University of Missouri St. Louis September 9, 2013 Recreation and Wellness Center #S

Similar documents
A. This Section includes the following fire-suppression piping inside the building:

WET-PIPE SPRINKLER SYSTEMS

B. Related Sections: The following Sections contain requirements that relate to this Section.

THE JAMES RUSHTON EARLY LEARNING AND FAMILY SUCCESS CENTER #2616 ISSUE FOR CONSTRUCTION

North Hanover Township School District North Hanover Township, New Jersey

SECTION FIRE-SUPPRESSION PIPING

B. Standard-Pressure Standpipe Piping: Fire-suppression standpipe piping designed to operate at working pressure 175 psig (1200 kpa) maximum.

CubeSmart Gulf Breeze Storage AUTOMATIC FIRE SPRINKLER SYSTEM

MASTERSPEC TECHNICAL SPECIFICATIONS DIVISION 21 FIRE SUPPRESSION

ADDENDUM #3 DATE: August 8, 2018 Page 1 of 1. The Curators of the University of Missouri

A. Standard-Pressure Piping System Component: Listed for 175-psig minimum working pressure.

UNIVERSITY SERVICES ANNEX James Madison University Harrisonburg, Virginia State Project Code: Architect s Project Number:

SECTION DRY-PIPE SPRINKLER SYSTEMS

SPRINKLERS TABLE OF CONTENTS

SECTION DRY-PIPE SPRINKLER SYSTEMS

SECTION FIRE-SUPPRESSION SYSTEMS

B. Galvanized-Steel-Sheet Sleeves: inch minimum thickness; round tube closed with welded longitudinal joint.

SECTION WET-PIPE SPRINKLER SYSTEMS

SECTION WET-PIPE SPRINKLER SYSTEMS

DIVISION 21 FIRE PROTECTION ISSUE DATE REVISION

B. Product Data: Provide manufacturers catalogue information. Indicate valve data and ratings.

SECTION PREACTION SPRINKLER SYSTEMS

Facility Fire-Suppression Water-Service Piping

C. All components of the systems described shall meet the requirements as stated herein and shall be approved by the Architect and Consultant.

MASTERSPEC TECHNICAL SPECIFICATIONS DIVISION 21 FIRE SUPPRESSION

SECTION SPRINKLER SYSTEMS

SECTION FIRE PROTECTION. A. Examine all conditions as they exist at the project, prior to submitting a bid for the work of this section

Council Bluffs, Iowa Division TOC 1 TABLE OF CONTENTS DIVISION 21 FIRE SUPPRESSION

SECTION SPRINKLER SYSTEMS

NORTHWESTERN UNIVERSITY PROJECT NAME JOB # ISSUED: 03/29/2017

FIRE PROTECTION. 1. Vertical fire pumps shall not be used at the University.

1.1 Refer to Section for General Mechanical Requirements. 1.3 Refer to Section for Pipe and Equipment Identification Requirements.

NORTHWESTERN UNIVERSITY PROJECT NAME JOB # ISSUED: 03/29/2017

ADDENDUM NO. 3 March 19, 2018

West District Library Section Campeau Drive, Ottawa SPRINKLER SYSTEMS City of Ottawa Project No. CR Page 1 of 8

Gas Station & C Store SECTION CWM Job No

DARTMOUTH COLLEGE DESIGN November 15, 2007 & CONSTRUCTION GUIDELINES

SECTION SLEEVES AND SLEEVE SEALS FOR FIRE-SUPPRESSION PIPING

1.2 CODES AND REGULATIONS A. Sprinkler system design, equipment, materials, devices, and installation shall conform to the following:

MLA Architects Pierz Public Schools ISD #484 Healy High School Multi-Purpose & Choir Additions Pioneer Elementary School Class Room Addition Pierz, MN

Addendum No. 2 to the Contract Documents

A. Section includes wet-pipe sprinkler system, system design, installation, and certification.

SECTION WET-PIPE SPRINKLER SYSTEMS

TABLE OF CONTENTS DIVISION 21- FIRE SUPPRESSION PAGES SECTION WATER BASED FIRE PROTECTION SYSTEMS... 5

DIVISION 21 - FIRE SUPPRESSION

SECTION FIRE PROTECTION

SECTION WET PIPE FIRE PROTECTION SPRINKLER SYSTEM

Essex County College - West Essex Campus Addition And Renovations dlb # / 11-14

FIRE SUPPRESSION SPRINKLER SYSTEM

SECTION WET-PIPE SPRINKLER SYSTEMS EASY RISER CHECK VALVE

DIVISION 21 - FIRE SUPPRESSION

DIVISION 21 FIRE SUPPRESSION SECTION FIRE PROTECTION SPECIALTIES

SECTION COMMON WORK RESULTS FOR FIRE SUPPRESSION

Copyright 2016 AIA MasterSpec Full Length 09/16 PRODUCT MASTERSPEC LICENSED BY AVITRU, LLC TO VICTAULIC COMPANY.

SECTION WET-PIPE FIRE-SUPPRESSION SPRINKLERS

DIVISION 21: FIRE SUPPRESSION WATER BASED FIRE SUPRESSION SYSTEMS

University of Houston Master Construction Specifications Insert Project Name SECTION DRY-PIPE FIRE SPRINKLER SYSTEM PART 1 - GENERAL

SECTION AUTOMATIC SPRINKLER PIPING

SECTION DRY PIPE SPRINKLER SYSTEMS MODEL F SERIES DRY VALVE

Mercy Hospital of Buffalo Catholic Health System 2 nd Floor Patient Holding Center 3 rd Floor Locker Rooms Shaflucas Architects, PC Project No.

SECTION DRY PIPE SPRINKLER SYSTEMS MODEL G SERIES DRY VALVE

B. The sprinkler system shall be designed to meet the more stringent of the requirements of NFPA 13 and FM Global requirements.

SECTION FIRE SUPPRESSION SYSTEMS

Copyright 2016 AIA MasterSpec Full Length 09/16 PRODUCT MASTERSPEC LICENSED BY AVITRU, LLC TO VICTAULIC COMPANY.

Wayne State University WSU Project No Chatsworth Tower Apts. Misc. Bldg. Upgrades DSD Project No

COBB COUNTY SCHOOLS /S&A % BID DOCUMENTS 2/18/11 SECTION SPRINKLER SYSTEM

END OF SECTION

SECTION DRY-PIPE FIRE-SUPPRESSION SPRINKLERS

SECTION WET-PIPE FIRE SUPPRESSION SPRINKLERS

A. Hydraulic calculations shall be prepared in accordance with Chapter 23 of NFPA 13 with the following exceptions:

A. This section includes design and performance information for fire protection and suppression systems.

UC Santa Cruz Campus Design Guide. Includes the following sections: None DESIGN REQUIREMENTS

ACADEMIC SUCCESS CENTER THE COLLEGE AT BROCKPORT STATE UNIVERSITY OF NEW YORK PROJECT NO

SECTION FIRE-SUPPRESSION STANDPIPES

B. Utility-furnished products include water meters that will be furnished to the site, ready for installation.

Mercury Plastics New Building February TABLE OF CONTENTS

TECHNICAL SPECIFICATIONS SECTION DRY PIPE SPRINKLER SYSTEM PLAISTOW PUBLIC LIBRARY 85 MAIN STREET PLAISTOW, NEW HAMPSHIRE 100%CD.

B. Section Identification for Fire Suppression Piping and Equipment.

Port of St Helens SIA Aircraft Hanger Scappoose, OR

1.02 SUMMARY A. This Section includes piping and specialties for combined potable-water and fire-protection water service outside the building.

PROJ. NO SECTION REFRIGERANT PIPING

SECTION FAN COIL UNITS

2016 CDM Smith All Rights Reserved July 2016 SECTION FIRE PROTECTION - SPRINKLER AND STANDPIPE SYSTEMS

A. This Section includes the following domestic water piping specialties:

2. Welding Materials and Procedures shall conform to the ASME Code.

SECTION WET FIRE SPRINKLER SYSTEMS

DENVER PUBLIC SCHOOLS DESIGN AND CONSTRUCTION STANDARDS This Standard is for guidance only. SECTION PUMPS

SECTION HYDRONIC PIPING

PART 1 - GENERAL SECTION FIRE PROTECTION BASIC MATERIALS AND METHODS

SECTION (15530) - REFRIGERANT PIPING

B. Shop Drawings: Detail fabrication of pipe anchors, hangers, special pipe support assemblies, alignment guides, expansion joints and loops,

SECTION COMMON WORK RESULTS FOR FIRE SUPPRESSION

SECTION FIRE PROTECTION

A. All Fire Suppression System design and installation shall comply with the most current and adopted version of NFPA 13.

SECTION WET AUTOMATIC FIRE SPRINKLER SYSTEMS

Division 21: FIRE SUPRESSION WET-PIPE SPRINKLER PROTECTION SYSTEM. The Academy Sept Table of Contents 1 Division 21

. ECTION METERS AND GAGES

D-11 OUTLINE SPECIFICATION FOR HTHW (ABOVE GRADE) HYDRONIC PIPING

New Rigby Elementary School February TABLE OF CONTENTS

A. Operation and Maintenance Data: For pumps to include in emergency, operation, and maintenance manuals.

Transcription:

SECTION 210548 - VIBRATION AND SEISMIC CONTROLS FOR FIRE-SUPPRESSION PIPING AND EQUIPMENT PART 1 - GENERAL 1.1 SUMMARY A. This Section includes the following: 1. Isolation pads. 2. Isolation mounts. 3. Restrained elastomeric isolation mounts. 4. Restraining braces. 1.2 DEFINITIONS A. IBC: International Building Code. B. ICC-ES: ICC-Evaluation Service. 1.3 PERFORMANCE REQUIREMENTS A. Seismic-Restraint Loading: 1. Site Class as Defined in the IBC: C. 2. Assigned Seismic Use Group or Building Category as Defined in the IBC: II. a. Component Importance Factor: 1.5. 3. Design Spectral Response Acceleration at Short Periods (0.2 Second): 0.426. 4. Design Spectral Response Acceleration at 1-Second Period: 0.1. 5. Comply with ASCE Manual 7-2010 and NFPA 13. 1.4 SUBMITTALS A. General: Submit the following in accordance with Division 21 Section "Basic Division 21 Requirements." 1.5 ACTION SUBMITTALS A. Product Data: For the following: 1. Include rated load, rated deflection, and overload capacity for each vibration isolation device. 2. Illustrate and indicate style, material, strength, fastening provision, and finish for each type and size of seismic-restraint component used. VIBRATION AND SEISMIC CONTROLS FOR FIRE-SUPPRESSION PIPING AND EQUIPMENT 210548-1

a. Tabulate types and sizes of seismic restraints, complete with report numbers and rated strength in tension and shear as evaluated by a Testing Agency. b. Annotate to indicate application of each product submitted and compliance with requirements. B. Delegated Design Services: For vibration isolation and seismic-restraint details indicated to comply with performance requirements and design criteria, including analysis data signed and sealed by the qualified professional engineer responsible for their preparation. 1. Design Calculations: Calculate static and dynamic loading due to equipment weight and operation, seismic forces required to select vibration isolators, seismic restraints, and for designing vibration isolation bases. 2. Seismic-Restraint Details: a. Design Analysis: To support selection and arrangement of seismic restraints. Include calculations of combined tensile and shear loads. b. Details: Indicate fabrication and arrangement. Detail attachments of restraints to the restrained items and to the structure. Show attachment locations, methods, and spacings. Identify components, list their strengths, and indicate directions and values of forces transmitted to the structure during seismic events. Indicate association with vibration isolation devices. c. Preapproval and Evaluation Documentation: Showing maximum ratings of restraint items and the basis for approval (tests or calculations). 1.6 INFORMATIONAL SUBMITTALS A. Qualification Data:. 1. Installer a. Welding certificates. 2. Professional Engineer 3. Testing Agency 1.7 QUALITY ASSURANCE A. Testing Agency Qualifications: An independent agency, with the experience and capability to conduct the testing indicated, that is a nationally recognized testing laboratory (NRTL) as defined by OSHA in 29 CFR 1910.7. B. Comply with seismic-restraint requirements in the IBC and NFPA 13 unless requirements in this Section are more stringent. C. Welding: Qualify procedures and personnel according to AWS D1.1/D1.1M, "Structural Welding Code - Steel." D. Seismic-restraint devices shall have horizontal and vertical load testing and analysis and shall bear anchorage preapproval OPA number from OSHPD, preapproval by ICC-ES, or preapproval by another agency acceptable to authorities having jurisdiction, showing maximum seismic-restraint ratings. Ratings based on independent testing are preferred to ratings based on calculations. If preapproved ratings are not available, submittals based on independent VIBRATION AND SEISMIC CONTROLS FOR FIRE-SUPPRESSION PIPING AND EQUIPMENT 210548-2

testing are preferred. Calculations (including combining shear and tensile loads) to support seismic-restraint designs must be signed and sealed by a qualified professional engineer. PART 2 - PRODUCTS 2.1 VIBRATION ISOLATORS A. Manufacturers: Subject to compliance with requirements, provide products by one of the following: 1. Ace Mountings Co., Inc. 2. Amber/Booth Company, Inc. 3. California Dynamics Corporation. 4. Isolation Technology, Inc. 5. Kinetics Noise Control. 6. Mason Industries. 7. Vibration Eliminator Co., Inc. 8. Vibration Isolation. 9. Vibration Mountings & Controls, Inc. B. Pads: Arranged in single or multiple layers of sufficient stiffness for uniform loading over pad area, molded with a nonslip pattern and galvanized-steel baseplates, and factory cut to sizes that match requirements of supported equipment. 1. Resilient Material: Oil- and water-resistant neoprene. C. Mounts: Double-deflection type, with molded, oil-resistant rubber, hermetically sealed compressed fiberglass, or neoprene isolator elements with factory-drilled, encapsulated top plate for bolting to equipment and with baseplate for bolting to structure. Color-code or otherwise identify to indicate capacity range. 1. Materials: Cast-ductile-iron or welded steel housing containing two separate and opposing, oil-resistant rubber or neoprene elements that prevent central threaded element and attachment hardware from contacting the housing during normal operation. 2. Neoprene: Shock-absorbing materials compounded according to the standard for bridgebearing neoprene as defined by AASHTO. D. Restrained Mounts: All-directional mountings with seismic restraint. 1. Materials: Cast-ductile-iron or welded steel housing containing two separate and opposing, oil-resistant rubber or neoprene elements that prevent central threaded element and attachment hardware from contacting the housing during normal operation. 2. Neoprene: Shock-absorbing materials compounded according to the standard for bridgebearing neoprene as defined by AASHTO. 2.2 SEISMIC-RESTRAINT DEVICES A. Manufacturers: Subject to compliance with requirements, provide products by one of the following: 1. Amber/Booth Company, Inc. VIBRATION AND SEISMIC CONTROLS FOR FIRE-SUPPRESSION PIPING AND EQUIPMENT 210548-3

2. California Dynamics Corporation. 3. Cooper B-Line, Inc.; a division of Cooper Industries. 4. Hilti, Inc. 5. Kinetics Noise Control. 6. Loos & Co.; Cableware Division. 7. Mason Industries. 8. TOLCO Incorporated; a brand of NIBCO INC. 9. Unistrut; Tyco International, Ltd. B. General Requirements for Restraint Components: Rated strengths, features, and applications shall be as defined in reports by an agency acceptable to authorities having jurisdiction. 1. Structural Safety Factor: Allowable strength in tension, shear, and pullout force of components shall be at least four times the maximum seismic forces to which they will be subjected. C. Channel Support System: MFMA-3, shop- or field-fabricated support assembly made of slotted steel channels with accessories for attachment to braced component at one end and to building structure at the other end and other matching components and with corrosion-resistant coating; and rated in tension, compression, and torsion forces. D. Hanger Rod Stiffener: Steel tube or steel slotted-support-system sleeve with internally bolted connections to hanger rod. E. Bushings for Floor-Mounted Equipment Anchor Bolts: Neoprene bushings designed for rigid equipment mountings, and matched to type and size of anchor bolts and studs. F. Bushing Assemblies for Wall-Mounted Equipment Anchorage: Assemblies of neoprene elements and steel sleeves designed for rigid equipment mountings and matched to type and size of attachment devices used. G. Resilient Isolation Washers and Bushings: One-piece, molded, oil- and water-resistant neoprene, with a flat washer face. H. Mechanical Anchor Bolts: Drilled-in and stud-wedge or female-wedge type in zinc-coated steel for interior applications and stainless steel for exterior applications. Select anchor bolts with strength required for anchor and as tested according to ASTM E 488. Minimum length of eight times diameter. I. Adhesive Anchor Bolts: Drilled-in and capsule anchor system containing polyvinyl or urethane methacrylate-based resin and accelerator, or injected polymer or hybrid mortar adhesive. Provide anchor bolts and hardware with zinc-coated steel for interior applications and stainless steel for exterior applications. Select anchor bolts with strength required for anchor and as tested according to ASTM E 488. 2.3 FACTORY FINISHES A. Finish: Manufacturer's standard prime-coat finish ready for field painting. B. Finish: Manufacturer's standard paint applied to factory-assembled and -tested equipment before shipping. 1. Powder coating on springs and housings. 2. All hardware shall be galvanized. Hot-dip galvanize metal components for exterior use. VIBRATION AND SEISMIC CONTROLS FOR FIRE-SUPPRESSION PIPING AND EQUIPMENT 210548-4

3. Baked enamel or powder coat for metal components on isolators for interior use. 4. Color-code or otherwise mark vibration isolation and seismic-control devices to indicate capacity range. PART 3 - EXECUTION 3.1 EXAMINATION A. Examine areas and equipment to receive vibration isolation and seismic-control devices for compliance with requirements for installation tolerances and other conditions affecting performance. B. Examine roughing-in of reinforcement and cast-in-place anchors to verify actual locations before installation. C. Proceed with installation only after unsatisfactory conditions have been corrected. 3.2 APPLICATIONS A. ALL EQUIPMENT MUST BE HUNG FROM STRUCTURAL MEMBERS, NOT FROM COMPOSITE METAL DECKS OR STEEL ROOF DECKS. B. Multiple Pipe Supports: Secure pipes to trapeze member with clamps approved for application by an agency acceptable to authorities having jurisdiction. C. Hanger Rod Stiffeners: Install hanger rod stiffeners where indicated or scheduled on Drawings to receive them and where required to prevent buckling of hanger rods due to seismic forces. D. Strength of Support and Seismic-Restraint Assemblies: Where not indicated, select sizes of components so strength will be adequate to carry present and future static and seismic loads within specified loading limits. 3.3 VIBRATION-CONTROL AND SEISMIC-RESTRAINT DEVICE INSTALLATION A. Equipment Restraints: 1. Install resilient bolt isolation washers on equipment anchor bolts where clearance between anchor and adjacent surface exceeds 0.125 inch (3.2 mm). 2. Install seismic-restraint devices using methods approved by an agency acceptable to authorities having jurisdiction providing required submittals for component. B. Piping Restraints: 1. Comply with requirements in MSS SP-127 and NFPA 13. 2. Space lateral supports a maximum of 40 feet (12 m) o.c., and longitudinal supports a maximum of 80 feet (24 m) o.c. 3. Brace a change of direction longer than 12 feet (3.7 m). C. Install cables so they do not bend across edges of adjacent equipment or building structure. VIBRATION AND SEISMIC CONTROLS FOR FIRE-SUPPRESSION PIPING AND EQUIPMENT 210548-5

D. Install seismic-restraint devices using methods approved by an agency acceptable to authorities having jurisdiction providing required submittals for component. E. Install bushing assemblies for anchor bolts for floor-mounted equipment, arranged to provide resilient media between anchor bolt and mounting hole in concrete base. F. Install bushing assemblies for mounting bolts for wall-mounted equipment, arranged to provide resilient media where equipment or equipment-mounting channels are attached to wall. G. Attachment to Structure: If specific attachment is not indicated, anchor bracing to structure at flanges of beams, at upper truss chords of bar joists, or at concrete members. H. Drilled-in Anchors: 1. Identify position of reinforcing steel and other embedded items prior to drilling holes for anchors. Do not damage existing reinforcing or embedded items during coring or drilling. Notify the structural engineer if reinforcing steel or other embedded items are encountered during drilling. Locate and avoid prestressed tendons, electrical and telecommunications conduit, and gas lines. 2. Do not drill holes in concrete or masonry until concrete, mortar, or grout has achieved full design strength. 3. Wedge Anchors: Protect threads from damage during anchor installation. Heavy-duty sleeve anchors shall be installed with sleeve fully engaged in the structural element to which anchor is to be fastened. 4. Adhesive Anchors: Clean holes to remove loose material and drilling dust prior to installation of adhesive. Place adhesive in holes proceeding from the bottom of the hole and progressing toward the surface in such a manner as to avoid introduction of air pockets in the adhesive. 5. Set anchors to manufacturer's recommended torque, using a torque wrench. 6. Install zinc-coated steel anchors for interior and stainless-steel anchors for exterior applications. 3.4 ACCOMMODATION OF DIFFERENTIAL SEISMIC MOTION A. Install flexible connections in piping where they cross seismic joints, where adjacent sections or branches are supported by different structural elements, and where the connections terminate with connection to equipment that is anchored to a different structural element from the one supporting the connections as they approach equipment. Comply with requirements in Division 13 Section "Water-Based Fire-Suppression Systems" for piping flexible connections. END OF SECTION 210548 VIBRATION AND SEISMIC CONTROLS FOR FIRE-SUPPRESSION PIPING AND EQUIPMENT 210548-6

SECTION 211000 - WATER-BASED FIRE-SUPPRESSION SYSTEMS PART 1 - GENERAL 1.1 SUMMARY A. This Section includes the following fire-suppression piping inside the building: 1. Manual wet-type, Class I standpipe systems. 2. Wet-pipe sprinkler systems. B. Related Sections include the following: 1. Division 10 Section "Fire Extinguisher Cabinets" and "Fire Extinguishers" for cabinets and fire extinguishers. 2. Division 22 Section "Facility Water Distribution Piping" for piping outside the building. 3. Division 28 Section "Fire Detection and Alarm" for alarm devices not specified in this Section. 1.2 DEFINITIONS A. CR: Chlorosulfonated polyethylene synthetic rubber. B. High-Pressure Piping System: Fire-suppression piping system designed to operate at working pressure higher than standard 175 psig (1200 kpa). C. Underground Service-Entrance Piping: Underground service piping below the building. 1.3 SYSTEM DESCRIPTIONS A. Combined Standpipe and Sprinkler System: Fire-suppression system with both standpipe and sprinkler systems. Sprinkler system is supplied from standpipe system. B. Manual Wet-Type, Class I Standpipe System: Includes NPS 2-1/2 (DN 65) hose connections. Has small water supply to maintain water in standpipes. Piping is wet, but water must be pumped into standpipes to satisfy demand. C. Wet-Pipe Sprinkler System: Automatic sprinklers are attached to piping containing water and that is connected to water supply. Water discharges immediately from sprinklers when they are opened. Sprinklers open when heat melts fusible link or destroys frangible device. Hose connections are included if indicated. 1.4 PERFORMANCE REQUIREMENTS A. Standard Piping System Component Working Pressure: Listed for at least 175 psig (1200 kpa). B. Fire-suppression standpipe system design shall be approved by Architect/Engineer and the owner's representative. WATER-BASED FIRE-SUPPRESSION SYSTEMS 211000-1

1. Minimum residual pressure at each hose-connection outlet is the following: a. NPS 2-1/2 (DN 65) Hose Connections: 100 psig (690 kpa). 2. Unless otherwise indicated, the following is maximum residual pressure at required flow at each hose-connection outlet: a. NPS 2-1/2 (DN 65) Hose Connections: 175 psig (1200 kpa). C. Fire-suppression sprinkler system design shall be approved by the Architect/Engineer. 1. Margin of Safety for Available Water Flow and Pressure: 10 psi minimum, including losses through water-service piping, valves, and backflow preventers. 2. Velocity shall not exceed 20 feet per second (FPS). 3. Sprinkler Occupancy Hazard Classifications: a. Building Service Areas: Ordinary Hazard, Group 1. b. Electrical Equipment Rooms: Ordinary Hazard, Group 1. c. General Storage Areas: Ordinary Hazard, Group 2. d. Laundries: Ordinary Hazard, Group 1. e. Mechanical Equipment Rooms: Ordinary Hazard, Group 1. f. Office and Public Areas: Light Hazard. 4. Minimum Density for Automatic-Sprinkler Piping Design: a. Light-Hazard Occupancy: 0.10 gpm over 1500-sq. ft. (6.3 ml/s over 139-sq. m) area. b. Ordinary-Hazard, Group 1 Occupancy: 0.15 gpm over 1500-sq. ft. (9.5 ml/s over 139-sq. m) area. c. Ordinary-Hazard, Group 2 Occupancy: 0.20 gpm over 1500-sq. ft. (12.6 ml/s over 139-sq. m) area. d. Special Occupancy Hazard: As determined by authorities having jurisdiction. 5. Maximum Protection Area per Sprinkler: Per UL listing. 6. Maximum Protection Area per Sprinkler: a. Office Spaces: 225 sq. ft. (20.9 sq. m). b. Storage Areas: 130 sq. ft. (12.1 sq. m). c. Mechanical Equipment Rooms: 130 sq. ft. (12.1 sq. m). d. Electrical Equipment Rooms: 130 sq. ft. (12.1 sq. m). e. Other Areas: According to NFPA 13 recommendations, unless otherwise indicated. 7. Total Combined Hose-Stream Demand Requirement: According to NFPA 13, unless otherwise indicated: a. Light-Hazard Occupancies: 100 gpm (6.3 L/s) for 30 minutes. b. Ordinary-Hazard Occupancies: 250 gpm (15.75 L/s) for 60 to 90 minutes. D. Seismic Performance: Fire-suppression piping shall be capable of withstanding the effects of earthquake motions determined according to NFPA 13 and ASCE 7, "Minimum Design Loads for Buildings and Other Structures": Section 9, "Earthquake Loads." E. Sprinkler systems are to be zoned by floor: Sprinkler zones shall be provided with a floor control valve, flow switch and tamper switch. Additional zoning shall be provided as shown on the plans. WATER-BASED FIRE-SUPPRESSION SYSTEMS 211000-2

1. The sprinkler piping shall be looped between risers. Piping arrangements shall be complete with control valves, flow switches, tamper switches, check valves, and inspectors test assemblies complete with drains as required by NFPA 13. 2. Inspectors test valve assemblies shall be provided at the remote end of each zone. Test assemblies shall be provided with site glasses and hard piped express drains to hub drains. Hub drains shall be located in the mechanical room. F. Electric Rooms/Closets, Elevator Machine Rooms, Telephone Rooms, and IT Closets: Shall be sprinklered in accordance with NFPA 13. 1.5 SUBMITTALS A. General: Submit the following in accordance with Division 21 Section "Basic Division 21 Requirements." 1.6 ACTION SUBMITTALS A. Product Data: For the following: 1. Piping materials, including dielectric fittings, flexible connections, and sprinkler specialty fittings. 2. Pipe hangers and supports, including seismic restraints. 3. Valves, including listed fire-protection valves, unlisted general-duty valves, and specialty valves and trim. 4. Air compressors, including electrical data. 5. Sprinklers, escutcheons, and guards. Include sprinkler flow characteristics, mounting, finish, and other pertinent data. 6. Hose connections, including size, type, and finish. 7. Roof hose cabinets. 8. Monitors. 9. Fire hydrants. 10. Fire department connections, including type; number, size, and arrangement of inlets; caps and chains; size and direction of outlet; escutcheon and marking; and finish. 11. Alarm devices, including electrical data. B. Shop Drawings: 1. Provide copies to the electrical contractor for coordination. a. Wiring Diagrams: Power signal, and control wiring. C. Delegated Design Services: 1. Approved Sprinkler Piping Drawings: Working plans, prepared according to NFPA 13, that have been approved by the Architect/Engineer, including hydraulic calculations. a. The working plans and hydraulic calculations shall be signed and sealed by a professional engineer licensed in the State of Missouri. b. The working plans and hydraulic calculations shall be submitted to the owner's representative. 2. Hydraulic Calculations: The hydraulic calculations shall include the hydraulically most remote area for systems supplied by more than one combination riser. Hydraulic WATER-BASED FIRE-SUPPRESSION SYSTEMS 211000-3

calculations shall show the remote areas being supplied solely from the hydraulically most remote combination riser. 1.7 INFORMATIONAL SUBMITTALS A. Qualification Data 1. Installer a. Welding certificates. 2. Field Quality Control Test Reports. a. Copies of test reports shall be submitted to the Owner s Representative and Architect/Engineer within 24 hours 1.8 CLOSEOUT SUBMITTALS A. Operation and Maintenance Data: For standpipe and sprinkler specialties to include in emergency, operation, and maintenance manuals. B. Record Documents: 1. Final Field Quality Controls Test Reports: a. Field Test Reports and Certificates: Indicate and interpret test results for compliance with performance requirements and as described in NFPA 13 and NFPA 14. Include Contractor s Material and Test Certificate for Aboveground Piping and Contractor s Material and Test Certificate for Underground Piping. b. Fire-Hydrant Flow Test Report: 1) The report shall include the test date, testing agency, static pressure, residual pressure, flow rate and hydrant locations including a site plan. 1.9 QUALITY ASSURANCE A. Installer Qualifications: 1. Installer's responsibilities include designing, fabricating, and installing fire-suppression systems and providing professional engineering services needed to assume engineering responsibility. Base calculations on results of fire-hydrant flow test. a. Engineering Responsibility: Preparation of working plans, calculations, and field test reports by a qualified professional engineer registered in the State of Missouri. B. Welding: Qualify processes and operators according to ASME Boiler and Pressure Vessel Code: Section IX. C. NFPA Standards: Fire-suppression-system equipment, specialties, accessories, installation, and testing shall comply with the following: WATER-BASED FIRE-SUPPRESSION SYSTEMS 211000-4

1. NFPA 13, "Installation of Sprinkler Systems." 2. NFPA 14, "Installation of Standpipe, Private Hydrant, and Hose Systems." 3. NFPA 24, "Installation of Private Fire Service Mains and Their Appurtenances." D. Insurance Underwriter: Fire-suppression-system equipment, specialties, accessories, installation, and testing shall comply with the owner s insurance underwriter. E. Underwriters Laboratory: Fire-suppression-system equipment, specialties, accessories, installation, and testing shall comply with Underwriters Laboratory, and shall be for approved. F. To assure uniformity and compatibility of piping components in grooved piping systems, all grooved products utilized shall be supplied by a single manufacturer. Grooving tools shall be supplied from the same manufacturer as the grooved components. 1.10 COORDINATION A. Coordinate layout and installation of sprinklers with other construction that penetrates ceilings, including light fixtures, HVAC equipment, and partition assemblies. 1.11 EXTRA MATERIALS A. Furnish extra materials described below that match products installed and that are packaged with protective covering for storage and identified with labels describing contents. 1. Sprinkler Cabinets: Finished, wall-mounting, steel cabinet with hinged cover, with space for minimum of six spare sprinklers plus sprinkler wrench. Include number of sprinklers required by NFPA 13 and sprinkler wrench. Include separate cabinet with sprinklers and wrench for each type of sprinkler on Project. PART 2 - PRODUCTS 2.1 MANUFACTURERS A. In other Part 2 articles where titles below introduce lists, the following requirements apply to product selection: 1. Manufacturers: Subject to compliance with requirements, provide products by one of the manufacturers specified. 2.2 DUCTILE-IRON PIPE AND FITTINGS A. Mechanical-Joint, Ductile-Iron Pipe: AWWA C151, with mechanical-joint bell end and plain end. 1. Mechanical-Joint, Ductile-Iron Fittings: AWWA C110, ductile- or gray-iron standard pattern or AWWA C153, ductile-iron compact pattern. 2. Glands, Gaskets, and Bolts: AWWA C111, ductile- or gray-iron gland, rubber gasket, and steel bolts and nuts. B. Push-on-Joint, Ductile-Iron Pipe: AWWA C151, with push-on-joint bell end and plain end. WATER-BASED FIRE-SUPPRESSION SYSTEMS 211000-5

1. Push-on-Joint, Ductile-Iron Fittings: AWWA C110, ductile- or gray-iron standard pattern or AWWA C153, ductile-iron compact pattern. 2. Gaskets: AWWA C111, rubber. C. Grooved-End, Ductile-Iron Pipe: AWWA C151, with factory- or field-formed, radius-cut-grooved ends according to AWWA C606. 1. Grooved-Joint Piping Systems: a. Manufacturers: 1) Tyco Fire & Building Products LP 2) Victaulic Co. of America. b. Grooved-End Fittings: ASTM A 536, ductile-iron casting with OD matching ductileiron-pipe OD and cement lining. c. Grooved-End-Pipe Couplings: AWWA C606, gasketed fitting matching ductileiron-pipe OD. Include ductile-iron housing with keys matching ductile-iron-pipe and fitting grooves, synthetic rubber gasket with center leg, and steel bolts and nuts. d. Grooved-End-Pipe Transition Coupling: UL 213 and AWWA C606, gasketed fitting with end matching ductile-iron-pipe OD and end matching steel-pipe OD. Include ductile-iron housing with key matching ductile-iron-pipe groove and key matching steel-pipe groove, synthetic rubber gasket listed for use with housing, and steel bolts and nuts. e. Grooved-End Transition Flange: UL 213, gasketed fitting with key for ductile-ironpipe dimensions. Include flange-type, ductile-iron housing with rubber gasket listed for use with housing and steel bolts and nuts. 2.3 STEEL PIPE AND FITTINGS A. Threaded-End, Standard-Weight, Schedule 40 Steel Pipe: ASTM A 53/A 53M, ASTM A 135, or ASTM A 795, hot-dip galvanized where indicated and with factory- or field-formed threaded ends. 1. Cast-Iron Threaded Flanges: ASME B16.1. 2. Malleable-Iron Threaded Fittings: ASME B16.3. 3. Gray-Iron Threaded Fittings: ASME B16.4. 4. Steel Threaded Pipe Nipples: ASTM A 733, made of ASTM A 53/A 53M or ASTM A 106, Schedule 40, seamless steel pipe hot-dip galvanized where indicated. Include ends matching joining method. B. Plain-End, Standard-Weight, Schedule 40 Steel Pipe: ASTM A 53/A 53M, ASTM A 135, or ASTM A 795 hot-dip galvanized-steel pipe where indicated. 1. Steel Welding Fittings: ASTM A 234/A 234M, and ASME B16.9 or ASME B16.11. 2. Steel Flanges and Flanged Fittings: ASME B16.5. C. Grooved-End, Standard-Weight, Schedule 40 Steel Pipe: ASTM A 53/A 53M, ASTM A 135, or ASTM A 795, hot-dip galvanized where indicated and with factory - or field-formed, square-cutor roll-grooved ends. 1. Grooved-Joint Piping Systems: a. Manufacturers: WATER-BASED FIRE-SUPPRESSION SYSTEMS 211000-6

1) Anvil International, Inc. 2) Tyco Fire & Building Products LP 3) Victaulic Co. of America. b. Grooved-End Fittings: UL-listed, ASTM A 536, ductile-iron casting with OD matching steel-pipe OD. c. Grooved-End-Pipe Couplings: UL 213 and AWWA C606, rigid pattern, unless otherwise indicated; gasketed fitting matching steel-pipe OD. Include ductile-iron housing with keys matching steel-pipe and fitting grooves, prelubricated rubber gasket listed for use with housing, and steel bolts and nuts. 1) Rigid Type: Housings shall be cast with offsetting, angle-pattern bolt pads to provide system rigidity and support and hanging in accordance with NFPA 13. a) 2 through 8 : Installation Read stab-on design, for direct stab installation onto grooved end pipe without prior field disassembly and no loose parts. b) 10 and Larger: Standard rigid coupling. 2) Flexible Type: Use in seismic areas and where required by NFPA 13. a) 2 through 8 : Installation Read stab-on design, for direct stab installation onto grooved end pipe without prior field disassembly and no loose parts. b) 10 and Larger: Standard flexible coupling. 2.4 CORROSION-PROTECTIVE ENCASEMENT FOR PIPING A. Encasement for Underground Metal Piping: ASTM A 674 or AWWA C105, PE film, 0.008-inch (0.20-mm) minimum thickness, tube or sheet. 2.5 SPRINKLER SPECIALTY FITTINGS A. Sprinkler specialty fittings shall be UL listed or FMG approved, with 175-psig (1200-kPa) minimum working-pressure rating, and made of materials compatible with piping. B. Outlet Specialty Fittings: 1. Manufacturers: a. Anvil International, Inc. b. Tyco Fire & Buildign Products LP c. Victaulic Co. of America. C. Sprinkler Drain and Alarm Test Fittings: Cast- or ductile-iron body; or bronze body, with threaded or grooved inlet and outlet, test valve, and orifice and sight glass. 1. Manufacturers: a. Fire-End and Croker Corp. b. Tyco Fire & Building Products LP c. Viking Corp. WATER-BASED FIRE-SUPPRESSION SYSTEMS 211000-7

d. Victaulic Co. of America. D. Sprinkler Branch-Line Test Fittings: Brass body with threaded inlet, capped drain outlet, and threaded outlet for sprinkler. 1. Manufacturers: a. Elkhart Brass Mfg. Co., Inc. b. Fire-End and Croker Corp. c. Potter-Roemer; Fire-Protection Div. E. Sprinkler Inspector's Test Fitting: Cast- or ductile-iron or bronze housing with grooved inlet and drain outlet and sight glass. 1. Manufacturers: a. AGF Manufacturing Co. b. Victaulic. F. Drop-Nipple Fittings: UL 1474, adjustable with threaded inlet and outlet, and seals. 1. Manufacturers: a. CECA, LLC. b. Merit. 2.6 LISTED FIRE-PROTECTION VALVES A. Valves shall be UL listed or FMG approved, with 175-psig (1200 kpa) minimum pressure rating. B. Gate Valves with Wall Indicator Posts: 1. Gate Valves: UL 262, cast-iron body, bronze mounted, with solid disc, nonrising stem, operating nut, and flanged ends. 2. Indicator Posts: UL 789, horizontal-wall type, cast-iron body, with operating wrench, extension rod, locking device, and cast-iron barrel. 3. Manufacturers: a. Grinnell Fire Protection. b. McWane, Inc.; Kennedy Valve Div. c. NIBCO. d. Stockham. C. Ball Valves: Comply with UL 1091, except with ball instead of disc. 1. NPS 1-1/2 (DN 40) and Smaller: Bronze body with threaded or grooved ends. 2. NPS 2 (DN 50): Bronze body with threaded ends or grooved ends. 3. Manufacturers: a. NIBCO. b. Victaulic Co. of America. D. Butterfly Valves: UL 1091: WATER-BASED FIRE-SUPPRESSION SYSTEMS 211000-8

1. NPS 2 (DN 50) and Smaller: Bronze body with threaded ends. a. Manufacturers: 1) Global Safety Products, Inc. 2) Milwaukee Valve Company. 2. NPS 2-1/2 (DN 65) and Larger: Bronze, cast-iron, or ductile-iron body; wafer type or with flanged or grooved ends. a. Manufacturers: 1) McWane, Inc.; Kennedy Valve Div. 2) Mueller Company. 3) NIBCO. 4) Pratt, Henry Company. 5) Tyco Fire & Building Products LP 6) Victaulic Co. of America. E. Check Valves NPS 2 (DN 50) and Larger: UL 312, swing type, cast-iron body with flanged or grooved ends. 1. Manufacturers: a. Crane Co.; Crane Valve Group; Crane Valves. b. Crane Co.; Crane Valve Group; Jenkins Valves. c. Hammond Valve. d. McWane, Inc.; Kennedy Valve Div. e. Mueller Company. f. NIBCO. g. Reliable Automatic Sprinkler Co., Inc. h. Stockham. i. Tyco Fire & Building Products LP j. Victaulic Co. of America. F. Gate Valves: UL 262, OS&Y type. 1. NPS 2 (DN 50) and Smaller: Bronze body with threaded ends. a. Manufacturers: 1) Crane Co.; Crane Valve Group; Crane Valves. 2) Hammond Valve. 3) NIBCO. 4) United Brass Works, Inc. 2. NPS 2-1/2 (DN 65) and Larger: Cast-iron body with flanged ends. a. Manufacturers: 1) Clow Valve Co. 2) Crane Co.; Crane Valve Group; Crane Valves. 3) Crane Co.; Crane Valve Group; Jenkins Valves. 4) Hammond Valve. 5) Milwaukee Valve Company. WATER-BASED FIRE-SUPPRESSION SYSTEMS 211000-9

6) Mueller Company. 7) NIBCO. 8) United Brass Works, Inc. 3. NPS-2-1/2 (DN 65) and Larger: Ductile iron body with grooved ends. a. Manufacturers: 1) Victaulic. G. Indicating Valves: UL 1091, with integral indicating device and ends matching connecting piping. 1. Indicator: Electrical, 115-V ac, prewired, single-circuit, supervisory switch. 2. NPS 2 (DN 50) and Smaller: Ball or butterfly valve with bronze body and threaded ends. a. Manufacturers: 1) Milwaukee Valve Company. 2) NIBCO. 3) Victaulic Co. of America. 3. NPS 2-1/2 (DN 65) and Larger: Butterfly valve with cast- or ductile-iron body; wafer type or with flanged or grooved ends. a. Manufacturers: 1) Grinnell Fire Protection. 2) McWane, Inc.; Kennedy Valve Div. 3) Milwaukee Valve Company. 4) NIBCO. 5) Victaulic Co. of America. 2.7 UNLISTED GENERAL-DUTY VALVES A. Ball Valves NPS 2 (DN 50) and Smaller: MSS SP-110, 2-piece copper-alloy body with chromeplated brass ball, 600-psig (4140-kPa) minimum CWP rating, blowout-proof stem, and threaded ends. B. Check Valves NPS 2 (DN 50) and Smaller: MSS SP-80, Type 4, Class 125 minimum, swing type with bronze body, nonmetallic disc, and threaded ends. C. Gate Valves NPS 2 (DN 50) and Smaller: MSS SP-80, Type 2, Class 125 minimum, with bronze body, solid wedge, and threaded ends. D. Globe Valves NPS 2 (DN 50) and Smaller: MSS SP-80, Type 2, Class 125 minimum, with bronze body, nonmetallic disc, and threaded ends. 2.8 SPECIALTY VALVES A. Sprinkler System Control Valves: UL listed or FMG approved, cast- or ductile-iron body with flanged or grooved ends, and 175-psig (1200-kPa) minimum pressure rating. WATER-BASED FIRE-SUPPRESSION SYSTEMS 211000-10

1. Manufacturers: a. Reliable Automatic Sprinkler Co., Inc. b. Victaulic Co. of America. c. Viking Corp. 2.9 SPRINKLERS A. Sprinklers shall be quick response type UL listed and FMG approved, with 175-psig (1200-kPa) minimum pressure rating. B. Sprinklers shall be glass bulb type. Body shall be die cast brass with hex shaped wrench boss cast into the body to facilitate installation and reduce the risk of damage during installation. C. Manufacturers: 1. Reliable Automatic Sprinkler Co., Inc. 2. Tyco Fire & Building Products LP. 3. Victaulic Co. 4. Viking Corp. D. Automatic Sprinklers: With heat-responsive element complying with the following: 1. UL 199, for nonresidential applications. E. Sprinkler Types and Categories: Nominal 1/2-inch (12.7-mm) orifice for "Ordinary" temperature classification rating, unless otherwise indicated or required by application. F. Sprinkler types, features, and options as follows: 1. Concealed ceiling sprinklers, including cover plate. 2. Extended-coverage sprinklers. 3. Flush ceiling sprinklers, including escutcheon. 4. Pendent sprinklers. 5. Pendent, dry-type sprinklers. 6. Quick-response sprinklers. 7. Recessed sprinklers, including escutcheon. 8. Sidewall sprinklers. 9. Sidewall, dry-type sprinklers. 10. Upright sprinklers. G. Sprinkler Finishes: Chrome plated, bronze, and painted. H. Special Coatings: Nickel Teflon, wax, lead, and corrosion-resistant paint. I. Sprinkler Escutcheons: Materials, types, and finishes for the following sprinkler mounting applications. Escutcheons for concealed, flush, and recessed-type sprinklers are specified with sprinklers. 1. Ceiling Mounting: Chrome-plated steel, one piece, flat. 2. Sidewall Mounting: Chrome-plated steel, one piece, flat. J. Sprinkler Guards: Wire-cage type, including fastening device for attaching to sprinkler. WATER-BASED FIRE-SUPPRESSION SYSTEMS 211000-11

K. Sprinkler escutcheons and guards shall be listed, supplied and approved for use with the sprinkler, by the sprinkler manufacturer. 2.10 HOSE CONNECTIONS A. Manufacturers: 1. Elkhart Brass Mfg. Co., Inc. 2. Fire-End and Croker Corp. 3. Fire Protection Products, Inc. 4. GMR International Equipment Corporation. 5. Grinnell Fire Protection. 6. Guardian Fire Equipment Incorporated. 7. McWane, Inc.; Kennedy Valve Div. 8. Mueller Company. 9. Potter-Roemer; Fire-Protection Div. 10. Tyco Fire & Building Products LP. B. Description: UL 668, brass or bronze, 300-psig (2070-kPa) minimum pressure rating, hose valve for connecting fire hose. Include angle or gate pattern design; female NPS inlet and male hose outlet; and lugged cap, gasket, and chain. Include NPS 1-1/2 or NPS 2-1/2 (DN 40 or DN 65) as indicated, and hose valve threads according to NFPA 1963 and matching local fire department threads. 1. Valve Operation: Nonadjustable type. 2. Finish: Rough metal or chrome-plated. 2.11 WALL-TYPE FIRE HYDRANTS A. Available Manufacturers: 1. Elkhart Brass Mfg. Co., Inc. 2. Guardian Fire Equipment Incorporated. 3. Potter-Roemer; Fire-Protection Div. B. Description: Cast-brass-body fire hydrant with brass wall escutcheon plates, brass lugged caps with gaskets and brass chains, and brass lugged swivel connections. Include outlets with threads according to NFPA 1963 and matching local fire department sizes and threads, inlet with pipe threads, extension pipe nipple, and valve control. 1. Type: Flush with two hose-connection outlets and square or rectangular escutcheon plate. 2. Type: Exposed, projecting, with two hose-connection outlets and round escutcheon plate. 3. Finish: Rough chrome-plated. 4. Hydrant Escutcheon-Plate Marking: "HYDRANT." 5. Hydrant Valve Control: Wall-mounting assembly with extension rod for manual control of valve inside building. 6. Hydrant Valve-Control Escutcheon-Plate Marking: "HYDRANT VALVE CONTROL." 2.12 FIRE DEPARTMENT CONNECTIONS A. Available Manufacturers: WATER-BASED FIRE-SUPPRESSION SYSTEMS 211000-12

1. Elkhart Brass Mfg. Co., Inc. 2. Fire-End and Croker Corp. 3. GMR International Equipment Corporation. 4. Guardian Fire Equipment Incorporated. 5. Potter-Roemer; Fire-Protection Div. 6. Reliable Automatic Sprinkler Co., Inc. 7. Tyco Fire & Building Products LP. B. Wall-Type, Fire Department Connection: UL 405, 175-psig (1200-kPa) minimum pressure rating; with corrosion-resistant-metal body with brass inlets, brass wall escutcheon plate, brass lugged caps with gaskets and brass chains, and brass lugged swivel connections. Include inlets with threads according to NFPA 1963 and matching local fire department sizes and threads, outlet with pipe threads, extension pipe nipples, check devices or clappers for inlets, and escutcheon plate with marking similar to "AUTO SPKR & STANDPIPE." 1. Type: Flush, with two inlets and square or rectangular escutcheon plate. 2. Type: Exposed, projecting, with two inlets and round escutcheon plate. 3. Finish: Polished chrome-plated. 2.13 ALARM DEVICES A. Alarm-device types shall match piping and equipment connections. B. Electrically Operated Alarm: UL 464, with 8-inch- (200-mm-) minimum-diameter, vibrating-type, metal alarm bell with red-enamel factory finish and suitable for outdoor use. 1. Available Manufacturers: a. Potter Electric Signal Company. b. System Sensor. C. Water-Flow Indicator: UL 346, electrical-supervision, paddle-operated-type, water-flow detector with 250-psig (1725-kPa) pressure rating and designed for horizontal or vertical installation. Include two single-pole, double-throw circuit switches for isolated alarm and auxiliary contacts, 7 A, 125-V ac and 0.25 A, 24-V dc; complete with factory-set, field-adjustable retard element to prevent false signals and tamperproof cover that sends signal if removed. 1. Available Manufacturers: a. ADT Security Services, Inc. b. Grinnell Fire Protection. c. ITT McDonnell & Miller. d. Potter Electric Signal Company. e. System Sensor. f. Viking Corp. g. Watts Industries, Inc.; Water Products Div. D. Pressure Switch: UL 753, electrical-supervision-type, water-flow switch with retard feature. Include single-pole, double-throw, normally closed contacts and design that operates on rising pressure and signals water flow. 1. Available Manufacturers: a. Grinnell Fire Protection. b. Potter Electric Signal Company. WATER-BASED FIRE-SUPPRESSION SYSTEMS 211000-13

c. System Sensor. d. Viking Corp. E. Valve Supervisory Switch: UL 753, electrical, single-pole, double-throw switch with normally closed contacts. Include design that signals controlled valve is in other than fully open position. 1. Available Manufacturers: a. McWane, Inc.; Kennedy Valve Div. b. Potter Electric Signal Company. c. System Sensor. F. Indicator-Post Supervisory Switch: UL 753, electrical, single-pole, double-throw switch with normally closed contacts. Include design that signals controlled indicator-post valve is in other than fully open position. 1. Available Manufacturers: a. Potter Electric Signal Company. b. System Sensor. 2.14 PRESSURE GAGES A. Available Manufacturers: 1. AGF Manufacturing Co. 2. AMETEK, Inc.; U.S. Gauge. 3. Brecco Corporation. 4. Dresser Equipment Group; Instrument Div. 5. Marsh Bellofram. 6. WIKA Instrument Corporation. B. Description: UL 393, 3-1/2- to 4-1/2-inch- (90- to 115-mm-) diameter, dial pressure gage with range of 0 to 250 psig (0 to 1725 kpa) minimum. 1. Water System Piping: Include caption "WATER" or "AIR/WATER" on dial face. 2. Air System Piping: Include retard feature and caption "AIR" or "AIR/WATER" on dial face. PART 3 - EXECUTION 3.1 PREPARATION A. Perform fire-hydrant flow test according to NFPA 13, NFPA 14 and NFPA 291. Use results for system design calculations required in Part 1 "Quality Assurance" Article. B. Notifications: Notify the Owner s Representative at least three working days in advance of performing the flow test. C. Perform test as close as possible to new wet-tap connection for new fire service. WATER-BASED FIRE-SUPPRESSION SYSTEMS 211000-14

1. Pressure drop from static to residual shall be at least 25 percent of the static pressure. The flow at the residual pressure shall meet or exceed the preliminary estimated design flow. Open additional hydrant butts as required to obtain the specified pressure drop or to match the preliminary estimated design flow. D. Record elevations of the test hydrants and submit hydraulic graph(s) indicating test results to the Owner s Representative and Architect/Engineer for review and approval before submitting hydraulic calculations and working plans. E. Hydraulic graph shall indicate elevation adjustments and water supply curve at wet-tap connection. F. Report test results within 48 hours and in writing to the Owner s Representative and the Architect/Engineer. 3.2 EARTHWORK A. Refer to Division 31 Section "Earth Moving" for excavating, trenching, and backfilling. 3.3 EXAMINATION A. Examine roughing-in for hose connections and stations to verify actual locations of piping connections before installation. B. Examine walls and partitions for suitable thicknesses, fire- and smoke-rated construction, framing for hose-station cabinets, and other conditions where hose connections and stations are to be installed. C. Proceed with installation only after unsatisfactory conditions have been corrected. 3.4 HYDRAULICALLY CALCULATED SPRINKLER SYSTEM A. The Contractor shall provide a hydraulically designed system in complete accordance with and as defined in applicable National Fire Protection Standards. B. Verification of Hydraulic Information: 1. The contractor shall perform hydrant flow tests to establish water supply availability. Water supply information shall be provided on shop drawings as outlined in NFPA 13. 2. The Contractor shall confirm that hazard classifications/density requirements, if noted on the contract drawings, conform with the Owner's fire insurance underwriter's requirements. C. Accompanying sprinkler shop drawings submitted to the Architect shall bear all sprinkler system requirements, water supply data, graph and work sheets all as defined by NFPA. The hydraulic graph shall include the following information: 1. Hydrant flow test curve. 2. Adjust flow test for friction and elevation at new wet tap connection. 3. System friction loss curve for sprinkler system with inside hose stream. 4. Available outside hose stream flow. 5. Fire pump discharge curve. WATER-BASED FIRE-SUPPRESSION SYSTEMS 211000-15

D. All calculations shall assume a 10 psi deterioration in static and residual pressures in the hydrant flow test results. E. Velocity shall not exceed 20 FPS. F. In addition to the above noted requirements, the hydraulic calculations shall include: 1. The hydraulically most remote area for each hazard classification/density requirements as noted on the contract documents. 3.5 PIPING APPLICATIONS, GENERAL A. Shop weld pipe joints where welded piping is indicated. B. Do not use welded joints for galvanized-steel pipe. C. Flanges, flanged fittings, unions, nipples, and transition and special fittings with finish and pressure ratings same as or higher than system's pressure rating may be used in aboveground applications, unless otherwise indicated. D. Piping between Fire Department Connections and Check Valves: Galvanized, standard-weight steel Schedule 40 pipe with grooved ends; grooved-end fittings; grooved-end-pipe couplings; and grooved joints. E. Underground Service-Entrance Piping: Ductile-iron, mechanical-joint pipe and fittings and restrained joints.[ Include corrosion-protective encasement. F. Underground Service-Entrance Piping: Ductile-iron, grooved-end pipe and fittings; groovedend-pipe couplings; and grooved joints. Include corrosion-protective encasement. 3.6 STANDPIPE SYSTEM PIPING APPLICATIONS A. Standard-Pressure, Wet-Type Standpipe System, 175-psig (1200-kPa) Maximum Working Pressure: 1. NPS 4 (DN 100) and Smaller: Threaded-end, black or galvanized, standard-weight schedule 40 steel pipe; cast- or malleable-iron threaded fittings; and threaded joints. 2. NPS 4 (DN 100) and Smaller: Plain-end, black, standard-weight schedule 40 steel pipe; steel welding fittings; and welded joints. 3. NPS 4 (DN 100) and Smaller: Grooved-end, black or galvanized, standard-weight schedule 40 steel pipe with square-cut- or roll-grooved ends; grooved-end fittings; grooved-end-pipe couplings; and grooved joints. 4. NPS 5 and NPS 6 (DN 125 and DN 150): Threaded-end, black or galvanized, standardweight schedule 40 steel pipe; cast- or malleable-iron threaded fittings; and threaded joints. 5. NPS 5 and NPS 6 (DN 125 and DN 150): Plain-end, black, standard-weight schedule 40 steel pipe; steel welding fittings; and welded joints. 6. NPS 5 and NPS 6 (DN 125 and DN 150): Grooved-end, black or galvanized, standardweight schedule 40 steel pipe with square-cut- or roll-grooved ends; grooved-end fittings; grooved-end-pipe couplings; and grooved joints. 7. NPS 8 (DN 200): Threaded-end, black or galvanized, standard-weight schedule 40 steel pipe; cast- or malleable-iron threaded fittings; and threaded joints. WATER-BASED FIRE-SUPPRESSION SYSTEMS 211000-16

8. NPS 8 (DN 200): Plain-end, black, standard-weight schedule 40 steel pipe; steel welding fittings; and welded joints. 9. NPS 8 (DN 200): Grooved-end, black or galvanized, standard-weight schedule 40 steel pipe with square-cut- or roll-grooved ends; grooved-end fittings; grooved-end-pipe couplings; and grooved joints. 3.7 SPRINKLER SYSTEM PIPING APPLICATIONS A. Standard-Pressure, Wet-Pipe Sprinkler System, 175-psig (1200-kPa) Maximum Working Pressure: 1. NPS 1-1/2 (DN 40) and Smaller: Threaded-end, black or galvanized, standard-weight schedule 40 steel pipe; cast- or malleable-iron threaded fittings; and threaded joints. 2. NPS 1-1/2 (DN 40) and Smaller: Plain-end, black or galvanized, standard-weight schedule 40 steel pipe; locking-lug fittings; and twist-locked joints. 3. NPS 1-1/2 (DN 40) and Smaller: Plain-end, black, standard-weight schedule 40 steel pipe; steel welding fittings; and welded joints. 4. NPS 2 (DN 50): Threaded-end, black or galvanized, standard-weight Schedule 40 steel pipe; cast- or malleable-iron threaded fittings; and threaded joints. 5. NPS 2 (DN 50): Plain-end, black, standard-weight Schedule 40 steel pipe; steel welding fittings; and welded joints. 6. NPS 2 (DN 50): Grooved-end, black or galvanized, standard-weight Schedule 40 steel pipe; grooved-end fittings; grooved-end-pipe couplings; and grooved joints. 7. NPS 2-1/2 to NPS 3-1/2 (DN 65 to DN 90): Threaded-end, black or galvanized, standard-weight Schedule 40 steel pipe; cast- or malleable-iron threaded fittings; and threaded joints. 8. NPS 2-1/2 to NPS 3-1/2 (DN 65 to DN 90): Plain-end, black, standard-weight Schedule 40 steel pipe; steel welding fittings; and welded joints. 9. NPS 2-1/2 to NPS 3-1/2 (DN 65 to DN 90): Grooved-end, black or galvanized, standardweight Schedule 40 steel pipe; grooved-end fittings; grooved-end-pipe couplings; and grooved joints. 10. NPS 4 to NPS 6 (DN 100 to DN 150): Threaded-end, black or galvanized, standardweight Schedule 40 steel pipe; cast- or malleable-iron threaded fittings; and threaded joints. 11. NPS 4 to NPS 6 (DN 100 to DN 150): Plain-end, black, standard-weight Schedule 40 steel pipe; steel welding fittings; and welded joints. 12. NPS 4 to NPS 6 (DN 100 to DN 150): Grooved-end, black or galvanized, standardweight Schedule 40 steel pipe; grooved-end fittings; grooved-end-pipe couplings; and grooved joints. 3.8 VALVE APPLICATIONS A. Drawings indicate valve types to be used. Where specific valve types are not indicated, the following requirements apply: 1. Listed Fire-Protection Valves: UL listed and FMG approved for applications where required by NFPA 13 and NFPA 14. a. Shutoff Duty: Use ball, butterfly, or gate valves. 2. Unlisted General-Duty Valves: For applications where UL-listed and FMG-approved valves are not required by NFPA 13 and NFPA 14. a. Shutoff Duty: Use ball, butterfly, or gate valves. WATER-BASED FIRE-SUPPRESSION SYSTEMS 211000-17

b. Throttling Duty: Use ball or globe valves. 3.9 JOINT CONSTRUCTION A. Refer to Division 21 Section "Common Work Results for Fire Suppression" for basic piping joint construction. B. Threaded Joints: Comply with NFPA 13 for pipe thickness and threads. Do not thread pipe smaller than NPS 8 (DN 200) with wall thickness less than Schedule 40. C. Pressure-Sealed Joints: Use UL-listed tool and procedure. Include use of specific equipment, pressure-sealing tool, and accessories. D. Grooved Joints: Assemble joints with listed coupling and gasket, lubricant, and bolts. 1. Ductile-Iron Pipe: Radius-cut-groove ends of piping. Use grooved-end fittings and grooved-end-pipe couplings. 2. Steel Pipe: Square-cut or roll-groove piping as indicated. Use grooved-end fittings and rigid, grooved-end-pipe couplings, unless otherwise indicated. 3. Dry-Pipe Systems: Use fittings and gaskets listed for dry pipe service. 4. Grooved joint piping systems shall be installed in accordance with the manufacturer s guidelines and recommendations. 5. The gasket style and elastomeric material (grade) shall be verified as suitable for the intended service as specified. Gaskets shall be molded and produced by manufacturer. 6. Grooved end shall be clean and free from indentions, projections and roll marks in the area from pipe end to groove for proper gasket sealing. E. Dissimilar-Metal Piping Joints: Construct joints using dielectric fittings compatible with both piping materials. 1. NPS 2 (DN 50) and Smaller: Use dielectric unions, couplings, or nipples. 2. NPS 2-1/2 to NPS 4 (DN 65 to DN 100): Use dielectric flanges. 3. NPS 5 (DN 125) and Larger: Use dielectric flange insulation kits. 3.10 SERVICE-ENTRANCE PIPING A. Connect fire-suppression piping to water-service piping of size and in location indicated for service entrance to building. Refer to Division 22 Section "Facility Water Distribution Piping" for exterior piping. B. Install shutoff valve, backflow preventer, pressure gage, drain, and other accessories indicated at connection to water-service piping. Refer to Division 22 Section "Facility Water Distribution Piping" for backflow preventers. C. Install shutoff valve, check valve, pressure gage, and drain at connection to water service. 3.11 WATER-SUPPLY CONNECTION A. Connect fire-suppression piping to building's interior water distribution piping. Refer to Division 22 Section "Domestic Water Piping" for interior piping. WATER-BASED FIRE-SUPPRESSION SYSTEMS 211000-18