Electrical Energy department

Similar documents
Lecture 4 Power System Protection. Course map

1S25. Arc Fault Monitor 4 Zones, 8 Sensors. Features. Introduction. ARC Fault Protection

7XG3120 ReyArc20 Arc Fault Monitor Relay Energy Management

Power System Protection Part 2 Dr.Prof. Mohammed Tawfeeq. Zones of Protection

Distribution Control Center Operator Training

Contents. Preface. Chapter 2 Faults, types and effects The development of simple distribution systems Faults-types and their effects 7

Three Terminal 230kV System Protection and Restoration at Calpine s Creed and Goose Haven Energy Centers Suisun City, California

PGR-8800 TECHNICAL FAQ

TRANSMISSION ENGINEERING STANDARDS SUBSTATIONS

Ground Fault Protection Improvement Study

Microgrid Fault Protection Based on Symmetrical and Differential Current Components

SEL Arc-Flash Solutions

Major Fault Caused by Stator Winding Circuit Ring Failure

SEL Arc-Flash Solutions

CONTACTORS FOR AEROSPACE GROW SMARTER AND MORE CAPABLE

17 TH APRIL 2017 Switch Board Monitoring Protecting Switchboard. Courtesy of ABB. Paul Lee

Electrical Safety Through Design. Mersen EP formerly Ferraz Shawmut

Standard PRC 004 5(i) Protection System Misoperation Identification and Correction

SECTION AUTOMATIC TRANSFER SWITCHES

TRANSMISSION ENGINEERING STANDARDS SUBSTATIONS

Monitoring Devices 11/1

Standard PRC Protection System Misoperation Identification and Correction

Standard PRC Protection System Misoperation Identification and Correction

SDG&E Feeder Protection Philosophy:

SECTION AUTOMATIC TRANSFER SWITCHES

CIRCUIT BREAKER FAIL PROTECTION

Operation and use. Functions and characteristics

Transmission Line Protection End to End Testing

MAINTENANCE OF LV SWITCHGEAR SECTOR / ENGINEERING TECHNICAL & CERTIFIED TRAINING COURSE

UC700 EMERGENCY TRANSFER SYSTEM SPECIFIER S HANDBOOK. 40 Dale Street West Babylon, NY Ph: Fx:

Guide Specification Model CTG Automatic Transfer Switch

Current transformers. Overview standardization. CIGRE B5 Workshop Stroomtransformatoren 26 Januari 2011 Marc Achterkamp (KEMA TIC en lid NEC38)

SACE PR021/K SIGNALLING UNIT

NFPA 70E Arc Flash Considerations for MV Equipment. By: Dominik Pieniazek, P.E. HV Engineering, LLC

To: Honorable Public Utilities Board Submitted by: /s/ Douglas Draeger AGM Engineering and Operations

Electrical. Bi-Metallic Thermal Cutouts. Linear Thermal Cutouts

VACUUM BREAKER MEDIUM VOLTAGE AUTOMATIC TRANSFER SWITCHES

TYPE APPROVAL CERTIFICATE

Welcome to Hager Presentation

M2500 Engine Controller Installation Manual

Brown University Revised June 29, 2012 Facilities Design & Construction Standards SECTION ELECTRICAL DESIGN CRITERIA

ITC 2000 HEATING CONTROL CABINET. Installation & Operation Manual

Fault Indicators for the Safe, Reliable, and Economical Operation of Modern Power Systems

Construction Electrical

Machinery Room Electrical Best Practices

Figure 30: Sample Case 8

Standard PRC Transmission Relay Loadability

CHAPTER 20 SERVICE EQUIPMENT

38-SDMS-04 REV. 0 SPECIFICATION FOR ANNUNCIATOR SYSTEMS FOR PRIMARY DISTRIBUTION SUBSTATION

National Grid / DG Installation Process Guide per NY SIR / July 2011 ver. 1.0

Powerohm Resistors Digital HRG System

1S20 User Guide. Arc Fault Monitor. Advanced Protection Devices. relay monitoring systems pty ltd. User Guide. Test Manual

3.4 SPINDLE AMPLIFIER MODULE

OPERATING INSTRUCTIONS COP-IE, COP-I, COP-E (ANSI 50,51,50N,51N)

Applications and Discussions of Arc Flash Protection Relay as a Main Busbar Protection in MV Switchboards

A. Section includes distribution panelboards and lighting and appliance branch-circuit panelboards.

TYPE APPROVAL CERTIFICATE

Flame Safeguards LFE10. Building Technologies HVAC Products

Residual Current Devices

PDD-8PCI. Power Distribution Board With Supervised Interface. Installation and Specifications Manual

Palak Parikh, Lalit Lopez GE Digital Energy. Acknowledgment: Scottish and Southern Energy(SSE)

Ground Fault Protection Improvements to Prevent Fires Description of problem and potential solutions Presented by Bill Brooks, PE Principal, Brooks

Student Services & Classroom Addition. A. Section includes distribution panelboards and lighting and appliance branch-circuit panelboards.

VAMP 120 & 121. Arc flash detection units. Product picture

PMAC202 Branch Circuit Power Meter User Manual V1.0

REA 105 Arc Protection Module. Operator s Manual

VAmP 120. Arc Flash Protection Units. Arc Protection. Customer benefits

EARTH LEAKAGE RELAY. User Manual - Issue 1.0

Measuring and Monitoring Relays Application Guide

NORTHWESTERN UNIVERSITY PROJECT NAME JOB # ISSUED: 11/06/2018

Flame Safeguards LFE10. Building Technologies HVAC Products

ELECTRICAL SAFETY IN HEALTHCARE FACITILIES

Table of Contents. Protective Relays

A. Introduction 1. Title: Transmission and Generation Protection System Maintenance and Testing

PRC-005. Tips and Updates. February 25th, Jonathan Hayes

SECTION P01 LIGHTING AND APPLIANCE PANELBOARDS - A-SERIES

RCMA423-DM RCMA423-DM1C RCMA423-DM2C RCMA423-DM3C. Operating Manual

SECTION ISOLATED POWER SYSTEMS

NATIONAL ELECTRICAL CODE (NEC) & NFPA 70E ARC FLASH ELECTRICAL SAFETY

Engineered Solutions SYSTEMS CUSTOM ENGINEERED TO YOUR SPECIFICATIONS. Fused Coordination Panelboards...ES 2. Fusible Shunt Trip Switch..

Operating Manual RCM420

FireNET Plus Wiring Instructions

Appendix B. FRCC regional application of the term transmission Protection Systems

Arc Fault Protection System D1000

D1000 Arc-fault Protection System

Heatrix Electric Duct Heater HXOB Installation Instructions

RD:30 Specification No. TI/SPC/PSI/AUTOTR/0090 For 50U5/150 MVA, 220/132 kv Auto Transformer

SENTINEL D - Fault Passage Monitoring

JW SERIES. Three Phase Thyristor Regulator PSE-351

SECTION DIGITAL, ADDRESSABLE FIRE-ALARM SYSTEM

CMD420 / CMD421 Series

Arc Fault Detection Devices (AFDDs) Protecting People and Property

IEEE Transformer Committee PC Distribution Transformer Monitoring - User

WIRING DIAGRAMS R410A MODELS PAC 2OAC/2OACH CAC OWC PWC

Part 3 Troubleshooting

Line Isolation Monitor (LIM) LIM2000plus

FACILITY CONNECTION STANDARD

VAMP 120 & 121. Arc Flash Protection Units. Arc Protection. Customer benefits

Products and Portfolio 01 Relay Panels Control Panels Special Panels

National Electrical Code

Transcription:

Al-Balqa Applied University Power systems Protection course Dr Audih al-faoury Electrical Energy department 2018-2019 Department of Electrical Energy Engineering 1

Part 1 Power System protection Introduction Dr Audih alfaoury 2

Power System protection Introduction:- Protection is the art or science of continuously monitoring the power system, detecting the faults and abnormal operation and correct tripping of CB,s. The objectives of power system protection are to : 1.Limit the extent and duration of service interruption thought the protection zone. 2.Minimize damage to the system components Protection engineering concerned with the design and operation of "protection schemes. Protection schemes monitoring the power system, detecting faults or abnormal conditions and initiate correct action. Main idea is to remove faults as quickly as possible while leaving as much of the system intact as possible. 3

Fault sequence of events 1. Fault occurs somewhere on the system, changing the system currents and voltages parameters. 2. Current transformers (CTs) and potential transformers (PTs) sensors detect the change in currents/voltages 3. Relays use sensor input to determine whether a fault has occurred. 4. If fault occurs relays open circuit breakers to isolated the fault. 4

Protection systems must be designed with : primary protection and Backup protection In designing power system protection there are two main types of systems that need to be considered: 1. Radial: this is the easiest from a protection. Radial power system protection systems usually use inverse-time overcurrent relays. 2. Ring : power can flow in both direction, Protection is considered the Secondary systems in a Power systems 5

Protection against faults and abnormalities Types of Faults and Abnormalities a) Faults : The principal electrical system faults are: short circuits and overloads. Short circuits: failure of insulation, mechanical damage to electrical distribution equipment, failure of equipment as a result of overloading or other. Short circuits may occur between two-phase, all phases, one or more phase conductors and ground, open circuit or inter-turn faults in windings The short circuit may be solid or has relatively low impedance. 6

7

b) Abnormalities: Under and over frequency. Power swings. Overload and over temperature. Overvoltage or under voltage. Under excitation of synchronous machines. Over fluxing of power transformers. Asynchronous operation of synchronous machines. Mechanical defects i.e. leaking oil, tap changer mechanism faults etc Typical Short-Circuit Type Distribution Single-Phase-Ground: 70-80 % Phase-Phase-Ground: 17-10 % Phase-Phase: 10-8 % Three-Phase: 3-2 % 8

Causes of Short-Circuit Faults: Insulation breakdown, Birds and animals,diggers for underground cables, poles collapsing, conductors breaking, vehicle impact,wind effect,incorrect operation by personnel..and so. Effects of Short-Circuit Type Faults 1) Large current can be involved. This cause equipment and generators would be damaged. Only be allowed to flow for a very short time as 10ms up to say 3 seconds. 2) Arcs, sparking and the heating effect can start fires 3) large mechanical forces which have potential to break or damage equipment. 4) Electric current linkage flow through paths where they could create a hazard to people 9

Planning system protection minimize the effects of faults and abnormalities occurring on the system. a) Quickly isolate faulted zone. b) Minimize the magnitude of short-circuit current and, minimize potential damage to the system. c) Provide alternate circuits, automatic transfers, or automatic reclosing devices, in order to minimize the duration outages. Performance Requirements of Protection System Discriminate between normal and abnormal conditions. Selectivity by coordinate with other protection systems. Fast enough to prevent damage and hazards - but not too fast. 10

No unprotected zones "blind spots.. High degree of reliability and availability. Secure against incorrect operation Should be easy to operate. What Info is Required to Apply Protection One-line diagram,impedances and connections of power system, system frequency, voltage level and phase sequence, existing schemes,maximum allowed clearance times,system fault studies, maximum load and system swing limits,cts and VTs locations, connections and ratios, future expansion and any special considerations for application 11

Basic Protection Scheme Components The primary protective equipment components are shown in the following figure: PR CB Equip CT VT DC Aux HMI PCL Tr Protection Relay Circuit Breaker Protected Item Current Transformer Voltage Transformer DC Auxiliary supply Man-machine interface Communications Link CB trip coil Mainly protection need are circuit breakers, and protective relays and transducers (CT and VT) 12