Model YCRL Remote Condenser Scroll Liquid Chiller Style A

Similar documents
MODEL YCRL REMOTE CONDENSER SCROLL LIQUID CHILLER STYLE A

MODEL YCRL REMOTE CONDENSER SCROLL LIQUID CHILLER STYLE A

YCAL-SB Millennium AIR COOLED LIQUID CHILLER R407C REFRIGERANT. COOLING CAPACITIES 141 kw to 360 kw

MODEL QTC3 AIR-COOLED SCROLL CHILLERS

Call us today! (800)

TON kw

MODEL YLUA AIR-COOLED SCROLL COMPRESSOR CONDENSING UNITS STYLE A

Call us today! (800)

MODEL YLAA AIR-COOLED SCROLL CHILLERS WITH BRAZED PLATE HEAT EXCHANGERS STYLE B

Call us today! (800)

MAC N-407 Air-Cooled Chiller

MACH N-407 Heat Pump Air-Cooled Chiller

B. Unit construction shall comply with ASHRAE 15 Safety Code, NEC, and ASME applicable codes (U.S.A. codes).

MODEL YLAA AIR-COOLED SCROLL CHILLERS WITH BRAZED PLATE HEAT EXCHANGERS STYLE B

YCWL0240SE-YCWL0395SE & YCWL / YCRL0200HE-YCWL / YCRL0610HE. Revision 2 Form EG2 (0709)

100 TON AIR-COOLED SCROLL PACKAGED. Call us today! (800) SPECIFICATIONS GENERAL DIMENSIONS ELECTRICAL DATA ADDITIONAL INFORMATION

FORM EG6 (513) Model YLAA Air-Cooled Scroll Chillers with Brazed Plate Heat Exchangers Style B TON kw 60 Hz R-410A

C. ASME Compliance: Fabricate and label water chiller heat exchangers to comply with ASME Boiler and Pressure Vessel Code: Section VIII, Division 1.

60Hz. R134a HXWC SERIES. 205 to 560 Tons. Products That Perform...By People Who Care WATER-COOLED SEMI-HERMETIC SCREW COMPRESSOR WATER CHILLERS

Exclusively published and distributed by Architectural Computer Services, Inc. (ARCOM) for the AIA

MODEL QTC3 AIR-COOLED SCROLL CHILLERS

Water-Cooled Dual Compressor Screw Chiller

SECTION ROTARY-SCREW WATER CHILLERS

60 TON AIR-COOLED CHILLER. Call us today! (800) PA-ACCTR-60 GENERAL DIMENSIONS ELECTRICAL DATA 60 TON AIR-COOLED CHILLER FEATURES

MODEL YSAA AIR-COOLED SCREW CHILLERS STYLE A

PACKAGED AIR COOLED Product Data Catalog

Date: August 21, Proposal Number: G Engineer: Payment Terms: Net 30 Days

TECHNICAL GUIDE. Description SPLIT-SYSTEM AIR-COOLED CONDENSING UNITS YD360, 480 & THRU 50 NOMINAL TONS YTG-B-0811

FORM EG2 (405) Air Cooled Screw Liquid Chillers STYLE A FPO 28971AR. R134a kw 50 Hz

MAC-120HE-03 Air-Cooled Chiller

Commercial High-Efficiency Condensing Units

MAC-060HE-01-L High Efficiency Air-Cooled Chiller Air-Cooled Chillers for Global Residential and Light Commercial Micro Climates Rev 1.

Air-Cooled Global Chiller

AVAILABLE MODELS, NOMINAL CAPACITIES TABLE 1 and SOUND PRESSURE LEVELS. Optional acoustic component enclosure and two speed fans

Model YCIV Air-Cooled Screw Liquid Chillers with Variable Speed Drive Style A

TECHNICAL GUIDE DESCRIPTION SPLIT-SYSTEM AIR-COOLED CONDENSING UNITS MODELS: HF-07 FEATURES B-0703

TECHNICAL GUIDE DESCRIPTION SPLIT-SYSTEM AIR-COOLED CONDENSING UNITS. HA300, HB360, HB480 & HB thru 50 NOMINAL TONS (50 Hz)

Submittal. Date: September 04, Customer P.O. Number: Customer Project Number:

SECTION AIR COOLED WATER CHILLER

MAC-036HE-02-L High Efficiency Air-Cooled Chiller Air-Cooled Chillers for Global Residential and Light Commercial Micro Climates Rev 1.

MAC-048HE-01-L High Efficiency Air-Cooled Chiller Air-Cooled Chillers for Global Residential and Light Commercial Micro Climates Rev 1.

Water-Cooled Modular Chillers. Product Data Catalog. Standard and Total Access Modules MS010X, MS015X, MS020X, MS030X, MS040X, MS050X, MS070X, MS085X

VariCool VAV Engineering Guide

Product Data. Features/Benefits. GEMINI 38AKS Commercial Air-Cooled Split Systems 50/60 Hz. 25 to 40 Nominal Tons (82.8 to 127.

RECORD SUBMITTAL COVER SHEET

Commercial High-Efficiency Condensing Units

.2 Section Waste Management and Disposal.

Air Cooled Screw Liquid Chillers (STYLE G)

SECTION CHILLERS

K*ES120 DESCRIPTION TECHNICAL GUIDE SPLIT-SYSTEM EVAPORATOR BLOWERS 10 NOMINAL TONS EER 8.5 ACCESSORIES FIELD INSTALLED TABLE 1: ARI RATINGS*

TECHNICAL GUIDE GENERAL SPECIFICATIONS COMMERCIAL SPLIT-SYSTEM COOLING UNITS FOUR PIPE SYSTEM OUTDOOR UNIT: INDOOR UNIT:

VertiCool Aurora Engineering Guide

Packaged Air-Cooled Water Chiller

JOB NAME: LOCATION: PURCHASER: ENGINEER: SUBMITTED TO: FOR: REFERENCE [ ] APPROVAL [ ] CONSTRUCTION [ ] SUBMITTED BY: DATE:

Water-to-Water Heat Pump Product Data Catalog R-134a Modules MR010AN, MR015AN, MR020AN, MR030AN, MR040AN, MR050AN, MR070AN, MR085AN

Product Data. Features/Benefits. 07DA, DB 07EA, EB, ED Condensing Units. 06D, 06E Compressors. 3 to 40 Nominal Tons

R4H4. Product Specifications

Model YVFA Air-Cooled Liquid Chillers With VSD Screw Compressor And Integrated Free Cooling Style A

Product Data. Features/Benefits. 19XB Positive Pressure Storage System

CHS. Product Specifications COMMERCIAL SPLIT SYSTEMS HEAT PUMP UNITS R 410A, 6 10 TONS BUILT TO LAST, EASY TO INSTALL AND SERVICE

Product Data. 50LJS/TJS Single- Package. Features / Benefits. Rooftop Units - 50 Hz 6 to 12 Nominal Tons

TECHNICAL, OPERATING & INSTALLATION MANUAL TC 15, 33, 52 AIR COOLED PACKAGED WATER CHILLERS

MODEL YVAA EQUIPMENT PRE-STARTUP AND STARTUP CHECKLIST CUSTOMER: LOCATION: ADDRESS: CUSTOMER ORDER NO: PHONE: JCI CONTRACT NO: JOB NAME:

EMBASSY SERIES SINGLE PACKAGE AIR CONDITIONERS (WATER-COOLED) C2ED060, 090, 120 & 180 5, 7-1/2, 10 & 15 Nominal Tons

Cutting Edge Compressor Technology

Technical Development Program. COMMERCIAL HVAC PACKAGED EQUIPMENT Split Systems PRESENTED BY: Ray Chow Sigler

YCIV Hz & Hz

FORM EG6 (712) Model YLAA Air-Cooled Scroll Chillers with Brazed Plate Heat Exchangers Style B TON kw 60 Hz R-410A

Multi-Institutional Academic Health Science & Research Center Evansville, IN

SLS 1202 to With or without total heat recovery. u Air Cooled Screw Chillers. 262 to 916 kw. Engineering Data Manual

N4H4. Product Specifications 14 SEER HEAT PUMP. ENVIRONMENTALLY SOUND R 410A REFRIGERANT 1½ THRU 5 TONS SPLIT SYSTEM 208 / 230 Volt, 1 phase, 60 Hz

Compact, Self-Contained unit that offer low installation cost plus dependable performance.

Liebert CSU3000 Chiller

NH4H4. Product Specifications 14 SEER HORIZONTAL DISCHARGE HEAT PUMP FOR USE WITH DUCTED INDOOR UNIT

PACKAGE AIR CONDITIONER

Water-Cooled Scroll Compressor Chillers

Product Data. Features/Benefits. 50TJ S Side Discharge Single-Package Rooftop Units 50/60 Hz 15 to 30 Nominal Tons

MODELS LIST. Nominal Capacity RT

Water-Cooled Scroll Compressor Chillers

NQ Series Portable Chillers

SECTION AIR COOLED WATER CHILLERS (LESS THAN 150 TONS)

Air-Cooled Condensing Units with Compact Screw Compressors

UP TO 17.5 SEER / 13.5 EER / 9.5 HSPF HEAT PUMP ENVIRONMENTALLY BALANCED R- 410A REFRIGERANT 2 THRU 5 TONS SPLIT SYSTEM

FLD = Furnished by Trane U.S. Inc. / Installed by Equipment Submittal Page 3 of 13

Air-Cooled Modular Split Systems. Product Data Catalog

INSTALLATION INSTRUCTIONS

Wicomico County Purchasing 125 N. Division St. Room B-3 Salisbury, MD Ph Fax Addendum # 1

Product Data. GEMINI SELECT 09DPS ,09DPM Air-Cooled Condensers with PURON Refrigerant (R-410A) 50/60 Hz

R4H4. Product Specifications

GUIDE SPECIFICATIONS AQUARIUS ii

Water-Cooled Scroll Compressor Chillers

Product Chillers A P P L I C AT I O N S

CLW QUAD SERIES 60 TO 140 TON

1025, BOUL. MARCEL-LAURIN INSTRUCTION MANUAL FOR WATER COOLED ENVIROCHILL CHILLER. Prepared par Claude Gadoury, P. Eng MTL TECHNOLOGIES INC.

30GN FLOTRONIC II AIR-COOLED CHILLERS

N4H4. Product Specifications

FALCON Rooftop Units ACPSE 50/60Hz Cooling Capacity : 36 to 1388 MBH (11 to 407 kw) Heating Capacity : 40 to 1298 MBH (12 to 380 kw)

CAS. Product Specifications. COMMERCIAL SPLIT SYSTEMS CONDENSING UNITS R 410A, 6 to 12.5 TONS BUILT TO LAST, EASY TO INSTALL AND SERVICE

Installation Instructions

Guide Specifications PART 1 GENERAL 1.01 SUMMARY

Transcription:

Model YCRL Remote Condenser Scroll Liquid Chiller Style A 50 THROUGH 150 TONS 175kW THROUGH 530 kw 60Hz Products are produced at a facility whose qualitymanagement systems are ISO9001 certified.

Table of Contents... 1 Introduction... 3 Specification... 4 Microprocessor Controls... 5 Accessories and Options... 7 Refrigerant Flow Diagram... 9 Design Parameters English & SI... 10 Pressure Drop Curves - English & SI...11 Selection Data... 12 Ratings- English - High Efficiency... 16 Physical Data Standard & High Efficiency English... 18 Isolator Selection Data... 19 Isolator Information... 20 Isolator Information - Continued... 22 Sound Data... 23 Unit Dimensions - English - Four Compressor... 24 Unit Dimensions - English - Six Compressor... 26 Electrical Data - Single Point... 28 Electrical Data - Dual Point... 30 Electrical Notes... 32 Ground Wire Sizing... 33 Typical Control Panel Wiring... 34 Customer Wiring Information... 38 Application Data... 40 Guide Specifications... 41 NOMENCLATURE 0096 2 JOHNSON CONTROLS

Introduction Model YCRL Remote Condenser Scroll Liquid Chillers YORK YCRL Remote Condenser Liquid Chillers provide chilled water for all air conditioning applications that use central station air handling or terminal units. They are self-contained and are designed for indoor (new or retrofit) installation. Each unit includes hermetic scroll compressors, a liquid evaporator, and a user-friendly, diagnostic Microcomputer Control Center all mounted on a rugged steel base. Remote condensers (model VDC) are available seperately from Johnson Controls. The units are produced at an ISO 9001 registered facility. The YCRL chillers are rated in accordance with ARI Standard 550/590. JOHNSON CONTROLS 3

Specification GENERAL The chiller will be completely assembled with all interconnecting refrigerant piping and internal wiring, ready for field connection to a remote condenser. The unit will be pressure-tested, evacuated, and charged with a nitrogen holding charge, and York V (POE) synthetic oil. The unit can be covered with an optional overspray coat of Caribbean Blue enamel. Units are designed in accordance with NFPA 70 (National Electric Code), ASHRAE/ANSI 15 Safety Code for Mechanical Refrigeration. All units are produced at an ISO 9001 registered facility. All YCRL condensing units are rated in accordance with ARI Standard 550/590 at ARI conditions. COMPRESSORS The chiller has suction-gas cooled, hermetic, scroll compressors. The YCRL s compressors incorporate a compliant scroll design in both the axial and radial direction. All rotating parts are statically and dynamically balanced. A large internal volume and oil reservoir provides greater liquid tolerance. Compressor crankcase heaters are also included for extra protection against liquid migration. All compressors are mounted on isolator pads to reduce transmission of vibration to the rest of the unit. REFRIGERANT CIRCUIT Two independent refrigerant circuits will be furnished on each unit. All piping will be copper with brazed joints. The liquid line will include: a shutoff valve with charging port; sight-glass with moisture indicator; thermal expansion valve; solenoid valve; and high-absorption removable-core filter drier. The entire suction line and the liquid line between the expansion valve and the cooler will be insulated with flexible, closed-cell, foam insulation. POWER AND CONTROL PANELS All controls and motor starting equipment necessary for unit operation shall be factory wired and function tested. The panel enclosures shall be designed to NEMA 1 (IP 32) and manufactured from powder-painted galvanized steel. The Power and Control Panel shall be divided into a power section for each electrical system, a common input section and a control section. Each power panel shall contain: Compressor starting contactors, control circuit serving compressor capacity control, compressor contactor coils and compressor motor overloads. The compressor motor overloads contain current transformers which sense each phase, as an input to the microprocessor, to protect the compressor motors from damage due to: low input current, high input current, unbalanced current, single phasing, phase reversal, and compressor locked rotor. The common input section shall contain: The control supply transformer providing 115V, customer relay board and control circuit switch disconnect/emergency stop device. 4 JOHNSON CONTROLS

Microprocessor Controls MICROPROCESSOR CONTROLS The control section shall contain: On/Off rocker switch, microcomputer keypad and display, microprocessor board, I/O expansion board, relay boards, and 24V fused power supply board. The control display shall include: Liquid Crystal Display with Light Emitting Diode backlighting for outdoor viewing: Two display lines Twenty characters per line Color coded 12-button non-tactile keypad with sections for: Display/Print of typical information: Chilled liquid temperatures System pressures (each circuit) Operating hours and starts (each compressor) Print calls up to the liquid crystal display: Operating data for the systems History of fault shutdown data for up to the last six fault shutdown conditions An RS-232 port, in conjunction with this pressto-print button, is provided to permit the capabil ity of hard copy print-outs via a separate printer (by others). Entry section to: ENTER setpoints or modify system values Setpoints updating can be performed to: Chilled liquid temperature setpoint and range Remote reset temperature range Set daily schedule/holiday for start/stop Manual override for servicing Number of compressors Low liquid temperature cutout Low suction pressure cutout High discharge pressure cutout Anti-recycle timer (compressor start cycle time) Anti-coincident timer (delay compressor starts) Unit section to: Set time Set unit options The microprocessor control center is capable of displaying the following: Return and leaving chilled liquid temperature Low leaving liquid temperature cutout setting English or Metric data Suction pressure cutout setting Each system suction pressure Discharge pressure Liquid Temperature Reset via a Building FIG. 1 CONTROL PANEL DETAILS JOHNSON CONTROLS 5

Automation System via a 4-20 milliamp input or a 0-10 VDC input Anti-recycle timer status for each system Anti-coincident system start timer condition Compressor run status No cooling load condition Day, date and time Daily start/stop times Holiday status Automatic or manual system lead/lag control Lead system definition Compressor starts & operating hours (each com pressor) Status of hot gas valves (if supplied) Run permissive status Number of compressors running Liquid solenoid valve status Load & unload timer status The standard controls shall include: automatic pumpdown, run signal contacts, demand load limit form external building automation system input, remote reset liquid temperature reset input, unit alarm contacts, chilled liquid pump control, automatic reset after power failure, automatic system optimization to match operating conditions. The operating program software shall be stored in nonvolatile memory (EPROM) to eliminate chiller failure due to AC power failure. Programmed setpoints are retained in lithium battery-backed regulated time clock (RTC) memory for 5 years minimum. COMMUNICATIONS Native communication capability for BACnet (MS/TP) and Modbus Optional communciation available for N2 and LON via elink option FIG. 2 POWER PANEL DETAILS 6 JOHNSON CONTROLS

Accessories and Options POWER OPTIONS: SINGLE POINT SUPPLY TERMINAL BLOCK - The standard power wiring connection on all models is a single point power connection to a factory provided terminal block. Components included are the enclosure, terminal-block and interconnecting wiring to the compressors. Separate external protection must be supplied, by others, in the incoming power wiring. (Factory-Mounted) SINGLE POINT CIRCUIT BREAKER - An optional unit mounted circuit breaker with external, lockable handle (in compliance with N.E.C. Article 440-14), can be supplied to isolate the power voltage for servicing. (Factory- Mounted) MULTIPLE POINT CIRCUIT BREAKER Optional multiple point supply with independent system circuit breakers and locking external handles (in compliance with Article 440-14 of N.E.C.) can be factory supplied. (Factory- Mounted). CONTROL TRANSFORMER Converts unit power voltage to 115-1-60 (0.5 or 1.0 KVA capacity). Factory mounting includes primary and secondary wiring between the transformer and the control panel. (Factory-Mounted) CONTROLS OPTIONS: LANGUAGE LCD AND KEYPAD - Standard display language and keypad is in English. Spanish, French, German, and Italian are available as an option. (Factory- Mounted) HEAT EXCHANGER OPTIONS: FLOW SWITCH An optional flow switch can be factory supplied for the evaporator. Vapor-proof SPDT, NEMA 3R switch, 150 psig (10.3 bar) DWP, 20 F to 250 F (-29 C to 121 C) with 1 NPT (IPS) connection for upright mounting in horizontal pipe. The flow switch or its equivalent must be furnished with each unit. (Field mounted) DIFFERENTIAL PRESSURE SWITCH - An alternative option to the paddle-type flow switch. 3-45 psig (0.2-3 bar) range with ¼ NPTE pressure connections. (Field Mounted) PRESSURE VESSEL CODES - Evaporator is supplied (Standard) in conformance with the A.S.M.E. pres sure codes. FLANGES (ANSI/AWWA C-606 COUPLINGS TYPE) Consists of (2) flange adapters for grooved end pipe on evaporator. Standard 150 psig (10.3 bar). (Field Kit, matching pipe flange by contractor.) DOUBLE THICK INSULATION Doubled thickness (totalling 1-1/2 or 38mm) insulation provided on the evaporator. (Factory-Mounted) CHILLER OPTIONS: FINAL PAINT OVERSPRAY - Overspray painting of unit after assembly. (Factory-Mounted) SERVICE ISOLATION VALVE - Service suction isolation valve added to unit per system in addition to the standard discharge service valve. (Factory-Mounted) HOT GAS BY-PASS Permits continuous, stable operation at capacities below the minimum step of compressor unloading to as low as 5% capacity (depending on both the unit and operating conditions) by introducing an artificial load on the evaporator. Hot gas by-pass is installed on only refrigerant system #2 on two-circuited units. (Factory-Mounted) COMPRESSOR ACOUSTIC SOUND BLANKET Each compressor is individually enclosed by an acoustic sound blanket. The sound blankets are made with one layer of acoustical absorbent textile fiber of 5/8 (15mm) thickness; one layer of anti-vibrating heavy material thickness of 1/8 (3mm). Both are closed by two sheets of welded PVC, reinforced for temperature and UV resistance. (Factory- Mounted) VIBRATION ISOLATION: Rubber Isolators Recommended for normal in stallations. Provides very good performance in most applications for the least cost. (Field-mounted) 1 Spring Isolators Level adjustable, spring and cage type isolators for mounting under the unit base rails. 1 nominal deflection may vary slightly by ap plication. (Field -Mounted) 2 Seismic Isolators Restrained Spring-Flex Mount ings incorporate a rugged welded steel housing with vertical and horizontal limit stops. Housings designed to withstand a minimum 1.0g accelerated force in all directions to 2. Level adjustable, deflection may vary slightly by application. (Field-Mounted) JOHNSON CONTROLS 7

(OPT) 8 JOHNSON CONTROLS

Refrigerant Flow Diagram Low-pressure liquid refrigerant enters the evaporator tubes and is evaporated and superheated by the heat energy absorbed from the chilled liquid passing through the evaporator shell. Low-pressure vapor enters the compressor where pressure and superheat are increased. High-pressure vapor is passed through a remote condenser where heat is rejected to the air flow passing through the coil. The fully condensed and subcooled liquid leaves the condenser and enters the expansion valve, where pressure reduction and further cooling take place. The low pressure liquid refrigerant then returns to the evaporator. JOHNSON CONTROLS 9

Design Parameters English & SI, 125 125 125 125 125 125 125 - NOTES: 1. For leaving brine temperature below 40 F (4.4 C), contact the nearest Johnson Controls Office for application requirements. 2. For leaving water temperature higher than 50 F (10 C), contact the nearest Johnson Controls Office for application guidelines. 52 52 52 52 52 52 10 JOHNSON CONTROLS

Pressure Drop Curves - English & SI YCRL Evaporator Pressure Drop (English Units) 100.0 A B D Pressure Drop (ft. H 2 O) 10.0 C 1.0 10 100 1000 Water Flow Rate (GPM) YCRL Model Number 0064HE 0074HE, 0084HE, 0118HE, 0096HE 0126HE, 0156HE Evap A B C D YCRL Evaporator Pressure Drop (SI Units) 1000.0 Pressure Drop (kpa) 100.0 10.0 C A B D 1.0 1.0 10.0 100.0 Water Flow Rate (l/s) JOHNSON CONTROLS 11

Selection Data GUIDE TO SELECTION Complete water chilling capacity ratings for YORK YCRL condensing units are shown on the following pages to cover the majority of job requirements. For any application beyond the scope of this Engineering Guide, consult your nearest Johnson Controls office. SELECTION RULES 1. RATINGS - All YCRL ratings are in accordance with ARI Standard 550/590, at the ARI standard condi tions. Ratings not at standard ARI conditions are rated in accordance with ARI rating procedures. These ratings may be interpolated but should not be extrapolated. 2. COOLING WATER QUANTITY - Ratings are based on 10ºF chilled water range with the evaporator at sea level. Use the chilled water correction factors (below) for other ranges except as limited by water pressure drop, minimum or maximum water flows for the evaporator. 3. FOULING FACTORS Ratings are based on 0.0001 evaporator fouling factor. For other fouling factors, consult the table below or contact your Johnson Controls representative. EVAPORATOR CORRECTION FACTORS FF = Temp 0.0001 0.0003 Split Tons Compr kw Tons Compr kw 6 0.976 0.998 0.969 0.997 8 0.990 0.999 0.980 0.998 10 1.000 1.000 0.991 0.999 12 1.009 1.001 0.999 1.000 14 1.017 1.002 1.007 1.001 4. ETHYLENE GLYCOL CORRECTION FACTORS The following factors are to be applied to the standard ratings for units cooling ethylene glycol. ETHYLENE GLYCOL COMPR % WEIGHT TONS GPM KW 10 1 1 1 1.1 26 20 1 1 1 1.2 18 30 1 1 1.1 1.3 7 40 0.9 1 1.1 1.4-8 50 0.9 1 1.1 1.6-29 5. PROPYLENE GLYCOL CORRECTION FACTORS The following factors are to be applied to the standard ratings for units cooling propylene glycol. PROPELENE GLYCOL COMPR % WEIGHT TONS GPM KW METHOD OF SELECTION PRESS DROP PRESS DROP FREEZE PT FREEZE PT 10 1 1 1 1.1 26 20 1 1 1 1.2 19 30 0.9 1 1 1.3 9 40 0.9 1 1 1.4-6 50 0.9 1 1 1.6-28 If the duty requires a 10ºF (6 C) range on the evaporator, see Ratings. For water ranges other than 10ºF (6 C), use the following procedure. Line sizes can be determined by reviewing York DX Piping Guide 050.40-ES2. Note: Temperature split factors @ 85ºF Entering Condenser Water Temp (ECWT) 12 JOHNSON CONTROLS

1. Determine capacity required from the following formula GPM x Chilled Water Range (ºF) Capacity (Tons) = 24 2. After applying any fouling factor corrections, the actual condenser heat rejection may be determined as follows: Correcting for the 12ºF chilled water range: Tons KW The unit is suitable. = 101.7 x 1.009 = 102.6 TR = 110.0 x 1.001 = 110.1 kw 3. Determine the average full load kw and EER at 100 Tons Heat Rejection (MBH) = Heat Rejection (Btuh) 1000 = (Tons x 12) = (kw x 3.415) 3. Size condenser using manufacturer s recommendations. SAMPLE SELECTION Water Cooled Chiller (YCRL) GIVEN Chill 200 GPM of water from 56ºF to 44ºF and 0.0001 evaporator fouling factor with 125 F saturated discharge temperature. 4. Determine the cond. Heat rejection as follows: Heat Rejection (MBH) = (Tons x 12) + (kw x 3.415) = (102.6 x 12) + (110.1 x 3.415) = 1231.2 + 376.0 = 1607.2 5. From curves on page 11, locate the pressure drops with 200 GPM through the evaporator of the Model YCRL118SE: Evaporator Pressure Drop at 200 GPM = 8 ft FIND The required unit size capacity, kw, EER, and water pressure drop, and the condenser MBH heat rejection. SOLUTION: 1. Chilled water range = 56ºF - 44ºF = 12ºF and correction factors are 1.009 for Tons and 1.001 for kw for the evaporator. Capacity (Tons) = = GPM x Chilled Water Range 24 200 x 12 = 100TR 24 2. From the rating, a model YCRL01180SE has a capacity range required. For the evaporator leaving water temperature of 44ºF and a saturated discharge temperature of 125 F, the unit capacity rating table indicates: Tons = 101.7 KW = 110.0 EER = 11.1 JOHNSON CONTROLS 13

Selection Data continued REFRIGERANT PIPING General When the unit has been located in its final position, the unit piping may be connected. Normal installation precautions should be observed in order to receive maximum operating efficiencies. System piping should conform to the York DX Piping Guide form 050.40-ES2 or ASHRAE refrigeration handbook guidelines. All piping design and installation is the responsibility of the user. JOHNSON CONTROLS ASSUMES NO WARRANTY RESPONSIBILITY FOR SYSTEM OPERATION OR FAIL- URES DUE TO IMPROPER PIPING OR PIPING DESIGN. All filter driers, sight glasses, expansion valves and liquid line solenoid valves are factory installed on each refrigerant circuit. Interconnecting refrigerant piping and refrigerant charge are supplied and installed by others. Table 2 lists refrigerant line connections sizes per unit model number. REFRIGERANT LINE SIZING Refrigerant piping systems must be designed to provide practical line sizes without excessive pressure drops, prevent compressor oil from being trapped in the refrigerant piping, and ensure proper flow of liquid refrigerant to the thermal expansion valve. Be sure to review form 050.40- ES2. Considerations should be given to: 1) Discharge line pressure drop due to refrigerant flow. 2) Discharge line refrigerant velocity for oil return. 3) Liquid line pressure drop due to refrigerant flow. 4) Liquid line pressure drop (or gain) due to vertical rise of the liquid line. To ensure a solid column of liquid refrigerant to the expansion valve, the total liquid line pressure drop should never exceed 40 psig (2.8 barg). Refrigerant vapor in the liquid line will measurably reduce valve capacity and poor system performance can be expected. To allow adequate oil return to the compressor, discharge risers should be sized for a minimum of 1000 FPM (5.08 m/s) while the system is operating at minimum capacity to ensure oil return up the suction riser. Chiller Below Condenser On a system where the chiller is located below the condenser, the discharge line must be sized for both pressure drop and oil return. In some cases a double discharge riser must be installed to ensure reliable oil return at reduced loads. Condenser Below Chiller When the condenser is located below the chiller, the liquid line must be designed for both friction loss and static head loss due the vertical rise. The value of static head loss of 5 PSI/ft. (3.4 kpa/30 cm) must be added to the friction loss pressure drop in addition to all pressure drops due to driers, valves, etc. OIL TRAPS All horizontal discharge lines should be pitched at least 1/4 per foot (2 cm/m) in the direction of the refrigerant flow to aid in the return of oil to the chiller. All discharge lines with a vertical rise exceeding 3 feet (.91 meters) should have a P trap at the bottom and top of the riser. Discharge lines with a vertical rise exceeding 25 feet (7.6 meters) should be trapped every 15 feet (4.6 meters). REFRIGERANT CHARGE The chiller is charged and shipped with a dry nitrogen holding charge. The operating charge for the chiller, remote condenser and refrigerant piping must be weighed in after all refrigerant piping is installed, leak checked, and evacuated. Final adjustment of refrigerant charge should be verified by subcooling values (refer to IOM section on Pre-Startup for checking subcooling). REFRIGERANT PIPING REFERENCE For more details, refer to ASHRAE Refrigeration Handbook, Chapter 2. 14 JOHNSON CONTROLS

TABLE 1 YCRL CHILLER CHARGES MODEL 60Hz TOTAL HFC-410A CHARGE, lb. PER SYSTEM, lb 0064HE 34 17 0074HE 40 20 0084HE 82 41 0096HE 106 53 0118HE 90 45 0126HE 126 63 0156HE 126 63 0177SE 122 63/59 0198SE 126 63 Note: Charge for remote condenser and interconnecting piping must be calculated separately. TABLE 2 YCRL LINE CONNECTION SIZES UNIT SIZE (60Hz) Liquid Line System 1, in. Liquid Line System 2, in. Discharge Line System 1, in. Discharge Line System 2, in. 0064HE 7/ 8 7/ 8 1 3/ 8 1 3/ 8 0074HE 1 1/ 8 7/ 8 1 5/ 8 1 3/ 8 0084HE 1 1/ 8 1 1/ 8 1 5/ 8 1 5/ 8 0096HE 1 1/ 8 1 1/ 8 1 3/ 8 1 3/ 8 0118HE 1 1/ 8 1 1/ 8 1 5/ 8 1 5/ 8 0126HE 1 1/ 8 1 1/ 8 2 1/ 8 2 1/ 8 0156HE 1 1/ 8 1 1/ 8 2 1/ 8 2 1/ 8 0177SE 1 1/ 8 1 1/ 8 2 1/ 8 2 1/ 8 0198SE 1 1/ 8 1 1/ 8 2 1/ 8 2 1/ 8 JOHNSON CONTROLS 15

Ratings- English - High Efficiency MODEL: YCRL0064HE IPLV= 17.7 SATURATED DISCHARGE TEMP ( F) LCWT 100.0 105.0 110.0 115.0 120.0 125.0 ( F) TONS KW EER TONS KW EER TONS KW EER TONS KW EER TONS KW EER TONS KW EER 40.0 60.5 46.3 15.7 58.8 48.9 14.4 57.0 51.8 13.2 55.3 54.9 12.1 53.5 58.3 11.0 51.6 62.0 10.0 42.0 62.7 46.4 16.2 61.0 49.0 14.9 59.3 51.9 13.7 57.4 55.0 12.5 55.6 58.4 11.4 53.6 62.0 10.4 44.0 65.2 46.6 16.8 63.3 49.1 15.5 61.5 52.0 14.2 59.7 55.0 13.0 57.7 58.4 11.9 55.8 62.1 10.8 45.0 66.4 46.7 17.0 64.6 49.2 15.7 62.7 52.0 14.5 60.8 55.1 13.2 58.8 58.4 12.1 56.8 62.1 11.0 46.0 67.6 46.9 17.3 65.8 49.3 16.0 63.9 52.1 14.7 62.0 55.1 13.5 60.0 58.5 12.3 57.9 62.1 11.2 48.0 70.1 47.1 17.9 68.3 49.5 16.5 66.3 52.2 15.2 64.3 55.2 14.0 62.3 58.6 12.8 60.2 62.2 11.6 50.0 72.6 47.4 18.4 70.7 49.8 17.1 68.8 52.4 15.7 66.7 55.4 14.5 64.6 58.7 13.2 62.5 62.2 12.0 MODEL: YCRL0074HE IPLV= 17.7 SATURATED DISCHARGE TEMP ( F) LCWT 100.0 105.0 110.0 115.0 120.0 125.0 ( F) TONS KW EER TONS KW EER TONS KW EER TONS KW EER TONS KW EER TONS KW EER 40.0 70.5 54.0 15.7 68.4 56.8 14.4 66.3 60.0 13.3 64.1 63.4 12.1 61.9 67.0 11.1 59.7 71.1 10.1 42.0 73.3 54.2 16.2 71.1 57.1 15.0 68.9 60.1 13.7 66.7 63.5 12.6 64.4 67.2 11.5 62.1 71.2 10.5 44.0 76.1 54.5 16.8 73.9 57.3 15.5 71.6 60.4 14.2 69.3 63.7 13.1 67.0 67.4 11.9 64.6 71.3 10.9 45.0 77.6 54.6 17.1 75.3 57.4 15.8 73.0 60.5 14.5 70.7 63.8 13.3 68.3 67.5 12.2 65.9 71.4 11.1 46.0 79.1 54.7 17.4 76.8 57.5 16.0 74.4 60.6 14.7 72.1 63.9 13.5 69.7 67.6 12.4 67.2 71.5 11.3 48.0 82.1 55.0 17.9 79.8 57.8 16.6 77.3 60.8 15.3 74.9 64.1 14.0 72.4 67.8 12.8 69.8 71.7 11.7 50.0 85.2 55.2 18.5 82.8 58.0 17.1 80.3 61.0 15.8 77.8 64.4 14.5 75.2 68.0 13.3 72.6 71.9 12.1 MODEL: YCRL0084HE IPLV= 19.6 SATURATED DISCHARGE TEMP ( F) LCWT 100.0 105.0 110.0 115.0 120.0 125.0 ( F) TONS KW EER TONS KW EER TONS KW EER TONS KW EER TONS KW EER TONS KW EER 40.0 79.9 59.5 16.1 77.4 62.5 14.9 74.9 65.8 13.7 72.4 69.3 12.5 69.9 73.1 11.5 67.4 77.3 10.5 42.0 83.1 59.8 16.7 80.5 62.8 15.4 78.0 66.0 14.2 75.4 69.5 13.0 72.8 73.4 11.9 70.2 77.6 10.9 44.0 86.4 60.0 17.3 83.7 63.1 15.9 81.1 66.3 14.7 78.4 69.8 13.5 75.7 73.7 12.3 73.0 77.8 11.3 45.0 88.1 60.2 17.6 85.4 63.2 16.2 82.7 66.5 14.9 80.0 70.0 13.7 77.2 73.8 12.6 74.5 78.0 11.5 46.0 89.8 60.3 17.9 87.1 63.3 16.5 84.3 66.6 15.2 81.6 70.1 14.0 78.8 73.9 12.8 76.0 78.1 11.7 48.0 93.3 60.5 18.5 90.5 63.6 17.1 87.6 66.9 15.7 84.8 70.4 14.4 81.9 74.2 13.2 79.0 78.4 12.1 50.0 96.9 60.7 19.1 94.0 63.8 17.7 91.0 67.2 16.3 88.1 70.7 14.9 85.1 74.5 13.7 82.1 78.7 12.5 MODEL: YCRL0096HE IPLV= 18.3 SATURATED DISCHARGE TEMP ( F) LCWT 100.0 105.0 110.0 115.0 120.0 125.0 ( F) TONS KW EER TONS KW EER TONS KW EER TONS KW EER TONS KW EER TONS KW EER 40.0 92.2 69.5 15.9 89.6 73.4 14.7 87.0 77.7 13.4 84.3 82.4 12.3 81.6 87.5 11.2 78.7 93.0 10.2 42.0 95.7 69.8 16.5 93.1 73.6 15.2 90.4 77.8 13.9 87.6 82.5 12.7 84.8 87.6 11.6 81.9 93.1 10.6 44.0 99.3 70.1 17.0 96.6 73.8 15.7 93.8 78.0 14.4 91.0 82.6 13.2 88.1 87.7 12.1 85.1 93.1 11.0 45.0 101.2 70.3 17.3 98.4 74.0 16.0 95.6 78.1 14.7 92.7 82.7 13.5 89.7 87.7 12.3 86.7 93.1 11.2 46.0 103.0 70.4 17.5 100.2 74.1 16.2 97.4 78.2 14.9 94.4 82.8 13.7 91.4 87.8 12.5 88.4 93.2 11.4 48.0 106.8 70.9 18.1 104.0 74.4 16.8 101.0 78.5 15.4 98.0 83.0 14.2 94.9 87.9 13.0 91.7 93.3 11.8 NOTES: 1. Tons = Unit Cooling Capacity Output 2. KW = Compressor Input Power 3. MBH = Condenser Heat Rejection 4. EER = Chiller Energy Efficiency Ratio 5. LCWT = Leaving Chilled Water Temperature 16 JOHNSON CONTROLS

MODEL: YCRL0118HE IPLV= 19.5 SATURATED DISCHARGE TEMP ( F) LCWT 100.0 105.0 110.0 115.0 120.0 125.0 ( F) TONS KW EER TONS KW EER TONS KW EER TONS KW EER TONS KW EER TONS KW EER 40.0 109.9 83.6 15.8 107.0 88.2 14.6 104.0 93.1 13.4 100.9 98.3 12.3 97.7 104.0 11.3 94.4 110.0 10.3 42.0 114.0 84.0 16.3 111.0 88.5 15.0 107.9 93.4 13.9 104.7 98.6 12.7 101.4 104.2 11.7 98.0 110.3 10.7 44.0 118.1 84.3 16.8 115.0 88.8 15.5 111.9 93.7 14.3 108.6 98.9 13.2 105.2 104.5 12.1 101.7 110.5 11.0 45.0 120.2 84.5 17.1 117.1 89.0 15.8 113.9 93.8 14.6 110.6 99.0 13.4 107.1 104.7 12.3 103.6 110.7 11.2 46.0 122.4 84.7 17.3 119.2 89.2 16.0 115.9 94.0 14.8 112.6 99.2 13.6 109.1 104.8 12.5 105.5 110.8 11.4 48.0 126.7 85.1 17.9 123.5 89.5 16.6 120.1 94.3 15.3 116.6 99.5 14.1 113.1 105.1 12.9 109.4 111.1 11.8 50.0 131.1 85.5 18.4 127.8 89.9 17.1 124.4 94.7 15.8 120.8 99.9 14.5 117.1 105.4 13.3 113.3 111.4 12.2 MODEL: YCRL0126HE IPLV= 20.6 SATURATED DISCHARGE TEMP ( F) LCWT 100.0 105.0 110.0 115.0 120.0 125.0 ( F) TONS KW EER TONS KW EER TONS KW EER TONS KW EER TONS KW EER TONS KW EER 40.0 120.6 91.2 15.9 117.0 95.8 14.7 113.3 100.8 13.5 109.6 106.1 12.4 105.8 112.0 11.3 102.0 118.5 10.3 42.0 125.3 91.6 16.4 121.6 96.2 15.2 117.9 101.2 14.0 114.0 106.6 12.8 110.1 112.4 11.8 106.2 118.8 10.7 44.0 130.1 91.9 17.0 126.3 96.6 15.7 122.4 101.6 14.5 118.6 107.0 13.3 114.6 112.9 12.2 110.5 119.2 11.1 45.0 132.5 92.1 17.3 128.7 96.8 15.9 124.8 101.8 14.7 120.8 107.2 13.5 116.8 113.1 12.4 112.7 119.5 11.3 46.0 135.0 92.3 17.6 131.1 97.0 16.2 127.1 102.0 15.0 123.1 107.5 13.8 119.1 113.3 12.6 114.9 119.7 11.5 48.0 140.1 92.6 18.1 136.0 97.4 16.8 131.9 102.5 15.5 127.8 107.9 14.2 123.7 113.8 13.0 119.4 120.1 11.9 50.0 145.2 92.9 18.8 141.1 97.8 17.3 136.9 102.9 16.0 132.6 108.3 14.7 128.3 114.2 13.5 124.0 120.6 12.3 MODEL: YCRL0156HE IPLV= 19.0 SATURATED DISCHARGE TEMP ( F) LCWT 100.0 105.0 110.0 115.0 120.0 125.0 ( F) TONS KW EER TONS KW EER TONS KW EER TONS KW EER TONS KW EER TONS KW EER 40.0 139.5 106.8 15.7 135.9 112.6 14.5 132.2 118.9 13.4 128.4 125.6 12.3 124.5 132.9 11.2 120.5 140.6 10.3 42.0 144.6 107.2 16.2 140.9 113.0 15.0 137.1 119.2 13.8 133.2 125.9 12.7 129.2 133.2 11.6 125.0 140.9 10.6 44.0 149.9 107.6 16.7 146.0 113.4 15.5 142.1 119.6 14.3 138.1 126.3 13.1 134.0 133.5 12.0 129.7 141.2 11.0 45.0 152.5 107.9 17.0 148.6 113.6 15.7 144.7 119.8 14.5 140.6 126.5 13.3 136.4 133.7 12.2 132.1 141.4 11.2 46.0 155.2 108.1 17.2 151.3 113.8 16.0 147.3 120.0 14.7 143.1 126.6 13.6 138.9 133.8 12.5 134.5 141.5 11.4 48.0 160.7 108.6 17.8 156.7 114.3 16.5 152.5 120.4 15.2 148.3 127.0 14.0 143.9 134.2 12.9 139.4 141.9 11.8 50.0 166.4 109.1 18.3 162.2 114.7 17.0 157.9 120.8 15.7 153.6 127.5 14.5 149.1 134.6 13.3 144.4 142.2 12.2 NOTES: 1. Tons = Unit Cooling Capacity Output 2. KW = Compressor Input Power 3. MBH = Condenser Heat Rejection 4. EER = Chiller Energy Efficiency Ratio 5. LCWT = Leaving Chilled Water Temperature JOHNSON CONTROLS 17

Physical Data Standard & High Efficiency English High Efficiency (HE) YCRL MODEL 0064HE 0074HE 0084HE 0096HE 0118HE 0126HE 0156HE General Unit Data Nominal Unit Capacity (Tons) 55.8 64.6 73 85.1 101.7 110.5 129.7 Number of Independent Refrigerant Circuits 2 2 2 2 2 2 2 Oil Charge, Ckt. 1/Ckt. 2, (gal.) 2.2/2.2 2.5/2.2 2.5/2.5 3.3/3.3 3.3/3.1 3.7/3.7 4.7/4.7 Shipping Weight (lbs.) 2743 3133 3311 3664 3629 4345 4903 Operating Weight (lbs.) 2950 3419 3597 4106 3915 4788 5346 Compressors, Scroll Quantity per Chiller 4 4 4 6 4 6 6 Nominal Size Ckt. 1/ Ckt. 2 15-15 / 15-15 20-20 / 15-15 20-20 / 20-20 15-15-15/ 20-20-20 / 25-25-25 / 32-32 / 25-25 15-15-15 20-20-20 25-25-25 Evaporator Water Volume (gals.) 37.3 59.8 59.8 57.6 59.8 77 77 Maximum Water Side Pressure (psig) Maximum Refrigerant Side Pressure (psig) 150 150 150 150 150 150 150 450 450 450 450 450 450 450 Dia. X Length (inches X feet) Water Nozzle Connection Size, (inches) 13 X 8 16 X 8 16 X 8 15 X 10 16 X 8 17 10 17 10 6 8 8 8 8 8 8 18 JOHNSON CONTROLS

Isolator Selection Data A B C CONTROL PANEL D 60 HZ (ASME) Eff Unit Shipping Weight Total Operating Weight in Pounds Model/Weights/isolators Weight Weight on Front on Each Isolators 1" Deflection Isolator Neoprene Isolator Back (Control Isolator Panel Side) Seismic Isolator Y2RSI-2D 0064 HE 2883 2973 776 699 CP-1D-1200 Gray RD-3 Charcoal Red/Black 0074 HE 3261 3531 913 797 CP-1D-1200 Gray RD-4 Brick Red Red/Black 0084 HE 3439 3709 977 821 CP-1D-1200 Gray RD-4 Brick Red Red/Black 0096 HE 3753 4043 1112 896 CP-1D-1360 White RD-4 Brick Red Pink 0118 HE 3705 3975 1092 866 CP-1D-1360 White RD-4 Brick Red Pink 0126 HE 4587 5037 1386 1008 CP-1D-1785N Gray/Red RD-4 Brick Red Pink/Gray 0156 HE 4989 5439 1609 1064 C2P-1D-2400 Gray RD-4 Brick Red Pink/Gray JOHNSON CONTROLS 19

Isolator Information ONE INCH DEFLECTION SPRING ISOLATOR CROSS-REFERENCE CPX-X- Mount Type Dimension Data (Inches) W D L B C T H CP1 3 5/8 7 3/4 6 1/2 4 3/4 ½ 5 5/8 CP2 3 5/8 10 1/2 9 1/4 7 3/4 9/16 6 MODEL NUMBER RATED CAPACITY (LBS.) DEFLECTION RATED (IN) COLOR CODE CP1-1D-85 85 1.360 LT. PURPLE CP1-1D-120 120 1.200 DK. YELLOW CP1-1D-175 175 1.170 DK. BLUE CP1-1D-250 250 1.400 YELLOW CP1-1D-340 340 1.130 RED CP1-1D-510 510 1.020 BLACK CP1-1D-675 675 1.320 DK. PURPLE CP1-1D-900 900 1.020 DK. GREEN CP1-1D-1200 1200 0.900 GRAY CP1-1D-1360 1360 0.770 WHITE CP1-1D-1785N 1785 0.880 GRAY/RED MODEL NUMBER RATED CAPACITY (LBS.) DEFLECTION RATED (IN) COLOR CODE CP2-1D-1020 1020 1.020 BLACK CP2-1D-1350 1350 1.320 DK. PURPLE CP2-1D-1800 1800 1.020 DK. GREEN CP2-1D-2400 2400 0.900 GRAY CP2-1D-2720 2720 0.770 WHITE CP2-1D-3570N 3570 0.880 GRAY / RED 20 JOHNSON CONTROLS

NEOPRENE ISOLATOR CROSS-REFERENCE RD-Style Isolators ELASTOMER Mount Type Dimension Data (inches) L W HF AL AD BT CD DW RD1-WR 3.13 1.75 1.25 2.38 0.34 0.19 5/16-18 UNC X 3/4 1.25 RD2-WR 3.88 2.38 1.75 3.00 0.34 0.22 3/8-16 UNC X 1 1.75 RD3-WR 5.50 3.38 2.88 4.13 0.56 0.25 1/2-13 UNC X 1 2.50 RD4-WR 6.25 4.63 2.75 5.00 0.56 0.38 1/2-13 UNC X 1 3.00 MODEL NUMBER RATED RATED RATED RATED CAPACITY DURO (± 5) MODEL NUMBER CAPACITY DEFLECTION DEFLECTION [IN] [LBS] [LBS] [IN] DURO (± 5) RD2-Light Blue-WR 35 0.4 30 RD3-Brown-WR 250 0.5 40 RD2-Brown-WR 45 0.4 40 RD3-Brick Red-WR 525 0.5 50 RD2-Brick Red-WR 70 0.4 50 RD3-Lime-WR 750 0.5 60 RD 2-Lime-WR 120 0.4 60 RD3-Charcoal-WR 1100 0.5 70 MODEL NUMBER RATED RATED CAPACITY DURO (± 5) RATED DEFLECTION [IN] RATED [LBS] MODEL NUMBER CAPACITY DEFLECTION [IN] [LBS] DURO (± 5) RD2-Light Blue-WR 135 0.5 30 RD2-Brown-WR 170 0.5 40 RD4-Brown-WR 1500 0.5 40 RD2-Brick Red-WR 240 0.5 50 RD4-Brick Red-WR 2250 0.5 50 RD 2-Lime-WR 380 0.5 60 RD4-Lime-WR 3000 0.5 60 RD2 Charcoal-WR 550 0.5 70 RD4-Charcoal-WR 4000 0.5 70 JOHNSON CONTROLS 21

Isolator Information - Continued TWO INCH DEFLECTION, SEISMIC SPRING ISOLATOR CROSS-REFERENCE Y2RS 1-1/8 5/8 2-3/4 2-3/4 3/8 GAP 3/4 TYP. (4) 8 P 4 3/4 7/8 4 4 STOP & 8-3/8 OPER. HEIGHT 8 MODEL Y2RSI-2D SEISMICALLY RESTRAINED VIBRATION ISOLATOR FOR 2" DEFLECTION RATED DEFLECTION SPRING RATE SEISMIC MOUNT SIZE RATED LOAD (LBS) SOLID LOAD (LBS) COLOR CODE (IN) (LBS/IN) ALLOWABLE G RATING HORIZONTAL Y2RSI-2D-150 150 2.4 62 234 WHITE 34.7 Y2RSI-2D-320 320 2.3 140 490 YELLOW 16.3 Y2RSI-2D-460 460 2.3 200 688 GREEN 11.3 Y2RSI-2D-710 710 2.2 330 1072 DK BROWN 7.3 Y2RSI-2D-870 870 1.9 460 1312 RED 6 Y2RSI-2D-1200N 1200 1.9 638 1818 RED/BLACK 4.3 Y2RSI-2D-1450 1450 1.8 900 2450 TAN 3.6 Y2RSI-2D-1690 1690 1.7 1140 2892 PINK 3.1 Y2RSI-2D-2000N 2000 1.7 1318 3342 PINK/BLACK 2.6 Y2RSI-2D-2640N 2640 1.5 1854 4283 PINK/GRAY 2 Y2RSI-2D-2870N 3080 1.5 2004 4629 PINK/GRAY/ORANGE 1.7 Y2RSI-2D-3280N 3740 1.8 2134 4930 PINK/GRAY/DK BROWN 1.4 22 JOHNSON CONTROLS

Sound Data YCRL High Efficiency BASE UNITS (ARI 575 Sound Pressure Levels db re: 20 micropascals) 63 125 250 500 1000 2000 4000 8000 YCRL0064HE 59 52 54 68 68 69 62 53 74 YCRL0074HE 60 56 63 70 70 75 68 57 78 YCRL0084HE 60 58 66 71 72 77 70 59 80 YCRL0096HE 61 54 55 69 70 71 64 55 75 YCRL0118HE 69 68 74 77 78 76 70 57 82 YCRL0126HE 62 59 68 73 73 79 72 61 82 YCRL0156HE 72 65 71 78 79 76 72 58 82 dba YCRL High Efficiency COMPRESSOR ACOUSTIC BLANKETS (ARI 575 Sound Pressure Levels db re: 20 micropascals) 63 125 250 500 1000 2000 4000 8000 YCRL0064HE 59 52 53 66 63 63 56 48 69 YCRL0074HE 60 56 62 68 65 69 62 52 72 YCRL0084HE 60 58 65 69 67 71 64 54 74 YCRL0096HE 61 54 54 67 65 65 58 50 70 YCRL0118HE 69 68 73 75 73 70 64 52 77 YCRL0126HE 62 59 67 71 68 73 66 56 76 YCRL0156HE 72 65 70 76 74 70 66 53 78 dba JOHNSON CONTROLS 23

Unit Dimensions - English - Four Compressor YCWL (4 Comp) 0064HE 0074HE 0084HE 0118HE W 32.5 33.7 33.7 33.7 H 56.6 63.6 63.6 63.3 L 121.5 120.5 123.2 120.5 A 13.8 13.8 13.8 13.8 B 27.5 27.5 27.5 27.5 D 11.8 16.0 16.0 16.0 E 8.6 8.6 8.6 8.6 F 24.5 29.0 29.0 29.0 G 29.0 29.0 29.0 29.0 J 17.7 17.7 17.7 17.7 K 12.3 12.8 12.8 12.8 M 12.3 12.3 12.3 12.3 N 12.3 12.3 12.3 12.3 R 85.0 83.0 83.0 83.0 S 3.5 4.5 4.5 4.5 T 116.7 115.7 118.3 115.7 U 24.7 23.7 26.3 22.1 X 21.0 22.2 22.3 22.2 AA 21.0 21.0 21.0 21.0 BB 50.0 50.0 50.0 50.0 CC 13.5 13.5 13.5 14.0 DD 30.7 33.0 33.0 33.0 EE 81.1 82.1 78.7 79.1 FF 37.3 34.9 34.4 34.8 GG-1 39.5 39.5 39.5 41.0 GG-2 39.5 39.5 39.5 41.0 HH 18.3 14.7 14.7 14.9 H* - for 200/230 volt units, which require a larger electrical enclosure 24 JOHNSON CONTROLS

RELIEF VALVE INLET OUTLET JOHNSON CONTROLS 25

Unit Dimensions - English - Six Compressor YCWL (6 Comp) 0096HE 0126HE 0156HE W 38.0 38.0 38.0 H 59.1 64.6 64.5 L 140.6 142.6 140.8 A 13.8 13.8 13.8 B 27.5 27.5 27.5 D 16.0 16.0 16.0 E 8.6 8.6 8.6 F 28.0 28.0 28.0 G 29.0 29.0 29.0 J 17.7 17.7 17.7 K 17.8 17.8 15.3 M 12.3 12.3 12.3 N 12.3 12.3 12.3 R 102.0 102.0 102.0 S 7.0 7.0 7.0 T 135.8 137.6 135.8 U 19.8 21.6 19.8 X 23.3 23.3 23.2 AA 32.8 32.8 32.8 BB 50.0 50.0 50.0 CC 15.0 15.3 17.8 DD 33.3 33.8 33.8 EE 94.2 95.4 95.4 FF 32.0 33.2 33.2 GG-1 57.9 57.7 53.7 GG-2 57.9 57.7 53.7 HH 14.7 14.9 14.9 H* - for 200/230 volt units, which require a larger electrical enclosure 26 JOHNSON CONTROLS

INLET OUTLET RELIEF VALVE EE JOHNSON CONTROLS 27

Electrical Data - Single Point HIGH EFFICIENCY W/O EXTERNAL COMPRESSOR OVERLOADS MODEL YCRL & MIN CB & MAX CB 0064HE 0074HE 0084HE 0096HE 0118HE 0126HE 0156HE VOLT HZ MINIMUM CIRCUIT AMPS MCA MIN N/F DISC SW MDSW MIN DUAL ELEM FUSE MAX DUAL ELEM FUSE CIRCUIT BREAKER LUG SIZE (OPT) LUGS PER PHASE TERMINAL BLOCK LUG SIZE (STD) QTY/ LUG INFO QTY/ LUG INFO 208 60 237 400 300 300 1 250-500 KCM 1 # 4-500 KCM 230 60 237 400 300 300 1 250-500 KCM 1 # 4-500 KCM 380 60 153 200 175 175 1 # 4-300 KCM 1 # 10-300 KCM 460 60 114 150 125 125 1 # 2-4/0 AWG 1 # 10-300 KCM 575 60 101 150 110 110 1 # 2-4/0 AWG 1 # 10-300 KCM 208 60 278 400 300 350 1 250-500 KCM 1 # 4-500 KCM 230 60 278 400 300 350 1 250-500 KCM 1 # 4-500 KCM 380 60 158 200 175 175 1 # 4-300 KCM 1 # 10-300 KCM 460 60 122 150 150 150 1 # 2-4/0 AWG 1 # 10-300 KCM 575 60 103 150 110 125 1 # 2-4/0 AWG 1 # 10-300 KCM 208 60 314 400 350 350 1 250-500 KCM 1 # 4-500 KCM 230 60 314 400 350 350 1 250-500 KCM 1 # 4-500 KCM 380 60 162 200 175 200 1 # 4-300 KCM 1 # 10-300 KCM 460 60 129 150 150 150 1 # 2-4/0 AWG 1 # 10-300 KCM 575 60 105 150 125 125 1 # 2-4/0 AWG 1 # 10-300 KCM 208 60 349 400 400 400 1 250-500 KCM 2 #10-300 KCM 230 60 349 400 400 400 1 250-500 KCM 2 #10-300 KCM 380 60 225 250 250 250 1 # 6-350 KCM 1 # 4-500 KCM 460 60 168 200 175 175 1 # 4-300 KCM 1 # 4-500 KCM 575 60 148 200 175 175 1 # 6-350 KCM 1 # 4-500 KCM 208 60 425 600 500 500 2 250-500 KCM 2 #10-300 KCM 230 60 425 600 500 500 2 250-500 KCM 2 #10-300 KCM 380 60 265 400 300 300 1 250-500 KCM 1 # 4-500 KCM 460 60 208 250 225 250 1 # 6-350 KCM 1 # 4-500 KCM 575 60 175 200 200 200 1 # 6-350 KCM 1 # 4-500 KCM 208 60 462 600 500 500 2 250-500 KCM 2 # 10-300 KCM 230 60 462 600 500 500 2 250-500 KCM 2 # 10-300 KCM 380 60 239 400 250 250 1 # 6-350 KCM 1 # 4-500 KCM 460 60 190 250 200 200 1 # 6-350 KCM 1 # 4-500 KCM 575 60 154 200 175 175 1 # 6-350 KCM 1 # 4-500 KCM 208 60 557 800 600 600 2 250-500 KCM 2 # 4-500 KCM 230 60 557 800 600 600 2 250-500 KCM 2 # 4-500 KCM 380 60 341 400 400 400 1 250-500 KCM 2 # 10-300 KCM 460 60 268 400 300 300 1 250-500 KCM 1 # 4-500 KCM 575 60 201 250 225 225 1 250-500 KCM 1 # 4-500 KCM 28 JOHNSON CONTROLS

HIGH EFFICIENCY W/O EXTERNAL COMPRESSOR OVERLOADS MODEL YCRL 0064HE 0074HE 0084HE 0096HE 0118HE 0126HE 0156HE SYSTEM # 1 SYSTEM # 2 COMPR 1 COMPR 2 COMPR 3 COMPR 1 COMPR 2 COMPR 3 RLA LRA RLA LRA RLA LRA RLA LRA RLA LRA RLA LRA 55.8 425.0 55.8 425.0 55.8 425.0 55.8 425.0 55.8 425.0 55.8 425.0 55.8 425.0 55.8 425.0 36.0 239.0 36.0 239.0 36.0 239.0 36.0 239.0 26.9 187.0 26.9 187.0 26.9 187.0 26.9 187.0 23.7 148.0 23.7 148.0 23.7 148.0 23.7 148.0 73.9 505.0 73.9 505.0 55.8 425.0 55.8 425.0 73.9 505.0 73.9 505.0 55.8 425.0 55.8 425.0 38.2 290.0 38.2 290.0 36.0 239.0 36.0 239.0 30.4 225.0 30.4 225.0 26.9 187.0 26.9 187.0 24.6 180.0 24.6 180.0 23.7 148.0 23.7 148.0 73.9 505.0 73.9 505.0 73.9 505.0 73.9 505.0 73.9 505.0 73.9 505.0 73.9 505.0 73.9 505.0 38.2 290.0 38.2 290.0 38.2 290.0 38.2 290.0 30.4 225.0 30.4 225.0 30.4 225.0 30.4 225.0 24.6 180.0 24.6 180.0 24.6 180.0 24.6 180.0 55.8 425.0 55.8 425.0 55.8 425.0 55.8 425.0 55.8 425.0 55.8 425.0 55.8 425.0 55.8 425.0 55.8 425.0 55.8 425.0 55.8 425.0 55.8 425.0 36.0 239.0 36.0 239.0 36.0 239.0 36.0 239.0 36.0 239.0 36.0 239.0 26.9 187.0 26.9 187.0 26.9 187.0 26.9 187.0 26.9 187.0 26.9 187.0 23.7 148.0 23.7 148.0 23.7 148.0 23.7 148.0 23.7 148.0 23.7 148.0 109.6 599.0 109.6 599.0 89.1 500.0 89.1 500.0 109.6 599.0 109.6 599.0 89.1 500.0 89.1 500.0 69.2 358.0 69.2 358.0 54.5 305.0 54.5 305.0 54.5 310.0 54.5 310.0 42.9 250.0 42.9 250.0 49.4 239.0 49.4 239.0 32.1 198.0 32.1 198.0 73.9 505.0 73.9 505.0 73.9 505.0 73.9 505.0 73.9 505.0 73.9 505.0 73.9 505.0 73.9 505.0 73.9 505.0 73.9 505.0 73.9 505.0 73.9 505.0 38.2 290.0 38.2 290.0 38.2 290.0 38.2 290.0 38.2 290.0 38.2 290.0 30.4 225.0 30.4 225.0 30.4 225.0 30.4 225.0 30.4 225.0 30.4 225.0 24.6 180.0 24.6 180.0 24.6 180.0 24.6 180.0 24.6 180.0 24.6 180.0 89.1 500.0 89.1 500.0 89.1 500.0 89.1 500.0 89.1 500.0 89.1 500.0 89.1 500.0 89.1 500.0 89.1 500.0 89.1 500.0 89.1 500.0 89.1 500.0 54.5 305.0 54.5 305.0 54.5 305.0 54.5 305.0 54.5 305.0 54.5 305.0 42.9 250.0 42.9 250.0 42.9 250.0 42.9 250.0 42.9 250.0 42.9 250.0 32.1 198.0 32.1 198.0 32.1 198.0 32.1 198.0 32.1 198.0 32.1 198.0 JOHNSON CONTROLS 29

Electrical Data - Dual Point HIGH EFFICIENCY W/O EXTERNAL COMPRESSOR OVERLOADS SYSTEM 1 WIRING SYSTEM 2 WIRING CHILLER MODEL VOLT HZ MINIMUM CIRCUIT AMPS MIN N/F DISC SW MIN DUAL ELEM FUSE & MIN CB MAX DUAL ELEM FUSE & MAX CB MINIMUM CIRCUIT AMPS MIN N/F DISC SW MIN DUAL ELEM FUSE & MIN CB MAX DUAL ELEM FUSE & MAX CB YCRL0064 YCRL0074 YCRL0084 YCRL0118 YCRL0096 YCRL0126 YCRL0156 208 60 126 150 150 175 126 150 150 175 230 60 126 150 150 175 126 150 150 175 380 60 81 100 90 110 81 100 90 110 460 60 61 100 70 80 61 100 70 80 575 60 53 60 60 70 53 60 60 70 208 60 166 200 200 225 126 150 150 175 230 60 166 200 200 225 126 150 150 175 380 60 86 100 100 110 81 100 90 110 460 60 68 100 80 90 61 100 70 80 575 60 55 60 70 70 53 60 60 70 208 60 166 200 200 225 166 200 200 225 230 60 166 200 200 225 166 200 200 225 380 60 86 100 100 110 86 100 100 110 460 60 68 100 80 90 68 100 80 90 575 60 55 60 70 70 55 60 70 70 208 60 247 400 300 350 200 250 225 250 230 60 247 400 300 350 200 250 225 250 380 60 156 200 175 200 123 150 150 175 460 60 123 150 150 175 97 100 110 125 575 60 111 150 125 150 72 100 90 100 208 60 181 200 200 225 181 200 200 225 230 60 181 200 200 225 181 200 200 225 380 60 117 150 150 150 117 150 150 150 460 60 87 100 100 110 87 100 100 110 575 60 77 100 90 100 77 100 90 100 208 60 240 400 300 300 240 400 300 300 230 60 240 400 300 300 240 400 300 300 380 60 124 150 150 150 124 150 150 150 460 60 99 150 110 125 99 150 110 125 575 60 80 100 90 100 80 100 90 100 208 60 290 400 350 350 290 400 350 350 230 60 290 400 350 350 290 400 350 350 380 60 177 200 200 225 177 200 200 225 460 60 139 150 175 175 139 150 175 175 575 60 104 150 125 125 104 150 125 125 30 JOHNSON CONTROLS

HIGH EFFICIENCY W/O EXTERNAL COMPRESSOR OVERLOADS CHILLER MODEL SYSTEM 1 CIRCUIT BREAKER LUG SIZE QTY/f LUG INFO SYSTEM 2 CIRCUIT SYSTEM # 1 SYSTEM # 2 BREAKER LUG SIZE COMPR COMPR 2 COMPR 3 COMPR 1 COMPR 2 COMPR 3 1 RLA LRA RLA LRA RLA LRA QTY/f LUG INFO RLA LRA RLA LRA RLA LRA YCRL0064 YCRL0074 YCRL0084 YCRL0118 YCRL0096 YCRL0126 YCRL0156 1 #6-350KCMIL 55.8 425 55.8 425 1 (1) #6-350KCMIL 55.8 425 55.8 425 1 #6-350KCMIL 55.8 425 55.8 425 1 (1) #6-350KCMIL 55.8 425 55.8 425 1 #14-1/0AWG 36.0 239 36.0 239 1 (1) #14-1/0AWG 36.0 239 36.0 239 1 #14-1/0AWG 26.9 187 26.9 187 1 (1) #14-1/0AWG 26.9 187 26.9 187 1 #14-1/0AWG 23.7 148 23.7 148 1 (1) #14-1/0AWG 23.7 148 23.7 148 1 #6-350KCMIL 73.9 505 73.9 505 1 (1) #6-350KCMIL 55.8 425 55.8 425 1 #6-350KCMIL 73.9 505 73.9 505 1 (1) #6-350KCMIL 55.8 425 55.8 425 1 #2-4/0AWG 38.2 290 38.2 290 1 (1) #14-1/0AWG 36.0 239 36.0 239 1 #14-1/0AWG 30.4 225 30.4 225 1 (1) #14-1/0AWG 26.9 187 26.9 187 1 #14-1/0AWG 24.6 180 24.6 180 1 (1) #14-1/0AWG 23.7 148 23.7 148 1 #6-350KCMIL 73.9 505 73.9 505 1 (1) #6-350KCMIL 73.9 505 73.9 505 1 #6-350KCMIL 73.9 505 73.9 505 1 (1) #6-350KCMIL 73.9 505 73.9 505 1 #2-4/0AWG 38.2 290 38.2 290 1 (1) #2-4/0AWG 38.2 290 38.2 290 1 #14-1/0AWG 30.4 225 30.4 225 1 (1) #14-1/0AWG 30.4 225 30.4 225 1 #14-1/0AWG 24.6 180 24.6 180 1 (1) #14-1/0AWG 24.6 180 24.6 180 1 250-300KCMIL 109.6 599 109.6 599 1 (1) #6-350KCMIL 89.1 500 89.1 500 1 250-300KCMIL 109.6 599 109.6 599 1 (1) #6-350KCMIL 89.1 500 89.1 500 1 #6-350KCMIL 69.2 358 69.2 358 1 (1) #6-350KCMIL 54.5 305 54.5 305 1 #6-350KCMIL 54.5 310 54.5 310 1 (1) #2-4/0AWG 42.9 250 42.9 250 1 #2-4/0AWG 49.4 239 49.4 239 1 (1) #14-1/0AWG 32.1 198 32.1 198 1 #6-350KCMIL 55.8 425 55.8 425 55.8 425 1 (1) #6-350KCMIL 55.8 425 55.8 425 55.8 425 1 #6-350KCMIL 55.8 425 55.8 425 55.8 425 1 (1) #6-350KCMIL 55.8 425 55.8 425 55.8 425 1 #2-4/0AWG 36.0 239 36.0 239 36.0 239 1 (1) #2-4/0AWG 36.0 239 36.0 239 36.0 239 1 #14-1/0AWG 26.9 187 26.9 187 26.9 187 1 (1) #14-1/0AWG 26.9 187 26.9 187 26.9 187 1 #14-1/0AWG 23.7 148 23.7 148 23.7 148 1 (1) #14-1/0AWG 23.7 148 23.7 148 23.7 148 1 250-300KCMIL 73.9 505 73.9 505 73.9 505 1 (1) 250-300KCMIL 73.9 505 73.9 505 73.9 505 1 250-300KCMIL 73.9 505 73.9 505 73.9 505 1 (1) 250-300KCMIL 73.9 505 73.9 505 73.9 505 1 #2-4/0AWG 38.2 290 38.2 290 38.2 290 1 (1) #2-4/0AWG 38.2 290 38.2 290 38.2 290 1 #2-4/0AWG 30.4 225 30.4 225 30.4 225 1 (1) #2-4/0AWG 30.4 225 30.4 225 30.4 225 1 #14-1/0AWG 24.6 180 24.6 180 24.6 180 1 (1) #14-1/0AWG 24.6 180 24.6 180 24.6 180 1 250-300KCMIL 89.1 500 89.1 500 89.1 500 1 (1) 250-300KCMIL 89.1 500 89.1 500 89.1 500 1 250-300KCMIL 89.1 500 89.1 500 89.1 500 1 (1) 250-300KCMIL 89.1 500 89.1 500 89.1 500 1 #6-350KCMIL 54.5 305 54.5 305 54.5 305 1 (1) #6-350KCMIL 54.5 305 54.5 305 54.5 305 1 #6-350KCMIL 42.9 250 42.9 250 42.9 250 1 (1) #6-350KCMIL 42.9 250 42.9 250 42.9 250 1 #2-4/0AWG 32.1 198 32.1 198 32.1 198 1 (1) #2-4/0AWG 32.1 198 32.1 198 32.1 198 JOHNSON CONTROLS 31

Electrical Notes 1. Minimum Circuit Ampacity (MCA) is based on 125% of the rated load amps for the largest motor plus 100% of the rated load amps for all other loads included in the circuit, per N.E.C. Article 43024. If the optional Factory Mounted Control Transformer is provided, add the following MCA values to the electrical tables for the system providing power to the transformer: 17, add 2.5 amps; 28, add 2.3 amps; 40, add 1.5 amps, 46, add 1.3 amps; 58, add 1 amps. 2. The minimum recommended disconnect switch is based on 115% of the rated load amps for all loads included in the circuit, per N.E.C. Article 440. 3. Minimum fuse size is based upon 150% of the rated load amps for the largest motor plus 100% of the rated load amps for all other loads included in the circuit to avoid nuisance trips at startup due to lock rotor amps. It is not recommended in applications where brown outs, frequent starting and stopping of the unit, and/or operation at ambient temperatures in excess of 95ºF (35ºC) is anticipated. 4. Maximum fuse size is based upon 225% of the rated load amps for the largest motor plus 100% of the rated load amps for all other loads included in the circuit, per N.E.C. Article 440-22. 5. Circuit breakers must be UL listed and CSA certified and maximum size is based on 225% of the rated load amps for the largest motor plus 100% of the rated load amps for all other loads included in the circuit. Otherwise, an HACR type circuit breakers must be used. Maximum HACR circuit breaker rating is based on 225% of the rated load amps for the largest motor plus 100% of the rated load amps for all other loads included in the circuit. 6. The INCOMING WIRE RANGE is the minimum and maximum wire size that can be accommodated by the unit wiring lugs. The (2) preceding the wire range indicates the number of termination points available per phase of the wire range specified. Actual wire size and number of wires per phase must be determined based on the National Electrical Code, using copper connectors only. Field wiring must also comply with local codes. 7. An equipment ground lug(s) is provided for the incoming power. Ground line sizing shall be in accordance with the current NEC Table 250-122. 8. Field Wiring by others which complies to the National Electrical Code & Local Codes. 9. Voltage Utilization Range LEGEND Rated Voltage Utilization Range 200/60/3 180-220 230/60/3 208-254 380/60/3 342-402 460/60/3 414-508 575/60/3 520-635 ACR C.B. D.E. DISC SW FACT MOUNT CB FLA HZ MAX MCA MIN MIN NF RLA S.P. WIRE UNIT MTD SERV SW LRA ECWT ACROSS THE LINE START CIRCUIT BREAKER DUAL ELEMENT FUSE DISCONNECT SWITCH FACTORY MOUNTED CIRCUIT BREAKER FULL LOAD AMPS HERTZ MAXIMUM MINIMUM CIRCUIT AMPACITY MINIMUM MINIMUM NON FUSED RATED LOAD AMPS SINGLE POINT WIRING UNIT MOUNTED SERVICE (NON-FUSED DISCONNECT SWITCH) LOCKED ROTOR AMPS ENTERING CONDENSER WATER TEMPERATURE 32 JOHNSON CONTROLS

Ground Wire Sizing GROUND LUG SIZING CIRCUIT BREAKER OPTION RATING INCOMING WIRE GROUND WIRE 60A # 14-1/0 AWG # 14-6 AWG 70A # 14-1/0 AWG # 14-6 AWG 80A # 14-1/0 AWG # 14-6 AWG 90A # 14-1/0 AWG # 14-6 AWG 100A # 14-1/0 AWG # 8-2 AWG 125A # 14-1/0 AWG # 8-2 AWG 125A # 2-4/0 AWG # 8-2 AWG 150A # 2-4/0 AWG # 8-2 AWG 175A # 4-300 KCM # 6-1/0 AWG 200A # 4-300 KCM # 6-1/0 AWG 225A # 4-300 KCM # 6-1/0 AWG 250A # 6-350 KCM # 4-3/0 AWG 400A # 250-500 KCM # 2-4/0 AWG 400A (2) # 3/0-250 KCM (2) # 6-1/0 AWG 600A (2) # 250-500 KCM (2) # 2-4/0 AWG TERMINAL BLOCK OPTION RATING INCOMING WIRE GROUND WIRE 130A # 12-1 AWG # 8-2 AWG 165A # 10-3/0 AWG # 6-1/0 AWG 240A # 10-300 KCM # 4-3/0 AWG 320A # 4-500 KCM # 2-4/0 AWG 480A (2) # 10-300 KCM (2) # 4-3/0 AWG Instructions: 1) Start in correct power option table (breaker, terminal block) 2) Match engineering guide value for Amperage 3) Match engineering guide value for wire range 4) Note corresponding ground wire range JOHNSON CONTROLS 33

Typical Control Panel Wiring 4 Compressor 34 JOHNSON CONTROLS

4 Compressor JOHNSON CONTROLS 35

Typical Control Panel Wiring 6 Compressor 36 JOHNSON CONTROLS

6 Compressor JOHNSON CONTROLS 37

Customer Wiring Information 1 2 FIGURE 1: SINGLE POINT POWER SUPPLY CONNECTION STANDARD UNIT 38 JOHNSON CONTROLS

FIG. 2 DUAL POINT POWER SUPPLY CONNECTION OPTIONAL JOHNSON CONTROLS 39

Application Data UNIT LOCATION Chillers are designed for indoor installation. Units should be located away from noise-critical areas. Service clearance must be allowed and include space for remov ing condenser tubes. A doorway or window can sometimes provide space for tube removal. Units should be installed indoors where they are not exposed to rain or water splash. Chillers should be located near a drain. The use of chillers in corrosive, dusty or ex plosive atmospheres should be avoided unless the unit is properly protected. A unit located in a clean room will run best, require least maintenance, and last longest. Heat or ventilation may be required to maintain the ambient between 40 F and 115 F (4.4 C and 46.1 C). UNIT ISOLATION The chiller foundation must be rigid to reduce vibration transmission to a minimum. All upper story installations should use vibration isolators under the unit base. To maintain isolator efficiency, no mechanical ties should be made to the building. Properly selected flexible connectors and piping isolators are recommended. All the above recommendations will help to reduce vibration transmission and result in a quieter operation. FIELD CONNECTED WATER PIPING Piping must comply in all respects with applicable local plumbing codes and ordinances. In no case should the unit support the weight of connecting piping. Since elbows, tees, and valves increase pressure drop, all piping should be kept as simple as possible. Hand stop valves should be installed where required to facilitate servicing. Piping to the inlet and outlet connections of the evaporator and condenser may include high-pressure rubber hose or piping loops to ensure against water pump transmission of vibration. Facilities should be provided for measuring temperature and pressure in the evaporator and condenser field water pip ing. Drain connections should be provided at all low points to permit complete drainage of the evaporator(s) and system piping. This is especially im portant if the unit is located in an unheated room where freezing could prevail. Water lines subjected to ambient temperatures below freezing may require heater cables or antifreeze (by others). Water loops should contain provisions for venting. A strainer, preferably 40 mesh, should be installed in the evaporator inlet line, located where it will protect the circulating pump and the heat exchanger tube bundles. It should be determined that the maximum water pressure at the evaporator does not exceed the maximum design working pressure. The water circulating pump should be located on the inlet side of the heat exchanger. If, however, space does not permit this, the pumps may be located in the outlet water piping. The net positive suction head must be considered when applying pumps. FIELD WIRING All field wiring must comply with the National Electric Code and all applicable local codes. YORK liquid chiller units are factory wired for optimum reliability. Therefore the unit controls must not be modified without ex pressed written consent by Johnson Controls. The use of a simple switch or timer from a remote point is permitted; but it must be connected to the unit panel at points expressly indicated for that purpose. REFRIGERANT RELIEF PIPING Each chiller is equipped with pressure relief valves. The purpose of the relief valves is to quickly relieve excess pressure of the refrigerant charge as a safety precaution in the event of an emergency such as a fire. Sized to the requirements of applicable local codes, a vent line must be run from the relief valve to the outside of the building. Vent piping must be arranged to avoid imposing a strain on the relief valves and should include flexible connections. The low side relief valve is located on the suction line. It has a pressure setting of 400 psig (27.6 bar) and a capacity of 28.6 lbs. air/min ( 166.3 l/s). The 0064, 0074, and 0096 units have additional relief valves on the discharge line(s) in lieu of compressor internal relief. The valve has a pressure setting of 650 psig (44.5 barg), a capacity of 44.6 lbs air/min (277 l/s) and a 1/2 flare connection. 40 JOHNSON CONTROLS