Addendum No. 2 to the Contract Documents

Similar documents
WET-PIPE SPRINKLER SYSTEMS

North Hanover Township School District North Hanover Township, New Jersey

SECTION WET-PIPE SPRINKLER SYSTEMS

A. Standard-Pressure Piping System Component: Listed for 175-psig minimum working pressure.

SPRINKLERS TABLE OF CONTENTS

B. Galvanized-Steel-Sheet Sleeves: inch minimum thickness; round tube closed with welded longitudinal joint.

SECTION DRY-PIPE SPRINKLER SYSTEMS

ADDENDUM #3 DATE: August 8, 2018 Page 1 of 1. The Curators of the University of Missouri

NORTHWESTERN UNIVERSITY PROJECT NAME JOB # ISSUED: 03/29/2017

UNIVERSITY SERVICES ANNEX James Madison University Harrisonburg, Virginia State Project Code: Architect s Project Number:

THE JAMES RUSHTON EARLY LEARNING AND FAMILY SUCCESS CENTER #2616 ISSUE FOR CONSTRUCTION

NORTHWESTERN UNIVERSITY PROJECT NAME JOB # ISSUED: 03/29/2017

CubeSmart Gulf Breeze Storage AUTOMATIC FIRE SPRINKLER SYSTEM

B. Related Sections: The following Sections contain requirements that relate to this Section.

SECTION WET-PIPE SPRINKLER SYSTEMS

B. Standard-Pressure Standpipe Piping: Fire-suppression standpipe piping designed to operate at working pressure 175 psig (1200 kpa) maximum.

B. Product Data: Provide manufacturers catalogue information. Indicate valve data and ratings.

MASTERSPEC TECHNICAL SPECIFICATIONS DIVISION 21 FIRE SUPPRESSION

SECTION WET-PIPE SPRINKLER SYSTEMS

DIVISION 21 FIRE PROTECTION ISSUE DATE REVISION

C. All components of the systems described shall meet the requirements as stated herein and shall be approved by the Architect and Consultant.

SECTION DRY-PIPE SPRINKLER SYSTEMS

A. This Section includes the following fire-suppression piping inside the building:

Gas Station & C Store SECTION CWM Job No

MASTERSPEC TECHNICAL SPECIFICATIONS DIVISION 21 FIRE SUPPRESSION

SECTION PREACTION SPRINKLER SYSTEMS

B. The sprinkler system shall be designed to meet the more stringent of the requirements of NFPA 13 and FM Global requirements.

SECTION SLEEVES AND SLEEVE SEALS FOR FIRE-SUPPRESSION PIPING

MLA Architects Pierz Public Schools ISD #484 Healy High School Multi-Purpose & Choir Additions Pioneer Elementary School Class Room Addition Pierz, MN

A. Section includes wet-pipe sprinkler system, system design, installation, and certification.

FIRE PROTECTION. 1. Vertical fire pumps shall not be used at the University.

1.2 CODES AND REGULATIONS A. Sprinkler system design, equipment, materials, devices, and installation shall conform to the following:

SECTION WET-PIPE SPRINKLER SYSTEMS EASY RISER CHECK VALVE

SECTION SPRINKLER SYSTEMS

SECTION FIRE PROTECTION. A. Examine all conditions as they exist at the project, prior to submitting a bid for the work of this section

University of Houston Master Construction Specifications Insert Project Name SECTION DRY-PIPE FIRE SPRINKLER SYSTEM PART 1 - GENERAL

TABLE OF CONTENTS DIVISION 21- FIRE SUPPRESSION PAGES SECTION WATER BASED FIRE PROTECTION SYSTEMS... 5

SECTION FIRE-SUPPRESSION PIPING

SECTION WET PIPE FIRE PROTECTION SPRINKLER SYSTEM

A. Hydraulic calculations shall be prepared in accordance with Chapter 23 of NFPA 13 with the following exceptions:

ADDENDUM NO. 3 March 19, 2018

1.1 Refer to Section for General Mechanical Requirements. 1.3 Refer to Section for Pipe and Equipment Identification Requirements.

SECTION SPRINKLER SYSTEMS

DIVISION 21 FIRE SUPPRESSION SECTION FIRE PROTECTION SPECIALTIES

FIRE SUPPRESSION SPRINKLER SYSTEM

Port of St Helens SIA Aircraft Hanger Scappoose, OR

TECHNICAL SPECIFICATIONS SECTION DRY PIPE SPRINKLER SYSTEM PLAISTOW PUBLIC LIBRARY 85 MAIN STREET PLAISTOW, NEW HAMPSHIRE 100%CD.

SECTION DRY PIPE SPRINKLER SYSTEMS MODEL F SERIES DRY VALVE

West District Library Section Campeau Drive, Ottawa SPRINKLER SYSTEMS City of Ottawa Project No. CR Page 1 of 8

Essex County College - West Essex Campus Addition And Renovations dlb # / 11-14

SECTION DRY PIPE SPRINKLER SYSTEMS MODEL G SERIES DRY VALVE

END OF SECTION

B. Section Identification for Fire Suppression Piping and Equipment.

SECTION FIRE-SUPPRESSION SYSTEMS

SECTION FIRE-SUPPRESSION STANDPIPES

Facility Fire-Suppression Water-Service Piping

DARTMOUTH COLLEGE DESIGN November 15, 2007 & CONSTRUCTION GUIDELINES

SECTION AUTOMATIC SPRINKLER PIPING

SECTION FIRE PROTECTION

COBB COUNTY SCHOOLS /S&A % BID DOCUMENTS 2/18/11 SECTION SPRINKLER SYSTEM

ACADEMIC SUCCESS CENTER THE COLLEGE AT BROCKPORT STATE UNIVERSITY OF NEW YORK PROJECT NO

A. This section includes design and performance information for fire protection and suppression systems.

SECTION COMMON WORK RESULTS FOR FIRE SUPPRESSION

DIVISION 21 - FIRE SUPPRESSION

SECTION WET AUTOMATIC FIRE SPRINKLER SYSTEMS

2. Welding Materials and Procedures shall conform to the ASME Code.

DIVISION 21: FIRE SUPPRESSION WATER BASED FIRE SUPRESSION SYSTEMS

DIVISION 21 - FIRE SUPPRESSION

Council Bluffs, Iowa Division TOC 1 TABLE OF CONTENTS DIVISION 21 FIRE SUPPRESSION

UNIVERSITY OF MISSOURI Fire Protection System Design 2016 Q1

Mercy Hospital of Buffalo Catholic Health System 2 nd Floor Patient Holding Center 3 rd Floor Locker Rooms Shaflucas Architects, PC Project No.

SECTION WET-PIPE FIRE-SUPPRESSION SPRINKLERS

Copyright 2016 AIA MasterSpec Full Length 09/16 PRODUCT MASTERSPEC LICENSED BY AVITRU, LLC TO VICTAULIC COMPANY.

SECTION WET FIRE SPRINKLER SYSTEMS

UC Santa Cruz Campus Design Guide. Includes the following sections: None DESIGN REQUIREMENTS

SECTION WET-PIPE SPRINKLER SYSTEMS

Division 21: FIRE SUPRESSION WET-PIPE SPRINKLER PROTECTION SYSTEM. The Academy Sept Table of Contents 1 Division 21

Mercury Plastics New Building February TABLE OF CONTENTS

REFRIGERANT PIPING

SECTION FIRE SUPPRESSION SYSTEMS

SECTION WET-PIPE FIRE SUPPRESSION SPRINKLERS

Springpoint Architects, pc SECTION Childcare Center Architect s Project No TABLE OF CONTENTS Monroe County Comm. Sch. Corp.

2016 CDM Smith All Rights Reserved July 2016 SECTION FIRE PROTECTION - SPRINKLER AND STANDPIPE SYSTEMS

NATURAL GAS PIPING

PART 1 - GENERAL SECTION FIRE PROTECTION BASIC MATERIALS AND METHODS

A. All Fire Suppression System design and installation shall comply with the most current and adopted version of NFPA 13.

Wayne State University WSU Project No Chatsworth Tower Apts. Misc. Bldg. Upgrades DSD Project No

SECTION ADDENDUM NO. 1 FIRE SPRINKLER SYSTEM

TABLE OF CONTENTS

PHYSICAL FACILITIES. 1 General. 2 Related Requirements. 5 Quality Assurance. 3 Wiring. 4 Submittals

PROJ. NO SECTION REFRIGERANT PIPING

DOCUMENT TABLE OF CONTENTS

Copyright 2016 AIA MasterSpec Full Length 09/16 PRODUCT MASTERSPEC LICENSED BY AVITRU, LLC TO VICTAULIC COMPANY.

NFPA 2001: Standard for Clean Agent Fire Extinguishing Systems NFPA 70: National Electrical Code (NEC) NFPA 72: National Fire Alarm Code

NITROGEN-GENERATING SPRINKLER CORROSION INHIBITING SYSTEM

B. Utility-furnished products include water meters that will be furnished to the site, ready for installation.

University of Missouri St. Louis September 9, 2013 Recreation and Wellness Center #S

SECTION GENERAL-SERVICE COMPRESSED-AIR SYSTEMS

DESIGN & CONSTRUCTION GUIDELINES

WET AUTOMATIC FIRE SPRINKLER SYSTEMS

Transcription:

Addendum No. 2 to the Contract Documents Lewis County Jefferson Community College Education Center Project CONTRACT 2A: GENERAL CONSTRUCTION CONTRACT 2B: ELECTRICAL CONSTRUCTION CONTRACT 2C: MECHANICAL CONSTRUCTION CONTRACT 2D: PLUMBING CONSTRUCTION August 2, 2018 To All Holders of the RFB Documents: Your attention is directed to the following additions to the Contract Documents for the project referenced above. Except as specifically stated herein, all conditions and requirements of the Contract Documents remain in full force and effect. ADDITION / DELETION: REMOVE AND REPLACE TECHNICAL SPECIFICATIONS TABLE OF CONTENTS There was an error on the table of contents provided in the original documents. Specification 211313 was labeled incorrectly as 111313. ADD SPECIFICATION 211313 WET PIPE SPRINKLER SYSTEMS The specification 211313 Wet Pipe Sprinkler Systems was inadvertently left out of the original documents: AUTHORIZED BY: END OF ADDENDUM NO. 2 C&S Engineers, Inc. Charles Brooks, P.E. NYSPE License No. 089275

LEWIS COUNTY LEWIS COUNTY JEFFERSON COMMUNITY COLLEGE EDUCATION CENTER PROJECT CONTRACT 2A: GENERAL CONSTRUCTION CONTRACT 2B: ELECTRICAL CONSTRUCTION CONTRACT 2C: MECHANICAL CONSTRUCTION CONTRACT 2D: PLUMBING CONSTRUCTION TECHNICAL SPECIFICATIONS TABLE OF CONTENTS DIVISION 01 GENERAL REQUIREMENTS 011000... Summary 012200... Unit Prices 012600... Contract Modification Procedures 012900... Payment Procedures 013100... Project Management and Coordination 013200... Construction Progress Documentation 013300... Submittal Procedures 014000... Quality Requirements 014200... References 015000... Temporary Facilities and Controls 016000... Product Requirements 017300... Execution 017700... Closeout Procedures 017839... Project Record Documents DIVISION 02 EXISTING CONDITIONS (NOT USED) DIVISION 03 CONCRETE 033000... Cast-In-Place Concrete DIVISION 04 MASONRY 042200... Concrete Unit Masonry TABLE OF CONTENTS 1 of 4

047000... Manufactured Masonry 047200... Cast Stone Masonry DIVISION 05 METALS 051200... Structural Steel 054000... Cold-Formed Metal Framing 055813... Column Covers DIVISION 06 WOOD AND PLASTICS 061053... Miscellaneous Rough Carpentry 061600... Sheathing 064116... Plastic-Laminate-Faced Architectural Cabinets DIVISION 07 THERMAL AND MOISTURE PROTECTION 072100... Thermal Insulation 072500... Weather Barriers 074113.16... Standing-Seam Metal Roof Panels 074213.13... Formed Metal Wall Panels 076200... Sheet Metal Flashing & Trim 077523... Snow Guards 079200... Joint Sealants DIVISION 08 DOORS AND WINDOWS 081113... Hollow Metal Doors & Frames 081416... Flush Wood Doors 083113... Access Doors & Frames 083323... Overhead Coiling Doors 084113... Aluminum-Framed Entrances & Storefronts 085200... Wood Windows 087100... Door Hardware 088000... Glazing DIVISION 09 FINISHES 092216... Non-Structural Metal Framing 092900... Gypsum Board 093013... Ceramic Tiling 095123... Acoustical Tile Ceilings 095200... Acoustical Metal Ceilings 096229... Cork Wall Tile 096513... Resilient Base & Accessories 096519... Resilient Tile Flooring 096813... Tile Carpeting 099113... Exterior Painting TABLE OF CONTENTS 2 of 4

099123... Exterior Painting 099600... High Performance Coatings DIVISION 10 SPECIALTIES 101100... Visual Display Units 101432... Panel Signage 102113.19... Plastic Toilet Compartments 102239... Folding Panel Partitions 102600... Wall and Door Protection 102800... Toilet, Bath & Laundry Accessories 104413... Fire Protection Cabinets 104416... Fire Extinguishers 107113... Exterior Sun Control Devices DIVISION 11 EQUIPMENT (NOT USED) DIVISION 12 FURNISHINGS 122413... Roller Window Shades 123661... Simulated Stone Countertops 124813... Entrance Floor Mats & Frames DIVISION 13 SPECIAL CONSTRUCTION (NOT USED) DIVISION 14 CONVEYING EQUIPMENT (NOT USED) DIVISION 21 FIRE PROTECTION 211313... Wet-Pipe Sprinkler Systems DIVISION 22 PLUMBING 220529... Supports & Anchors 220553... Piping Identification 220700... Plumbing Insulation 223000... Plumbing General 224000... Plumbing Fixtures DIVISION 23 MECHANICAL (NOT USED) DIVISION 25 INTEGRATED AUTOMATION (NOT USED) DIVISION 26 ELECTRICAL 260501... Common Work Results for Electrical 260519... Low-Voltage Electrical Power Conductors & Cables TABLE OF CONTENTS 3 of 4

260526... Grounding and Bonding for Electrical Systems 260529... Hangars & Supports for Electrical Systems 260533... Raceways & Boxes for Electrical Systems 260553... Identification for Electrical Systems 260923... Lighting Control Devices 260943... Distributed Digital Lighting Control System 262213... Low-Voltage Distribution Transformers 262416... Panelboards 262726... Wiring Devices 262813... Fuses 262816... Enclosed Switches 264313... Surge Protection for Low-Voltage Electrical Power Curcuits 265119... LED Interior Lighting 265213... Emergency & Exit Lighting 265619... LED Exterior Lighting DIVISION 27 COMMUNICATION 270500... Common Work Results 270528... Communications Pathway Systems 271100... Telecommunications Room Fittings 271300... Backbone Cabling 271500... Horizontal Cabling 271700... Testing & Identification DIVISION 28 ELECTRONIC SAFETY AND SECURITY 281300... Access Controls 282300... Video Surveillance 283111... Digital, Addressable Fire-Alarm System DIVISION 31 EARTHWORK (NOT USED) DIVISION 32 EXTERIOR IMPROVEMENTS (NOT USED) DIVISION 33 UTILITES (NOT USED) DIVISION 34 TRANSPORTATION (NOT USED) END OF TABLE OF CONTENTS TABLE OF CONTENTS 4 of 4

SECTION 211313 - WET-PIPE SPRINKLER SYSTEMS PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 01 Specification Sections, apply to this Section. 1.2 SUMMARY A. Section includes wet-pipe sprinkler system, system design, installation, and certification. The entire system shall be installed in conformance with NFPA 13. B. Section Includes: 1. Pipes, fittings, and specialties. 2. Fire-department connections. 3. Sprinklers. 4. Alarm devices. 5. Pressure gages. 6. Hangers and supports. 1.3 DEFINITIONS A. Standard-Pressure Sprinkler Piping: Wet-pipe sprinkler system piping designed to operate at working pressure of 175 psig maximum. 1.4 REFERENCES A. International Building Code, 2015 B. International Fire Code, 2015 C. International Plumbing Code, 2015 D. 2017 NYS Uniform Code Supplement E. NFPA 13 (National Fire Protection Association) - Installation of Sprinkler Systems, 2013 F. NFPA 24 (National Fire Protection Association) - Installation of Private Fire Service Mains and Their Appurtenances, 2007 G. NFPA 25 (National Fire Protection Association) Standard for the Inspection, Testing, and Maintenance of Water-Based Fire Protection System, 2014 WET-PIPE SPRINKLER SYSTEMS 211313-1

H. NFPA 291 (National Fire Protection Association) Standard for fire flow testing and Marking of Hydrants, 2013 I. NFPA 72 (National Fire Protection Association) National Fire Alarm Code, 2013 J. 2017 Underwriters Laboratories, Inc. (UL) Fire Protection Equipment Directory K. 2017 Factory Mutual (FM) Approval Guide L. Requirements of Owner Insurance Underwriter and Other Authorities Having Jurisdiction as applicable. 1.5 SYSTEM DESCRIPTIONS A. Wet-Pipe Sprinkler System: Automatic sprinklers are attached to piping containing water that is connected to the water supply through an alarm valve. Water discharges immediately from sprinklers when they are opened. Sprinklers open when heat melts the fusible link or destroys the frangible device. Hose connections are included if indicated. System to provide coverage for all areas in the building except those noted on the contract documents. B. Provide hydraulically designed system to NFPA 13 occupancy requirements. Provide all sprinkler risers with hydraulic data plate with system design information. Mount to respective riser. This data plate shall include the location of the design area or areas, discharge densities over the design area or areas, required flow and residual pressure demand at the base of the riser, occupancy classification or commodity classification and maximum permitted storage height/configuration, and hose stream demand included in addition to the sprinkler demand. C. Water supply data by flow test at 10 in. underground main located on East Road indicates: 47 psi static and 35 psi residual with 488 gpm flow. Contractor shall perform flow test per NFPA 291 to verify available supply. D. Interface system with building fire alarm system. E. Sprinkler system shall be hydraulically calculated. Pipe sizes shown on drawings shall be maintained and used in calculations. F. Light Hazard Design Criteria: 0.10 gpm/ft2 over 1500 ft2 design area with an outside hose stream demand of 100 gpm for a duration of 30 minutes. G. Ordinary Hazard Group 1 Design Criteria: 0.15 gpm/ft2 over 1500 ft2 design area with an outside hose stream demand of 250 gpm for a duration of 60-90 minutes. H. Ordinary Hazard Group 2 Design Criteria: 0.20 gpm/ft2 over 1500 ft2 design area with an outside hose stream demand of 250 gpm for a duration of 60-90 minutes. I. Sprinkler spacing shall not exceed 196 ft2 for Light Hazard and130 ft2 for Ordinary Hazard. J. A 10 psi safety factor shall be incorporated into all hydraulic calculations. WET-PIPE SPRINKLER SYSTEMS 211313-2

K. Maximum 20 fps system flow velocity and 15 fps in mains with paddle waterflow switches. 1.6 PROJECT SCOPE A. Provide an automatic wet-pipe sprinkler system throughout the building as indicated on the contract documents. 1.7 PERFORMANCE REQUIREMENTS A. Standard-Pressure Piping System Component: Listed for 175-psig minimum working pressure. B. Sprinkler system design shall be approved by authorities having jurisdiction. 1. Sprinkler Occupancy Hazard Classifications: a. Instructional/Fabrication Labs: Ordinary Hazard, Group 2. b. Mechatronics Classrooms: Ordinary Hazard, Group 1. c. Mech/Elec/General Storage Areas and Similar Spaces: Ordinary Hazard, Group 1. d. Classrooms/Corridors/Offices/Conference Rooms and Similar Spaces: Light Hazard. 1.8 SUBMITTALS A. Submittal Procedures: Submittal procedures as indicated in Division 1 of these specifications. B. Shop Drawings: NFPA 13 drawings, hydraulic calculations for each design area with cross reference to applicable drawings, water supply data, and equipment schedule. Indicate layout of finished ceiling areas indicating sprinkler locations coordinated with ceiling installation. Indicate detailed pipe layout, hangers and supports, sprinklers, components and accessories. Indicate system controls. Provide coordination drawings indicating the work of other trades. 1. Sprinklers shall be referred to on drawings, submittals and other documentation, by the sprinkler identification or Model number as specifically published in the appropriate agency listing or approval. Trade names or other abbreviated designations shall not be allowed. C. Product Data: Submit data on sprinklers, valves, and specialties, including manufacturers catalog information. Submit performance ratings, rough-in details, weights, support requirements, and piping connections. D. Fire Hydrant Flow Test Report: Prior to system layout, submit detailed fire flow test data per NFPA 291. Include scaled/dimensioned drawing showing flow/pressure locations/elevations; number/size/coefficient for orifices; pitot/static/residual pressures; test time/date; main sizes. E. Approved sprinkler drawings: working plans, prepared according to NFPA 13, that have been approved by authorities having jurisdiction and owner s representative, including hydraulic calculations. WET-PIPE SPRINKLER SYSTEMS 211313-3

F. Submit firestopping system and material product data and UL listed firestopping details to be utilized for the project. 1.9 CLOSEOUT SUBMITTALS A. Execution Requirements: Closeout procedures as indicated in division 1 of these specifications. B. Project Record Documents: Record actual locations of sprinklers and deviations of piping from drawings. Indicate drain and test locations. C. Operation and Maintenance Data: Submit components of system, servicing requirements, record drawings, inspection data, replacement part numbers and availability, and location and numbers of service depot. D. Submit the latest edition of NFPA 25 Standard for the Inspection, Testing, and Maintenance of Water Based Fire Protection System to the owner upon completion of project. E. Field Test Reports and Certificates: Indicate and interpret test results for compliance with performance requirements and as described in NFPA 13. Include Contractor s Material and Test Certificate for Above Ground Piping. F. Schedule of preventative maintenance inspections/testing and outline of what inspections/testing shall occur. 1.10 QUALITY ASSURANCE A. Manufacturer: Company specializing in manufacturing products specified in this section with minimum three years documented experience, and with service facilities within 100 miles of project. B. Installer: Company specializing and licensed in performing work of this section with minimum five years documented experience and NICET (National Institute for Certification in Engineering Technologies) certified. C. System shall be designed and installed under the direct supervision of a NICET Level IV certified designer in Fire Protection/Automatic Sprinkler System Layout. D. Firestop Installer Qualifications: FM 4991, UL, or proof of certified training. E. Electrical Components, Devices, and Accessories: Listed and labeled as defined in NFPA 70, by a qualified testing agency, and marked for intended location and application. 1.11 MAINTENANCE SERVICE A. Furnish service and maintenance of the system components for one year from the Date of Substantial Completion as outlined in Division 21 specifications. WET-PIPE SPRINKLER SYSTEMS 211313-4

1.12 COORDINATION A. Coordinate layout and installation of sprinklers with other construction that penetrates ceilings, including light fixtures, HVAC equipment, and partition assemblies. 1.13 EXTRA MATERIALS A. Provide extra sprinklers as required by NFPA 13. B. Provide suitable wrenches for each sprinkler type. C. Provide metal storage cabinet located adjacent to sprinkler riser. D. Provide all manufacturer special tools for maintenance of system. 1.14 ADDITIONAL SPRINKLERS AND GUARDS A. Furnish extra materials that match products installed and that are packaged with protective covering for storage and identified with labels describing contents. B. Provide [insert value] additional sprinklers with associated piping and supports and [insert value] additional sprinkler guards installed at locations where directed and where job conditions may require. PART 2 - PRODUCTS 2.1 PIPING MATERIALS A. Comply with requirements in "Piping Schedule" Article for applications of pipe, tube, and fitting materials, and for joining methods for specific services, service locations, and pipe sizes. 2.2 STEEL PIPE AND FITTINGS A. Standard Weight, Galvanized and/or Black Steel Pipe: ASTM A 53/A 53M, or ASTM A 135, ASTM A 795, Schedule 40 for NPS 2 and smaller. Pipe ends may be factory or field formed to match joining method. B. Standard Weight, Galvanized and/or Black Steel Pipe: ASTM A 53/A 53M, or ASTM A 135, ASTM A 795, Schedule 10 for NPS 2.5 and larger. Pipe ends may be factory or field formed to match joining method C. Black-Steel Pipe Nipples: ASTM A 733, made of ASTM A 53/A 53M, standard-weight, seamless steel pipe with threaded ends. D. Uncoated, Steel Couplings: ASTM A 865, threaded. E. Uncoated, Gray-Iron Threaded Fittings: ASME B16.4, Class 125, standard pattern. WET-PIPE SPRINKLER SYSTEMS 211313-5

F. Malleable- or Ductile-Iron Unions: UL 860. G. Cast-Iron Flanges: ASME 16.1, Class 125. H. Steel Flanges and Flanged Fittings: ASME B16.5, Class 150. I. Steel Welding Fittings: ASTM A 234/A 234M and ASME B16.9. J. Grooved-Joint, Steel-Pipe Appurtenances: a. Anvil International, Inc. b. Tyco Fire & Building Products LP. c. Victaulic Company. 2. Pressure Rating: 250 psig minimum. 3. Uncoated, Grooved-End Fittings for Steel Piping: ASTM A 47/A 47M, malleable-iron casting or ASTM A 536, ductile-iron casting; with dimensions matching steel pipe. 4. Grooved-End-Pipe Couplings for Steel Piping: AWWA C606 and UL 213, rigid pattern, unless otherwise indicated, for steel-pipe dimensions. Include ferrous housing sections, EPDM-rubber gasket, and bolts and nuts. 2.3 PIPING JOINING MATERIALS A. Pipe-Flange Gasket Materials: AWWA C110, rubber, flat face, 1/8 inch thick or ASME B16.21, nonmetallic and asbestos free. 1. Class 125, Cast-Iron Flanges and Class 150, Bronze Flat-Face Flanges: Full-face gaskets. 2. Class 250, Cast-Iron Flanges and Class 300, Steel Raised-Face Flanges: Ring-type gaskets. B. Metal, Pipe-Flange Bolts and Nuts: ASME B18.2.1, carbon steel unless otherwise indicated. C. Welding Filler Metals: Comply with AWS D10.12M/D10.12 for welding materials appropriate for wall thickness and chemical analysis of steel pipe being welded. 2.4 LISTED FIRE-PROTECTION VALVES A. General Requirements: 1. Valves shall be UL listed or FM approved. 2. Minimum Pressure Rating for Standard-Pressure Piping: 175 psig. B. Ball Valves: WET-PIPE SPRINKLER SYSTEMS 211313-6

a. Anvil International, Inc. b. Victaulic Company. c. Tyco Fire and Building Products 2. Standard: UL 1091 except with ball instead of disc. 3. Valves NPS 1-1/2 and Smaller: Bronze body with threaded ends. 4. Valves NPS 2 and NPS 2-1/2: Bronze body with threaded ends or ductile-iron body with grooved ends. 5. Valves NPS 3: Ductile-iron body with grooved ends. C. Iron Butterfly Valves: a. Anvil International, Inc. b. Kennedy Valve; a division of McWane, Inc. c. Milwaukee Valve Company. 2. Standard: UL 1091. 3. Pressure Rating: 175 psig. 4. Body Material: Cast or ductile iron. 5. Style: Lug or wafer. 6. End Connections: Grooved. D. Check Valves: a. Reliable Automatic Sprinkler Co., Inc. b. Tyco Fire & Building Products LP. c. Victaulic Company. d. Viking Corporation. 2. Standard: UL 312. 3. Pressure Rating: 250 psig minimum. 4. Type: Swing check. 5. Body Material: Cast iron. 6. End Connections: Flanged or grooved. E. Iron OS&Y Gate Valves: a. Anvil International. b. Milwaukee Valve Company. c. Mueller Co.; Water Products Division. 2. Standard: UL 262. WET-PIPE SPRINKLER SYSTEMS 211313-7

3. Pressure Rating: 250 psig minimum. 4. Body Material: Cast or ductile iron. 5. End Connections: Flanged or grooved. F. Indicating-Type Butterfly Valves: a. Anvil International, Inc. b. Tyco Fire & Building Products LP. c. Victaulic Company. 2. Standard: UL 1091. 3. Pressure Rating: 175 psig minimum. 4. Valves NPS 2 and Smaller: a. Valve Type: Ball or butterfly. b. Body Material: Bronze. c. End Connections: Threaded. 5. Valves NPS 2-1/2 and Larger: a. Valve Type: Butterfly. b. Body Material: Cast or ductile iron. c. End Connections: Flanged, grooved, or wafer. 6. Valve Operation: Integral electrical, 115-V ac, prewired, two-circuit, supervisory switch, visual indicating device. 2.5 TRIM AND DRAIN VALVES A. General Requirements: 1. Standard: UL's "Fire Protection Equipment Directory" listing or "Approval Guide," published by FM Global, listing. 2. Pressure Rating: 175 psig minimum. B. Angle Valves: C. Ball Valves: a. Fire Protection Products, Inc. b. United Brass Works, Inc. c. Nibco Inc. WET-PIPE SPRINKLER SYSTEMS 211313-8

D. Globe Valves: a. Anvil International, Inc. b. Kennedy Valve; a division of McWane, Inc. c. NIBCO INC. a. Fire Protection Products, Inc. b. United Brass Works, Inc. c. Nibco Inc. 2.6 SPECIALTY VALVES A. General Requirements: 1. Standard: UL's "Fire Protection Equipment Directory" listing or "Approval Guide," published by FM Global, listing. 2. Pressure Rating: a. Standard-Pressure Piping Specialty Valves: 175 psig minimum. 3. Body Material: Cast or ductile iron. 4. Size: Same as connected piping. 5. End Connections: Flanged or grooved. B. Riser Check Valve: Designed for horizontal or vertical installation, with bronze groove seat with O-ring seals, single hinge pin, and latch design. Include trim sets for drain and pressure gauges. C. Riser Manifold Assembly: Shall be a manufactured assembly fabricated from carbon steel piping with integral grooved ends with an orange enamel finish. Assembly shall include an alarm test module combination inspector s test/drain valve of bronze construction complete with dual integral sight glasses and a standard ½ test orifice and allow single handle operation for both test and drain functions. The assembly shall also include an integral vane type water flow detector with sealed retard, visual switch activation, and mechanical delay adjustment. D. Automatic (Ball Drip) Drain Valves: a. Viking Company. b. Reliable Automatic Sprinkler Co., Inc. c. Tyco Fire & Building Products LP. WET-PIPE SPRINKLER SYSTEMS 211313-9

2. Standard: UL 1726. 3. Pressure Rating: 175 psig minimum. 4. Type: Automatic draining, ball check. 5. Size: NPS 3/4. 6. End Connections: Threaded. 2.7 BACKFLOW PREVENTER A. Double Detector Check Valve Type: a. Watts b. Febco c. Apollo 2. Cast iron body, stainless steel bolts and internal parts, with test ports and isolation valves. 3. UL/FM; NYS Approved for horizontal and vertical installation. 4. The backflow prevention valve assembly shall be provided with a means of testing the backflow prevention assembly for forward flow tests at system demand. Provide one (1) 2-1/2 national standard threaded male connection with integral valve for every 250 gallons per minute of system demand. 2.8 FIRE-DEPARTMENT CONNECTIONS A. Exposed-Type, Fire-Department Connection: a. Elkhart Brass Mfg. Company, Inc. b. Fire-End & Croker Corporation. c. Potter-Roemer 2. Standard: UL 405. 3. Type: Exposed, projecting, for wall mounting. 4. Pressure Rating: 175 psig minimum. 5. Body Material: Corrosion-resistant metal. 6. Inlets: Brass with threads according to NFPA 1963 and matching local fire-department sizes and threads. Include extension pipe nipples, brass lugged swivel connections, and check devices or clappers. 7. Caps: Brass, lugged type, with gasket and chain. 8. Escutcheon Plate: Round, brass, wall type. 9. Outlet: Back, with pipe threads. 10. Number of Inlets: Two. 11. Escutcheon Plate Marking: Similar to "AUTO SPKR." 12. Finish: Rough brass or bronze. 13. Outlet Size: NPS 4. WET-PIPE SPRINKLER SYSTEMS 211313-10

2.9 SPRINKLER SPECIALTY PIPE FITTINGS A. Branch Outlet Fittings: a. Anvil International, Inc. b. Tyco Fire & Building Products LP. c. Victaulic Company. 2. Standard: UL 213. 3. Pressure Rating: 175 psig minimum. 4. Body Material: Ductile-iron housing with EPDM seals and bolts and nuts. 5. Type: Mechanical-T and -cross fittings. 6. Configurations: Snap-on and strapless, ductile-iron housing with branch outlets. 7. Size: Of dimension to fit onto sprinkler main and with outlet connections as required to match connected branch piping. 8. Branch Outlets: Grooved, plain-end pipe, or threaded. B. Flow Detection and Test Assemblies: a. AGF Manufacturing Inc. b. Reliable Automatic Sprinkler Co., Inc. c. Tyco Fire & Building Products LP. d. Victaulic Company. 2. Standard: UL's "Fire Protection Equipment Directory" listing or "Approval Guide," published by FM Global, listing. Pressure Rating: 175 psig minimum Body Material: Cast- or ductile-iron housing with orifice, sight glass, and integral test valve. 3. Size: Same as connected piping. 4. Inlet and Outlet: Threaded. C. Sprinkler Inspector's Test Fittings: a. AGF Manufacturing Inc. b. Tyco Fire & Building Products LP. c. Victaulic Company. d. Viking Corporation. 2. Standard: UL's "Fire Protection Equipment Directory" listing or "Approval Guide," published by FM Global, listing. 3. Pressure Rating: 175 psig minimum. WET-PIPE SPRINKLER SYSTEMS 211313-11

4. Body Material: Cast- or ductile-iron housing with sight glass. 5. Size: Same as connected piping. 6. Inlet and Outlet: Threaded. D. Flexible, Sprinkler Hose Fittings: a. Victaulic b. FlexHead Industries, Inc. c. Sprinkflex 2. Standard: UL 1474. 3. Type: Flexible hose for connection to sprinkler, and with bracket for connection to ceiling grid. 4. Pressure Rating: 175 psig minimum. 5. Size: Same as connected piping, for sprinkler. 6. Corrugated (Unbraided) Flexible Hose Assemblies not permitted. 2.10 SPRINKLERS A. Manufacturers: Subject to compliance with requirements, provide products by one of the 1. Reliable Automatic Sprinkler Co., Inc. 2. Tyco Fire & Building Products LP. 3. Victaulic Company. 4. Viking Corporation. B. General Requirements: 1. Standard: UL's "Fire Protection Equipment Directory" listing or "Approval Guide," published by FM Global, listing. 2. Pressure Rating for Automatic Sprinklers: 175 psig minimum. C. Automatic Sprinklers with Heat-Responsive Element: 1. Nonresidential Applications: UL 199. 2. Characteristics: Nominal 1/2-inch orifice with Discharge Coefficient K of 5.6, and for "Ordinary" temperature classification rating unless otherwise indicated or required by application. D. Open Sprinklers with Heat-Responsive Element Removed: UL 199. 1. Characteristics: E. Sprinkler Finishes: a. Nominal 1/2-inch Orifice: With Discharge Coefficient K between 5.3 and 5.8. WET-PIPE SPRINKLER SYSTEMS 211313-12

1. Chrome plated. 2. Bronze. 3. Painted. F. Special Coatings: 1. Wax. 2. Lead. 3. Corrosion-resistant paint. G. Sprinkler Escutcheons: Materials, types, and finishes for the following sprinkler mounting applications. Escutcheons for concealed, flush, and recessed-type sprinklers are specified with sprinklers. 1. Ceiling Mounting: Chrome-plated steel, two piece, with 1-inch vertical adjustment. 2. Sidewall Mounting: Chrome-plated steel, two piece, with 1-inch vertical adjustment. H. Sprinkler Guards: a. Reliable Automatic Sprinkler Co., Inc. b. Tyco Fire & Building Products LP. c. Victaulic Company. d. Viking Corporation. 2. Standard: UL 199. 3. Type: Wire cage with fastening device for attaching to sprinkler. 2.11 ALARM DEVICES A. Alarm-device types shall match piping and equipment connections. B. Electrically Operated Alarm Bell: a. System Sensor; a Honeywell company. b. Notifier; a Honeywell company. c. Potter Electric Signal Company. 2. Standard: UL 464. 3. Type: Vibrating, metal alarm bell. 4. Size: 8-inch minimum-diameter. 5. Finish: Red-enamel factory finish, suitable for outdoor use. C. Water-Flow Indicators: WET-PIPE SPRINKLER SYSTEMS 211313-13

a. Potter Electric Signal Company. b. System Sensor; a Honeywell company. c. Viking Corporation. 2. Standard: UL 346. 3. Water-Flow Detector: Electrically supervised. 4. Components: Two single-pole, double-throw circuit switches for isolated alarm and auxiliary contacts, 7 A, 125-V ac and 0.25 A, 24-V dc; complete with factory-set, fieldadjustable retard element to prevent false signals and tamperproof cover that sends signal if removed. 5. Type: Paddle operated. 6. Pressure Rating: 250 psig. 7. Design Installation: Horizontal or vertical. D. Valve Supervisory Switches: a. Potter Electric Signal Company. b. System Sensor; a Honeywell company. 2. Standard: UL 346. 3. Type: Electrically supervised. 4. Components: Single-pole, double-throw switch with normally closed contacts. 5. Design: Signals that controlled valve is in other than fully open position. 2.12 PRESSURE GAGES A. Manufacturers: Subject to compliance with requirements, provide products by one of the 1. AMETEK; U.S. Gauge Division. 2. Ashcroft, Inc. 3. Brecco Corporation. B. Standard: UL 393. C. Dial Size: 3-1/2- to 4-1/2-inch diameter. D. Pressure Gage Range: 0 to 250 psig minimum. E. Water System Piping Gage: Include "WATER" or "AIR/WATER" label on dial face. 2.13 HANGERS, INSERTS, DRILL-IN EXPANSION ANCHORS AND SUPPORTS A. Standard: NFPA approved, UL Listed, or FM approved. WET-PIPE SPRINKLER SYSTEMS 211313-14

B. Hangers, clamps: 1. Adjustable, wrought malleable iron or steel, cadmium plated or galvanized. Copper plated or PVC coated where in contact with copper piping. 2. Adjustable swivel ring type for sprinkler piping under 6 in. and smaller. 3. Nuts and rods with electroplated zinc or cadmium (0.005 in. minimum) finish. 4. Spacing and rod sizes in accordance with NFPA. 5. Concrete inserts: Galvanized finish, maximum loading 400 lbs. 6. Drill-in expansion anchors: Maximum loading 1000 lbs., galvanized finish. C. Supports: 1. For weights under 1000 lbs.: Drill in expansion anchor, "U" Channel, beam clamps or other structurally reviewed support. The factor of safety shall be at least five. Follow manufacturer's recommendations and NFPA. 2. For weights above 1000 lbs.: Drill through floor slabs and provide flat flush plate welded to top of rod or provide additional drill in expansion anchor and hangers to reduce load per hanger below 1000 lbs. 3. For metal decks: Drill hole through for hanger rods and imbed a welded plate in concrete or use devices designed for this application, with a safety factor of five. PART 3 - EXECUTION 3.1 PREPARATION A. Perform fire-hydrant flow test according to NFPA 13 and NFPA 291. Use results for system design calculations required in "Systems Description Article. B. Report test results promptly and in writing. 3.2 SERVICE-ENTRANCE PIPING A. Connect sprinkler piping to water-service piping for service entrance to building. B. Install backflow preventer, pressure gage, drain, and other accessories indicated at connection to water-service piping. C. Install shutoff valve, check valve, pressure gage, and drain at connection to water service. 3.3 PIPING INSTALLATION A. Locations and Arrangements: Drawing plans, schematics, and diagrams indicate general location and arrangement of piping. Install piping as indicated, as far as practical. 1. Deviations from approved working plans for piping require written approval from authorities having jurisdiction. File written approval with Architect before deviating from approved working plans. WET-PIPE SPRINKLER SYSTEMS 211313-15

2. Install piping to minimize obstructions to other trades. 3. Install piping concealed above finished ceilings unless noted otherwise. 4. Pipe size called for shall be maintained. Pipe size changes made only as reviewed by owner s representative. Where discrepancy in size occurs, the larger size shall be provided. B. Piping Standard: Comply with requirements for installation of sprinkler piping in NFPA 13. C. Use listed fittings to make changes in direction, branch takeoffs from mains, and reductions in pipe sizes. D. Install unions adjacent to each valve in pipes NPS 2 and smaller. E. Install flanges, flange adapters, or couplings for grooved-end piping on valves, apparatus, and equipment having NPS 2-1/2 and larger end connections. F. Install "Inspector's Test Connections" in sprinkler system piping, complete with shutoff valve, and sized and located according to NFPA 13. G. Install sprinkler piping with drains for complete system drainage. H. Install sprinkler control valves, test assemblies, and drain risers adjacent to standpipes when sprinkler piping is connected to standpipes. I. Install automatic (ball drip) drain valve at each check valve for fire-department connection, to drain piping between fire-department connection and check valve. Install drain piping to and spill over floor drain or to outside building. J. Install alarm devices in piping systems. K. Install hangers and supports for sprinkler system piping according to NFPA 13. Comply with requirements for hanger materials in NFPA 13. L. Install pressure gages on riser or feed main, at each sprinkler test connection, and at top of each standpipe. Include pressure gages with connection not less than NPS 1/4 and with soft metal seated globe valve, arranged for draining pipe between gage and valve. Install gages to permit removal, and install where they will not be subject to freezing. M. Fill sprinkler system piping with water. N. Install sleeves for piping penetrations of walls, ceilings, and floors. O. Install sleeve seals for piping penetrations of concrete walls and slabs. P. Install escutcheons for piping penetrations of walls, ceilings, and floors. WET-PIPE SPRINKLER SYSTEMS 211313-16

3.4 JOINT CONSTRUCTION A. Install couplings, flanges, flanged fittings, unions, nipples, and transition and special fittings that have finish and pressure ratings same as or higher than system's pressure rating for aboveground applications unless otherwise indicated. B. Install unions adjacent to each valve in pipes NPS 2 and smaller. C. Install flanges, flange adapters, or couplings for grooved-end piping on valves, apparatus, and equipment having NPS 2-1/2 and larger end connections. D. Ream ends of pipes and tubes and remove burrs. Bevel plain ends of steel pipe. E. Remove scale, slag, dirt, and debris from inside and outside of pipes, tubes, and fittings before assembly. F. Flanged Joints: Select appropriate gasket material in size, type, and thickness suitable for water service. Join flanges with gasket and bolts according to ASME B31.9. G. Threaded Joints: Thread pipe with tapered pipe threads according to ASME B1.20.1. Cut threads full and clean using sharp dies. Ream threaded pipe ends to remove burrs and restore full ID. Join pipe fittings and valves as follows: 1. Apply appropriate tape or thread compound to external pipe threads. 2. Damaged Threads: Do not use pipe or pipe fittings with threads that are corroded or damaged. H. Welded Joints: Construct joints according to AWS D10.12M/D10.12, using qualified processes and welding operators according to "Quality Assurance" Article. 1. Shop weld pipe joints where welded piping is indicated. Do not use welded joints for galvanized-steel pipe. I. Steel-Piping, Roll-Grooved Joints: Roll rounded-edge groove in end of pipe according to AWWA C606. Assemble coupling with housing, gasket, lubricant, and bolts. Join steel pipe and grooved-end fittings according to AWWA C606 for steel-pipe grooved joints. J. Dissimilar-Material Piping Joints: Make joints using adapters compatible with materials of both piping systems. 3.5 VALVE AND SPECIALTIES INSTALLATION A. Install listed fire-protection valves, trim and drain valves, specialty valves and trim, controls, and specialties according to NFPA 13 and authorities having jurisdiction. B. Install listed fire-protection shutoff valves supervised open, located to control sources of water supply except from fire-department connections. Install permanent identification signs indicating portion of system controlled by each valve. WET-PIPE SPRINKLER SYSTEMS 211313-17

C. Install check valve in each water-supply connection. Install backflow preventers instead of check valves in potable-water-supply sources. D. Auxiliary drains shall be provided where a change in piping direction prevents drainage of system piping through the main drain valve. 1. Where the capacity of isolated trapped sections of pipe is 50 gallons or more, the auxiliary drain shall consist of a valve not smaller than 1, accessibly located (no more than 7 feet above finished floor). 2. Where the capacity of isolated trapped sections of pipe is more than 5 gallons and less than 50 gallons, the auxiliary drain shall consist of a valve ¾ or larger and a plug or nipple and cap. E. Specialty Valves: 1. General Requirements: Install in vertical position for proper direction of flow, in main supply to system. 3.6 SPRINKLER INSTALLATION A. Install sprinklers in suspended ceilings in center of narrow dimension of acoustical ceiling panels. B. Install dry-type sprinklers with water supply from heated space. Do not install pendent or sidewall, wet-type sprinklers in areas subject to freezing. C. Install sprinklers into flexible, sprinkler hose fittings and install hose into bracket on ceiling grid. D. The sprinkler bulb protector must remain in place until the sprinkler is completely installed and before the system is placed in service. Failure to follow this instruction could cause damage to the glass bulb, resulting in improper sprinkler operation, serious personal injury and property damage. Remove bulb protectors carefully by hand after installation. Do not use any tools to remove bulb protectors. E. Do not install sprinklers that have been dropped, damaged, or show a visible loss of fluid. Never install sprinklers with cracked bulbs. F. Provide protection in electric, telephone, elevator equipment, and electronic equipment spaces. Piping shall not pass directly over electric panel boards, switchboards, motor control centers, elevator rooms/hoist ways, controllers, and similar electric/telephone equipment. G. Provide guards for sprinklers in mechanical, storage, closet, and similar spaces than 8-0 above finished floor. H. Provide protection under ductwork, groups of ductwork, and other obstructions to water spray distribution. Use intermediate level sprinklers if subject to water spray from above. WET-PIPE SPRINKLER SYSTEMS 211313-18

3.7 FIRE-DEPARTMENT CONNECTION INSTALLATION A. Install wall-type, fire-department connections. Located as indicated on contract drawings. B. The fire department connection shall be provided with an automatic ball drip assembly to prevent freezing. Install automatic (ball drip) drain valve at each check valve for firedepartment connection. Each fire department connection shall be provided with a listed check valve. C. Inlets: Coordinate fire department connection inlet type with local fire department and authority having jurisdiction. Fire department connection shall be a 2-1/2 Siamese with National Standard Threads unless otherwise specified by the local fire department. Provide chained caps. The fire department connection shall be located not less than 18 and not more than 48 above finished grade. The size of the fire department connection pipe shall be a minimum of 4 or for a hydraulically calculated system no less than the size of the system riser where one riser is being served. D. The fire department connection shall be piped to the system side of the alarm check valve. For combined systems, the fire department connection shall be connected between the supply control valves and the system control valves. E. Locate fire department connection with sufficient clearance from walls, obstructions, or to allow full swing of fire department wrench handle. Coordinate location with local fire department. F. Install a 30 elbow between the inlet pipe stubbing outside of the building/stand alone connection and the fire department connection at all fire department connections to prevent fire department hose kinking. 3.8 IDENTIFICATION A. Install labeling and pipe markers on equipment and piping according to requirements in NFPA 13. B. Identify system components, wiring, cabling, and terminals. Comply with requirements for identification specified in Division 26 Section "Identification for Electrical Systems." C. Provide sign at or near fire department connection a minimum of an 18 by 18 reflective diagrammatic sign meeting NFPA 170 requirements. The sign shall also indicate the building name and address in which it services, systems within the building in which it serves, and the pressure required at the inlets to deliver the greatest system demand. D. Valve Signage: 1. All main and sectional system control valves, including water supply control valves, shall have a sign indicating the portion of the system that is controlled by the valve. 2. All control, drain, and test connection valves shall be provided with signs indicating their purpose. WET-PIPE SPRINKLER SYSTEMS 211313-19

3. Where a main or section control valve is located in a closed room or concealed space, the location of the valve shall be indicated by a sign in an approved location on the outside of the door or near the opening to the concealed space. 3.9 FIELD QUALITY CONTROL A. Perform tests and inspections. B. Final Acceptance/Commissioning Test: The system will be accepted only after satisfactory test of the entire system has been accomplished by the Contractor at the direction of the C&S Engineers, Inc., in the presence of the Authority Having Jurisdiction and the Owner. The Contractor shall notify the above witnesses, in writing, 72 hours prior to the commencement of testing. Failure to contact the above parties will require the Contractor to conduct tests a second time at the Contractor s expense in the presence of the above parties. C&S Engineers, Inc. shall have complete direction over the final acceptance/commissioning test of the system. C. Water flow detecting devices including the associated alarm circuits shall be flow tested through the inspector s test connection and shall result in an audible alarm on the premises within 5 minutes after such flow begins and until such flow stops. D. The main drain valve shall be opened and remain open until the system pressure stabilizes. Static and residual pressures shall be recorded. E. Tests and Inspections: 1. Leak Test: After installation, charge systems and test for leaks. Repair leaks and retest until no leaks exist. 2. Test and adjust controls and safeties. Replace damaged and malfunctioning controls and equipment. 3. Flush, test, and inspect sprinkler systems according to NFPA 13, "Systems Acceptance" Chapter. 4. Energize circuits to electrical equipment and devices. 5. Coordinate with fire-alarm tests. Operate as required. 6. Verify that equipment hose threads are same as local fire-department equipment. F. Sprinkler piping system will be considered defective if it does not pass tests and inspections. G. Prepare test and inspection reports. H. Test backflow preventer in accordance with NFPA 13, Systems Acceptance chapter. 3.10 INTERFACE WITH OTHER PRODUCTS A. Verify signal devices are installed and connected to fire alarm system. WET-PIPE SPRINKLER SYSTEMS 211313-20

3.11 PROTECTION OF INSTALLED CONSTRUCTION A. Apply masking tape or paper cover to protect concealed sprinklers, cover plates, and sprinkler escutcheons not receiving field paint finish. Remove after painting. Replace painted sprinklers with new. 3.12 CLEANING A. Clean dirt and debris from sprinklers. B. Remove and replace sprinklers with paint other than factory finish. 3.13 DEMONSTRATION AND TRAINING A. The Contractor shall provide a minimum of 2 hours of instruction and operation, and maintenance of all elements of the materials and methods specified above for non-technician personnel prior to the commissioning of the building fire suppression system. All training shall take place prior to final acceptance testing of the system. All demonstration and training provided to Owner personnel shall be witnessed by the C&S Engineers, Inc. construction management representative. The Contractor shall notify the above witnesses, in writing, 72 hours prior to the commencement of testing. Failure to contact the above parties will require the Contractor to conduct training a second time at the contractor s expense in the presence of the above parties. B. Instruction shall be provided by a material or system manufacturer s certified representative familiar with the equipment and special operating requirements of the system provided and the Owner s operating procedures. C. Instructions shall include classroom training as well as hands on training of all components of the system and their operation. D. Instruction shall be made available on a schedule acceptable to the Owner and the availability of the operating personnel. Instructions shall be in two separate groupings with the last instruction time frame 30 days after the second grouping. This is to allow the operating personnel to familiarize themselves with the equipment and get follow-up training as required. The last training session shall be a minimum of 1 hour(s). E. Contractor shall be responsible for providing sufficient training materials for all present at the training session, (minimum 15 personnel). Coordinate actual requirements with the Owner at time of training. F. The Contractor shall be responsible for providing videotaped training sessions, which will be submitted to the owner for future employee training. All of the training sessions conducted shall be videotaped. WET-PIPE SPRINKLER SYSTEMS 211313-21

3.14 PIPING SCHEDULE A. Piping between Fire-Department Connections and Check Valves: Galvanized, standard-weight steel pipe with grooved ends; grooved-end fittings; grooved-end-pipe couplings; and grooved joints. B. Sprinkler specialty fittings may be used, downstream of control valves, instead of specified fittings. C. Standard-pressure, wet-pipe sprinkler system, NPS 2 and smaller, shall be the 1. Standard-weight, Schedule 40, black-steel pipe with threaded ends; uncoated, gray-iron threaded fittings; and threaded joints. Use galvanized pipe where exposed to exterior. D. Standard-pressure, wet-pipe sprinkler system, NPS 2-1/2 and larger shall be the 1. Standard-weight, Schedule 10, black-steel pipe with roll-grooved ends; uncoated, grooved-end fittings for steel piping; grooved-end-pipe couplings for steel piping; and grooved joints. 3.15 SPRINKLER SCHEDULE A. Use sprinkler types in subparagraphs below for the following applications: 1. Rooms without Ceilings: Upright sprinklers. 2. Rooms with Suspended Ceilings: Semi-recessed pendent. 3. Wall Mounting: Sidewall sprinklers. 4. Spaces Subject to Freezing: Upright, pendent, dry sprinklers; and sidewall, dry sprinklers as indicated. B. Provide sprinkler types in subparagraphs below with finishes indicated. 1. Recessed Sprinklers: Bright chrome, with bright chrome escutcheon. Coordinate sprinkler finish with surrounding architectural finishes. 2. Upright, Pendent, and Sidewall Sprinklers: Chrome plated in finished spaces exposed to view; rough bronze in unfinished spaces not exposed to view; wax coated where exposed to acids, chemicals, or other corrosive fumes. Coordinate sprinkler finish with surrounding architectural finishes. END OF SECTION 211313 WET-PIPE SPRINKLER SYSTEMS 211313-22