers 1-1 Printer / Recorder The industrial grade thermal printer is housed in a rugged steel enclosure within the controller.

More information

PART GENERAL 1.01 SECTION INCLUDES

PART GENERAL 1.01 SECTION INCLUDES Specification Number: 26 24 16.06 Product Name: Emergency Lighting Control NQ Circuit Panelboards: 240 Vac, 48 Vdc Maximum SECTION 26 24 16.06 Emergency Lighting Control NQ Circuit Panelboards: 240 Vac,

More information

Microprocessor Based Wye-Delta Reduced Current Type Starting

Microprocessor Based Wye-Delta Reduced Current Type Starting Metron Fire Pump Controls and Accessories NEW Microprocessor Based Wye-Delta Reduced Current Type Starting PRODUCT PILOT SERIES MPT430TS (Open Transition) - MPT435TS (Closed Transition) ONLY 32 WIDE WITH

More information

VACUUM BREAKER MEDIUM VOLTAGE AUTOMATIC TRANSFER SWITCHES

VACUUM BREAKER MEDIUM VOLTAGE AUTOMATIC TRANSFER SWITCHES Part One General 1.01 Scope A. It is the intent of this specification to provide a medium voltage automatic transfer system. B. All components, testing and services specified and required for a complete

More information

1.1 REFERENCES.1 American National Standards Institute/National Fire Protection Association (ANSI/NFPA).1 ANSI/NFPA 20, Centrifugal Fire Pumps.

1.1 REFERENCES.1 American National Standards Institute/National Fire Protection Association (ANSI/NFPA).1 ANSI/NFPA 20, Centrifugal Fire Pumps. Issued 2006/08/01 Section 13920 Packaged Fire Pumps and Controllers Page 1 of 7 PART 1 GENERAL 1.1 REFERENCES.1 American National Standards Institute/National Fire Protection Association (ANSI/NFPA).1

More information

SECTION FIRE PUMPS 1.00 PART 1 & GENERAL Description of Work. A. Provide pumps for fire suppression Section Includes

SECTION FIRE PUMPS 1.00 PART 1 & GENERAL Description of Work. A. Provide pumps for fire suppression Section Includes SECTION 210200 Formatted 1.00 PART 1 & GENERAL 1.01 Description of Work A. Provide pumps for fire suppression. 1.02 Section Includes A. Single Stage, Double Suction, 8100 Series Horizontal Splitcase Fire

More information

EATON LMR Plus Electric Fire Pump Controllers

EATON LMR Plus Electric Fire Pump Controllers O & M Manual IM05805020K EATON LMR Plus Description Page 1. INTRODUCTION... 3 2. INSTALLATION AND ELECTRICAL CONNECTIONS... 3 3. HARDWARE DESCRIPTION... 4 4. OPERATION...7 5. PROGRAMMING... 8 6. HISTORY,

More information

CONTENTS AUTOMATIC TRANSFER SWITCHES

CONTENTS AUTOMATIC TRANSFER SWITCHES CONTENTS AUTOMATIC TRANSFER SWITCHES PART 1 GENERAL 1.1 Related Documents 1.2 Summary 1.3 References 1.4 Quality Assurance 1.5 Submittals 1.6 Delivery, Storage and Handling 1.7 Instructions And Training

More information

PS914 Power Supply. 900-KL Keylock (optional) Page BB Battery Backup (optional) Page 3

PS914 Power Supply. 900-KL Keylock (optional) Page BB Battery Backup (optional) Page 3 F1! DANGER 44487056 These instructions cover the following parts: PS914 Power Supply Installation Instructions! DANGER: To avoid risk of electric shock, turn off A power before installing or servicing

More information

Fire Pump Controller. For Electric Motor Driven Fire Pumps. Wye Delta Reduced Current Types

Fire Pump Controller. For Electric Motor Driven Fire Pumps. Wye Delta Reduced Current Types Fire Pump Controller For Electric Motor Driven Fire Pumps Wye Delta Reduced Current Types Series MP430 and Series MP435 Combined Manual and Automatic Metron Fire Pump Controllers conform to the latest

More information

SECTION AUTOMATIC TRANSFER SWITCHES

SECTION AUTOMATIC TRANSFER SWITCHES PART 1 - GENERAL 1.1 DESCRIPTION SECTION 26 36 23 This section specifies the furnishing, complete installation, and connection of automatic transfer switches. 1.2 RELATED WORK A. Section 14 21 00, ELECTRIC

More information

PILOT SERIES MPT700TS

PILOT SERIES MPT700TS Metron Fire Pump Controls and Accessories Microprocessor Based Soft Start/Stop Solid State Reduced Voltage NEW PRODUCT PILOT SERIES MPT700TS ONLY 32 WIDE WITH ATS Available in Across-The-Line, Soft Start,

More information

SECTION P01 LIGHTING AND APPLIANCE PANELBOARDS - A-SERIES

SECTION P01 LIGHTING AND APPLIANCE PANELBOARDS - A-SERIES PART 1 GENERAL A. The requirements of the Contract, Division 1, and Division 16 apply to work in this Section. 1.01 SECTION INCLUDES A. Lighting and appliance panelboards 1.02 RELATED SECTIONS A. 16475,

More information

SECTION AUTOMATIC TRANSFER SWITCHES

SECTION AUTOMATIC TRANSFER SWITCHES SECTION 26 36 23 AUTOMATIC TRANSFER SWITCHES PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. General provisions of the Contract, including General and Supplementary Conditions and Division 01 Specification Sections,

More information

SECTION AUTOMATIC TRANSFER SWITCHES PART 1 - GENERAL

SECTION AUTOMATIC TRANSFER SWITCHES PART 1 - GENERAL SECTION 16400 AUTOMATIC TRANSFER SWITCHES 1.01 RELATED DOCUMENTS PART 1 - GENERAL A. Drawings and general provisions of Contract, including General Conditions and Division 1 Specification sections, apply

More information

Commercial and Light Industrial Fire Alarm Control Panel

Commercial and Light Industrial Fire Alarm Control Panel FireSystem 2000 Commercial and Light Industrial Fire Alarm Control Panel Features Easily expandable. All new plug-in board design Two supervised audible circuits Lamp and system trouble circuit test Ground

More information

P.C. Simonton & Associates, Inc. Consulting Engineers. Paul C. Simonton

P.C. Simonton & Associates, Inc. Consulting Engineers. Paul C. Simonton P.C. Simonton & Associates, Inc. Consulting Engineers 309 North Main Street 1050 Parkside Commons Post Office Box 649 Suite 101 Hinesville, Georgia 31310 Greensboro, Georgia 30642 Addendum No. One Date:

More information

Notes: Warrick Series 67 Intrinsically Safe Multi-Function Control Installation and Operation Bulletin

Notes: Warrick Series 67 Intrinsically Safe Multi-Function Control Installation and Operation Bulletin Notes: Warrick Series 67 Intrinsically Safe Multi-Function ontrol Installation and Operation Bulletin Form 670 Sheet P/N 100501-1 Rev. F Table of ontents Page 3 Page Page 5 Page 6 Page 7 Page 8 Page 9

More information

SA100L. General Description. Features. Temperature Limit Controller SA100L. Simple Mounting on DIN Rail. Over/Under Temperature Protection

SA100L. General Description. Features. Temperature Limit Controller SA100L. Simple Mounting on DIN Rail. Over/Under Temperature Protection SA00 SA00 SA00 SA00 Temperature Limit ontroller SA00L FM APPROVED SA00L General Description The SA00L is a FM approved high limit or low limit controllers. The SA00 is a socket mounting type temperature

More information

UltraLITE Model ELU Centralized Emergency Lighting Inverter 4.2 KW- 5 KW

UltraLITE Model ELU Centralized Emergency Lighting Inverter 4.2 KW- 5 KW 12/23/16 Rev 9 UltraLITE Model ELU General Specification 4.2 KW to 5 KW UltraLITE Model ELU Centralized Emergency Lighting Inverter 4.2 KW- 5 KW 1.0 General General Specification This specification describes

More information

SCC Inc. Master Panel. Specifications. Document No. TS 2010 February 11, Product Description. Sample Specification

SCC Inc. Master Panel. Specifications. Document No. TS 2010 February 11, Product Description. Sample Specification February 11, 2019 Master Panel Product Description The Master Panel shall provide lead/lag control and time based, automatic rotation of up to eight (8) boilers, when used in conjunction with LMV3 or LMV5

More information

232xt Wiring Diagrams and Specifications SPECIFICATIONS: REV 1.01

232xt Wiring Diagrams and Specifications SPECIFICATIONS: REV 1.01 232xt Wiring Diagrams and Specifications Voltage Selection Settings 1 2 3 Wire Xtreme Pad color to color to the wires on Programmer (Red to Red, ect.) ( / Yellow ) Position 12-24VA 15-24VD P5* Position

More information

A. This Section includes transfer switches rated 600 V and less, including the following:

A. This Section includes transfer switches rated 600 V and less, including the following: SECTION 16415 - TRANSFER SWITCHES PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 1 Specification

More information

TotalPac 3 Deluge, Electric release Self-contained system

TotalPac 3 Deluge, Electric release Self-contained system (Optional) DESRIPTION This TOTALPA 3 integrated fire protection system by FireFlex Systems Inc. consists of a deluge system trim totally preassembled, pre-wired and factory tested. All electrical and mechanical

More information

RA889A Switching Relay

RA889A Switching Relay Switching Relay FEATURES PRODUT DATA High load switching capability. Troubleshooting LED. Push-to-test button. Replaceable transformer fuse. Long-life D relay drive control technology. Relay for use with

More information

Model APD. Remote alarm panel for diesel motor driven fire pump. Drawing Submittal Package

Model APD. Remote alarm panel for diesel motor driven fire pump. Drawing Submittal Package Project: Customer: Engineer: Pump Manufacturer: Model APD Remote alarm panel for diesel motor driven fire pump Drawing Submittal Package Contents: Brochure Dimensional Data Wiring Schematics Field Connections

More information

INSTALLATION/OPERATING INSTRUCTIONS SEQUENCING PANELS

INSTALLATION/OPERATING INSTRUCTIONS SEQUENCING PANELS R INSTALLATI/OPERATING INSTRUTIS SEQUENING PANELS SEQ-6, SEQ-6P and SEQ-12 Panels to Sequence up to 12 Individual Stages with Lead-Lag and Manual Override apabilities TENTS SEQ FUNTI HART... 2 DIP SWITH

More information

Pressure Transducers Ultrahigh-Purity

Pressure Transducers Ultrahigh-Purity www.swagelok.com Pressure Transducers Ultrahigh-Purity PTU Series Single-end, flow-through, and modular surface-mount models Positive pressure ranges to 5000 psi, 400 bar, and 40 MPa; compound pressure

More information

Specification/ Data Sheet

Specification/ Data Sheet Specification/ Data Sheet TRITON RP Agent Release Control Panel FEATURES Agent Release Control Panel designed specifically for suppression release operation with: Four initiating device circuits (IDCs)

More information

RAYCHEM NGC-30 COMPONENTS

RAYCHEM NGC-30 COMPONENTS PANEL MOUNTED ELECTRONIC MULTI-CIRCUIT HEAT-TRACING CONTROL, MONITORING AND POWER DISTRIBUTION SYSTEM PRODUCT OVERVIEW CABLE DUCT Card Rack Modules TERMINAL STRIP PLINTH MAIN SWITCH 800 mm USER INTERFACE

More information

7800 SERIES RM7888A Relay Module

7800 SERIES RM7888A Relay Module 7800 SERIES RM7888A Relay Module SPECIFICATION DATA FEATURES APPLICATION The Honeywell RM7888A Relay Module is a microprocessor-based integrated burner control for industrial process semi-automatically

More information

Installation Operation Maintenance

Installation Operation Maintenance Installation Operation Maintenance RTAF SE/HE/XE/HSS/HSE Air-cooled Helical-rotary chillers 300-1600 kw Sintesis chillers are part of the Ingersoll Rand EcoWise portfolio of products that are designed

More information

PANEL MOUNTED ELECTRONIC MULTI-CIRCUIT HEAT-TRACING CONTROL, MONITORING AND POWER DISTRIBUTION SYSTEM mm. 100 mm

PANEL MOUNTED ELECTRONIC MULTI-CIRCUIT HEAT-TRACING CONTROL, MONITORING AND POWER DISTRIBUTION SYSTEM mm. 100 mm PANEL MOUNTED ELECTRONIC MULTI-CIRCUIT HEAT-TRACING CONTROL, MONITORING AND POWER DISTRIBUTION SYSTEM Card Rack Modules CABLE DUCT MAIN SWITCH 800 mm USER INTERFACE TERMINAL PRODUCT OVERVIEW The nvent

More information

MPT Electric Fire Pump Controller

MPT Electric Fire Pump Controller Setup and Operating Instructions MPT Electric Fire Pump Controller This manual provides general information, installation, operation, maintenance, and system setup information for Metron MPT Electric Fire

More information

NGC-40 PANEL MOUNTED ADVANCED MODULAR HEAT-TRACING CONTROL SYSTEM HTC HTC3

NGC-40 PANEL MOUNTED ADVANCED MODULAR HEAT-TRACING CONTROL SYSTEM HTC HTC3 NGC-40 PANEL MOUNTED ADVANCED MODULAR HEAT-TRACING CONTROL SYSTEM Local configuration and monitoring with Raychem Touch 1500 touch screen display PRODUCT OVERVIEW The Raychem NGC-40 is a multipoint electronic

More information

Latch key safety limit switches Technical data

Latch key safety limit switches Technical data Latch key safety Safety General Data Standards IE 6047-1, IE 6047-5-1, EN 6047-1, EN 6047-5-1, UL 508, and SA 22-2 No. 14 ertifications - Approvals UL and SA Air temperature near the device during operation

More information

GE Security. FP1200, FP2000 and KSA1200 series fire panels, repeaters and emulators Interconnection and wiring

GE Security. FP1200, FP2000 and KSA1200 series fire panels, repeaters and emulators Interconnection and wiring GE Security FP1200, FP2000 and KSA1200 series fire panels, repeaters and emulators Interconnection and wiring Version v2-2 / September 2005 Aritech and Kilsen are GE Security brands. http://www.geindustrial.com/ge-interlogix/emea

More information

DESCRIPTION. 42 mm. 125 mm

DESCRIPTION. 42 mm. 125 mm RMM2-DI TRACE-HEATING REMOTE MONITORING MODULE FOR DIGITAL INPUTS DESCRIPTION 125 mm 60 mm The Remote Monitoring Module for Digital Inputs (RMM2-DI) provides the capability for the Raychem NGC controller

More information

MODEL GPT-130 SINGLE POINT HEAT TRACE CONTROL THERMOSTAT

MODEL GPT-130 SINGLE POINT HEAT TRACE CONTROL THERMOSTAT TRACON MODEL GPT-130 SINGLE POINT HEAT TRACE CONTROL THERMOSTAT TABLE OF CONTENTS GPT 130 Overview... 2 Installation... 3 Power Source and Load Connection... 4 Temperature Sensor Installation... 5 Panel

More information

FireSystem 2000 Commercial and Light Industrial Fire Alarm Control Panel

FireSystem 2000 Commercial and Light Industrial Fire Alarm Control Panel PROTECTOWIRE FireSystems Features Easily expandable Two supervised audible circuits Lamp and system trouble circuit test Ground fault detection Initiating device circuit (IDC) alarm test Monitors up to

More information

Datasheet. Dry-pipe Vacuum Sprinkler System, Electric Release Self contained unit. Features. FIREFLEX VACTEC description

Datasheet. Dry-pipe Vacuum Sprinkler System, Electric Release Self contained unit. Features. FIREFLEX VACTEC description FIREFLEX VACTEC description This FIREFLEX VACTEC integrated fire protection system consists of a vacuum system trim totally pre-assembled, prewired and factory tested. All electrical and mechanical components

More information

CONsOlIDATOR 4 & 8. MulTI- C h ANNEl CONTROllERs. ConsoliDator 4 Model PD940 ConsoliDator 4 Features. ConsoliDator 8 Features.

CONsOlIDATOR 4 & 8. MulTI- C h ANNEl CONTROllERs. ConsoliDator 4 Model PD940 ConsoliDator 4 Features. ConsoliDator 8 Features. CONsOlIDATOR 4 & 8 MulTI- C h ANNEl CONTROllERs ConsoliDator 4 Model PD940 ConsoliDator 4 Features Four 4-20 Four 4-20 Outputs ConsoliDator 8 Features Eight 4-20 Two 4-20 Outputs Common Features Four Pulse

More information

PolyGard Single Point Controller SPC-X3-20XX for refrigerant gases and vapours

PolyGard Single Point Controller SPC-X3-20XX for refrigerant gases and vapours PolyGard Single Point Controller SPC-X3-20XX for refrigerant gases and vapours DESCRIPTION Gas measuring, monitoring and warning controller based on state-of-the-art micro-technology with integrated sensor

More information

7EF/7HF/7EC/7ES Temperature Controllers

7EF/7HF/7EC/7ES Temperature Controllers 7EF/7HF/7E/7ES Temperature ontrollers Dual 4 Digit LED Display Universal Input (6 T/, RTD, mv, V, ma) Autotuning NEMA 4X 100 to 240 Vac Switching Power Supply Algorithms for Heat or Heat/ool ontrol 2 Independent

More information

1.1 Remote Annunciator Controller (RAC) using the one ATC-300+ connected via RS-485 network.

1.1 Remote Annunciator Controller (RAC) using the one ATC-300+ connected via RS-485 network. Remote Annunciator Controller (RAC) Instruction Sheet for Automatic Transfer Switches (ATS) Revision: 01 IB01602085E 1.1 Remote Annunciator Controller (RAC) using the one ATC-300+ connected via RS-485

More information

UC700 EMERGENCY TRANSFER SYSTEM SPECIFIER S HANDBOOK. 40 Dale Street West Babylon, NY Ph: Fx:

UC700 EMERGENCY TRANSFER SYSTEM SPECIFIER S HANDBOOK. 40 Dale Street West Babylon, NY Ph: Fx: UC700 EMERGENCY TRANSFER SYSTEM SPECIFIER S HANDBOOK 40 Dale Street West Babylon, NY 11704 Ph: 631-753-9550 Fx: 631-753-9560 www.unionconnector.com Emergency Automatic Transfer System STANDARD SPECIFICATIONS

More information

FireShield Plus. GE Security. EST Life Safety & Communications Conventional Small Building Solutions. Conventional Fire Alarm Control Panels

FireShield Plus. GE Security. EST Life Safety & Communications Conventional Small Building Solutions. Conventional Fire Alarm Control Panels GE Security EST Life Safety & ommunications onventional Small Building Solutions Overview The FireShield Plus fire alarm family consists of 3, 5 and 10 zone conventional fire alarm s, an integrated DAT/Dialer,

More information

Gas Controller Module GC-06

Gas Controller Module GC-06 Page 1 Oct. 2015/2 Measuring, warning and controlling module for toxic, combustible and refrigerant gases and vapours. The gas controller series GC-06 is designed in accordance with the standard EN 50545-1.

More information

Index Arc Guard Systems. Arc Guard Systems. Arc Guard Systems Industrial Automation Supply - Tel:

Index Arc Guard Systems. Arc Guard Systems. Arc Guard Systems Industrial Automation Supply   - Tel: Systems Index Systems - Systems Systems...1 -.16 General information Description...1 System description...2 Overview...3 Ordering details Arc monitor with detectors...4 Current sensing unit...5 Technical

More information

SPECIFICATION MICROMIST FIRE SUPPRESSION SYSTEM WITH SHP-PRO CONTROL PANEL

SPECIFICATION MICROMIST FIRE SUPPRESSION SYSTEM WITH SHP-PRO CONTROL PANEL SECTION 1 - GENERAL CONDITIONS I. SCOPE: This specification outlines the requirements for a Fike Micromist Water Mist Fire Suppression System with automatic detection and control. The work described in

More information

FTA550 JOCKEY PUMP CONTROLLERS

FTA550 JOCKEY PUMP CONTROLLERS FTA550 JOCKEY PUMP CONTROLLERS STANDARD SUBMITTAL PACKAGE SBP550E (A) FTA550E XG Jockey Pump Controllers Product Description Failed to start indication Main switch not in Auto alarm Pressure recording

More information

ICM 275. Replacement Description

ICM 275. Replacement Description IM 275 Fan ontrol enter Replacement Description The IM275 Gas Furnace ontrol enter is a new generation control for the replacement market. The IM275 Gas Furnace ontrol enter is designed to function similarly

More information

Datasheet. Vacuum Double-interlock Preaction System, Electric Release Self contained unit. Features. FIREFLEX VACTEC description

Datasheet. Vacuum Double-interlock Preaction System, Electric Release Self contained unit. Features. FIREFLEX VACTEC description FIREFLEX VACTEC description This FIREFLEX VACTEC integrated fire protection system consists of a vacuum system trim totally pre-assembled, prewired and factory tested. All electrical and mechanical components

More information

FTA550F JOCKEY PUMP CONTROLLERS STANDARD SUBMITTAL PACKAGE

FTA550F JOCKEY PUMP CONTROLLERS STANDARD SUBMITTAL PACKAGE FTA550F JOCKEY PUMP CONTROLLERS STANDARD SUBMITTAL PACKAGE SBP550F (A) FTA550F XG Jockey Pump Controllers Product Description Description Firetrol FTA550F XG Jockey Pump Controllers are intended for use

More information

Conventional Fire Alarm Systems

Conventional Fire Alarm Systems Kidde atalog u Small Building Fire Alarm Solutions Technology that saves lives onventional Fire Alarm Systems FX-10RD, FX-10R, FX-5RD, FX-5R OA 6230 Overview Kidde brand conventional fire alarm systems

More information

ASCO Series 185 Power Transfer Switches

ASCO Series 185 Power Transfer Switches ASCO Series 185 Power Transfer Switches 24-hour protection no matter when trouble strikes ASCO Series 185 POWER TRANSFER SWITCHES An Automatic Transfer Switch helps prevent... Your business or home from

More information