La Marche Manufacturing Company Option 16 Series. Digital Combined Accessory Package. Installation and Operation Manual

Similar documents
La Marche Manufacturing Company Option 46 Series. Digital Combined Accessory Package. Installation and Operation Manual

TPSD. Installation and Operation Manual. Filtered Battery Charger Power Supply / Battery Eliminator

A77 Series. Microprocessor Controlled SCR Filtered/Battery Eliminator Filtered Charger. Installation and Operation Manual

La Marche Manufacturing Company A36D. Battery Charger / Power Supply. Installation and Operation Manual

Setup Instructions. This manual is only valid for A36D/TPSD Chargers. equipped with a 341S control card with P341S0012 or P341S0013 software

A36D/TPSD Modbus RTU (Serial) SCADA INTERFACE INSTRUCTIONS

Revision: None DCN No. First Issue Date: November 30, 1998 Product: Standard DCT, 120-volts

A77 SNMPv1 SCADA INTERFACE INSTRUCTIONS

F PC and AO OUTPUT BOARDS INSTRUCTION MANUAL. Blue-White. Industries, Ltd.

A36D/TPSD Modbus TCP SCADA INTERFACE INSTRUCTIONS

1 Description. 2 Specifications. HP600ULM Access Control Power Supply/Charger with Power Distribution Controller PN 52393:A 1/05/06 ECN

A77 SNMPv3 SCADA INTERFACE INSTRUCTIONS

DIESEL ENGINE CONTROL UNIT DCU USER S MANUAL - N-2000 Lillestrøm, Norway Tel: (+47) Fax: (+47)

Installation and Operation Manual

AL400ULACM AL600ULACM - 4 amp - 12VDC or 6 amp. - Fused Outputs - Fused Outputs

Installation, Operating and Maintenance Manual

PNC 1000 SERIES 2, 4, 8 Zone Fire Alarm Control Panel

Analox 1000 Series. User Manual. Analox Sensor Technology Ltd. 15 Ellerbeck Court, Stokesley Business Park North Yorkshire, TS9 5PT, UK

Carbon Monoxide Transmitter

Commercial and Light Industrial Fire Alarm Control Panel

FireSystem 2000 Commercial and Light Industrial Fire Alarm Control Panel

Installation Guide for AL600ULM. Multi-Output Access Control Power Supply Charger. Rev

Multi-Output Access Control Power Supply Charger VDC or 24VDC VDC or 3 24VDC.

MADE IN THE U.S.A. ADVANCE FIRE CONTROL MODEL LM21-AFC MANUAL RELEASE DEVICES TEST WEEKLY TO ASSURE PROPER OPERATION OF RELEASE DEVICE/CONTROL PANEL

1200-HCM DIN RAIL MOUNTING FIRE SYSTEM MODULE Fire Detection & Extinguishant Control A R T PATOL LIMITED SUPPLY FAULT SOUNDER

Flopurge TS. Operation Manual

TECHNICAL DATA. Humidity: 85% Relative Humidity (non-condensing) at 90 F (32 C) maximum.

Product Manual SZ1145

MR-2602 Two Zone Fire Alarm Control Panel

SCR/SCRF SERIES. Industry s First Choice for Time-Tested Proven Reliability FLOAT BATTERY CHARGERS. Single-Phase Input

BS-316. Gas detection control panel up to 16 inputs. Installation operation manual

MPT Electric Fire Pump Controller

VE.NET GMDSS PANEL USER MANUAL INSTALLATION MANUAL

FDF Foam Pump Controllers Features

Application, Installation, Operation & Maintenance Manual

Float Battery Chargers Unfiltered SCR and Filtered SCRF Series Single Phase Input / Three Phase Input

Multi-Output Access Control Power Supply Chargers VDC or 24VDC VDC or 4 24VDC.

Securitron Magnalock Corporation S. 51 st St., Ste. 102 Phoenix, AZ Phone: (800) MAGLOCK

Flostop TS D7E and A8E. Operation Manual

Control/Communicator Installation Manual

OPERATION & MAINTENANCE MANUAL GUARDIAN SPACE PRESSURE MONITOR WITH REMOTE AUXILLARY ALARM

Installation Guide for AL300ULM. Multi-Output Access Control Power Supply Charger

MAINTENANCE & TROUBLESHOOTING GUIDE LEAK ALARM CHANNEL DRY OIL WATER AUX ALARM HIGH LOW CRITICAL WATER TANK LEVEL ALARM MODEL LDE-740 ADVANCE PAPER

HOKKIM INTEGRATED AMF CONTROL BOARD MANUAL FOR MODELS: HAMF-8 AND HAMF-4

THA2 TEMPERATURE/ HUMIDITY/ DEWPOINT ALARM WITH LOGGING CAPABILITY. 99 Washington Street Melrose, MA Phone Toll Free

Product Manual SZ1144

Analog Room Pressure Monitor RPC Series

Introduction. OM-THA2

ANALOX SENSOR TECHNOLOGY LTD ANALOX DD1101 INSTALLATION & OPERATION MANUAL

UltraLITE Model ELU Centralized Emergency Lighting Inverter 4.2 KW- 5 KW

FLOAT BATTERY CHARGERS

Addendum for STI-6406 with Dual Access Control

SERVICE INSTRUCTIONS FOR. Fire Alarm System MINI-2000

CommStat 6. Controller for Redundant HVAC Systems PRODUCT DATA SHEET

Public Safety DAS Annunciator Panel

SP-1000X. Panic Device Power Controller Installation Guide. Rev

Installation Guide for AL400ULM. Multi-Output Access Control Power Supply Charger

Models NFPA 1221-A, NFPA 1221-B Public Safety DAS Annunciator Panel. Revision E 61117

SCR/SCRF SERIES. Industry s First Choice for Time-Tested Proven Reliability FLOAT BATTERY CHARGERS. Single-Phase Input

MYRIAD TRIPLEX PUMP CONTROLLER INSTRUCTION MANUAL

Installation Guide for models:

Setup & Operation Index

AL800ULADA. NAC Power Extender. Installation Guide

PS6 SERIES. Installation PS6 SERIES. Power Supplies c/w Fire Panel Interface, EOL Trigger and Standby Power Option

Batt-Safe Battery String Monitoring System

Series. Access Power Controllers. Installation Guide

TT /97. Features INSTALLATION INSTRUCTIONS. Horn. Lamps

DS9400 Series. Release Notes for Firmware V2.07. Fire Alarm Control Panel

HA-263K HA-263D. OWNER'S MANUAL Installation And Operation 8-ZONE ALARM CONTROL PANEL FOR HOME AND OFFICE PROTECTIONS OPEN THE CABINET FOR SERVICE

Installation Guide for models:

STA16 SELECTRONIC ALARM ANNUNCIATORS DESIGN, INSTALLATION AND OPERATING MANUAL STA16

Installation and user manual for the CF5000, MF5000 and FXP5000 range of fire panels

INSTALLATION INSTRUCTIONS

Tempco PCT-3000 Series Temperature Control Console with Relay Output for Heating or Cooling Applications

AL600ULADA. NAC Power Extender. Installation Guide

CM-RQE70 PIR REQUEST TO EXIT DETECTOR

Pump Logic User Manual CB-1000 P/N ILK-CB1000-1

GasScanner 8C. Eight Channel Monitor. Operator s Manual. MINT-0281-XX Rev. A 01/29/08

Meridian wiredhart. HART Field Device Specification Goldmine Rd. Monroe, NC USA

ANALOX 3000 Carbon Monoxide Monitor

Gas Safety Products. Installation, operating and maintenance 11/18/2015. Merlin 1000S+ Gas Utility & Electrical Isolation Controller

MS-4012/4024 and CMS-4012/4024. Instruction Manual for the. Fire Alarm Control Panels

Installation Guide for AL800UL-ADA. NAC Power Extender. Rev

PRODUCT INSTRUCTIONS. Fire Door Control Panel (FDCP) Stock Code Description Doc No: PI-115. Ellard Fire Door Control Panel Ellard Slave Repeater Unit

NS (A) ECN

ModSync Sequencing System Installation & Operation Manual. For use with Fulton Steam Boilers.

DSGH. Radiation-Based Detector with GEN2000 Electronics for Density Measurement QUICK REFERENCE GUIDE

User s Manual. TIGER S EYE E-Series Mark V Jockey. TIGERFLOW Systems, Inc Mint Way Dallas, Texas

1 measurement signal input 4-20 ma for connection to an external gas sensor 5 freely programmable alarm switching points per measuring point

CM-RQE70A PIR REQUEST TO EXIT DETECTOR

Beacon 200 Gas Monitor Operator s Manual. Part Number: RK Released: 6/6/08

RELEASE DEVICE CONTROLS

MTRA-FSP Level Control Relay. Installation & Operation Manual

21-light Remote Annunciator. Owner s Manual

Motorised Infrared Optical Beam Smoke Detector. User Guide

FTEN1, FTEN2, & FTEN4 1, 2 & 4 ZONE FIRE DETECTION AND ALARM CONTROL PANELS

Instruction Manual Model A

Intelligent Security & Fire Ltd

ITC 2000 HEATING CONTROL CABINET. Installation & Operation Manual

Ammonia Leak Detector Manual

Transcription:

La Marche Manufacturing Company www.lamarchemfg.com Option 16 Series Digital Combined Accessory Package Installation and Operation Manual This manual is subject to change without notice. You may obtain the newest version of the manual at www.lamarchemfg.com 106 Bradrock Dr. Des Plaines, IL 60018-1967 CPN 102966 Instruction Drawing Number: P25-LOPT16SERIES-1 i Tel: 847-299-1188 Fax: 847-299-3061 Revision A07 Rev. Date: 03/17 ECN: 21360

1.0 Option 16 Series Operation 1.1 General Description The 16 series option includes the LED user-interface display panel which has eleven functional LED indicators on the front panel. One LED is used to indicate Equalize mode, one LED is to indicate AC voltage, five LEDs are used for various alarms, and four LEDs are used for display indications. The display also has a High Voltage Shutdown alarm reset push button and an Equalize/Select toggle switch. Figure 1A LED Display Showing System Output Voltage (while in Float mode) Toggling down on the Equalize/Select switch changes the display. The four green meter-select LEDs that are mounted horizontally on the bottom of the display indicate the display status. The following items can be displayed and have an LED indicator: DC Volts Displays the output DC voltage. DC Amps Displays the output DC amperage. Timer Mode Shows what Equalize timer mode the charger is currently set for. Figure 1B Display Diagram NOTE: In 16J, 16Q, 46T, and 46U option, the two LEDs will also be provided on the door as positive ground and negative ground alarm indicators. Refer to Figure 2. In 16P and 16T option, an audible alarm with silence switch will be provided on the front panel. Figure 2 Negative and Positive Ground LEDs (On Front Panel 16J/Q/T/U Option) EQ Time In Float mode, displays the set Equalize time. In Equalize mode, counts down from the Equalize set time. When the charger is in Equalize mode, the yellow Equalize LED will be on and the voltage will change to the set Equalize value. Refer to Figure 3A. Toggling down on the Equalize/Select switch until the green EQ TIME LED is on will change the display to indicate the Equalize timer countdown. Refer to Figure 3B. Figure 3A LED Display Showing System Output Voltage (while in Equalize Mode) Figure 3B LED Display Showing Equalize Timer Countdown 2

1.2 Selecting the Charging Mode The digital display used in the 16 Series has two modes for DC output voltage; Float mode and Equalize mode. Float charging mode is used for all normal battery charging needs. Equalize mode is used when it is necessary to Equalize (or balance) the level of charge across all cells present in the battery. One LED is used to indicate Equalize mode on the front panel. There is no Float LED indicator. If the charger is in Float mode, simply toggle up the Equalize/Select switch to change into Equalize mode. If the charger is in Equalize mode, it will automatically switch back to Float mode after the designated Equalize time cycle is complete; alternatively, the charger can be manually switched to Float mode by toggling the Equalize/Select switch. 2.0 Alarms The available alarms for the 16 Series are: Low Voltage1, Low Voltage2, End of Discharge, High Voltage, Low Current, High Voltage Shutdown, Positive Ground, Negative Ground, AC Power Failure, and Summary. The corresponding alarm LED will illuminate when an alarm is triggered, if applicable. Figures 4A 4E illustrate the alarm relays provided on the 198 relay board. Each set of alarm relays have two sets of form C contacts which function identical to each other. Not all alarm relays function the same; refer to Table 1 for the logic of each relay. Figure 4A (16J/T Option) Figure 4B (16E/G/P Option) Figure 4C (16L Option) S2A-198 Relay Information Relay Function High DC Voltage Shutdown Low DC Current High DC Voltage Low DC Voltage 1/ Low DC Voltage 2 (End of Discharge) AC Power Failure Summary Positive Ground Negative Ground Logic Energize On Fail De-Energize On Fail Energize On Fail De-Energize On Fail De-Energize On Fail De-Energize On Fail Energize On Fail Energize On Fail Figure 4D (16Q Option) Figure 4E (16U Option) NOTE: See schematic or manual cover page to determine which alarm option is included. Table 1 3

2.1 Alarm Contact Specifications Load Resistive Load (P.F. = 1) Contact Material Maximum Allowed Current Max. Operating Voltage and Current Max. Switching Capacity Min. Permissible Load Ag (Au clad) 2 A 0.5 A at 125 VAC 0.25 A at 125 VDC 2 A at 30 VDC 62.50 VA 60 W 10 ua, 10 mvdc Table 2 2.2 Alarm Definitions AC POWER FAILURE ALARM will trigger and the green AC ON LED will turn off if the AC power to the charger is lost for longer than 5 seconds. There is no AC Power Failure LED, only alarm contacts. The alarm will automatically reset when AC power is restored to the charger. When AC power is lost, the front panel display and indicators will remain powered by the connected batteries. LOW DCV1 ALARM will trigger and the red LOW DCV1 LED will turn on if the DC voltage falls below the specified voltage threshold of the alarm for longer than 5 seconds. The alarm will clear once the low DC voltage condition is no longer present. LOW DCV2 / END OF DISCHARGE ALARM will trigger and the red LOW DCV2 LED will turn on if the DC voltage falls below the specified voltage threshold of the alarm for longer than 5 seconds. The alarm will clear once the low DC voltage condition is no longer present. Some options will define this as an End of Discharge Alarm with a different threshold. HIGH DC VOLTAGE SHUTDOWN ALARM will trigger and the red HI V SHUT DOWN LED will turn on if the output DC voltage of the charger rises above the alarm threshold for longer than 20 seconds and there is load on the charger. If the high DC voltage shutdown alarm activates, the DC output of the charger shuts off to prevent irreversible damage to the battery. This alarm will stay latched until the charger is reset by isolating from all power sources or pushing the reset button. NOTE: This alarm will not trigger if there is a Low Current alarm present. HIGH DC VOLTAGE ALARM will trigger and the red HI V LED will turn on if the output DC voltage rises above the specified voltage threshold of the alarm for longer than 5 seconds. The alarm will clear once the high DC voltage condition is no longer present. LOW DC CURRENT ALARM will trigger and the red LO A LED will turn on if the output DC current of the charger falls below the alarm threshold for longer than 5 seconds. This alarm can be disabled if considered a nuisance alarm. SUMMARY ALARM will default trigger if any of the other alarms are triggered. There is no Summary alarm LED, only alarm contacts. The Low Current, AC Power Failure, and Ground Detection alarms can be removed from the Summary alarm, but are included by default. POSITIVE GROUND ALARM will trigger and the green POSITIVE GROUND LED will turn on if 1.2mA or greater current is measured between the positive terminal of the battery and earth ground for longer than 5 seconds. This LED is found on a separate circuit board. The alarm will clear once the positive ground fault is no longer present. NEGATIVE GROUND ALARM will trigger and the green NEGATIVE GROUND LED will turn on if 1.2mA or greater current is measured between the negative terminal of the battery and earth ground for longer than 5 seconds. This LED is found on a separate circuit board. The alarm will clear once the negative ground fault is no longer present. 4

Alarm Delay (sec.) Summary Selectable Clearing Threshold Alarming Threshold (V/C) LED Indication AC Power Failure 5 Yes - - - Low Voltage 1 5 No 5% 1.975 LA / 1.2 NC LO DCV1 Low Voltage 2 5 No End of Discharge 5 No 5% (shown DCV) 5% (shown DCV) 1.975 LA / 1.2 NC LO DCV2 1.75 LA / 1.1 NC LO DCV2 High Voltage 5 No - 2.45 LA / 1.61 NC HI V High Voltage Shut Down 20 No - 2.5 LA / 1.65 NC HI V SHUTDOWN Low Current 5 Yes * * LO A Summary 5 - - Other Alarms - Positive Ground 5 Yes - - POSITIVE GROUND Negative Ground 5 Yes - - NEGATIVE GROUND Table 3 Alarm Default Values and Indications * Low Current alarming threshold is dependent on shunt size V/C Volts per Cell, LA Lead Acid, NC Nickel Cadmium NOTE: These recommended parameters are set as factory default settings. If required, change the alarm threshold levels after verifying with battery manufacturer. 2.3 Alarm Connection Procedure Before making any alarm connections, ensure that the AC power is off at the main breaker. Verify that no voltage is present by using a voltmeter at all AC and DC terminals. For relays mentioned as ENERGIZED on alarm condition: If it is desired that the annunciator be active until the alarm triggers, connect the annunciator leads to the NC and C contacts of the desired alarm (located on the relay alarm contacts on S2A-198 board). If it is desired that the annunciator be deactivated until the alarm triggers, connect the annunciator leads to the NO and C contacts of the desired alarm. For relays mentioned as DE-ENERGIZED on alarm condition: If it is desired that the annunciator be active until the alarm triggers, connect the annunciator leads to the NO and C contacts of the desired alarm (located on the relay alarm contacts on S2A-198 board). If it is desired that the annunciator be deactivated until the alarm triggers, connect the annunciator leads to the NC and C contacts of the desired alarm. 5

3.0 Adjusting Parameters All equipment is shipped from the factory fully checked and adjusted based on the model number. Do not make any adjustments unless the equipment has been powered-up and the settings have been determined to be incorrect. If the settings have been determined to be incorrect, adjustments may be made as detailed below. 3.1 Customer Calibration Mode In Customer Calibration Mode, the customer can access and change various parameters. To access the Customer Calibration Mode, hold the Equalize/Select toggle switch up towards Equalize for about 5 seconds. After CAL appears on the LED display, immediately release the toggle switch. The parameters will automatically cycle every 5 seconds if no change is made. Once in calibration mode, the customer can raise and lower values with the same toggle switch. After the last setting is passed, the settings will automatically be saved. If a setting is accidentally passed over, the customer can press the reset push button and restart calibration from the beginning. The calibration settings are listed in order below with a brief description and default values. NOTE: Some chargers could have additional settings included in the Customer Calibration menu; contact La Marche for further explanation of settings not mentioned below. The Customer Calibration menu is as follows: Low Voltage 1 Alarm This setting changes the voltage threshold that causes the Low DC Voltage Alarm to activate. The default setting is 1.98 V/C (for Lead Acid batteries), based on the number of battery cells that the charger was designed for. The number and type of cells is listed on the charger s nameplate. (EX: A charger designed for 24L has a default Low Voltage alarm setting of 47.5VDC) Low Voltage 2 Alarm This setting changes the voltage threshold that causes the Battery End of Discharge Alarm to activate. The default setting is 1.75 V/C (for Lead Acid batteries), based on the number of battery cells that the charger was designed for. The number and type of cells is listed on the charger s nameplate. (EX: A charger designed for 24L has a default Battery End of Discharge alarm setting of 42VDC) EQ Timer Mode This setting changes the mode of the Equalize Timer. The Equalize timer mode determines when the charger will go into an Equalize charging cycle. The timer modes are Mode 0 (P0), Mode 1 (P1), Mode 2 (P2), Mode 3 (P3), and Mode 4 (P4). The default setting for the Equalize timer mode is Mode 0 (P0). The Equalize Timer Modes are discussed in further detail in Section 3.2. EQ Timer Setting This setting changes the amount of time that the charger remains in the Equalize charging cycle once activated. When an Equalize cycle is started, the charger will remain in Equalize mode until the time selected by this setting has passed. By default, the Equalize timer is set for 8 hours. The battery manufacturer documentation should be referenced for battery specific settings. High Voltage Shutdown Alarm This setting changes the voltage threshold that causes the High Voltage Shutdown Alarm to activate. The default setting is 2.50 V/C (for Lead Acid batteries), based on the number of battery cells that the charger was designed for. The number and type of cells is listed on the charger s nameplate. (EX: A charger designed for 24L has a default High Voltage Shutdown alarm setting of 60VDC) High Voltage Alarm This setting changes the voltage threshold that causes the High Voltage Alarm to activate. The default setting is 2.45 V/C (for Lead Acid batteries), based on the number of battery cells that the charger was designed for. The number and type of cells is listed on the charger s nameplate. (EX: A charger designed for 24L has a default High Voltage alarm setting of 58.8VDC) Low DC Current Alarm This setting changes the current threshold that causes the Low DC Current Alarm to activate. The default setting is dependant on the shunt size of the charger. This alarm can be disabled if considered a nuisance alarm by lowering the threshold value to OFF. 6

3.2 Equalize Timer Modes The 16 Series offers five different modes of Equalize charging operation. The Equalize mode can be viewed on the charger display by toggling the Equalize/Select switch until the green Timer Mode LED turns on. The Equalize mode can be changed via the Customer Calibration menu, refer to section 3.1. In all of the Equalize modes below, the charger will return to Float mode if the Equalize/Select toggle switch is toggled up or when it completes its full charge time. Mode 0 (Displayed As P0 ) Mode 0 is a manual Equalize cycle and is the default setting for the charger. When the charger is set for Mode 0, the Equalize cycle must be activated manually. Once activated, the Equalize timer will turn on and the Equalize "LED" will light. The length of the timer is eight hours by default and can be changed via Customer Calibration. After the timer cycles to zero, the charger will immediately return to Float mode. Equalize mode will not start again until it is manually activated by the user. Mode 1 (Displayed As P1 ) Mode 1 is an automatic Equalize cycle that activates every 7 days. The length of the Equalize cycle is determined by the timer setting. The length of the timer is eight hours by default and can be changed via Customer Calibration. When the Equalize timer expires, the charger will immediately return to Float mode. Equalize mode will restart again after 7 days. Mode 2 (Displayed As P2 ) Mode 2 is an automatic Equalize cycle that activates every 14 days. The length of the Equalize cycle is determined by the timer setting. The length of the timer is eight hours by default and can be changed via Customer Calibration. When the Equalize timer expires, the charger will immediately return to Float mode. Equalize mode will restart again after 14 days. Mode 3 (Displayed As P3 ) Mode 3 is an automatic Equalize cycle that activates every 30 days. The length of the Equalize cycle is determined by the timer setting. The length of the timer is eight hours by default and can be changed via Customer Calibration. When the Equalize timer expires, the charger will immediately return to Float mode. Equalize mode will restart again after 30 days. Mode 4 (Displayed As P4 ) Mode P4 is an automatic Equalize cycle that is triggered when the battery experiences a sizeable discharge. When the DC voltage drops below the Low Voltage alarm threshold, and exceeds the Low Voltage alarm time delay, Mode 4 is activated. However, the Equalize timer will only start and run the charger in Equalize mode for the duration set in the Equalize menu after the charger has raised the battery voltage high enough to clear the Low Voltage alarm. When the Equalize timer expires, the charger will immediately return to Float mode. 7

4.0 Display Calibration In order to calibrate the display voltage and current to match the measured values, two small potentiometers are provided, located on the bottom of the 225A display board. P1 potentiometer is used to calibrate the display voltage and P2 potentiometer is used to calibrate the display current. Please refer to figure 5. NOTE: Adjusting the potentiometers mentioned will NOT change the output of the charger; only the display values will be changed. P1 (VCAL) Display Voltage Adjustment P2 (LCAL) Display Current Adjustment Figure 5 Display Calibration 8

Document Control and Revision History Part Number: 102966 Instruction Number: P25-LOPT16SERIES-1 Issue ECN: 14370 04/01 21360 03/17 20737 02/15 16600 12/04 16064 07/03 15382 05/02 15339 04/02 14767 07/01 9