HW 22 District heating substation for indirect heating and domestic hot water systems

Similar documents
Akva Lux VX District heating substation for indirect heating and domestic hot water systems

WL Instantaneous water heater

Akva Vita TDP District heating flat station for direct heating and domestic hot water systems

Akva Lux TDP-F District heating flat station for direct heating and domestic hot water systems

Akva Vita TDP-F District heating flat station for direct heating and domestic hot water systems

Akva Vita Instantaneous water heater

Operating Guide. Termix Compact 28 VX-FI / HWP / HWS. 1.0 Table of Contents. 1.0 Table of Contents

Operating Guide. Termix Solar A+/B+ 1.0 Table of Contents. 1.0 Table of Contents

Installation Guide. Termix Distribution unit. 1.0 Table of Contents. 1.0 Table of Contents

Domestic hot water (DHW) The substation can be supplied with connection pipes for DHW cylinder on the supply or return line.

Instructions for installation and use Akva Lux II VX substations 1. Contents

Reno Exchange of gas boilers.

MAKING MODERN LIVING POSSIBLE. Akva Lux II TDP-F. Instructions for installation and use. Danfoss District Energy

Instructions. VX Solo II. 1.0 Table of contents

Wall-mounted substation PKL-113

T. +44 (0) E.

ModuSat TP. Energy. Heat Interface Units

Thermostatic mixing valves with interchangeable cartridges

Technical Data TYPE T14 & T14D TEMPERATURE PILOT SPENCE ENGINEERING COMPANY, INC. 150 COLDENHAM ROAD, WALDEN, NY SD 4511A T14 PILOT

heat interface units A BOILER WITHOUT A FLAME

5231 Series. Low Lead High Flow Thermostatic Mixing Valves. Installation, commissioning and service instructions ASSE 1017 NA10341

Intatherm Safe Touch Basin Tap IT1008CP

ModuSat TP. Energy. Heat Interface Units

Installation Guide DSA 1 MINI. Contents

SEALED THERMAL STORE

ELECTRIC BOILERS FOR CENTRAL HEATING

60 C water temperature ensures thermal disinfection during hot water production

Empty unit Cover Water Total weight 15 kg 8 kg 10 kg 33 kg

Syrup Server. Thank You MODEL: SY MODEL: SY for purchasing this Syrup Server to heat and neatly dispense sticky syrups and sauces.

CALEFFI. Thermostatic mixing valves with replaceable cartridge for centralized systems. 5230, 5231 series 01080/13 NA ASSE Replaces 01080/11 NA

Series 1140 and 1141 Temperature Regulators

Operation and Maintenance Manual Sondex All-Welded Heat Exchangers (SAW)

5231 Series. Low Lead High Flow Thermostatic Mixing Valves. Installation, commissioning and service instructions ASSE 1017 NA10341.

OPERATING AND MAINTENANCE MANUAL FOR PLATE HEAT EXCHANGER INDIRECT FIRED WATER HEATER. Electric Heater Company Base Model "BWXP"

a Danfoss Platform for Flensburg Secondary Network

Airfield Industrial Estate Hixon Staffordshire ST18 0PF

TERMO-Blok TERMO-Extra TERMO-Blok PTV

User instructions DHP-AT

Thermostatic mixing valves with replaceable cartridge for centralized systems

C66. ECL Comfort. User's Guide. Installer's Guide. ECL Comfort C66. User's Guide. Installer's Guide. *vi7cc502* *087R8069* *087R8069* *vi7cc502*

HX-30/40 and HX-30/40 S Glass and Dishwashers

Niles Steel Tank Hot Water Generator Installation and Operation Manual

WH-TD20B3E5 WH-TD30B3E5

P20. ECL Comfort. User's Guide. Installer's Guide. ECL Comfort P20. User's Guide. Installer's Guide *VI7BD502* *087R8014* *087R8014* *VI7BD502*

541D19 SERIES. Technical Manual. A Division of Aquion Partners L.P.

INSTALLATION MANUAL. Domestic hot water tank with option kit for air to water heat pump system EKHWSU150B3V3 EKHWSU200B3V3 EKHWSU300B3V3 EKUHWB

Model: 1413 Model: 1418 Float-Controlled Condensate Trap, PN 100

Armstrong J Series Float, Thermostatic Steam Traps, Condensate Controllers & Liquid Drainers Installation and Maintenance Manual

C62. ECL Comfort. User's Guide. Installer's Guide. ECL Comfort C62. User's Guide. Installer's Guide *VIKME102* *087R8091* *087R8091* *VIKME102*

521 Series. MixCal adjustable three-way thermostatic mixing valve. Installation, commissioning and service instructions

C37. ECL Comfort. User's Guide. Installer's Guide. ECL Comfort C37. User's Guide. Installer's Guide *VI7CE602* *087R8070* *087R8070* *VI7CE602*

Operating Manual. Model: 1400 Model: 1400-N RIFOmat Float-Controlled Condensate Traps, PN Safety instructions. 2 General description and use

INSTALLATION MANUAL. Domestic hot water tank for air to water heat pump system EKHWS150B3V3 EKHWS200B3V3 EKHWS300B3V3 EKHWS200B3Z2 EKHWS300B3Z2

CONCEALED THERMOSTATIC SHOWER MIXER VALVE installation & aftercare instruction

Diplomat Inverter/Diplomat Duo Inverter

SATK50-60 series CONTENTS. Recess Mounted Heat Interface Unit - SATK series INSTRUCTIONS FOR INSTALLATION, COMMISSIONING AND MAINTENANCE

Model T-45NL: Certified in compliance with ASSE 1017, 1069, 1070, and ANSI/NSF 61 PLEASE READ THESE INSTRUCTIONS BEFORE INSTALLING AND OPERATING!

AUTOMATIC GRANULAR ICE FLAKER

ECL Comfort 110, application 116

CONCEALED THERMOSTATIC TOUCH SHOWER MIXER VALVE Installation & Aftercare Instructions (1) (2) PLEASE READ BEFORE INSTALLATION

T. +44 (0) E.

Indirect Expansion. USER MANUAL FOR OPERATORS AND PLUMBERS HEAT INTERFACE UNITS

CALEFFI. SATK wall-mounted heat interface unit Fitted for connection to DHW storage. SATK40 series 01216/14 GB

Fusion 200, 300 & 500

Thermostatic mixing valve VADO-PRO-100P

User s Information Manual

Signature Touch Squeeze Bottle Warmer

SOTTOSTAZIONI PER TELERISCALDAMENTO DISTRICT HEATING SUBSTATIONS

SATK wall-mounted Heat Interface Unit (HIU) Instantaneous domestic hot water production

Installation Manual. Instrucciones de instalación y manual de usuario 1

ENERSTORE. Vented Hot Water Storage System INSTRUCTIONS PLEASE LEAVE WITH HOUSEHOLDER

J120 STEAM BOOSTER INSTALLATION, OPERATION, AND SERVICE MANUAL J120 STEAM BOOSTER. J120 Steam Booster Manual D

Contact person RISE Date Reference Page Björn Folkeson P03675B 1 (11) Energy and circular economy

Installation, commissioning and servicing instructions. Technical Characteristics. -Lead Plumbing Law Certifi ed by IAPMO R&T

Kinetic. Logic. Astin. THERMOSTATIC INLINE CONTROL SHOWER VALVES Installation & aftercare instructions. Please retain for future reference

Cleaning unit for coolant. :_decftez`_>r_fr] Book No.: V2

THERMflow Thermal Store Cylinders

Information Job Sheet 4. Closed-Loop Drainback Systems. Drainback tanks

TERMO-Blok TERMO-Extra TERMO-Blok PTV TERMO-Mini

! WARNING. McDonnell & Miller Installation & Maintenance Instructions MM-214(C) Series 61 Low Water Cut-Off OPERATION

Kiko Bath Shower Mixing Valve KK90015CP

13-1. Temperature Regulator

Model: 1100 Float-Controlled Condensate Trap, PN 25

Adjustable three-way thermostatic mixing valve... connections ½", ¾", 1" NPT male union and sweat union and ¾" press

Sanitary Water Tank INSTALLATION & SVC MANUAL

Inta City Shower Mixing Valve CT20010CP

Installation, Operating and Servicing Instructions

PLEASE LEAVE THIS MANUAL WITH THE OSO UNIT AFTER INSTALLATION INSTALLATION MANUAL

INSTALLATION AND OPERATION MANUAL STEAM COIL BASE CONVECTION STEAMER MODEL SCX-16

Technote. Frese AquaHeat HW - DH. Application. Design. Features and Benefit. Operation. Optional.

CUBEflow Thermal Store Tank

The Classeq under counter range

INSTALLATION & OPERATION Rev 1.00A DISTRIBUTED EXCLUSIVELY BY CMA DISHMACHINES KNOTT AVENUE GARDEN GROVE, CALIFORNIA 92841

Installation, Operation and Maintenance Manual

s y ens Av Avensys FIN EST RUS SLO RUS UAE

Deluge Shower Mixing Valve 10045CP

HKF 8180 Operating instructions

Installation, Operation and Maintenance Instructions Electric Flow Heater OM009

Residential Gas Condensing Boiler Greenstar ZBR16/21/28/35/42-3A... ZWB28/35/42-3A...

Operating and assembly manual: Electric instantaneous flow heater Admiral

Transcription:

HW 22 District heating substation for indirect heating and domestic hot water systems HW 22 Table of contents HW 22... 1 Table of contents... 1 Safety notes... 2 Delivery... 2 Transport and storage... 2 Mounting... 3 Pipes connections... 3 Electrical connection... 3 Filling, start-up... 4 Control... 4 Maintenance... 7 Troubleshooting DHW... 8 Troubleshooting HE... 9 DH-SMT/PL VI.KS.C1.02 Danfoss 08/2006 1

Safety notes The following instructions refer to the standard design of the HW 22 substation. Special versions of substations are available on request. To avoid injury of persons and damages to the device, it is absolutely necessary to read and observe these instructions carefully. Necessary assembly, start-up and maintenance work must be performed by qualified and authorized personnel only. Please comply with the instructions of the system manufacturer or system operator. Unused connections and shut-off valves must be sealed with a plug. The plugs can be removed by an authorized service technician only. Warning of high pressure and temperature The maximum temperature of the flow medium in a substation is 120 C. The maximum operating pressure of the substation is 16 bar. Be aware of the installation s permissible system pressure and temperature. The risk of persons being injured and equipment damaged increases considerably if the recommended permissible operating parameters are exceeded. The installation of substation is equipped with safety valves. Warning of hot surface The substation has got hot surfaces, which can cause skin burns. Please be extremely cautious in close proximity to the substation. Warning of transport damage Before installation of substation, please make sure that the substation has not been damaged during transport. Sound level 55 db Corrosion protection All pipes and components are made of stainless steel and brass. The maximum chloride compounds of the medium should not exceed 300 mg/l. The risk of equipment corrosion increases considerably if the recommended permissible chloride compounds are exceeded. Delivery The HW 22 substation is delivered without cover as a standard. Optional substation equipment: - electronic temperature controller or self-acting thermostatic controller on DHW, - white-lacquered steel sheet cover. Transport and storage If the substation is stored before installation in a warehouse or any other room, make sure that the place is dry and heated. During transport of the substation to an installation place it is recommended to lift it with special straps attached to the bottom (by substation support construction). 2 VI.KS.C1.02 Danfoss 08/2006 DH-SMT/PL

Mounting The substation must be installed and connected by authorized service personnel. Installation must be in compliance with the local standards and regulations. Keep adequate space around the substation for mounting and maintenance purposes. Prior to the HW 22 installation all substation pipes and connections should be cleaned and rinsed. Due to vibrations during transport all connections must be checked and tightened before the substation is installed. Heat meter assembly, fitting piece Substation is equipped with a fitting piece for insertion of heat meter. Assembly of heat meter: Loosen nuts of fitting piece, remove fitting piece and replace with heat meter. Mount the heat meter according to the medium flow direction. After each mounting of heat meter remember to check all threaded connections. Pipes connections Internal installation and district heating* pipes connections must be made by means of threaded or welded connections. Connections: 1 District heating (DH) return 2 District heating (DH) supply 3 Circulation DHW 4 Domestic cold water (DCW) 5 Domestic hot water (DHW) 6 Heating (HE) return 7 Heating (HE) supply Connection sizes: DH DCW + DHW + HE Circulation G 1 (int. thread) G 1 (int. thread) G 1 (int. thread) Dimensions (mm): Without cover: H 1100 x W 720 x D360 With cover: H 1100 x W 740 x D 400 * District heating (DH) - In the following DH is specified as the heat source for the substations. However, also other heat sources such as an oil or gas boiler or solar heating etc. could be used as the primary supply for the fitted substations, enabling the Danfoss Redan substations to be used in numerous schemes with different energy sources, depending on the local operating conditions. In order to simplify we have decided to use DH as designation for the primary supply. DH-SMT/PL VI.KS.C1.02 Danfoss 08/2006 3

Electrical connection Standard substation: Connect pump to main supply (1x230 V) according to local standards. Substation equipped with electronic controller: The electronic controller is electronically connected to the actuator, sensors and the pump, - ending up in a CEE-plug connection for main supply (1x230V) and earth grounding. Filling, start-up Prior to the HW 22 installation all its pipes and connections should be cleaned and rinsed. Before starting-up, check if: - pipes are connected according to the circuit diagram, - release valves are shut-off, - threaded connections are tightened. The heat exchanger must be filled with water so that the pressure slowly reaches the working pressure. After that the shut-off valves should be opened and the operation of the heat exchanger must be observed (e.g. temperatures, pressure, thermal expansion, leakages). If the heat exchanger operates unproblematically, it can be taken into continuous use. All Danfoss heat exchangers and substations have been pressure tested prior to delivery. Control 1. Differential pressure controller The differential pressure controller reduces the fluctuating pressure in the district heating network to a small and invariable operating pressure in the substation. The differential pressure controller is preset from factory and should not be adjusted afterwards. If a later adjustment of the differential pressure is necessary, please refer to producer instructions for differential pressure controller. The required room temperature is controlled on your radiator thermostats (fixed setting throughout the year). It is recommended that all radiators are opened a bit in each room. 2. HE temperature control The temperature of the heating supply is controlled automatically with weather compensation. The required room temperature is controlled on your radiator thermostats. It is recommended that all radiator thermostats are set on minimum setting in each room. Weather compensation The HE temperature is controlled by weather controller with settings card, controlling circulation pump and actuator operation of indirect flow. Weather controller is also equipped with an outdoor temperature sensor and sensors of HE flow. The controller is ready from factory to control of selected HE system. It is possible to make own settings/to insert set value for daily usage both in basic configuration and in extended service settings. Additional control should be made in accordance with producer instructions for the mounted controller. 4 VI.KS.C1.02 Danfoss 08/2006 DH-SMT/PL

3. Operation in summer and winter season, circulation pump, substation start-up, maintenance Summer season, circulation pump In summer season the circulation pump should be switched off and simultaneously the shut-off valve of HE supply should be closed (ball-valve placed on HE supply, first connection to your right). It is recommended to start-up the circulation pump (for a few minutes) once a month during the summer period; the shut-off valve of HE supply must be shut. Winter season, substation start-up - open shut-off valves, - set the pump at highest speed of rotation before start-up, - switch-off the pump and vent the installation after the radiators have been warmed, - set the pump at lowest speed of rotation in consideration of electricity consumption and heating comfort. Normally the change-over switch is set in the centre position (default), however for systems with floor-heating or one-pipe systems it may be necessary to turn the change-over switch upwards (clockwise). Higher speed of rotation is used only if the heating requirement increases. 4. HE manometer The HE manometer indicates the pressure value in HE system. The pressure during operation should be 1-1,5 bar. If the pressure drops below 1 bar, water must be added to the system. The operating pressure should never exceed 1,5 bar. 5. Expansion vessel (not part of the delivery) Expansion vessels are designed for operation in self-contained heating and cooling systems. When water in the system is heated it will expand and the task of the expansion vessel is to accommodate the increased volume of water, as well as to limit the pressure increase to defined maximum value. During decrease in temperature the task of the expansion vessel is to ensure pressure compensation by supplying previously accommodated water to the installation. For information about regulation or maintenance please refer to instructions for installed expansion vessel. DH-SMT/PL VI.KS.C1.02 Danfoss 08/2006

6. DHW temperature control The DHW temperature can be controlled by self-acting thermostatic valve(s) or electronic controller. Self-acting thermostatic controller The DHW temperature can be controlled by self-acting thermostatic valve, which closes on rising temperature. Setting changes: Turning the setting knob counterclockwise increases the temperature, turning it clockwise reduces the temperature. The scale is graduated with reference values, i.e. the temperature cannot be read from the scale, but must be read from a thermometer placed near the sensor in the medium to be temperature-controlled. Appoximate termostat scale settings : 1 = 20 C 2 = 35 C 3 = 50 C 4 = 60 C 5 = 70 C Electronic temperature controller The DHW temperature can be controlled by electronic controller, controlling DHW circulation pump and actuator operation of indirect flow. Electronic controller is also equipped with a sensor of DHW flow. The controller is ready from factory to control of selected DHW system. It is possible to make own settings/to insert set value for daily usage both in basic configuration and in extended service settings. The control of substations equipped with electronic controller should be done in accordance with producer instructions for the mounted controller. 7. Safety valve The safety valve s task is to protect the substation from pressures exceeding the permissible pressure. The blow-off pipe of the safety valve must not be closed. The blow-off pipe outlet should be placed so that it provides safety relief and it is possible to observe water dropping from the safety valve. It is advisable to check the operation of the safety valve by turning the valve head into the indicated direction, every six months. 8. Filters Filters should frequently be cleaned from sediments by authorized personnel, according to producer s instructions and dependent on the substation s operating conditions. VI.KS.C1.02 Danfoss 08/2006 DH-SMT/PL

Maintenance It is necessary to check and maintain the substation on a regular basis in order to keep it in good operating condition. The frequency of the maintenance and service inspections should be according to system manufacturer specifications and local legislation. However, maintenance inspections should take place at least twice each year (before and after the heating season). In addition to the check of the substation as to its functionality, it is also recommended to check if the following system parameters are compliant with the requirements of the system manufacturer and local regulations: - no leakages, - correct temperatures in the distribution network, - stable district heating supply and return temperatures, - correct cooling of the district heating supply, - DHW temperature (requested temperature should be in accordance with the local regulations), - pressure drops in filtering and water conditioning plants (filters, sludgers etc.), - pressure drops in the heat exchangers (primary and secondary side of heat exchangers). The substation operator should consider the above parameters and prepare written maintenance reports. Service inspections by authorized personnel are usually more precise (complex) than user maintenance inspections and the intervals between them are longer. DH-SMT/PL VI.KS.C1.02 Danfoss 08/2006 7

Troubleshooting DHW If operating disturbances occur, the following basic features should be checked before carrying out actual troubleshooting: - the installation is connected to electricity - pump and automatic controls (does not apply to all units) - the strainer on the district heating supply pipe is clean - the supply temperature of the district heating is at the normal level (summer, at least 60 C - winter, at least 70 C) - the differential pressure is higher than or equal to the normal (local) differential pressure in the district heating network - if in doubt, ask the district heating plant. Problem Possible cause Solution Insufficient pressure on the hot water Long wait for DHW No hot water Temperature too low Temperature too high Variation in temperature Declining temperature during draining Lime scale precipitation in plate heat exchanger for DHW (= poor cooling at high load) Strainer in cold water meter clogged. Circulation pump out of operation. Strainer in district heating supply clogged. Defective thermostat - possibly dirt in the valve housing. Defective actuator - possibly dirt in the valve housing. Automatic controls wrongly set or defective - possibly power failure. As above. Non-return valve on the circulation line defective (leads to mixing - and the circulation water pipes are getting cold during tapping. Thermostat defective- possibly dirt in the valve housing. Actuator defective - possibly dirt in the valve housing. Automatic controls wrongly set or defective. The non-return valve on the circulation line is defective (leads to mixing and the circulation water pipes get cold during tapping). Automatic controls wrongly set. Lime scale precipitation in plate heat exchanger for DHW (possibly an underscaled exchanger). Replace plate heat exchanger. Clean strainer - possibly in consultation with the water supply co. Check whether the pump is running - whether the pump is receiving power. Check that there is no air in the pump housing - see pump manual. Clean strainer. Check the operation of the thermostat clean the valve seat if required. Check the operation of the actuator - clean the valve seat if required. Check that the setting of the controller is correct - see separate instructions. Check the power supply. Temporary setting of motor to manual control - see instructions on automatic controls. As above. Replace non-return valve. Check the operation of the thermostat - clean the valve seat if required. Check the operation of the actuator - clean the valve seat if required. Check that the controller has been correctly set - see separate instructions. Replace non-return valve. Check that the controller has been correctly set - see separate instructions. Replace plate heat exchanger. 8 VI.KS.C1.02 Danfoss 08/2006 DH-SMT/PL

Troubleshooting HE If operating disturbances occur, the following basic features should be checked before carrying out actual trouble shooting: - the substation is connected to electricity, - the strainer on the district heating supply pipe is clean, - the supply temperature of the district heating is at the normal level (summer, at least 60 C - winter, at least 70 C), - the differential pressure is higher than or equal to the normal (local) differential pressure in the district heating network if in doubt, ask the district heating plant, - there is pressure on the system. Problem Possible cause Solution Strainer clogged on DH or HE side Clean the gate/strainer. (radiator circuit). The filter in the district heating meter clogged. Defective or unadjusted differential pressure controller. No heat Sensor defective or possibly dirt in the valve housing. Automatic controls, if any, wrongly set or defective - possibly power failure. The pump out of operation. The pump is set at too low speed of rotation. Pressure drop - the manometer on the radiator circuit shows lower than recommended operating pressure. Air pockets in the system. Clean the filter (after consulting the district heating plant). Check the operation of the differential pressure controller clean the valve seat if required. Check the operation of the controller and the actuator. Check if the setting of the controller is correct see separate instructions. Check the power supply. Temporary setting of motor to manual control see instructions on automatic controls. Check if the pump is receiving power and that it runs. Check if there is no air trapped in the pump housing - see pump manual. Set the pump at higher speed of rotation. Fill the system with water and check the functioning of the pressure expansion vessel if required. Air the installation thoroughly. Uneven heat distribution. DH supply temperature too high. DH supply temperature too low. Poor cooling Air pockets in the system. Wrong setting of thermostat or of automatic controls, if any. Defective regulator. The regulator does not react as it should in accordance with the instructions. Defective sensor on self-acting thermostat. Wrong setting of automatic controls, if any. Defective controller. The controller does not react as it should in accordance with the instructions. Defective sensor on self-acting thermostat. Wrong placement/fitting of outdoor temperature sensor. Strainer clogged. Too small heating surface/too small radiators in relation to the total heating requirement of the building. Poor utilization of existing heating surface. The system is single-pipe. Air the installation thoroughly. Adjust automatic controls, - see instructions for automatic controls. Call automatic controls manufacturer or replace the regulator. Replace thermostat, - or sensor only. Adjust automatic controls see instructions for automatic controls. Call in automatic controls manufacturer or replace controller. Replace thermostat or sensor only. Place/fit an outdoor temperature sensor correctly. Clean gate/strainer. Increase total heating surface. Make sure the heat is distributed evenly across the full heating surface. It is recommended to avoid fully opened thermostats on some radiators and fully shut-off thermostats on others. Higher temperature at the top and lower temperature at the bottom part of radiators means that the system operation is correct. It is extremely important too keep the supply temperature the radiators as low as ever possible, while maintaining a reasonable level of comfort. The system should feature electronic controls as well as return sensors. DH-SMT/PL VI.KS.C1.02 Danfoss 08/2006 9

Danfoss Redan A/S Sindalsvej 33-35 DK-8240 Risskov, Denmark Phone: +45 87 43 89 43 Fax: +45 87 43 89 44 redan@danfoss.com www.redan.danfoss.dk 10 VI.KS.C1.02 Danfoss 08/2006 DH-SMT/PL