N2 BLAST Datasheet SUREFIRE double interlock c/w N 2 Blast Nitrogen generating system Self contained unit

Similar documents
N2 BLAST Datasheet Preaction double interlock, Electric/Pneumatic c/w N 2 Blast Nitrogen generating system Self contained unit

N2 BLAST Datasheet Preaction double interlock, Electric/Pneulectric c/w N 2 Blast Nitrogen generating system Self contained unit

TotalPac 3 Double interlock Preaction, Electric/PneuLectric release Self-contained system

Datasheet. Dry-pipe Vacuum Sprinkler System, Electric Release Self contained unit. Features. FIREFLEX VACTEC description

Datasheet. Vacuum Double-interlock Preaction System, Electric Release Self contained unit. Features. FIREFLEX VACTEC description

TotalPac 3 Single interlock Firecyle III Preaction Self-contained system

TotalPac 3 Firecyle III Deluge Remote controlled system

TotalPac 3 Wet pipe system c/w retard chamber

TotalPac 3 Deluge, Electric release Self-contained system

TotalPac X Single interlock SUREFIRE system

TotalPac X Firecycle III Preaction Double interlock system

FireFlex DUAL Double Interlock, Self-contained system

TotalPac 3 Single interlock Preaction, Electric release Self-contained system

TotalPac 3 Non interlock Preaction, Electric release Self-Contained system

FireFlex 1230 Self-contained system

TOTALPAC2 Integrated Fire Protection System

Advanced Integrated Fire Protection Systems TOTALPAC 2. Owner's Operation and Maintenance Manual FIRECYCLE III. September 2009 FM-086G-0-5E

TECHNICAL DATA. multi-hazard. model vfr400. Release Control Panel 290a. January 16, 2014

TECHNICAL DATA SINGLE INTERLOCKED PREACTION SYSTEM WITH ELECTRIC RELEASE

Not to be distributed outside of FM Approvals and its affiliates except by Customer APPROVAL REPORT

Technical Data. Approvals The 1-1/2 in. to 8 in. (DN40 to DN200) DV-5 Red-E Cabinets are UL Listed and C-UL Listed with the following system types:

TECHNICAL DATA DOUBLE INTERLOCKED PREACTION SYSTEM WITH ELECTRIC/ PNEUMATIC RELEASE 1. DESCRIPTION 2. LISTINGS AND APPROVALS 3.

Technical Data. Approvals The 1-1/2 thru 8 inch (DN40 thru DN200) DV-5 Red-E Cabinets are UL Listed and C-UL Listed with the following system types:

TECHNICAL DATA DOUBLE INTERLOCKED PREACTION SYSTEM WITH ELECTRIC/ PNEU-LECTRIC RELEASE

TECHNICAL DATA. 319a. January 27, 2012

DV-5 Red-E Cabinet Integrated Deluge Fire Protection Package. General Description. Technical Data. Page 1 of 6 AUGUST 2018 TFP1300. Worldwide Contacts

Technical Data. Working Pressure Range 20 to 250 psi (1,4 to 17,2 bar)

Worldwide Contacts.

TECHNICAL DATA OBSOLETE

Specification/ Data Sheet

TECHNICAL DATA 1. SYSTEM DESCRIPTION 2. SYSTEM OPERATION 3. INSTALLATION. Page 1 of 5

Pre-Pack INTEGRATED PRE-ACTION SYSTEM

30.45 Electric Release PDRP-2001

Instructions for Installation, Operation, Care and Maintenance

Instructions for. Care and Maintenance 10 psi (0,7 bar) Pneumatic Supervising Pressure. Single Interlock

SECTION DRY PIPE SPRINKLER SYSTEMS MODEL F SERIES DRY VALVE

Deluge System. Pneumatic Release. Deluge System. Pneumatic Release

TECHNICAL DATA. Humidity: 85% Relative Humidity (non-condensing) at 90 F (32 C) maximum.

Deluge & Preac tion Systems

Operation & Maintenance Manual

Model DV-5 Red-E Cabinet 1-1/2 thru 8 Inch (DN40 thru DN200), 250 psi (17,2 bar) Integrated Preaction Fire Protection Package General Description

Model DV-5 Red-E Cabinet 1-1/2 thru 8 Inch (DN40 thru DN200), 250 psi (17,2 bar) Integrated Deluge Fire Protection Package General Description

SECTION DRY PIPE SPRINKLER SYSTEMS MODEL G SERIES DRY VALVE

SINGLE INTERLOCK, SUPERVISED PREACTION SYSTEM WITH ELECTRIC RELEASE

1935, Lionel-Bertrand Blvd. Boisbriand, Quebec, Canada J7H 1N8 Tel.: (450) Fax: (450) Toll Free: (866)

TECHNICAL DATA OBSOLETE

DOUBLE INTERLOCK, PREACTION SYSTEM WITH ELECTRIC/PNEUMATIC RELEASE

TECHNICAL DATA. Factory Mutual Approval is pending for the system as a whole.

SINGLE INTERLOCK, SUPERVISED PREACTION SYSTEM WITH WET PILOT ACTUATION

VIZOR Electronic Dry Pipe Accelerator (EDPA) Quick-Opening Device for Dry Pipe Systems General Description

MR-2602 Two Zone Fire Alarm Control Panel

ECS Protector Nitrogen Generator PGEN-40FK/PGEN-50FK/PGEN-60FK PGEN-40M/PGEN-50M/PGEN-60M

TECHNICAL DATA DELUGE SYSTEM CONTROLLED BY ELECTRIC RELEASE

OPEN SPRINKLER SYSTEM

Commercial and Light Industrial Fire Alarm Control Panel

ECS Pre-Engineered Nitrogen Generator. ECS Pre-Engineered Wall Mount Nitrogen Generator PGEN-10/(PGEN-10E)

BERMAD Fire Protection

Installation Manual CFP-105. Fire Alarm Control Panel. Version 1.0

FireSystem 2000 Commercial and Light Industrial Fire Alarm Control Panel

SPECIFICATION MICROMIST FIRE SUPPRESSION SYSTEM WITH SHP-PRO CONTROL PANEL

Data Sheet Fire Safety & Security Products. System Overview. Initiating Circuits SXL-EX FACP 7906

DIVISION 21 FIRE SUPPRESSION SECTION FIRE PROTECTION SPECIALTIES

Model DDX Deluge Valve

ECS Protector Nitrogen Generator. ECS Protector Nitrogen Generator PGEN-30. Specifications

PSN-1000 & PSN 1000(E) Installation Manual

ECS Pre-Engineered Nitrogen Generator. ECS Pre-Engineered Wall Mount Nitrogen Generator PGEN-3/(PGEN-3E) PGEN-5/(PGEN-5E)

Electric Release Panel Wiring Tips

PRICE BID. UNIT QTY Rate in Figure Rate in words Amount DESCRIPTION OF ITEM D: FIRE PROTECTION SYSTEM

Power Flame Incorporated

INTELLIGENT FIRE ALARM CONTROL PANEL

SECTION PREACTION SPRINKLER SYSTEMS

Discontinued Product

Becoming an Expert on Dry-pipe, Preaction, and Deluge Sprinkler Systems

AEGIS FEATURES DESCRIPTION. Conventional Fire Alarm-Suppression Control Unit. Effective: March Programmable Relays

SECTION SPRINKLER SYSTEMS

TECHNICAL DATA OBSOLETE

good things in small packages

CONVENTIONAL FIRE ALARM CONTROL UNITS. MR-2300 SERIES Fire Alarm Control Units MEA

Release Control Fire Alarm Systems

CONSTRUCTION REQUIREMENTS

VSR-M REPLACEMENT Waterflow Switch for Globe Sprinkler Model UMC Manifold

DELUGE VALVE MODEL: SD-DVH2 TECHNICAL DATA TRIM DESCRIPTION DESCRIPTION VALVE OPERATION. 82 ASTM A 216 WBC.

LifeAlarm Fire Alarm Control Panels

POWERPATH PS-8 (105531) PS-8E (100263) PS-6 (105530) PS-6E (100262)

SPECIFICATION MICROMIST FIRE SUPPRESSION SYSTEM WITH CHEETAH Xi 50 CONTROL PANEL

Technical Data. Minimum Inlet Supply Pressure All MCC Models...0 psi. Minimum Inlet Supply Capacity Match system design calculations

Installation Guide for models:

Technical Data. Minimum Inlet Supply Pressure All MCC Models...0 psi. Minimum Inlet Supply Capacity Match system design calculations

MS-4012/4024 and CMS-4012/4024. Instruction Manual for the. Fire Alarm Control Panels

Installation Guide for models:

Addressable Fire Alarm Control Panel

SPECIFICATION FOR A TOTAL FLOOD ECARO-25 TM CLEAN AGENT FIRE SUPPRESSION SYSTEM FOR USE WITH THE SHP PRO CONTROL PANEL SYSTEM

RAPID RESPONSE Model RCP-1 Residential Control Panel 1 or 1-1/2 Inch (DN25 or DN40), 175 psi (12,1 bar) General Description.

SECTION WET-PIPE SPRINKLER SYSTEMS EASY RISER CHECK VALVE

AutoTest VSR (VSR-AT) (EU) Vane Type Waterflow Alarm Switch With Electronic Retard and Auto Test Feature

FireNET Plus Wiring Instructions

TECHNICAL DATA. model c-2

CONVENTIONAL FIRE ALARM CONTROL PANELS. SFC-200 Series Fire Alarm Control Panels MEA. Features. Description

AL802ULADA. NAC Power Extender. Installation Guide. (See Application Guide for additional information) Rev

B. The sprinkler system shall be designed to meet the more stringent of the requirements of NFPA 13 and FM Global requirements.

Transcription:

SUREFIRE double interlock c/w N 2 Blast Nitrogen generating system FireFlex N 2 Blast description The FIREFLEX N2 Blast integrated system consists of an integrated SUREFIRE double interlock preaction automatic sprinkler system combined with a Nitrogen generating system, factory-assembled in a single cabinet. All the necessary components are integrated. The FIREFLEX N2 Blast is fully tested at factory. The FIREFLEX N2 Blast System uses the N2 Blast Nitrogen generator system Type 1 FPS-250 or FPS-750 system, made by South-Tek Systems. All the deluge valves are rated up to a maximum of 250 psi WWP (1724 kpa) max. and are available in the following diameters: 1½" (40 mm) 3" (80 mm) 6" (150 mm) 2" (50 mm) 4" (100 mm) Warning: 6" (150 mm) available with N2 Blast Type 1 FPS-750 only. Features Inhibits corrosion with 98%+ pure Nitrogen Trouble-free design for safe and easy application Available in 2 cabinet sizes Uses South-Tek N2 Blast Best value in nitrogen generation technology Limits the liability of early pipe replacement Uses the Viking deluge valve Trim is fully assembled and tested at the factory All trims are galvanized steel, Listed and Approved for 250 psi (17.2 bar) service maximum Quick connections to water supply and drain on left side, and sprinkler riser on top of unit, all available with grooved end or flanged fittings No open drain cup inside unit Separate unlocked access hatch to emergency manual release Compact, aesthetic and easy to move User-friendly standardized owner's manual with every unit Unique serial number on every unit Uses UL, ULC and/or FM Approved components Designed in accordance with NFPA Standards Sturdy 14 gauge steel cabinet painted fire red with oven baked polyester powder on phosphate base Textured rust proof finish Neoprene gasket on all doors to eliminate vibrations Manufactured under ISO-9001 quality control procedures Prewired to the Viking VFR-400 releasing control panel 1 of 16 FM-076D-0-125C

SUREFIRE double c/w N 2 Blast Nitrogen generating system System configurations SUREFIRE Double Interlock Preaction combined with N2 Blast Type 1 FPS-250 (250 gallons system) SUREFIRE Double Interlock Preaction combined with N2 Blast Type 1 FPS-750 (750 gallons system) Systems hydraulic limitations The information contained herewith is for estimation and evaluation purposes only. Its use remains the responsibility of the designer. Designers should refer to the appropriate NFPA Standards and any other applicable codes for their final design. Also refer to FireFlex Systems Inc. appropriate user manuals and to manufacturer's data sheets for additional details. Systems limitations indicated below are nominal flow limitations. Piping Equivalent Lengths w/o System size Usage Range shut off valve (in.) (gpm) Piping Equivalent Lengths c/w shut off valve (m.) (ft.) (m.) (ft.) GPM 1½ 0 210 8.3 27.2 8.5 27.9 272 2 0 360 11.65 38.2 11.85 38.9 272 3 100-700 16.8 55.1 20.33 66.7 762 4 200 1400 21.89 71.8 25.33 83.1 1597 6 400-3500 33.28 109.15 37.28 122.3 1597 Sequence of operation Drain flow @ 250 PSIG w.p. SUREFIRE operation 1. The activation of the electric detection AND the opening of an automatic sprinkler is necessary to cause the deluge valve actuation. 2. The activation of the electric detection alone will not cause water to enter the system piping. 3. The opening of an automatic sprinkler OR damage to system piping without the detection condition satisfied will activate the "very low air" alarm pressure switch, The normally open solenoid valve (F2) will be activated but water will not enter the system piping. 4. Activation of the electric detection AND the "very low air" alarm pressure switch will activate will activate solenoid valves (F1) & (F2), causing the deluge valve to open and allowing water to enter the system piping. The alarm pressure switch (C1) will activate. Water will flow out of any open sprinklers and/or any openings on the system. 5. Operation of the emergency manual release will depressurize the priming chamber, causing the deluge valve to open and allowing water to enter the system piping and water will discharge through any open sprinklers.the alarm pressure switch (C1) will activate. 6. When AC Power and DC power supplied by the back up batteries is lost, the system shall fail-safe and function as a dry pipe system. The normally open solenoid will remain open, and the pneumatic actuator is the only device holding the priming water in the priming chamber. When a sprinkler operates, air pressure is lost and the pneumatic actuator opens. Priming water is drained from the priming chamber, causing the deluge valve to open and allowing water to enter the system piping. The alarm pressure switch will activate. Water will flow out of any open sprinklers and/or any openings on the system. 7. Trouble condition on detection zones, or "very low air" alarm zone, or the normally closed solenoid output disables the normally open solenoid and the pneumatic actuator is the only device holding the priming water in the priming chamber. When a sprinkler operates, air pressure is lost and the pneumatic actuator opens. Priming water is drained from the priming chamber, causing the deluge valve to open and allowing water to enter the system piping. The alarm pressure switch will activate. Water will flow out of any open sprinklers and/or any openings on the system. N2 Blast Nitrogen generator system operation 1. The initial air supply fill of the piping system within 30 minutes as per NFPA 13 is accomplished using the initial fill air compressor. This compressor is equipped with a factory-adjusted ON/OFF pressure switch which is tied into the sprinkler system piping. It is factory-set at 20 and 35 psi for the cut-in and cut-out pressures respectively. There is a "low air" supervisory pressure switch which monitors system piping air/nitrogen pressure at all times. It is factory-set at 25 psi to provide a "low air" supervisory signal and 23 psi to provide a "very low air" supervisory signal. 2. The nitrogen generation/maintenance air compressor is supplied as an integral part of the STS N 2-Blast Nitrogen Generation System. It is equipped with a factory-adjusted ON/OFF pressure switch which is tied into the nitrogen storage tank. It is factory-set at 65 psi and 75 psi for the cut-in and cut-out pressures respectively. The Viking D-2 Air Pressure Maintenance Device is installed and factory-adjusted to 35 psi (normal system air/nitrogen pressure) downstream of the nitrogen storage tank. As the system continually purges with Nitrogen, the APMD will continually draw from the Nitrogen storage tank to maintain supervisory pressure (35 psi). Should the N 2-Blast generator run for more than 6 hours consecutively, the Leak Detection System (LDS) will automatically shut it down and activate a trouble contact. 3. The air and nitrogen supply systems are fully integrated and fully automatic in the FireFlex - N 2-Blast. No shutoff or bypass valve is required. The nitrogen generator is equipped with a BlastOff Leak Detection System (LDS). Should the nitrogen generator compressor fail or a leak occur that can not be compensated by the nitrogen generating system, the preaction system air compressor will act as a back-up and start-up at 20 psi system pressure. FM-076D-0-125C 2 of 16

SUREFIRE double interlock c/w N 2 Blast Nitrogen generating system Standard equipments Releasing control panel 120 VAC / 60 Hz, 165VA. 12VDC / 12Ah batteries. (factory installed) 12VDC / 18Ah batteries. (optional) The releasing control panel integrated into the TOTALPAC 3 cabinet is Viking's Model VFR-400. This panel includes four Class B, programmable detection zones (optional Class A); two Class B supervisory zones and four Class B, programmable output circuits (optional Class A). It is also provided with menu driven programming, including a specific program assigned at the factory. The panel is compatible with many types of fire alarm & supervisory devices such as linear heat detectors, spottype heat and smoke detectors, water flow and release indicators, low and high air pressure switches, manual pull stations. The releasing control panel also includes an alphanumeric display with 2 lines of 16 characters describing all the system conditions, as well as a set of red and yellow LED lamps individually indicating each of the alarm and trouble conditions of the system Easy to operate control buttons are also provided to activate and operate the system's various functions. Releasing circuit disconnect switch The releasing circuit disconnect switch is used to disable the releasing solenoid. When the key is set to Disable, the releasing solenoid will be disconnected from the control panel s releasing circuit, causing a trouble signal and preventing accidental discharge during maintenance or inspection. Deluge valve The Viking Model F-1 Deluge Valve is a quick-opening, differential diaphragm flood valve with one moving mechanism. The deluge valve is used to control water flow in preaction sprinkler systems. The valve is held closed by system water pressure trapped in the priming chamber, keeping the outlet chamber and system piping dry. In fire conditions, when the releasing system operates, pressure is released from the priming chamber. The deluge valve clapper opens to allow water to flow into the system Water supply control valve The water inlet control valve is a supervised, indicating butterfly valve. Purpose of this vale is to manually shutoff the preaction system. 3 of 16 FM-076D-0-125C

SUREFIRE double c/w N 2 Blast Nitrogen generating system Standard equipments (continued) Preaction riser check valve The Viking 1-½ and 2 spring loaded In-Line check valve is a general purpose rubber-faced check valve approved for use in fire-service systems. The Spring Loaded In-Line check valve is manufactured with a brass body, brass seat, and a rubber-faced clapper assembly. The Viking 3, 4 and 6 Easy Riser Swing check valve is a general purpose rubber-faced check valve approved for use in fire service systems. The valve is for use in preaction system risers. Low air supervisory switch The low pressure switches monitors the pressure within the sprinkler piping should a loss pressure of the air below 25PSI occurs, the pressure switch contacts transfer indicating low air supervisory signal. Should a loss pressure of the air below 23PSI occurs, the pressure switch contacts transfer indicating low air alarm signal. POTTER PS40-2A Solenoid valve The high pressure solenoid valve is a two-way type with one inlet and one outlet. It is a packless, internal pilot operated valve, suitable for use in releasing water pressure from the priming chamber of Viking Deluge Valves. The solenoid valve has floating diaphragm construction, which requires a minimum pressure drop across the valve to operate properly. Alarm pressure switch The alarm pressure switch monitors the water flow within the sprinkler piping. Should the Deluge Valve clapper opens to allow water to flow into the sprinkler piping. The alarm pressure switch will activate, indicating a water flow signal POTTER PS10-1A IN OUT FM-076D-0-125C 4 of 16

SUREFIRE double interlock c/w N 2 Blast Nitrogen generating system Standard equipments (continued) N2 Blast Nitrogen generator South-Tek Systems utilizes Membrane technology in the N2-Blast Corrosion Inhibiting Systems in order to efficiently separate Nitrogen molecules from the air we breathe. Membrane technology, used in our smaller applications, has a simple air flow design, is wall-mounted and easy to service. PSA technology is more cost effective and energy efficient in larger Fire Protection Systems, those requiring more Nitrogen to compensate for the NFPA acceptable leak rate. BlastOff Leak detection system Unless the leak rate is catastrophic, the supervisory low pressure alarm on the FPS will not activate. Minor leaks cause the air compressor and N2-Blast to run excessively in order to maintain supervisory pressure. The unnecessary additional run-time decreases the lifespan of the equipment. The Patent Pending BlastOff - Leak Detection System is designed to detect significant leaks before they compromise the FPS and the Nitrogen Generation System. It has an internal audible alarm and dry contact for wiring into the Building Monitoring System (BMS) and will also alarm if the air compressor or the N2- Blast is not working properly. Nitrogen generator storage cylinder Type 1 Nitrogen Generation Systems include a 16 gallon Nitrogen receiver tank (12.2 dia x 44.8 H). Nitrogen generated by the N2-Blast is stored in the tank, and then sent to the sprinkler system through the Nitrogen air pressure maintenance device. N2 Blast AutoPurge System High purity Nitrogen must be equally distributed throughout the entire sprinkler piping system in order to effectively inhibit corrosion. The Patent Pending AutoPurge System provides a low volume, constant purge of Nitrogen within sprinkler piping. The rate in which gas is evacuated from the sprinkler piping is within NFPA guidelines and allows breathing to occur. The AutoPurge System also assists in drying out the residual water from a hydro test. Computational Fluid Dynamics modeling proves that this is the most effective way to ensure that high purity Nitrogen reaches all branches within the sprinkler piping. Install one AutoPurge System per system at a high point. There is a Label on one side of the housing that lists the proper setting for a variety of zone sizes. The Label list: Gallons in Zone, and APS Flow Setting. The Flow Setting is labeled from A-E and has three Settings in between each letter. Nitrogen generator air pressure maintenance device FIREFLEX N2 Blast use the Viking Model D-2 Air Pressure Maintenance Device (APMD) which is a pressure regulator that automatically reduces the supply air pressure to a preset requirement when connected to a constantly maintained air supply. The APMD is used to regulate the nitrogen pressure to 35 psi in the sprinkler piping at the specified system pressure for FIREFLEX N2 Blast Single interlock preaction system. 5 of 16 FM-076D-0-125C

SUREFIRE double c/w N 2 Blast Nitrogen generating system Optional preaction equipments Shut-off valve & sight glass (optional) The Shut-off Valve & Sight Glass Option is intended to be used for applications where testing of the system operation without filling the sprinkler piping network is desirable and where it is critical that all functions of the preaction system be tested under actual discharge conditions. Main drain valve Sight glass assembly Shut-off valve Riser check valve Semi-flange inlet / outlet (optional) When required by the user, FIREFLEX N2 Blast units can be provided in a semi-flanged configuration. The semi flanged option provides flanged fittings only on the water inlet pipe (left side) and on the system riser outlet. The drain manifold is provided with a threaded connection (left side). The rest of the fittings are the same as usual with the main components being provided in the standard flanged / grooved configuration. Flange fitting outside cabinet Point flashlight HERE Deluge valve Riser check valve Main water supply control valve Deluge valve FM-076Z-0-4B-1 Anti-column device option The model LD-1 anti-column device is an optional trim component designed for use with preaction sprinkler systems. The anti-column device automatically prevents an unwanted water column from establishing within the system riser. On preaction sprinkler systems the anticolumn device prevents water from columning downstream of the easy riser check valve. Threaded drain output Flange fitting outside cabinet FM-076Z-0-4B-2 Main water supply control valve From Sprinkler Riser To Drain Collector FM-061H-0-146A FM-076D-0-125C 6 of 16

SUREFIRE double interlock c/w N 2 Blast Nitrogen generating system Preaction system - Air supply Direct air compressor (Style A ) Used only for the sprinkler piping network of the preaction system. Air supply style "A" includes the air compressor mounted inside the FIREFLEX N2 Blast cabinets with its supervisory trim and options. Compressors are of the tankless, oiless piston type and are factory piped to the sprinkler system riser, all within the FIREFLEX N2 Blast cabinets. Compressors are available in four (4) sizes: 1/6HP 1/2HP 1/3HP 1HP This section replaced by Dehydrator option (when used) E4 (plugged with SureFire trim) Copper tubing TO OPTIONAL ACCELERATOR (plugged when not used) 2 TO DRAIN COLLECTOR 1 TO SPRINKLER RISER Pressure relief valve Compressor Service Factor Amp (S.F.A) rating Compressor Size (HP) 115Vac / 60Hz 230Vac / 60Hz 1/6 5.0 Amp. 2.5 Amp. 1/3 7.4 Amp. 3.7 Amp. 1/2 10.0 Amp. 5.0 Amp. 1 18.0 Amp. 9.0 Amp. 115 / 220 Vac 60Hz Compressor selection Table: H.P CFM @ 40 PSI System capacity to fill system to 20 PSI in 30 minutes * 1/6 1.33 250 gal. 1/3 2.61 500 gal. 1/2 4.06 730 gal. 1 7.40 1230 gal. * For systems with maximum water supply pressure up to 250 PSI (1724 kpa) WARNING The information contained herewith is for estimation and evaluation purposes only. Its use remains the responsibility of the designer. 3 TO PNEUMATIC ACTUATOR (plugged when not used) CONTRACTOR'S HYDROSTATIC TEST PORT (system side) FM-061H-0-118C Air Pressure Maintenance Device (Style B ) Used only for the sprinkler piping network of the preaction system, when an external air supply is provided by others (tank mounted compressor or plant air) and piped to the air inlet port of the unit. Air supply style "B" provides an Air Pressure Maintenance Device (APMD) trim, factory mounted in the FIREFLEX N2 Blast cabinets. This section replaced by Dehydrator option (when used) E4 (plugged with SureFire trim) TO PNEUMATIC ACTUATOR (plugged when not used) 3 Contractor external Air or Nitrogen connection TO OPTIONAL ACCELERATOR (plugged when not used) 1 TO SPRINKLER RISER FM-061H-0-119B CONTRACTOR'S HYDROSTATIC TEST PORT (system side) 7 of 16 FM-076D-0-125C

SUREFIRE double c/w N 2 Blast Nitrogen generating system Details & field wiring diagrams P & ID Autopurge System Sprinkler N2 Blast Compressor Preaction Compressor Air Maintenance Device/s (AMD/s) Supplied by Fireflex Riser towards the nozzles Tank Provided with brackets and Strap Low Air Pressure Switch Preaction Air Kit Preaction System Nitrogen Air FM-076D-0-125C 8 of 16

SUREFIRE double interlock c/w N 2 Blast Nitrogen generating system Cabinet with main components, shown without door(s) FM-06LM-0-1A-4 9 of 16 FM-076D-0-125C

SUREFIRE double c/w N 2 Blast Nitrogen generating system Trim diagram E4 F5 E9 FIELD CONNECTION TO SPRINKLER PIPING NETWORK To Air Supply System Trim C1 1 D2 F4 B10 B8 C2 B5 D3 F1 A1 B11 F2 F3 To Air Supply System Trim 2 B7 B6 D1 B9 B13 FIELD CONNECTION TO OPEN DRAIN (left side only) B12 B3 B4 B2 B1 FIELD CONNECTION TO WATER SUPPLY (left side only) TotalPac Base (shown without enclosure) CONTRACTOR'S HYDROSTATIC TEST PORT (water supply side) FM-076Z-0-64A Trim Components: A1 Deluge valve B1 Priming valve B2 Strainer B3 1/16" Restricted orifice B4 Spring loaded check valve B5 Alarm test valve B6 Flow test valve B7 Drip check valve B8 Drain check valve B9 Pressure operated relief valve (PORV) B10 Emergency release valve B11 Priming pressure water gauge & valve B12 Water supply pressure gauge & valve B13 Clapper check valve C1 C2 D1 D2 D3 E4 E9 F1 F2 F3 F4 F5 Alarm pressure switch Connection to water motor gong (strainer supplied by contractor) Water supply control valve Riser check valve Main drain valve Air supervisory pressure switch Float-check assembly N.C. Solenoid valve 24Vdc N.O. Solenoid valve 24Vdc Pneumatic actuator Pneumatic actuator pressure gauge 5/64" Restricted orifice FM-076D-0-125C 10 of 16

SUREFIRE double interlock c/w N 2 Blast Nitrogen generating system Wiring diagram TBB WIRING IN CLASS B / STYLE B TBA DETECTION ZONE 1 5.1K EOLR 1 LINE 2 NEUTRAL 3 GROUND 4 GROUND 5 NEUTRAL 6 LINE 7 LINE 8 NEUTRAL 9 GROUND 120VAC, 60Hz AIR COMPRESSOR 1HP MAX WITH AIR OPTION "A" ONLY Refer to Local Electrical Codes for wiring size. MANUAL PULL STATIONS ZONE 4 WIRING OF INPUT POWER SOURCE NAC1 SILENCEABLE ALARM 5.1K 5.1K EOLR EOLR 1 2 3 4 5 6 7 8 9 10 11 12 CONTROL PANEL 100VA MAX N²BLAST UNIT 20A MAX Branch circuit for air compressor shall not be the same as the control panel power source. WIRING IN CLASS B / STYLE Y NAC2 NON SILENCEABLE WATERFLOW 5.1K EOLR 13 14 C TROUBLE NO NC C ALARM NO NC C SUPERVISORY NO C TBA 15 16 17 18 19 20 21 22 23 24 25 26 NOTES: Class A / Style D requires CA2Z modules. End-of-line devices are not required for Class A / Style D wiring. WATER FLOW NO 24VDC RESETTABLE OPTIONAL WIRING IN CLASS A / STYLE D DETECTION ZONE 1 MANUAL PULL STATIONS ZONE 4 1 2 3 4 5 6 7 8 TBC 24VDC NON RESETTABLE RS485 120 SHIELD 1 2 3 4 5 C MAIN VALVE NO NC LEGEND SMOKE DETECTOR HEAT DETECTOR MANUAL RELEASE BELL OR HORN DRY CONTACT END OF LINE RESISTOR CHICAGO OPTION LOS ANGELES OPTION 6 7 8 C 9 OPTIONAL SHUT-OFF VALVE NO NC 10 11 TBA POWER LIMITED 4-WIRE DETECTION CIRCUIT 1 2 25 26 24VDC COM UL-Listed 24VDC 4-Wire Smoke Detector CONTACTS RATED 3A, 30VDC RESISTIVE 24VDC COM UL-Listed 24VDC 4-Wire Smoke Detector 5.1K EOLR PAM-4 Power Supervisory Relay (EOL Relay) CONTACTS RATED: 5A, 1/6HP, 125/250VAC 0.5A, 250VDC 0.25A, 250VDC NOTE: Contact provided for connection to the building's central Fire Alarm Panel. NOTES: Control panel AC power source is supervised and non-power limited. All devices are shown in their normal supervisory state. Use dry contacts with power limited circuits only. FM-061H-0-235B Power Limited (supervised) Initiating Device Circuits Detection Zone 1, 2, 3, and 4. Max. loop resistance: 100 ohms End of line: 5.1K ohms, 1/4W Leave ELR (provided) on all unused circuits. Refer to Device Compatibility in the VFR-400 Releasing control panel Manual. Power Limited (supervised) Initiating Device Circuits Supervision Zone 1, and 2. Max. loop resistance: 100 ohms End of line: 5.1K ohms, 1/4W Leave ELR (provided) on all unused circuits. For dry contact supervisory devices such as tamper, low air, or high air switches. (Class-B only) Power Limited (supervised) Notification Appliance Circuits Output Circuit 1, 2, 3, and 4 Maximum operating voltage: 27Vdc (ripple: 0.3Vdc) Maximum usable current per circuit: 1.0A Total current available (all circuits): 2.5A Polarity is reversed in supervisory condition. Leave ELR (provided) on all unused circuits. Refer to Device Compatibility in the VFR-400 Releasing control panel Manual. Auxiliary Power 24Vdc Regulated Source Total current available: 0.2A Resettable for 4 wires smoke detectors WARNING Releasing control panel shall be supplied by a dedicated circuit breaker, as per NFPA 70, Section 760 and Canadian Electrical Code, Section 32. 11 of 16 FM-076D-0-125C

SUREFIRE double c/w N 2 Blast Nitrogen generating system Optional electrical equipment's Relay module ARM-44 The ARM-44 is an auxiliary relay module designed to operate with the Viking VFR-400 releasing control panel to provide 4 independent form C relay outputs. The 4 output circuits each have a dedicated relay. Each relay is rated for 3 amps at 24 volts DC resistive load. The relay module mounts directly to the back of the cabinet and is connected to the main board. All of the relay terminals are wired back to the field wiring junction box. A disable switch is available for disabling the relays when the system is being tested or serviced. Class A initiating device module CA2Z The Model CA2Z Class A Module is designed to be used with the Viking VFR-400 releasing control panel to convert from two (Class B) initiating device circuits to two (Class A) circuits. The module is to be mounted in the upper right hand corner of the panel. All the connections are wired back to the field wiring junction box. 24Vdc RS-485 P Remote Annunciator RA-4410-RC The RA-44410-RC remote annunciator is designed to operate with the Viking VFR-400 releasing control panel. There are 34 LED's to indicate a change in panel status. There is a buzzer on the annunciator that sounds for any trouble or supervisory condition. The release control panel supervises and communicates with the annunciator via separate connections for the RS-485 communication and the 24VDC power requirement of the RA-4410-RC. Separate cables should be used for power and communication. Shielded cable MUST be used for the RS-485 communication line. Class A Indicating Appliance Circuit Module The Model CAM Class A Module is designed to be used with the Viking VFR-400 releasing control panel to convert a single (Class B) indicating appliance circuit to a (Class A) circuit (one module is required for each indicating appliance circuit). After installing the CAM, the indicating circuit should be activated to ensure proper operation and connections. The module is provided with double-sided foam tape and should be mounted in the field wiring junction box so that the terminals are accessible. RA-4410-RC ZONE 1 OUTPUT 1 ZONE 1 OUTPUT 1 ZONE 2 OUTPUT 2 ZONE 2 OUTPUT 2 ZONE 3 OUTPUT 3 ZONE 4 OUTPUT 4 AC POWER SUPERVISORY ZONE 3 OUTPUT 3 POWER TROUBLE SYSTEM TROUBLE GROUND FAULT SUPERVISORY LAMP TEST TROUBLE COMMON ALM. SILENCE ALM. SILENCE STEADY : DISCHARGED FLASHING : PRE-DISCHARGE ZONE 4 OUTPUT 4 FM-076D-0-125C 12 of 16

SUREFIRE double interlock c/w N 2 Blast Nitrogen generating system Cabinet The FIREFLEX N2 Blast cabinet is made of sturdy 14 gauge steel. Refer to figure 4 for dimensions. All surfaces are rust proof coated, inside and outside, with fire red, oven baked polyester powder on phosphate base. Cabinet is provided with two doors, all provided with a neoprene gasket to avoid vibrations, giving the access to the pressure gauges reading and the manual emergency release. The cabinet assembly is pre-assembled, pre-wired, and factory tested under ISO-9001 conditions. Refer to figures 2 & 3 for installation and clearances details. Electrical junction boxes are integrated inside the cabinet for connection of the supervisory and alarm devices contacts. Knockouts are pre-punched for the installing contractor as indicated on figure 1. Figure 1 - knockouts details Top of Cabinet High voltage 2½" Low voltage 2½" Typ. 8½" 3¾" 3" FM-061H-0-68B-12 Figure 2 - Floor anchoring template F 5'' Ø3/4" E G FM-061H-1-49B-6 Size E F G 46" 15" 48" 25" 54" 21" 56" 27" Figure 3 - Required clearance 12'' MIN 12'' MIN 22'' MIN FM-061H-1-49B-7 Size A 46" 24" 54" 32" 13 of 16 FM-076D-0-125C

SUREFIRE double c/w N 2 Blast Nitrogen generating system Figure 4 - Cabinet dimensions D P TBA, TBB & TBC Q TBB TBA & TBC CONTROL PANEL (except for Remote Controlled Unit) CONTROL PANEL OPTIONAL SHUT-OFF VALVE ØB SPRINKLER RISER SCH.40 GROOVED OUTLET F SPRINKLER RISER SCH.40 GROOVED OUTLET S R N DRAIN - SCH.40 GROOVED OUTLET ØA ØC M WATER INLET SCH.40 GROOVED OUTLET G T FM-06LM-0-2A System Size A B C D E F G H J K L M N P Q R S T 1½" 2" 1½" 2" 46" 25" 77¼" 4" 8¾" 11½" 13¾" 3¾" 2¾" 2¾" 15" 11½" 37½" 44¾" 50" 2" 2" 2" 2" 46" 25" 77¼" 4" 8¾" 11½" 13¾" 3¾" 2¾" 2¾" 15" 11½" 37¾" 45" 50" 3" 4" 3" 2" 46" 25" 77¼" 4" 10" 11½" 13¾" 3¾" 2¾" 2¾" 15" 11½" 44" 47¾" 50" 4" 4" 4" 2" 54" 31" 81¼" 4" 10" 11½" 13¾" 3¾" 2½" 2½" 23¾" 11½" 48½" 53" 58" 6" 6" 6" 2" 54" 31" 81¼" 4" 11" 13" 13¾" 5¼" 2¾" 2¾" 25" 13" 59¼" 65¼ 58" Dimensions are nominal and may vary by ¼ FM-076D-0-125C 14 of 16

15 of 16 FM-076D-0-125C

1935, Lionel-Bertrand Blvd. Boisbriand QC Canada J7H 1N8 Tel.: 450-437-3473 Fax: 450-437-1930 Toll Free: 866-347-3353 Email: info@fireflex.com Web: www.fireflex.com FM-076D-0-125C 16 of 16